Power Measurements and Basic Electrical Diagnostic Tests
|
|
- Paulina Willis
- 6 years ago
- Views:
Transcription
1 Power Measurements and Basic Electrical Diagnostic Tests
2 Instrument Basics Burden VA Sources V and I Meters V and I KVL and KCL Kelvin Connection
3 KVL and KCL
4 Kelvin Connection 4-Wire Technique Exclude the resistance from the measurement circuit leads and any contact resistance at the connection points of these leads Voltage sense leads (P3 and P4) "inside" the current leads (P1 and P2)
5 Test Properties 1. Overall PF/CAP 2. Bushing PF/CAP (C1, C2, EC) 3. Exciting Current (Phase A, B, C) 4. Surge Arresters 5. Insulating Fluids (Main Tank, LTC) 6. Turns Ratio (H-X, H-Y, H-T, X-Y, X-T) 7. Leakage Reactance (3 Equiv, Per ) 8. Insulation Resistance 9. DC Winding Resistance (H, X, Y)
6 Topics of Discussion 1. Diagnostic Test Methods 2. Transformer Test Protocol 3. Transformer Test Plan 4. Analyzing the Results
7 Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer Turns Ratio Leakage Reactance DC Winding Resistance SFRA (Sweep Frequency Response Analysis) FRAnalyzer DFR (Dielectric Frequency Response) DIRANA Thermal Imaging FLIR Insulation Resistance MEGGER Partial Discharge MPD PDL DAYCORE
8 Transformer Tests Dielectric Thermal Mechanical DGA DGA SFRA Oil Screen Oil Screen Leakage Reactance PF/TD CAP IR PF/TD CAP Exciting Ima DC Winding RES Exciting Ima Turns Ratio Tests DC Winding RES DFR Insulation Resistance Partial Discharge
9 Diagnostic Testing - FOCUS 1. Power Factor / Capacitance 2. Exciting Current 3. Transformer Turns Ratio 4. Leakage Reactance 5. Insulation Resistance 6. DC Winding Resistance 1. Overall PF/CAP 2. Bushing PF/CAP (C1, C2, EC) 3. Exciting Current (Phase A, B, C) 4. Surge Arresters 5. Insulating Fluids (Main Tank, LTC) 6. Turns Ratio (H-X, H-Y, H-T, X-Y, X-T) 7. Leakage Reactance (3 Equiv, Per ) 8. Insulation Resistance 9. DC Winding Resistance (H, X, Y)
10 Power Factor Tests 1. Overall PF/CAP 2. Bushing PF/CAP (C1, C2, EC) 3. Surge Arresters 4. Insulating Fluids (Main Tank, LTC) Dependent on Transformer Type 2-Winding XFMR 3-Winding XFMR Autotransformers Will cause variances in test plans from protocol.
11 Overall PF/CAP Type Main Insulation Bushings Surge Arresters 2-Winding CH, CL, CHL Up to 8 C1, C2, EC 3-Winding CH, CL, CT CHL, CHT, CLT Up to 12 C1, C2, EC Auto w/tert CAuto, CT, CAutoT Up to 10 C1, C2, EC Auto wo/tert CAuto Up to 7 C1, C2, EC Up to 6 Stacks Up to 9 Stacks Up to 9 Stacks Up to 6 Stacks Insulation Fluids Main Tank Tap Changer Main Tank Tap Changer Main Tank Tap Changer Main Tank Tap Changer
12 Power Factor / Capacitance Measurement I TOT I R I C Insulation can be modeled through: Capacitance (Physical Geometry) Resistance (Losses) V R C I R Losses can be categorized as: Conductive Polarization (60 Hz Range) I TOT I C Power Factor 0.00% - 100% cos φ = I R /I TOT x 100% Power Factor measures bulk degradation: Moisture Aging Contamination V
13 Insulation Losses Loss Types: Conductive Losses: Electrons and Ions Polarization Losses: Electrons, Molecular, Interfacial Polarization Partial Discharge PD: Locally Discharge Loss Dependences: Aging Moisture Contamination Temperature Insulation Geometry Electrical Field Strength (PD)
14 Power Factor / Capacitance Applied Test at Rated Frequency (60 Hz) Measurements Normalized to 20 C. Test voltages for a typical field test set range from below 100 V to as high as 12 kv. (IEEE Std. 62) 10 kv is Normally Applied a) 2000 VA b) 80,000 pf Data should be analyzed by: a) Limits b) Trending c) Nameplate
15 Power Factor vs. Capacitance Power Factor Aging Moisture Contamination Capacitance Change in Dielectric Constant (Aging and Contamination) Air(Vacuum) : 1.0 Oil: 2.2 Porcelain: Physical and Mechanical Changes (Movement).
