ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Size: px
Start display at page:

Download "ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services"

Transcription

1 ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

2 edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion to a voltage or current waveform. The term harmonic refers to a component of a wave form that occurs at an integer multiple of the fundamental frequency. Fourier theory tells us that any repetitive waveform can be defined in terms of summing sinusoidal waveforms which are integer multiples (or harmonics) of the fundamental frequency. For the purpose of a steady state waveform with equal positive and negative half-cycles, the Fourier series can be expressed as follows: F (t) = An. Sin (npt / T) S n=1 where f(t) is the time domain function n is the harmonic number (only odd values of n are required) An is the amplitude of the nth harmonic component T is the length of one cycle in seconds A common term that is used in relation to harmonics is THD or Total Harmonic distortion. THD can be used to describe voltage or current distortion and is calculated as follows: THD (%) = (ID1² + ID2² IDn²) where IDn: is the magnitude of the nth harmonic as a percentage of the fundamental (individual distortion). info@edaratgroup.com 2

3 Harmonics are currents or voltages with frequencies that are integer multiples of the fundamental power frequency. If the fundamental power frequency is 6 Hz, then the 2 nd harmonic is 12 Hz, the 3 rd is 18 Hz, etc. (see Figure 1). When harmonic frequencies are prevalent, electrical power panels and transformers become mechanically resonant to the magnetic fields generated by higher frequency harmonics. When this happens, the power panel or transformer vibrates and emits a buzzing sound for the different harmonic frequencies. Harmonic frequencies from the 3 rd to the 25 th are the most common range of frequencies measured in electrical distribution systems. Distorted wave form (6 Hz - Fundamental + 3rd Harmonic) Fundamental (6 Hz) 3rd Harmonic (18 Hz) Figure 1 When all harmonic currents are added to the fundamental a waveform known as complex wave is formed. An example of complex wave consisting of the fundamental (1 st harmonic), 3 rd harmonic and 5 th harmonic is illustrated in Figure 2: Hz Waveform 15 Hz Waveform 2 Hz Waveform Symmetrical Complex Waveform Figure 2 info@edaratgroup.com 3

4 The total harmonic distortion (THD) of a signal is a measurement of the harmonic distortion present and is defined as the ratio of the sum of the powers of all harmonic components to the power of the fundamental. It provides an indication of the degree to which a voltage or current signal is distorted (see Figure 3). 1 %-Fund Harmonic THD = 98% Figure 3 info@edaratgroup.com 4

5 NON-LINEAR LOADS A linear load draws current that is instantaneously proportional to the voltage, such as in Figure 4 (Linear time-aligned (unity or 1% power factor) voltage and current waveforms) and Figure 5 (Linear shifted alignment (at 8% leading power factor) between voltage and current). One example of a linear load is a resistive load, such as an incandescent light bulb Figure Figure 5 info@edaratgroup.com 5

6 A nonlinear load either draws a current waveform that is not instantaneously proportional to the voltage or is a load that causes current to distort its sinusoidal shape. The current waveform also leads or lags voltage or phase. Harmonics are distortions of the normal electrical current waveform, generally transmitted by nonlinear loads -Non-linear loads occur when the resistance is not a constant and changes during each sine wave of the applied voltage waveform, resulting in a series of positive and negative pulses. Switch-mode power supplies (SMPS), variable speed motors and drives, photocopiers, personal computers, laser printers, fax machines, battery chargers, and UPSs are examples of nonlinear loads. Single-phase nonlinear loads are prevalent in modern office buildings- Data Center, while 3-phase nonlinear loads are common in factories and industrial plants. A large portion of the nonlinear electrical loads in most electrical distribution systems comes from SMPS equipment. For example, all computer systems use SMPS that convert utility AC voltage to regulated low-voltage DC for internal electronics. These nonlinear power supplies draw current in high-amplitude short pulses that create significant distortion in the electrical current and voltage wave shape (see Figure 6). This harmonic distortion, measured as total harmonic distortion (THD), travels back into the power source and can affect other equipment connected to the same source. Figure 6 Most power systems can accommodate a certain level of harmonic currents but will experience problems when harmonics become a significant component of the overall load. As these higher frequencies harmonic currents flow through the power system, they can cause communication errors, overheating and hardware damage, such as: z Overheating of electrical distribution equipment, cables, transformers, standby generators, etc. z High voltages and circulating currents caused by harmonic resonance z Equipment malfunctions due to excessive voltage distortion z Increased internal energy losses in connected equipment, causing component failure and shortened life span z False tripping of branch circuit breakers z Metering errors z Fires in wiring and distribution systems z Generator failures z Crest factors and related problems z Lower system power factor, resulting in penalties on monthly utility bills info@edaratgroup.com 6

