1 Section PREMISE CABLING SYSTEMS PART ONE GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work of this section. B. Division-16 Basic Materials and Methods section apply to work specified in this section. 1.2 DESCRIPTION OF WORK A. This work includes the installation of: 1. Computer structured building cabling, Category Computer modular outlets: Where shown on the plans provide combination types and configurations as detailed. 3. Computer patch panels. B. The Owner shall purchase and install the telephone switch, computer system and associated equipment. Owner s telephone vendor shall perform the cross-connect. C. Note: All work specified under this section shall be omitted under the Deductive Alternate listed on Bid Form. All raceways and boxes shall remain. 1.3 SUBMITTALS A. General: 1. Material and documentation shall be submitted for review and approval as follows: a. Index with individual tabbed sections in three ring binder b. Installation and operation instructions c. Manufacturer s descriptive literature d. Applicable riser diagrams e. Floor plans as described below f. Submit four copies 2. Incomplete or partial submittals will not be reviewed nor approved until all requested items are provided to the Engineer. Completeness of the submittal is the sole responsibility of the Contractor. 3. Sufficient information, clearly marked, shall be presented in order for the reviewer to determine compliance with contract documents. Unmarked submittals shall be returned un-reviewed. 4. A complete submittal shall contain: a. Product Descriptions, b. Floor Plans and Comm. Closet layouts, c. O & M Manual (excluding project test reports) VADEN, RAGSDALE & WOODWARD, INC Page 1 of 6
2 B. Product Descriptions: 1. Provide manufacturer s standard catalog sheets for the voice/data system devices proposed. This shall include (but not limited to) cabling (copper and fiber optic), modular jacks, device plates, patch panels, equipment racks, surge protection devices, sample labels, and sample test report. 2. Each item proposed shall be clearly marked with complete part numbers. C. Floor Plans: 1. Provide large scale drawings (24 x 36 or 32 x 42 ). Drawings shall be produced with a CAD program. Photocopied floor plans from the contract document set are unacceptable. 8½ x 11 drawings are also unacceptable. CAD file background drawings are available from the Architect/Engineer; refer to Section Basic Electrical Requirements. 2. Floor plans shall show as a minimum: 1/8 scale walls, rooms with names and numbers, voice/data outlet locations, symbol legend, wire and cable types and counts. 3. Provide large scale (e.g. ¼ = 1-0 ) of communication closet layouts showing all equipment locations and dimensioned from walls. 4. Provide a site plan showing exterior building connections where applicable. D. O & M Manuals: 1. Manuals shall be bound into book form and marked O & M VOICE/DATA System Manual. 2. Manuals shall contain system operating information along with component technical sheets. 3. Manuals shall contain system component interconnection wiring diagrams marked as applicable for this project. General wiring diagrams are unacceptable. 4. Manuals shall provide clear and concise information on such items (but not limited to): a. Product data sheets b. Basic Troubleshooting c. Cabling test reports d. Contact Information for Warranty, Repair, Maintenance work 1.4 QUALITY ASSURANCE A. Manufacturers: Firms regularly engaged in manufacture of premise cabling products of types and ratings required, whose products have been in satisfactory use in similar service for not less than 5 years. B. Installer: Qualified with at least 5 years of successful installation experience on projects with voice and data cabling work similar to that required for this project. Installers shall have proof of factory certification for products specified for this project. C. NEC Compliance: Comply with NEC as applicable to construction and installation of products and work specified herein. VADEN, RAGSDALE & WOODWARD, INC Page 2 of 6
3 1.5 ACCEPTABLE MANUFACTURERS A. Companies who have formed alliances and have engaged in manufacture of Category 6 cabling products of types and ratings as specified herein and whose products have been in satisfactory use in similar service for not less than 3 years. PART TWO PRODUCTS 2.1 CABLING 1. Group 1: Berk-Tek and Ortronics under the trade name NETCLEAR. 2. Group 2: Amp Products under the trade name NETCONNECT. 3. Group 3: Siemon and Commscope under the trade name SYSTEM 6. A. Computer building wiring shall be 4 pair Category 6 UTP #24 AWG plenum rated, NEC type CMP. Outer jacket shall be blue in color. Accepted Category 6 manufacturer shall be as listed in Section (Cable shall be 550 MHz rated.) 2.2 MODULAR JACKS A. Provide data modular jacks style RJ-45, 8P8C, 568B wired, with 110 style punch down terminations for computer use. Color selection by Owner. Accepted Category 6 manufacturer shall be as listed in Section B. Provide thermoplastic faceplates with two, three, or four modular ports and configuration of modular jacks as specified on the plans. Where required provide blank closures. Color to match other wiring devices. 