16 2-Winding XFMR
17 3-Winding XFMR
18 Autotransformers WITH & WITHOUT Tertiary WITH WITHOUT
19 Two-Winding Transformer Model Windings are short-circuited to remove unwanted inductance CH, CL and CHL insulation systems CH includes H-C1 CL includes X-C1
20 GST Measurement Both CH and CHL are measured together
21 GST GUARD Measurement - CH CH is isolated by use of the GSTg measurement circuit
22 UST Measurement - CHL CHL is isolated by use of the UST measurement circuit
23 Overall Test Data 2-WINDING TRANSFORMER OVERALL Measurement Type kv Test # Energize Ground Guard UST Test kv I ma Cap pf Watt Loss PF [%] Measured PF [%] Corrected Correction Factor ICH+ICHL H (prim) L (sec) GST Mode Insulation Condition ICH H (prim) L (sec) GST ga PASS ICHL H (prim) L (sec) UST A PASS Calculated ICHL PASS ICH-C1 = ICH minus H (prim) bushings; HV C1 ONLY PASS ICL+ICHL L (sec) H (prim) GST ICL L (sec) H (prim) GST ga PASS ICHL L (sec) H (prim) UST A PASS Calculated ICHL PASS ICL-C1 = ICL minus L (sec) bushings; LV C1 ONLY PASS
24 Transformer Test Results
25 Transformer Test Results Notice severe exponential increase!
26 Bushing Taps
27 Field Tests The following test are electrical field tests performed with portable test equipment to determine bushing suitability for service. Condenser Bushing with Potential Tap Condensers Bushing with Test Tap Non Condenser Visual Inspection Visual Inspection Visual Inspection C1 Power Factor (60 Hz) C1 Power Factor (60 Hz) Energize Collar Test C1 Capacitance (60 Hz) C1 Capacitance (60 Hz) Infrared Test C2 Power Factor (2.5 kv) C2 Capacitance (2.5 kv) Advance Power Factor Measurements Power Factor Tip Up Test C2 Power Factor (0.5 kv) C2 Capacitance (0.5kV) Advance Power Factor Measurements Power Factor Tip Up Test Infrared Test Infrared Test
28 Power Factor / Capacitance - BUSHING C1 Bushing H1-C1 UST All Terminals Remain Shorted
29 Bushing C1 Test Data Bushings - NAMEPLATE Bushing Manufact. Model/ Serial Catalog Drawing BIL kv A C1 C1 Year Type Number Number Number kv Rating Rating PF[%] Cap (pf) H1 ABB O+C H2 ABB O+C H3 ABB O+C H0 C2 PF[%] C2 Cap (pf) X1 ABB O+C X2 ABB O+C X3 ABB O+C X0 ABB O+C Bushings - C1 Measurement Type Ref@10 kv Bushing Energize Ground Guard UST Test kv I ma Cap pf Watt PF [%] PF [%] Correction Mode Insulation Loss Measured Corrected Factor Condition H1 Conductor - - Tap UST A PASS H2 Conductor - - Tap UST A PASS H3 Conductor - - Tap UST A PASS H0 Conductor - - Tap n/a n/a n/a 1.00 UST A X1 Conductor - - Tap UST A PASS X2 Conductor - - Tap UST A PASS X3 Conductor - - Tap UST A PASS X0 Conductor - - Tap UST A PASS
30 Bushing Standard Limits Power Factory limits at power frequency and corrected to 20 C Insulation %PF IEEE (C ) %DF (IEC 60137) Typical %PF New values Oil Impregnated Paper <0.5% <0.7% 0.2%-0.4% Resin Impregnated Paper <0.85% <0.7% 0.3% - 0.4% Resin Bonded Paper <2.0% <1.5% 0.5%-0.6%
31 Power Factor / Capacitance - BUSHING C2 H1-C2 GST ga
32 Bushing C2 Test Data Bushings - C2 Measurement Type Ref@10 kv Bushing Energize Ground Guard UST Test kv I ma Cap pf Watt Loss PF [%] PF [%] Measured Corrected Correction Factor Mode Insulation Condition H1 Tap - Conductor GST ga PASS H2 Tap - Conductor GST ga PASS H3 Tap - Conductor GST ga PASS H0 Tap - Conductor - n/a n/a n/a 1.00 GST ga X1 Tap - Conductor GST ga PASS X2 Tap - Conductor GST ga PASS X3 Tap - Conductor GST ga PASS X0 Tap - Conductor GST ga PASS
33 Power Factor / Capacitance - BUSHING EC H1-EC GST or UST UST and GUARD circuits can be used for external contamination investigation and/or isolation
34 Energized Hot Collar Test Data Bushings - Energized Collar Measurement Type Ref@10 kv Bushing Energize Ground Guard UST Test kv I ma Watt Loss Mode Insulation Condition H1 Collar GST PASS H2 Collar GST PASS H3 Collar GST PASS H0 Collar n/a GST X1 Collar GST PASS X2 Collar GST PASS X3 Collar GST PASS X0 Collar GST PASS
35 Transformer Exciting Current Test Vs 1. Apply Voltage Vs on on primary phase, secondary winding left floating 2. Measure currurent I ex 3. The current required to force ``transformer action (the use of one winding to induce a voltage in the second winding).
