Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers
|
|
- Liliana Gregory
- 5 years ago
- Views:
Transcription
1 Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers
2 Introduction Tap changer at active part Example of 3-phase tapchanger Page 2
3 Winding Configurations Primary > High voltage, many turns Secondary > Heavy current, more copper
4 Winding Configurations Tap Changers and Tap Windings: DETC or OLTC? OLTC vs. external Regulator? Separate or integral tap windings? Page 4
5 Reactance-Type on-load Tap changer (LV) Page 5
6 Resistance-type OLTC (HV or LV) Page 6
7 Function of the Preventive Auto-transformer Enables the tap changer to move from one position to an adjacent position Without breaking the tap connection Without causing a winding short circuit. Provides an intermediate voltage step between the tap winding steps.
8 Components of the Preventive Auto The PA has 2 equal windings connected in series as an Auto The windings are inter-wound to reduce the impedance to load current. main transformer tap winding P4 P1 Core Selector switches PA I L The voltage drop due to load current is insignificant. Winding 2 Vacuum interrupter P3 By-pass switches Winding 1 P2 I L P
9 Non-bridging position P4 P1 I L /2 I L /2 Currents in the 2 windings are in opposing directions. P3 P2 The windings are inter-wound to reduce the impedance to a low level to avoid voltage drop across the PA. 1 No voltage is applied to the windings and there is no core flux.
10 Bridging position P4 I L /2+I C P1 I L /2-I C When bridging, voltage applied to 2 windings in series. Selected of selected tap voltages. This circulates a current (I C ) through both windings, tap winding section, and by-pass switches. P3 P2 Circulating current limited by PA s magnetizing impedance. If used standard transformer core, impedance would be very high and circulating current would be small (<1%). 6 It s necessary to reduce magnetizing impedance to allow reasonable circulating current,. This done by introducing airgaps in PA s core leg. The transformer now has the magnetizing characteristics of a gapped core reactor.
11 Loss Evaluation at Nominal Rating Three possibilities for loss evaluation 1. Bridging 2. Non-bridging 3. Average Recommend average of bridging and non-bridging position losses.
12 Components: Helical windings with CTC
13 Components: Disc windings with simple conductors
14 Components: Rectangular core and windings Core E Foil windings E with windings fitted Top yoke, clamps and tie rods fitted
15 Noise level Noise occurs whenever legs excited (on bridging position). Noise also produced during commutation; it sounds like a grunt lasting about 1 sec. Noise created by compression of gap material, - Can be reduced by making gap material very hard, -OR- -Some designs use very high compression forces & softer gap material. As gaps are magnetically compressed, leg blocks & yokes are subject to vibration. Anti-vibration mountings may be used to reduce vibration transmitted to the tank.
16 Types of regulation Reversing Regulation Similar to linear arrangement, Selector contact moves up or down. There is also a reversing switch which reverses the sense of regulating winding. Maximum tap position > Regulating winding is 100% in positive sense. Mid tap position > none of regulating winding is in circuit Minimum tap position > when 100% regulation is in negative sense Page 16
17 Autotransformer Line End Regulation HV Do autotransformers require flux remaining constant across all tap positions? MV Can position regulating winding at MV terminal, rather than at neutral. Disadvantage - regulating winding (& tap changer) directly exposed to transients (lightning strikes) from MV terminal Page kV and 230KV voltages require 3 x single-phase tap changers (high currents). Maybe also Metal Oxide Varistors (MOV s) across regulating winding (lightning surges)
18 Autotransformer with Neutral End regulation HV Better alternative - place cheaper 3-phase tap changer at neutral end. MV With graded insulation, neutral terminal & OLTC have lower insulation levels. Disadvantage - number of turns in both MV and HV circuits changes simultaneously. Without one winding acting as a constant voltage, the transformer becomes a variable flux transformer. If tertiary winding is used, its output voltage will vary, unless a booster is fitted to compensate. Page 18
19 Page 19
20 In-tank Tap changer Cut-away Showing Completed Tap changer Regulating Leads Connections Motor Drive Page 20
21 Tap changer Basics Mounting flange Elbow pipes for connection to conservator Diverter Housing Connections for transformer leads Selector The main components are the selector, diverter, drive mechanism and surge relay. The selector is in the main bulk oil. The diverter, which makes and breaks the current path, is in a separate oil compartment with it s own conservator & surge relay. The drive mechanism houses the drive motor which moves tap switches, and controls and indications. Page 21
