Reactive Energy Management

Size: px
Start display at page:

Download "Reactive Energy Management"

Transcription

1 Power Factor Correction Reactive Energy Management Low Voltage components Catalogue 2013

2 Reactive Energy management Your requirements. Optimize energy consumption By reducing electricity bills, By reducing power losses, By reducing CO 2 emissions. Increase power availability Compensate for voltage sags detrimental to process operation, Avoid nuisance tripping and supply interruptions. Improve your business performance Optimize installation size, Reduce harmonic distortion to avoid the premature ageing of equipment and destruction of sensitive components.

3 Our solutions. Reactive energy management In electrical networks, reactive energy results in increased line currents for a given active energy transmitted to loads. The main consequences are: Need for oversizing of transmission and distribution networks by utilities, Increased voltage drops and sags along the distribution lines, Additional power losses. This results in increased electricity bills for industrial customers because of: Penalties applied by most utilities on reactive energy, Increased overall kva demand, Increased energy consumption within the installations. Reactive energy management aims to optimize your electrical installation by reducing energy consumption, and to improve power availability. Total CO 2 emissions are also reduced. Utility power bills are typically reduced by 5 % to 10 %. + Our energy con-sumption was reduced by 9 % after we installed 10 capacitor banks with detuned reactors. Electricity bill optimised by 8 % and payback in 2 years. Testifies Michelin Automotive in France. Energy consumption reduced by 5 % with LV capacitor bank and active filter installed. POMA OTIS Railways, Switzerland. 70 capacitor banks with detuned reactors installed, energy consumption reduced by 10 %, electrcity bill optimised by 18 %, payback in just 1 year. Madrid Barrajas airport Spain. I

4 Improve electrical networks and reduce energy costs Power Factor Correction Every electric machine needs active power (kw) and reactive power to operate. The power rating of the installation in kva is the combination of both: (kva)² = (kw)² + ². The Power Factor has been defined as the ratio of active power (kw) to apparent power (kva). Power Factor = (kw) / (kva). The objective of Reactive Energy management is improvement of Power Factor, or Power Factor Correction. This is typically achieved by producing reactive energy close to the consuming loads, through connection of capacitor banks to the network. II

5 Ensure reliability and safety on installations Quality and reliability Continuity of service thanks to the high performance and long life expectancy of capacitors. 100% testing in manufacturing plant. Design and engineering with the highest international standards. Safety Tested safety features integrated on each phase. Over-pressure system for safe disconnection at the end of life. All materials and components are free of PCB pollutants. + Thanks to the know-how developed over 50 years, Schneider Electric ranks as the global specialist in Energy management providing a unique and comprehensive portfolio. Schneider Electric helps you to make the most of your energy with innovative, reliable and safe solutions. Efficiency and productivity Product development including innovation in ergonomics and ease of installation and connection. Specially designed components to save time on installation and maintenance. All components and solutions available through a network of distributors and partners in more than 100 countries. III

6 Quality & Environment Quality certified - ISO 9001 and ISO A major strength In each of its units, Schneider Electric has an operating organization whose main role is to verify quality and ensure compliance with standards. This procedure is: uniform for all departments; recognized by numerous customers and official organizations. But, above all, its strict application has made it possible to obtain the recognition of independent organizations. The quality system for design and manufacturing is certified in compliance with the requirements of the ISO 9001 and ISO Quality Assurance model. Stringent, systematic controls During its manufacture, each equipment item undergoes systematic routine tests to verify its quality and compliance: measurement of operating capacity and tolerances; measurement of losses; dielectric testing; checks on safety and locking systems; checks on low-voltage components; verification of compliance with drawings and diagrams. The results obtained are recorded and initialled by the Quality Control Department on the specific test certificate for each device. Schneider Electric undertakes to reduce the energy bill and CO 2 emissions of its customers by proposing products, solutions and services which fit in with all levels of the energy value chain. The Power Factor Correction and harmonic filtering offer form part of the energy efficiency approach. IV

7 A new solution for building your electrical installations A comprehensive offer Power Factor Correction and harmonic filtering form part of a comprehensive offer of products perfectly coordinated to meet all medium- and low-voltage power distribution needs. All these products have been designed to operate together: electrical, mechanical and communications consistency. The electrical installation is accordingly both optimized and more efficient: improved continuity of service; reduced power losses; guarantee of scalability; efficient monitoring and management. You thus have all the trumps in hand in terms of expertise and creativity for optimized, reliable, expandable and compliant installations. Tools for easier design and setup With Schneider Electric, you have a complete range of tools that support you in the knowledge and setup of products, all this in compliance with the standards in force and standard engineering practice. These tools, technical notebooks and guides, design aid software, training courses, etc. are regularly updated. Schneider Electric joins forces with your expertise and your creativity for optimized, reliable, expandable and compliant installations. Because each electrical installation is a specific case, there is no universal solution. The variety of combinations available allows you to achieve genuine customization of technical solutions. You can express your creativity and highlight your expertise in the design, development and operation of an electrical installation. V

8

9 Reactive Energy Management General contents Power Factor Correction guideline 3 Low Voltage capacitors 15 Detuned reactors 54 Power Factor controllers 60 Contactors 64 Appendix 68 2

10 2

11 Power Factor Correction guideline Contents Presentation Why reactive energy management? 4 Method for determining compensation 6 Low Voltage capacitors with detuned reactors 10 Rated voltage and current 11 Capacitor selection guide 12 Construction of references 13 Principle 13 Low Voltage capacitors 15 Detuned reactors 67 Power Factor controllers 71 Contactors 75 Appendix 79 3

12 Power Factor Correction guideline Why reactive energy management? Principle of reactive energy management + Due to this higher supplied current, the circulation of reactive energy in distribution networks results in: > Overload of transformers > Higher temperature rise in power cables > Additional losses > Large voltage drops > Higher energy consumption and cost > Less distributed active power. DE90087.eps In this representation, the Power Factor (P/S) is equal to cosj. DE90071_r.eps All AC electrical networks consume two types of power: active power (kw) and reactive power : The active power P (in kw) is the real power transmitted to loads such as motors, lamps, heaters, computers, etc. The electrical active power is transformed into mechanical power, heat or light. The reactive power Q (in kvar) is used only to power the magnetic circuits of machines, motors and transformers. The apparent power S (in kva) is the vector combination of active and reactive power. The circulation of reactive power in the electrical network has major technical and economic consequences. For the same active power P, a higher reactive power means a higher apparent power, and thus a higher current must be supplied. The circulation of active power over time results in active energy (in kwh). The circulation of reactive power over time results in reactive energy (kvarh). In an electrical circuit, the reactive energy is supplied in addition to the active energy. Power generation Active energy Reactive energy Transmission network Reactive energy supplied and billed by the energy provider. Active energy Reactive energy Motor DE90088.eps Q Q c For these reasons, there is a great advantage in generating reactive energy at the load level in order to prevent the unnecessary circulation of current in the network. This is what is known as power factor correction. This is obtained by the connection of capacitors, which produce reactive energy in opposition to the energy absorbed by loads such as motors. The result is a reduced apparent power, and an improved power factor P/S as illustrated in the diagram opposite. The power generation and transmission networks are partially relieved, reducing power losses and making additional transmission capacity available. DE90071_r.eps Power generation Active energy Transmission network Active energy Reactive energy Motor The reactive power is supplied by capacitors. No billing of reactive power by the energy supplier. Capacitors 4

13 Why reactive energy management? + Benefits of reactive energy management Optimized management of reactive energy brings economic and technical advantages. Savings on the electricity bill > Eliminating penalties on reactive energy and decreasing kva demand. > Reducing power losses generated in the transformers and conductors of the installation. Example: Loss reduction in a 630 kva transformer PW = 6,500 W with an initial Power Factor = 0.7. With power factor correction, we obtain a final Power Factor = The losses become: 3,316 W, i.e. a reduction of 49 %. Increasing available power A high power factor optimizes an electrical installation by allowing better use of the components. The power available at the secondary of a MV/LV transformer can therefore be increased by fitting power factor correction equipment on the low voltage side. The table opposite shows the increased available power at the transformer output through improvement of the Power Factor from 0.7 to 1. Power factor Increased available power % % % % % % Reducing installation size Installing power factor correction equipment allows conductor cross-section to be reduced, since less current is absorbed by the compensated installation for the same active power. The opposite table shows the multiplying factor for the conductor cross-section with different power factor values. Power factor Cable crosssection multiplying factor Reducing voltage drops in the installation Installing capacitors allows voltage drops to be reduced upstream of the point where the power factor correction device is connected. This prevents overloading of the network and reduces harmonics, so that you will not have to overrate your installation. 5

14 Power Factor Correction guideline Method for determining compensation The selection of Power Factor Correction equipment can follow a 4-step process: Calculation of the required reactive energy. Selection of the compensation mode: - Central, for the complete installation - By sector - For individual loads, such as large motors. Selection of the compensation type: - Fixed, by connection of a fixed-value capacitor bank; - Automatic, by connection of a different number of steps, allowing adjustment of the reactive energy to the required value; - Dynamic, for compensation of highly fluctuating loads. Allowance for operating conditions and harmonics. Step 1: Calculation of the required reactive power DE90091.eps The objective is to determine the required reactive power Q c to be installed, in order to improve the power factor cos φ and reduce the apparent power S. For φ < φ, we obtain: cos φ > cos φ and tan φ < tan φ. This is illustrated in the diagram opposite. Qc can be determined from the formula Qc = P. (tan φ - tan φ ), which is deduced from the diagram. Q c = power of the capacitor bank in kvar. P = active power of the load in kw. tan φ = tangent of phase shift angle before compensation. tan φ = tangent of phase shift angle after compensation. The parameters φ and tan φ can be obtained from billing data, or from direct measurement in the installation. The following table can be used for direct determination. Before compensation Reactive power to be installed per kw of load, in order to get the required cos j or tan j tan j cos j tan j cos j Example: consider a 1000 kw motor with cos j = 0.8 (tan j = 0.75). In order to obtain cos j = 0.95, it is necessary to install a capacitor bank with a reactive power equal to k x P, i.e.: Qc = 0.42 x 1000 = 420 kvar. 6

15 Method for determining compensation Step 2: Selection of the compensation mode Supply Bus Transformer Circuit breaker The location of low-voltage capacitors in an installation constitutes the mode of compensation, which may be central (one location for the entire installation), by sector (section-by-section), at load level, or some combination of the latter two. In principle, the ideal compensation is applied at a point of consumption and at the level required at any moment in time. In practice, technical and economic factors govern the choice. IC CC GC GC IC IC IC The location for connection of capacitor banks in the electrical network is determined by: th e overall objective (avoid penalties on reactive energy relieve transformer or cables, avoid voltage drops and sags) the operating mode (stable or fluctuating loads) the foreseeable influence of capacitors on the network characteristics the installation cost. M M M M CC : Central Compensation GC : Group Compensation IC : Individual Compensation M : Motor Load Central compensation The capacitor bank is connected at the head of the installation to be compensated in order to provide reactive energy for the whole installation. This configuration is convenient for a stable and continuous load factor. Group compensation (by sector) The capacitor bank is connected at the head of the feeders supplying one particular sector to be compensated. This configuration is convenient for a large installation, with workshops having different load factors. Compensation of individual loads The capacitor bank is connected right at the inductive load terminals (especially large motors). This configuration is very appropriate when the load power is significant compared to the subscribed power. This is the ideal technical configuration, as the reactive energy is produced exactly where it is needed, and adjusted to the demand. 7

16 Power Factor Correction guideline Method for determining compensation Step 3: Selection of the compensation type Different types of compensation should be adopted depending on the performance requirements and complexity of control: Fixed, by connection of a fixed-value capacitor bank Automatic, by connection of a different number of steps, allowing adjustment of the reactive energy to the required value Dynamic, for compensation of highly fluctuating loads. Fixed compensation This arrangement uses one or more capacitor(s) to provide a constant level of compensation. Control may be: Manual: by circuit-breaker or load-break switch Semi-automatic: by contactor Direct connection to an appliance and switched with it. These capacitors are installed: At the terminals of inductive loads (mainly motors) At busbars supplying numerous small motors and inductive appliances for which individual compensation would be too costly In cases where the load factor is reasonably constant. Automatic compensation This kind of compensation provides automatic control and adapts the quantity of reactive power to the variations of the installation in order to maintain the targeted cos j. The equipment is installed at points in an installation where the active-power and/or reactive-power variations are relatively large, for example: on the busbars of a main distribution switchboard on the terminals of a heavily-loaded feeder cable. Where the kvar rating of the capacitors is less than or equal to 15 % of the power supply transformer rating, a fixed value of compensation is appropriate. Above the 15 % level, it is advisable to install an automatically-controlled capacitor bank. Control is usually provided by an electronic device (Power Factor Controller) which monitors the actual power factor and orders the connection or disconnection of capacitors in order to obtain the targeted power factor. The reactive energy is thus controlled by steps. In addition, the Power Factor Controller provides information on the network characteristics (voltage amplitude and distortion, power factor, actual active and reactive power ) and equipment status. Alarm signals are transmitted in case of malfunction. Connection is usually provided by contactors. For compensation of highly fluctuating loads, fast and highly repetitive connection of capacitors is necessary, and static switches must be used. Dynamic compensation This kind of compensation is required when fluctuating loads are present, and voltage fluctuations have to be prevented. The principle of dynamic compensation is to associate a fixed capacitor bank and an electronic var compensator, providing either leading or lagging reactive currents. The result is continuously varying fast compensation, perfectly suitable for loads such as lifts, crushers, spot welding, etc. 8

