CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Size: px
Start display at page:

Download "CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS"

Transcription

1 66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic controllers behave as nonlinear load and cause serious distortion in the distribution system and introduce unwanted harmonics in the system, leading to decreased efficiency of the power system network and equipment connected in the network. To meet the requirements of harmonic reduction, passive and active power filters are being used in combination with the conventional converters. Presently, active power filters are becoming more affordable due to cost reductions in power semiconductor devices, their auxiliary parts and integrated digital control circuits. Resent research focuses on use of the UPQC to compensate for power-quality problems. The performance of UPQC mainly depends upon how accurately and quickly reference signals are derived. After efficient extraction of the distorted signal, a suitable dc-link current regulator is used to derive the actual reference signals. Various control approaches, such as the PI, sliding-mode, predictive, unified constant frequency (UCF) controllers are in use. Modern control theory-based controllers are state feedback controllers, self-tuning controllers and model reference adaptive controllers. These controllers also need mathematical models and are therefore sensitive to parameter variations. In recent years, a major effort has been underway to develop new and unconventional control techniques that can often augment or replace conventional control techniques. A number of unconventional control techniques have evolved, offering

2 67 solutions to many difficult control problems in industry and manufacturing sectors. However, at the same time, these advanced power electronics systems also help in reducing the harmonics flowing in the power systems. The THD value is the effective value of all the harmonics current added together compared with the value of the fundamental current, as discussed by John et al (2001). When excessive harmonic voltage and current are generated, filters are usually installed to reduce the harmonic distortion Fang et al (1990) and Helga et al (2004). Other methods of harmonic reduction is considered such as current injected by active power filter, discussed by Sangsun et al (2001) and Ambra et al (2003). Ideally, voltage and current waveforms are pure sinusoids. However, because of the increased usage of nonlinear loads, these waveforms become distorted. This deviation from a pure sine wave can be represented by harmonic components having a frequency that is an integral multiple of the fundamental frequency. Thus, a pure voltage or current sine wave has no distortion and no harmonics. In order to quantify the distortion, the term of total harmonics distortion is used. The inverter switches are connected and disconnected at discrete time instant to generate desired output voltage of specific magnitude and frequency. Such an output voltage in addition to its fundamental component contains a lot of other undesired harmonic components as well. Hamadi et al (2004) has discussed the minimization of the harmonic injection from an inverter into the power system. But, his work did not meet the IEEE Standard since the THD value high. IEEE recommended practices and requirements for harmonic control in electrical power systems address harmonics limits at the consumer and service provider interface. This standard provides procedure for controlling harmonics on the power system along with recommended limits for customer harmonics

3 68 injection and overall power system harmonics levels to ensure overall system voltage integrity. The utilities are responsible for maintaining the quality of voltage on the overall system and for the voltage distortion at the PCC. Excessive harmonic levels in voltage or current in the utility system can result in increased equipment heating, equipment malfunction and premature equipment failure, communication interference, fuse blowing in capacitor banks and customer equipment and process problems. Rizy et al (2003), has discussed about implementation of ANN control strategy. But unfortunately, the methodology adopted by them has some serious drawbacks. ANNs may not be suitable for a large distribution system since many smaller subsystems are required and the training time becomes excessive. However, once networks are trained, iterative calculations are no longer required and a fast solution for a given set of inputs can be provided. Suresh Mikkili et al (2011) has discussed about implementation of fuzzy control optimization approach. It is very simple and naturally fast as compared to other optimization methods. However, for some problems the procedure might get trapped in a local optimal point and fail to converge to the global (or near global) optimal solution. In order to sustain the constant frequency in the utility, utilized the Fuzzy Logic Controller based constant frequency UPFC. A Constant Frequency (CF) UPQC is composed of a UPQC and a matrix converter based frequency changer. UPQC is a combination of series active and shunt active filter. The series active filter and shunt active filter have been employed to compensate the voltage, current imbalance and harmonics. The Frequency Converter (matrix converter) has been used to control the supply frequency when it exceeds the power quality limit. Therefore, in order to overcome the flaws in the above mentioned control, hysteresis control strategies are used for better performance. When

4 69 the distortion levels on the utility system cause a problem, the proposed mitigation measures need to be implemented. In order to reduce the harmonics injected into power system by PV-UPQC, harmonics reduction technique is developed. 4.1 PROCEDURES FOR HARMONICS REDUCTION USING UPQC WITH DIFFERENT CONTROLLERS The shunt inverter filter using ANN current controller as discussed by Jeno Paul et al (2011), is essentially a cluster of suitably interconnected nonlinear elements of very simple form that possess the ability of learning and adaptation. These networks are characterised by their topology, the way in which they communicate with their environment, the manner in which they are trained and their ability to process information. Their ease of use, inherent reliability and fault tolerance has made ANNs a viable medium for control. An alternative to fuzzy controllers in many cases, neural controllers share the need to replace hard controllers with intelligent controllers in order to increase control quality. A feed forward neural network works as compensation signal generator. This network is designed with three layers. The input layer with seven neurons, the hidden layer with 21 neurons and the output layer with 3 neurons. Activation functions chosen are tan sigmoidal and pure linear in the hidden and output layers respectively. The training algorithm used is Levenberg Marquardt Back Propagation (LMBP). The compensator output depends on input and its evolution. The chosen configuration has seven inputs, three each for reference load voltage and source current respectively and one for output of error PI controller. The neural network trained for giving fundamental reference currents output. The signals thus obtained are compared in a

5 70 current controller to give switching signals. The block diagram of ANN compensator is shown in Figure 4.1. Source currents Figure 4.1 Block diagram of ANN-based compensator Fuzzy Controller Rama Rao et al (2010), has discussed the implementation of fuzzy control optimization approach. Figure 4.2 shows the block diagram of the fuzzy logic control scheme. The control scheme consists of fuzzy controller, limiter and three phase sine wave generator for reference current generation and generation of switching signals. The peak value of reference currents is estimated by regulating the DC link voltage. In order to implement the control algorithm of a shunt active power filter in a closed loop, the dc capacitor voltage V DC is sensed and then compared with the desired reference value V DC-ref. The error signal V DC-error = V DC-ref V DC is passed through Butterworth design based LPF with a cut off frequency of 50 Hz, that pass only the fundamental component. The error signal e(n) and integration of error signal Ie(n) are used as inputs for fuzzy processing. The output of the fuzzy logic controller limits the magnitude of peak reference current I max. This current takes care of the active power demand of the non-linear load and losses in the distribution system. The switching signals for the PWM inverter are generated by comparing the actual source