36 Exciting Current Test Considerations: The exciting current test is an open-circuit test; the secondary side bushings should not be shorted together. If the secondary winding is a Wye-configuration, the Neutral must be grounded. Apply AC Voltage across each winding phase, measuring the current and watts. On a HV Delta-Configured winding, the third terminal must be grounded, or the results can no longer be characterized as a single phase measurement. Voltage sensitive test, must apply the same voltage to each phase and as that used for previous results in order to compare.
37 Analyzing Results Unexpected results can be observed from the following: 1. Full or partially short circuited turns 2. Open Turns 3. Core Construction Problems 4. Saturated Core
38 Exciting Current Test Procedure Routine Test Perform test on each phase with the DETC on its as found position. DETC should not be moved unless specified by company or manufacturer Ideally test should be performed on all phases at each LTC positions
39 Analyzing Results Confirm Expected Phase Pattern Confirm Expected LTC Pattern (For load tap changing transformers) Compare to Previous Results Make sure same voltage is applied Magnitudes do not have to match Any change should be uniform across phases (similar percent change).
40 Analyzing Results Confirming the Expected Phase Pattern: 1. High Low High (HLH) Pattern Expected for a 3-legged core type transformer. Expected for a 5-legged core (or shell) type transformer with a Delta connected secondary winding. 2. Low High Low (LHL) Pattern Will be obtained on a 3-legged core type transformer if the traditional test protocals are not followed. Neutral on high side Wye-configured transformer is inaccessible Forget to ground 3 rd terminal on a Delta-connected transformer Expected for a 4-legged core type transformer. 3. All 3 Similar Pattern Expected for a 5-legged core (or shell) type transformer with a non-delta secondary winding.
41 Exciting Current Test Transformer: HV Delta LV - Wye H2 X2 X1 X0 H1 H3 X3 Test HV Lead LV Lead Ground Float Mode Measure Result 1 H1 H3 H2, X0 X1,X2,X3 UST H1-H ma 2 H2 H1 H3, X0 X1,X2,X3 UST H2-H ma 3 H3 H2 H1, X0 X1,X2,X3 UST H3-H ma
42 Exciting Current Test Transformer: HV Wye LV - Delta H2 X2 H1 H0 H3 X1 X3 Test HV Lead LV Lead Ground Float Mode Measure Result 1 H1 H0 NONE X1,X2,X3 UST H1-H ma 2 H2 H0 NONE X1,X2,X3 UST H2-H ma 3 H3 H0 NONE X1,X2,X3 UST H3-H ma
43 Exciting Current Test Transformer: HV Wye LV - Delta Inaccessible Neutral Bushing (H0) X2 H2 H1 H3 X1 X3 Test HV Lead LV Lead Ground Float Mode Measure Result 1 H1 H2 NONE H0,X1,X2,X3 UST H1-H ma 2 H2 H3 NONE H0,X1,X2,X3 UST H2-H ma 3 H3 H1 NONE H0,X1,X2,X3 UST H3-H ma
44 Exciting Current Exciting Current LTC Pattern Reactor Type Exciting Current A B C L 15L 14L 13L 12L 11L 10L 9L 8L 7L 6L 5L 4L 3L 2L 1L N 1R 2R 3R 4R 5R 6R 7R 8R 9R 10R 11R 12R 13R 14R 15R 16R LTC Position OMICRON
45 Demag. Routine Before and After
46 Stacking Arresters Arresters can be found in the following stack options: Pos.4 Pos.5 Pos.4 Pos.3 Pos.3 Pos.3 Pos. 2 Pos.2 Pos.2 Pos.2 Pos. 1 Pos. 1 Pos. 1 Pos. 1 Single Stack Two Stack Three Stack Four Stack Five Stack
47 Dielectric Loss Measurement The Loss measurement can provide valuable information to help identify physical changes, deterioration, moisture ingress, and most importantly help determine suitability for service. Each arrester in the stack should be measured independently Only Watts and Current are measured; Power Factor is not calculated due to the small magnitude of the current Test Arrester Pos 2 10 kv UST Test Equipment
48 Dielectric Loss Measurement The Loss measurement can provide valuable information to help identify physical changes, deterioration, moisture ingress, and most importantly help determine suitability for service. Each arrester in the stack should be measured independently Only Watts and Current are measured, Power Factor is not calculated due to the small magnitude of the current Test Arrester Pos 1 10 kv GST-gA Test Equipment
49 Routine Test The following test should be performed on a routine basis and compared to previous results Routine Tests Visual Inspection Dielectric Loss Measurement Infrared Analysis
50 Analyzing Results The results should be analyzed by the following methods: 1. Previous Test Result 2. Similar Specimens Analyzing Dielectric Loss Results The result should compare to similar arresters. Make sure you are comparing A phase position 1 to B Phase position 1 to C phase position 1, and so on. Typically watts loss measurement are very low under 0.1 watts. Current measurement should compare very close to similar units due to same design and construction
51 Analyzing Results Abnormal Dielectric Loss Measurement (Watts) Silicon Carbide Arrester Metal Oxide Arrester Higher than Normal Losses Contamination located inside or externally Corroded Gaps Crack porcelain housing Higher than Normal Losses Contamination located inside or externally Crack porcelain housing Lower than Normal Losses Broken Shunt Resistor Poor Contact among elements Lower than Normal Losses Discontinuities in internal configuration
52 Example Arrester Test Results
53 IR Surge Arrester Heating Due to Internal Leakage Path 15 C Rise Differential
54 Surge Arrester - ZOOM
55 Leakage Reactance Leakage flux is flux that does not link all the turns of the winding Leakage flux creates reactive magnetic energy that behaves like an inductor in series in the primary and secondary circuits Winding movement changes the reluctance of the leakage flux path, resulting in a change in the expected leakage reactance measurement.