7 HARMONICS REDUCTION SOLUTIONS To determine if harmonic mitigation is necessary, should conduct an assessment to precisely measure the harmonics affecting the data center and identify their origin. Options for harmonic mitigation vary in complexity and cost and can be deployed individually or in combination. The strategy that makes the most sense for a facility will vary based on the loads it supports, its budget, and the nature of the harmonic-related problems it is experiencing. There are several approaches that can be taken to compensate for or reduce harmonics in the power system, with varying degrees of effectiveness and efficiency. 2% neutral conductors One option is to specify an 2% neutral conductor or to use separate neutral conductors. Triple n harmonics (3, 9, 15, etc.) can produce neutral currents that can be up to the theoretical maximum of 173% of the phase current, which is why a 2% neutral conductor is usually specified. K-rated transformers: A standard transformer is not designed for high harmonic currents produced by nonlinear loads. It will overheat and fail prematurely when connected to these loads. Therefore, when harmonics were first introduced into electrical systems at levels that showed detrimental effects (circa 198), the industry responded by developing the K-rated transformer. K-rated transformers are not used to eliminate harmonics, but to manage the heat generated by harmonic currents. K factor ratings range between 1 and 5. A standard transformer designed for linear loads is designated with a K-factor of 1. The higher the K-factor, the more heat from harmonic currents the transformer is able to withstand. When selecting a K rating, managers should consider the trade-offs between size, efficiency, and heat tolerance. For example, transformers with higher K factors are typically larger than those with lower K factors. The table 1 below shows appropriate K ratings to use for different percentages of nonlinear current in the electrical system. Non-linear load K- Rating Incidental electronic equipment representing less than 5% K 1 Harmonic producing equipment representing less than 35 % K4 Harmonic producing equipment representing less than 5 % K 7 Harmonic producing equipment representing less than 75 % K 13 Harmonic producing equipment representing less than 1 % K 2 Table 1 info@edaratgroup.com 7

8 Uninterruptable Power Supply- UPS Since UPSs and the loads they serve have historically been considered some of the most significant harmonic loads on a power system, companies can also use harmonic-mitigating UPSs to reduce line harmonics. Much like active filters, harmonic-mitigating UPSs eliminate harmonic distortion by inserting equal and opposite current into the line. They also compensate for reactive power from low power factor loads and balance loads across three phases to avoid stranded capacity, while providing clean and continuous power during utility outages or in response to electrical disturbances. Harmonics filters Harmonic filters remove harmonics and correct the phase of the fundamental current, thus converting non-linear loads into linear loads. Passive, and Active filters, it can be either used as a standalone part integral to a large nonlinear load or can be used for a multiple small single phase nonlinear loads by connecting it to a switch board. Passive filter A Passive Filter uses inductors capacitors and resistors in combination to create the filter. Passive implementations of linear filters are based on combinations of resistors (R), inductors (L) and capacitors (C). These types are collectively known as passive filters, because they do not depend upon an external power supply and/or they do not contain active components such as transistors. Active filter This method uses sophisticated electronics and power section IGBTs to inject equal and opposite harmonics onto the power system to cancel those generated by other equipment. These filters monitor the nonlinear currents demanded from nonlinear loads and electronically generate currents that match and cancel the destructive harmonic currents. Active filters are inherently non-resonating and are easily connected in parallel with system loads. PRINCIPLE DRAWING LOAD i LOAD MAINS Connection i MAINS MAINS H LOAD H MAINS AHF i LOAD i AHF i MAINS info@edaratgroup.com 8

