1 Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power quality and efficiency. Low Pass Harmonic Filters are often applied in commercial, industrial, institutional, military, mining, municipal, solar, wind turbine as well as many other environments. Product Benefits Summary PQI Low Pass ( LP ) Harmonic Filters provide many benefits including but not limited to the following: Extend equipment life by reducing transformer and motor internal temperatures Eliminate nuisance tripping of overcurrent protective devices (OCPDs) by reducing RMS and peak current Increase available power from existing sources by reducing kva demand Increase energy cost savings by reducing penalty losses in the facility power system Improve equipment performance by eliminating harmonic influence from other equipment connected to the system Increase true power factor by increasing distortion power factor thereby reducing kva consumption. Increase productivity and profits Popular Options PQI LP Harmonic Filters include several different installation options: Enclosure: NEMA 1, 3R, 4, 4X, 12, etc. Mounting: Fixed, Modular (Open), OEM Kit Phase Configurations: 3-phase or 1-phase Customized Assemblies: o Filter with Bypass o Filter with Capacitor Cut-Out o Other custom options upon request Open Panel Style Enclosed Style Suitability PQI LP Harmonic Filters may be applied in, but are not limited to, the following applications: Diode converter with or without internal inductance SCR converter with or without internal inductance Variable or constant torque applications Nonlinear loads supplied from inverter power sources Harmonics, Cause and Effect The Cause of Harmonics Harmonics are recurring sinusoidal waveform disturbances of varying frequency, typically in the range of Hz, that together form a distorted, nonsinusoidal waveform. Harmonics are a wasteful derivative of the AC to DC conversion process common in today s commercial and industrial power electronic equipment such as adjustable speed drives, welders, arc furnaces, battery charges, UPSs, computers, fluorescent lighting, etc. During the AC to DC conversion process, current is drawn in pulses by the on/off conducting of rectifier diodes. As a result of this switching action, a composite, non-sinusoidal current waveform is created which consists of individual harmonic frequencies including the fundamental. Electronic loads cause harmonic currents to flow, not just from the power source to the electronic loads themselves, but very often to other non-linear and linear loads connected throughout the same electrical distribution system.

2 Three-phase rectifiers containing two (2) diodes per phase, often referred to as 6-pulse, are common in three-phase power electronics and most often cause the formation of 5 th, 7 th, 11 th, 13 th,, etc. positive- and negative-sequence harmonics within the system. The harmonic number indicates the waveform frequency as a multiple of the fundamental frequency. The Effect of Harmonics As discussed previously, the various harmonic current frequencies that form a non-sinusoidal waveform flow individually as sine waves but together produce a distorted, composite waveform. Based on this fact, it is evident that the root-mean-square (RMS) value of the input current is dependent upon the magnitude of the various harmonic frequencies that comprise the load s input current waveform. Depending upon the severity of system harmonics, RMS current can increase by as much as 40% above the fundamental current. Clearly, harmonic currents distort the input current waveform which ultimately increases RMS current, kva demand and I 2 R losses in transformer windings and conductors. Furthermore, harmonic currents cause the degradation of equipment due to overheating and an overall reduction in true power factor. As harmonic currents flow through the system s impedances, they also cause distortion of the input voltage waveform at the particular frequencies that are present in the waveform thus increasing transformer core losses and decreasing each load s published efficiency. Harmonic currents diminish the quality of system electrical power and can cause equipment malfunction. In summary, current and voltage harmonics have a negative impact on a facility s bottom line. By eliminating harmonic distortion, load and system losses are reduced and overall performance is enhanced. Product Performance Characteristics PQI LP Harmonic Filter Options PQI offers two choices for LP Harmonic Filters Type 2 and Type 3. Use our standard three-stage, Type 3 LP Harmonic Filter when a guaranteed performance level of 5% THD I is required. Use our basic two-stage, Type 2 LP Harmonic Filter for those applications where internal inductance already exists as part of the load or when 8% - 12% THD I is acceptable. Harmonic Filtering Stages 1.) Input Stage This stage is intended to isolate the shunt stage from other harmonic sources connected to the same power source and to prevent power system resonance. This stage also protects the load and filter capacitors from transients. 2.) Output Stage This stage is intended to provide a precise amount of impedance to minimize the amount of harmonics produced by the load. This stage also reduces the harmonic burden placed on the shunt stage and prevents resonance between the shunt stage and the load. 3.) Shunt Stage This stage is intended to absorb residual harmonics remaining after the input and output stages have performed their role of reducing load harmonics. Supply Input Stage Output Stage Load 1 2 Shunt Stage Three Stage Type 3 LP Harmonic Filter 3-Stage (Standard), Type 3 for THD I 5% The PQI Type LPF standard Type 3 Low Pass Harmonic Filter includes all three filter stages and achieves THD I 5% at virtually any load condition when used in combination with a 6-pulse diode rectifier. It can also be used with phase controlled (SCR) rectifiers with excellent results. 3