22 Tap changer Motor Drive Unit Page HAND CRANK 2. INSPECTION LAMP 3. SHAFT FOR HAND CRANK 4. OPERATION COUNTER 5. POSITION COUNTER 6. DRAG HANDS 7. TAP CHANGE INDICATOR 8. DOOR HAND FOR LAMP 9. MOTOR PROTECTION DEVICE 10. RAISE/LOWER CONTROL SWITCH 11.HEATING PANEL 12. SWING-FRAME LATCH 13. DRAWINGS 14.COVER PLATE 15. PADLOCKING FACILITY 16.QUICK RELEASE SCREWS
23 Tap changer Separate Oil Systems of OLTC and expansion tank Separation wall Siliga gel breather OLTC expansion tank Protective relay Diverter switch oil Silica gel breather Main Buchholz relay Main transformer oil Page 23
24 Tap changer Protective Relay OLTC Surge Relay A type RS 2001 surge relay is fitted in the pipe work between the divertor compartment and the OLTC conservator. The surge relay generates a trip signal on a fault which is latched. A red flag can be seen in the relay window when it has tripped. Testing Remove the terminal box lid to reveal the test and reset buttons. Pressing the test button latches the switch in the trip position. It must be reset. TERMINAL BOX INSPECTION WINDOW Page 24
25 Examples for Tap Changers OLTC V III 200 D (MR) OLTC M III 350/M III 500 (MR) OLTC RM III 600 (MR) Page 25
26 Siemens US s Contact James McIver Principal Application Engineer E T TR US 6860 Bermuda Road, STE 100 Las Vegas NV USA Mobile: (702) james.mciver@siemens.com siemens.com/transformers Page 26
Transformer Technology Seminar Winding Selection
Pomona, CA May 24 25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Windings: Page 2 Example GSU 274/464MVA H0 H1 H2 H3 U U I I H L H L N = N N = N L H H L HV: 405kV ±8x1.25%
More informationRegional Technical Seminar
Regional Technical Seminar LOAD TAP CHANGERS (LTCS) DESIGN, OPERATION, AND MAINTENANCE CONSIDERATIONS SPX Dallas Facility Damon Jones General Manager SPX Transformer Solutions Components Group Cell: 214-422-8979
More informationTertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.
Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing
More informationON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA
ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria 2017-2 EA 710. /1 EN Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current
More informationON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA
ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria 2017 EA 782/15 ENG Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current (Iu),
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationShunt Reactors. Global Top Energy, Machinery & Plant Solution Provider
Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical
More informationON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA
ON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria EA 675/15 ENG Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current (Iu),
More informationOn-Load Tap Changer Type M
On-Load Tap Changer Type M OLTC type model M III 500 Y, U m = 123 Kv, 500A, ± 9 steps The type M On Load tap changers are used to vary the ratio of oil-immersed transformers under load.in general they
More informationTECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER
TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER HM0.154.1901 SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. General 1. General 3 2. Technical specifications 4 3. Type explanation 5 4. Terms and definitions
More informationThe measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms
Why Measure Winding Resistance? The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Partial or dead short-circuited
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationDATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO
PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %
More informationTransformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications
The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of
More informationMODERN POWER TRANSFORMER PRACTICE BIBLIOGRAPHY
354 BIBLIOGRAPHY MODERN POWER TRANSFORMER PRACTICE Bolton, D. J., Electrical Engineering Economics, Chapman and Hall, London, 2nd edn (1936) Brownsey, C. M., 'The Problem of Noise with Particular Reference
More informationRegional Technical Seminar TAP CHANGERS
Regional Technical Seminar TAP CHANGERS SPX Transformer Solutions, Inc. September 4, 2018 De-Energized and Load Tap Changers Jason Varnell Lead Design Engineer jason.varnell@spx.com SPX Transformer Solutions,
More informationTECHNICAL SPECIFICATION FOR POWER TRANSFORMER
TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL
More informationsave energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers
save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationTechnical guide. Type VRLTC load tap changer
Technical guide Type VRLTC load tap changer Table of contents General information... 2 Electrical characteristics... 3 Type tests... 4 Switching sequence... 5 Tank characteristics... 7 Terminal board...