9 Advantages z Guarantee compliance with IEEE if sized correctly z Harmonic cancellation from the 2nd to 51st harmonic z No series connection provides easy installation with no major systema rework z Provide VAR currents, improving system power factor Disadvantages z Can be more expensive than other methods due to the high performance control and power sections z The filter s input semiconductors are exposed to line transients. With increase in use of non-linear loads, the issues of power supply harmonics are more noticeable than ever. Controlling and monitoring industrial system designs and their effects on utility distribution systems are potential problems for the industrial consumer, who is responsible for complying with the IEEE 519, recommended practices and procedures. Industrial facilities should include a system evaluation, including a harmonic distortion analysis, while planning facility construction or expansion. Vendors of non-linear loads, such as variable frequency drives, can provide services and recommend equipment that will reduce harmonics in order to comply with IEEE 519 guidelines. Generally, at any point the measured value of total harmonic voltage distortion should not exceed 5% and that of any individual harmonic voltage distortion should not exceeding 3% of the fundamental value of the line voltage. Normally, in typical applications, the harmonics are measured up to 25 th order, but in critical applications, those are measured up to 5 th or 1 th order. A better way to handle harmonics in the data center is to simply design better systems and devices, which fortunately has already been accomplished for the most part. In order to offer products in the world-wide market, nearly every computer equipment manufacture is in compliance. To comply with the regulation, global computer equipment vendors developed Power Factor Corrected (PFC) power supply technology. Power factor is the ratio of the real power to the load and the apparent power and is a number between zero and one (e.g.,.5 pf = 5%pf). Real power is the capacity of the circuit. Apparent power is the product of the current and voltage in the circuit. If energy is stored in the load and returned to the source, or if is distorted by a non-linear load, the apparent power will be greater than the real power. Loads with a high power factor draw less current than loads with low power factors, and these higher currents increase energy loss and require larger equipment. Switched-mode power supplies have a low power factor. PFC power supplies control the harmonic current using either a filter or an electronic system that controls the amount of power drawn by the load. The purpose of the PFC is to make the power factor as close to one as possible, where the current waveform is proportional to the voltage waveform. When this is the case, the voltage and current are in phase and the reactive power consumption is zero, enabling power companies to efficiently deliver power. In other words, all of the energy supplied by the source is consumed by the load and none is returned to the source. info@edaratgroup.com 9

10 CONCLUSION Harmonics in the data center was a real concern in the past. Fortunately, it is one of those issues that are close to being solved, at least for computing equipment, by regulatory agencies and computer equipment manufactures. It s not an issue that receives a lot of press or marketing, as companies tend to focus more on the more tangible benefit of energy efficiency and reduced energy costs, which is why the subject of harmonics is still occasionally raised as an issue when designing new power distribution systems. Facilities managers or electrical architects who are unfamiliar with modern computer equipment might specify costly solutions such as K-factor transformers or 2% neutral conductors, to handle non-linear loads and harmonic neutral currents that are relatively rare in today s IT environments. Data center managers who are armed with the knowledge that computer vendors are compliant with harmonic elimination standards can help drive more realistic and cost-effective power distribution designs in the data center and be more proactive in replacing non-conforming, legacy equipment. Simply stated, 1% rated neutral conductors are suitable for the vast majority of applications. Circumstances might arise where oversize neutral conductors are necessary for the remaining non-linear loads in the data center, such as lighting and cooling equipment, or legacy equipment that must be maintained for a particular application. info@edaratgroup.com 1

11 References Mitigating data center harmonics Neutral Ratings for Power Distribution Systems in the Data Center Harmonics in your electrical system Training/HarmonicsInYourElecSystem.pdf. Harmonic reduction methods