6 71 currents (i sa,i sb,i sc ) with the reference current (i sa *,i sb *,i sc *) The output of the fuzzy controller is estimating the magnitude of peak reference current I max. This current I max comprises of active power demand of the non-linear load and losses in the distribution system. The peak reference current is multiplied with PLL output for determining the desired reference current. (a) (b) Figure 4.2 (a) and (b) Control block diagram of fuzzy controller Proposed PI with Hysteresis Controller The proposed control strategy, described in section and shown in figure 3.3, ensures fast elimination of higher order current harmonics of the load. Hysteresis controller is designed for controlling the switching of

7 72 the shunt inverter. Based on the active power demand of the load, a suitable sinusoidal reference is selected for the incoming utility current and in addition, appropriate hysteresis band is selected. Narrower hysteresis band ensures higher THD elimination, at the cost of higher switching frequency of the inverter. Suitable trade off in design is required to optimize all criteria. The constant bandwidth hysteresis current control technique is widely used in voltage-source grid connected inverters. The hysteresis current control block diagram is shown in figure 4.3 The measured phase current (i A ) is subtracted from reference current (i Aref ), and current error (i error ) is obtained. This error is compared with hysteresis band and switching pulses are generated. The bandwidth value (h) is constant and hysteresis control restricts the current in the band. (a) (b) Figure 4.3 (a) and (b) Hysteresis current control and waveforms

8 73 Hysteresis current controller compares the current error with lower and upper hysteresis band. For phase- A, if i Aerror > +h, upper switch is ON, and i A increases. If i Aerror < -h, upper switch is OFF. As discussed earlier, the dc link voltage ideally should not decay, unless some active power loss occurs in the PV-UPQC. Therefore, the deviation of the DC link voltage acts as a measure of active power requirement from utility supply. The error is processed through a PI controller and a suitable sinusoidal reference signal in phase with the supply voltage is multiplied with the output of the PI controller, to generate the reference current for the supply. Hysteresis band is imposed on top and bottom of this reference current. The width of the hysteresis band is adjusted such that the supply current THD remains within that specified by the standards. As the supply current hits the upper or lower band, appropriate switching of the shunt inverter takes place so as to compel the supply current to remain within the band, by either aiding its dc link voltage to utility supply Simulation Parameter The three-phase PV- UPQC system simulation model is described in section 3.8 and shown in figure 3.6. In the simulation model, the following data parameters are used for system simulation. The source voltage is 230V in rms (325 peak voltage). A linear load of 6 KW and 4.5 KVAR is connected to the system, in addition to a nonlinear load of 5 KW and 3.75 KVAR. The DC link capacitor of 2000 F is connected between two inverters mh is the value of both shunt and series interface inductors. The filter capacitors of the series and shunt branches are 140 F and 20 F, respectively. A 4 damping resistor is connected in series with the shunt filter capacitor. Coupling transformers are used to connect the series and shunt active filters to the PCC.

9 RESULTS AND DISCUSSION The three-phase PV- UPQC system simulation model is described in section 3.8 and is shown in figure 3.6. The results obtained using the simulation model is presented in this section. The PV-UPQC model is simulated with following case studied: Unbalanced supply voltage and nonlinear loads with sag Unbalanced supply voltage and liner and nonlinear loads without sag Balanced supply voltage and liner and nonlinear loads with sag Unbalanced Supply Voltage and Nonlinear Loads with Sag The supply voltages are unbalanced, distorted and undergoing 30% sag as shown in figure 4.4(a). The nonlinear load is connected in this case to study the PV-UPQC steady-state performance. It is investigated and the simulation results are illustrated in figures 4.4(a) to 4.4(f) and figures 4.5(a) to 4.5(d). Case Study 1: Current No Sag Sag No Sag Time(s) Figure 4.4(a) Supply voltage with sag

10 75 Figure 4.4(b) Load current Figure 4.4(c) Load current (THD=14.3%) Figure 4.4 (d) Current injected by shunt active filter

11 76 Figure 4.4 (e) Supply current (THD=1.15%) Figure 4.4(f) Phase A Supply, Load and Injected currents Figure 4.4 (c) shows the load currents, which are highly distorted. The THD is 14.3%, whereas according to IEEE Standard they should not exceed 5% in our case. The effects of the injection of compensating currents are shown in figure 4.4 (d). Figure 4.4(e) shows the harmonics minimization sinusoidal wave (THD=1.15%), which fulfills the 5% stipulated by the IEEE standard. From figure 4.5 (e), the supply current

12 77 is in-phase with the load voltage, which is due to the in-phase series voltage injection. The injection is in-phase with the fundamental of the supply voltage. Thus, no reactive power is drawn from the supply. In figure 4.4 (f), the supply current, load current and injected current of are plotted together. If the injected current wave is subtracted from the load current wave, the result will be the supply current wave. Case Study 1: voltage Figure 4.5 (a) Supply voltages (THD=7.7%) Figure 4.5 (b) Voltages injected by series active filter

13 78 Figure 4.5 (c) Load voltage (THD=0.7%) Figure 4.5 (d) DC link voltages Figure 4.5 (e) Phase A load voltage and supply current

14 79 Figure 4.5(f) Phase A supply voltages, injected and load voltages From figure 4.5 (a), the supply voltages are unbalanced, distorted (THD=7.7%) and undergoing a sag. The series compensator injects voltages as shown in figure 4.5 (b). Due to this series compensation, the voltages on the load side are balanced sinusoidal. Figure 4.5(c) shows THD of 0.7%, which is much below the 5% limit stipulated by the IEEE Standard. It can be seen from figure 4.5 (c) that the load voltages are kept at the nominal level of 325 volts. The load and injected voltages for phase A are plotted together. The sum of the injected voltage and the supply voltage is the load voltage. In figure 4.5 (d), the concept of dc link voltage has been illustrated. The shunt compensator is connected at 0.02s which causes a drop in dc link voltage. After the sag from 0.02 s to 0.5s, the dc link voltage is restored. From figure 4.5 (d), it is observed that the average dc link voltage is kept constant at 400 V.