17 Method for determining compensation + To know more about the influence of harmonics in electrical installations, see appendix page 69 Step 4: Allowing for operating conditions and harmonics Capacitors should be selected depending on the working conditions expected during their lifetime. Allowing for operating conditions The operating conditions have a great influence on the life expectancy of capacitors. The following parameters should be taken into account: Ambient Temperature ( C) Expected over-current, related to voltage disturbances, including maximum sustained overvoltage Maximum number of switching operations/year Required life expectancy. Allowing for harmonics Depending on the magnitude of harmonics in the network, different configurations should be adopted. Standard capacitors: when no significant non-linear loads are present. Oversized capacitors: when a few non-linear loads are present. The rated current of capacitors must be increased in order to cope with the circulation of harmonic currents. Harmonic rated capacitors used with detuned reactors. Applicable when a significant number of non-linear loads are present. Reactors are necessary in order to limit the circulation of harmonic currents and avoid resonance. Tuned filters: when non-linear loads are predominant, requesting harmonic mitigation. A special design is generally necessary, based on on-site measurements and computer simulations of the network. Capacitor selection Different ranges with different levels of ruggedness are proposed: "SDuty": Standard duty capacitors for standard operating conditions, and when no significant non-linear loads are present. "HDuty": Heavy duty capacitors for difficult operating conditions, particularly voltage disturbances, or when a few non-linear loads are present. The rated current of capacitors must be increased in order to cope with the circulation of harmonic currents. "Energy": Specially designed capacitors, for harsh operating conditions, particularly high temperature. Capacitors with detuned reactors: applicable when a significant number of non-linear loads are present. Before After 9

18 Power Factor Correction guideline Low Voltage capacitors with detuned reactors Reactors should be associated with capacitor banks for Power Factor Correction in systems with significant non-linear loads, generating harmonics. Capacitors and reactors are configured in a series resonant circuit, tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. For this reason, this configuration is usually called Detuned Capacitor Bank, and the reactors are referred to as Detuned Reactors. The use of detuned reactors thus prevents harmonic resonance problems, avoids the risk of overloading the capacitors and helps reduce voltage harmonic distortion in the network. The tuning frequency can be expressed by the relative impedance of the reactor (in %), or by the tuning order, or directly in Hz. The most common values of relative impedance are 5.7, 7 and 14 % (14 % is used with high level of 3rd harmonic voltages). Relative impedance (%) Tuning order Tuning 0Hz (Hz) Tuning 60Hz (Hz) The selection of the tuning frequency of the reactor capacitor depends on several factors: Presence of zero-sequence harmonics (3, 9, ) Need for reduction of the harmonic distortion level Optimization of the capacitor and reactor components Frequency of ripple control system if any. To prevent disturbances of the remote control installation, the tuning frequency should be selected at a lower value than the ripple control frequency. In a detuned filter application, the voltage across the capacitors is higher than the system s rated voltage. In that case, capacitors should be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents is absorbed by the detuned capacitor bank. In that case, capacitors should be designed to withstand higher currents, combining fundamental and harmonic currents. Effective reactive energy In the pages relating to detuned capacitor banks (Harmonic HDuty and Harmonic Energy), the reactive energy given in the tables is the resulting reactive energy provided by the combination of capacitors and reactors. Capacitor rated voltage Capacitors have been specially designed to operate in detuned bank configurations. Parameters such as the rated voltage, over-voltage and over-current capabilities have been improved, compared to standard configuration. 10

19 Rated voltage and current According to IEC standard, the rated voltage (U N ) of a capacitor is defined as the continuously admissible operating voltage. The rated current (I N ) of a capacitor is the current flowing through the capacitor when the rated voltage (U N ) is applied at its terminals, supposing a purely sinusoidal voltage and the exact value of reactive power generated. Capacitor units shall be suitable for continuous operation at an r.m.s. current of (1.3 x I N ). In order to accept system voltage fluctuations, capacitors are designed to sustain over-voltages of limited duration. For compliance to the standard, capacitors are for example requested to sustain over-voltages equal to 1.1 times U N, 8 h per 24 h. VarplusCan and VarplusBox capacitors have been designed and tested extensively to operate safely on industrial networks. The design margin allows operation on networks including voltage fluctuations and common disturbances. Capacitors can be selected with their rated voltage corresponding to the network voltage. For different levels of expected disturbances, different technologies are proposed, with larger design margin for capacitors adapted to the most stringent working conditions (HDuty & Energy). VarplusCan and VarplusBox capacitors when used along with Detuned Reactors have to be selected with a rated voltage higher than network service voltage (U s ). In detuned filter applications, the voltage across the capacitor is higher than the network service voltage (U s ). The recommended rated voltage of capacitors to be used in detuned filter applications with respect to different network service voltage (U s ) and relative impedance is given in the table below. These values ensure a safe operation in the most stringent operating conditions. Less conservative values may be adopted, but a case by case analysis is necessary. Capacitor Rated Voltage U N (V) Network Service Voltage U S (V) 50 Hz 60 Hz Relative Impedance 5.7 (%)

20 Power Factor Correction guideline Capacitor selection guide Capacitors must be selected depending on the working conditions expected during their lifetime. Solution Description Recommended use for Max. condition SDuty Standard capacitor > Networks with non significant N LL y 10 % non-linear loads HDuty Energy Available in can construction Heavy-duty capacitor Available in can and box construction Capacitor for special conditions > Standard over-current 1.5 I N > Standard operating 55 C (class D) temperature > Normal switching frequency 5,000 / year > Standard life expectancy Up to 100,000h* > A few non-linear loads N LL y 20 % > Significant over-current 1.8 I N > Standard operating 55 C (class D) temperature > Significant switching 7,000 / year frequency > Long life expectancy Up to 130,000h* > Significant number of nonlinear N LL y 25 % loads (up to 25 %) Available in box construction > Severe over-current 2.5 I N > Extreme temperature 70 C conditions > Very frequent switching 10,000 / year > Extra long life expectancy Up to 160,000h* * The maximum life expectancy is given considering standard operating conditions: rated voltage (U N ), rated current (I N ), 35 C ambient temperature. WARNING: the life expectancy will be reduced if capacitors are used in maximum working conditions. Since the harmonics are caused by non-linear loads, an indicator for the magnitude of harmonics is the ratio of the total power of non-linear loads to the power supply transformer rating. This ratio is denoted N LL, and is also known as G h /S n : N LL = Total power of non-linear loads (G h ) / Installed transformer rating (S n ). Example: Power supply transformer rating: S n = 630 kva Total power of non-linear loads: G h = 150 kva N LL = (150/630) x 100 = 24 % It is recommended to use Detuned Reactors with Harmonic Rated Capacitors (higher rated voltage than the network service voltage - see the Harmonic Application Tables) for N LL > 20 % and up to 50 %. Note: there is a high risk in selecting the capacitors based only on N LL as the harmonics in grid may cause current amplification and capacitors along with other devices may fail. Refer to page 69 for further details. 12

21 Construction of references Principle Capacitors B L R C H A B 4 0 Construction Range Power Voltage C = CAN B = BOX Power at 60 Hz 12.5 kvar at 60 Hz V V S = SDuty H = HDuty E = Energy at 50 Hz 10.4 kvar at 50 Hz A = 50 Hz B = 60 Hz "000B" means: labelled only for 50 Hz V V V V V V V Example: BLRBH172A206B48 = VarplusBox Heavy Duty, 480 V, 17.2 kvar at 50 Hz and 20.6 kvar at 60 Hz Detuned reactors L V R A 6 9 Detuned Reactor Relative impedance Power Freq. Voltage 05 = 5.7 % 07 = 7 % 14 = 14 % 12.5 kvar A = 50 Hz B = 60 Hz V V V V Example: LVR05125A69 = Detuned Reactor, 690 V, 5.7 %, 12.5 kvar, 50 Hz. 13

22

23 Low Voltage capacitors Contents Presentation Power Factor Correction guideline 3 Low Voltage capacitors 15 Offer Overview 16 VarplusCan 18 VarplusCan SDuty 20 VarplusCan HDuty 24 VarplusCan SDuty harmonic applications 29 VarplusCan SDuty + Detuned Reactor + Contactor 30 VarplusCan HDuty harmonic applications 32 VarplusCan HDuty + Detuned Reactor + Contactor 33 VarplusCan mechanical characteristics 35 VarplusBox capacitor 37 VarplusBox HDuty 39 VarplusBox Energy 43 VarplusBox HDuty harmonic applications 46 VarplusBox HDuty + Detuned Reactor + Contactor 47 VarplusBox Energy Harmonic applications 48 VarplusBox Energy + Detuned Reactor + Contactor 49 VarplusBox Mechanical characteristics 50 Detuned reactors 54 Power Factor controllers 60 Contactors 64 Appendix 68 15

24 Low Voltage Capacitors Offer Overview VarplusCan group of 3caps_r.eps SDuty HDuty Construction Extruded aluminium can Voltage range 230 V V 230 V V Power range 1-30 kvar 1-50 kvar (three-phase) Peak inrush Up to 200 x I n Up to 250 x I n current Overvoltage 1.1 x U n 8 h every 24 h Overcurrent 1.5 x I n 1.8 x I n Mean life expectancy Up to 100,000 h Up to 130,000 h Safety Self-healing + pressure-sensitive disconnector + discharge device (50 V/1 min) Dielectric Metallized Polypropylene film with Zn/Al alloy Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Impregnation Non-PCB, Biodegradable resin Non-PCB, sticky (dry) Biodegradable resin Ambient min. -25 C max 55 C temperature Protection IP20, indoor Mounting Upright Upright, horizontal Terminals Double fast-on + cable ( 10 kvar) CLAMPTITE - Three-phase terminal with electric shock protection (finger-proof) Stud type terminal (> 30 kvar) 16

25 Offer Overview VarplusBoX HDuty Energy Construction Steel sheet enclosure Voltage range 230 V V 380 V V Power range 5-60 kvar kvar (three-phase) Peak inrush Up to 250 x I n Up to 350 x I n current Overvoltage 1.1 x U n 8 h every 24 h Overcurrent 1.8 x I n 2.5 x I n Mean life expectancy Up to 130,000 h Up to 160,000 h Safety Self-healing + pressure-sensitive disconnector + discharge device (50 V/1 min) Dielectric Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film Impregnation Non-PCB, sticky (dry) Non-PCB, oil Biodegradable resin Ambient min. -25 C max 55 C min. -25 C max 70 C temperature Protection IP20, Indoor Mounting Upright Terminals Bushing terminals designed for large cable termination 17

26 Low Voltage Capacitors VarplusCan PE90131_r.eps Aluminum can capacitors specially designed and engineered to deliver a long working life with low losses in standard, heavy-duty and severe operating conditions. Suitable for Fixed and Automatic PFC, real time compensation, detuned and tuned filters. Main features Easy installation & maintenance Optimized design for low weight, compactness and reliability to ensure easy installation. Unique termination system that allows maintained tightness. 1 point for mounting and earthing. Vertical and horizontal position. 3 phase simultaneous disconnection. Disconnection independent of mechanical assembly. Resin filled technology for better cooling. Factory fitted non-removable discharge resistors; for extra safety. Safety Self-healing. Pressure-sensitive disconnector on all three phases. Discharge resistors fitted - non removable. Finger-proof CLAMPTITE terminals to reduce risk of accidental contact and to ensure firm termination (10 to 30 kvar). Special film resistivity and metallization profile for higher thermal efficiency, lower temperature rise and enhanced life expectancy. Compacity Optimized geometric design (small dimensions and low weight). Available on request in single phase. VarplusCan. For professionnals High life expectancy up to 130,000 hours. Very high overload capabilities and good thermal and mechanical properties. Economic benefits due to its compact size. Easy maintenance. Unique finger proof termination to ensure tightness. 18

27 VarplusCan group of 3caps_r.eps SDuty HDuty Construction Extruded aluminium can Voltage range 230 V V 230 V V Power range 1-30 kvar 5-50 kvar (three-phase) Peak inrush Up to 200 x I n Up to 250 x I n current Overvoltage 1.1 x U n 8 h every 24 h Overcurrent 1.5 x I n 1.8 x I n Mean life expectancy Up to 100,000 h Up to 130,000 h Safety Self-healing + pressure-sensitive disconnector + discharge device (50 V/1 min) Dielectric Metallized Polypropylene film with Zn/Al alloy Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Impregnation Non-PCB, Biodegradable resin Non-PCB, sticky (dry) Biodegradable resin Ambient min. -25 C max 55 C temperature Protection IP20 Indoor Mounting Upright Upright, horizontal Terminals Double fast-on + cable ( 10 kvar) CLAMPTITE - Three-phase terminal with electric shock protection (finger-proof) Stud terminal (> 30 kvar) 19