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules
More informationPhase Shifter Application Workshop. Siemens Energy, Inc.
Phase Shifter Application Workshop Siemens Energy, Inc. PJM Power Pool, March, 2015 siemens.com/energy Phase Shifter Application Workshop Phase Shifting Transformers Principles, Design Aspects and Operation
More informationPhase Shifting Transformers. Presented by
Phase Shifting Transformers Presented by Phase Shifting Transformers (PST s) (a.k.a. Phase Angle Regulators) VS φ S P V V S = X L L X L sin( φ φ ) L S VL φ L PST s are power flow control devices between
More informationPRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer
More informationTECHNICAL DATA TYPE SHZV VACUUM ON-LOAD TAP CHANGER FOR OIL-IMMERSED TRANSFORMER
TECHNICL DT TYPE SHZV VCUUM N-LD TP CHNGER FR IL-IMMERSED TRNSFRMER HM0.154.3901-02.06/2018 SHZV(cylinder tap selector) SHZV(cage tap selector) SHNGHI HUMING PWER EQUIPMENT C., LTD. General 1. General
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationTAP CHANGER SELECTING MANUAL TECHNICAL DATA
TECHNICAL DATA HM0.154.000 SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. General 1. General requirement for tap changer selecting 2 2. Attention for tap changer mounting 10 3. Tap changer accessories 10 4.
More informationParticulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX
Particulate Control O&M Training APC/PCUG Conference July 12-16, 2009 The Woodlands, TX WPCA Particulate Training Seminar July 11, 2009 ESP Power Supply Choices Slide No 1 Precipitator Power Supplies Conventional
More informationTransformer Technology Seminar What to consider at Design Reviews
Pomona CA, May 24-25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Why to perform Design Review Meetings? To ensure both parties having the same understanding of the
More information1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide
1ZSC000562-AAJ en, Rev. 1 Vacuum on-load tap-changers, type VUBB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationPower transformers for Network, Rectifiers, Furnace
E N G L I S H OTN, OTR, OTF Transformers Power transformers for Network, Rectifiers, Furnace TTR TTO OTN, OTR, OTF reactors TTH OTN, OTR, OTF Transformers Technology Design Our designers experience combined
More informationBasic Principles and Operation of Transformer
Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core
More informationTechnical guide. Type VRLTC load tap changer
Technical guide Type VRLTC load tap changer Table of contents 2 General information 4 Switching sequences 6 Tank characteristics 6 Terminal board 7 Tap selector 7 Stationary contacts 7 Reversing switch
More informationTesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis
feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.
More informationTRANSFORMER TECHNOLOGY GPT
Core-Form TRANSFORMER TECHNOLOGY GlobalPT Corporation performs research and engineering developments and co-ordination of works of technical partners in the field of technological progress and commercial
More informationProlific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2
Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationLoad Tap Changers for Power Transformers
Load Tap Changers for Power Transformers Dr. Dieter Dohnal / Maschinenfabrik Reinhausen GmbH Dipl. Ing. Bernhard Kurth / Reinhausen Manufacturing Inc. Load Tap Changers for Power Transformers Content Basic
More informationReport on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)
Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/F.06/2015-16/Mgr(Bawana)/353 dated
More informationChapter 7 Conclusion 7.1 General
Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due
More informationPower Transformers Basics
Power Transformers Basics Transformer Basic Objective Introduce Basic Transformer Theory as it Relates to Diagnostics Provide a Better Understanding of the Diagnostic Test Environment Identify Important
More informationCHAPTER 4. Distribution Transformers
CHAPTER 4 Distribution Transformers Introduction A transformer is an electrical device that transfers energy from one circuit to another purely by magnetic coupling. Relative motion of the parts of the
More informationOIL-IMMERSED ARC-SUPPRESSION COILS
ISO 9001:2000 99-320 Żychlin, ul. Narutowicza 70 ISO 14001:2004 PN-N-18001:2004 www.ftz.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31 zarzad@ftz.pl Sales and Marketing Department
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationOn-load tap-changer VACUTAP VRC and VRE
www.reinhausen.com On-load tap-changer VACUTAP VRC and VRE Technical Data TD 246/03 Table of Contents Table of Contents 1 General / Technical data... 4 1.1 On-load tap-changer designations... 4 1.2 Summary
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationCONTENTS. 1. Introduction Generating Stations 9 40
CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific
More informationSiemens Transformer Technology Seminar Insulation & Thermal Design
Customer Technical Meeting Pomona, CA May 24 25, 2016 Siemens Transformer Technology Seminar Insulation & Thermal Design Siemens AG Transformers siemens.com/answers Winding Selection Windings: Page 2 Winding
More informationDynamic Testing for On Load Tap Changer Condition Assessment
4th International Colloquium "Transformer Research and Asset Management TUTORIAL Dynamic Testing for On Load Tap Changer Condition Assessment Dr. Raka Levi, AMforum Abstract The tutorial covers different
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,
More informationUnderstanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques
Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion
More informationProblems connected with Commissioning of Power Transformers
Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.
