TECHNICAL SPECIFICATION FOR POWER TRANSFORMER
|
|
- Jordan Norton
- 6 years ago
- Views:
Transcription
1 TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL DATA SHEET HPCL S REQUIREMENT VENDORS COMMENTS 1.0 SCOPE DESIGNING, MANUFACTURING, TESTING, SUPPLYING & COMMISSIONING OF POWER TRANSFORMER 2.0 APPLICABLE CODES IS:335 IS: 2026, PART I, II, III & IV IS: 2147 IS: 3696 IS: 1180, PART I IS: 10028, PART I IS: 11171, MAKE TO BE SPECIFIED BY VENDOR 4.0 TYPE DOUBLE WOUND, COPPER CONDUCTOR, ONAN 5.0 SERVICE OUTDOOR TYPE 6.0 CAPACITY 1500 kva (REFER TERMS & CONDITIONS) 7.0 NO LOAD VOLTAGE 33 kv / 11 kv RATIO 8.0 FREQUENCY & PHASES 50 HZ, 3 PHASE 9.0 INSULATION CLASS A 10.0 WINDING INSULATION Primary: Uniform; Secondary: Uniform 11.0 POWER FLOW Unidirectional 12.0 NORMAL LOAD(% of 80% ONAN Rating) 13.0 CONNECTION DELTA / STAR 14.0 VECTOR GROUP Dyn TAP CHANGER ON LOAD TAP CHANGER 16.0 TAPPING RANGE & STEPS -12.5% TO % IN STEPS OF 2.5% 17.0 ONLOAD TAP CHANGER /RTCC - WITH REMOTE CUBICLE. - AUTOMATIC VOLTAGE CONTROL, LOCAL / REMOTE OPERATION TO BE PROVIDED. - SINGLE FLOAT BUCHHOLZ
2 PROVISION OF OLTC PANEL PARAMETERS FOR ECS/REMOTE INTERFACE 18.0 MAX. AMBIENT TEMPERATURE 18.1 TEMPERATURE RISE IN WINDING TEMPERATURE 18.2 TEMPERATURE RISE IN RELAY / OIL SURGE RELAY. - ADDITIONAL LOOSE SUPPLY OF TAP POSITION INDICATOR, RAISE / LOWER PUSH BUTTONS, TRANSDUCERS & NECESSARY INTERFACE TO BE PROVIDED ON RTCC. CONTACTS FOR OLTC TROUBLE ALARM, TAP POSITION 48 C 55 C AS MEASURED BY RESISTANCE 45 C TOP OIL 19.0 NO LOAD LOSS WITHIN IS SPECIFIED TOLERANCE LIMITS AT RATED VOLTAGE AND FREQUENCY FULL LOAD LOSS WITHIN IS SPECIFIED TOLERANCE LIMITS AT 75 C AND AT PRINCIPLE TAP IMPEDANCE AT 75 C AND AT PRINCIPLE TAP 22.0 SYSTEM NEUTRAL EARTHING 23.0 DEGREE OF PROTECTION IP TERMINATION PRIMARY SIDE 25.0 TERMINATION SECONDARY SIDE 26.0 NEUTRAL GROUNDING RESISTOR (NGR) Continuous Rating (as 10% of short time rating) VENDOR TO SPECIFY. Secondary: Resistance Earthing OUTDOOR TYPE H.T. CABLE BOX SUITABLE FOR 3 CORE, 120 SQ.MM, 33 kv GRADE, XLPE ARMOURED CABLE. (on the small side of Transformer) OUTDOOR TYPE H.T. CABLE BOX SUITABLE FOR 3 CORE, 185 SQ.MM, 11 kv GRADE, XLPE ARMOURED CABLE (on the side at right angle to the primary terminal side) Rated Voltage: 6351 V Required Terminal Connections Transformer Neutral to NGR: 185 Sq.mm AL conductor, XLPE insulated 11KV armored cable.