2.3 COMPUTER SUPPORT EQUIPMENT A. Patch Panels: Provide rack mounted Category 6 patch panels wired for 568B as required for termination of computer cables. Configure panels in 24 and 48; provide 50% spare capacity in each rack. Each rack shall have a maximum of 240 ports. Accepted Category 6 manufacturer shall be as listed in Section A. Provide self-supporting 4-post floor mounted rack(s) for mounting of computer patch panels, fiber optic termination panels, and Owner's equipment. Unit shall be 84" in height and 19" in width constructed of anodized aluminum. Rails shall be drilled and tapped. Provide equivalent to AMP, Siemon, or Ortronics. Rack shall be fully enclosed with smoke glass door and have lockable front and back panels. PART THREE EXECUTION 3.1 GENERAL A. All system components and appurtenances shall be installed in accordance with the manufacturer's instructions as specified and indicated. All installation work must be done in accordance with the safety requirements set forth in the general requirements of ANSI C2 and NFPA 70. VADEN, RAGSDALE & WOODWARD, INC Page 3 of 6
4 B. Interior cabling shall be installed and terminated at all station locations as indicated on the Drawings and herein specified. Cabling shall take the form of a "Structural Building Wiring Plan" where station cables are wired directly from a distribution point to the appropriate outlet location. Station cables shall not be installed in the same raceway with AC power cables. Station cables not installed in raceways shall be properly secured above the ceiling on system cable supports as shown on the Drawings. Cables shall not be installed on top of the tiles of lay-in ceiling grid system. C. Labeling and marking shall be as follows: 1. Provide permanent markers on each cable at each termination point for easy identification. Numbering for jack identification shall be as described below unless the Owner has a predetermined identification scheme. 2. Jack numbering shall match the corresponding patch panel in the communications closet. Labels are to be machine made; hand written labels are unacceptable. 3. Data jacks shall be numbered with the flowing scheme: nn-01-d01, where nn is the building number, 01 is the floor number, D indicates data, and 01 is the 1 st cable in the sequence for that floor. D. All cables shall be terminated in approved modular jacks or termination enclosures. No cables shall be left "free" unless so stated on the Drawings. 3.2 INSTALLATION OF STRUCTURED COMPUTER CABLING A. The computer wiring standard shall be T568B. B. The Contractor shall install the computer system connecting all outlets and cabling to patch panels for a complete premise wiring system. This system shall be tested as specified herein. 3.3 TESTING - GENERAL A. After installation the Contractor shall test the structured cabling systems as outlined below. Tests performed will have the results recorded in a three ring binder form and submitted to the Architect; provide three copies for review. Test reports shall be attached a signed affidavit by the contractor certifying the reports. Outlets/cables failing these test procedures shall be corrected (or replaced) and retested at no additional cost to the Owner. After testing all cables will have a PASS rating. B. The Contractor shall provide the necessary testing equipment for testing all cabling under this project. Installers testing cabling shall have a minimum of three years experience in industry testing procedures; installers shall also have factory certification in testing. Copies of this certification shall be available to Owner for examination upon request. C. The Owner reserves the right to witness any or all testing. The Contractor shall advise the Owner in written when testing is scheduled at least one week in advance of actual testing. 3.4 TESTING - STRUCTURED COMPUTER CABLING A. Each computer cable shall be tested from each outlet (jack) to the patch panel for the following parameters: VADEN, RAGSDALE & WOODWARD, INC Page 4 of 6
5 Frequen cy MHz 1. Basic data: a. Cable manufacturer and part number, NVP b. ester manufacturer, model, serial number and hardware/software versions. c. Project name and circuit ID number d. Autotest specification used e. Overall PASS/FAIL indication f. Date of test 2. Wire Map: a. Continuity b. Shorts between conductors c. Crossed pairs d. Reversed pairs e. Split/open pairs 3. TIA/EIA 568-B.2 testing criteria for Permanent Link shall be followed as described below and shall meet the minimum values specified in the table below. a. Cable length in meters b. Propagation delay c. Delay skew d. Attenuation e. Near End Cross Talk (NEXT); both ends f. Power sum NEXT (PS NEXT); both ends g. ELFEXT; both ends h. Power Sum ELFEXT (PS ELFEXT); both ends i. Return Loss; both ends j. ACR k. Power Sum ACR Attenuati on, Permanent Link Performance based upon TIA/EIA 568-B.2 (Draft 9b) Return Loss, NEXT, PS NEXT, ELFEXT, PS ELFEXT, ACR, PS ACR, Propagation Delay: 498 ns Delay Skew: 44 ns VADEN, RAGSDALE & WOODWARD, INC Page 5 of 6
