Regional Technical Seminar SHORT CIRCUIT FORCES
|
|
- Antonia Morris
- 5 years ago
- Views:
Transcription
1 Regional Technical Seminar SHORT CIRCUIT FORCES
2 Short Circuit Forces Wallace Exum Electrical Design Engineer
3 Agenda 1. What is Short Circuit 2. Types of Faults 3. How to Calculate Short Circuit Current 4. Relationship between Current, Magnetic Field and Forces 5. Short Circuit Failure Modes 6. Non-standard Requirements 7. Types of Transformer Applications with Special Fault Duty SPX Transformer Solutions, Inc. August 31,
4 What is Short Circuit SPX Transformer Solutions, Inc.
5 Normal Transformer Operation Normal Circuit An AC source supplies power to a given load (i.e. a city). A complete circuit has a source, with power entering a load and returning to the source. Amount of current that flows is directly related to the load on the transformer amps 1000 amps SPX Transformer Solutions, Inc. June 20 th,
6 12500 amps What is a Fault? System Fault An un-intended electrical connection made between two energized components having different voltage potentials. Results in some (or all) of the current bypassing the intended load. Currents are typically very high due to low fault impedance SPX Transformer Solutions, Inc. June 20 th,
7 Types of Faults SPX Transformer Solutions, Inc.
8 Types of Faults Basic Types of Faults in Power Systems Line-to-Ground (Most Common) One or more conductors make electrical contact with ground Example: Wildlife or Lightning. A lightning strike causes a flashover. The stroke between the line and ground causes ionization of the air (a low impedance path to ground). SPX Transformer Solutions, Inc. August 31,
9 Types of Faults Basic Types of Faults in Power Systems Line-to-Line Two different phases come into direct or indirect contact with each other Example: A bird with a large wingspan touches two conductors simultaneously SPX Transformer Solutions, Inc. August 31,
10 Types of Faults Basic Types of Faults in Power Systems Double Line-to-ground Three Phase (least common) Similar to Line-to-Line but when all three phases make contact with each other Example: A falling tree on a transmission line SPX Transformer Solutions, Inc. August 31,
11 Types of Faults IEEE Standards for Transformers and Short Circuit: C Section 7 Liquid-immersed transformers shall be designed and constructed to withstand the mechanical and thermal stresses produced by external short circuits under the conditions specified in 7.1.3, 7.1.4, and The external short circuits shall include three-phase, single line-toground, double line-to-ground, and line-to-line faults on any one set of terminals at a time. Duration of faults shall be limited to 2 seconds unless otherwise specified by the user Transformer components such as leads, bushings, LTCs, de-energized tap changers, and current transformers that carry current continuously shall comply with all the requirements of and However, when not explicitly specified, LTCs are not required to change taps successfully under short circuit conditions. The temperature of the winding conductor (copper) during short circuit shall not exceed 250C C Section 12 Impedance variation shall not exceed 2% for transformers <= 30MVA (ONAN) Impedance variation shall not exceed 1% for transformers > 30MVA (ONAN) Transformers shall be designed to withstand all types of faults SPX Transformer Solutions, Inc. August 31,
12 Types of Faults IEEE Standards for Transformers and Short Circuit: IEEE Standard C Sample I 2 * t curve for a Category IV transformer. Category IV transformer > 10,000 KVA single-phase > 30,000 KVA three-phase SPX Transformer Solutions, Inc. August 31,