3 NGR to Earth: 75 X 10 sq.mm GI earth strip PAINT & SHADE EPOXY PAINT OF SHADE RAL 7035 B ACCESSORIES 1.0 OIL CONSERVATOR WITH DRAIN PLUG WITH OIL LEVEL INDICATOR 2.0 VALVE BETWEEN CONSERVATOR & TANK 3.0 DIAL TYPE THERMOMETER 4.0 SAMPLE VALVE, TOP/BOTTOM FILTER VALVE & DRAIN VALVE 5.0 DOUBLE DIAPHRAGM EXPLOSION VENT & AIR RELEASE PLUG 6.0 EARTHING TERMINALS 2 NOs. 7.0 SILICA GEL BREATHER 8.0 LIFTING LUGS AND FOUR BIDIRECTIONAL FLAT ROLLERS 9.0 BASE CHANEL WITH TOWING LOCK 10.0 DIAGRAM PLATE & RATING PLATE 11.0 DOUBLE FLOAT BUCHHOLZ RELAY WITH ALARM AND TRIP CONTACTS 12.0 WINDING TEMPERATURE INDICATOR 13.0 RADIATOR WITH COOLING LUBE 14.0 MARSHALLING BOX (IP- 55)FOR AUXILIARY WIRING 15.0 TAP CHANGER (OLTC/RTCC) C PERFORMANCE & PARAMETERS 1.0 NO LOAD LOSS AT RATED VOLTAGE & FREQUENCY (OPERATION OF TRIP CONTACT OF THE RELAY SHOULD TRIP THE VCB IN SUB STATION) WITH ALARM & TRIP CONTACTS AND MAXIMUM READING POINTER WITH RESETTING FACILITY. WITH LOCKING ARRANGEMENT AND POSITION INDICATOR VENDOR TO SPECIFY
4 (Guaranteed) 2.0 LOAD LOSS AT RATED VENDOR TO SPECIFY CURRENT AT 75 C (Guaranteed) 3.0 % IMPEDANCE AT RATED VENDOR TO SPECIFY CURRENT AND FREQUENCY AT 75 C 4.0 REACTANCE AT RATED VENDOR TO SPECIFY CURRENT & FREQUENCY AT 75 C 5.0 EFFICIANCY AT 75 C AT U.P.F. 5.1 AT FULL LOAD VENDOR TO SPECIFY 5.2 AT 75% LOAD VENDOR TO SPECIFY 5.3 AT 50% LOAD VENDOR TO SPECIFY 6.0 REGULATION AT FULL C 6.1 AT U.P.F VENDOR TO SPECIFY 6.2 AT 0.8 P.F. VENDOR TO SPECIFY 7.0 WEIGHT VENDOR TO SPECIFY 7.1 CORE VENDOR TO SPECIFY 7.2 WINDING VENDOR TO SPECIFY 7.3 TANK & FITTINGS VENDOR TO SPECIFY 7.4 OIL VENDOR TO SPECIFY 8.0 DIMENSIONS 8.1 LENGTH VENDOR TO SPECIFY 8.2 BREADTH VENDOR TO SPECIFY 8.3 HEIGHT VENDOR TO SPECIFY D SPECIAL REQUIREMENTS 1.0 TYPE TEST CERTIFICATE FOR THE GIVEN CAPACITY FROM CPRI 2.0 SURGE WITHSTAND CAPACITY TRANSFORMER SHOULD WITHSTAND SURGE DUE TO STARTING OF HIGH RATING
5 3.0 DETAILS OF CORE WINDING AND SATURATION LEVEL OF CORE 4.0 DRAWINGS AND DATAS (4 COPIES) PUMP MOTORS (LARGEST MOTOR IS OF 110 KW IN STAR- DELTA MODE) -OUTLINE DIMENSIONAL DRAWINGS AND THE GENERAL ARRANGEMENT OF TRANSFORMER AND ACCESSORIES SHOWING ALL REQD. CLEARANCES -FOUNDATION PLAN DRAWINGS -WIRING DIAGRAM FOR W.T.I. & MARSHALLING BOX. 5.0 INSTRUCTION MANUAL 4 SETS REQUIRED COVERING OPERATION & MAINTENANCE. 6.0 PACKING - TRANSFORMER SHOULD BE SUITABLY PACKED. PACKING IN A WOODEN CASE IS NOT REQUIRED. HOWEVER, SUPPLIER HAS TO SUPPLY A TARPAULIN FOR COVERING. - CONSERVATOR TO BE PACKED SEPARATELY 7.0 UNLOADING AT SITE BY HPCL 8.0 TESTING AND COMMISSIONING E SCOPE OF THIRD PARTY INSPECTION. BY VENDOR AS PER SCOPE OF WORK. Note: The Guaranteed parameter of Iron & Copper losses will be taken into consideration for evaluation of bids and the actual Iron & Copper losses based on the factory testing, duly certified by TPI shall be reviewed to assess the applicability of penalty. (Please refer terms and conditions for calculation of loading and penalty criteria) 1.0 AGENCIES THIRD PARTY INSPECTION SHALL BE ARRANGED BY THE VENDOR ON THEIR OWN COST BY ONE OF THE FOLLOWING AGENCIES: - D N V / CE I L / L L O Y D S / I R S/ BV
6 2.0 ACTIVITIES TO BE CARRIED OUT BY THIRD PARTY INSPECTION AGENCIES F MAKE OF ACCESSORIES CERTIFYING THE FOLLOWING TESTS ON THE TRANSFORMER: -RATIO TEST, POLARITY TEST & VECTOR GROUP TEST -IMPEDANCE VOLTAGE TEST -SPECIFIC RESISTANCE TEST -INSULATION RESISTANCE TEST OF PRIMARY, SECONDARY WINDINGS AND BETWEEN CORE AND WINDINGS - NO LOAD LOSSES AND CURRENT TEST - LOAD LOSSES TEST - INDUCED OVERVOLTAGE WITHSTAND TEST - THIRD PARTY INSPECTION AGENCY SHALL GIVE A CERTIFICATE TO THE EFFECT THAT ENTIRE TRANSFORMER ALONG WITH THE ACCESSORIES CONFORM TO THE SPECIFICATIONS GIVEN IN THE PURCHASE ORDER. TRANSFORMER SHALL BE TESTED BY THE MANUFACTURERS AS PER THE RELEVANT CODES AND THE CERTIFICATES SHALL BE PROVIDED TO THE THIRD PARTY INSPECTION AGENCY DURING THE INSPECTION FOR THEIR VERIFICATION AND ENDORSEMENT. ONE COPY OF THIRD PARTY INSPECTION REPORT AND TEST CERTIFICATES SHALL BE SENT TO SITE ALONG WITH THE TRANSFORMER AND BALANCE 2 COPIES SHALL BE SENT ALONG WITH THE INVOICE. (In case the vendor intends to provide the accessories of make not indicated below, the same shall be done with the approval from HPCL) 1 BUCHHOLZ RELAY A J SERVICES/ ATVUS 2 MAGNETIC OIL LEVEL INSTRUMENT & CONTROL / GAUGE SUKRUT UDYOG 3 OIL TEMPERATURE PERFECT CONTROL /
