Reduction in Load (Copper) loss Due to Overhauling of Power Transformer or OLTC

Size: px
Start display at page:

Download "Reduction in Load (Copper) loss Due to Overhauling of Power Transformer or OLTC"

Transcription

1 Reduction in Load (Copper) loss Due to Overhauling of Power Transformer or OLTC by Neeraj Khare BSES RAJDHANI POWER LTD.

2 BSES Rajdhani Power Limited BSES Rajdhani Power Limited is a Joint Venture of Government of Delhi and Reliance Infrastructure Limited with effect from July BSES Rajdhani Power Limited is the largest of the private discoms in Delhi and distribute power to to an area spread over 750 sq. km- 55% of Delhi s geographical area, with a population density of 2200 per sq km. It s over 22 lakh customers are spread in 9 districts across South and West of Delhi 2

3 Transformation in BRPL area AT&C loss reduction : The company has reduced AT&C by a record 39 % from a high of 5.54% in July 2002 to.9 % as on 3 st March 206. Power Demand : Successfully met the maximum power demand of 2778 MW during the summer of 206 a 20 % increase over the maximum demand of 259 MW in Being biggest of the three discoms, BRPL has a 42 % share in Delhi s electricity pie. System Reliability : Increased to % in 206 from 65% in

4 Overhauling of Power Transformer or OLTC With the passage of time condition of cellulose, oil and contacts of OLTC s of transformer deteriorates and hence overhauling is required for utilizing max. life of transformers. Depending upon the condition of cellulose, oil and no. of operation of OLTC s, Power transformers and OLTC s are overhauled as per standards available and maintenance practices of utilities. 4

5 Overhauling of Power Transformer or OLTC During overhauling process, along with ( i) moisture removal, (ii) oil filteration/replacement, (iii) replacement of gaskets etc., re-tightening of all connections of (a) core coil assembly, (b) metal parts /bushings of both HT & LT side & (c) OLTC also takes place. Re-tightening of all connections during overhauling, results into change in over all winding resistance, if we go through tests results before and after overhauling. 5

6 Winding Resistance Conductor used in transformers have some resistance which depends upon length and area of conductor used for coil winding. But over all winding resistance of assembled transformer is a result of conductor resistance plus contact resistance of following connections,. Tap changer contacts 2. Metal parts 3. Bushings Winding resistance plays an important role in load (copper ) as mathematically, copper loss in a transformer is given by I² R. 6

7 Winding Resistance With the passage of time, because of connections getting loose, contact resistance increases resulting into increase in winding resistance which further increases copper or load of a transformer. Because of re-tightening of all connections during overhauling, a good amount of change takes place in winding resistance, if we go through results before and after overhauling. As reduction on winding resistance will lead to reduction in I² R, hence it can be concluded that overhauling of Power transformers and OLTC S results into loss reduction also. For establishing this fact, we will see test results of winding resistance before and after overhauling of power trf. s and OLTC s. 7

8 Overhauling of OLTC s Case : 20 MVA, 66/KV, NGEF make trf. at JNU Grid Test results of winding resistance before Overhauling of OLTC Resistance/phase R at rated tap no. 5 = ( ( )*/3)*3/2 =.762 Ω Phase Current I of HV side = 0.02 Amp. Assuming 60 % annual average loading of transformer Copper = 3 (I*60/00)²*R = 3(0.02*0.6)²*.762 = W () 8

9 Overhauling of OLTC s Test results of winding resistance after Overhauling of OLTC Resistance/phase R at rated tap no. 5 = ( ( )*/3)*3/2 =.68 Ω Phase Current I of HV side = 0.02 Amp. Assuming 60 % annual average loading of transformer Copper = 3 (I*60/00)²*R = 3(0.02*0.6)²*.68 = W (2) Loss reduction = () (2) = ( ) W = W MU gain = (Loss reduction*24*365)/.00e+09 = ( *24*365)/.00E+09 =