Understanding Harmonics

Understanding Harmonics Understanding Harmonics Terry Gaiser Sensus What Are Harmonics? 1 » What is Power Quality?» Power quality is the degree to which both the utilization and delivery of electric power affects the performance

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez Harmonic Power A VFDs.com Whitepaper Written by Ernesto Jimenez Table of Contents 1. Need for Clean Electricity 2. What Are Harmonics? 3. Lower Order Harmonics 4. Causes of Harmonics 5. Effects of Harmonics

More information

CHAPTER 4 HARMONICS AND POWER FACTOR

CHAPTER 4 HARMONICS AND POWER FACTOR 4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried

More information

Technical Paper. Harmonic Distortion in Data Centers

Technical Paper. Harmonic Distortion in Data Centers Technical Paper Harmonic in Data Centers Written By: Ian Wallace Summary Power quality and power reliability are critical to data center operation. As strides have been made to improve energy efficiency

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

NJWA - Harmonics and Drives Proper System Design

NJWA - Harmonics and Drives Proper System Design Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives

More information

Harmonics White Paper

Harmonics White Paper Harmonics White Paper New Breakthrough In PWM Drives Technology Reduces Input Line Harmonics Without the Use of Filtering Devices Harmonic Distortion Damages Equipment and Creates a Host of Other Problems

More information

Active Harmonic Filter (AF3)

Active Harmonic Filter (AF3) Active Harmonic Filter (AF3) Active Harmonic Filter Improving the Efficiency and Life of System by use of Digital Active Power Conditioner HARMONICS 50 Hz, fundamental 100 Hz, 2nd Harmonic 150 Hz, 3rd

More information

Understanding Power Quality

Understanding Power Quality Understanding Power Quality Produced by Dr Bruce Girdwood For Energy Mad Ltd Version 1: 23 October 2007 The electronics revolution and the growing number of utility programmes promoting compact fluorescent

More information

Fluke 40/41 Power Harmonics Analysers

Fluke 40/41 Power Harmonics Analysers Data Pack A Issued March 2002 232-4752 Fluke 40/41 Power Harmonics Analysers This data sheet refers to the Fluke 40 and Fluke 41 Power Harmonics Analysers. RS stock no. Description 215-9621 Fluke 41B power

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1 Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS December 14, 2011 Slide 1 Agenda Harmonics: What they are? Where do they come from? Why bother? Regulations How to detect? How to avoid? Summary

More information

Electromagnetic Harmonic Filters Technical Guide

Electromagnetic Harmonic Filters Technical Guide Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other triplen

More information

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics

More information

ECET Modern Power

ECET Modern Power ECET 273000 Modern Power Course Instructors Course Philosophy This course is an introduction to a wide range of electrical energy systems technologies. Topics include fundamentals of energy conversion,

More information

Power Quality Issues and Harmonics Reduction by Hybrid Filter

Power Quality Issues and Harmonics Reduction by Hybrid Filter IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 02, 2015 ISSN (online): 2321-0613 Tejas M Patel 1 Akash N Lathiya 2 Nidhish G Misra 3 Yogesh R Prajapati 4 1,2,3,4 Department

More information

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017 Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates

More information

A. Harmonics. non-linear loads. are. required)

A. Harmonics. non-linear loads. are. required) Harmonic Comparison between Fluorescent and WOLED (White Organic LED) Lamps Hari Maghfiroh, Fadhila Tresna Nugraha, and Harry Prabowo Abstract Fluorescent and WOLED are widely used because it consumes

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Reliable power onboard and offshore

Reliable power onboard and offshore Reliable power onboard and offshore AccuSine PCS+ Active Harmonic Filters For electrical network reliability and quality in Marine 2 What causes harmonics in Marine applications? Power electronics with

More information

Tuningintobetter power quality

Tuningintobetter power quality Technology Review Third harmonic filters Tuningintobetter power quality Jouko Jaakkola Your PC screen flickers, stops flickering, starts again... Irritating to be sure, and perhaps the first visible sign