6 B. UTP testers shall be approved for Level III as a field test device. Testers shall be factory calibrated by the manufacturer. The contractor shall provide a copy of the calibration certificate upon request by the Engineer or Owner. 3.5 WARRANTY A. The Contractor shall warrant his installation against product defects and workmanship. All cabling components shall meet or exceed the requirements of TIA/EIA-568B, for a minimum period of 10 years. END OF SECTION VADEN, RAGSDALE & WOODWARD, INC Page 6 of 6
Communications Integrators, Inc. June S. Wilson Street, Suite 105 Tempe, Arizona Toll Free (800) Web Site
Communications Integrators, Inc. June 2008 2625 S. Wilson Street, Suite 105 Tempe, Arizona 85282 Toll Free (800) 679-9711 Web Site www.ciinet.com Product Guide Specification Specifier Notes: This product
More information1. This Section specifies the ethernet Category 5E data cabling system for buildings and structures.
PAGE 271200-1 SECTION 271200 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationA. Action Submittals: Written and graphic information that requires Architect's responsive action.
SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification
More informationREVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty
HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to
More informationSECTION SUBMITTAL PROCEDURES
SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification
More information.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal
City of Winnipeg Brady Road Landfill Site Section 01300 New Entrance and Scale Facility Page 1 of 4 SUBMITTALS 1. SHOP DRAWINGS 1.1 General.1 Arrange for the preparation of clearly identified Shop Drawings
More informationSECTION BUILDING WIRE AND CABLE
SECTION 260519 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wire and cable. 2. Wiring connectors and connections. B. RELATED SECTIONS 1. Section 26 05 53 Electrical Identification. 2. Section
More informationSECTION PANELBOARDS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 01 3300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationCOMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationJEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia
BULLETIN NO. 6 TO THE PLANS AND SPECIFICATIONS FOR JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia EwingCole Architects.Engineers.Interior Designers.Planners
More informationUCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL
SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationSECTION ELECTRICAL IDENTIFICATION
SECTION 16075 ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationTCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II
SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationEast Central College
SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationSpec Section: , Complete Elec, Comm, and Fire Alarm , Complete Elec, Comm, and Fire Alarm Data Sheets RAN/GCAN
SUBMITTAL REVIEW Submittal: No. 019.00 Spec Section: 26 0000, 28 0000 Complete Elec, Comm, and Fire Alarm Reviewed By: Laura Landon, Comma-Q Architecture Date: June 29, 2012 Project: BPS Belgrade Elementary
More informationUNION COUNTY VOCATIONAL-TECHNICAL SCHOOLS West Hall Addition Project Raritan Road, Scotch Plains, NJ
SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 General
More informationA. Product Data: For each electrical identification product indicated.
SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT Henderson Engineers, Inc. PART 1 - GENERAL REQUIREMENTS 1.1 SUMMARY A. Extent of Plumbing work to be identified as required by this Section
More informationA. Action Submittals: Written and graphic information that requires Engineer's responsive action.
SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification
More informationSECTION SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 01 33 00 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationSECTION COMMUNICATIONS COPPER BACKBONE CABLING
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationSECTION SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS
SECTION 01300 SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and other Division-1 Specification Sections,
More informationSECTION IDENTIFICATION FOR COMMUNICATIONS SYSTEMS
Part 1 General 1.1 Summary 1.1.1 This section shall govern the products and installation of identification and labeling of all required parts, pieces and accessories of the communications cabling system,
More informationB. The designated coverage areas shall include both indoor and outdoor coverage.
Page 1 of 8 This Wi-Fi Section shall be included in the Contract Specifications, unless directed by the University Project Manager. Contact the UW Project Manager to determine if the design for Wi-Fi outlet
More informationSPECIAL PROVISION Description of Project, Scope of Contract and Sequence of Work
2004 Specifications CSJ 0110-04-166 SPECIAL PROVISION 000--363 Description of Project, Scope of Contract and Sequence of Work 1. General. The work to be performed on this project consists of furnishing,
More informationB. Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form.