13 How to Calculate Short Circuit Current SPX Transformer Solutions, Inc.
14 How to Calculate Short Circuit Current C Section 7 defines both symmetrical and asymmetrical current Symmetrical Current Asymmetrical Current Isc symmetrical SC Current (A, rms) Ir rated current (A, rms) Zt transformer impedance for same voltage tap and MVA as rated current (Ir) Zs system impedance in per unit on the same MVA base for rated current (Ir) Make sure Ir and Zt are on the same MVA base SPX Transformer Solutions, Inc. August 31,
15 How to Calculate Short Circuit Current EXAMPLE: Assume we have a 30MVA transformer with a 69kV primary and a rated secondary current of 1000 amps. The tested load losses are 72 kw, and the tested impedance is 8.0%. Find Isc and Isc(pk,asym). Symmetrical Current with Zs Symmetrical Current without Zs Z s Z s = MVA T MVA S = = 0.31% = 12,034 A = 12,500A Difference is almost 500A or 4% Note: Zs is derived from C Table 14 if not specified from customer. SPX Transformer Solutions, Inc. August 31,
16 How to Calculate Short Circuit Current EXAMPLE: Assume we have a 30MVA transformer with a 69kV primary and a rated secondary current of 1000 amps. The tested load losses are 72 kw, and the tested impedance is 8.0%. Find Isc and Isc(pk,asym). Asymmetrical Current without Zs I SC pk asym = ,500 I SC pk asym = 33,775 A Note: Forces are proportional to current-squared. Therefore the forces from this example will be (33,775 amps / 1000 amps) 2 = (33.775) 2 = 1140 x normal forces 1. Find %R Load Loss (kw) %R = 100x KVA T 2. Find X/R X R = Z T %R = 8% 0.24% = = 100x72 30,000 = 0.24% K = 1 + e tan π sin(tan 1 (33.33)) 2 K = SC Current is much greater than normal load current SPX Transformer Solutions, Inc. August 31,
17 How to Calculate Short Circuit Current EXAMPLE: Assume we have a 30MVA transformer with a 69kV primary and a rated secondary current of 1000 amps. The tested load losses are 72 kw, and the tested impedance is 8.0%. Find Isc and Isc(pk,asym). C Table 13 K = 1 + e tan π sin(tan 1 (33.33)) 2 K = Peak factor can be calculated or more easily looked up in table SPX Transformer Solutions, Inc. August 31,
18 How to Calculate Short Circuit Current COMPARISON EXAMPLE: Assume we have a 30MVA transformer with a 69kV primary and a rated secondary current of 1000 amps. What is the symmetrical current considering only the transformer impedance of 8%. What is it at 6% Symmetrical Current, 8% Zt Symmetrical Current, 6% Zt = 12,500A = 16,667A SPX Transformer Solutions, Inc. August 31,
19 How to Calculate Short Circuit Current Impedance Consequences Standard Impedances are tabulated in C Section Standard Impedances are classified by HV BIL and whether or not the unit has an LTC Standard Impedances are tabulated for the self-cooled (ONAN) rating SPX Transformer Solutions, Inc. August 31,
20 Relationship Between Current, Magnetic Field and Force SPX Transformer Solutions, Inc.
21 Relationship Between Current, Magnetic Field and Force Resulting Magnetic Field Direction (CW) Current Flow Derived from Maxwell s MMF Law SPX Transformer Solutions, Inc. August 31,
22 Relationship Between Current, Magnetic Field and Force Effect of Many Turns Fields at inner/outer edges add together. One uniform magnetic path results Magnetic field (B) intensifies with # turns (N) or the current (I). B NI F (NI) 2 Forces are proportional to the amount of current, squared SPX Transformer Solutions, Inc. August 31,
23 Relationship Between Current, Magnetic Field and Force Left hand rule Resulting Magnetic Field Direction (CW) F Resulting Force Direction F - Force B Flux I - Current Current Flow (I) Leakage Magnetic Field (B) Remember TIM and the FBI SPX Transformer Solutions, Inc. August 31,
24 Relationship Between Current, Magnetic Field and Force Weaker Magnetic Field Weaker Magnetic Field Arrows represent FORCE and its relative magnitude & direction Max LV COIL Strongest Magnetic Field HV COIL SPX Transformer Solutions, Inc. Min Magnetic Field Radial Distance August 31,
25 Relationship Between Current, Magnetic Field and Force A net magnetic force also results between two coils (i.e. HV to LV), because the two coils are essentially two huge electro-magnets that repel each other. Repulsive Force Directions Between Magnets or Coils Summative force between these coils could be millions of pounds The inner coil experiences net inward radial crushing compressive forces The outer coil experiences net outward radial expanding type forces SPX Transformer Solutions, Inc. August 31,
26 Relationship Between Current, Magnetic Field and Force INDICATES FORCE DIRECTION Mag field leaks out radially whenever there is an axial spreading out of turns in a coil. The larger the axial spread of turns, the more radial the field becomes Axial Location of DETC Taps Finite Element Analysis of Leakage Field Between Coils SPX Transformer Solutions, Inc. August 31,