10 Overhauling of OLTC s Case 2 : 6 MVA, 33/KV, Bharat Bijlee make trf. at Siri Fort Grid Test results of winding resistance before Overhauling of OLTC Resistance/phase R at rated tap no. 5 = ( ( )*/3)*3/2 = Ω Phase Current I of HV side = 6.66 Amp. Assuming 60 % annual average loading of transformer Copper = 3 (I*60/00)²*R = 3(6.66*0.6)²* = W () 0

11 Overhauling of OLTC s Test results of winding resistance after Overhauling of OLTC Resistance/phase R at rated tap no. 5 = ( ( )*/3)*3/2 = Ω Phase Current I of HV side = 6.66 Amp Assuming 60 % annual average loading of transformer Copper = 3 (I*60/00)²*R = 3(6.66*0.6)²* = W (2) Loss reduction = () (2) = ( ) W = W MU gain = (Loss reduction*24*365)/.00e+09 = ( *24*365)/.00E+09 =

12 Overhauling of Transformer Case : 6 MVA, 33/KV, Pushp Vihar Grid Test results of winding resistance before Overhauling of Transformer Resistance/phase R of HV side at rated tap no. 5 = ( ( )*/3)*3/2 = Ω Phase Current I of HV side = 6.66 Amp. Resistance/phase r of LV side = ( ( )*/3) = Ω Phase Current i of LV side = Amp Assuming 60 % annual average loading of transformer Copper = 3 ( (I*60/00)²*R + ( i*60/00)²*r ) ) = 3( (6.66*0.6)²* ( 839.8*0.6)² ) ) = W () 2

13 Overhauling of Transformer Test results of winding resistance after Overhauling of Transformer Resistance/phase R of HV side at rated tap no. 5 = ( ( )*/3)*3/2 = Ω Phase Current I of HV side = 6.66Amp. Resistance/phase r of LV side = ( ( )*/3) = Ω Phase Current i of LV side = Amp Assuming 60 % annual average loading of transformer Copper = 3 ( (I*60/00)²*R + ( i*60/00)²*r )) = 3 ( (6.66*0.6)²* ( 839.8*0.6)² 0.024) ) = W (2) Loss reduction = () (2) = ( ) W = W MU gain = (Loss reduction*24*365)/.00e+09 = ( *24*365)/.00E+09 =

14 Overhauling of Transformer Case 2 : 20 MVA, 66/KV, Okhla I Grid Test results of winding resistance before Overhauling of Transformer Resistance/phase R of HV side at rated tap no. 5 = ( ( )*/3)*3/2 =.305 Ω Phase Current I of HV side = 0.02 Amp. Resistance/phase r of LV side = ( )*/3 = Ω Phase Current i of LV side = Amp Assuming 60 % annual average loading of transformer Copper = 3 ( (I*60/00)²*R + ( i*60/00)²*r ) ) = 3 ( (0.02*0.6)²* ( *0.6)² ) ) = W () 4

15 Overhauling of Transformer Test results of winding resistance after Overhauling of Transformer Resistance/phase R of HV side at rated tap no. 5 = ( ( )*/3)*3/2 =.23 Ω Phase Current I of HV side = 0.02 Amp. Resistance/phase r of LV side = ( )*/3 = Ω Phase Current i of LV side = Amp Assuming 60 % annual average loading of transformer Copper = 3 ( (I*60/00)²*R + ( i*60/00)²*r ) ) = 3 ( (0.02*0.6)²*.23 + ( *0.6)² 0.022)) = W (2) Loss reduction = () (2) = ( ) W = W MU gain = (Loss reduction*24*365)/.00e+09 = ( *24*365)/.00E+09 =

16 Case 6th International Conference on Large Power Transformers Modern Trends in Summary of loss Reduction of the four cases Rated Ph current I (amp) i (amp) Results before overhauling R (ohm) r (Ohm) HV LV Overhauling of OLTC Total Results before overhauling R (ohm) r (Ohm) HV LV Total Reduction in MU gain Revenue gain (Rs) , ,025.6 Case Rated Ph current Results before overhauling Overhauling of Transformer Results before overhauling 2 I (amp) i (amp) R (ohm) r (Ohm) HV LV Total R (ohm) r (Ohm) HV LV Total Reductio n in MU gain Revenue gain (Rs) ,44, ,95,299. Note: Annual average loading of transformer is taken 60 %. 2 Revenue gain is Rs 5.75 /unit. 6