3 Our standard Type 3 filter achieves 5% THD I or less for VFDs operating under any load condition and with any source impedance. Source Type 3 LP Harmonic Filter for 5% THDI Variable Frequency Drive Motor 2-Stage (Basic), Type 2 for 8%-12% THD I The PQI Type 2 Low Pass Harmonic Filter includes two filter stages and takes advantage of existing circuit inductance, which may be in the form of either AC or DC reactors. It can also be used without external AC or DC reactors for those applications where the current distortion limit is above 5%. When the load includes AC or DC reactors, Type 2 filters will typically maintain distortion levels as low as 5%-8% THD I. Without additional AC or DC inductance, Type 2 filters will maintain distortion within 8%-12% THD I. Source Variable Frequency Drive Motor The standard three stage (Type 3) filter design achieves the lowest possible harmonic distortion levels while preventing power system resonance. Application Example A typical 6-pulse, adjustable speed drive (or VFD) has been known to cause total harmonic distortion of current (THDi) in excess of 30% and sometimes as high as 100%, depending upon the device rating and system impedance. When THDi is reduced to 8%-12% by using Type 2, or less than or equal to 5% by using Type 3, PQI LP Harmonic Filters, I RMS current is significantly reduced. This also reduces I 2 R losses in transformer windings and conductors, decreases kva demand and increases load efficiency by decreasing total harmonic distortion of voltage (THDv). Harmonic Current Distortion PQI LP Harmonic Filters provide results that achieve the lowest THD I and THD V in the industry, under any operating condition (0% to 100% full load). The THD I for a given load will vary slightly depending upon the effective source impedance. Type 3 LP Harmonic Filters are capable of maintaining 5% THD I across the entire operating range from 0% to 100% full load. THD I may be slightly higher for low impedance power sources. Harmonic Voltage Distortion VFDs equipped with Type 3 LP Harmonic Filters will typically add approximately 1% THD V at the load side of the filter. The THD V for a given load will vary slightly depending upon the effective source impedance. THD V may be slightly higher for high impedance power sources. Voltage Regulation PQI Type LP Harmonic Filters control the output voltage to +5% at no load and -5% at full load. Type 2 LP Harmonic Filter for 8%-12% THDI

4 Product Technical Specifications Electrical Specification Major Component Specifications Reactor Specifications System Voltage: , , 480, 600 and 690 VAC Voltage Tolerance: +/-10% Frequency: 60Hz or 50Hz available Phases: 3-phase and 1-phase available Input Current Ratings: 3 to 3000 amps Input Power Ratings: 1.1 to 2500 kw (1.5 to 3000 HP) Total Harmonic Current Distortion (THDi): 5% (Type 3) 5% - 8% (Type 2, if VFD has internal AC or DC reactor) 8% - 12% (Type 2, if VFD has internal AC or DC reactor) Total Demand Distortion: Meets IEEE-519, Table 10.3 Inductance Tolerance Maximum Voltage Maximum Current Power Loss Dielectric Strength Coil to coil Coil to core Core construction Impregnation +/-3% (balanced in all 3 phases) 600V (Except 690V filters) 125% of rated AC current, 1 minute 0.4 Watts per kvar 3000V AC for 1 second 3000V AC for 1 second PolyGap TM, Low audible noise, low harmonic loss Vacuum, overpressure varnish Total Harmonic Voltage Distortion (THDv): VFD typically contributes < 2% THDv to background THDv Voltage Regulation: +/-5% (no load to full load) Efficiency: 99% at rated load Dielectric Strength: Reactors V (1 minute) Capacitors - 2x rated +1000V (1 minute) Overload Capability: 1.5x rated current (1 min, 1 time/hr) Damping: Self damping reactors (no power resistors req d) Life Expectancy: > 480k hours at 50 C, rated power Environmental Ventilation - Natural convection (No fans required) Enclosures Available (NEMA 1, 3R, 4, 4X, 12, etc.) - Indoor, Outdoor, Industrial, Open, Kits Ambient Temperature - (-30 C to +50 C) Reduced kva Demand - Up to 30%, when THDi is reduced from 100% to 5% Reduced Current Demand - Up to 30%, when THDi is reduced from 100% to 5% Potential Energy Savings - Up to 4% (depending on transformer and conductors) Standards Underwriters Laboratories (UL): - Assemblies are UL-508A approved ( 600V) - Components are UL component recognized - Complies with UL1531 IEC / EN: Complies with EN60289, EN CE (Low Voltage Directive): LVD certificate available Operating Temperature Over Temperature Protection Life Expectancy Terminals Agency Approval Capacitor Specifications -40 C to +50 C Temperature switch included in shunt reactor (center leg) Over 20 years at 40 C operation Copper Capacitor Tolerance +/-4% Maximum Voltage Maximum Current Power Loss Dielectric Strength Terminal - case Terminal - terminal Construction Impregnation Operating Temperature Life Expectancy Terminals Agency Approval UL Component Recognized (File #E173113) 110% of rated AC voltage 135% of rated AC current 0.4 Watts per kvar 2x rated AC voltage V, for 1s 1.75x rated AC voltage for 1 second Impregnated Metalized Polypropylene (MPP) Vacuum, overpressure varnish -40 C to +80 C Over 1M hours at 40 C operation Brass UL Component Recognized (File #E71645) Note: There is no minimum source impedance requirement for PQI, Type 2 & 3, LP harmonic filters. Harmonic Standards: - Meets IEEE-519, AN-2279, EN , EN , G5/4