27 Short Circuit Failure Modes Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc.
28 Short Circuit Failure Modes Axial Radial Combined Beam Bending Beam Bending Spiraling Keyspacer Compression Buckling Telescoping Conductor Tilting Hoop Facture of Axial Support SPX Transformer Solutions, Inc. August 31,
29 Short Circuit Failure Modes Ribs Cooling duct Radial spacers Paper insulated conductor SPX Transformer Solutions, Inc. August 31,
30 Short Circuit Failure Modes Due to Axial Forces Axial Beam Bending & Keyspacer Compression Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc. August 31,
31 Short Circuit Failure Modes Due to Axial Forces Conductor Tilting SPX Transformer Solutions, Inc. August 31,
32 Short Circuit Failure Modes Due to Axial Forces Fracture of Axial Support Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc. August 31,
33 Short Circuit Failure Modes Axial Forces - Design Criteria Fracture of Axial Support Coil Supports Limited on deflection and flexural strength Verticals/ Flitch-plates are designed to some % of yield strength Active-Part is pre-stressed (clamped) Keyspacer Compression Stress must be no more than 11,600 PSI (80 mpa) for Paper Covered Conductor (Much less than facture limit) Stress must be no more than 17,400 PSI (120 mpa) for Paperless Conductor (such as netting CTC) Axial Beam Bending Stress must be no more than some % of yield strength Conductor Tilting Stress must be no more than some % critical tilting limit SPX Transformer Solutions, Inc. August 31,
34 Short Circuit Failure Modes Due to Radial Forces Beam Bending SPX Transformer Solutions, Inc. August 31,
35 Short Circuit Failure Modes Due to Radial Forces Buckling Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc. August 31,
36 Short Circuit Failure Modes Due to Radial Forces Hoop SPX Transformer Solutions, Inc. August 31,
37 Short Circuit Failure Modes Radial Forces - Design Criteria Radial Beam Bending and Hoop Stress must be no more than some % of yield strength Buckling Designed for Free and Forced Buckling Stress must be no more than some % of critical buckling limit Critical buckling limit depends on the slenderness ratio of the winding and the yield strength of the conductor SPX Transformer Solutions, Inc. August 31,
38 Short Circuit Failure Modes Due to Combined Forces Spiraling Telescoping Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc. August 31,
39 Winding Temperature During a Short Circuit Calculated on basis that all heat is stored (heats up too quickly to radiate heat to equilibrium) Insulation Temperature not to exceed 250 C for copper 200 C for EC grade aluminum Copper or Aluminum Method defined on IEEE C section 7.4. Insulated Conductor SPX Transformer Solutions, Inc. June 20 th,
40 Winding Temperature During a Short Circuit Approximate method: Tf = (SΔk)2 t Km + TOR + Ta Tf = final winding temperature at end of a short circuit ( C) TOR = maximum top liquid temperature rise over ambient temperature ( C) Ta = ambient temperature ( C) SΔk = winding current density at symmetrical short circuit current (W/dm 2 ) t = short circuit duration (s). Km = 156 for copper / 73 for EC grade aluminum SPX Transformer Solutions, Inc. June 20 th,