7 INDICATOR PRECIMEASURE 4 WINDING TEMPERATURE INDICATOR CONTROL 5 CURRENT TRANSFORMER PERFECT CONTROL / PRECIMEASURE ABB/ ELECTRIC CONTROLS & SYSTEMS / KAPPA ELECTRICALS/PRAGATI ELECTRICALS / ALSTOM 6 OLTC BHEL / CGL / TRANSFORMERS & ELECTRICALS KERALA LTD. /EASUN-MR TAP CHANGERS PVT. LTD. /ONLOAD GEARS / CTR MANUFACTURING INDUSTRIES LTD. 7 Control Switches Alstom / Siemens / L&T / Switron Devices / Havells / Hotline Switchgear & Controls / Kaycee / Reliable Electronic Company Pvt.Ltd. 8 Fuse / Fusebase Siemens / L&T / GE Power Control / Indo-Asian Fuse Gear
DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO
PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %
More informationsave energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers
save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED
More informationPRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationPURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS
PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY
More informationProlific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2
Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II
More informationPRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS
PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules
More informationIntroduction. Centrado leading-edge transformer. Introduction
Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,
More informationSCHEDULE OF WORK. Balmer Lawrie Co. Ltd. PRICED BID (PART-II) MMLH
SCHEDULE OF WORK Supply, Installation, Testing & Commissioning (SITC) of 33KV Electrical Substation for Multi Modal Logistics Hub at Visakhapatnam, Andhra Pradesh. Tender No. MMLH /HTELEC/PT /18 dated
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More informationOIL-IMMERSED ARC-SUPPRESSION COILS
ISO 9001:2000 99-320 Żychlin, ul. Narutowicza 70 ISO 14001:2004 PN-N-18001:2004 www.ftz.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31 zarzad@ftz.pl Sales and Marketing Department
More informationGroup F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A
Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating
More informationAPDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL
PART 1: GENERAL 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, offloading and performance requirements of 11/0.433kV distribution transformers for outdoor
More informationPUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT
PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT SPECIFICATION SS-25 / 14 POWER TRANSFORMERS 150/15.75-21kV, 40/50 MVA WITH AUTOMATIC LOAD-RATIO CONTROL CONNECTION
More informationMESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION
Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:
More informationBasic Principles and Operation of Transformer
Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core
More informationGeneral Electricity Company of Libya
GES 22214 Technical Specification of GECOL 11/0.4kV Oil Immersed Ground Mounted Three Phase Sealed Type Distribution Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company
More informationNEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :
NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE
More informationForm-IV. Form of Inspection/Test Report. (Under Regulation 43)
Form-IV Form of Inspection/Test Report (Under Regulation 43) 1. Name and address of the Chartered Electrical Safety Engineer 2. Name and address of the consumer (or) Owner(or) supplier: Contact No: E-Mail:
More informationPomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers
Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers Introduction Tap changer at active part Example of 3-phase tapchanger Page 2 Winding Configurations
More informationSOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)
E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION
More information51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V
SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without
More informationWESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)
WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices
More information51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS
SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS This specification is property of SEC and Subject to change or modification without any notice Table of Contents Clause Page 1.0 SCOPE
More informationSPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION February 2017 SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER
More informationTECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) S. No. PARTICULARS BHEL SPECIFICATIONS
TECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) BIDDER s OFFER S. No. PARTICULARS BHEL SPECIFICATIONS 1.0 Area of Application The 300kV Constant potential
More informationINTERPLANT STANDARD - STEEL INDUSTRY CODE OF PRACTICE FOR TESTING & COMMISSIONING OF TRANSFORMERS AND RELATED SWITCHGEARS
INTERPLANT STANDARD - STEEL INDUSTRY IPSS CODE OF PRACTICE FOR TESTING & COMMISSIONING OF TRANSFORMERS AND RELATED SWITCHGEARS Corresponding IS does not exist IPSS:1-04-035-08 0. FOREWORD 0.1 This Inter
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationHOW TO SAFE GUARD THE TRANSFORMER..???
CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationEARTHING TRANSFORMER
EARTHING TRANSFORMER December 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;
More informationDISTRIBUTION TRANSFORMER 11 / kv
Ministry of Electricity (MOE) Power Distribution Office Baghdad IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 11 / 0.416 kv 2BREVISION 3BYEAR 2013 1 Table of Contents: Clause : no. 1. Scope of The
More informationK Factor Power Transformers
Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business
More informationA Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment
International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV
More information36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)
CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994
More informationMESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER Version: 3 Issued: February 2018 Owner: Head of Engineering - Electrical Approved By: Andrew Russack Head
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationMV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer
PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationCONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationPS REV NO: 01 PAGE : 2 OF 22
PAGE : 2 OF 22 1.0 INTRODUCTION Bharat Heavy Electricals Limited (BHEL), Electronics Division, Bangalore is setting up a 10 MW Solar PV Grid-connected power plant for its customer BEL at O.F.BOL, Badmal,
More informationTECHNICAL DESCRIPTION ND-387. THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1
HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. December 2017 TECHNICAL DESCRIPTION ND-387 THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1 I. SCOPE The scope of the present description
More informationCompact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED
Dial : (033)2677-5835 & 2667-8358 Tele Fax : (033)2667-8358 Manufacturer of Dry Type Transformers E-mail : unimag111@gmail.com Office & Factory : 26/5, Sarat Chatterjee Road, Howrah 711 104, West Bengal,
More informationEE059: Transformer Operation, Maintenance, Diagnosis & Testing
EE059: Transformer Operation, Maintenance, Diagnosis & Testing EE059 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: Power and distribution transformers are essential devices in electricity
More informationTRANSFORMER OPERATIONAL. Principles, Selection & Troubleshooting
TRANSFORMER OPERATIONAL Principles, Selection & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Power and distribution transformers
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationShunt Reactors. Global Top Energy, Machinery & Plant Solution Provider
Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical
More informationDISTRIBUTION TRANSFORMERS
DISTRIBUTION TRANSFORMERS OIL IMMERSED up to 6 MVA www.alfanar.com Contents 1 - General Information 4 2 - Applications 10 3 - Product Portfolio 11 4 - Product Breakdown 12 5 - Transformer Classifications
More informationOnsite Mobile AC High Voltage Test System
TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument
More informationElectrical Description
History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced
More informationMaharashtra State Electricity Distribution Co. Ltd.