5 Product Selection Tables (Page 1 of 3 PQI LP Harmonic Filters are suitable for use with one or more 6-pulse VFDs. LPF s are not intended for use with linear loads (such as across-the-line started motors). Variable Torque Applications: Determine the total load (VFD) horsepower (HP) of kw rating. Select the appropriate filter based on the VFD HP or kw and then confirm that the total rated current is within the filter full load current rating. Full Load Amps (FLA) refers to the filter fundamental current rating. Constant Torque Applications: Determine the maximum current requirement. Select the appropriate filter based on the maximum required current in amperes. Example: A 100 HP, 480V, VFD rated for 124 full load amps (FLA), temporarily operated at 130% will require a filter rated for at least 161 amps (i.e. LPF XX- XX). Other Applications: Consult the factory for singlephase drives, DC drive applications, other rectifier types, frequency ratings, voltage ratings, load ratings, styles, etc. Horsepower Rating 1 HP to 1200 HP Voltage Rating 240V, 400V, 480V, 600V or 690V Frequency 50 or 60 Hz Type T2 (2-stage), T3 (3-stage) Model No. Configuration Enclosure Type NEMA [1, 3R, 4, 4X, 12, OP, (OPEN)] LPF - HP- Volts - Hz - Type - Enclosure Sample Model No. LPF T3-3R] VAC, 50 Hz LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX VAC, 60 Hz HP kw Max. Amps Model No LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX

6 Product Selection Tables (Page 2 of 3) VAC, 50 Hz LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX VAC, 60 Hz LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX

7 Product Selection Tables (Page 3 of 3) 600 VAC, 60 Hz LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX 690 VAC, 50 Hz LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX LPF XX-XX

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE - 519 Solutions Harmonics Tutorial 1 Power Conversion Equipment can save energy and control motors, heaters,

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017 Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates

More information

GE Energy. Matrix Harmonic Filter Series D

GE Energy. Matrix Harmonic Filter Series D GE Energy Matrix Harmonic Filter Series D Matrix Harmonic Filter GE Matrix Harmonic Filters provide broadband reduction of harmonics. Matrix Harmonic Filters not only offer better performance over other

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

Harmonic Distortion and Variable Frequency Drives

Harmonic Distortion and Variable Frequency Drives Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation

More information

High Frequency Sinewave Guardian TM Filter

High Frequency Sinewave Guardian TM Filter High Frequency Sinewave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL FORM: SHF-TRM-E REL. April 2015 REV. 001 2015 MTE Corporation Caution Prior to start up; confirm the drive operation mode

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV 6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV SOLIDSTATE CONTROLS, INC. Solidstate Controls Incorporated 875 Dearborn Drive Columbus, Ohio 43085 Tel : (614) 846-7500 Fax: (614) 885-3990 6L]LQJ $ 836 6\VWHP )RU 1RQ/LQHDU

More information

Tuningintobetter power quality

Tuningintobetter power quality Technology Review Third harmonic filters Tuningintobetter power quality Jouko Jaakkola Your PC screen flickers, stops flickering, starts again... Irritating to be sure, and perhaps the first visible sign

More information

Active Harmonic Filter

Active Harmonic Filter Reactive Power and Harmonic Compensation Active Harmonic Filter The new StacoSine Plus active harmonic filter is available in 100, 150, 200 and 300 amp assemblies. Modules can be paralleled for a maximum

More information

General Description & Features Selection Charts Definition of Terms... 42

General Description & Features Selection Charts Definition of Terms... 42 SECTION NON-LINEAR LOAD ISOLATION TRANSFORMERS Special winding techniques minimize eddy current losses. A double sized neutral handles excessive neutral currents. UL Listed for K Factor Loads 4, 1 & 20.