15 80 Case Study Linear and nonlinear loads without sag The supply voltages, as shown in figure 4.6(a), are unbalanced and distorted (the 5th harmonic is present) but there is no sag this time. The nonlinear load is permanently connected and the linear load is connected at 0.2s and disconnected at 0.5s. In this case study, the PV-UPQC dynamic performance at load change is investigated and the simulation results are illustrated through the figures 4.6 to Case Study 2: load currents Figure 4.6 (a) Load current dynamics

16 81 Figure 4.6 (b) Load current with nonlinear load (THD =14.4%) Figure 4.6 (c) Load current with Nonlinear and linear loads (THD =7.9%)

17 82 Figure 4.6 (d) Load current with Nonlinear load (THD = 14.4%) The simulated duration is composed of three sub-intervals: 0 s to 0.2 s, only with the nonlinear load connected to the system 0.2 s to 0.5 s, with both the linear and nonlinear loads connected to the system 0.5 s to 0.8 s, only with the nonlinear load is connected to the system For clarity, the load current waveforms, shown in figure 4.6(a), for each of these three subintervals is zoomed in figures 4.6 (b) to 4.6 (d). The injected and supply currents are shown in figures 4.7 and 4.8. The load current changes are reflected in both injected and supply currents. A change in the load causes the system to go through a transient period after which the supply currents become balanced sinusoids, as shown in figures 4.8(b) to 4.8(d), in phase with the load voltage as shown in figure Thus, the PV-UPQC adjusts the injected current according to the load condition, ensuring that, in steady-state, the supply currents are always balanced sinusoids and no reactive power is drawn from the supply.

18 83 25 Linear and Nonlinear loads Nonlinear load Nonlinear load Time(s) Figure 4.7 (a) Injected current dynamics Figure 4.7 (b) Injected current with nonlinear load

19 84 Figure 4.7(c) Injected current with linear and nonlinear loads Figure4.7 (d) Injected current for nonlinear load Figure 4.8(a) Supply current with dynamics

20 85 Figure 4.8 (b) Source current with nonlinear load (THD =2.4%) Figure 4.8 (c) Source current with nonlinear and linear loads (THD =1.3%) Figure 4.8(d) Source current with nonlinear load (THD=2.4%)

21 86 During the entire simulation period (from 0s to 0.8 s), the supply voltages are unbalanced and distorted (THD=5.05%), as shown in figure 4.9 (a). The injected voltage by the series compensator is shown in figure 4.9 (b). Due to this series compensation, the voltages on the load side are balanced sinusoidal waveforms, as shown in figure 4.9(c), with THD 1%, which is much lower than the 5% limit recommended by IEEE Standard From figure 4.9(c), it can be seen that the load voltages are kept at the nominal level (325 V). Figure 4.9 (a) Supply voltage (THD = 5.05%) Figure 4.9 (b) Inverter injected voltage

22 87 Figure 4.9 (c) Load voltage (THD=1%) Figure 4.9 (d) DC link Voltage The DC link voltage dynamics is shown in figure 4.6(d).The load current increases at 0.2s and decreases at 0.5s. This is due to the connection or disconnection of the linear load. Since it takes a finite time interval to calculate the new reference current, the shunt compensator cannot immediately respond to the load change. Some settling time is required to stabilize the controlled parameter around its reference. During transient periods, the DC link capacitor is supplying active power in order to ensure the power balance.

23 88 Figure 4.10 (a) Load voltage and load current with nonlinear load Figure 4.10(b) Load voltage and load current with nonlinear and linear loads Due to this transient supply of active power, the dc link voltage decreases during the sag at the time interval of 0.2s 0.4s and the swell in the voltage occurs during the interval 0.5s 0.7s. After clearing the

24 89 interruptions, as illustrated through the figure 4.6 (d), the dc link voltage is restored back to its reference value (400 V). The shunt compensator is controlled in such a way that the supply current is in-phase with the fundamental of the supply voltage, which means that no reactive power is drawn from the supply. The fundamental of the series injected voltage is in-phase with the supply current, as shown in figure Case study Balanced linear and nonlinear loads with sag During the time interval from 0s to 0.8 s, both the linear and nonlinear loads are connected with 30% of supply voltage sag, which is generated at 0.2 s and cleared at 0.5 s. During the same time, the supply voltage becomes balanced and distorted (the 5th harmonic is present). The supply voltages are as shown in figure 4.11(a) and figure 4.11 (e) Supply current during the sag with fuzzy logic control. In this case study, the dynamic performance of the PV-UPQC system, at the occurrence or clearance of the supply voltage sag, is investigated and the simulation results are illustrated through figures 4.11 to The supply current is increased considerably during the sag, as shown in figure During the sag, the load should draw the same amount of power from the supply as it does in the normal condition (nominal power). Since the supply voltage is decreased during the sag, the supply current should be accordingly increased in order to provide the same nominal power to the load.

25 90 Figure 4.11 (a) Supply current with dynamics Figure 4.11 (b) Supply current before sag (THD=3.8%) Figure 4.11(c) Supply current during the sag (THD=1.1%)

26 91 Figure 4.11 (d) Supply current after the clearance sag (THD =3.8%) Figure 4.11 (e) Supply current during the sag with fuzzy logic control (THD=1.2%) The supply voltage dynamics are shown in figure 4.12(a). During the sag condition from 0.2 s to 0.5s, the supply voltages undergo 60% sag. They are unbalanced and distorted with THD of 7.7%, as shown in figure 4.12 (c). During the other two sub-intervals from 0s to 0.2s and from 0.5s to 0.8s, the supply voltages are balanced sinusoidal waveforms at nominal level (325V), as shown in the figures 4.12 and 4.13.