17 Conclusion From the 4 cases, 2 each of transformer overhauling and of OLTC, it is established that there is reduction in HV and LV winding resistance after overhauling of trf. s and OLTC s. Reduction in winding resistance leads to reduction in I² R, resulting in revenue gain, along with improvement of insulation condition of trf., enhancing its life due to overhauling. Revenue gain due to loss reduction, results into pay back period of Cost of overhauling in couple of years. 7

18 Thank you 8

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer

More information

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating

More information

S C Strength of Winding Exits and Leads : A critical area for Failure Prevention in Power Transformers

S C Strength of Winding Exits and Leads : A critical area for Failure Prevention in Power Transformers S C Strength of Winding Exits and Leads : A critical area for Failure Prevention in Power Transformers by MANAN PANDYA SIEMENS LTD. manan.pandya@siemens.com 1 Introduction Short circuit withstand capability

More information

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander

More information

Operational Management of Grid Transformers An Experience of POWERGRID

Operational Management of Grid Transformers An Experience of POWERGRID Operational Management of Grid Transformers An Experience of POWERGRID 1.0 Introduction P.N. Dixit, GM; S. Victor, AGM; V.K. Bhaskar, CM; Gunjan Agrawal, Manager Operation Services Department Power Grid

More information

Transformer condition assessment with an integrated test van

Transformer condition assessment with an integrated test van Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)

More information

HOW TO SAFE GUARD THE TRANSFORMER..???

HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,

More information

Substation Preventive Maintenance

Substation Preventive Maintenance Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS

More information

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M SL. NO NOMINAL DIAMETER "D" mm GASKETED JOINT (Nm) WOODEN CORE CLAMP (Nm) STEEL FIXING STUD FOR BUSHING (Nm) BUSHING STEM (Nm) (BRASS /COPPER) COPPER BUSBAR (Nm) 1 M6 5 - - - - 2 M8 12 - - 10-3 M10 22

More information

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa

More information

Effective maintenance test techniques for power transformers

Effective maintenance test techniques for power transformers Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure

More information

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/F.06/2015-16/Mgr(Bawana)/353 dated

More information

Benefits of SFRA - Case Studies

Benefits of SFRA - Case Studies 6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO

More information

REPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD.

REPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD. REPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD. (DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/2015-16/Mgr(T)O&M-E-2/22

More information

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

HVDC High Voltage Direct Current

HVDC High Voltage Direct Current HVDC High Voltage Direct Current Typical HVDC Station BACK TO BACK CONVERTER STATION MONO POLAR WITH GROUND RETURN PA Back to Back Converters indicates that the Rectifiers & Inverters are located in the

More information

Regional Technical Seminar SHORT CIRCUIT FORCES

Regional Technical Seminar SHORT CIRCUIT FORCES Regional Technical Seminar SHORT CIRCUIT FORCES Short Circuit Forces Wallace Exum Electrical Design Engineer wallace.exum@spx.com Agenda 1. What is Short Circuit 2. Types of Faults 3. How to Calculate

More information

CHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses

CHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses CHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses 8.1 Introduction The present level of Transmission and Distribution (T & D) losses in Indian power system is estimated

More information

Regional Technical Seminar

Regional Technical Seminar Regional Technical Seminar LOAD TAP CHANGERS (LTCS) DESIGN, OPERATION, AND MAINTENANCE CONSIDERATIONS SPX Dallas Facility Damon Jones General Manager SPX Transformer Solutions Components Group Cell: 214-422-8979

More information

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS 38 CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS 3.1 INTRODUCTION Addition of more generating capacity and interconnections to meet the ever increasing power demand are resulted in