28 Low Voltage Capacitors VarplusCan SDuty group of 2caps.eps A safe, reliable and high-performance solution for power factor correction in standard operating conditions. Operating conditions For networks with insignificant non-linear loads: (N LL y 10 %). Standard voltage disturbances. Standard operating temperature up to 55 C. Normal switching frequency up to /year. Maximum current (including harmonics) is 1.5 x I N. Technology Constructed internally with three single-phase capacitor elements assembled in an optimized design. Each capacitor element is manufactured with metallized polypropylene film as the dielectric having features such as heavy edge metallization and special profiles which enhance the self-healing properties. The active capacitor elements are encapsulated in a specially formulated biodegradable, non-pcb, PUR (soft) resin which ensures thermal stability and heat removal from inside the capacitor. The unique finger-proof CLAMPTITE termination is fully integrated with discharge resistors and allows suitable access to tightening and ensures cable termination without any loose connections. Once tightened, the design guarantees that the tightening torque is always maintained. For lower ratings, double fast-on terminals with wires are provided. VarplusCan SDuty Benefits Stacked design for better stability. Resign filled technology for long life. Safety: self-healing pressure-sensitive disconnector on all three phases discharge resistor. Life expectancy up to 100,000 hours. Economic benefits and easy installation due to its compact size an low weight. Easy maintenance thanks to its unique finger-proof termination to ensure tightening. Also available in small power ratings from 1 to 5 kvar. 20

29 VarplusCan SDuty Technical specifications General characteristics Standards IEC /-2 Voltage range Frequency Power range Losses (dielectric) Losses (total) 230 to 525 V 50 / 60 Hz 1 to 30 kvar < 0.2 W / kvar < 0.5 W / kvar Capacitance tolerance -5 %, +10 % Voltage test Between terminals 2.15 x U N (AC), 10 s Between terminal & container Impulse voltage Discharge resistor 3 kv (AC), 10 s or 3.66 kv (AC), 2 s 8 kv Fitted, standard discharge time 60 s Working conditions Ambient temperature -25 / 55 C (Class D) Humidity 95 % Altitude 2,000 m above sea level Overvoltage 1.1 x U N 8 h in every 24 h Overcurrent Up to 1.5 x I N Peak inrush current 200 x I N Switching operations (max.) Up to 5,000 switching operations per year Mean Life expectancy Up to 100,000 hrs Harmonic content withstand N LL 10 % Installation characteristics Mounting position Indoor, upright Fastening Earthing Terminals Safety features Safety Protection Construction Casing Dielectric Impregnation Threaded M12 stud at the bottom CLAMPTITE - three-way terminal with electric shock protection (finger-proof) & double fast-on terminal in lower kvar Self-healing + Pressure-sensitive disconnector + Discharge device IP20 Extruded Aluminium Can Metallized polypropylene film with Zn/Al alloy Biodegradable, Non-PCB, PUR (soft) resin 21

30 Low Voltage Capacitors VarplusCan SDuty Rated Voltage 240/260 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) 230 V 240 V 260 V at 260 V 230 V 240 V 260 V at 260 V HC BLRCS021A025B HC BLRCS027A033B HC BLRCS042A050B LC BLRCS054A065B NC BLRCS063A075B NC BLRCS083A100B SC BLRCS109A130B24 Rated Voltage 380/400/415 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) 380 V 400 V 415 V at 400 V 380 V 400 V 415 V at 400 V EC BLRCS010A012B DC BLRCS017A020B DC BLRCS020A024B DC BLRCS025A030B DC BLRCS030A036B HC BLRCS042A050B HC BLRCS050A060B HC BLRCS063A075B LC BLRCS075A090B LC BLRCS083A100B MC BLRCS093A111B MC BLRCS104A125B NC BLRCS125A150B NC BLRCS139A167B NC BLRCS150A180B SC BLRCS167A200B SC BLRCS200A240B SC BLRCS208A250B SC BLRCS222A266B SC BLRCS250A300B VC BLRCS277A332B40 22

31 VarplusCan SDuty Rated Voltage 440 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) DC BLRCS030A036B HC BLRCS050A060B HC BLRCS075A090B LC BLRCS100A120B NC BLRCS125A150B NC BLRCS143A172B NC BLRCS150A180B SC BLRCS169A203B SC BLRCS182A218B SC BLRCS200A240B SC BLRCS250A300B SC BLRCS268A322B SC BLRCS285A342B SC BLRCS303A364B SC BLRCS225A270B SC BLRCS250A300B SC BLRCS285A342B SC BLRCS303A364B44 Rated Voltage 480 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) DC BLRCS042A050B HC BLRCS052A063B HC BLRCS067A080B HC BLRCS075A090B LC BLRCS088A106B MC BLRCS104A125B MC BLRCS113A136B NC BLRCS125A150B NC BLRCS144A173B NC BLRCS155A186B NC BLRCS170A204B SC BLRCS186A223B SC BLRCS208A250B SC BLRCS258A310B VC BLRCS288A346B VC BLRCS315A378B XC BLRCS339A407B48 Rated Voltage 525 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) HC BLRCS050A060B MC BLRCS106A127B NC BLRCS125A150B NC BLRCS154A185B SC BLRCS185A222B SC BLRCS200A240B SC BLRCS250A300B SC BLRCS275A330B52 23

32 Low Voltage Capacitors VarplusCan HDuty group of 3caps_r.eps A safe, reliable and high-performance solution for power factor correction in heavy-duty operating conditions. VarplusCan HDuty Operating conditions For networks with insignificant non-linear loads: (N LL < 20 %). Significant voltage disturbances. Standard operating temperature up to 55 C. Normal switching frequency up to /year. Maximum current (including harmonics) is 1.8 x I N. Technology Constructed internally with three single-phase capacitor elements. Each capacitor element is manufactured with metallized polypropylene film as the dielectric, having features such as heavy edge, slope metallization and wave-cut profile to ensure increased current handling capacity and reduced temperature rise. The active capacitor elements are coated with specially formulated sticky resin which ensures high overload capabilities and good thermal and mechanical properties The unique finger-proof CLAMPTITE termination is fully integrated with discharge resistors, allowing suitable access for tightening and ensuring cable termination without any loose connections. For lower ratings, double fast-on terminals with wires are provided. Benefits Slope metalised wavecut film reduce connect density, hence better current handling. Dry type sticky resin improves mechanical stability and cooling. Total safety: self-healing pressure-sensitive disconnector discharge resistor. Long life expectancy (up to 130,000 hours). Installation in any position. Optimized geometric design for improved thermal performance. Special resistivity and metallisation profile will enhance life and will give higher thermal efficiency with lower temperature rise. Unique finger-proof termination that ensures tightening for CLAMPITE terminals. 24

33 VarplusCan HDuty Technical specifications General characteristics Standards IEC /-2 Voltage range Frequency Power range Losses (dielectric) Losses (total) 230 to 830 V 50 / 60 Hz 1 to 50 kvar < 0.2 W / kvar < 0.5 W / kvar Capacitance tolerance -5 %, +10 % Voltage test Between terminals 2.15 x U N (AC), 10 s Discharge resistor Between terminal & container Impulse voltage Working conditions Ambient temperature -25 / 55 C (Class D) 525 V: 3 kv (AC), 10 s or 3.66 kv (AC), 2 s > 525 V: 3.66 kv (AC), 10 s or 4.4 kv (AC), 2 s 690 V: 8 kv > 690 V: 12 kv Fitted, standard discharge time 60 s Humidity 95 % Altitude 2,000 m above sea level Overvoltage 1.1 x U N 8 h in every 24 h Overcurrent Up to 1.8 x I N Peak inrush current 250 x I N Switching operations (max.) Up to 7,000 switching operations per year Mean Life expectancy Up to 130,000 hrs Harmonic content withstand N LL 20 % Installation characteristics Mounting position Indoor, upright & horizontal Fastening Earthing Terminals Threaded M12 stud at the bottom CLAMPTITE - three-way terminal with electric shock protection (finger-proof) & double fast-on terminal in lower kvar Safety features Safety Self-healing + Pressure-sensitive disconnector + Discharge device Protection Construction Casing Dielectric Impregnation IP20 Extruded Aluminium Can Metallized polypropylene film with Zn/Al alloy. Special resistivity & profile, special edge (wave-cut) Non-PCB, PUR sticky resin (Dry) 25

34 Low Voltage Capacitors VarplusCan HDuty Rated Voltage 240/260 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) 230 V 240 V 260 V at 260 V 230 V 240 V 260 V at 260 V HC BLRCH021A025B HC BLRCH027A033B HC BLRCH042A050B LC BLRCH054A065B RC BLRCH063A075B RC BLRCH083A100B TC BLRCH109A130B TC BLRCH117A140B TC BLRCH131A157B24 Rated Voltage 380/400/415 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) 380 V 400 V 415 V at 400 V 380 V 400 V 415 V at 400 V DC BLRCH025A030B DC BLRCH030A036B HC BLRCH050A060B HC BLRCH063A075B LC BLRCH075A090B LC BLRCH083A100B RC BLRCH104A125B RC BLRCH125A150B RC BLRCH150A180B TC BLRCH167A200B TC BLRCH200A240B TC BLRCH208A250B TC BLRCH250A300B VC BLRCH300A360B VC BLRCH333A400B YC BLRCH400A480B YC BLRCH417A500B YC BLRCH500A000B40 Rated Voltage 440 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) HC BLRCH050A060B LC BLRCH075A090B RC BLRCH100A120B RC BLRCH125A150B RC BLRCH143A172B RC BLRCH150A180B TC BLRCH169A203B TC BLRCH182A218B TC BLRCH200A240B TC BLRCH238A286B TC BLRCH250A300B VC BLRCH285A342B VC BLRCH303A000B VC BLRCH315A378B VC BLRCH335A401B YC BLRCH400A480B YC BLRCH476A571B YC BLRCH500A000B YC BLRCH571A000B44 26

35 VarplusCan HDuty Rated Voltage 480 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) HC BLRCH042A050B HC BLRCH050A060B LC BLRCH075A090B LC BLRCH088A106B RC BLRCH104A125B RC BLRCH113A136B RC BLRCH125A150B RC BLRCH136A163B RC BLRCH144A173B RC BLRCH155A186B TC BLRCH170A204B TC BLRCH180A216B TC BLRCH192A230B TC BLRCH208A250B TC BLRCH227A272B TC BLRCH258A310B VC BLRCH288A346B VC BLRCH315A378B XC BLRCH339A407B48 Rated Voltage 525 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) HC BLRCH050A060B HC BLRCH080A096B MC BLRCH100A120B RC BLRCH106A127B RC BLRCH125A150B RC BLRCH135A162B RC BLRCH150A180B RC BLRCH154A185B RC BLRCH172A206B TC BLRCH185A222B TC BLRCH200A240B TC BLRCH250A300B TC BLRCH275A331B VC BLRCH309A371B VC BLRCH344A413B VC BLRCH377A452B XC BLRCH400A480B52 Rated Voltage 575 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) LC BLRCH060A072B RC BLRCH120A144B TC BLRCH150A180B VC BLRCH292A350B57 27

36 Low Voltage Capacitors VarplusCan HDuty Rated Voltage 600 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) RC BLRCH083A100B TC BLRCH104A125B TC BLRCH125A150B VC BLRCH167A200B VC BLRCH208A250B60 Rated Voltage 690 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) MC BLRCH055A066B RC BLRCH100A120B RC BLRCH111A133B RC BLRCH125A150B TC BLRCH138A165B TC BLRCH150A180B TC BLRCH200A240B VC BLRCH250A300B VC BLRCH276A331B VC BLRCH300A360B YC BLRCH400A480B YC BLRCH520A624B69 Rated Voltage 830 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) VC BLRCH171A205B83 Available in star connection 28

37 VarplusCan SDuty harmonic applications PE90154.eps This harmonic rated range of capacitors is dedicated to applications where a high number of non-linear loads are present. These capacitors are designed for use with detuned reactors, based on the Standard Duty technology. PE90131.eps Operating conditions For networks with a large number of non-linear loads (N LL < 50 %). Significant voltage disturbances. Significant switching frequency up to /year. Rated voltage In a detuned filter application, the voltage across the capacitors is higher than the network service voltage (U S ). Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents are absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents. Detuned reactor + VarplusCan SDuty The rated voltage of VarplusCan SDuty capacitors is given in the table below, for different values of network service voltage and relative impedance. Capacitor Rated Voltage U N (V) Relative Impedance (%) Network Service Voltage U S (V) 50 Hz 60 Hz In the following pages, the effective power given in the tables is the reactive power provided by the combination of capacitors and reactors. 29