More information

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to

More information

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS. MAIN TOPICS DISCUSSED Electric Rates Electrical system utilization ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K Power quality Harmonics Power factor (Cos phi) improvement Section K - 2 ELECTRIC

More information

Technical Paper. Harmonic Distortion in Data Centers

Technical Paper. Harmonic Distortion in Data Centers Technical Paper Harmonic in Data Centers Written By: Ian Wallace Summary Power quality and power reliability are critical to data center operation. As strides have been made to improve energy efficiency

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

AC Drives and Soft Starter Application Guide

AC Drives and Soft Starter Application Guide Feature AC Drives and Soft Starter Application Guide by Walter J Lukitsch PE, Gary Woltersdorf Jeff Theisen, and John Streicher Allen-Bradley Company Abstract: There are usually several choices for starting

More information

Figure 1 Typical Inverter Block Diagram

Figure 1 Typical Inverter Block Diagram AC Drives and Soft Starter Application Guide Walter J Lukitsch PE, Gary Woltersdorf Jeff Theisen, John Streicher Allen-Bradley Company Milwaukee, WI Abstract: There are usually several choices for starting

More information

McGill Power Sales & Engineering, INC.

McGill Power Sales & Engineering, INC. 1 McGill Power Sales & Engineering, INC. Power Factor Correction Terry McGill President McGill Power Sales & Engineering Inc. 2007 Eaton Corporation. All rights reserved. Agenda What is power factor? What

More information

Principles for Controlling Harmonics

Principles for Controlling Harmonics Principles for Controlling Harmonics Harmonic distortion is present to some degree on all power systems. Fundamentally, one needs to control harmonics only when they become a problem. There are three common

More information

VFDs and Harmonics in HVAC Applications

VFDs and Harmonics in HVAC Applications VFDs and Harmonics in HVAC Applications Larry Gardner Product Marketing Manager Yaskawa America, Inc. Jeff Grant Senior Sales Engineer LONG Building Technologies October 20, 2016 2016 Yaskawa America,

More information

Harmonic Filters and Reactors

Harmonic Filters and Reactors Harmonic Filters and Reactors Harmonics are invisible but costly If one looks up the meaning of harmonics in any one of several technical dictionaries, it is normally defined as being A sinusoidal component

More information

Power Quality and Harmonic :Causes and Effects with Paper Mill Factory

Power Quality and Harmonic :Causes and Effects with Paper Mill Factory Power Quality and Harmonic :Causes and Effects with Paper Mill Factory Danaisak Tangsakha PEA Thailand danaisakpq@gmail.com Provincial Electricity Authority, Thailand 1 Topics Introduction Power Quality

More information

Power factor correction and harmonic filtering. Harmonic filters and EMI

Power factor correction and harmonic filtering. Harmonic filters and EMI Power factor correction and harmonic filtering Harmonic filters and EMI Introduction 3 R.7 - Harmonic filters and EMI Filtering unit selection guide 12 LCL Harmonic filter for power converters 13 LCL-TH

More information

VARIABLE FREQUENCY RESONANT TEST SYSTEM

VARIABLE FREQUENCY RESONANT TEST SYSTEM VARIABLE FREQUENCY RESONANT TEST SYSTEM 400kV,1200kVA Tank Type Reactor for Outdoor Cable Test Field 650kV, 5850kVA, Cylinder Type Reactors for Onsite Testing of GIS and Cable PHENIX Variable Frequency

More information

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY D. M. Soomro and M. M. Almelian Department of Electrical Power Engineering, Faculty of Electrical and Electronic

More information

Electric Power Quality: Voltage Sags Momentary Interruptions

Electric Power Quality: Voltage Sags Momentary Interruptions Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage

More information

Amps Without HGA. Amps With HGA. Amps Without HSD Time (ms)

Amps Without HGA. Amps With HGA. Amps Without HSD Time (ms) Harmonic Solutions HarmonicGuard Active (HGA) Filter Save money and space: a single bus-applied HGA can correct harmonics for multiple loads Reduce current harmonic distortion to less than 5% allowing

More information

Real Time Power Factor Correction Units (Transient Free Switching)

Real Time Power Factor Correction Units (Transient Free Switching) Real Time Power Factor Correction Units (Transient Free Switching) Designers and Manufacturers of Power Factor Correction Equipment and Harmonic Filters 1016 34 AV SE Calgary, AB T2G 1V4 Canada Tel: 403