McKee and Associates Architecture and Interior Design Addendum No. THREE Date: 12.11.17 Project: A NEW BUILDING FOR THE GREATER LIMESTONE COUNTY CHAMBER OF COMMERCE ATHENS, ALABAMA A3.1 GENERAL PROJECT
More informationSECTION EMERGENCY RESPONDER RADIO COVERAGE SYSTEMS
510.1 Emergency responder radio coverage in new buildings. Approved radio coverage for emergency responders shall be provided within all buildings meeting any one of the following conditions: 1. There
More informationLevel III measurement accuracy of field testers for Twisted Pair Copper Cabling Explained in Technical Detail
Level III measurement accuracy of field testers for Twisted Pair Copper Cabling Explained in Technical Detail 1 Outline Henriecus Koeman Fluke Networks July 9, 2001 This rather technical discussion contains
More informationSECTION SUBMITTAL PROCEDURES
SECTION 013300 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply
More information1) The addition of TCL and ELTCTL requirements to Category 6
Subject 444 TO: SUBJECT: 455 East Trimble Road San Jose, CA 95131 July 28, 2008 Subscribers to UL s Listing and Verification Services for Communications Cable (DUZX) Revised Test and Follow-Up Service
More information1. Land survey Work. 2. Civil and Structural engineering services.
SECTION 01050 FIELD ENGINEERING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division-1 Specification
More informationSt. Monica Food Pantry
St. Monica Food Pantry 26 5113-1 ELECTRICAL WORK DIVISION 26 SECTION 265113 INTERIOR LIGHTING FIXTURES PART 1. GENERAL 1.1 WORK INCLUDES A. Extent, location, and details of interior lighting fixture work
More informationSECTION CONTRACTOR SUBMITTALS. A. All submittals by the CONTRACTOR shall be submitted to the ENGINEER.
SECTION 01300 - PART 1 - GENERAL 1.1 GENERAL A. All submittals by the CONTRACTOR shall be submitted to the ENGINEER. B. Unless otherwise noted, within 14 days after the date of commencement as stated in
More informationSECTION LIGHTING PART 1- GENERAL
SECTION 16500 LIGHTING PART 1- GENERAL 1.01 WORK INCLUDED A. The Contractor shall provide all lighting fixtures, panelboards, labor, material, etc., in accordance with the preceding specifications, the
More informationRegal Series Recessed Flatwalls
Regal Series Recessed Flatwalls General Specifications The Amico Regal Series Recessed Flatwall shall be manufactured by Amico Corporation, in accordance with job specific shop drawings and documents.
More informationTSB-67. Transmission Performance Specifications for Field Testing of UTP Cabling Systems
TSB-67 Transmission Performance Specifications for Field Testing of UTP Cabling Systems Prepared by: ANSI/EIA/TIA PN-3287 Task Group on UTP Link Performance Required Field Test Parameters for TSB-67 Wire
More informationAESA TECHNOLOGY OF LAN CABLE
TECHNOLOGY OF LAN CABLE CONTENT CHAPTER INTRODUCTION CHAPTER LOCAL AREA NETWORK (LAN) CHAPTER STRUCTURED CABLING SYSTEM (SCS) CHAPTER OPTICAL FIBER CABLE CHAPTER STANDARD CHAPTER COPPER LAN CABLE DESIGN
More informationWATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.:
WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO-00111 Job No.: 16-7003 To Respondent of Record: ADDENDUM 2 July 5, 2017 This addendum, applicable to work referenced
More informationAMP NETCONNECT Category 6 System
AMP NETCONNECT Category 6 System 2 How Did We Get Here? Basic Cabling Structure Component Specifications Link/Channel Specifications Additional Structure Options EIA/TIA TSB36 EIA/TIA 568 TIA/EIA TSB40
More informationMISSISSIPPI STATE UNIVERSITY Office of Planning Design and Construction Administration
SECTION 01 340 - SHOP DRAWINGS, PRODUCT DATA AND SAMPLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other
More informationSECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES
SECTION 01 33 23 SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES PART 1 GENERAL 1.1 DESCRIPTION A. This specification defines the general requirements and procedures for submittals. A submittal is information
More informationSPECIAL SPECIFICATION 1806 Spread Spectrum Wireless Modem
1993 Specifications CSJ s 0902-48-442 & 0902-48-432 SPECIAL SPECIFICATION 1806 Spread Spectrum Wireless Modem 1. General. This Item shall govern for the furnishing and installation of Spread Spectrum Wireless
More informationB. Related Sections include the following: 1. Division 16 Sections for basic electrical and telecom design requirements
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2
More informationPROJECT TITLE PROJECT NO: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA
SECTION 01 78 00 CLOSE-OUT SUBMITTALS PART 1 - GENERAL 1.1 GUARANTEES A. Compile and submit guarantees, bonds, and service and maintenance contracts specified in the individual B. Guarantees from Subcontractors
More informationCITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT. Emergency Responder Radio Enhancement Coverage System (RES)
Reference: Denver Fire Code Sections 510 Approved: Manuel Almagure Division Chief, Fire Prevention Division Number: 510-1 Effective Date: February 1, 2018 Page 1 of 8 This Policy 510-1 provides additional
More informationCategory 7 A /Class F A Products
CATEGORY 7 A /CLASS F A PRODUCTS Category 7 A /Class F A Products Exceeding ISO/IEC category 7 A /class F A specifications, Siemonʼs fully shielded TERA endto-end cabling solution is the highest-performing,
More informationThe School District of Palm Beach County Project Name SDPBC Project No. SECTION ( ) SIGNAGE PART 1 GENERAL 1.1 RELATED DOCUMENTS
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 10441 (10 14 00) SIGNAGE A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1 specification section,
More informationSECTION SIGNAGE
SECTION 10 14 00 SIGNAGE PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1 specification section, apply
More informationLAUSD Facilities Technology Program Management Group
LAUSD Facilities Technology Program Management Group 034 Mignonette Street Los Angeles, CA 9006 Ph #: 3-0-690 Fax: 3-48-8475 Date: 0/07/04 To: LAUSD/New Facilities Project Management From: Stefan Brown
More informationSECTION COMMUNICATIONS COPPER OSP CABLING
SECTION 27 13 14 COMMUNICATIONS COPPER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,
More informationSECTION INTERIOR SIGNAGE
SECTION 10 14 02 INTERIOR SIGNAGE PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by
More informationSECTION IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY
SECTION 280553-IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION A. This specification section covers the furnishing and installation of nameplates, labels, wire markers,
More informationSECTION MECHANICAL IDENTIFICATION
SECTION 15190 MECHANICAL IDENTIFICATION PART 1 GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. Nameplates. 2. Tags. 3. Stencils. 4. Pipe Markers. 1.02 SUBMITTALS A. Submit valve chart and schedule,
More informationCLARK COUNTY FIRE CODE AMENDMENTS
CLARK COUNTY FIRE CODE AMENDMENTS SECTION 510 EMERGENCY RESPONDER RADIO COVERAGE SYSTEM is amended to read as follows: SECTION 510 EMERGENCY RESPONDER RADIO COVERAGE SYSTEM 510.1 Emergency responder radio
More informationSECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Project Record Documents. B. Operation and Maintenance Manuals. C. Warranties and bonds. 1.02 RELATED REQUIREMENTS SECTION 01 78 00 A. Section 01 30 00 - Administrative
More informationSPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM
2004 Specifications CSJ 3622-01-001, ETC. SPECIAL SPECIFICATION 8398 LIGHTNING PROTECTION SYSTEM 1. Description. This Special Specification governs the design and installation of Lightning Protection System
More informationn Proper pin termination at each end n Continuity to the remote end n Shorts between any two or more conductors n Transposed pairs: n Crossed pairs.
INTRODUCTION Structured Cabling or data cabling (also known Local Area Network or LAN Cabling) is increasing in its deployment for business, commercial and residential use to carry signaling for networks
More informationSECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION
SECTION 16715 COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION PART 1 - GENERAL 1.01 SECTION DESCRIPTION AND BASIC REQUIREMENTS A. The Electrical Power Distribution System provides power distribution from
More informationSECTION COMMUNICATIONS COPPER BACKBONE CABLING
SECTION 27 13 13 COMMUNICATIONS COPPER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
More informationExcavating, Backfilling, and Compaction for Utilities Piping (Plumbing).
SECTION 15047 - IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Identification including necessary accessories indicated on Construction Documents and specified in this section or as required
More informationSECTION INTERCOMMUNICATIONS SYSTEMS. A. Section Includes: Manually switched intercommunications systems with the following components:
SECTION 275123 INTERCOMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: Manually switched intercommunications systems with the following components: 1. Master stations (EXISTING).