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

Power Factor and Power Factor Correction

Power Factor and Power Factor Correction Power Factor and Power Factor Correction Long gone are the days when only engineers that worked with large electric motors and high power electric loads need worry about power factor. The introduction

More information

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic

More information

Harmonics Elimination Using Shunt Active Filter

Harmonics Elimination Using Shunt Active Filter Harmonics Elimination Using Shunt Active Filter Satyendra Gupta Assistant Professor, Department of Electrical Engineering, Shri Ramswaroop Memorial College of Engineering and Management, Lucknow, India.

More information

1C.4.1 Harmonic Distortion

1C.4.1 Harmonic Distortion 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well

More information

Effective Harmonic Mitigation with Active Filters

Effective Harmonic Mitigation with Active Filters Advancing Power Quality White Paper Effective Harmonic Mitigation with Active Filters Written by: Ian Wallace Variable Speed Drive with no Harmonic Mitigation Industry standard variable speed drives, with

More information

Harmonic Distortion and Variable Frequency Drives

Harmonic Distortion and Variable Frequency Drives Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation

More information

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY Approximation based on the know-how of SEMAN S.A. The non-linear nature of modern electric loads makes the reception of measures for the confrontation

More information

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant CASE STUDY Implementation of Ford Motor Company SA Silverton Plant 1 SCENARIO Ford Motor Company is a global automotive and mobility company based in Dearborn, Michigan. Ford Motor Company of Southern

More information

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution Agenda I. Harmonic Basics II.Harmonic Mitigation Solutions III.Case Study 2 Harmonic

More information

Reduction Of Harmonics By Using Active Harmonic Filter

Reduction Of Harmonics By Using Active Harmonic Filter Reduction Of Harmonics By Using Active Harmonic Filter Amit Gupta 1, Shivani Tiwari 2, Palash Selot 3 1 Assistant Professor, Department of Electrical Engineering, TIETECH, Jabalpur 2 UG Scholor, Department

More information

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder R. W. Erickson Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder 16.4. Power phasors in sinusoidal systems Apparent power is the product of the rms voltage and

More information

McGill Power Sales & Engineering, INC.

McGill Power Sales & Engineering, INC. 1 McGill Power Sales & Engineering, INC. Power Factor Correction Terry McGill President McGill Power Sales & Engineering Inc. 2007 Eaton Corporation. All rights reserved. Agenda What is power factor? What

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives For your business and technology editors Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives The use of AC induction motors is essential for industry and utilities. AC induction

More information

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

Active Harmonic Filter

Active Harmonic Filter Reactive Power and Harmonic Compensation Active Harmonic Filter The new StacoSine Plus active harmonic filter is available in 100, 150, 200 and 300 amp assemblies. Modules can be paralleled for a maximum

More information

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS MERLIN GERIN KNOW HOW THM filtering and the management of harmonics upstream of UPS THM filtering and the control of harmonics upstream of UPSs Authors : S. BERNARD - J.N. FIORINA - B GROS - G. TROCHAIN

More information

Power Quality Monitoring and Power Metering Tutorial

Power Quality Monitoring and Power Metering Tutorial Power Quality Monitoring and Power Metering Tutorial Power generation and transmission today are accomplished using three phase alternatingcurrent. To understand electrical power quality monitoring and

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

Emicon Engineering Consultants L.L.C.