More information

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner conditioning products Electronic voltage regulator -Sure 700 & 800 -Suppress T7 & 100 Harmonic correction unit Sag ride-through power conditioner The power to work Basics of power quality The partner you

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Power Quality Monitoring and Power Metering Tutorial

Power Quality Monitoring and Power Metering Tutorial Power Quality Monitoring and Power Metering Tutorial Power generation and transmission today are accomplished using three phase alternatingcurrent. To understand electrical power quality monitoring and

More information

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web: -

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web:  - ADJUSTABLE SPEED DRIVES HX7 Series 18 Pulse Toshiba HX7 In some industrial applications, users need reliable and efficient adjustable speed drives that do not contribute significant harmonic distortion

More information

Alternators Reactance for Nonlinear Loads

Alternators Reactance for Nonlinear Loads Alternators Reactance for Nonlinear Loads Allen Windhorn. P.E. 26 July, 2013 Introduction Widespread invocation of IEEE Std 519 on systems powered by generators, together with increased use of equipment

More information

How Harmonics have led to 6 Power Factor Misconceptions

How Harmonics have led to 6 Power Factor Misconceptions Harmonic and Energy Saving Solutions How Harmonics have led to 6 Power Factor Misconceptions Tony Hoevenaars, P.Eng. Power Factor Misconceptions 1. Low power factor is normally caused by electric motors

More information

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics Power IT LV Active Filters PQFI PQFM PQFK The ABB comprehensive solution for active filtering of harmonics Harmonics and Power Quality Power Quality relates to the amplitude, frequency and distortion of

More information

Power Quality Analysers

Power Quality Analysers Power Quality Analysers Review of Power Quality Indicators and Introduction to Power Analysers ZEDFLO Australia 6-Mar-2011 www.zedflo.com.au Power Quality Indicators Review of main indicators of electrical

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

BALLAST HANDBOOK. Basic Reference Manual. Integral Ballast Characteristics and Performance Data High Pressure Sodium Metal Halide HL-301 5/03

BALLAST HANDBOOK. Basic Reference Manual. Integral Ballast Characteristics and Performance Data High Pressure Sodium Metal Halide HL-301 5/03 BALLAST Basic Reference Manual Integral Ballast Characteristics and Performance Data High Pressure Sodium Metal Halide HL-301 5/03 BALLAST Why Use Ballasts? The high intensity discharge lamps -high pressure

More information

Improve Power Factor and Reduce the Harmonics Distortion of the System

Improve Power Factor and Reduce the Harmonics Distortion of the System Research Journal of Engineering Sciences ISSN 2278 9472 Improve Power Factor and Reduce the Harmonics Distortion of the System Abstract Jain Sandesh, Thakur Shivendra Singh and Phulambrikar S.P. Electrical

More information

DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS

DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS Dr.S.K.PURUSHOTHAMAN Associate Professor Department of EEE Sri Venkateswara College Of Engineering And Technology, Thirupachur

More information

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection: Utility Systems Technologies, Inc. Sag Fighter TM Deep Voltage Sag Protection: D e e p Vo l t a g e S a g P r o t e c t i o n For three phase application: Q u a l i t y P o w e r. B e t t e r B u s i n

More information

Harmonic Analysis and Its Mitigation Using Different Passive Filters

Harmonic Analysis and Its Mitigation Using Different Passive Filters Harmonic Analysis and Its Mitigation Using Different Passive Filters Ashlin Gloria Reginald 1, K J Thomas 2 1 PG Scholar, Amal Jyothi College of Engineering, Kanjirapally Kottayam, India ashlingloriar@gmail.com

More information

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems December 2010/AT301 by Reza Tajali, P.E. Square D Power Systems Engineering Make the most of your energy SM Revision

More information

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION NON-LINEAR TRANSFORMER PRESENTATION 1 PROBLEM: HARMONICS CAUSE EXCESSIVE TRANSFORMER HEATING Increased Losses Proximity Skin Effect Stray Losses Circulating Effect Triplen Harmonics Add in Neutral Increased

More information

Power Protection and Conditioning

Power Protection and Conditioning 2/50 Voltage Wave Attenuation CBEMA Constant Voltage Power Supply Voltage surge with a virtual front time of 1.2 ms and a time to half-value of 50 ms delivered across an open circuit. 8/20 Current Wave

More information

Failure of Transformers Due to Harmonic Loads

Failure of Transformers Due to Harmonic Loads Failure of Transformers Due to Harmonic Loads 1 Jyotirmaya Ghadai, 2 Chinmay Das 1,2 Department of Electrical Engineering, Indira Gandhi Institute of Technology Email: 1 jyotighadai05@gmail.com, 2 Chinmaydas14@gmail.com

More information

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse ADJUSTABLE SPEED DRIVES HX7 Series 18-Pulse Toshiba HX7 In some industrial applications, users need reliable and efficient adjustable speed drives that do not contribute significant harmonic distortion

More information

An easy-to-use Precision Power Analyser. The touch of a button gives direct readout of true power and a host of other useful measurements.