56 Leakage Reactance
57 Leakage Reactance Short circuit LV winding or winding pairs Inject % of rated current 60 Hz (Line-to-Line) A variable 280 VAC source is recommended Measure Series Current and Terminal Voltage RESULT - Z, R, and X There are two ways to perform the measurement 1. 3 Phase Equivalent 2. Per Phase
58 Leakage Reactance 3 Phase Equivalent Short LV terminals; do not include neutral Compare to nameplate +/- 3% Inject Short Measure H1-H3 X1, X2, X3 ZA, RA, XA, LA H2-H1 X1, X2, X3 ZB, RB, XB, LB H3-H2 X1, X2, X3 ZC, RC, XC, LC 1 UNIT 3 UNIT
59 Leakage Reactance Per Phase Short corresponding LV terminals Compare deviation from average Inject Short Measure H1-H3 X1-X0, X1-X3 ZA, RA, XA, LA H2-H1 X2-X0, X2-X1 ZB, RB, XB, LB H3-H2 X3-X0, X3-X2 ZC, RC, XC, LC
60 Leakage Reactance NAMEPLATE
61 Leakage Reactance Example Nameplate: 6.85% 69 kv 12.5 MVA Phase V I Z R X L H1-H H2-H H3-H
62 Insulation Resistance Insulation Check (Main Insulation, Bushings, Core Grounds) Insulation resistance measurements on transformers are normally performed at dc voltages up to 5000 VDC 1. Capacitive Charging Current 2. Absorption Current 3. Leakage Current Temperature Sensitive (Inverse) Polarization Index PI = R(10)min/R(1)min PI for Transformer Insulation < 1.0 => FAIL >1.0 => Acceptable
63 Transformer Turns Ratio Primary winding Np turns + Secondary winding Ns turns Basic Ideal Transformer Circuit Ip Is Np:Ns + Vp Vs L Turn Ratio (N) Equation Np N = Ns Vs = Vp = Vs Np Ns Is = Ip Vp
64 Turns Ratio Test Field Turns Ratio Test obejective Example: Transformer Nameplate Tap Voltage Measure transformer turn ratio of each phase and tap position (Matching Nameplate) HV Winding Measure Phase Angle of the voltage from the high voltage winding and low voltage winding Polarity check is performed as well LV Winding
65 Turns Ratio Test How is it performed? H2 X2 Three Phase Transformer X1 X0 HV 34500GRDY/19920 Volts LV Volts H1 H3 X3 A Phase Test Input Measure Phase Ratio 1 H1-H3 X1-X0 A 2 H2-H1 X2-X0 B 3 H3-H2 X3-X0 C Calculated Ratio = 1.51 Measurement Ratio % Dev Angle % 0.05
66 Turns Ratio Test Procedure Routine Test Should perform turns ratio test on as found DETC positions Unless specified by company or manufacturer Ideally turns ratio test on all LTC positions Place DETC in as found position
67 Analyzing Results The turn ratio measurement results should be within 0.5% of nameplate markings according to IEEE C Results should also compare very closely among phases Any winding open circuits, short circuits and turn to turn shorts will show up change this measurement The phase angle measured between the high voltage and low voltage winding is generally very low. Damage or deterioration in the core will increase the phase angle
68 Turn Ratio OMICRON
69 Turn Ratio OMICRON
70 Turn Ratio OMICRON
71 16R 15R 14R 13R 12R 11R 10R 9R 8R 7R 6R 5R 4R 3R 2R 1R N 1L 2L 3L 4L 5L 6L 7L 8L 9L 10L 11L 12L 13L 14L 15L 16L Exciting Current [ma] Turn Ratio 25.0 Low-Voltage Exciting Current A B C Tap Changer Position OMICRON
72 Turns Ratio Test
73 Turns-Ratio H-X
74 Transformer Winding Resistance One Phase Transformer Equivalent Circuit R1 = Power Loss in HV winding L1= Leakage Inductance of HV Winding Rn = Iron Loss in Core Lm = Core Inductance R2 = Power Loss in LV winding L2= Leakage Inductance of LV Winding
75 Failure Modes A change greater than the criteria mentioned can be indicative of the following: 1. Shorted Circuited Turns 2. Open Turns 3. Defective DETC or LTC (contacts) 4. A Poor Connection Between Terminals Measured
76 Winding Resistance Principle of Winding Resistance Test 1. Inject DC Current from one terminal to the other terminal of a phase 2. Measure the voltage drop across the two terminals under test once core magnetic circuit has stabilized 3. As long as stable voltage DC source is used, winding inductance Xp is negligible. Vp = Ip * Rp Rp = Ip / Vp
77 Winding Resistance Very Important when Performing this test 1. Transformer high voltage and low voltage terminals need to be disconnected and isolated 2. Be aware and use saftey at all time. Make sure the winding is discharged after a test by grounding the terminal. 3. Never inject a DC current higher than 15% of the winding rated current 4. Temperature affects the test results and should be corrected to a common temperature of 75 C or 85 C 5. The temperature of insulated liquid has to be stabilized (top and bottom temperature should not deviate more than 5 C
78 Winding Resistance Test Example of how is it performed? H2 X2 H1 H0 Three Phase Transformer HV 230 Amps LV 350 Amps H3 X1 X3 Winding Temperature 35 C B Phase H2 X2 Factory Result (75 C) DC + + V Ω Measurement H0 Core is neglected X1 Result Corr. %Dev
79 Winding Resistance Temperature Correction Resistance changes with temperature Results have to be corrected to either 75 C or 85 C to be compare Factory or Previous Field Test Formula Cf Rcor = Rm * Tc * Cf * Tw Rcor = Resistance Corrected Rm = Resistance measured Cf = Correction for material [Copper = 234.5, Aluminum 225] Tc = Corrected Temperature Tw = Winding Temperature at Test Previous Example Rcor = * * * 35 Rcor = 0.170