38 Low Voltage Capacitors VarplusCan SDuty + Detuned Reactor + Contactor PE90154_L28_r.eps Network 400 V, 50 Hz Capacitor Voltage 480 V 5.7 % / 7 % Filter Effective Capacitor Ref. 5.7 % 7 % Capacitor Duty Power at 480 V (210 Hz) (190 Hz) Contactor Ref. R Ref R Ref. Power Contactor Ref BLRCS088A106B48 x 1 LVR05065A40T x 1 LVR07065A40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS170A204B48 x 1 LVR05125A40T x 1 LVR07125A40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS339A407B48 x 1 LVR05250A40T x 1 LVR07250A40T x 1 LC1-DMK11M7 x 1 LC1D32 x BLRCS339A407B48 x 2 LVR05500A40T x 1 LVR07500A40T x 1 LC1-DWK12M7 x 1 LC1D80 x BLRCS339A407B48 x 4 LVR05X00A40T x 1 LVR07X00A40T x 1 - LC1D115 x 1 PE90131_L28_r.eps Network 400 V, 50 Hz Capacitor Voltage 480 V 14 % Filter Effective Capacitor Ref. 14 % (135 Hz) Capacitor Duty Power at Contactor Ref. R Ref 480 V Power Contactor Ref BLRCS088A106B48 x 1 LVR14065A40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS155A186B48 x 1 LVR14125A40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS315A378B48 x 1 LVR14250A40T x 1 LC1-DLK11M7 x 1 LC1D25 x BLRCS315A378B48 x 2 LVR14500A40T x 1 LC1-DTK12M7 x 1 LC1D50 x BLRCS315A378B48 x 4 LVR14X00A40T x 1 - LC1D115 x 1 PE90158_L20_r.eps Network 400 V, 50 Hz Capacitor Voltage 525 V 5.7 % / 7 % Filter Effective Capacitor Ref. 5.7 % 7 % Capacitor Duty Power at 525 V (210 Hz) (190 Hz) Contactor Ref. R Ref. R Ref. Power Contactor Ref BLRCS106A127B52 x 1 LVR05065A40T x 1 LVR07065A40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS200A240B52 x 1 LVR05125A40T x 1 LVR07125A40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS200A240B52 x 2 LVR05250A40T x 1 LVR07250A40T x 1 LC1-DMK11M7 x 1 LC1D32 x BLRCS275A330B52 x 3 LVR05500A40T x 1 LVR07500A40T x 1 LC1-DWK12M7 x 1 LC1D80 x BLRCS275A330B52 x 6 LVR05X00A40T x 1 LVR07X00A40T x 1 - LC1D115 x 1 Contactor LC1DPK. Network 400 V, 50 Hz Capacitor Voltage 525 V 14 % Filter Effective Capacitor Ref. 14 % (135 Hz) Capacitor Duty Power at Contactor Ref. 525 V R Ref. Power Contactor Ref BLRCS106A127B52 x 1 LVR14065A40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS185A222B52 x 1 LVR14125A40T x 1 LC1-DGK11M7 x 1 LC1D12 x BLRCS185A222B52 x 2 LVR14250A40T x 1 LC1-DLK11M7 x 1 LC1D25 x BLRCS250A300B52 x 3 LVR14500A40T x 1 LC1-DTK12M7 x 1 LC1D50 x BLRCS250A300B52 x 6 LVR14X00A40T x 1 - LC1D115 x 1 30

39 VarplusCan SDuty + Detuned Reactor + Contactor PE90154_L28_r.eps Network 400 V, 60 Hz Capacitor Voltage 480 V 5.7 % / 7 % Filter Effective Capacitor Ref. 5.7 % 7 % Capacitor Duty Power at 480 V (250 Hz) R Ref (230 Hz) R Ref Contactor Ref. Power Contactor Ref BLRCS075A090B48 x 1 LVR05065B40T x 1 LVR07065B40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS113A136B48 x 1 LVR05100B40T x 1 LVR07100B40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS144A173B48 x 1 LVR05125B40T x 1 LVR07125B40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCS288A346B48 x 1 LVR05250B40T x 1 LVR07250B40T x 1 LC1-DMK11M7 x 1 LC1D32 x BLRCS288A346B48 x 2 LVR05500B40T x 1 LVR07500B40T x 1 LC1-DWK12M7 x 1 LC1D80 x BLRCS339A407B48 x 4 LVR05X00B40T x 1 LVR07X00B40T x 1 - LC1D115 x 1 PE90131_L28_r.eps Network 400 V, 60 Hz Capacitor Voltage 480 V 14 % Filter Effective Capacitor Ref. 14 % (135 Hz) Capacitor Duty Power at Contactor Ref. 480 V R Ref. Power Contactor Ref BLRCS067A080B48 x 1 LVR14065B40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRCS104A125B48 x 1 LVR14010B40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRCS144A173B48 x 1 LVR14125B40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRCS258A310B48 x 1 LVR14250B40T x 1 LC1-DLK11M7 x1 LC1D25 x BLRCS258A310B48 x 2 LVR14500B40T x 1 LC1-DTK12M7 x1 LC1D50 x BLRCS258A310B48 x 4 LVR14X00B40T x 1 - LC1D115 x 1 PE90158_L20_r.eps Contactor LC1DPK. 31

40 Low Voltage Capacitors VarplusCan HDuty harmonic applications PE90154.eps This harmonic rated range of capacitors is dedicated to applications where a high number of non-linear loads are present. These capacitors are designed for use with detuned reactors, based on the Standard Heavy technology. PE90131.eps Operating conditions For networks with a large number of non-linear loads (N LL < 50 %). Significant voltage disturbances. Significant switching frequency up to /year. Rated voltage In a detuned filter application, the voltage across the capacitors is higher than the network service voltage (U S ). Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents are absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents. Detuned reactor + VarplusCan HDuty The rated voltage of VarplusCan HDuty capacitors is given in the table below, for different values of network service voltage and relative impedance. Capacitor Rated Voltage U N (V) Network Service Voltage U S (V) 50 Hz 60 Hz Relative Impedance 5.7 (%) In the following pages, the effective power given in the tables is the reactive power provided by the combination of capacitors and reactors. 32

41 VarplusCan HDuty + Detuned Reactor + Contactor PE90154_L28_r.eps Network 400 V, 50 Hz Capacitor Voltage 480 V 5.7 % / 7 % Filter Effective Capacitor Ref. 5.7 % 7 % Capacitor Duty Power at 480 V (210 Hz) R Ref (190 Hz) R Ref Contactor Ref. Power Contactor Ref BLRCH088A106B48 x 1 LVR05065A40T x1 LVR07065A40T x1 LC1-DFK11M7 1 LC1D12 x BLRCH170A204B48 x 1 LVR05125A40T x1 LVR07125A40T x 1 LC1-DFK11M7 1 LC1D12 x BLRCH339A407B48 x 1 LVR05250A40T x1 LVR07250A40T x1 LC1-DMK11M7 1 LC1D32 x BLRCH339A407B48 x 2 LVR05500A40T x1 LVR07500A40T x1 LC1-DWK12M7 1 LC1D80 x BLRCH339A407B48 x 4 LVR05X00A40T x1 LVR07X00A40T x1 - LC1D115 x 1 PE90131_L28_r.eps Network 400 V, 50 Hz Capacitor Voltage 480 V 14 % Filter Effective Capacitor Ref. 14 % (135 Hz) Capacitor Duty Power at Contactor Ref. 480 V R Ref. Power Contactor Ref BLRCH088A106B48 x 1 LVR14065A40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRCH155A186B48 x 1 LVR14125A40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRCH315A378B48 x 1 LVR14250A40T x 1 LC1-DLK11M7 x1 LC1D25 x BLRCH315A378B48 x 2 LVR14500A40T x 1 LC1-DTK12M7 x1 LC1D50 x BLRCH315A378B48 x 4 LVR14X00A40T x 1 - LC1D115 x 1 Network 400 V, 50 Hz Capacitor Voltage 525 V 5.7 % / 7 % Filter Effective Capacitor Ref. 5.7 % 7 % Capacitor Duty Power at 525 V (210 Hz) R Ref (190 Hz) R Ref Contactor Ref. Power Contactor Ref BLRCH106A127B52 x 1 LVR05065A40T x 1 LVR07065A40T x 1 LC1-DFK11M7 1 LC1D12 x BLRCH200A240B52 x 1 LVR05125A40T x 1 LVR07125A40T x 1 LC1-DFK11M7 1 LC1D12 x BLRCH400A480B52 x 1 LVR05250A40T x 1 LVR07250A40T x 1 LC1-DMK11M7 1 LC1D32 x BLRCH400A480B52 x 2 LVR05500A40T x 1 LVR07500A40T x 1 LC1-DWK12M7 1 LC1D80 x BLRCH400A480B52 x 4 LVR05X00A40T x 1 LVR07X00A40T x 1 - LC1D115 x 1 PE90158_L20_r.eps Network 400 V, 50 Hz Capacitor Voltage 525 V 14 % Filter Effective Capacitor Ref. 14 % (135 Hz) Capacitor Duty Power at 525 V R Ref. Contactor Ref. Power Contactor Ref BLRCH106A127B52 x 1 LVR14065A40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCH185A222B52 x 1 LVR14125A40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCH377A452B52 x 1 LVR14250A40T x 1 LC1-DLK11M7 x 1 LC1D25 x BLRCH377A452B52 x 2 LVR14500A40T x 1 LC1-DTK12M7 x 1 LC1D50 x BLRCH377A452B52 x 4 LVR14X00A40T x 1 - LC1D115 x 1 Network 690 V, 50 Hz Capacitor Voltage 830 V 5.7 % / 7 % Filter Effective Capacitor Ref. 5.7 % 7 % Capacitor Duty Power at 830 V (210 Hz) R Ref (190 Hz) R Ref Contactor Ref. Power Contactor Ref BLRCH171A205B83 x 1 LVR05125A69T x 1 LVR07125A69T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCH171A205B83 x 2 LVR05250A69T x 1 LVR07250A69T x 1 LC1-DLK11M7 x 1 LC1D25 x BLRCH171A205B83 x 4 LVR05500A69T x 1 LVR07500A69T x 1 LC1-DTK12M7 x 1 LC1D50 x BLRCH171A205B83 x 8 LVR05X00A69T x 1 LVR07X00A69T x 1 LC1-DWK12M7 x 1 LC1D80 x 1 33

42 Low Voltage Capacitors VarplusCan HDuty + Detuned Reactor + Contactor PE90154_L28_r.eps Network 400 V, 60 Hz Capacitor Voltage 480 V 5.7 % / 7 % Filter Effective Capacitor Ref. 5.7 % 7 % Capacitor Duty Power at 480 V (250 Hz) R Ref (230 Hz) R Ref Contactor Ref. Power Contactor Ref BLRCH075A090B48 x 1 LVR05065B40T x 1 LVR07065B40T x 1 LC1-DFK11M7 1 LC1D12 x BLRCH113A136B48 x 1 LVR05100B40T x 1 LVR07100B40T x 1 LC1-DFK11M7 1 LC1D12 x BLRCH144A173B48 x 1 LVR05125B40T x 1 LVR07125B40T x 1 LC1-DFK11M7 1 LC1D12 x BLRCH288A346B48 x 1 LVR05250B40T x 1 LVR07250B40T x 1 LC1-DMK11M7 1 LC1D32 x BLRCH288A346B48 x 2 LVR05500B40T x 1 LVR07500B40T x 1 LC1-DWK12M7 1 LC1D80 x BLRCH288A346B48 x 4 LVR05X00B40T x 1 LVR07X00B40T x 1 - LC1D115 x 1 PE90131_L28_r.eps Network 400 V, 60 Hz Capacitor Voltage 480 V 14 % Filter Effective Capacitor Ref. 14 % (160 Hz) Capacitor Duty Power at Contactor Ref. 480 V R Ref. Power Contactor Ref BLRCH075A090B48 x 1 LVR14065B40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRCH104A125B48 x 1 LVR14010B40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRCH136A163B48 x 1 LVR14125B40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRCH258A310B48 x 1 LVR14250B40T x 1 LC1-DLK11M7 x1 LC1D25 x BLRCH258A310B48 x 2 LVR14500B40T x 1 LC1-DTK12M7 x1 LC1D50 x BLRCH258A310B48 x 4 LVR14X00B40T x 1 - LC1D115 x 1 PE90158_L20_r.eps Network 480 V, 60 Hz Capacitor Voltage 575 V 5.7 % Filter Effective Capacitor Ref. 5.7 % (250 Hz) Capacitor Duty Power at R Ref. Contactor Ref. 575 V Power Contactor Ref BLRCH150A180B57 x 1 LVR05125B48T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCH292A350B57 x 1 LVR05250B48T x 1 LC1-DLK11M7 x 1 LC1D25 x BLRCH292A350B57 x 2 LVR05500B48T x 1 LC1-DTK12M7 x 1 LC1D50 x BLRCH292A350B57 x 4 LVR05X00B48T x 1 - LC1D115 x 1 Network 600 V, 60 Hz Capacitor Voltage 690 V 5.7 % Filter Effective Capacitor Ref. 5.7 % (250 Hz) Capacitor Duty Power Power at R Ref. Contactor Ref. Contactor 690 V Ref. Contactor LC1DPK BLRCH138A165B69 x 1 LVR05125B60T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRCH276A331B69 x 1 LVR05250B60T x 1 LC1-DLK11M7 x 1 LC1D25 x BLRCH276A331B69 x 2 LVR05500B60T x 1 LC1-DTK12M7 x 1 LC1D50 x BLRCH276A331B69 x 4 LVR05X00B60T x 1 - LC1D115 x 1 34