More information

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical

More information

Lecturer: Dr. J B E AL-ATRASH No. of Pages: 4

Lecturer: Dr. J B E AL-ATRASH No. of Pages: 4 Philadelphia University Faculty of Engineering Dept. of Electrical Engineering Student Name: Student Number: Final Exam Course Title: Design of T&D System Date: 15 th June 2016 Course No: 610 515/650511

More information

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site

More information

TRANSFORMER TECHNOLOGY GPT

TRANSFORMER TECHNOLOGY GPT Core-Form TRANSFORMER TECHNOLOGY GlobalPT Corporation performs research and engineering developments and co-ordination of works of technical partners in the field of technological progress and commercial

More information

POWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

POWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E POWER TRANSFORMER Failure Analysis & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Electricity is high-grade energy. Working

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz

Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz 2007 1979 1892 Transformer reliability Ability to perform its required functions under stated conditions for a specified period of time Failure

More information

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY) E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION

More information

Efacec work every day to anticipate solutions for a sustainable world in the new energy era.

Efacec work every day to anticipate solutions for a sustainable world in the new energy era. Transformers Efacec is the largest industrial portuguese company of the electric and electromechanical sector developing high technology products, solutions and systems used every day by millions of people

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Phase Shifting Transformers. Presented by

Phase Shifting Transformers. Presented by Phase Shifting Transformers Presented by Phase Shifting Transformers (PST s) (a.k.a. Phase Angle Regulators) VS φ S P V V S = X L L X L sin( φ φ ) L S VL φ L PST s are power flow control devices between

More information

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2 Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II

More information

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...

More information

ABB Power Products Service

ABB Power Products Service Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?

More information

Distribution Equipments - Technology and Applications. Training Module for DISTRIBUTION TRANSFORMER

Distribution Equipments - Technology and Applications. Training Module for DISTRIBUTION TRANSFORMER Distribution Equipments - Technology and Applications Training Module for DISTRIBUTION TRANSFORMER Transformer specification Transformer design Manufacturing / quality control Testing in the Works Transportation

More information

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX Particulate Control O&M Training APC/PCUG Conference July 12-16, 2009 The Woodlands, TX WPCA Particulate Training Seminar July 11, 2009 ESP Power Supply Choices Slide No 1 Precipitator Power Supplies Conventional

More information

EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY

EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY EPS AUSTRALIA SERVICES COMPANY OVERVIEW EPS is a recognised company specialising in Electrical, Instrumentation, Structural, Mechanical and

More information

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

DISTRIBUTION TRANSFORMER kv

DISTRIBUTION TRANSFORMER kv ELECTRICITY COMMISSION PLANNING AND STUDY DEP BAGHDAD, REPUBLIC OF IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER kv REVISION YEAR 2001 DISTRIBUTION TRANSFORMERS 1- SCOPE OF THE TENDER : Tenderer

More information

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K UNIT II TRANSFORMERS PART A 1. Define a transformer? A transformer is a static device which changes the alternating voltage from one level to another. 2. What is the turns ratio and transformer ratio of

More information

CAST RESIN DRY TRANSFORMER

CAST RESIN DRY TRANSFORMER CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,

More information

The Upgradabilty of Conventional Three Phase Delta/Star Networks

The Upgradabilty of Conventional Three Phase Delta/Star Networks The Upgradabilty of Conventional Three Phase Delta/Star Networks WHY NEW STANDARDS? CAPITAL COSTS Initial Final OPERATIONAL COSTS UPGRADABILITY SAFETY MAINTAINANCE CONVENTIONAL CONFIGURATION Electrification

More information

Variation in SFRA plot due to design and external parameter

Variation in SFRA plot due to design and external parameter Chapter 6 Variation in SFRA plot due to design and external parameter 6.1 Introduction As the experience grows with Sweep Frequency Response Analysis in world, it is useful to discuss the measurements

More information

TRAFO ELECTRIC P. LTD.