41 Non-Standard Requirements SPX Transformer Solutions, Inc.
42 Non-Standard Requirements Short Circuit Current shall only be limited by the transformer impedance. Windings shall be designed for infinite bus condition (no system impedance). Any pre-fault operating voltage greater than 1.0 per unit rated voltage Any customer specified asymmetrical peak factor (Ex: 2.762) Any customer specified minimum offset of the winding s electrical centers Any customer specified buckling limits Example: Stress must be less than 35% of yield strength for Magwire Customer specifies CTC for all windings subjected to compressive forces References to IEC Annex A Fault duration longer than 2 seconds Special fault duty (C Section ) Specific lead support requirements (max span, material, density, etc.) SPX Transformer Solutions, Inc. August 31,
43 Non-Standard Requirements - EXAMPLE EXAMPLE IS A TWO WINDING NON-LTC TRANSFORMER (DYN1). 12/16/20MVA 69KV 26.4KV 8.0% IZ FOUR CASES 0.25% OF WINDING OFFSET, 0% OVERVOLTAGE 0.50% OF WINDING OFFSET, 0% OVERVOLTAGE 0.50% OF WINDING OFFSET, 5% OVERVOLTAGE 0.50% OF WINDING OFFSET, 10% OVERVOLTAGE SPX Transformer Solutions, Inc. August 31,
44 Non-Standard Requirements - EXAMPLE STRESS (PSI) FOR THE FOUR DIFFERENT CASES Low Voltage (Inner Winding) Radial Axial Beam Beam Keyspacer Hoop Buckling Bending Bending Compression Conductor Tilting 0.25% Wdg Offset, 0% Overvoltage % Wdg Offset, 0% Overvoltage % Wdg Offset, 5% Overvoltage % Wdg Offset, 10% Overvoltage SPX Transformer Solutions, Inc. August 31,
45 Non-Standard Requirements - EXAMPLE STRESS (PSI) FOR THE FOUR DIFFERENT CASES High Voltage (Outer Winding) Radial Axial Beam Beam Keyspacer Conductor Hoop Buckling Bending Bending Compression Tilting 0.25% Wdg Offset, 0% Overvoltage % Wdg Offset, 0% Overvoltage % Wdg Offset, 5% Overvoltage % Wdg Offset, 10% Overvoltage SPX Transformer Solutions, Inc. August 31,
46 Non-Standard Requirements - EXAMPLE PERCENT INCREASE FOR THE FOUR DIFFERENT CASES Low Voltage (Inner Winding) Radial Axial Beam Beam Keyspacer Hoop Buckling Bending Bending Compression Conductor Tilting 0.25% Wdg Offset, 0% Overvoltage % Wdg Offset, 0% Overvoltage -0.04% -0.04% -0.03% 0.59% 7.27% 7.20% 0.50% Wdg Offset, 5% Overvoltage 10.23% 10.23% 10.22% 10.90% 18.26% 18.20% 0.50% Wdg Offset, 10% Overvoltage 20.97% 20.97% 20.96% 21.71% 29.79% 29.77% SPX Transformer Solutions, Inc. August 31,
47 Non-Standard Requirements - EXAMPLE PERCENT INCREASE FOR THE FOUR DIFFERENT CASES High Voltage (Outer Winding) Radial Axial Beam Beam Keyspacer Conductor Hoop Buckling Bending Bending Compression Tilting 0.25% Wdg Offset, 0% Overvoltage % Wdg Offset, 0% Overvoltage -0.04% % 6.61% 6.66% 0.50% Wdg Offset, 5% Overvoltage 10.21% % 17.55% 17.59% 0.50% Wdg Offset, 10% Overvoltage 20.95% % 29.01% 29.00% SPX Transformer Solutions, Inc. August 31,
48 Non-Standard Requirements - EXAMPLE Changing the offset of electrical centers of the windings primarily affects the axial forces Changing the pre-fault overvoltage condition increases the Peak Factor (K) by that same percentage thereby increasing the peak current. Both axial and radial forces are affected. 5% Overvoltage will increase the short circuit forces by about 10% 10% Overvoltage will increase the short circuit forces by about 21% SPX Transformer Solutions, Inc. August 31,
49 Questions SPX Transformer Solutions, Inc.
Regional Technical Seminar SHORT CIRCUIT FORCES
Regional Technical Seminar SHORT CIRCUIT FORCES Douglas W Reed Principal Electrical Design Engineer douglas.reed@spx.com SPX Transformer Solutions, Inc. June 20th, 2018 Agenda 1.Review transformers: How
More informationTransformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications
The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of
More informationCHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION
18 CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION 2.1 INTRODUCTION Transformers are subjected to a variety of electrical, mechanical and thermal stresses during normal life time and they fail when these
More informationWestern Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.