27 No Sag Sag No Sag Time(s) Figure 4.12 (a) Supply voltage with dynamics Figure 4.12 (b) Supply voltage before sag (THD=0.55%)

28 93 Figure 4.12 (c) Supply voltage during sag (THD=7.7%) Figure 4.12 (d) Load voltage after the clearance of sag (THD=0.55%) Figure 4.13 (a) Voltages injected during sag

29 94 Figure 4.13(b) DC link voltage during sag No sag Sag No sag Time(s) Figure 4.14 (a) Load voltage with dynamics Figure 4.14 (b) Load voltage before sag (THD=1.4%)

30 95 Figure 4.14 (c) Load voltage during sag (THD=0.75%) Figure 4.14 (d) Load voltage sag with ANN controller (THD=1.2%) During the supply voltage sag, the series compensator injects voltages, as shown in figure 4.14(a). Due to this series compensation, the voltages on the load side are balanced sinusoidal waveforms with THD of 0.75%, which is much lower than the 5% limit recommended by IEEE Standard , as shown in figure 4.14(c) and figure 4.14 (d) shows the load voltage sag with ANN controller. Figure 4.15 shows that the load voltages are kept at the nominal voltage throughout the simulation time interval.

31 96 The DC link voltage dynamics are shown in figure 4.13 (b). Due to the occurrence of the supply voltage sag at 0.2 s, the supply current is increased. With the clearance of sag at 0.5s, the supply current decreased. Since it takes a finite time interval to calculate the new reference current, the shunt compensator cannot immediately respond to this supply current change. Some settling time is required to stabilize the controlled parameter around its reference. Consequently, after the occurrence or clearance of the sag instants (0.2s and 0.5s), there exist some transient periods during which the DC link capacitor is supplying active power in order to ensure the balanced power. Due to this transient supply of active power, the DC link voltage is undergoing sag during the time interval 0.2 s 0.4 s and a swell during the interval 0.5 s 0.7 s. From figure 4.14 (d), it can be observed that after clearing the transients, the DC link voltage is restored back to its reference value (400 V). Figure 4.15 (a) without sag the voltage and current

32 97 Figure 4.15 (b) during sag the voltage and current Figure 4.15(c) after clearance of the sag voltage and current Due to unity power factor compensation throughout the entire simulated period, the supply current is in phase with the fundamental of the supply voltage, as shown in figure 4.15, which implies that no reactive power is drawn from the supply. A complete summary of the results with and without the proposed system is given in table 4.1 and in figures 4.16 to 4.21.

33 98 Table 4.1 Comparative percentage THD voltage and current with and without PV-UPQC system. Case study No s Events Without PV- UPQC Current Voltage %THD %THD With PV-UPQC Current Voltage %THD %THD Unbalanced supply voltage nonlinear loads with sag Unbalanced supply voltage linear and nonlinear loads without sag Balanced supply voltage linear and nonlinear loads with sag

34 99 Figure 4.16 Percentage THD with and without PV-UPQC for nonlinear loads with sag and unbalanced supply voltage Figure 4.17 Percentage THD with and without PV-UPQC for unbalanced supply voltage linear without sag and nonlinear loads

35 100 Figure 4.18 Percentage THD with and without PV-UPQC for balanced supply voltage with sag and linear and nonlinear loads Figure 4.19 Percentage THD with and without PV-UPQC for unbalanced supply voltage with sag and nonlinear loads

36 101 Figure 4.20 Percentage THD with and without PV-UPQC for unbalanced supply voltage without sag with liner and nonlinear loads Figure 4.21 Percentage THD with and without PV-UPQC for balanced supply voltage with sag and nonlinear loads

37 102 Table 4.2 THD values of load current with fuzzy logic control Rama Rao et al (2010) and proposed PI with hysteresis control THD load current without controller Fuzzy logic control THD load currents Proposed PI with hysteresis control THD load currents 14.3% 1.2% 1.1% Figure 4.22 Percentage THD for fuzzy logic control and proposed hysteresis control

38 103 Table 4.3 THD value of load voltage Artificial Neural Networks (ANN) Jeno Paul et al (2011) and proposed PI with hysteresis control THD for load voltage without controller ANN control THD load voltage PI with Hysteresis control THD load voltage 7.7% 1.2% 0.55% Figure 4.23 Percentage THD for ANN control and proposed hysteresis control The performance evaluation of PV-UPQC system associated with linear and nonlinear loads with sag using hysteresis control, in terms of the THD of the load current, is given in table 4.2. Comparing with the results of THD of 1.2% in the load current obtained using an ANN control by Jeno Paul et al (2011), the proposed hysteresis control has achieved a lower THD of 1.1%, which is shown in figure Comparing with the results of THD of 1.2% in the load voltage obtained using a fuzzy logic control by Rama Rao et al (2010), the proposed hysteresis control has achieved a lower THD of 0.55% as shown in table 4.3 and figure The analysis shows that the proposed

39 104 approach is more efficient with respect to ANN and fuzzy logic control strategies. On the basis of the research work presented in this chapter, a paper entitled Photovoltaic based improved power quality using unified power quality conditioner has been published in the International Journal of Electrical Engineering Vol.4, No.2, pp , July On the basis of the research work presented in this chapter, a paper entitled Power Quality Improvement using Photovoltaic Compensation Techniques has been published in the International Journal of Power Engineering Vol.2, No.1, pp , June CONCLUSION In this chapter, three significant case studies of an unbalanced system with linear and nonlinear loads are presented. The first case is supply voltage sag with nonlinear loads. The second case is linear and nonlinear loads without sag. The third case is linear and nonlinear loads with sag. The simulation results shows that the linear and nonlinear loads are connected the voltage becomes unacceptably distorted due to the switching frequencies in the supply current. For comparative analysis of the proposed PI with hysteresis control, the fuzzy logic and ANN control strategies of other researchers have been considered. Among various control techniques, the proposed hysteresis current control is the most preferable technique for shunt compensation. The hysteresis control method has simpler implementation, enhanced system stability and fast response. The proposed approach ensures that the unwanted harmonics are reduced compared to the other control strategies.