TRAFO ELECTRIC P. LTD. TRAFO ELECTRIC P. LTD. About Us Trafo Electric P. Ltd. started manufacturing Power & Distribution Transformers in 1974. Originally known as J B Electricals, the unit s entire production was for BSES( Bombay

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

Be on guard for effective testing: Introduction

Be on guard for effective testing: Introduction Be on guard for effective testing: Introduction The development of the insulation tester by Evershed and Vignoles is part of our electrical history, with insulation testers produced by Megger Instruments

More information

86 chapter 2 Transformers

86 chapter 2 Transformers 86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.

More information

Subject: Computer Aided Electrical drawing (CAED) Subject Code: 10EE65

Subject: Computer Aided Electrical drawing (CAED) Subject Code: 10EE65 Subject: Computer Aided Electrical drawing (CAED) Subject Code: 10EE65 Syllabus Covered Part-B 3. Electrical machine assembly drawing using design data or sketches or both (a) Transformers- sectional views

More information

SPE. Subsea Power Transfer. - What is the challenge APPLIED TECHNOLOGY WORKSHOP. Technology for for the Next Generation Subsea Systems

SPE. Subsea Power Transfer. - What is the challenge APPLIED TECHNOLOGY WORKSHOP. Technology for for the Next Generation Subsea Systems Subsea Power Transfer - What is the challenge By Svend Rocke, ABB offshore Systems as SPE 110203Page 1- SPE APPLIED TECHNOLOGY WORKSHOP Technology for for the Next Generation Subsea Systems Oslo February

More information

QUESTIONNAIRE for Wind Farm Power Stations only

QUESTIONNAIRE for Wind Farm Power Stations only TRANSMISSION SYSTEM OPERATOR QUESTIONNAIRE for Wind Farm Power Stations only To be submitted by the Generation Licensees together with the Application for Connection Certificate according to IEC 61400-21

More information

Constant Terminal Voltage. Working Group Meeting 4 19 th September 2014

Constant Terminal Voltage. Working Group Meeting 4 19 th September 2014 Constant Terminal Voltage Working Group Meeting 4 19 th September 014 Overview Options summary System under investigation Options analysis Discussion Options Option 1 Constant Terminal Voltage controlled

More information

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED Dial : (033)2677-5835 & 2667-8358 Tele Fax : (033)2667-8358 Manufacturer of Dry Type Transformers E-mail : unimag111@gmail.com Office & Factory : 26/5, Sarat Chatterjee Road, Howrah 711 104, West Bengal,

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

Introduction. Centrado leading-edge transformer. Introduction

Introduction. Centrado leading-edge transformer. Introduction Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,

More information

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA Taking into account that power transformer is the major item of equipment in power systems, its correct operation is vital to system operation. It is well known that transformer failures are sometimes

More information

Power Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer

Power Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer Power Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer Ivica Pavić Faculty of Electrical Engineering and Computing Zagreb, CROATIA Sejid Tešnjak Faculty of Electrical

More information

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER JESSE M LOPEZ CPS ENERGY USA EMILIO MORALES CRUZ QUALITROL USA SUMMARY Power transformers are essential

More information

Power Transformer Condition Assessment Based on Standard Diagnosis

Power Transformer Condition Assessment Based on Standard Diagnosis Power Transformer Condition Assessment Based on Standard Cattareeya Suwanasri Abstract The diagnostic techniques of electrical and insulating oil testing are proposed to assess the internal condition of

More information

Siemens Transformer Technology Seminar Low Partial Discharge Transformers

Siemens Transformer Technology Seminar Low Partial Discharge Transformers West Coast Technical Meeting Pomona CA, May 24-25, 2016 Siemens Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Low Partial Discharge Page 2 Why highlight Low Partial Discharge

More information

LOSS ESTIMATION FOR THREE 33/11kV TRANSFORMERS AT SCOTTISH & SOUTHERN ENERGY POWER DISTRIBUTION

LOSS ESTIMATION FOR THREE 33/11kV TRANSFORMERS AT SCOTTISH & SOUTHERN ENERGY POWER DISTRIBUTION LOSS ESTIMATION FOR THREE 33/11kV TRANSFORMERS AT SCOTTISH & SOUTHERN ENERGY POWER DISTRIBUTION by SIMON RYDER Addressee: MACIEJ FILA (SCOTTISH& SOUTHERN ENERGY POWER DISTRIBUTION) Registered in England