Western Mining Electric Association San Antonio TX NOVEMBER 15, 2012 PRESENTED BY David L. Harris, PE Customer Technical Executive SPX Transformer Solutions, Inc. Office: 262-521-0166 Cell: 262-617-3039
More informationElectrical Design Process
Electrical Design Process Jason Varnell Lead Design Engineer Jason.Varnell@spx.com SPX Transformer Solutions, Inc. September 26, 2018 Agenda 1. Bid Design Process Parameters Affecting Bid Design 2. Final
More informationTransformer Technology Seminar What to consider at Design Reviews
Pomona CA, May 24-25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Why to perform Design Review Meetings? To ensure both parties having the same understanding of the
More informationPES & IAS NY Chapter And NY LMAG June 23 rd, 2015
PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 High Temperature Insulation Systems and their use in Mobile Transformers Myron B. Bell, PE mbell@deltastar.com Delta Star, Inc. June 23 rd 2015 Introduction
More informationCHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS
38 CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS 3.1 INTRODUCTION Addition of more generating capacity and interconnections to meet the ever increasing power demand are resulted in
More informationRegional Technical Seminar TAP CHANGERS
Regional Technical Seminar TAP CHANGERS SPX Transformer Solutions, Inc. September 4, 2018 De-Energized and Load Tap Changers Jason Varnell Lead Design Engineer jason.varnell@spx.com SPX Transformer Solutions,
More informationTransformer Technology Seminar Winding Selection
Pomona, CA May 24 25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Windings: Page 2 Example GSU 274/464MVA H0 H1 H2 H3 U U I I H L H L N = N N = N L H H L HV: 405kV ±8x1.25%
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationTRANSFORMER TECHNOLOGY GPT
Core-Form TRANSFORMER TECHNOLOGY GlobalPT Corporation performs research and engineering developments and co-ordination of works of technical partners in the field of technological progress and commercial
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationTransformer Design: Economics & Reliability
Transformer Design: Economics & Reliability Weidmann-ACTI Inc. Technical Conference New Diagnostic Concepts for Better Asset Management November 8 10, 2004 Holiday Inn Capitol Plaza, Sacramento, CA H.
More informationDATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO
PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %
More informationsave energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers
save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED
More informationHOW TO SAFE GUARD THE TRANSFORMER..???
CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various
More informationUnderstanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques
Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion
More information86 chapter 2 Transformers
86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.
More informationTIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M
SL. NO NOMINAL DIAMETER "D" mm GASKETED JOINT (Nm) WOODEN CORE CLAMP (Nm) STEEL FIXING STUD FOR BUSHING (Nm) BUSHING STEM (Nm) (BRASS /COPPER) COPPER BUSBAR (Nm) 1 M6 5 - - - - 2 M8 12 - - 10-3 M10 22
More informationGroup F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A
Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating
More informationShort-Circuit Current Calculations
Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.
More informationS C Strength of Winding Exits and Leads : A critical area for Failure Prevention in Power Transformers
S C Strength of Winding Exits and Leads : A critical area for Failure Prevention in Power Transformers by MANAN PANDYA SIEMENS LTD. manan.pandya@siemens.com 1 Introduction Short circuit withstand capability
More informationCONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationPhase Shifting Transformers. Presented by
Phase Shifting Transformers Presented by Phase Shifting Transformers (PST s) (a.k.a. Phase Angle Regulators) VS φ S P V V S = X L L X L sin( φ φ ) L S VL φ L PST s are power flow control devices between
More informationPROBLEMS on Transformers
PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationWESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)
WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices
More informationS. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)
S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical
More informationSOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)
E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationPCS Working Group on General Requirements C
WG Item 82 C57.12.00-2000 Section 7.1.4.4 Stabilizing windings Change Requested by : V. Sankar 5/07/2005 & 10/23/2006 Requested Change : Request to form a task force to discuss the following on buried
More informationANALYSIS OF OPERATION MODE AND PERFORMANCE INDICATORS OF A TRANSFORMER WHEN CONTROLLING ITS VOLTAGE WITH AN ALTERNATING MAGNETIC FLUX
International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 10, October 2018, pp. 211 218, Article ID: IJMET_09_10_020 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=9&itype=10
More informationDEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What
More informationHendrix Tap, Tie & Ground Wire