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 09 (September. 2014), V3 PP 11-20 www.iosrjen.org A Versatile Control Scheme for UPQC for Power Quality Improvement

More information

Literature Review for Shunt Active Power Filters

Literature Review for Shunt Active Power Filters Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller

More information

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems

More information

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Application of Fuzzy Logic Controller in Shunt Active Power Filter IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 11 April 2016 ISSN (online): 2349-6010 Application of Fuzzy Logic Controller in Shunt Active Power Filter Ketan

More information

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION 1 Arsha.S.Chandran, 2 Priya Lenin 1 PG Scholar, 2 Assistant Professor 1 Electrical & Electronics Engineering 1 Mohandas College of Engineering

More information

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy Abstract This paper presents a new unified power-quality conditioning system (MC-UPQC), capable

More information

CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC

CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC 90 CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC 5.1 INTRODUCTION This chapter deals with the performance comparison between a closed loop and open loop UPFC system on the aspects of power quality. The UPFC

More information

2020 P a g e. Figure.2: Line diagram of series active power filter.

2020 P a g e. Figure.2: Line diagram of series active power filter. Power Quality Improvement By UPQC Using ANN Controller Saleha Tabassum 1, B.Mouli Chandra 2 (Department of Electrical & Electronics Engineering KSRM College of Engineering, Kadapa.) (Asst. Professor Dept

More information

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 86 CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 5.1 INTRODUCTION Distribution systems face severe power quality problems like current unbalance, current harmonics, and voltage unbalance,

More information

CHAPTER 7 CONCLUSIONS AND FUTURE SCOPE

CHAPTER 7 CONCLUSIONS AND FUTURE SCOPE CHAPTER 7 CONCLUSIONS AND FUTURE SCOPE 7.1 INTRODUCTION A Shunt Active Filter is controlled current or voltage power electronics converter that facilitates its performance in different modes like current

More information

NEURAL NETWORK BASED UNIFIED POWER QUALITY CONDITIONER

NEURAL NETWORK BASED UNIFIED POWER QUALITY CONDITIONER Vol.2, Issue.1, Jan-Feb 2012 pp-359-365 ISSN: 2249-6645 NEURAL NETWORK BASED UNIFIED POWER QUALITY CONDITIONER N.Ramchandra 1, M.Kalyanchakravarthi 2 1 (Student, Department of Electrical and Electronics

More information

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System International Journal of Electrical Engineering. ISSN 0974-2158 Volume 5, Number 7 (2012), pp. 853-862 International Research Publication House http://www.irphouse.com A Novel FPGA based PWM Active Power

More information

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti

More information

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 3, Issue 8 (September 2012), PP. 16-20 Implementation of SRF based Multilevel Shunt

More information

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System 1 G.Balasundaram, 2 Dr.S.Arumugam, 3 C.Dinakaran 1 Research Scholar - Department of EEE, St.

More information

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method Vol.2, Issue.3, May-June 2012 pp-682-686 ISSN: 2249-6645 Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method C. Prakash 1, N. Suparna 2 1 PG Scholar,

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD T PRAHLADA 1, P SUJATHA 2, P BHARATH KUMAR 3 1PG Scholar,

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Power Quality improvement of a three phase four wire system using UPQC

Power Quality improvement of a three phase four wire system using UPQC International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Volume: 2 Issue: 4 July-215 www.irjet.net p-issn: 2395-72 Power Quality improvement of a three phase four wire system

More information

Chapter 2 Shunt Active Power Filter

Chapter 2 Shunt Active Power Filter Chapter 2 Shunt Active Power Filter In the recent years of development the requirement of harmonic and reactive power has developed, causing power quality problems. Many power electronic converters are

More information

International Journal of Research (IJR) e-issn: , p- ISSN: X Volume 2, Issue 09, September 2015

International Journal of Research (IJR) e-issn: , p- ISSN: X Volume 2, Issue 09, September 2015 A Novel Multi Level Converter Unified Power-Quality (MC- UPQC) Conditioning System on Line Loading, Losses, and Voltage Stability of Radial Distribution Systems Abstract: Popuri Krishna Chaitanya* 1 ;Tajuddin

More information

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 10, Issue 7 (July 2014), PP.01-15 Reduction of Voltage Imbalance in a Two Feeder

More information

Improvement of Power Quality Using a Hybrid Interline UPQC

Improvement of Power Quality Using a Hybrid Interline UPQC Improvement of Power Quality Using a Hybrid Interline UPQC M.K.Elango 1, C.Vengatesh Department of Electrical and Electronics Engineering K.S.Rangasamy College of Technology Tiruchengode, Tamilnadu, India

More information

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

Voltage Quality Enhancement in an Isolated Power System through Series Compensator International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 12, Issue 6 (June 2016), PP.20-26 Voltage Quality Enhancement in an Isolated Power

More information

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p. Preface p. xv Acknowledgements p. xix Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p. 6 Power Quality Monitoring p. 7 Power

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER Rajesh Kr. Ahuja 1, Aasha Chauhan 2, Sachin Sharma 3 Rajesh Kr. Ahuja Faculty, Electrical & Electronics Engineering Dept.

More information

A Power Control Scheme for UPQC for Power Quality Improvement

A Power Control Scheme for UPQC for Power Quality Improvement A Power Control Scheme for UPQC for Power Quality Improvement 1 Rimpi Rani, 2 Sanjeev Kumar, 3 Kusum Choudhary 1 Student (M.Tech), 23 Assistant Professor 12 Department of Electrical Engineering, 12 Yamuna

More information

CONCLUSIONS AND SUGGESTIONS FOR FUTURE WORK

CONCLUSIONS AND SUGGESTIONS FOR FUTURE WORK CHAPTER 7 CONCLUSIONS AND SUGGESTIONS FOR FUTURE WORK The objective of this work is to design, fabricate and test a harmonic filter configuration, with simple and effective control algorithm under both