An easy-to-use Precision Power Analyser. The touch of a button gives direct readout of true power and a host of other useful measurements. An easy-to-use Precision Power Analyser. The touch of a button gives direct readout of true power and a host of other useful measurements. Easy to use-fully autoranging for voltage, current and frequency

More information

Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants

Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants Sherif M. Ismael Electrical Engineering Division, Engineering for the Petroleum and Process

More information

Large-Capacity, High-Efficiency 3-Level UPS for North America 7000HX-T3U

Large-Capacity, High-Efficiency 3-Level UPS for North America 7000HX-T3U Large-Capacity, High-Efficiency 3-Level for North America 7000HX-T3U KAWASAKI, Daisuke HAMADA, Ippei SATO, Atsushi ABSTRACT Due to the development of information and communications systems in the information

More information

SINPAC Switches: Brief Operating Description. Mounting Options

SINPAC Switches: Brief Operating Description. Mounting Options SINPAC Switches: Brief Operating Description For over 75 years, single-phase motors have utilized a mechanical centrifugal switch to switch the start circuit. Inherent characteristics of a mechanical device

More information

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation UPEC21 31st Aug - 3rd Sept 21 Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation H. M. Zubi IET and IEEE member hz224@bath.ac.uk R. W. Dunn IEEE member E-mail r.w.dunn@bath.ac.uk

More information

Chapter M Harmonic management

Chapter M Harmonic management Chapter M Harmonic management 3 4 5 6 7 8 Contents The problem: why is it necessary to detect and eliminate harmonics? Standards General Main effects of harmonics in installations 4. Resonance M6 4. Increased

More information

Electrical Submersible Pumping Systems

Electrical Submersible Pumping Systems Electrical Submersible Pumps (ESP) Electrical Submersible Pumping Systems Variable Speed Drive Halliburton s HAL 1200 electrical submersible pumping (ESP) system variable speed drive (VSD) provides a number

More information

MODEL 421 Over/Under Motor Load Monitor

MODEL 421 Over/Under Motor Load Monitor MODEL 421 Over/Under Motor Load Monitor Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or, Single-phase or 3-phase Built-in Trip and Restart

More information

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse ADJUSTABLE SPEED DRIVES W7 Series 18 Pulse Meets or Exceeds Your Specifications Standard Specifications Item Voltage Class 460V Maximum HP 60 75 100 125 150 200 250 300 400 500 600 700 800 Drive Rating

More information

shunt (parallel series

shunt (parallel series Active filters Active filters are typically used with diode/thyristor rectifiers, electric arc furnaces, etc. Their use in electric power utilities, industry, office buildings, water supply utilities,

More information

Introduction to Rectifiers and their Performance Parameters

Introduction to Rectifiers and their Performance Parameters Electrical Engineering Division Page 1 of 10 Rectification is the process of conversion of alternating input voltage to direct output voltage. Rectifier is a circuit that convert AC voltage to a DC voltage

More information

TMdrive -XL Series Family Product Application Guide. solar inverters. power generation

TMdrive -XL Series Family Product Application Guide. solar inverters. power generation TMdrive -XL Series Family Product Application Guide metals cranes mining testing oil & gas solar inverters power generation cement TMdrive-XL Series 8 MVA 15 MVA 20 MVA 30 MVA The TMdrive XL series family

More information

Application of Tuned Passive Filter for Industrial Six-Pulse Rectifier with R-L Load Viralkumar A. Rana 1 Keyur Rana 2 Atul Talati 3

Application of Tuned Passive Filter for Industrial Six-Pulse Rectifier with R-L Load Viralkumar A. Rana 1 Keyur Rana 2 Atul Talati 3 IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 02, 2014 ISSN (online): 2321-0613 Application of Tuned Passive Filter for Industrial Six-Pulse Rectifier with R-L Load

More information

To be automatically connected to the nearest North American Technical Sales Office:

To be automatically connected to the nearest North American Technical Sales Office: DIN-A-MITE C SCR Power Controller Delivers Up To 80 Amperes in a Compact Package TOTAL CUSTOMER SATISFACTION 3 Year Warranty The Watlow DIN-A-MITE Style C silicon controlled rectifier (SCR) power controller

More information

Power Quality Monitoring:

Power Quality Monitoring: Power Quality Monitoring: Analyse and Improve your Energy Performance Presented by: David Bradley B.Eng (Hons), MBA, C.Eng, MIET Energy Management & Power Quality Key Drivers PART L The energy efficiency

More information

PowerFlex Medium Voltage Drives with Direct-to-Drive Technology Eliminating the Isolation Transformer

PowerFlex Medium Voltage Drives with Direct-to-Drive Technology Eliminating the Isolation Transformer PowerFlex Medium Voltage Drives with Direct-to-Drive Technology Eliminating the Isolation Transformer Transformerless drives help industry reduce the cost of motor control while using standard motors.

