Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)
|
|
- Brent McBride
- 5 years ago
- Views:
Transcription
1 Name: Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC) 1. T F In three-phase four-wire delta systems rated 240/120 volts, sometimes called red leg delta systems, the nominal voltage from the red leg (sometimes called the wild leg ) to the secondary neutral conductor is 208 volts. 2. T F The primary windings of three-phase distribution transformers, or three single-phase distribution transformers (transformer bank) can be connected in grounded wye only if the primary system supplying the three-phase transformer or transformer bank is an ungrounded (delta) primary system. 3. T F When three single-phase distribution transformers are connected to the multi-grounded neutral primarysystem with the primary (HV) windings connected in grounded wye (one end of each HV winding connected to the neutral conductor), and the secondary (LV) windings connected in delta, one or more of the fuses in the primary leads of the distribution transformer bank cannot blow for single lineto-ground faults that are on the primary feeder, either upstream or downstream of the transformer bank. 4. T F A single-phase distribution transformer with a high voltage winding designated 7620/13200 Y volts on the nameplate has one high voltage bushing, with the rated voltage of the high voltage winding being 7620 volts. 5. T F A single-phase distribution transformer with a high voltage winding designated grd Y/7620 volts on the nameplate has two high voltage bushings, with the rated voltage of the high voltage winding being 7620 volts. 6. T F When paralleling two single-phase distribution transformers, the transformers should have the same turns ratio between the primary and secondary windings, and the same nameplate impedance in percent so that the kva rating of the parallel combination is the sum of the kva rating of the two units being paralleled. 1
2 7. T F A 50 kva single-phase transformer is paralleled with a 100 kva single-phase transformer. The impedance on the nameplate of the 50 kva transformer is 1.6 %, and the impedance on the nameplate of the 100 kva transformer is 2.2 %. The derating factor for the parallel combination is T F When three single-phase distribution transformers are connected in a delta-delta bank (primary windings connected in delta, secondary windings connected in delta), it is not necessary that each transformer have the same primary winding to secondary winding turns ratio. This is because the fuses installed in the primary lines for the transformers will always thermally protect the transformers if they have different turns ratios. 9. T F Con Edison has single-phase distribution transformers in open-wye open-delta banks on Staten Island to supply three-phase four-wire delta loads. In these banks, the primary (HV) winding of each transformer is connected from phase to ground (neutral), and the secondary (LV) windings are in open delta to supply 240-volt three-phase three-wire load and 120/240-volt single-phase three-wire load. If the line terminal of the high-voltage winding of each transformer is inadvertently connected to the same high-voltage phase, two of the secondary phase-tophase voltages will be normal (240-volts), and the other phase-to-phase secondary voltage will be one half of the normal value. 10. T F In three-phase distribution transformers having the primary windings connected in grounded-wye and the secondary windings connected in grounded-wye, placing the transformer windings on a three-legged core assures that the transformer will not experience tank heating during a single phase-to-ground fault at the HV terminal (From H1 to H0) with a blown fuse between the primary source and the faulted HV terminal (H1), with terminals H2 and H3 energized at rated voltage. 2
3 11. T F In three-phase distribution transformers having the primary windings connected in grounded-wye and the secondary windings connected in grounded-wye, placing the transformer windings on a four-or five-legged core assures that the transformer will not experience tank heating. This applies to all types of faults and unbalances that can occur on the primary system to which the transformer is connected. 12. T F Three-phase distribution transformers for supplying 208Y/120 volt or 480Y/277-volt services have the secondary windings connected in grounded wye, with the primary windings connected in either delta or groundedwye. With the grounded-wye grounded-wye connections for the transformer primary and secondary windings, fundamental frequency currents and harmonic currents from the secondary load which are zerosequence in nature (in-phase in each phase on the secondary) will flow in the neutral conductor of the primary feeder supplying the transformer. 13. T F Fuses applied at the high-voltage HV) terminals of a transformer with the delta connected HV winding and grounded-wye connected LV winding should have a voltage rating equal to or greater than the system line-toline voltage, whereas fuses applied at the high-voltage terminals of a transformer with the grounded-wye grounded-wye connections can have a voltage rating that is less than system line-to-line voltage. 14. T F When a fault occurs at the service entrance in a typical single-phase three-wire 120/240-volt service, the current for the 120-volt fault (phase-to-neutral fault) is higher than the current for the 240-volt fault (phase-to-phase fault). 15. T F When a fault occurs at the low-voltage (secondary) terminals of a single-phase distribution transformer with the low-voltage winding rated 120/240 volts, the current for the 120-volt fault (phase-to-neutral fault) is higher than the current for the 240-volt fault (phase-to-phase fault). 3