43 VarplusCan mechanical characteristics VPCDC,HC &LC_r.eps d 1 TS TH a h 2 h 2 + t Termination cable (300 mm length) FAST-ON Terminal 6.35 x 0.8 Toothed washer Hex nut Case Code: DC, HC & LC Creepage distance Clearance Expansion (a) Mounting details (for M10/M12 mounting stud) Torque Toothed washer Hex nut Terminal assembly Ht. (t) min.16 mm min.16 mm max.10 mm M10: 7 N.m M12: 10 N.m M10/M12 M10/M12 50 mm Size (d) TS TH Ø 50 M10 10 mm VarplusCan DC, EC, FC, HC & LC. Ø 63 M12 13 mm Ø 70 M12 16 mm Case code Diameter d (mm) Height h (mm) Height h + t (mm) DC EC FC HC LC Weight (kg) VPC MC, NC, RC & SC_r.eps d d 1 M12 h 3 h 3 + a (expansion) (t) h 3 + t VarplusCan MC, NC, RC & SC. Finger proof CLAMPTITE terminal In-built resistor type Toothed washer Hex nut Tightening Torque = 2.5 Nm Case Code: MC, NC, RC & SC Creepage distance Clearance Expansion (a) Mounting details (for M12 mounting stud) min.13 mm min.13 mm max.12 mm Torque T = 10 Nm Toothed washer J12.5 DIN 6797 Hex nut BM12 DIN 439 Terminal screw M5 Terminal assembly Ht. (t) Case code Diameter d (mm) Height h (mm) Height h + t (mm) MC NC RC SC mm Weight (kg) 35

44 VPCTC,UC &VC_r.eps d d M12 M 2 h 3 h 3 + a (expansion) (t) h 3 + t Finger proof CLAMPTITE terminal In-built resistor type Toothed washer Hex nut Case Code: TC, UC & VC Creepage distance Clearance Expansion (a) Mounting details (for M12 mounting stud) min.13 mm min.13 mm max.12 mm Torque T = 10 Nm Toothed washer J12.5 DIN 6797 Hex nut BM12 DIN 439 Terminal screw M5 Terminal assembly Ht. (t) 30 mm Tightening Torque = 2.5 Nm Case code Diameter d (mm) Height h (mm) Height h + t (mm) TC UC VC Weight (kg) VarplusCan TC, UC & VC. VPC XC, YC_r.eps d M10 t 2 STUD type terminal In-built resistor type Case Code: XC & YC Creepage distance Clearance Expansion (a) min.13 mm 34 mm max.12 mm d 1 h 3 h 3 + a (expansion) h 3 + t Mounting details (for M12 mounting stud) Torque T = 10 Nm Toothed washer J12.5 DIN 6797 Hex nut BM12 DIN 439 Terminal screw M10 Terminal assembly Ht. (t) 43 mm M12 Toothed washer Hex nut Case code Diameter d (mm) Height h (mm) Height h + t (mm) XC YC Weight (kg) Tightening Torque = 12 N.m 47 1 VarplusCan XC & YC. 36

45 Low Voltage Capacitors VarplusBox capacitor PE90135_r.eps VarplusBox capacitors deliver reliable performance in the most severe application conditions, in Fixed & Automatic PFC systems, in networks with frequently switched loads and harmonic disturbances. Main features Robustness Double metallic protection. Mechanically well suited for stand-alone installations. Safety Its unique safety feature electrically disconnects the capacitors safely at the end of their useful life. The disconnectors are installed on each phase, which makes the capacitors very safe, in addition to the protective steel enclosure. Flexibility These capacitors can be easily mounted inside panels or in a stand-alone configuration. Suitable for flexible bank configuration. VarplusBox. For professionnals Metal box enclosure. High power ratings up to 100 kvar. Easy repair and maintenance. Up to 70 C temperature. High inrush current withstand up to 400 x I N. Stand-alone PFC equipment. Direct connection to a machine, in harsh environmental conditions. 37

46 VarplusBox capacitor PE90135 PE90134 HDuty Energy Construction Steel sheet enclosure Voltage range 230 V V 400 V V Power range 5-60 kvar kvar (three-phase) Peak inrush Up to 250 x I N Up to 350 x I N current Overvoltage 1.1 x U N 8 h every 24 h Overcurrent 1.8 x I N 2.5 x I N Mean life expectancy Up to 130,000 h Up to 160,000 h Safety Self-healing + pressure-sensitive disconnector + discharge device (50 V/1 min) Dielectric Metallized Polypropylene film with Zn/Al alloy with special profile metallization and wave cut Double metallized paper + Polypropylene film Impregnation Non-PCB, sticky (dry) Non-PCB, oil Biodegradable resin Ambient min. -25 C max 55 C min. -25 C max 70 C temperature Protection IP20 Indoor Mounting Upright Terminals Bushing terminals designed for large cable termination 38

47 VarplusBox HDuty PE90137 A safe, reliable and high-performance solution for power factor correction in standard operating conditions. Operating conditions For networks with significant non-linear loads (N LL 20 %). Standard voltage disturbances. Standard operating temperature up to 55 C. Significant number of switching operations up to 7,000/year. Long life expectancy up to 130,000 hours. Technology Constructed internally with three single-phase capacitor elements. The design is specially adapted for mechanical stability. The enclosures of the units are designed to ensure that the capacitors operate reliably in hot and humid tropical conditions, without the need of any additional ventilation louvres (see technical specifications). Special attention is paid to equalization of temperatures within the capacitor enclosures since this gives better overall performance. VarplusBox HDuty PE90135 Benefits High performance: heavy edge metallization/wave-cut edge to ensure high inrush current capabilities special resistivity and profile metallization for better self-healing & enhanced life. Safety: its unique safety feature electrically disconnects the capacitors safely at the end of their useful life the disconnectors are installed on each phase, which makes the capacitors very safe, in addition to its protective steel enclosure. 39

48 Low Voltage Capacitors VarplusBox HDuty Technical specifications General characteristics Standards IEC /-2 Voltage range Frequency Power range Losses (dielectric) Losses (total) 400 to 830 V 50 / 60 Hz 5 to 60 kvar < 0.2 W / kvar < 0.5 W / kvar Capacitance tolerance -5 %, +10 % Voltage test Between terminals 2.15 x U N (AC), 10 s Discharge resistor Between terminal & container Impulse voltage Working conditions Ambient temperature -25 / 55 C (Class D) 525 V: 3 kv (AC), 10 s or 3.66 kv (AC), 2 s > 525 V: 3.66 kv (AC), 10 s or 4.4 kv (AC), 2 s 690 V: 8 kv > 690 V: 12 kv Fitted, standard discharge time 60 s Humidity 95 % Altitude 2,000 m above sea level Overvoltage 1.1 x U N 8h in every 24 h Overcurrent Up to 1.8 x I N Peak inrush current 250 x I N Switching operations (max.) Up to 7,000 switching operations per year Mean Life expectancy Up to 130,000 hrs Harmonic content withstand N LL 20 % Installation characteristics Mounting position Indoor, upright Fastening Earthing Terminals Safety features Safety Protection Construction Casing Dielectric Impregnation Mounting cleats Bushing terminals designed for large cable termination Self-healing + Pressure-sensitive disconnector for each phase + Discharge device IP20 Sheet steel enclosure Metallized polypropylene film with Zn/Al alloy. special resistivity & profile. Special edge (wave-cut) Non-PCB, PUR sticky resin (Dry) 40

49 VarplusBox HDuty Rated Voltage 380/400/415 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) 380 V 400 V 415 V at 400 V 380 V 400 V 415 V at 400 V AB BLRBH025A030B AB BLRBH050A060B AB BLRBH075A090B AB BLRBH083A100B AB BLRBH104A125B AB BLRBH125A150B GB BLRBH151A181B GB BLRBH201A241B GB BLRBH208A250B GB BLRBH250A300B IB BLRBH417A500B IB BLRBH500A000B40 Rated Voltage 440 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) AB BLRBH100A120B AB BLRBH125A150B GB BLRBH250A300B IB BLRBH500A000B44 Rated Voltage 480 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) AB BLRBH083A100B AB BLRBH088A106B AB BLRBH104A125B AB BLRBH125A150B GB BLRBH156A187B GB BLRBH171A205B GB BLRBH193A231B GB BLRBH208A250B GB BLRBH216A259B GB BLRBH227A272B GB BLRBH258A310B GB BLRBH288A346B GB BLRBH315A378B GB BLRBH339A407B IB BLRBH417A500B IB BLRBH516A619B IB BLRBH566A679B IB BLRBH619A000B48 41

50 Low Voltage Capacitors VarplusBox HDuty Rated Voltage 525 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) AB BLRBH100A120B AB BLRBH125A150B GB BLRBH166A199B GB BLRBH201A241B GB BLRBH250A300B IB BLRBH400A480B IB BLRBH500A600B52 Rated Voltage 600 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) AB BLRBH042A050B AB BLRBH083A100B AB BLRBH104A125B AB BLRBH125A150B GB BLRBH167A200B GB BLRBH208A250B JB BLRBH417A500B KB BLRBH625A750B LB BLRBH833AX00B60 Rated Voltage 690 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) AB BLRBH138A165B GB BLRBH151A181B GB BLRBH200A240B GB BLRBH276A331B69 Rated Voltage 830 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) GB BLRBH341A409B83 42

51 VarplusBox Energy A safe, reliable and high-performance solution for power factor correction in extreme operating conditions. Operating conditions For networks with significant non-linear loads: (N LL < 25 %). Severe voltage disturbances. Highest operating temperature (up to 70 C). High switching frequency, up to 10,000/year Maximum current withstand 2.5 x I n. PE90135 PE90134 Technology Special technology of double metalized paper impregnated in oil to provide extra long life for your capacitor needs in worst environments. Constructed internally with three single-phase capacitor elements. The design is specially adapted for mechanical stability. The enclosures of the units are designed to ensure that the capacitors operate reliably in hot and humid tropical conditions, without the need of any additional ventilation louvres (see technical specifications). VarplusBox Energy Energy capacitors are the only technology which is capable of giving the longest life, highest overload limits and the highest operating ambient temperature due to use of the combination of polypropylene film and metallized paper. Benefits High performance: high life expectancy up to 160,000 hours very high overload capabilities and good thermal and mechanical properties highest operating temperature (up to 70 C). Safety: its unique safety feature electrically disconnects the capacitors safely at the end of their useful life; the disconnectors are installed on each phase, which makes the capacitors very safe, in addition to its protective steel enclosure. 43

52 Low Voltage Capacitors VarplusBox Energy Technical specifications General characteristics Standards IEC /-2 Voltage range Frequency Power range Losses (dielectric) Losses (total) 400 to 525 V 50 / 60 Hz 10 to 60 kvar < 0.2 W / kvar < 0.5 W / kvar Capacitance tolerance -5 %, +10 % Voltage test Between terminals 2.15 x U N (AC), 10 s Between terminal & container Impulse voltage Discharge resistor 3 kv (AC), 10 s or 3.66 kv (AC), 2 s 8 kv Fitted, standard discharge time 60 s Working conditions Ambient temperature -25 / 70 C (Class D) Humidity 95 % Altitude 2,000 m above sea level Overvoltage 1.1 x U N 8 h in every 24 h Overcurrent Up to 2.5 x I N Peak inrush current 350 x I N Switching operations (max.) Up to 10,000 switching operations per year Mean Life expectancy Up to 160,000 hrs Harmonic content withstand N LL 25 % Installation characteristics Mounting position Indoor & upright Fastening Earthing Terminals Safety features Safety Protection Construction Casing Dielectric Impregnation Mounting cleats Bushing terminals designed for large cable termination Self-healing + Pressure-sensitive disconnector for each phase + Discharge device IP20 Sheet steel enclosure Double metallized paper + polypropylene film Non-PCB, oil 44