More informationWIREMOLD AL7450 Series Isoduct Aluminum Raceway
Three-Channel, Dual-Cover, Prewired Aluminum Raceway System Isoduct AL7450 Series Raceway is a costeffective, highly aesthetic solution for providing access to communication cabling and electrical wiring
More informationA. This section specifies procedural requirements for Shop Drawings, product data, samples, and other miscellaneous Work-related submittals.
SECTION 01300 PART 1 GENERAL 1.1 SECTION INCLUDES A. Description of Requirements B. Submittal Procedures C. Specific Submittal Requirements D. Action on Submittals E. Repetitive Review 1.2 DESCRIPTION
More informationPROJECT LOCATION BOZEMAN HIGH SCHOOL. ELECTRICAL ENGINEER: Van Dykken Engineering 37 Spanish Peak Drive Bozeman, MT Phone:
DRAWING INDEX GENERAL C. PROJECT COVER G-WING A/V IMPROVEMENTS.0 AREA PLAN ST FLOOR SOUTH. TYP. PROJECTOR MOUNTING & PROJECTOR NOTES.2 G-WING TECHNOLOGY CABINET ELEVATIONS.3 G-WING WIRING DIAGRAM.4 G-WING
More informationSPECIAL SPECIFICATION Inch LED Traffic Signal Lamp Unit
1993 Specifications SPECIAL SPECIFICATION 1201 12 Inch LED Traffic Signal Lamp Unit 1. Description. This specification describes the minimum acceptable design and performance requirements for a twelve
More informationInformation for Digital Antenna System (DAS)/ Bi-Directional Amplification (BDA) Systems
Information for Digital Antenna System (DAS)/ Bi-Directional Amplification (BDA) Systems (Public Safety/Emergency Responder Radio System) Orange County Sheriff s Department, Communications & Technology
More informationWAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)
WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) 1 PART 1: GENERAL This section describes materials and installation requirements for low voltage
More informationSECTION WIREWAYS FOR RADIOLOGY EQUIPMENT
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable
More information[Note to PSC: Include these sections in the Contract Documents, even though some are not included in the U of I Facilities Standards]
SECTION 01 78 23 - OPERATION AND MAINTENANCE DATA PART I - GENERAL 1.1 SUMMARY A. Operation and Maintenance Data shall be submitted in appropriately-sized binders, with dividers, and organized by each
More informationb. Army Reserve Design Process Submittal Requirements (DPSR) c. USARC G-2/6 IT Design Whitepaper, 26 Jun 2012 ( ENCLOSURE 1)
CELRL-PM-R July ARCOS BULLITEN - SUBJECT: IT Design. REFERENCE: a. Army Reserve IT Manual, Change b. Army Reserve Design Process Submittal Requirements (DPSR) c. USARC G-/ IT Design Whitepaper, Jun ( ENCLOSURE
More informationSynergy RJ45 LCS 6 Category 6 data outlets
Legrand Electric Ltd. Arena Park - Dial Lane West Bromwich - West Midlands - B70 0EB- United Kingdom Technical enquiries : Tel. 0870 8 90 - Fax. 0870 8 9021 CONTENTS PAGE 7300 56 7300 57 1. Applications...
More informationSECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES
SECTION 01 33 23 - SHOP DRAWINGS, PRODUCT DATA, AND PART 1 - GENERAL 1.1 SUMMARY A. Products include, but are not limited to, the following construction submittals: 1. Shop Drawings. 2. Product Data. 3.
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-26 00 00.00 20 (July 2006) ------------------------------- Preparing Activity: NAVFAC Superseding UFGS-26 00 00.00 20 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More information1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.
PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02
More informationSection Project Closeout
Section 01700 - Project Closeout PART 1 GENERAL A. STIPULATIONS The section Special Requirements forms a part of this section by this reference thereto and shall have the same force and effect as if printed
More informationCampus Cable Plant Specification for Year 1 Wireless Coverage (Phase I)
Campus Cable Plant Specification for Year 1 Wireless Coverage (Phase I) July 17, 2017 1. General 1.1. Overview This document identifies and describes the specification supporting the installation of data
More informationSECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT
SECTION 21 05 53 IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2015-2015 ARCAT, Inc. - All rights reserved PART 1 GENERAL
More informationINDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS:
INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS: 013300 SUBMITTAL PROCEDURES 018116 CONSTRUCTION WASTE MANAGEMENT DIVISION 2 EXISTING CONDITIONS: 023000 EARTHWORK
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 SUBMITTALS A.