4 16. T F When a fault occurs at the low-voltage terminals of a particular distribution transformer, with low-voltage windings rated 120/240 volts, the current in the fault path is 10,000 amperes rms when the two halves of the lowvoltage (secondary) winding are in series and the fault is across the entire secondary winding. For practical purposes, if the two halves of the secondary winding, each rated 120 volts, are paralleled, and a fault placed across the terminals of the paralleled windings, the current in the fault path will be 20,000 amperes. 17. T F In ungrounded secondary systems supplied from open delta transformer banks, such as a 480-volt delta secondary system, voltages of 1000 volts or higher may appear from phase-to-ground in the secondary system under normal operating condition when the transformer bank is energized from the primary system. 18. T F When ferroresonance occurs in radial primary distribution circuits during single-pole switching of a cable circuit and an unloaded three-phase distribution transformer, the waveshapes of the phase currents, phase-to-phase voltages, and phase to ground voltages are perfect sine waves. 19. T F When ferroresonance occurs in radial primary distribution circuits during single-pole switching of a cable circuit and an unloaded three-phase transformer connected to the end of the cable circuit, there are very high currents in the energized phase(s) [phases with closed switch at the sending end], and the line-to-ground voltages on the open phase(s) [phases with open switch at the sending end] are always less than the rated line-to-ground voltage of the system. 20. T F Transformers with triplex construction use three singlephase core-coil assemblies in a common tank with no magnetic coupling between the three phases within the transformer tank. 4
5 21. T F Ferroresonance is very unlikely during energization or deenergization of a three-phase cable circuit and an unloaded three-phase transformer connected to the circuit, using single-pole switches located at the source end of the cable circuit, if the transformer primary windings are connected in grounded wye and the three-phase transformer employs triplex construction. 22. T F Ferroresonance is very unlikely during energization or deenergization of a three-phase cable circuit and an unloaded three-phase transformer connected to the circuit, using single-pole switches located at the source end of the cable circuit, if the transformer primary windings are connected in delta. 23. T F Ferroresonance can not occur when energizing, with single-phase fused cutouts (switches), unloaded transformers banks made with three single-phase pole-top transformers with ungrounded primary windings (connected in floating wye with secondary windings in delta) in the overhead system when the fuse cutouts are on the same pole as the transformer bank. 24. T F When energizing with single-pole switches a floating-wye delta transformer bank with unbalanced load connected to the secondary (delta) side, the voltage from the primary terminal to ground at the transformer whose cutout has not yet been closed can never exceed times the system nominal phase-to-ground voltage. 25. T F When a current-limiting fuse is applied at the HV terminals of a single-phase single-bushing distribution transformer with primary (HV) winding connected from phase-toground (neutral), rather than a fused cutout (expulsion fuse), the transformer is less likely to rupture should a high-current fault occur internally from a primary (HV) winding lead to the grounded tank of the transformer. 26. T F In a secondary system with a nominal phase-to-phase voltage of 240 volts, the three measured phase-to-phase voltages are 235 volts, 230 volts, and 222 volts. Using the NEMA definition for voltage unbalance, the percent voltage unbalance is %. 5
6 27. T F Ferroresonance will not occur in Con Edison network systems supplied from 13.8 kv or 27 kv primary feeders because the network transformers use the grounded wye connections for both the primary (HV) and secondary (LV) windings. 28. T F Con Edison three-phase pole-top distribution transformers use the delta connection for the primary (HV) windings (13.8 kv and 27 kv systems), and the grounded-wye connection for the secondary (LV) windings to supply either 208Y/120-volt or 480Y277 volt secondary systems. 29. T F Con Edison three-phase pole-top transformers in the cylindrical tank utilize a four-loop five-legged core design, and three-phase pole-top transformers in the rectangular tank utilize triplex construction (three single-phase corecoil assemblies). March
Transformers. 4.1 Basics
4 Transformers Ac transformers are one of the keys to allowing widespread distribution of electric power as we see it today. Transformers efficiently convert electricity to higher voltage for long distance
More informationExperiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE
Experiment 45 Three-Phase Circuits OBJECTIVE To study the relationship between voltage and current in three-phase circuits. To learn how to make delta and wye connections. To calculate the power in three-phase
More informationTopic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017
Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationCONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationTertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.
Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing
More informationUNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More information3Ø Short-Circuit Calculations
3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective
More informationRarely used, problems with unbalanced loads.
THREE-PHASE TRANSFORMERS Transformers used in three-phase systems may consist of a bank of three single-phase transformers or a single three-phase transformer which is wound on a common magnetic core.
More informationThree Phase Transformers
Three Phase Transformers Theory and Calculations 8/29/2016 Copyright 2016 Dan Dudley & Associates Page 1 DELTA Transformer 8/29/2016 Copyright 2016 Dan Dudley & Associates Page 2 WYE Transformer 8/29/2016
More informationMV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer
PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with
More informationR Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data
Distribution Transformers Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections R201-90-2 Reference Data CONTENTS POPULAR DlSTRIBUTlON TRANSFORMER AND CIRCUIT VOLTAGES... 1 2400-Volt Systems
More informationHPS Universal BUCK-BOOST TRANSFORMERS
BUCK-BOOST TRANSFORMERS Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
More informationShort-Circuit Current Calculations
Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.
More informationUnit 29 Three-Phase Transformers
Unit 29 Three-Phase Transformers Objectives: Discuss the construction of three-phase transformers. Discuss the formation of a three-phase transformer bank. Discuss primary and secondary connections. Objectives:
More information86 chapter 2 Transformers
86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More information12.6 Delta Phase versus Line Current
Unit 12 Delta/Delta and Delta/Wye Transformers Electrical NEC Exam Preparation 12.6 Delta Phase versus Line Current Since each line conductor from a delta transformer is actually connected to two transformer
More informationPOWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS
POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS Juan Manuel Gers, PhD Protection coordination principles Relay coordination is the process of selecting settings that will assure that the relays
More informationShort Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More informationECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 22 1 Today Homework 5 questions Homework 6 discussion More on
More informationTab 8 Surge Arresters
s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationCapstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:
Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation
More information~=E.i!=h. Pre-certification Transformers
7 Transformers Section 26 of the electrical code governs the use and installations of transformers. A transformer is a static device used to transfer energy from one alternating current circuit to another.
More informationSECTION TRANSFORMERS
SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section
More informationUnit 27 Three-Phase Circuits
Unit 27 Three-Phase Circuits Objectives: Discuss the differences between threephase and single-phase voltages. Discuss the characteristics of delta and wye connections. Compute voltage and current values
More informationSection 2 Outdoor Voltage Transformers
Section 2 Outdoor Voltage Transformers GE Meter 130 Main St., Somersworth, NH 03878 USA & Canada: (800) 626-2004 Fax: (518) 869-2828; GE Worldwide: (518) 869-5555 2-1 120 V to 600 V BIL 10 kv Outdoor Voltage
More informationWESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)
WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices
More informationThe Variable Threshold Neutral Isolator (VTNI)
The Variable Threshold Isolator (VTNI) Installation Instructions INTRODUCTION The is designed specifically for installation between the primary neutral of a power utility distribution system and the secondary
More informationDesigning For a Critical Load using a Spot Network
This is a photographic template your photograph should fit precisely within this rectangle. Designing For a Critical Load using a Spot Network Tony Oruga, P.E. Product and Sales Manager Network Protectors
More informationNotes 1: Introduction to Distribution Systems
Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission
More informationTECHNICAL BULLETIN 004a Ferroresonance
May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques
More informationUnit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21
Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive
More informationOPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES
OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES U AJMAL, GE Grid Solutions UK Ltd, usman.ajmal@ge.com S SUBRAMANIAN, GE Grid Solutions UK Ltd, sankara.subramanian@ge.com H Ha GE Grid Solutions
More informationPreface...x Chapter 1 Electrical Fundamentals
Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5
More informationMILWAUKEE SCHOOL OF ENGINEERING LABORATORY SESSION 4 THREE PHASE TRANSFORMERS
LABORATORY SESSION 4 THREE PHASE TRANSFORMERS PURPOSE To investigate the three phase transformer connections and characteristics DISCUSSION Most electrical energy is generated and transmitted using three
More informationAlternator winding pitch and power system design
Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering
More informationFigure 1. Two- and Three-phase MagneX Interrupter.