More informationIndustrial Applications
Industrial Applications Transformers for Industrial Applications Tamini has always produced industrial transformers of high quality and reliability, designed to satisfy the most diverse and complex technical
More informationOn-load tap-changers, type UC and VUC Technical guide
1ZSE 5492-105 en, Rev. 7 On-load tap-changers, type UC and VUC Technical guide The manufacturer Hereby declares that The products Manufacturer s declaration ABB AB Components SE-771 80 LUDVIKA Sweden comply
More informationHands-On Transformer Testing and Maintenance
Hands-On Course Description This Hands-On course will teach you how to prioritize your transformer maintenance strategy, stretch your maintenance budget and at the same time maximize the life and condition
More informationTECHNICAL DATA TYPE CV & SV OIL-IMMERSED ON-LOAD TAP CHANGER
TECHNICAL DATA TYPE CV & SV OIL-IMMERSED ON-LOAD TAP CHANGER SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. CONTENT 1. General 2 2. Technical specifications 2 3. Model explanation 4 4. Terms and definitions
More informationSPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION February 2017 SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER
More informationTransformers. 6.1 Principles of operation. Professor D.J. Allan Merlindesign. Chapter 6
Chapter 6 Transformers Professor D.J. Allan Merlindesign 6.1 Principles of operation In simple form, a transformer consists of two windings connected by a magnetic core. One winding is connected to a power
More information1ZSE en, Rev. 9. On-load tap-changers, type UC and VUC Technical guide
1ZSE 5492-105 en, Rev. 9 On-load tap-changers, type UC and VUC Technical guide The manufacturer Hereby declares that The products Manufacturer s declaration ABB AB Components SE-771 80 LUDVIKA Sweden comply
More information3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]
Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant
More informationTraining Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.
Training Title POWER SYSTEM GENERATION & DISTRIBUTION Training Duration 5 days Training Venue and Dates Power System Generation & Distribution 5 08-12 December, 2019 $4,000 Dubai, UAE Trainings will be
More informationImpact of Distributed Generation on Network Voltage Levels
EEE8052 Distributed Generation Taster Material Impact of Distributed Generation on Network Voltage Levels Steady-state rise in network voltage levels Existing practice is to control distribution voltage
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationTransformer Protection Principles
Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major
More informationPUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT
PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT SPECIFICATION SS-25 / 14 POWER TRANSFORMERS 150/15.75-21kV, 40/50 MVA WITH AUTOMATIC LOAD-RATIO CONTROL CONNECTION
More informationTap Changer Condition Assessment Using Dynamic Resistance Measurement
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Tap
More informationTab 8 Surge Arresters
s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationHOW TO SAFE GUARD THE TRANSFORMER..???
CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various
More informationECE 3600 Transformers b
Transformer basics and ratings A Transformer is two coils of wire that are magnetically coupled. Transformers b Transformers are only useful for AC, which is one of the big reasons electrical power is
More informationGE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class
GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial
More informationUnit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21
Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive
More informationPreface...x Chapter 1 Electrical Fundamentals
Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5
More informationPower Measurements and Basic Electrical Diagnostic Tests
Power Measurements and Basic Electrical Diagnostic Tests Instrument Basics Burden VA Sources V and I Meters V and I KVL and KCL Kelvin Connection KVL and KCL Kelvin Connection 4-Wire Technique Exclude
More informationIN ELECTRICAL ENGINEERING - I C M E T CRAIOVA
Taking into account that power transformer is the major item of equipment in power systems, its correct operation is vital to system operation. It is well known that transformer failures are sometimes
More information1ZSC AAW en, Rev. 2. On-load tap-changers, type UC Technical guide
1ZSC000562-AAW en, Rev. 2 On-load tap-changers, type UC Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationRegional Technical Seminar SHORT CIRCUIT FORCES
Regional Technical Seminar SHORT CIRCUIT FORCES Short Circuit Forces Wallace Exum Electrical Design Engineer wallace.exum@spx.com Agenda 1. What is Short Circuit 2. Types of Faults 3. How to Calculate
More informationSOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)
E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION
More informationnical catalogue Tech
Technical catalogue About Etra 33 has been acting as transformer manufacturer over more than 75 years. Specializing in the manufacturing of power transformers rating up to 500 MVA and 420 kv the company
More informationGroup F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A
Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating
More informationBenefits of SFRA - Case Studies
6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO
More informationINTERNATIONAL STANDARD
NTERNATONAL STANDARD EC 60214-1 Edition 2.0 2014-05 colour inside Tap-changers Part 1: Performance requirements and test methods EC 60214-1:2014-05(en) THS PUBLCATON S COPYRGHT PROTECTED Copyright 2014
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationPRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY
Sheet 1 of 12 TEST DATE CUSTOMER SERIAL No OLTC ACKNOWLEDGE SETUP AUTOMATIC or FEEDBACK CONTROL PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY Issue Date Level I 21/05/1998 Initial issue. Summary
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More information148 Electric Machines
148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional
More informationTECHNICAL DESCRIPTION ND-387. THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1
HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. December 2017 TECHNICAL DESCRIPTION ND-387 THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1 I. SCOPE The scope of the present description
More informationSecondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.
Surge Arresters Secondary Arresters and Protective Gaps Electrical Apparatus 235-10 GENERAL INFORMATION The necessity of providing surge arrester protection on low-voltage circuits is fundamentally the
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationReyrolle Protection Devices. 7PG11-18 Alpha Electromechanical Relays. Siemens. Answers for energy.
Reyrolle Protection Devices 7PG11-18 Alpha Electromechanical Relays Answers for energy. Siemens Alpha Technical Manual Contents Contents Technical Manual Chapters 1. Introduction to Electromechanical
More informationEPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY
EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY EPS AUSTRALIA SERVICES COMPANY OVERVIEW EPS is a recognised company specialising in Electrical, Instrumentation, Structural, Mechanical and
More informationElectrical Design Process
Electrical Design Process Jason Varnell Lead Design Engineer Jason.Varnell@spx.com SPX Transformer Solutions, Inc. September 26, 2018 Agenda 1. Bid Design Process Parameters Affecting Bid Design 2. Final
More informationRegional Technical Seminar
Regional Technical Seminar TRANSFORMER 101 Transformer 101 Dharam Vir Vice President of Engineering Dharam.Vir@spx.com Agenda 1.Review transformers: How they work (textbook vs reality) 2.How do we build
More informationPRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY
Sheet 1 of 15 TEST DATE: CUSTOMER: SERIAL NO: OLTC ACKNOWLEDGE SETUP AUTOMATIC or FEEDBACK CONTROL PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY Issue Date Level A 06/01/1997 Initial issue. Summary
More informationPOWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS
POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A
More informationSDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01
SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice
More informationPOWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
POWER TRANSFORMER Failure Analysis & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Electricity is high-grade energy. Working
More informationINTERPLANT STANDARD - STEEL INDUSTRY CODE OF PRACTICE FOR TESTING & COMMISSIONING OF TRANSFORMERS AND RELATED SWITCHGEARS
INTERPLANT STANDARD - STEEL INDUSTRY IPSS CODE OF PRACTICE FOR TESTING & COMMISSIONING OF TRANSFORMERS AND RELATED SWITCHGEARS Corresponding IS does not exist IPSS:1-04-035-08 0. FOREWORD 0.1 This Inter
More information