Maharashtra State Electricity Distribution Co. Ltd. SPEC. NO. STORES:MSC-II/ conventional power Trf/ 2011 SPECIFICATION FOR 5 MVA and 10 MVA 33/11 kv, 33/22 kv & 22/11 kv POWER TRANSFORMERS FOR VARIOUS
More informationCOMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS
006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR
More informationSGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:
SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument
More informationCast resin transformers HARMONY TM
Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety
More informationNPS/003/021 Technical Specification for Continuous Maximum Rated (CMR) Transformers.
Document Reference :- NPS/003/021 Document Type :- Code of Practice Version :- 4.0 Date of Issue :- November 2016 Page 1 of 43 NPS/003/021 Technical Specification for Continuous Maximum Rated (CMR) Transformers.
More information2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type
PAGE 2 of 6 2.14 Main Cable Type HO7RN-F4G10-15 Metres each 2.15 (a) O/P Voltage-350V(Max.) (b) O/P Current 150A(Max.) 2.16 Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type 2.17
More informationDistribution Equipments - Technology and Applications. Training Module for DISTRIBUTION TRANSFORMER
Distribution Equipments - Technology and Applications Training Module for DISTRIBUTION TRANSFORMER Transformer specification Transformer design Manufacturing / quality control Testing in the Works Transportation
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More information66/ or 23.1 kv, 05, 10, 15 & 20 MVA POWER TRANSFORMER
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 66/ 11.55 or 23.1 kv, 05, 10, 15 & 20 MVA POWER TRANSFORMER GETCO/E/TS
More informationWEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED
1.00 SCOPE OF SPECIFICATION 1.01 This specification is intended to cover design, manufacture, assembly testing at manufacturer s works, supply and delivery upto placement on plinth of three phase 50HZ,
More informationSPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.
SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. 1. SCOPE: This specification covers design, manufacture, testing and supply of 6.64/10.12 KV 24/15.7, 30/19.7
More informationELETTROMECCANICA. Since english OIL IMMERSED DISTRIBUTION TRANSFORMERS
ELETTROMECCANICA P I O S S A S C O Since 1962 english OIL IMMERSED DISTRIBUTION TRANSFORMERS ELETTROMECCANICA PIOSSASCO was created from the transformation of Elettromeccanica Luparia established in the
More informationSCHEDULE-VII TECHNICAL SPECIFICATIONS. Specification No
SCHEDULE-VII TECHNICAL SPECIFICATIONS Specification No. 01410116 11KV/415V, 400 kva, 630 kva, 1000 kva and 1600 kva, SINGLE RATIO, ONAN TYPE DISTRIBUTION TRANSFORMERS Notice for revision of specification
More information1 SCOPE & INTENT OF SPECIFICATION
1 SCOPE & INTENT OF SPECIFICATION Welspun Solar UP Private Limited. is setting up a 5 MW Solar PV Power Plant in state of Rajasthan at Village Deh, Tehsil Kolayat, District Bikaner 4.5MVA Inverter Transformer
More informationCONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS
CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased
More informationPOWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
POWER TRANSFORMER Failure Analysis & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Electricity is high-grade energy. Working
More informationUNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationOIL TRANSFORMER HV/LV
Rev.02 - Pag. 1/23 Installation, use and maintenance Manual OIL TRANSFORMER Rev.02 - Pag. 2/23 TABLE OF CONTENTS 1 INTRODUCTION... 4 1.1 Reference standard... 4 1.2 Electromagnetic compatibility... 4 1.3
More informationNSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation
Version:- 1.0 of Issue:- March 2016 Page 1 of 7 NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation 1. Purpose The purpose of this document is to provide guidance
More informationCAST RESIN DRY TRANSFORMER
CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,
More informationIndustrial Applications
Industrial Applications Transformers for Industrial Applications Tamini has always produced industrial transformers of high quality and reliability, designed to satisfy the most diverse and complex technical
More informationPOWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS
POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A
More informationGE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class
GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial
More informationCommissioning Manual Distribution Transformers - Three-phase Oil Filled
1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...