53 VarplusBox Energy Rated Voltage 380/400/415 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) 380 V 400 V 415 V at 400 V 380 V 400 V 415 V at 400 V DB BLRBE083A100B DB BLRBE104A125B GB BLRBE125A150B GB BLRBE150A180B GB BLRBE167A200B GB BLRBE208A250B GB BLRBE250A300B IB BLRBE417A500B IB BLRBE500A600B40 Rated Voltage 440 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) DB BLRBE100A120B DB BLRBE125A150B GB BLRBE150A180B GB BLRBE200A240B GB BLRBE250A300B IB BLRBE500A600B44 Rated Voltage 480 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) DB BLRBE088A106B DB BLRBE104A125B DB BLRBE113A136B FB BLRBE125A150B FB BLRBE136A163B GB BLRBE155A186B GB BLRBE170A204B GB BLRBE208A250B GB BLRBE258A310B GB BLRBE288A346B IB BLRBE315A378B IB BLRBE339A407B IB BLRBE417A500B48 Rated Voltage 525 V 50 Hz 60 Hz µf (X3) Case Code Reference Number I N (A) I N (A) DB BLRBE100A120B FB BLRBE125A150B FB BLRBE154A185B GB BLRBE200A240B GB BLRBE250A300B IB BLRBE500A600B52 45

54 Low Voltage Capacitors VarplusBox HDuty harmonic applications This harmonic rated range of capacitors is dedicated to applications where a high number of non-linear loads are present (N LL up to 30 %). These capacitors are designed for use with detuned reactors, based on the Heavy Duty technology. Operating conditions For networks with a large number of non-linear loads (N LL < 50 %). Significant voltage disturbances. Very frequent switching operations, up to 7,000/year. PE90154+PE90134_r.eps Rated voltage In a detuned filter application, the voltage across the capacitors is higher than the network service voltage (U S ). Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents is absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents. The rated voltage of VarplusBox HDuty capacitors is given in the table below, for different values of network service voltage and relative impedance. Detuned reactor VarplusBox HDuty Capacitor Rated Voltage U N (V) Network Service Voltage U s (V) 50 Hz 60 Hz Relative Impedance 5.7 (%) In the following pages, the effective power given in the tables is the reactive power provided by the combination of capacitors and reactors. 46

55 VarplusBox HDuty + Detuned Reactor + Contactor PE90154_L28_r.eps Network 400 V, 50 Hz Capacitor Voltage 480 V 5.7 % / 7 % Detuned Reactor Effective Capacitor Ref. 5.7 % 7 % Capacitor Duty Power Power at 480 V (210 Hz) R Ref (190 Hz) R Ref Contactor Ref. Contactor Ref BLRBH171A205B48 x 1 LVR05125A40T x 1 LVR07125A40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRBH339A407B48 x 1 LVR05250A40T x 1 LVR07250A40T x 1 LC1-DMK11M7 x1 LC1D32 x BLRBH339A407B48 x 2 LVR05500A40T x 1 LVR07500A40T x 1 LC1-DWK12M7 x 1 LC1D80 x BLRBH339A407B48 x 4 LVR05X00A40T x 1 LVR07X00A40T x 1 - LC1D115 x 1 PE90134_L28_r.eps Network 400 V, 50 Hz Capacitor Voltage 480 V 14 % Detuned Reactor Effective Power at 480 V Capacitor Ref. 14 % (135 Hz) R Ref. Capacitor Duty Contactor Ref. Power Contactor Ref BLRBH156A187B48 x 1 LVR14125A40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRBH315A378B48 x 1 LVR14250A40T x 1 LC1-DLK11M7 x1 LC1D25 x BLRBH619A000B48 x 1 LVR14500A40T x 1 LC1-DTK12M7 x1 LC1D50 x BLRBH619A000B48 x 2 LVR14X00A40T x 1 - LC1D115 x 1 Network 690 V, 50 Hz Capacitor Voltage 830 V 5.7 % / 7 % Filter Effective Power at 830 V Capacitor Ref. 5.7 % (210 Hz) R Ref 7 % (190 Hz) R Ref Capacitor Duty Contactor Ref. Power Contactor Ref BLRBH341A409B83 x 1 LVR05250A69T x 1 LVR07250A69T x1 LC1-DLK11M7 x 1 LC1D25 x BLRBH341A409B83 x 2 LVR05500A69T x 1 LVR07500A69T x1 LC1-DTK12M7 x 1 LC1D50 x BLRBH341A409B83 x 4 LVR05X00A69T x 1 LVR07X00A69T x1 LC1-DWK12M7 x 1 LC1D80 x 1 PE90158_L20_r copy.eps Network 400 V, 60 Hz Capacitor Voltage 480 V 5.7 % / 7 % Detuned Reactor Effective Power at 480 V Capacitor Ref. 5.7 % (250 Hz) R Ref 7 % (230 Hz) R Ref Capacitor Duty Contactor Ref. Power Contactor Ref BLRBH288A346B48 1 LVR05250B40T 1 LVR07250B40T 1 LC1-DMK11M7 1 LC1D BLRBH566A679B48 1 LVR05500B40T 1 LVR07500B40T 1 LC1-DWK12M7 1 LC1D BLRBH566A679B48 2 LVR05X00B40T 1 LVR07X00B40T 1 - LC1D115 1 Network 400 V, 60 Hz Capacitor Voltage 480 V 14 % Detuned Reactor Effective Power at 480 V Capacitor Ref. 14 % (135 Hz) R Ref. Capacitor Duty Contactor Ref. Power Contactor Ref BLRBH258A310B48 1 LVR14250B40T 1 LC1-DLK11M7 1 LC1D BLRBH516A619B48 1 LVR14500B40T 1 LC1-DTK12M7 1 LC1D BLRBH516A619B48 2 LVR14X00B40T 1 - LC1D115 1 Network 600 V, 60 Hz Capacitor Voltage 690 V 5.7 % Detuned Reactor Effective Power at 690 V Capacitor Ref. 14 % (250 Hz) R Ref. Capacitor Duty Contactor Ref. Power Contactor Ref BLRBH276A331B69 1 LVR05250B60 1 LC1-DLK11M7 1 LC1D BLRBH276A331B69 2 LVR05500B60 1 LC1-DTK12M7 1 LC1D BLRBH276A331B69 4 LVR05X00B LC1D

56 VarplusBox Energy Harmonic applications This harmonic rated range of capacitors is dedicated to applications where a high number of non-linear loads are present. These capacitors are designed for use with detuned reactors, based on the Energy technology. Operating conditions For networks with a large number of non-linear loads (N LL < 50 %). Significant voltage disturbances. Severe temperature conditions up to 70 C. Very frequent switching operations up to 10,000/year. PE90154+PE90134_r.eps Rated voltage In a detuned filter application, the voltage across the capacitors is higher than the network service voltage (U S ). Then, capacitors must be designed to withstand higher voltages. Depending on the selected tuning frequency, part of the harmonic currents is absorbed by the detuned capacitor bank. Then, capacitors must be designed to withstand higher currents, combining fundamental and harmonic currents. The rated voltage of VarplusBox Energy capacitors is given in the table below, for different values of network service voltage and relative impedance. Detuned reactor VarplusBox Energy Capacitor Rated Voltage U N (V) Relative Impedance (%) Network Service Voltage U S (V) 50 Hz 60 Hz In the following pages, the effective power given in the tables is the reactive power provided by the combination of capacitors and reactors. 48

57 Low Voltage Capacitors VarplusBox Energy + Detuned Reactor + Contactor Network 400 V, 50 Hz Capacitor Voltage 480 V 5.7 % / 7 % Detuned Reactor Effective Power Capacitor Ref. 5.7 % (210 Hz) 7 % (190 Hz) at 480 V R Ref R Ref Capacitor Duty Contactor Ref. Power Contactor Ref BLRBE088A106B48 x 1 LVR05065A40T x 1 LVR07065A40T x 1 LC1-DFK11M7 1 LC1D12 x BLRBE170A204B48 x 1 LVR05125A40T x 1 LVR07125A40T x 1 LC1-DFK11M7 1 LC1D12 x BLRBE339A407B48 x 1 LVR05250A40T x 1 LVR07250A40T x 1 LC1-DMK11M7 1 LC1D32 x BLRBE339A407B48 x 2 LVR05500A40T x 1 LVR07500A40T x 1 LC1-DWK12M7 1 LC1D80 x BLRBE339A407B48 x 4 LVR05X00A40T x 1 LVR07X00A40T x 1 LC1D115 x 1 Network 400 V, 50 Hz Capacitor Voltage 480 V 14 % Detuned Reactor Effective Power at 480 V Capacitor Ref. 14 % (135 Hz) R Ref. Capacitor Duty Contactor Ref. Power Contactor Ref BLRBE088A106B48 x1 LVR14065A40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRBE155A186B48 x1 LVR14125A40T x 1 LC1-DFK11M7 x1 LC1D12 x BLRBE315A378B48 x1 LVR14250A40T x 1 LC1-DLK11M7 x1 LC1D25 x BLRBE315A378B48 x2 LVR14500A40T x 1 LC1-DTK12M7 x1 LC1D50 x BLRBE315A378B48 x4 LVR14X00A40T x 1 LC1D115 x 1 Network 400 V, 60 Hz Capacitor Voltage 480 V 5.7 % / 7 % Detuned Reactor Effective Power Capacitor Ref. 5.7 % (250 Hz) 7 % (230 Hz) at 480 V R Ref R Ref Capacitor Duty Contactor Ref. Power Contactor Ref BLRBE113A136B48 x 1 LVR05100B40T x 1 LVR07100B40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRBE155A186B48 x 1 LVR05125B40T x 1 LVR07125B40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRBE288A346B48 x 1 LVR05250B40T x 1 LVR07250B40T x 1 LC1-DMK11M7 x 1 LC1D32 x BLRBE288A346B48 x 2 LVR05500B40T x 1 LVR07500B40T x 1 LC1-DWK12M7 x 1 LC1D80 x BLRBE288A346B48 x 4 LVR05X00B40T x 1 LVR07X00B40T x 1 LC1D115 x 1 Network 400 V, 60 Hz Capacitor Voltage 480 V 14 % Detuned Reactor Effective Power at 480 V Capacitor Ref. 14 % (160 Hz) R Ref. Capacitor Duty Contactor Ref. Power Contactor Ref BLRBE104A125B48 x 1 LVR14010B40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRBE136A163B48 x 1 LVR14125B40T x 1 LC1-DFK11M7 x 1 LC1D12 x BLRBE258A310B48 x 1 LVR14250B40T x 1 LC1-DLK11M7 x 1 LC1D25 x BLRBE258A310B48 x 2 LVR14500B40T x 1 LC1-DTK12M7 x 1 LC1D50 x BLRBE258A310B48 x 4 LVR14X00B40T x 1 LC1D115 x 1 49

58 VarplusBox Mechanical characteristics Case Code: AB - VarplusBox Compact dimension Creepage distance 30 mm Clearance Phase to phase 25 mm (min.) Phase to earth 19 mm (min.) Mounting details: mounting screw M6, 2 Nos. Case code W1 (mm) W2 (mm) W3 (mm) H (mm) D (mm) Weight (kg) AB D DB eps Plastic Terminal cover H Enclosure W3 W2 W1 Plastic Terminal cover 192 Case Code: DB, EB, FB, GB & HB Creepage distance 30 mm Clearance Phase to phase 25 mm (min.) Phase to earth 19 mm (min.) Mounting details: mounting screw M6, 2 Nos. Case code W1 (mm) W2 (mm) W3 (mm) H (mm) D (mm) Weight (kg) DB EB FB GB HB D DB eps Rubber grommet for cable entry H Enclosure W3 W1 W2 50

59 Low Voltage Capacitors VarplusBox Mechanical characteristics Case Code: IB Creepage distance 30 mm Clearance Phase to phase 25 mm (min.) Phase to earth 19 mm (min.) Mounting details: mounting screw M6, 2 Nos. Case code W1 (mm) W2 (mm) W3 (mm) H (mm) D (mm) Weight (kg) IB D DB eps Rubber grommet for cable entry H Enclosure W3 W1 W2 51

60 52

61 53

62 Detuned reactors Contents Presentation Power Factor Correction guideline 3 Low Voltage capacitors 15 Detuned reactors 55 Power Factor controllers 60 Contactors 64 Appendix 68 54

63 Detuned reactors Detuned reactors PE90154.eps The detuned reactors (DR) are designed to protect the capacitors by preventing amplification of the harmonics present on the network. Operating conditions Use: indoor. Storage temperature: -40 C, +60 C. Relative humidity in operation: %. Salt spray withstand: 250 hours (for 400 V - 50 Hz range). Operating temperature: altitude: 1000 m: Min = 0 C, Max = 55 C, highest average over 1 year = 40 C, 24 hours = 50 C. altitude: 2000 m: Min = 0 C, Max = 50 C, highest average over 1 year = 35 C, 24 hours = 45 C. Installation guidelines Forced ventilation required. Vertical detuned reactor winding for better heat dissipation. As the detuned reactor is provided with thermal protection, the normally closed dry contact must be used to disconnect the step in the event of overheating. Technical specifications General characteristics Description Degree of protection Insulation class Rated voltage Three-phase, dry, magnetic circuit, impregnated IP00 H 400 to 690 V - 50 Hz 400 to 600 V - 60 Hz Other voltages on request Inductance tolerance per phase -5, +5 % Insulation level 1.1 kv Dielectric test 50/60 Hz between 4 kv, 1 min windings and windings/earth Thermal protection Restored on terminal block 250 V AC, 2 A Let s define the service current (I S ) as the current absorbed by the capacitor and detuned reactor assembly, when a purely sinusoidal voltage is applied, equal to the network service voltage (V). I S = Q / ( 3 x U S ) In order to operate safely in real conditions, a detuned reactor must be designed to accept a maximum permanent current (I MP ) taking account of harmonic currents and voltage fluctuations. The following table gives the typical percentage of harmonic currents considered for the different tuning orders. (%) Harmonic currents Tuning order i 3 i 5 i 7 i H W1 D1 W D For dimensions and more details, please consult us. A 1.1 factor is applied in order to allow long-term operation at a supply voltage up to (1.1 x U S ). The resulting maximum permanent current (I MP ) is given in the following table: Tuning order I MP (times I S )