80 Winding ResistanceTest Procedure 1. By performing DC Winding Resistance test, this will magnetize your core. A magnetized core will affect your Exciting Current and SFRA Test Results. 2. Recommended to perform DC Winding Resistance last. 3. Imporant to let the measurement stabilize. Depending on the size of the transformer could take up to several minutes
81 Winding ResistanceTest Procedure Routine Test Should perform test for phases on as found DETC positions DETC should not be moved unless specified by company or manufacturer Ideally test for phases on all LTC positions Place DETC in as found position
82 DC Winding Resistance OMICRON
83 DC Winding Resistance Normal Pattern; but Unique OMICRON
84 DC Winding Resistance OMICRON
85 DC Winding Resistance OMICRON
86 Transformer Nameplate POS Volts LTC X1-X2-X3 A B 9 16R R R R R R R R R M 7R R R R R R R N N L L L L L L L L L L L L L L L L K Connection 7 Common to 14R and 4L
87
88 DC Winding Resistance OMICRON
89 DC Winding Resistance OMICRON
90 Analyzing Results The winding resistance measurement can be evaluated by the following three methods: (+/-5%) 1. Compare to Factory Results 2. Compare to Previous Results 3. Compare Among Phases
91 Thank You for Your Attention
Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques
Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON Transformers Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,
More informationTesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis
feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.
More informationFIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.
Regional Technical Seminar FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC. Field Electrical Testing Applications Key Purposes of Field Electrical Testing: Receiving inspection Acceptance testing/commissioning
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationRESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS
RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)
More informationPower Factor Insulation Diagnosis: Demystifying Standard Practices
Power Factor Insulation Diagnosis: Demystifying Standard Practices Dinesh Chhajer, PE 4271 Bronze Way, Dallas Tx Phone: (214) 330 3238 Email: dinesh.chhajer@megger.com ABSTRACT Power Factor (PF) testing
More informationRegional Technical Seminar TAP CHANGERS
Regional Technical Seminar TAP CHANGERS SPX Transformer Solutions, Inc. September 4, 2018 De-Energized and Load Tap Changers Jason Varnell Lead Design Engineer jason.varnell@spx.com SPX Transformer Solutions,
More informationPower Transformers Basics
Power Transformers Basics Transformer Basic Objective Introduce Basic Transformer Theory as it Relates to Diagnostics Provide a Better Understanding of the Diagnostic Test Environment Identify Important
More informationHands-On Transformer Testing and Maintenance
Hands-On Course Description This Hands-On course will teach you how to prioritize your transformer maintenance strategy, stretch your maintenance budget and at the same time maximize the life and condition
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationInnovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander
More informationPower Transformer Condition Assessment Based on Standard Diagnosis
Power Transformer Condition Assessment Based on Standard Cattareeya Suwanasri Abstract The diagnostic techniques of electrical and insulating oil testing are proposed to assess the internal condition of
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationDELTA Reference Manual Applications Guide. 12 kv Insulation Diagnostic System ZM-AH02E
DELTA 4000 12 kv Insulation Diagnostic System Reference Manual Applications Guide WWW.MEGGER.COM ZM-AH02E DELTA 4000 12 kv Insulation Diagnostic System Reference Manual Applications Guide NOTICE OF COPYRIGHT
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationTRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING
Training Title TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING Training Duration 5 days Training Date Transformer Operational Principles, Selection & Troubleshooting 5 15 19 Nov $4,250
More informationMatz Ohlen Director Transformer Test Systems. Megger Sweden
Matz Ohlen Director Transformer Test Systems Megger Sweden Frequency response analysis of power transformers Measuring and analyzing data as function of frequency, variable frequency diagnostics Impedance
More informationAlternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER
Alternative Testing Techniques for Current Transformers Dinesh Chhajer, PE Technical Support Group MEGGER Agenda Current Transformer Definition and Fundamentals Current Transformer Applications o Metering
More informationChapter 7 Conclusion 7.1 General
Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due
More information86 chapter 2 Transformers
86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.