Hendrix Tap, Tie & Ground Wire MADE IN U.S.A. 53 Old Wilton Road Milford, NH 03055-3119 603-673-2040 www.marmonutility.com A Marmon Wire & Cable/Berkshire Hathaway Company Tap Wire Description Hendrix
More informationEffects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More informationMV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer
PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with
More informationPower Transformers Basics
Power Transformers Basics Transformer Basic Objective Introduce Basic Transformer Theory as it Relates to Diagnostics Provide a Better Understanding of the Diagnostic Test Environment Identify Important
More informationTRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K
UNIT II TRANSFORMERS PART A 1. Define a transformer? A transformer is a static device which changes the alternating voltage from one level to another. 2. What is the turns ratio and transformer ratio of
More informationGOVERNMENT COLLEGE OF ENGINEERING, BARGUR
1. Which of the following is the major consideration to evolve a good design? (a) Cost (b) Durability (c) Compliance with performance criteria as laid down in specifications (d) All of the above 2 impose
More informationPomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers
Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers Introduction Tap changer at active part Example of 3-phase tapchanger Page 2 Winding Configurations
More informationRegional Technical Seminar
Regional Technical Seminar LOAD TAP CHANGERS (LTCS) DESIGN, OPERATION, AND MAINTENANCE CONSIDERATIONS SPX Dallas Facility Damon Jones General Manager SPX Transformer Solutions Components Group Cell: 214-422-8979
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON Transformers Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer
More informationAssessment of Winding Deformation in Power Transformer using SFRA and Numerical Techniques Ashwini Bhujangrao Gaikwad
Assessment of Winding Deformation in Power Transformer using SFRA and Numerical Techniques Ashwini Bhujangrao Gaikwad Department of Electrical Engineering National Institute of Technology Rourkela Assessment
More informationUNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationProlific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2
Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II
More informationTransformers handling and transport
Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,
More informationProtecting power transformers from common adverse conditions
Protecting power transformers from common adverse conditions by Ali Kazemi, and Casper Labuschagne, Schweitzer Engineering Laboratories Power transformers of various size and configuration are used throughout
More informationCONTENTS. 1. Introduction Generating Stations 9 40
CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific
More informationShunt Reactors. Global Top Energy, Machinery & Plant Solution Provider
Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical
More information3Ø Short-Circuit Calculations
3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective
More informationAPPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS
109 APPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS TYPICAL LAYOUT The purpose of a transformer is to transfer energy from the input to the output through the magnetic field. The layout of a partial typical
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationElectrical Description
History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced
More informationCopper Core & Coil Transformer
Copper Core & Coil Transformer Transformer Stomach Pain Normal Operation: Transformer internal structures and windings are subjected to mechanical forces due to the magnetic forces. Through fault current
More informationand cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.
-156 Purpose & Industrial Control Purpose (1000 kva and Below) mounted dry-type transformers of the two-winding type, self-cooled, with ratings and voltages as indicated on the drawings. shall be manufactured
More information51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V
SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without
More informationShort Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More informationGREEN TRAFO PRODUCTS SHR - THREE-PHASE SHUNT REACTOR
SHR - THREE-PHASE SHUNT REACTOR Three-phase shunt for compensation of reactive power and stopping of the electric arc of one-phase short circuit. Maximal allowed time of the one-phase short circuit depends
More informationTABLE OF CONTENT
Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES
More informationMEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly
MEDIUM VOLTAGE PRODUCT PARAMETERS GUIDE How to specify the indoor instrument transformers correctly The range of electric values in the power supply systems is very extensive. This is why it is necessary
More informationPower transformers for Network, Rectifiers, Furnace
E N G L I S H OTN, OTR, OTF Transformers Power transformers for Network, Rectifiers, Furnace TTR TTO OTN, OTR, OTF reactors TTH OTN, OTR, OTF Transformers Technology Design Our designers experience combined
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationCurve accuracy (enough data points to be statistically significant): See Attachment B.