More information

FAQ for SIMOREG 6RA70 and Control Module

FAQ for SIMOREG 6RA70 and Control Module I DT LD CS 28 / February / 2011 FAQ for SIMOREG 6RA70 and Control Module Question: What requirements apply for line quality and what line interference can occur? Answer: Line requirements: Voltage: rated

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

Inter Harmonics of Cycloconveter Excited Induction Motor and Design its Filter Circuit

Inter Harmonics of Cycloconveter Excited Induction Motor and Design its Filter Circuit International Journal of Electrical Engineering. ISSN 974-2158 Volume 5, Number 3 (212), pp. 329-334 International Research Publication House http://www.irphouse.com Inter Harmonics of Cycloconveter Excited

More information

Grid Converters for Photovoltaic

Grid Converters for Photovoltaic Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements

More information

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System WHO SHOULD FILE THIS SUBMITTAL: Anyone in the final stages of interconnecting a Generation System with Nodak Electric Cooperative, Inc. This submittal shall be completed and provided to Nodak Electric

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

Medium Voltage Drives in Industrial Applications. By: Navid Zargari & Steven Rizzo Rockwell Automation Cambridge, ON

Medium Voltage Drives in Industrial Applications. By: Navid Zargari & Steven Rizzo Rockwell Automation Cambridge, ON Medium Voltage Drives in Industrial Applications By: Navid Zargari & Steven Rizzo Rockwell Automation Cambridge, ON Outline Introduction Medium Voltage Drive Topologies A Brief Comparison Power Semiconductors

More information

Application Guidance Notes: Technical Information from Cummins Generator Technologies

Application Guidance Notes: Technical Information from Cummins Generator Technologies Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 087 Power Factor DEFINITIONS What is Power Factor? Power factor is a way of identifying the electrical relationship

More information

Residual current circuit breakers (RCCBs)

Residual current circuit breakers (RCCBs) Residual current circuit breakers (RCCBs) Description Automatically trips in event of earth leakage fault Provides protection against direct & indirect contact with live parts Technical data IS 12640-1,

More information

DC CIRCUITS Part I of III Parts. Part II installation. Part III troubleshooting

DC CIRCUITS Part I of III Parts. Part II installation. Part III troubleshooting DC CIRCUITS Part I of III Parts Part II installation Part III troubleshooting Trane ComfortSite is a user-friendly Internet site designed to save you time and it s FREE for Trane Customers. Order Equipment,

More information

Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with MTE Matrix AP Harmonic Filter vs. 18-Pulse Drive

Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with MTE Matrix AP Harmonic Filter vs. 18-Pulse Drive DRIVING POWER QUALITY ISO 9001:2008 Certification Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with MTE Matrix AP Harmonic Filter vs. 18-Pulse Drive Abstract November 13, 2012 Todd Shudarek,

More information

Clamp Meter ABCs. Application Note. The transformer action

Clamp Meter ABCs. Application Note. The transformer action Clamp Meter ABCs What is a clamp meter and what can it do? What measurements can be made with a clamp meter? How do you get the most out of a clamp meter? Which clamp meter is best suited to the environment

More information

Thermal Imaging, Power Quality and Harmonics

Thermal Imaging, Power Quality and Harmonics Thermal Imaging, Power Quality and Harmonics Authors: Matthew A. Taylor and Paul C. Bessey of AVO Training Institute Executive Summary Infrared (IR) thermal imaging (thermography) is an effective troubleshooting

More information

Harmonic Variations in Three-phase Induction Motors Fed by PWM Inverter with Different Stator Coil Pitches

Harmonic Variations in Three-phase Induction Motors Fed by PWM Inverter with Different Stator Coil Pitches Proceedings of the 6th WSEAS International Conference on Applications of Electrical Engineering, Istanbul, Turey, May 7-9, 7 95 Harmonic Variations in Three-ase Induction Motors Fed by PWM Inverter with

More information

Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives

Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives D.Uma 1, K.Vijayarekha 2 1 School of EEE, SASTRA University Thanjavur, India 1 umavijay@eee.sastra.edu 2 Associate Dean/EEE