More informationEffective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa
More informationTransformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018
Transformer Testing & Maintenance Fundamentals 1 AVO Training Institute, Inc. 2018 Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the
More informationEffective maintenance test techniques for power transformers
Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure
More information148 Electric Machines
148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional
More informationSURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company
SURGE ARRESTERS AND TESTING Keith Hill Doble Engineering Company Surge arresters are often overlooked when performing Power Factor tests on transformers, breakers and other apparatus in a substation. Often
More informationIDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy
IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy 1 Frequency Domain Spectroscopy Hi V A Lo Ground C HL Measure at several frequencies Use
More informationDiagnostic measurements on instrument transformers
Diagnostic measurements on instrument transformers A classification and overview of diagnostic measurements ABSTRACT The article presents the most common diagnostic measurements on instrument transformers
More informationTesting and Diagnostic of Power Transformers & Distribution Transformers
Testing and Diagnostic of Power Transformers & Distribution Transformers APT Power Technology Co., Ltd. Xi an FOREWORD Transformers play an very important role in power transmission and distribution system.
More informationCDAX 605 High Precision Capacitance & Dissipation Factor Test Set
CDAX 605 High Precision Capacitance & Dissipation Factor Test Set 1 Tan delta and capacitance measurements Hi V A Lo Ground C HL Measure with AC test signal, use Ohms law to calculate: Dissipation factor
More informationRESONANT TRANSFORMER
RESONANT TRANSFORMER Whenever the requirement of the test voltage is too much high, a single unit transformer can not produce such high voltage very economically, because for high voltage measurement,
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More informationTransformers handling and transport
Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary
More informationVariation in SFRA plot due to design and external parameter
Chapter 6 Variation in SFRA plot due to design and external parameter 6.1 Introduction As the experience grows with Sweep Frequency Response Analysis in world, it is useful to discuss the measurements
More informationHIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24
LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should
More informationPractical Transformer on Load
Practical Transformer on Load We now consider the deviations from the last two ideality conditions : 1. The resistance of its windings is zero. 2. There is no leakage flux. The effects of these deviations
More information~=E.i!=h. Pre-certification Transformers
7 Transformers Section 26 of the electrical code governs the use and installations of transformers. A transformer is a static device used to transfer energy from one alternating current circuit to another.
More informationMitigating Murphy s Law While Test. Frédéric Dollinger
Mitigating Murphy s Law While Test Frédéric Dollinger Curriculum Vitae Frédéric Dollinger HAEFELY HIPOTRONICS factory Basel Switzerland Area Sales & Marketing Manager Dipl. Ing. / M.Sc. Mechatronic Language:
More informationSERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT
SERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT Page TABLE OF CONTENTS POWER SYSTEM STUDY: 5 DATA COLLECTION AND NETWORK MODELLING 5 LOAD FLOW STUDY 5 SHORT CIRCUIT
More informationTertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.
Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing
More informationCondition-based maintenance of power transformers Complete three-phase system Turns Ratio: Recovery Voltage: Winding Resistance:
ETP SYSTEM Condition-based maintenance of power transformers The predictive and condition based maintenance is nowadays accepted as the most efficient solution to guarantee the proper operation of critical
More informationField Measurement of Transmission Cable Dissipation Factor
Workshop 2000, Alexandria, Virginia, 13 & 14 September 2000 paper No.: 1 Field Measurement of Transmission Cable Dissipation Factor John H. Cooper, Power Delivery Consultants, Inc. Abstract This presentation
More informationWe can classify test failure modes in power transformers according to transformer components
ON-SITE TESTS We can classify test failure modes in power transformers according to transformer components ABSTRACT To prevent unexpected outages it is necessary to implement a field test programme. It
More informationTest description for dry-type transformers chapter for special tests
Test description for dry-type transformers chapter for special tests 1. SCOPE 4 2. STANDARDS 5 3. LIGHTNING IMPULSE TEST 6 4. SOUND LEVEL MEASUREMENT 7 4.1. STANDARD 7 4.2. AIM 7 4.3. THEORETICAL PRINCIPAL
More informationThe measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms
Why Measure Winding Resistance? The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Partial or dead short-circuited
More informationElectrical Machines I : Transformers
UNIT TRANSFORMERS PART A (Q&A) 1. What is step down transformer? The transformer used to step down the voltage from primary to secondary is called as step down transformer. (Ex: /11).. Draw the noload
More informationCurve accuracy (enough data points to be statistically significant): See Attachment B.
Curve accuracy (enough data points to be statistically significant): See Attachment B. /11.0 proposals Mar 2006.doc /11.0 proposals Mar 2006.doc ATTACHMENT A New Business By Subhash Tuli Waukesha Electric
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationTRANSFORMER OPERATION
Chapter 3 TRANSFORMER OPERATION 1 A transformer is a static device (no moving parts) used to transfer energy from one AC circuit to another. This transfer of energy may involve an increase or decrease
More informationFGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI
FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown
More informationComparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137
ITEM Power factor (tanδ) & Capacitance Measurement Dry 1-minute Power frequency with partial discharge measurement CAN/CSA C88.1-96 IEEE C57.19.00/01 IEC 60137 Requirement Requirement Requirement Clause
More informationAutomatic Transformer Winding Analyser
2293 Automatic Transformer Winding Analyser The 2293 is an automatic winding analyser, optimized for three phase power and distribution transformer measurements. It uniquely combines winding resistance
More informationRegional Technical Seminar
Regional Technical Seminar LOAD TAP CHANGERS (LTCS) DESIGN, OPERATION, AND MAINTENANCE CONSIDERATIONS SPX Dallas Facility Damon Jones General Manager SPX Transformer Solutions Components Group Cell: 214-422-8979
More informationIMPORTANCE OF INSULATION RESISTANCE
IMPORTANCE OF INSULATION RESISTANCE What is Good Insulation? Every electric wire in your plant whether it s in a motor, generator, cable, switch, transformer, etc., is carefully covered with some form
More informationSingle-Phase Transformation Review
Single-Phase Transformation Review S T U D E N T M A N U A L March 2, 2005 2 STUDENT TRAINING MANUAL Prerequisites: None Objectives: Given the Construction Standards manual and a formula sheet, you will
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationBenefits of SFRA - Case Studies
6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO
More informationPomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers
Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers Introduction Tap changer at active part Example of 3-phase tapchanger Page 2 Winding Configurations
More informationPhase Shifting Transformers. Presented by
Phase Shifting Transformers Presented by Phase Shifting Transformers (PST s) (a.k.a. Phase Angle Regulators) VS φ S P V V S = X L L X L sin( φ φ ) L S VL φ L PST s are power flow control devices between
More informationTransformer & Induction M/C
UNIT- 2 SINGLE-PHASE TRANSFORMERS 1. Draw equivalent circuit of a single phase transformer referring the primary side quantities to secondary and explain? (July/Aug - 2012) (Dec 2012) (June/July 2014)
More informationEEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers
Department of Electrical Engineering Lecture Basic Operating Principles of Transformers In this Lecture Basic operating principles of following transformers are introduced Single-phase Transformers Three-phase
More informationDiscipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1
Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector
More informationTab 8 Surge Arresters
s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.
More informationGE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class
GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial
More informationTRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K
UNIT II TRANSFORMERS PART A 1. Define a transformer? A transformer is a static device which changes the alternating voltage from one level to another. 2. What is the turns ratio and transformer ratio of
More informationDiagnostic measurements on instrument transformers. Part II. A classification and overview of diagnostic measurements DIAGNOSIS EVENTS ABSTRACT
EVENTS DIGNOSIS BSTRCT Part 1 of this article, published in Vol ume 3 Issue 4, pages 100ff, describes the measurements of excitation, wind ing resistance, turns ratio and accu racy as the most common diagnostic
More informationThree-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method
Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is
More informationTECHNIQUES AND STANDARD
TRANSFORMER TESTING TECHNIQUES AND STANDARD DEVELOPMENT BY DIEGO M. ROBALINO, PhD, PMP, MEGGER-AVO Training Institute Transformer manufacturers and field operators have always benefitted when new technologies
More informationDEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER
DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER JESSE M LOPEZ CPS ENERGY USA EMILIO MORALES CRUZ QUALITROL USA SUMMARY Power transformers are essential
More informationDispersing the clouds gain clear insight into your bushings using advanced diagnostic methods
Topic Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods Abstract: Bushing diagnosis can include various methods, from a simple visual inspection or a conventional
More informationSpring 2000 EE361: MIDTERM EXAM 1
NAME: STUDENT NUMBER: Spring 2000 EE361: MIDTERM EXAM 1 This exam is open book and closed notes. Assume f=60 hz and use the constant µ o =4π 10-7 wherever necessary. Be sure to show all work clearly. 1.