More informationS. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)
S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical
More informationPower Processor - Series 700F 10KVA to 150KVA
Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines
More informationTechnical Specifications SECTION C
Page 1 of 19 INSTITUTE FOR PLASMA RESEARCH Technical Specifications SECTION C Design/engineering, manufacture, inspection, testing at vendor s site, delivery, handling at site, erection, precommissioning
More informationTraining Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.
Training Title POWER SYSTEM GENERATION & DISTRIBUTION Training Duration 5 days Training Venue and Dates Power System Generation & Distribution 5 08-12 December, 2019 $4,000 Dubai, UAE Trainings will be
More informationVOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)
TENDER DOCUMENT NIT No. DLI/C&E/WI-665/535R FOR Tender for Supply of 3CX185 mm2, 11 KV (UE) grade, Power Cable for Augmentation of Raw Material Handling Receipt and Handling Facilities with new OHP Part
More informationSECTION TRANSFORMERS
SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section
More information50-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------
More informationSECTION VI TECHNICAL SCHEDULES
SECTION VI TECHNICAL SCHEDULES Kenya Power and Lighting Company VI 4.3 - i Contract A36B TECHNICAL SCHEDULES 1 PREAMBLE...1 TECHNICAL SCHEDULES SUBSTATIONS...2 SCHEDULE VI-1a TECHNICAL GUARANTEES, OUTDOOR
More informationTechnical Specifications
Page 1 of 14 INSTITUTE FOR PLASMA RESEARCH Technical Specifications Design/engineering, manufacture, inspection, testing at vendor s site, delivery at site of resin cast dry type Cast Resin Transformer
More informationTesar s.r.l. Installation and maintenance manual. Installation, use and maintenance. Manual. Page :1\20
Installation, use and maintenance Manual Page :1\20 1. INTRODUCTION 1.1. Reference Standards 1.2. Outline of the transformers and the accessories 2. RECEPTION, HANDLING, STORAGE 2.1. Reception 2.2. Transport
More informationUBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS
More informationHands-On Transformer Testing and Maintenance
Hands-On Course Description This Hands-On course will teach you how to prioritize your transformer maintenance strategy, stretch your maintenance budget and at the same time maximize the life and condition
More informationReport on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)
Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/F.06/2015-16/Mgr(Bawana)/353 dated
More informationDiscipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1
Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector
More information220/132 kv, 150 & 100 MVA; 132/66 kv, 50 MVA AUTO TRANSFORMER
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220/132 kv, 150 & 100 MVA; 132/66 kv, 50 MVA AUTO TRANSFORMER GETCO/E/TS
More informationSection L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES
Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE The following is PG&E's procedure for pre-energization inspections. For PG&E to provide the Load
More informationVI 3 - i TABLE OF CONTENTS
VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3
More informationPOTENTIAL TRANSFORMER
POTENTIAL TRANSFORMER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK PO Box 25876 Safat 13119 Kuwait Contact: Mr Atul Madhukar Vaidya Tel: +965 1822600 Fax: +965 24761963 E-Mail: factory@ahleiasg.com Website:
More informationEPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY
EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY EPS AUSTRALIA SERVICES COMPANY OVERVIEW EPS is a recognised company specialising in Electrical, Instrumentation, Structural, Mechanical and
More informationTECHNICAL SPECIFICATION OF 630 KVA, 11/ KV DRY TYPE OUTDOOR TRANSFORMERS.
TECHNICAL SPECIFICATION OF 630 KVA, 11/ 0.415 KV DRY TYPE OUTDOOR TRANSFORMERS. 1. 0 Scope: This specification covers design, manufacture, testing and supply of 630 KVA, 11/0.415 KV, Dry Type Distribution
More informationDistribution and Power Transformers
Distribution and Power Transformers The data provided in this document is accurate at time of going to press. As standards, specifications and designs are subject to change, please ask for confirmation
More information