Emicon Engineering Consultants L.L.C. Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com

More information

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,

More information

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV 6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV SOLIDSTATE CONTROLS, INC. Solidstate Controls Incorporated 875 Dearborn Drive Columbus, Ohio 43085 Tel : (614) 846-7500 Fax: (614) 885-3990 6L]LQJ $ 836 6\VWHP )RU 1RQ/LQHDU

More information

ABB n.v. Power Quality Products, October 2014

ABB n.v. Power Quality Products, October 2014 ABB n.v. Power Quality Products, October 2014 Power Quality Harmonic Basics Problems and solutions March 19, 2015 Slide 1 828m high 160 floors in total Total 113 PQF in this tower, 12000A PQFS 45M IP30

More information

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM Liebert AF2 Next Generation Active Harmonic Filter Power Protection for Business-Critical Continuity TM LIEBERT AF2 You Need To Be Aware Of Harmonics During the last few years industries has witnessed

More information

Harmonics, its Mitigation & Result of Case study of Spinning Mill

Harmonics, its Mitigation & Result of Case study of Spinning Mill International Journal of Innovative Research in Engineering & Management (IJIREM) ISSN: 2350-0557, Volume-2, Issue-4, July 2015, its Mitigation & of Case of Spinning Mill Yogesh Subhash Shimpi M. Tech

More information

Analysis of Harmonic Distortion in Non-linear Loads

Analysis of Harmonic Distortion in Non-linear Loads Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna

More information

Harmonic Analysis to Improve Power Quality

Harmonic Analysis to Improve Power Quality Harmonic Analysis to Improve Power Quality Rumana Ali Assistant Professor, MITE Moodbidri Abstract- Presence of nonlinear & power electronic switching devices produce distorted output & harmonics into

More information

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink Parag Datar 1, Vani Datar 2, S. B. Halbhavi 3, S G Kulkarni 4 1 Assistant Professor, Electrical and Electronics Department,

More information

Active Harmonic Filter (AHF)

Active Harmonic Filter (AHF) Power Quality Active Harmonic Filter (AHF) AHF Wallmount AHF Cabinet Mount INTRODUCTION TO HARMONICS Harmonics are an increasing problem in today s modern electrical system. The rapid uptake of sophisticated

More information

Harmonic Filters for Single Phase Equipment

Harmonic Filters for Single Phase Equipment POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics

More information

Harmonics I Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update

Harmonics I   Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update Power Protection Products, Inc. White Paper by Dan Maxcy l 2018 Update P3 is the industry s trusted and respected critical power, cooling and energy solutions provider. 877-393-1223 I www.p3-inc.com HARMONICS

More information

Drives 101 Lesson 5. Power Input Terminology for a VFD

Drives 101 Lesson 5. Power Input Terminology for a VFD Drives 101 Lesson 5 Power Input Terminology for a VFD This lesson covers the terminology associated with the incoming power to a Variable Frequency Drive (VFD) and the efforts to protect both the VFD and

More information

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD Scientific Journal of Impact (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 04, April -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 ANALYSIS AND

More information

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014

More information

Fundamentals of Power Quality

Fundamentals of Power Quality NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»

More information

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control International Journal of Scientific Engineering and Research (IJSER) Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control Rahul Kumar Patel 1, S. Subha 2 Abstract:

More information

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018 Electrical Theory Power Principles and Phase Angle PJM State & Member Training Dept. PJM 2018 Objectives At the end of this presentation the learner will be able to: Identify the characteristics of Sine

More information

New power tools provide quality and efficiency By

New power tools provide quality and efficiency By Typical Delta-wye transformer New power tools provide quality and efficiency By Steve Terry For quite some time, it has been well understood that phase-control SCR dimming systems used in the entertainment

More information

Study and analysis of THD and content of Harmonics in Three Phase PWM Inverter with Filters.

Study and analysis of THD and content of Harmonics in Three Phase PWM Inverter with Filters. Study and analysis of THD and content of Harmonics in Three Phase PWM Inverter with Filters. Abstract- In this paper a traditional three phase inverter drive is constructed with RL load. The inverter and

More information

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS 66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

SHUNT ACTIVE POWER FILTER

SHUNT ACTIVE POWER FILTER 75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation R. S. Al Abri, M. H. Albadi, M. H. Al Abri, U. K. Al Rasbi, M. H. Al Hasni, S. M. Al Shidi Abstract This paper presents an analysis

More information

Alternator winding pitch and power system design

Alternator winding pitch and power system design Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering

More information

Improve Power Factor and Reduce the Harmonics Distortion of the System

Improve Power Factor and Reduce the Harmonics Distortion of the System Research Journal of Engineering Sciences ISSN 2278 9472 Improve Power Factor and Reduce the Harmonics Distortion of the System Abstract Jain Sandesh, Thakur Shivendra Singh and Phulambrikar S.P. Electrical

More information

Understanding Input Harmonics and Techniques to Mitigate Them

Understanding Input Harmonics and Techniques to Mitigate Them Understanding Input Harmonics and Techniques to Mitigate Them Mahesh M. Swamy Yaskawa Electric America YASKAWA Page. 1 Organization Introduction Why FDs Generate Harmonics? Harmonic Limit Calculations

More information

HARMONIC MITIGATIONCASE STUDY

HARMONIC MITIGATIONCASE STUDY HARMONIC MITIGATIONCASE STUDY CNCE AND NCE INSTALLATION AT BROADCASTING STUDIO Concerned about video noise detected on some of its studio equipment, E! Entertainment Television (ETV), commissioned a study

More information

Introduction to Rectifiers and their Performance Parameters

Introduction to Rectifiers and their Performance Parameters Electrical Engineering Division Page 1 of 10 Rectification is the process of conversion of alternating input voltage to direct output voltage. Rectifier is a circuit that convert AC voltage to a DC voltage

More information

Literature Review for Shunt Active Power Filters

Literature Review for Shunt Active Power Filters Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller

More information

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System 1 G.Balasundaram, 2 Dr.S.Arumugam, 3 C.Dinakaran 1 Research Scholar - Department of EEE, St.

More information

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY Journal of Electrical Engineering & Technology (JEET) (JEET) ISSN 2347-422X (Print), ISSN JEET I A E M E ISSN 2347-422X (Print) ISSN 2347-4238 (Online) Volume

More information

Chapter 2 Shunt Active Power Filter

Chapter 2 Shunt Active Power Filter Chapter 2 Shunt Active Power Filter In the recent years of development the requirement of harmonic and reactive power has developed, causing power quality problems. Many power electronic converters are

More information

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to

More information

UNDERSTANDING POWER QUALITY

UNDERSTANDING POWER QUALITY Technical Note No. 1 June 1998 UNDERSTANDING POWER QUALITY This Technical Note describes the range of problems, what causes them, what they affect and what could be done to manage them. Integral Energy,

More information

Power Quality Analysis of Domestic Wind Mill Inverter-Harmonic Analysis and its Mitigation

Power Quality Analysis of Domestic Wind Mill Inverter-Harmonic Analysis and its Mitigation e t International Journal on Emerging Technologies 2(2): 40-45(2011) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Power Quality Analysis of Domestic Wind Mill Inverter-Harmonic Analysis and

More information

CHAPTER 5 SWITCH MODE POWER SUPPLIES

CHAPTER 5 SWITCH MODE POWER SUPPLIES 57 CHAPTER 5 SWITCH MODE POWER SUPPLIES 5.1 INTRODUCTION The latest advancements in the consumer electronics market resulted in producing high quality classy electronic equipment, but they are compelled

More information

APPLICATION GUIDE. Harmonics in HVAC applications

APPLICATION GUIDE. Harmonics in HVAC applications APPLICATION GUIDE Harmonics in HVAC applications Table of contents 4 Harmonics in general and why we should care 4 Introduction 4 Basics of harmonics 5 Causes of harmonic distortion 5 Problems caused

More information

Active Harmonic Filters IPC150 AHF Series

Active Harmonic Filters IPC150 AHF Series IPC150 AHF Series Multi Function Ultra Fast Power Quality Compensation Harmonics Power Factor Correction Unbalance Compensation www.inphase.in ISO 9001:2008 Certified THE CHALLENGE To increase the productivity,