More information5 Mbit/s Repeater Carrierband to Single-mode Fiber Optic
Installation and Testing 5 Mbit/s Repeater Carrierband to Single-mode Fiber Optic Models CBR-7AC CBR-7DC This manual describes the procedures for installing and testing the CBR-7 Fiber-Optic Repeaters.
More informationSECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationDELTA Test Report. Certification testing of generic cabling products: Unscreened channel, Class E, 4 connector model. Performed for Sterling
DELTA Test Report TEST Reg. no. 19 Certification testing of generic cabling products: Unscreened channel, Class E, 4 connector model Performed for Sterling DANAK-19/16909 Project no.: T213173-01 Page 1
More informationIFB PAINTING AT HAYDON ELEMENTARY ADDENDUM #1
IFB 18-14 PAINTING AT HAYDON ELEMENTARY ADDENDUM #1 IFB MODIFICATIONS: BONDING REQUIREMENTS: Due to the complexity of the scope of work, MCPS is requiring bonding for this bid. The following bonds are
More informationPart VIII Electrical GENERAL REQUIREMENTS CHAPTER 33
Part VIII Electrical CHAPTER 33 GENERAL REQUIREMENTS < SECTION E3301 GENERAL E3301.1 Scope. The installation of electrical systems, equipment and components indoors and outdoors that are within the scope
More informationTechnical Specifications SECTION C
Page 1 of 12 INSTITUTE FOR PLASMA RESEARCH Technical Specifications SECTION C Design, Fabrication, assembly, testing and supply of Filter polychromators & associated components and demonstration of performance
More informationSECTION CABLE TRAYS
SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More informationSEI Certification Program Manual
Safety Equipment Institute SEI Certification Program Manual Section 29: Industrial Protective Clothing and Equipment Program 0 of 6 SEI Certification Program Manual Section 29: Industrial Protective Clothing
More informationSECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL
PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.
More informationSECTION OPERATION AND MAINTENANCE DATA
SECTION 01787 OPERATION AND MAINTENANCE DATA PART 1 GENERAL 1.01 SUMMARY A. Compile product data and related information appropriate for OWNER's maintenance and operation of products furnished under Contract.
More informationCSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe Markers. 2. Valve Tags. 3. Equipment Nameplates. 4. Underground Marking Tape. 5. Duct
More informationPMA ONLINE TRAINING. Commercial Drawings. One Hour Continuing Education
PMA ONLINE TRAINING Commercial Drawings One Hour Continuing Education PMA training disclaimer The information provided in this document is intended for use as a guideline and is not intended as, nor does
More informationINVITATION TO TENDER ITT No. PS FIRE HALL 5 + HOUSING CONSTRUCTION. ADDENDUM No. 2 and AMENDMENT No. 2
FINANCE, RISK AND BUSINESS PLANNING Supply Chain Management May 17, 2016 INVITATION TO TENDER ITT No. PS20160468 FIRE HALL 5 + HOUSING CONSTRUCTION ADDENDUM No. 2 and AMENDMENT No. 2 RE: Various additions
More informationHeat Exchanger Construction Checklist
Heat Exchanger Checklist Project: Pump tag: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing. The checklist
More informationAnswer: Qualification statement should be provided with the bid.
Little Diversified Architectural Consulting, Inc. 5815 Westpark Drive Charlotte, North Carolina 28217 Phone: 704-525-6350 Fax: 704-561-8700 Lincoln County Probation Renovation 208 N. Government Street
More informationD. The contractor shall furnish the owner with three (3) complete sets of service and operating literature.
CLASSROOM SOUNDFIELD DISTRIBUTION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
More informationPREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!
PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling
More informationPower Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL
Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL 1.01 SUMMARY: The following technical specification describes the requirements of the high accuracy standalone 3 phase Power
More informationCopyright Teletronics International, Inc. Patent Pending
Copyright 2003 By Teletronics International, Inc. Patent Pending FCC NOTICES Electronic Emission Notice: This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
More informationPiping & Equipment Identification
Piping & Equipment Identification Part 1 General 1.01 Description of Work A. Work in this section includes: Identification materials, including necessary accessories indicated on Contract Documents and
More information