More information

Enhancement of Power Quality Using Advanced Series Active Power Filters

Enhancement of Power Quality Using Advanced Series Active Power Filters Enhancement of Power Quality Using Advanced Series Active Power Filters Manoj siva kumar 1, P.Rayalakshmi 2 Associate Professor, Dept. of EEE, PBRVITS, Kavali, SPSR Nellore, A.P, India 1 M.Tech Student,

More information

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction Anju Yadav 1, K. Narayanan 2, Binsy Joseph 3 1, 2, 3 Fr. Conceicao Rodrigues College of Engineering, Mumbai, India

More information

CHAPTER 3 DESIGN OF A PV-UPQC SYSTEM FOR VOLTAGE SAG AND SWELL COMPENSATION

CHAPTER 3 DESIGN OF A PV-UPQC SYSTEM FOR VOLTAGE SAG AND SWELL COMPENSATION 21 CHAPTER 3 DESIGN OF A PV-UPQC SYSTEM FOR VOLTAGE SAG AND SWELL COMPENSATION INTRODUCTION The recent increase in the use of non-linear loads creates many power quality problems such as oltage sag, swell

More information

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013 A Statcom-Control Scheme for Power Quality Improvement of Grid Connected Wind Energy System B.T.RAMAKRISHNARAO*, B.ESWARARAO**, L.NARENDRA**, K.PRAVALLIKA** * Associate.Professor, Dept.of EEE, Lendi Inst.Of

More information

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating P.Ankineedu Prasad 1, N.Venkateswarlu 2. V.Ramesh 3, L.V.Narasimharao 4 Assistant Professor 12 & Professor 4& Research Scholar

More information

TRANSFORMER LESS H6-BRIDGE CASCADED STATCOM WITH STAR CONFIGURATION FOR REAL AND REACTIVE POWER COMPENSATION

TRANSFORMER LESS H6-BRIDGE CASCADED STATCOM WITH STAR CONFIGURATION FOR REAL AND REACTIVE POWER COMPENSATION International Journal of Technology and Engineering System (IJTES) Vol 8. No.1 Jan-March 2016 Pp. 01-05 gopalax Journals, Singapore available at : www.ijcns.com ISSN: 0976-1345 TRANSFORMER LESS H6-BRIDGE

More information

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller M. Ajay Department of Electronics and Electrical Engineering, Avanthi institute

More information

Performance of DVR under various Fault conditions in Electrical Distribution System

Performance of DVR under various Fault conditions in Electrical Distribution System IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 8, Issue 1 (Nov. - Dec. 2013), PP 06-12 Performance of DVR under various Fault conditions

More information

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, PP 20-26 www.iosrjournals.org Shunt Active Power Filter based on SRF theory and Hysteresis Band Current

More information

B.Tech Academic Projects EEE (Simulation)

B.Tech Academic Projects EEE (Simulation) B.Tech Academic Projects EEE (Simulation) Head office: 2 nd floor, Solitaire plaza, beside Image Hospital, Ameerpet Ameerpet : 040-44433434, email id : info@kresttechnology.com Dilsukhnagar : 9000404181,

More information

Kalman Filter Based Unified Power Quality Conditioner for Output Regulation

Kalman Filter Based Unified Power Quality Conditioner for Output Regulation Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 4, Number 3 (2014), pp. 247-252 Research India Publications http://www.ripublication.com/aeee.htm Kalman Filter Based Unified Power

More information

IMPORTANCE OF VSC IN HVDC

IMPORTANCE OF VSC IN HVDC IMPORTANCE OF VSC IN HVDC Snigdha Sharma (Electrical Department, SIT, Meerut) ABSTRACT The demand of electrical energy has been increasing day by day. To meet these high demands, reliable and stable transmission

More information

p. 1 p. 6 p. 22 p. 46 p. 58

p. 1 p. 6 p. 22 p. 46 p. 58 Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for

More information

Power Quality Analysis: A Study on Off-Line UPS Based System

Power Quality Analysis: A Study on Off-Line UPS Based System Power Quality Analysis: A Study on Off-Line UPS Based System P.K.DHAL Department of Electrical and Electronics Engineering VelTech Dr.RR&Dr.SR Technical University # 42 Avadi- VelTech Road, Chennai-62

More information

International Journal of Advance Research in Engineering, Science & Technology

International Journal of Advance Research in Engineering, Science & Technology Impact Factor (SJIF): 3.632 International Journal of Advance Research in Engineering, Science & Technology e-issn: 2393-9877, p-issn: 2394-2444 (Special Issue for ITECE 2016) Harmonic Mitigation of Fluctuating

More information

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive B. Mohan Reddy 1, G.Balasundaram 2 PG Student [PE&ED], Dept. of EEE, SVCET, Chittoor

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

Power Quality Improvement using Active shunt Power filter using PI Controller

Power Quality Improvement using Active shunt Power filter using PI Controller Power Quality Improvement using Active shunt Power filter using PI Controller Viki S. Patel M.tech Scholar Electrical Engineering, U.V Patel College of Engineering, Kherva, India patel.viki4@gmail.com

More information

ISSN Vol.04,Issue.16, October-2016, Pages:

ISSN Vol.04,Issue.16, October-2016, Pages: WWW.IJITECH.ORG ISSN 2321-8665 Vol.04,Issue.16, October-2016, Pages:3000-3006 Active Control for Power Quality Improvement in Hybrid Power Systems VINUTHAS 1, DHANA DEEPIKA. B 2, S. RAJESH 3 1 PG Scholar,

More information

Indirect Current Control of LCL Based Shunt Active Power Filter

Indirect Current Control of LCL Based Shunt Active Power Filter International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 3 (2013), pp. 221-230 International Research Publication House http://www.irphouse.com Indirect Current Control of LCL Based

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

Mitigation of Voltage Sag/Swell Using UPQC

Mitigation of Voltage Sag/Swell Using UPQC Mitigation of Voltage Sag/Swell Using UPQC 1 Rajat Patel, 2 Prof.Maulik A. Chaudhari 1 PG Scholar, 2 Assistant Professor Electrical Department, Government engineering college, Bhuj Gujarat Technological

More information

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

Harmonics Elimination Using Shunt Active Filter

Harmonics Elimination Using Shunt Active Filter Harmonics Elimination Using Shunt Active Filter Satyendra Gupta Assistant Professor, Department of Electrical Engineering, Shri Ramswaroop Memorial College of Engineering and Management, Lucknow, India.