More informationThe power transformer
ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit
More informationSECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University
SECTION 4 TRANSFORMERS Yilu (Ellen) Liu Associate Professor Electrical Engineering Department Virginia Tech University Analysis of Transformer Turns Ratio......................... 4.2 Analysis of a Step-Up
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationTransformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications
The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of
More informationModule 7. Transformer. Version 2 EE IIT, Kharagpur
Module 7 Transformer Lesson 28 Problem solving on Transformers Contents 28 Problem solving on Transformer (Lesson-28) 4 28.1 Introduction. 4 28.2 Problems on 2 winding single phase transformers. 4 28.3
More informationTRANSFORMER THEORY. Mutual Induction
Transformers Transformers are used extensively for AC power transmissions and for various control and indication circuits. Knowledge of the basic theory of how these components operate is necessary to
More informationMonitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers
in cooperation with Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers BZ-MS/1 pazifik power Complete Transformer Monitoring System (TMS) ZVCM-1001 Bushing Monitoring
More informationSTRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS
1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com
More informationINSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad
INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 00 0 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name Course Code Class Branch : ELECRICAL MACHINES - II : A0 :
More informationCHAPTER 4. Distribution Transformers
CHAPTER 4 Distribution Transformers Introduction A transformer is an electrical device that transfers energy from one circuit to another purely by magnetic coupling. Relative motion of the parts of the
More informationCase Studies of Electric Power Equipment Diagnostics Using Acoustic Emission
17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission Oswaldo G. SANTOS FILHO 1, Sergio L. ZAGHETTO
More informationTransformers: Basics, Maintenance, and Diagnostics
Basics, Maintenance, and Diagnostics U.S. Department of the Interior Bureau of Reclamation April 2005 Basics, Maintenance, and Diagnostics U.S. Department of the Interior Bureau of Reclamation Technical
More informationINSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING
Course Name Course Code Class Branch INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK : ELECRICAL MACHINES I : A40212
More informationISSN: [IDSTM-18] Impact Factor: 5.164
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A REVIEW OF ROUTINE TESTING ON DISTRIBUTION TRANSFORMER Sukhbir Singh 1, Parul Jangra 2, Anoop Bhagat 3, Vipin Saini 4 1 Assistant
More informationMAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
Important Instructions to examiners: 1) The answers should be examined by key words and not as word-to-word as given in the model answer scheme. 2) The model answer and the answer written by candidate
More informationMAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
Important Instructions to examiners: 1) The answers should be examined by key words and not as word-to-word as given in the model answer scheme. 2) The model answer and the answer written by candidate
More informationPractical Tricks with Transformers. Larry Weinstein K0NA
Practical Tricks with Transformers Larry Weinstein K0NA Practical Tricks with Transformers Quick review of inductance and magnetics Switching inductive loads How many voltages can we get out of a $10 Home
More informationPHYS 1441 Section 001 Lecture #22 Wednesday, Nov. 29, 2017
PHYS 1441 Section 001 Lecture #22 Chapter 29:EM Induction & Faraday s Law Transformer Electric Field Due to Changing Magnetic Flux Chapter 30: Inductance Mutual and Self Inductance Energy Stored in Magnetic
More informationAdvanced Diagnostic Testing Services. Provides detailed and reliable results
Advanced Diagnostic Testing Services Provides detailed and reliable results Advanced Diagnostic Testing Services from the world s leading manufacturer of power transformers ABB leadership begins with our
More informationISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer
ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering
More informationCHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES
CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES 3.1. Introduction Power Transformer is the nerve centre of any power distribution system. The capacity of power transformers is generally decided
More informationTEST VOLTAGES INFLUENCE ON TURN RATIO TESTING ndb Technologies model ART-3D
TEST VOLTAGES INFLUENCE ON TURN RATIO TESTING model ART-3D Application has been working with several transformer maintenance crews manufacturers over the years. One of the prevalent challenges was obtaining
More informationEPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY
EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY EPS AUSTRALIA SERVICES COMPANY OVERVIEW EPS is a recognised company specialising in Electrical, Instrumentation, Structural, Mechanical and
More informationDISTRIBUTION TRANSFORMERS
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 4 DISTRIBUTION TRANSFORMERS A transformer is a static device that
More informationAC Dielectric Test Sets
AC Dielectric Test Sets AC Test Systems Hipotronics standard line of AC Test Systems are designed to perform high voltage AC tests on electrical apparatus in accordance with IEC60, IEEE 4 and IEC 270 and
More information