More information

WHR Series STABILINE Voltage Regulators

WHR Series STABILINE Voltage Regulators WHR Series STABILINE Voltage Regulators The WHR Series is the most extensive line of STABILINE Voltage Regulators Superior Electric has ever offered. This line of regulators includes units for use on all

More information

ELG4139: DC to AC Converters

ELG4139: DC to AC Converters ELG4139: DC to AC Converters Converts DC to AC power by switching the DC input voltage (or current) in a pre-determined sequence so as to generate AC voltage (or current) output. I DC I ac + + V DC V ac

More information

AC System Monitoring Device

AC System Monitoring Device AC System Monitoring Device Andrew Jarrett Project Adviser: Professor Steven D.Gutschlag Department of Electrical and Computer Engineering May 11, 2016 ABSTRACT This document covers the design of a device

More information

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers Motor Bearing Solution from MH&W International Corp. http://www.coolblue-mhw.com Variable Frequency Motor Drive Systems 1. What is the problem 2.

More information

Mitigation of harmonics using shunt active filter Mrs.Chhaya S Bandgar 1, Ms.Shamal B Patil 2

Mitigation of harmonics using shunt active filter Mrs.Chhaya S Bandgar 1, Ms.Shamal B Patil 2 Journal of Electronicsl and Communication Engineering (IOSR-JECE) ISSN: 78-834-, ISBN: 78-8735, PP: 44-54 www.iosrjournals.org Mitigation of harmonics using shunt active filter Mrs.Chhaya S Bandgar 1,

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations Bulletin LP NEMA AC Permanent Magnet-Latching Lighting Contactors Product Overview/Product Selection/Wiring Diagram A, -Pole Open Type without Enclosure Bulletin LP Top wiring permanent magnet latching

More information

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax: POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION

More information

Harmonic Distortion Effects and Mitigation in Distribution Systems

Harmonic Distortion Effects and Mitigation in Distribution Systems Journal of American Science 00;6(0) Harmonic Distortion Effects and Mitigation in Distribution Systems Hussein A. Attia, M. El-Metwally and Osama M. Fahmy Cairo University, Faculty of Engineering, Electrical

More information

Short-Circuit Current Calculations

Short-Circuit Current Calculations Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.

More information

Power Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers

Power Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers EPCOS Product Brief 2017 Power Quality Solutions of Active Harmonic Filters and Power Optimizers EPCOS has been offering a comprehensive range of key components for power factor correction (PFC) and power

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

Parallel AMX AC Power Systems

Parallel AMX AC Power Systems Parallel AMX AC Power Systems 8kVA to 30kVA 20-5,000 Hz 1Ø4 0-338VL-N 2Ø4 0-600V L-L 4 0-338V L-N /585V L-L Standard Features: Master/Slave Operation of 2 to 5 AMX AC s provides AC Power Levels to from

More information

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state.

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state. 1991 1.12 The operating state that distinguishes a silicon controlled rectifier (SCR) from a diode is (a) forward conduction state (b) forward blocking state (c) reverse conduction state (d) reverse blocking

More information

Alternator winding pitch and power system design

Alternator winding pitch and power system design Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering

More information

150 Watt Industrial (WLT)

150 Watt Industrial (WLT) 150 Watt Industrial (WLT) Features 4 x 2 x 1.3 inches form factor 150 W with forced-air cooling Class 1 & Class 2 options 12 V @ 0.5 A fan voltage auxiliary output High efficiency > 86% Low conducted and

More information

VARIABLE FREQUENCY DRIVE SPECIFICATION

VARIABLE FREQUENCY DRIVE SPECIFICATION VARIABLE FREQUENCY DRIVE SPECIFICATION 1.0. SUMMARY The use of variable frequency drives (VFDs) in conjunction with wastewater lift stations has been identified as a means improve efficiency and to moderate

More information

CAPACITORS. Capacitors for AC and DC General Purpose Applications. Proven EIA-456-A Compliant 60,000 Hour Reliability Industry Standard

CAPACITORS. Capacitors for AC and DC General Purpose Applications. Proven EIA-456-A Compliant 60,000 Hour Reliability Industry Standard CAPACITORS Capacitors for AC and DC General Purpose Applications Proven EIA-456-A Compliant 60,000 Hour Reliability Industry Standard To ensure correct selection of a capacitor for your application, please

More information

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company Engineering data submittal Page 1 WHO SHOULD FILE THIS SUBMITTAL : Anyone in the final stages of in terconnecting a Generation System with Otter Tail Power. This submittal shall be completed and provided

More information