More information

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 36-41 Analysis, Modeling and Simulation of Dynamic Voltage

More information

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC 1 G.ANNAPURNA, 2 DR.G.TULASIRAMDAS 1 G.Narayanamma Institute Of Technology And Science (For Women) Hyderabad, Department Of EEE 2

More information

Mitigation of Power system Disturbance by Using MC-UPQC with PI, ANN & FUZZY Controller Technique

Mitigation of Power system Disturbance by Using MC-UPQC with PI, ANN & FUZZY Controller Technique Mitigation of Power system Disturbance by Using MC-UPQC with PI, ANN & FUZZY Controller Technique Dr.K.Ravichandrudu 1,D.Sahitya Devi 2, P.Yohan Babu 3 1,2,3 Krishnaveni Engineering College for Women,Narasaraopet,Guntur,AP

More information

Fuzzy Logic Controller Based Three-phase Shunt Active Filter for Line Harmonics Reduction

Fuzzy Logic Controller Based Three-phase Shunt Active Filter for Line Harmonics Reduction Journal of Computer Science 3 (: 76-8, 7 ISSN 549-3636 7 Science Publications Fuzzy Logic Controller Based Three-phase Shunt Active Filter for Line Harmonics Reduction C.Sharmeela, M.R.Mohan, G.Uma, J.Baskaran

More information

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 651-660 Research India Publications http://www.ripublication.com/aeee.htm Design and Simulation of Three Phase

More information

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults Enhancement of Power Quality in Distribution System Using D-Statcom for Different s Dr. B. Sure Kumar 1, B. Shravanya 2 1 Assistant Professor, CBIT, HYD 2 M.E (P.S & P.E), CBIT, HYD Abstract: The main

More information

Unified Power Quality Conditioner (UPQC) for Power Distribution Systems

Unified Power Quality Conditioner (UPQC) for Power Distribution Systems Unified Power Quality Conditioner (UPQC) for Power Distribution Systems Shyama P. Das Department of Electrical Engg. IIT Kanpur E-mail: spdas@iitk.ac.in Introduction Motivation Design, Simulation and Hardware

More information

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 4 (2013), pp. 473-483 International Research Publication House http://www.irphouse.com A Simple Control Algorithm for Three-Phase

More information

Power Quality Improvement using Shunt Passive Filter

Power Quality Improvement using Shunt Passive Filter Power Quality Improvement using Shunt Passive Filter Assistant Professor, Department of Electrical Engineering Bhutta Group of Institutions, India Abstract: The electricity supply would, ideally, show

More information

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES P. K. Mani 1 and K. Siddappa Naidu 2 1 Department of Electrical and Electronics Engineering, Vel Tech Multitech Dr. Rangarajan Dr. Sakunthala Engineering

More information

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR Rongali. Shiva Kumar P.G Student Scholar, Department of Electrical & Electronics Engineering, Gokul Group Of Institutions Abstract:

More information

Unified Power Quality Conditioner (UPQC) using MATLAB Hiya Divyavani, Prof.(Dr.)Mohd.Muzzam Noida International University ----------------------------------------------------------------- Abstract: The

More information

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers Akashdeep Soni 1, Mr. Vikas Kumar 2 1 M.Tech (Control System) Scholar, Department

More information

Power Quality Improvement Using Shunt Active FilterWith Fuzzy Logics

Power Quality Improvement Using Shunt Active FilterWith Fuzzy Logics Power Quality Improvement Using Shunt Active FilterWith Fuzzy Logics Kamalesh sharma, Sunil kumar goyal, Nagendra kumar swarnkar Abstract Power quality is a very important issue. Non-linear loads and semi-conductor

More information

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER Bhargav R. Gamit 1, Sanjay R. Vyas 2 1PG Scholar, EE Dept., LDRP-ITR, Gandhinagar, Gujarat, India. 2Head of Department, EE Dept.,

More information

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter B.S.Nalina 1 Ms.V.J.Vijayalakshmi 2 Department Of EEE Department Of EEE 1 PG student,skcet, Coimbatore, India

More information

Lavopa, Elisabetta (2011) A novel control technique for active shunt power filters for aircraft applications. PhD thesis, University of Nottingham.

Lavopa, Elisabetta (2011) A novel control technique for active shunt power filters for aircraft applications. PhD thesis, University of Nottingham. Lavopa, Elisabetta (211) A novel control technique for active shunt power filters for aircraft applications. PhD thesis, University of Nottingham. Access from the University of Nottingham repository: http://eprints.nottingham.ac.uk/1249/1/elisabetta_lavopa_thesis.pdf

More information

Application of Model Predictive Control in PV-STATCOM for Achieving Faster Response

Application of Model Predictive Control in PV-STATCOM for Achieving Faster Response Application of Model Predictive Control in PV-STATCOM for Achieving Faster Response Sanooja Jaleel 1, Dr. K.N Pavithran 2 1Student, Department of Electrical and Electronics Engineering, Government Engineering

More information

Harmonic Reduction in Five Level Inverter Based Dynamic Voltage Restorer

Harmonic Reduction in Five Level Inverter Based Dynamic Voltage Restorer Research Journal of Applied Sciences, Engineering and Technology 2(8): 789-797, 2010 ISSN: 2040-7467 Maxwell Scientific Organization, 2010 Submitted date: September 27, 2010 Accepted date: November 18,

More information

UPQC (Unified Power Quality Conditioner)

UPQC (Unified Power Quality Conditioner) A Unified Power Quality Conditioner (UPQC) is a device that is similar in construction to a Unified Power Flow Conditioner (UPFC). The UPQC, just as in a UPFC, employs two voltage source inverters (VSIs)

More information

ISSN Vol.03,Issue.07, August-2015, Pages:

ISSN Vol.03,Issue.07, August-2015, Pages: WWW.IJITECH.ORG ISSN 2321-8665 Vol.03,Issue.07, August-2015, Pages:1276-1281 Comparison of an Active and Hybrid Power Filter Devices THAKKALAPELLI JEEVITHA 1, A. SURESH KUMAR 2 1 PG Scholar, Dept of EEE,