More information

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers Introduction Tap changer at active part Example of 3-phase tapchanger Page 2 Winding Configurations

More information

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)

More information

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is

More information

Resistance and Ohm s law

Resistance and Ohm s law Resistance and Ohm s law Objectives Characterize materials as conductors or insulators based on their electrical properties. State and apply Ohm s law to calculate current, voltage or resistance in an

More information

Case Study 1. Power System Planning and Design: Power Plant, Transmission Lines, and Substations

Case Study 1. Power System Planning and Design: Power Plant, Transmission Lines, and Substations Case Study 1 Power System Planning and Design: Power Plant, Transmission Lines, and Substations Lindsay Thompson, 5203120 Presented to Riadh Habash ELG 4125 11/10/2013 1.0 ABSTRACT A power plant delivers

More information

Working Group Members

Working Group Members POWER TRANSFORMER - STANDARDISATION MANUAL 6 Chapter - 7 Design Review Working Group Members Mr. M. Vijayakumaran ALSTOM Ltd Mr. S. K. Negi Mr. Y. V. Joshi GETCO GETCO 6 POWER TRANSFORMER - STANDARDISATION

More information

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES 3.1. Introduction Power Transformer is the nerve centre of any power distribution system. The capacity of power transformers is generally decided

More information

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc. Western Mining Electric Association San Antonio TX NOVEMBER 15, 2012 PRESENTED BY David L. Harris, PE Customer Technical Executive SPX Transformer Solutions, Inc. Office: 262-521-0166 Cell: 262-617-3039

More information

3-phase short-circuit current (Isc) at any point within a LV installation

3-phase short-circuit current (Isc) at any point within a LV installation 3-phase short-circuit current (Isc) at any point within a LV installation In a 3-phase installation Isc at any point is given by: where U 20 = phase-to-phase voltage of the open circuited secondary windings

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Power transformers for Network, Rectifiers, Furnace

Power transformers for Network, Rectifiers, Furnace E N G L I S H OTN, OTR, OTF Transformers Power transformers for Network, Rectifiers, Furnace TTR TTO OTN, OTR, OTF reactors TTH OTN, OTR, OTF Transformers Technology Design Our designers experience combined

More information

PROBLEMS on Transformers

PROBLEMS on Transformers PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary

More information

Federal Power Transformers LLC based in Abu Dhabi, UAE

Federal Power Transformers LLC based in Abu Dhabi, UAE www.fpt.ae Federal Power Transformers LLC based in Abu Dhabi, UAE CONTENTS The Company...03 Design Process...05 Manufacturing...07 Testing...11 Quality...13 After Sales Support & Other Services...15 Satisfied

More information

Type VAEM 22 Negative Potential Biasing Relay

Type VAEM 22 Negative Potential Biasing Relay Type VAEM 22 Negative Potential Biasing Relay Type VAEM 22 Negative Potential Biasing Relay VAEM 22 Relay withdrawn from case Features l Simple and robust construction l High sensitivity Application The

More information

DISTRIBUTION TRANSFORMERS

DISTRIBUTION TRANSFORMERS The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 4 DISTRIBUTION TRANSFORMERS A transformer is a static device that

More information

The Advantages and Application of Three Winding Transformers

The Advantages and Application of Three Winding Transformers The Advantages and Application of Three Winding Transformers MSc, CEng, FIEE, FIMechE, FIPENZ Principal, Sinclair Knight Merz Abstract Although seldom used in Australia and New Zealand, three winding transformers

More information

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.