64 50 Hz Detuned reactors Network voltage 400 V, 50 Hz Relative Impedance (%) kvar Inductance (mh) I MP (A) W (mm) W1 (mm) D (mm) D1 (mm) H (mm) Weight (kg) LVR05065A40T LVR05125A40T LVR05250A40T LVR05500A40T LVR05X00A40T LVR07065A40T LVR07125A40T LVR07250A40T LVR07500A40T LVR07X00A40T LVR14065A40T LVR14125A40T LVR14250A40T LVR14500A40T LVR14X00A40T Reference Number * Network voltage 690 V, 50 Hz Relative Impedance (%) kvar Inductance (mh) I MP (A) W (mm) W1 (mm) D (mm) D1 (mm) H (mm) Weight (kg) LVR05125A69T LVR05250A69T LVR05500A69T LVR05X00A69T LVR07125A69T LVR07250A69T LVR07500A69T LVR07X00A69T Reference Number Network voltage 230 V, 50 Hz Relative Impedance (%) kvar Inductance (mh) I MP (A) W (mm) W1 (mm) D (mm) D1 (mm) H (mm) Weight (kg) 5.70% LVR05065A23T LVR05125A23T LVR05250A23T Reference Number 56

65 60 Hz Detuned reactors Network voltage 400 V, 60 Hz 60 Hz Relative Impedance (%) kvar Inductance (mh) I MP (A) W (mm) W1 (mm) D (mm) D1 (mm) H (mm) Weight (kg) 5.70% LVR05125B40T LVR05250B40T LVR05500B40T LVR05X00B40T 7% LVR07125B40T LVR07250B40T LVR07500B40T LVR07X00B40T 14% LVR14125B40T LVR14250B40T LVR14500B40T LVR14X00B40T Reference Number Network voltage 480 V, 60 Hz 5.70% LVR05125B48T LVR05250B48T LVR05500B48T LVR05X00B48T Network voltage 600 V, 60 Hz 5.70% LVR05125B60T LVR05250B60T LVR05500B60T LVR05750B60T LVR05X00B60T LVR05X50B60T Network voltage 220 V, 60 Hz 5.70% LVR05125B22T LVR05250B22T LVR05500B22T LVR05X00B22T Network voltage 240 V, 60 Hz 5.70% LVR05125B24T LVR05250B24T LVR05500B24T 57

66 58

67 59

68 Power Factor controllers Contents Presentation Power Factor Correction guideline 3 Low Voltage capacitors 15 Detuned reactors 54 Varlogic series 61 NR6/NR12, NRC12 61 Contactors 64 Appendix 68 60

69 Power Factor controllers Varlogic series RT6, NR6/NR12, NRC12 PE90161.eps PE90156.eps The Varlogic controllers permanently monitor the reactive power of the installation and control the connection and disconnection of capacitor steps in order to obtain the targeted power factor. Varlogic NR6/12 Performance Permanent monitoring of the network and equipment. Information provided about equipment status. Alarm signals transmitted in case of anomaly (for NR6, NR12, NRC12). Communication by Modbus protocol (for NRC12). New control algorithm designed to reduce the number of switching operations and quickly attain the targeted power factor. Simplicity Simplified programming and possibility of intelligent self set-up. Ergonomic layout of control buttons. Quick and simple mounting and wiring. A special menu allows controller self-configuration. User-friendliness The large display allows: Direct viewing of installation electrical information and capacitor stage condition. Direct reading of set-up configuration. Intuitive browsing in the various menus (indication, commissioning, configuration). Alarm indication. Monitoring and protection Alarms Should an anomaly occur on the network or the capacitor bank, alarms are indicated on the screen and alarm contact closure is initiated. The alarm message is maintained on the screen once the fault clears until it is manually removed. Protection If necessary, the capacitor steps are automatically disconnected to protect the equipment. Varlogic NRC12 Range Type Number of step output contacts Part number NR NR NRC Accessories Communication RS485 Modbus set for NRC Temperature external probe for NRC12 type in addition to internal probe allows measurement at the hottest point inside the capacitor bank

70 Technical specifications General characteristics Output relays AC 2 A / 250 V 1 A / 400 V DC 0.6 A / 60 V 2 A / 24 V Protection Index Front panel IP41 Rear IP20 Measuring current 0 to 5 A Specific features NR-6/12 NRC12 Number of steps 6 / Supply voltage (V AC) 88 to to / 60 Hz 185 to to to to 460 Display 4 digit 7 segment LEDs 65 x 21 mm backlit screen 55 x 28 mm backlit screen Dimensions 155 x 158 x x 158 x 80 Flush panel mounting 35 mm DIN rail mounting (EN 50022) Operating temperature 0 C 60 C 0 C 60 C Alarm contact Internal temperature probe Separate fan relay contact Alarm history Last 5 alarms Last 5 alarms Type of connection Phase-to-neutral Phase-to-phase Current input CT 10000/5 A CT 25/5 A 6000/5 A CT 25/1 A 6000/5 A Target cosφ setting 0.85 ind ind. 0.9 cap. Possibility of a dual cosφ target Accuracy ±5 % ±2 % Response delay time 10 to 120 s 10 to 180 s Reconnection delay time 10 to 1800 s 10 to 600 s 10 to 900 s 4-quadrant operation for generator application Communication protocol Modbus 62

71 63

72 Contactors Contents Presentation Power Factor Correction guideline 3 Low Voltage capacitors 15 Detuned reactors 54 Power Factor controllers 60 Contactors 65 Appendix 68 64

73 Contactors Contactors PE90157.eps Special contactors LC1 D K are designed for switching 3-phase, single- or multiple-step capacitor banks. They comply with standards IEC and 60831, NFC , VDE 0560, UL and CSA. Operating conditions There is no need to use choke inductors for either single or multiple-step capacitor banks. Short-circuit protection must be provided by gi type fuses rated at In. Specifications These contactors are fitted with a block of early make poles and damping resistors, limiting the value of the current on closing to 60 IS max. This current limiting increases the life of all the installation s components, especially the fuses and capacitors. Technical specifications Network voltage (V) 50-60Hz Part number kvar LC1 DFK LC1 DGK LC1 DLK LC1 DMK LC1 DPK LC1 DTK LC1 DWK---- Contactor LC1DFK Standard control circuit voltages (@ 50/60 Hz) are: 24, 42, 48, 110, 115, 220, 230, 240, 380, 400, 415, 440 V. Other voltages are available on request. PE90158.eps The power values given in the selection table are for the following operating conditions: Prospective peak current LC1 D K 200 In at switch-on Maximum operating rate LC1 DFK, DGK, DLK, DMK, DPK 240 operating cycles/hour LC1 DTK, DWK 100 operating cycles/hour Electrical durability at nominal load All contactor ratings 400 V 300,000 operating cycles 690 V 200,000 operating cycles Contactor LC1DPK 65

Power Factor Correction

Power Factor Correction Power Quality Power Factor Correction Low Voltage components Catalogue 2017 Power Quality Your requirements. Optimize energy consumption By reducing electricity bills, By reducing power losses, By reducing

More information

Reactive Energy Management

Reactive Energy Management Energy management Reactive Energy Management Low Voltage Components Catalogue 2010 Reactive Energy Management Main contents Power Factor Correction guideline 2 Low Voltage capacitors 3-9 Detuned reactors

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design

More information

PFCC-1000 series. Powerful Flexibility Durability - Quality. Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter

PFCC-1000 series. Powerful Flexibility Durability - Quality. Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter PFCC-1000 series Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter Powerful Flexibility Durability - Quality email.us.at:.quotes@tanddproducts.com www.tanddproducts.com

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

DATA SHEET POWER CAPACITOR

DATA SHEET POWER CAPACITOR Issued August 2009 10470 DATA SHEET POWER CAPACITOR General Data * POWER FACTOR CORRECTION The power factor of a load is defined as the ratio of active power to apparent power, i.e. kw : kva and is referred

More information

Chapter L Power factor correction and harmonic filtering

Chapter L Power factor correction and harmonic filtering Chapter L Power factor correction and 1 2 3 4 5 6 7 8 9 10 Contents Reactive energy and power factor 1.1 The nature of reactive energy L2 1.2 Equipment and appliances requiring reactive energy L2 1.3 The

More information

LV Compensation & Filtering Products

LV Compensation & Filtering Products GE Grid Solutions LV Compensation & Filtering Products Providing Power Quality and Energy Efficiency Low (LV) reactive power compensation and harmonic filtering solutions help customers to improve the

More information

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1 LV PFC Basics Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1 What are the different types of loads? Ohmic loads Lighting bulbs Iron Resistive heating Capacative loads Capacitors Underground

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS High voltage shunt capacitor banks Alstom Grid high voltage shunt capacitor bank offering is divided in: By bank construction HV open rack capacitor banks HV enclosed capacitor banks By bank design HV

More information

NSL-10 STANDARD LIFE MODULAR CAPACITORS

NSL-10 STANDARD LIFE MODULAR CAPACITORS ADVANCE P.F. CORRECTION SOLUTIONS FROM NEPTUNE-DUCATI Channel Partner Ph: 02621-234524, 99242 04524 Industrial Trading Co. 10B Dharma Super Market, Kim Char Rasta, Contact : Paresh Gandhi (98241 31205)

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA SETTING UP REACTIVE POWER COMPENSATION DEVICES SELECTING A REACTIVE POWER COMPENSATION DEVICE To effectively compensate the

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Automatic capacitor banks with detuned filters

Automatic capacitor banks with detuned filters Power factor correction and harmonic filtering 5 R. /6 Automatic capacitor banks with detuned filters R. 5 /6 Automatic capacitor banks with detuned filters Introduction R5/6-3 R.5 - Automatic capacitor

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

McGill Power Sales & Engineering, INC.

McGill Power Sales & Engineering, INC. 1 McGill Power Sales & Engineering, INC. Power Factor Correction Terry McGill President McGill Power Sales & Engineering Inc. 2007 Eaton Corporation. All rights reserved. Agenda What is power factor? What

More information

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

شركة الوقت للكهرباء والمقاوالت ذ.م.م. CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution

More information

Power Factor Correction Catalogue VarSet. Low Voltage Capacitor Banks

Power Factor Correction Catalogue VarSet. Low Voltage Capacitor Banks Power Factor Correction Catalogue 2013 VarSet Low Voltage Capacitor Banks Do you need an easy solution to immediately boost your facility s energy efficiency and productivity? Are products that blend superior

More information

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz POWER QUALITY INSTRUCTION MANUAL Type SWF Sine Wave Filters 690 Volts, 50Hz Page 2 of 24 Contents 1. Introduction & SAFETY 2. Theory of operation 3. Typical results of the Sine Wave Filters 4. Transportation,

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Automatic capacitor banks with detuned filters

Automatic capacitor banks with detuned filters الکتروه م ند Power factor correction and harmonic filtering Automatic capacitor banks with detuned filters www.electrohamand.com Automatic capacitor banks with detuned filters Introduction R5/6-3 R.5 -

More information

Power Factor Correction Catalogue VarSet. Low Voltage Capacitor Banks

Power Factor Correction Catalogue VarSet. Low Voltage Capacitor Banks Power Factor Correction Catalogue 2013 VarSet Low Voltage Capacitor Banks Do you need an easy solution to immediately boost your facility s energy efficiency and productivity? Are products that blend superior

More information

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900 Coil Products Coil Products Customer partnership around the globe More than 250,000 coil products delivered to more than 170 countries. More than 60 years of operational experience. 35,000 in Europe 13,000

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Commissioning and Maintenance of Power Factor Correction Systems

Commissioning and Maintenance of Power Factor Correction Systems Dear Customer, We would like to thank you for choosing a power factor correction system from FRAKO Kondensatoren- und Anlagenbau GmbH. It is a pleasure to welcome you into the ever-expanding circle of

More information

Power supply CP-E 24/20.0

Power supply CP-E 24/20.0 2CDC 271 027 F0008 a OUTPUT L+, L+, L, L-: terminals output b INPUT L, N, PE: terminals input c 13-14: terminals - signalling contact d OUTPUT OK: green LED output voltage OK e OUTPUT LOW: red LED output

More information

VarSet. Catalogue 2018 Low Voltage Capacitor Banks. schneider-electric.com

VarSet. Catalogue 2018 Low Voltage Capacitor Banks. schneider-electric.com VarSet Catalogue 2018 Low Voltage Capacitor Banks schneider-electric.com Your requirements Optimize energy consumption By reducing electricity bills, By reducing power losses, By reducing CO 2 emissions.