Fusing Equipment Two- & Three-Phase MagneX Interrupter Electrical Apparatus 2-33 General The Cooper Power Systems MagneX Interrupter is an overcurrent protective device that protects distribution transformers
More informationChapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math
Chapter 1 Electrical Theory and Code Questions 1 Unit 1 Electrician s Math and Basic Electrical Formulas 3 Part A Electrician s Math 3 1 1 Fractions 3 1 2 Kilo 4 1 3 Knowing Your Answer 4 1 4 Multiplier
More informationMV network design & devices selection EXERCISE BOOK
MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester
More information148 Electric Machines
148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional
More informationTwo- and three-phase MagneX interrupter
Fusing Equipment Catalog Data CA132017EN Supersedes 2-33 July 2011 COOPER POWER SERIES Two- and three-phase MagneX interrupter General Eaton protects distribution transformers from damaging overloads and
More informationWAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)
WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) 1 PART 1: GENERAL This section describes materials and installation requirements for low voltage
More informationBrown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS
SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600
More informationThe Effect of Various Types of DG Interconnection Transformer on Ferroresonance
The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:
More informationFERRORESONANCE SIMULATION STUDIES USING EMTP
FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in
More informationFerroresonance on Transformer 13-kV Ungrounded Tertiary at Arab
Ferroresonance on Transformer 13-k Ungrounded Tertiary at Arab Gary L. Kobet, P.E. Tennessee alley Authority In October 1997, at TA s Arab AL 161k Substation, a distributor built a 13k switchyard to load
More informationPrimary Metering. What is Primary Metering?
NWEMS Primary Metering August 22, 2018 Bill Unbehaun, Tacoma Power Exchanging Expertise Since 1893 What is Primary Metering? Metering energy flow past a point at high voltage above 600v Both PTs and CTs
More informationEffects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More informationIndustrial Electrician Level 3
Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide
More informationOpen-Delta Systems Affect Variable Frequency Drives
Open-Delta Systems Affect Variable Frequency Drives To avoid premature drive failure, proper precautions must be taken when installing VFDs on open-delta supplies. Written by: Dan Peters, Yaskawa America,
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationthepower to protect the power to protect i-gard LITERATURE Low and medium voltage
thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors
More informationProtection of Electrical Networks. Christophe Prévé
Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé
More informationCahier technique no. 212
Collection Technique... Cahier technique no. 212 The neutral: A live and unique conductor J. Schonek Building a ew Electric World "Cahiers Techniques" is a collection of documents intended for engineers
More informationModelling Parameters. Affect on DER Impact Study Results
Modelling Parameters Affect on DER Impact Study Results Agenda Distributed Energy Resources (DER) Impact Studies DER Challenge Study Steps Lessons Learned Modeling Reverse Power Transformer Configuration
More informationINTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...
INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...xv UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1
More informationNeed for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design
IEEE PES Transmission and Distribution Conference 2008 Panel Session Large Wind Plant Collector Design Wind Farm Collector System Grounding by Steven W. Saylors, P.E. Chief Electrical Engineer Vestas Americas
More informationSingle-Phase Transformation Review
Single-Phase Transformation Review S T U D E N T M A N U A L March 2, 2005 2 STUDENT TRAINING MANUAL Prerequisites: None Objectives: Given the Construction Standards manual and a formula sheet, you will
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationVoltage Regulation. 5.1 Voltage Standards
5 Voltage Regulation One of a utility s core responsibilities is to deliver voltage to customers within a suitable range, so utilities must regulate the voltage. On distribution circuits, voltage drops
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection
More informationwww. ElectricalPartManuals. com Type CGR Ratio Ground Relay Descriptive Bulletin Page 1
November, 1981 New nformation Mailed to: E,D,C/211, 219/DB Westinghouse Electric Corporation Relay-nstrument Division Coral Springs, FL 65 Page 1 Type CGR Ratio Ground Relay "" Page 2 Application Three
More informationConnection Impact Assessment Application
Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,
More informationTHREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA
THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA Witnessed by: Jim Phillips, PE, Consultant Craig DeRouen, ERMCO Director
More informationAC Power Instructor Notes
Chapter 7: AC Power Instructor Notes Chapter 7 surveys important aspects of electric power. Coverage of Chapter 7 can take place immediately following Chapter 4, or as part of a later course on energy
More informationFerroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions
Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR
More informationTransformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications
Electrical Power Systems PSL2 Investigates the principles and operating characteristics of single-phase and three-phase power and distribution transformers Key Features Educational transformers with fully
More informationSHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS
SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS Introduction Shunt capacitor units are typically used to deliver capacitive reactive compensation or power factor correction. The use of shunt capacitor
More informationEarthing Guidance Notes
Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head
More informationVoltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority
Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority S. Songsiri * and S. Sirisumrannukul Abstract This paper presents an application
More informationGENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW
GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW Electric Utility Contact Information DTE Energy Interconnection Coordinator One Energy Plaza, SB
More information35 kv Class M.O.V.E. DirectConnect elbow arrester
Surge Arresters Catalog Data CA235026EN Supersedes November 2015 COOPER POWER SERIES 35 kv Class M.O.V.E. DirectConnect elbow arrester General Eaton's Cooper Power series M.O.V.E. DirectConnect elbow arrester
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON Transformers Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer
More informationBE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %
BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and
More informationDP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation
DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase
More informationThe Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.
The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why
More informationArticle 225: Outside Branch Circuits And Feeders
Part C: Code Book Questions Article 225: Outside Branch Circuits And Feeders 1.! Open (individual) aerial overhead conductors shall be insulated or covered when within! feet of a building.! (a) 10! (c)
More informationEarth Fault Protection
Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationPacific Crest Transformers
April 2013 Multi-voltage Testing Transformers Anyone familiar with Pacific Crest Transformers is aware that the company offers a wide range of specialty transformers to suit a host of load applications.
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationa) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.
ECET4520 Exam II Sample Exam Problems Instructions: This exam is closed book, except for the reference booklet provided by your instructor and one (8.5 x11 ) sheet of handwritten notes that may not contain
More informationSubstation applications
Substation applications To make it easy to choose the right for a protection application, the most typical applications are presented with the type of for them. Each sample application is presented by:
More informationGENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW
GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationElectrical Description
History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationOPTIMIZING MAINS IMPEDANCE: REAL WORLD EXAMPLES by Judith M. Russell Consulting Electrical Engineer PowerLines
by Judith M. Russell Consulting Electrical Engineer PowerLines Introduction Power Quality has historically been quantified in terms of voltage. Metering equipment measures RMS voltage level, voltage sags
More informationNew Methods to Mitigate Distribution System Harmonics
Alberta Power Industry Consortium 214 Power & Energy Innovation Forum New Methods to Mitigate Distribution System Harmonics By Wilsun Xu Power Disturbance & Signaling Research Lab November 5, 214 Outline
More informationTransformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications
The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of
More informationUNBALANCED CURRENT BASED TARRIF
UNBALANCED CURRENT BASED TARRIF Hossein ARGHAVANI Tehran Electricity Distribution (TBTB) Co.-Iran hosein.argavani@gmail.com ABSTRACT The voltage ¤t unbalance are serious power quality problems with
More informationVariable Transformers Product Design & Engineering Data
Variable Transformers Product Design & Engineering Data Product Design & Engineering Data Type 1010B Cutaway General Information STACO ENERGY PRODUCTS CO. is a leading manufacturer of variable transformers,
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More information