More information

TRANSMISSION ASSETS. Filed: September 12, 2006 EB Exhibit D1 Tab 1 Schedule 2 Page 1 of INTRODUCTION

TRANSMISSION ASSETS. Filed: September 12, 2006 EB Exhibit D1 Tab 1 Schedule 2 Page 1 of INTRODUCTION Filed: September, 00 EB-00-00 Schedule Page of TRANSMISSION ASSETS.0 INTRODUCTION 0 Hydro One Networks Inc. is licensed by the Ontario Energy Board (OEB) to own, operate and maintain transmission facilities

More information

Basic Principles and Operation of Transformer

Basic Principles and Operation of Transformer Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core

More information

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

Electrical Description

Electrical Description History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced

More information

N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon

N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon POWER TRANSFORMERS Factory condition POWER TRANSFORMERS Site condition POWER TRANSFORMER FAULTS Faults in a Transformer 1. Internal Faults

More information

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1 Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector

More information

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION - S K Mishra & S K Das NHPC Ltd O&M Division 1 PRESENTATION COVERS Introduction DESCRIPTION OF EVENTS INITIAL RESPONSE DETAILED INSPECTION

More information

Sensor Technology. Applications for medium voltage

Sensor Technology. Applications for medium voltage Sensor Technology Applications for medium voltage Contents Introduction to sensor technology... 3 Sensors versus instrument transformers... 6 Advantages for builders and users of switchgear... 7 The impact

More information

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION Important Instructions to examiners: 1) The answers should be examined by key words and not as word-to-word as given in the model answer scheme. 2) The model answer and the answer written by candidate

More information

INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H.

INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H. INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H. Aliche 1,2 nnamdi azikiwe university, awka, anambra state, nigeria.

More information

Regional Technical Seminar SHORT CIRCUIT FORCES

Regional Technical Seminar SHORT CIRCUIT FORCES Regional Technical Seminar SHORT CIRCUIT FORCES Douglas W Reed Principal Electrical Design Engineer douglas.reed@spx.com SPX Transformer Solutions, Inc. June 20th, 2018 Agenda 1.Review transformers: How

More information

The Polytransformer. The Multivoltage Substation Power Transformer

The Polytransformer. The Multivoltage Substation Power Transformer The Polytransformer The Multivoltage Substation Power Transformer The need for a single transformer for different transmission systems. Change of electric power industry to a fully competitive and deregulated

More information

Welcome to the Session on. HT Distribution Network

Welcome to the Session on. HT Distribution Network Welcome to the Session on HT Distribution Network Learning Objective By the end of this session you will be able to: Explain the HT distribution network breakdown maintenance - possible faults, identification

More information

ON-SITE TESTING OF SPECIAL TRANSFORMERS

ON-SITE TESTING OF SPECIAL TRANSFORMERS ON-SITE TESTING OF SPECIAL TRANSFORMERS Simanand GANDHI JEYARAJ, Megger Ltd, UK, Simanand.gandhi@megger.com, Robert MILNE, UK Power Networks, UK, robert.milne83@googlemail.com Grant MITCHELL, Transmag

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

MODEL INFORMATION. Model AWRMS TM 200. Automated Winding Resistance Measurement System

MODEL INFORMATION. Model AWRMS TM 200. Automated Winding Resistance Measurement System Model AWRMS TM 200 Automated Winding Resistance Measurement System Currents up to 200A for performing Winding Resistance and Heat Run Tests. Heavy Duty Protection Circuit. Accuracy with Four Wire Measurements

More information

DISTRIBUTION TRANSFORMER 11 / kv

DISTRIBUTION TRANSFORMER 11 / kv Ministry of Electricity (MOE) Power Distribution Office Baghdad IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 11 / 0.416 kv 2BREVISION 3BYEAR 2013 1 Table of Contents: Clause : no. 1. Scope of The

More information

148 Electric Machines

148 Electric Machines 148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional

More information

Single-Phase Transformation Review

Single-Phase Transformation Review Single-Phase Transformation Review S T U D E N T M A N U A L March 2, 2005 2 STUDENT TRAINING MANUAL Prerequisites: None Objectives: Given the Construction Standards manual and a formula sheet, you will

More information