Curve accuracy (enough data points to be statistically significant): See Attachment B. /11.0 proposals Mar 2006.doc /11.0 proposals Mar 2006.doc ATTACHMENT A New Business By Subhash Tuli Waukesha Electric
More informationSiemens Transformer Technology Seminar Insulation & Thermal Design
Customer Technical Meeting Pomona, CA May 24 25, 2016 Siemens Transformer Technology Seminar Insulation & Thermal Design Siemens AG Transformers siemens.com/answers Winding Selection Windings: Page 2 Winding
More informationA Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment
International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV
More informationLiquid-Filled Transformers
Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of
More informationTechnical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL
Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL ENGLISH SC_Trafo-TI-en-66 Version 6.6 Table of Contents SMA Solar Technology AG Table of
More information2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd
2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required
More information148 Electric Machines
148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional
More informationAGN 034 Alternator Reactance
Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 034 Alternator Reactance DEFINITION Reactance Periods Inherent to the design of an alternator are certain internal
More informationROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING
ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR 621 212 DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING EE1003 HIGH VOLTAGE ENGINEERING QUESTION BANK UNIT-I OVER VOLTAGES IN ELECTRICAL POWER SYSTEM
More informationANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER
ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER Jozef JURCIK 1, Miroslav GUTTEN 1, Daniel KORENCIAK 1 1 Department of Measurement and Applied Electrical Engineering, Faculty of Electrical
More informationAnalysis of Major Changes to Arrester Standards IEC STEVE BREWER
Analysis of Major Changes to Arrester Standards IEC 60099-4 STEVE BREWER Analysis of Major Changes to Arrester Standard IEC 60099-4 Steve Brewer- Senior Product Manager - HPS Arrester Business Unit Agenda
More informationTechnical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL
Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL ENGLISH SC_Trafo-TI-en-65 Version 6.5 Table of Contents SMA Solar Technology AG Table of
More informationDiscipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1
Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector
More informationCONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS
CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased
More informationCork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)
Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:
More informationEvaluating the Response of Surge Arresters
1 Jens Schoene Chandra Pallem Tom McDermott Reigh Walling Evaluating the Response of Surge Arresters to Temporary Overvoltages Panel Session of the IEEE Wind and Solar Collector Design Working Group 2014
More informationComparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137
ITEM Power factor (tanδ) & Capacitance Measurement Dry 1-minute Power frequency with partial discharge measurement CAN/CSA C88.1-96 IEEE C57.19.00/01 IEC 60137 Requirement Requirement Requirement Clause
More informationINTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER
Volume: 03 Issue: 07 July16 www.irjet.net p-issn: 2395-0072 INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER Sameer S. Patel 1, 1 Student, Electrical Dept, Rajasthan Institute
More informationANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER
POWER ENGINEERING AND ELECTRICAL ENGINEERING, VOL. 9, NO. 2, JUNE 2011 65 ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER Jozef JURCIK.1, Miroslav GUTTEN 1, Daniel KORENCIAK 1 1 Department
More informationThree-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method
Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is
More informationCOMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3
CONTENTS COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONSTRUCTION... 4 ~ 5 A. CORE AND FRAME... 4 B. COIL... 5 C. TEMPERATURE INDICATOR... 5 CHARACTERISTICS... 6 MANUFACTURING FACILITIES...
More informationTesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis
feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.
More informationOptimization of power transformers based on operative service conditions for improved performance
21, rue d Artois, F-75008 PARIS A2-207 CIGRE 2012 http : //www.cigre.org SUMMARY Optimization of power transformers based on operative service conditions for improved performance A.Prieto, M.Cuesto, P.Pacheco,
More informationCourse 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)
Name: Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC) 1. T F In three-phase four-wire delta systems rated 240/120 volts, sometimes
More informationLoss prophet. Predicting stray losses in power transformers and optimization of tank shielding using FEM
Loss prophet Predicting stray losses in power transformers and optimization of tank shielding using FEM JANUSZ DUC, BERTRAND POULIN, MIGUEL AGUIRRE, PEDRO GUTIERREZ Optimization of tank shielding is a
More informationComparison of Leakage Impedances of Two Single-phase Transformers
Aim Comparison of Leakage Impedances of Two Single-phase Transformers To understand the effect of core construction on leakage impedance in a single-phase transformers To understand factors affecting leakage
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK PO Box 25876 Safat 13119 Kuwait Contact: Mr Atul Madhukar Vaidya Tel: +965 1822600 Fax: +965 24761963 E-Mail: factory@ahleiasg.com Website:
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More information3-phase short-circuit current (Isc) at any point within a LV installation
3-phase short-circuit current (Isc) at any point within a LV installation In a 3-phase installation Isc at any point is given by: where U 20 = phase-to-phase voltage of the open circuited secondary windings
More informationTougher than any challenge. Transformers for highcurrent. industrial applications. siemens.com/transformers
Tougher than any challenge Transformers for highcurrent and large drive industrial applications siemens.com/transformers Powering industry Water-cooled LV-side high-current U-tube bushings Metallurgical
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationPOWER TRANSFORMERS CATALOGUE
COMPANY INFORMATION ARTRANS S.A. started off as a small factory in April 2, 1982 located in Mendoza, Argentina. Now, three decades later it is a globally recognized manufacturer of distribution, transmission,
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More information