More information

Enhancement of Power Quality with Multifunctional D-STATCOM Operated under Stiff Source for Induction Motor Applications

Enhancement of Power Quality with Multifunctional D-STATCOM Operated under Stiff Source for Induction Motor Applications International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume, Issue 2 (December 205), PP.72-79 Enhancement of Power Quality with Multifunctional

More information

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink Parag Datar 1, Vani Datar 2, S. B. Halbhavi 3, S G Kulkarni 4 1 Assistant Professor, Electrical and Electronics Department,

More information

CHAPTER 4 AN EFFICIENT ANFIS BASED SELF TUNING OF PI CONTROLLER FOR CURRENT HARMONIC MITIGATION

CHAPTER 4 AN EFFICIENT ANFIS BASED SELF TUNING OF PI CONTROLLER FOR CURRENT HARMONIC MITIGATION 92 CHAPTER 4 AN EFFICIENT ANFIS BASED SELF TUNING OF PI CONTROLLER FOR CURRENT HARMONIC MITIGATION 4.1 OVERVIEW OF PI CONTROLLER Proportional Integral (PI) controllers have been developed due to the unique

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter

Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter V.Balasubramanian 1, T.Rajesh 2, T.Rama Rajeswari 3 P.G. Student,

More information

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Comparison

More information

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK IMPROVED CONTROL METHOD OF GUPQC UNDER DISTORTED AND UNBALANCED LOAD CONDITION

More information

DYNAMIC VOLTAGE RESTORER FOR EFFICIENT DETECTION AND COMPENSATION OF VOLTAGE SAG USING ANN BASED LMS AS A NEW CONTROL STRATEGY

DYNAMIC VOLTAGE RESTORER FOR EFFICIENT DETECTION AND COMPENSATION OF VOLTAGE SAG USING ANN BASED LMS AS A NEW CONTROL STRATEGY Journal of Engineering Science and Technology Special Issue on Applied Engineering and Sciences, October (2014) 21-29 School of Engineering, Taylor s University DYNAMIC VOLTAGE RESTORER FOR EFFICIENT DETECTION

More information

Keyword: Distributed System, Filters, Harmonics, Power quality improvement, THD, UPQC and Voltage Harmonics.

Keyword: Distributed System, Filters, Harmonics, Power quality improvement, THD, UPQC and Voltage Harmonics. ISSN XXXX XXXX 2017 IJESC Research Article Volume 7 Issue No.5 Improvement of Power Quality in the Distribution System by Placement of UPQC Madhu Mathi.M. A 1, Sasiraja.R. M 2 PG Scholar 1, Faculty 2 Anna

More information

Power Quality Compensation by using UPFC

Power Quality Compensation by using UPFC ISSN: 2454-132X Impact factor: 4.295 (Volume 4, Issue 2) Available online at: www.ijariit.com Power Quality Compensation by using UPFC P. Madhumathi madhumathi9196@gmail.com Vivekanada College of Engineering

More information

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 6, Issue 4 (Jul. - Aug. 2013), PP 48-54 Modified three phase Unified Power Quality Conditioner

More information

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim

More information

Improving Passive Filter Compensation Performance With Active Techniques

Improving Passive Filter Compensation Performance With Active Techniques IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan

More information

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN 2250-155X Vol. 3, Issue 2, Jun 2013, 309-318 TJPRC Pvt. Ltd. PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID

More information

P. Sivakumar* 1 and V. Rajasekaran 2

P. Sivakumar* 1 and V. Rajasekaran 2 IJESC: Vol. 4, No. 1, January-June 2012, pp. 1 5 P. Sivakumar* 1 and V. Rajasekaran 2 Abstract: This project describes the design a controller for PWM boost Rectifier. This regulates the output voltage

More information

Key terms: Voltage, Phase Angle, FACTS, Multilevel Converter, Power Quality, STATCOM.

Key terms: Voltage, Phase Angle, FACTS, Multilevel Converter, Power Quality, STATCOM. Modeling and Analysis of Multi Level Voltage Source Inverter Based Statcom for Improving Power Quality *P.UPENDRA KUMAR, **J.ANAND KUMAR, **K.MANOHAR, **T.M.MANOHAR, **CH.S.K.CHAITANYA *Associate.Professor,

More information

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 04 September 2016 ISSN (online): 2349-6010 A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link

More information

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Phanikumar.Ch, M.Tech Dept of Electrical and Electronics Engineering Bapatla Engineering College, Bapatla,

More information

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review S.N. Bhalerao 1, P.J. Bhakre, C.O.Reddy 3 1 Student, Department of Electrical Engineering, MSS Collage Of Engineering,

More information

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION N.VANAJAKSHI Assistant Professor G.NAGESWARA RAO Professor & HOD Electrical & Electronics Engineering Department Chalapathi Institute of

More information

Implementation of UPQC for Voltage Sag Mitigation

Implementation of UPQC for Voltage Sag Mitigation Implementation of UPQC for Voltage Sag Mitigation C.H. Ram Jethmalani 1, V. Karthikeyan 2, and Narayanappa 3 1 Adhiyamaan College of Engineering, Hosur, India Email: malanisuryakumaran@gmail.com 2,3 Adhiyamaan

More information

Transient Stability Improvement of Multi Machine Power Systems using Matrix Converter Based UPFC with ANN

Transient Stability Improvement of Multi Machine Power Systems using Matrix Converter Based UPFC with ANN IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 04, 2015 ISSN (online): 2321-0613 Transient Stability Improvement of Multi Machine Power Systems using Matrix Converter

More information

Design and Control of Interline Unified Power Quality Conditioner for Power Quality Disturbances

Design and Control of Interline Unified Power Quality Conditioner for Power Quality Disturbances ISSN: 227881 Vol. 1 Issue 1, December- 212 Design and Control of Interline Unified Power Quality Conditioner for Power Quality Disturbances B.Sasikala 1, Khamruddin Syed 2 Department of Electrical and

More information