More information

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY by Cesar Chavez, Engineering Manager, Arteche / Inelap, and John Houdek, President, Allied Industrial Marketing, Inc. Abstract: Industrial facility harmonic distortion problems can surface in many different

More information

PRODUCT CATALOGUE QUALITY MADE IN ITALY

PRODUCT CATALOGUE QUALITY MADE IN ITALY 2016 PRODUCT CATALOGUE PARTS AND TRA AYS POWER FACTOR CORRECTION LV QUALITY MADE IN ITALY ICAR: products and solutions Founded in 1946, ICAR is a leading manufacturer of capacitors and power factor correction

More information

AC Resonant Test Systems Tank Type Up to 500 kv

AC Resonant Test Systems Tank Type Up to 500 kv R AC Resonant Test Systems Tank Type Up to 500 kv PHENIX TECHNOLOGIES Testing Applications High power AC Resonant Test Systems are used where the load is largely capacitive with very low real power losses

More information

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. 1 PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. DEFINATIONS Working /Active Power: Normally measured in kilowatts (kw). It does the "work" for the system--providing the motion, torque,

More information

Power Factor. Power Factor Correction.

Power Factor. Power Factor Correction. Power Factor. Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively

More information

Power supply CP-E 24/2.5

Power supply CP-E 24/2.5 2CDC 271 015 F0t06 a OUTPUT L+, L : terminals output b DC OK: terminal signalling output c INPUT L, N, PE: terminals input d OUTPUT OK: green LED output voltage OK e OUTPUT Adjust: potentiometer adjustment

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

SHARDA Make Harmonics Filter

SHARDA Make Harmonics Filter SHARDA Make Harmonics Filter SHARDA offers perfect solution to minimize Harmonics level of industries where non-linear load like, VFD, Electronics load, Convertors, Voltage booster equipment s are present.

More information

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation Portable Description Features Measures all of the main electrical parameters of an electricity network Measurement in true root mean square Built-in energy meter With 4 voltage channels and 4 current channels

More information

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics Power IT LV Active Filters PQFI PQFM PQFK The ABB comprehensive solution for active filtering of harmonics Harmonics and Power Quality Power Quality relates to the amplitude, frequency and distortion of

More information

Power Quality Monitoring and Power Metering Tutorial

Power Quality Monitoring and Power Metering Tutorial Power Quality Monitoring and Power Metering Tutorial Power generation and transmission today are accomplished using three phase alternatingcurrent. To understand electrical power quality monitoring and

More information

PRODUCT CATALOGUE. amelec Electronic GmbH CH-8157 Dielsdorf QUALITY MADE IN ITALY

PRODUCT CATALOGUE.   amelec Electronic GmbH CH-8157 Dielsdorf QUALITY MADE IN ITALY 2014 PRODUCT CATALOGUE PARTS AND TRA AYS POWER FACTOR CORRECTION LV QUALITY MADE IN ITALY ICAR Means Capacitors ICAR S.p.A. is synonym of capacitor from 1946, coniugated over its multiple applications.

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

Technical Application Papers No.8 Power factor correction and harmonic filtering in electrical plants

Technical Application Papers No.8 Power factor correction and harmonic filtering in electrical plants Technical Application Papers No.8 Power factor correction and harmonic filtering in electrical plants Index Technical Application Papers Power factor correction and harmonic filtering in electrical plants

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Laboratory no. 3 FLUORESCENT LAMPS FITTINGS

Laboratory no. 3 FLUORESCENT LAMPS FITTINGS Laboratory no. 3 FLUORESCENT LAMPS FITTINGS 3.1 General information The fluorescent lamps powered at industrial frequency voltage act as nonlinear resistors, non-inertial, with a dynamic symmetric volt-ampere

More information

Power supply CP-T 48/20.0 Primary switch mode power supply

Power supply CP-T 48/20.0 Primary switch mode power supply Data sheet Power supply CP-T 48/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation Variable Frequency Drive Packages with Harmonic Mitigation Low Harmonic Drive Packages Engineered by Rockwell Automation What Do I Need to know About Harmonics? What are Harmonics? Harmonics are deviations

More information

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY Approximation based on the know-how of SEMAN S.A. The non-linear nature of modern electric loads makes the reception of measures for the confrontation

More information

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014

More information

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201 Low Voltage Products Enclosed Third Harmonic Filter and star Enclosed units Brochure S1GB 3_4 1SCC333C21 The Third Harmonic - a Growing Problem Today's electrical networks and plants are under much more

More information

DATA SHEET MKP 435 X2

DATA SHEET MKP 435 X2 DATA SHEET Interference suppression film capacitors, NEW File under BCcomponents, BC05 2001 Jun 22 MKP RADIAL POTTED TYPE PITCH 15/22.5/27.5 mm 296x12(full_width) CBB112 Fig.1 Simplified outlines. FEATURES

More information

Varplus 2 capacitors installation guide

Varplus 2 capacitors installation guide 2006 Varplus 2 capacitors installation guide Contents Reactive power Power definition 3 Electrical network pollution Choice of compensation type 4 Choice of detuned reactor tuning frequency 6 Control and

More information

Capacitor Switching Contactors

Capacitor Switching Contactors Capacitor Switching D385E51 Technical catalogues and news under: www.benedict.at Motor-Starter Mini- Overload Relays Capacitor Switching Motor-Starters Modular Circuit Breakers M4-32T... up to 32A M4-32R..

More information

Onsite Mobile AC High Voltage Test System

Onsite Mobile AC High Voltage Test System TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument

More information

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Power Frequency Withstand Voltage On-site testing of 400 kv GIS Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:

More information

Welcome. Power Survey International

Welcome. Power Survey International Welcome Company profile Established since 1948 Manufacturer of low and medium voltage products: Power Factor correction system Harmonic Filter system Steel Cabinet customized to your needs Other products

More information

TMC Transformers TMC

TMC Transformers TMC TMC Product & Technology Presentation Cast Resin Transformer (CRT) History Cast resin transformers first appeared in Germany during the 1960s. This new style of dry type transformer was developed with

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

ReactiVar AT6000/AT7000 transient-free reactive compensation system

ReactiVar AT6000/AT7000 transient-free reactive compensation system ReactiVar AT6000/AT7000 transient-free reactive compensation system nergy and cost savings benefits Power factor correction capacitors supply the reactive power (kvar) required by inductive loads. By correcting

More information

MEDIUM & HIGH VOLTAGE

MEDIUM & HIGH VOLTAGE MEDIUM & HIGH VOLTAGE TESTING EQUIPMENT VOLTAGE WITHSTAND SGM Series Resonant Systems The SGM series are used for generating high AC voltages at a fixed frequency (mainly 50 or 60 Hz) by means of an excited

More information

Film Capacitors Power Factor Correction

Film Capacitors Power Factor Correction Series/Type: Ordering code: Date: April 2016 Version: 1.1 Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the table and then change the

More information

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives 2 TECHNICAL GUIDE NO. 6 GUIDE TO HARMONICS WITH AC DRIVES Guide to harmonics This guide is part of ABB s technical guide series, describing

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Power Factor Correction

Power Factor Correction EPCOS Product Profile (India) 2013 Power Factor Correction Power Quality Solutions www.epcos.com Preview U I I U Linear loads: voltage was followed by current. Non linear load produce non sinusoidal currents

More information

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock

More information

Power supply CP-T 48/5.0 Primary switch mode power supply

Power supply CP-T 48/5.0 Primary switch mode power supply Data sheet Power supply CP-T 48/5.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Reduce harmonics in HVAC&R inverters through C-Less technology

Reduce harmonics in HVAC&R inverters through C-Less technology Reduce harmonics in HVAC&R inverters through C-Less technology Karim Lamrabtine Global Product Manager VSD 14-15 SEPTEMBER 2011, MUNICH Agenda www.infoplc.net What are Harmonics? Standards Compliance How

More information

Emicon Engineering Consultants L.L.C.

Emicon Engineering Consultants L.L.C. Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com

More information

TSX Series. Modicon Manuals. Presented by: Modicon PLC. Schneider Electric Quantum Modicon Gould Gettys

TSX Series. Modicon Manuals. Presented by: Modicon PLC. Schneider Electric Quantum Modicon Gould Gettys TSX Series Modicon Manuals Presented by: Modicon PLC Schneider Electric Quantum Modicon Gould Gettys For Product Needs: Email: sales@modiconplc.com Call: 1-800-691-8511 Fax: 919-415-1614 ModiconPLC.com

More information

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

Power factor correction and harmonic filtering. Automatic power factor regulators

Power factor correction and harmonic filtering. Automatic power factor regulators Power factor correction and harmonic filtering Automatic power factor regulators Automatic power factor reguladors R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent

More information

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS MERLIN GERIN KNOW HOW THM filtering and the management of harmonics upstream of UPS THM filtering and the control of harmonics upstream of UPSs Authors : S. BERNARD - J.N. FIORINA - B GROS - G. TROCHAIN

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications: SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument

More information

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells

More information

Real Time Power Factor Correction Units (Transient Free Switching)

Real Time Power Factor Correction Units (Transient Free Switching) Real Time Power Factor Correction Units (Transient Free Switching) Designers and Manufacturers of Power Factor Correction Equipment and Harmonic Filters 1016 34 AV SE Calgary, AB T2G 1V4 Canada Tel: 403

More information

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS Enrique PÉREZ Santiago REMENTERIA Aitor LAKA Arteche Spain Arteche Spain Ingeteam Power Technology-Spain ep@arteche.es sr@arteche.es Aitor.Laka@ingeteam.com

More information

(

( (www.xatianhong.com) Introduction to XATH Xi'an Tianhong Electric Co., Ltd. (XATH) is a solely state-owned enterprise, set up by China Shipbuilding Industry Corporation (CSIC). It is one of the largest

More information

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions Issue #65 - December 2012 Technical News Industrial Electrical and Automation Products, Systems and Solutions Part 2: Harmonics The link between harmonics and power factor Written by Justin Charlot Product

More information

Index. Capacitor Switching - 2 Contactors. Typical Circuit Diagram 2. Auxiliary Contact Blocks 2. Contactors 3. Dimensions 3. Technical Data 4,5,6

Index. Capacitor Switching - 2 Contactors. Typical Circuit Diagram 2. Auxiliary Contact Blocks 2. Contactors 3. Dimensions 3. Technical Data 4,5,6 Index Index Page Capacitor Switching - 2 Contactors Typical Circuit Diagram 2 Auxiliary Contact Blocks 2 Contactors 3 Dimensions 3 Technical Data 4,5,6 Contactor operation 7 Function 8 Construction 9 Oscillogram

More information

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -

More information

Reducing Total Harmonic Distortion with Variable Frequency Drives

Reducing Total Harmonic Distortion with Variable Frequency Drives Reducing Total Harmonic Distortion with Variable Frequency Drives Low Harmonic Technology in Optidrive Eco Overview Overview Both AC line chokes and DC link chokes have historically been used with Variable

More information

Power supply CP-T 24/20.0 Primary switch mode power supply

Power supply CP-T 24/20.0 Primary switch mode power supply Data sheet Power supply CP-T 24/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics Reactive Power and Harmonic Compensation Guide to Harmonics POWER QUALITY The Basics of Harmonics All business types, commercial, industrial, government and energy/utility have a concern with power quality.

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

Power supply CP-D 24/4.2 Primary switch mode power supply

Power supply CP-D 24/4.2 Primary switch mode power supply Data sheet Power supply CP-D 24/4.2 Primary switch mode power supply The CP-D range of modular power supply units in MDRC design (modular DIN rail components) is ideally suited for installation in distribution

More information

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 40 CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 3.1 INTRODUCTION The low power factor effects on transmission line, switchgear, transformers etc. It is observed that if the power

More information

Power IT LV Active Filters PQFA - PQFL - PQFT

Power IT LV Active Filters PQFA - PQFL - PQFT Power IT LV Active Filters PQFA - PQFL - PQFT The ABB comprehensive solution for active filtering of harmonics Pst Harmonics and Power Quality Harmonics caused by non-linear electrical loads such as variable

More information

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease Fluke 1740 Series Three-Phase Power Quality Loggers Memobox Technical Data Assess power quality and conduct long-term studies with ease Compact and rugged, the Fluke 1740 Series three-phase power quality

More information

Power supply CP-T 24/10.0 Primary switch mode power supply

Power supply CP-T 24/10.0 Primary switch mode power supply Data sheet Power supply CP-T 24/10.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017 Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates

More information

Power supply CP-T 24/40.0 Primary switch mode power supply

Power supply CP-T 24/40.0 Primary switch mode power supply Data sheet Power supply CP-T 24/40.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information