More information

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion Harmonic Solutions Clean Power Drive Solution to Harmonic Distortion UTILITY GRID UTILITY SWITCH YARD IN THE FACILITY IEEE-519 POINT OF COMMON COUPLING POWER PLANT GENERATION TRANSMISSION MEDIUM VOLTAGE

More information

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. 1 PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. DEFINATIONS Working /Active Power: Normally measured in kilowatts (kw). It does the "work" for the system--providing the motion, torque,

More information

Power Quality and Power Factor Correction

Power Quality and Power Factor Correction Power Quality and Power Factor Correction Introduction Since most loads in modern electrical distribution systems are inductive, there is an ongoing interest in improving power factor. The low power factor

More information

Voltage and Current Waveforms Enhancement using Harmonic Filters

Voltage and Current Waveforms Enhancement using Harmonic Filters Voltage and Current Waveforms Enhancement using Harmonic Filters Rajeb Ibsaim rabsaim@yahoo.com, Azzawia University, Libya Amer Daeri ibnjubair1@yahoo.co.uk Azzawia University, Libya Abstract The demand

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Phanikumar.Ch, M.Tech Dept of Electrical and Electronics Engineering Bapatla Engineering College, Bapatla,

More information

DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS

DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS Dr.S.K.PURUSHOTHAMAN Associate Professor Department of EEE Sri Venkateswara College Of Engineering And Technology, Thirupachur

More information

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics Reactive Power and Harmonic Compensation Guide to Harmonics POWER QUALITY The Basics of Harmonics All business types, commercial, industrial, government and energy/utility have a concern with power quality.

More information

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications.

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications. Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications. 1 Vikas Kumar Chandra, 2 Mahendra Kumar Pradhan 1,2 ECE Department, School of

More information

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY by Cesar Chavez, Engineering Manager, Arteche / Inelap, and John Houdek, President, Allied Industrial Marketing, Inc. Abstract: Industrial facility harmonic distortion problems can surface in many different

More information

Power Quality Analysis: A Study on Off-Line UPS Based System

Power Quality Analysis: A Study on Off-Line UPS Based System Power Quality Analysis: A Study on Off-Line UPS Based System P.K.DHAL Department of Electrical and Electronics Engineering VelTech Dr.RR&Dr.SR Technical University # 42 Avadi- VelTech Road, Chennai-62

More information

Power Quality Analysis in Power System with Non Linear Load

Power Quality Analysis in Power System with Non Linear Load International Journal of Electrical Engineering. ISSN 0974-2158 Volume 10, Number 1 (2017), pp. 33-45 International Research Publication House http://www.irphouse.com Power Quality Analysis in Power System

More information

Harmonics Analysis Of A Single Phase Inverter Using Matlab Simulink

Harmonics Analysis Of A Single Phase Inverter Using Matlab Simulink International Journal Of Engineering Research And Development e- ISSN: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 14, Issue 5 (May Ver. II 2018), PP.27-32 Harmonics Analysis Of A Single Phase Inverter

More information

VFDs and Harmonics in HVAC Applications

VFDs and Harmonics in HVAC Applications VFDs and Harmonics in HVAC Applications Larry Gardner Product Marketing Manager Yaskawa America, Inc. Jeff Grant Senior Sales Engineer LONG Building Technologies October 20, 2016 2016 Yaskawa America,

More information

PQ Audit - The right choice to ensure power system performance. Mr Lalit Kumar Wasan Tata Power- DDL

PQ Audit - The right choice to ensure power system performance. Mr Lalit Kumar Wasan Tata Power- DDL PQ Audit - The right choice to ensure power system performance Mr Lalit Kumar Wasan Tata Power- DDL Outline vpower Quality v Present Challenges v Harmonics & Its Impact on DISCOM v Future Challenges Roof-Top

More information

Harmonic Filters and Reactors

Harmonic Filters and Reactors Harmonic Filters and Reactors Harmonics are invisible but costly If one looks up the meaning of harmonics in any one of several technical dictionaries, it is normally defined as being A sinusoidal component

More information