Article 225: Outside Branch Circuits And Feeders

Size: px
Start display at page:

Download "Article 225: Outside Branch Circuits And Feeders"

Transcription

1 Part C: Code Book Questions Article 225: Outside Branch Circuits And Feeders 1.! Open (individual) aerial overhead conductors shall be insulated or covered when within! feet of a building.! (a) 10! (c) 15! (b) 12! (d) 25 2.! Conductors for festoon lighting shall be of the type, unless supported by messenger wires.! (a) thermoplastic! (c) #12 or larger! (b) rubber covered! (d) all of these 3.! What is the minimum size conductor (AWG) that may be used for an overhead feeder which is 35! feet in length from a residence to a remote garage?! (a) #10 copper! (c) #6 copper! (b) #8 copper! (d) #4 copper 4.! Messenger wires used to support festoon wiring shall not be attached to any.! (a) downspout! (c) plumbing equipment! (b) fire escape! (d) all of these 5.! Running open wiring on insulators, MI or MC cable, messenger-supported wiring, conductors in! raceway, and other approved means on the outdoor building surfaces is permitted for circuits! operating at a maximum of volts nominal.! (a) 600! (c) 1000! (b) 750! (d) ! Open conductors shall be supported on glass, porcelain-knobs, or.! (a) racks! (c) strain insulators! (b) brackets! (d) all of these 7.! Conductors on poles shall have a separation of not less than feet where not placed on racks! or brackets.! (a) 1! (c) 2! (b) 1-1/2! (d) 2-1/2

2 8.! For open conductors of not over 600 volts, clearance from ground shall be feet, above! finished grade where the supply conductors have a nominal voltage limited to 150 volts to ground! and accessible to pedestrians only.! (a) 8! (c) 12! (b) 10! (d) 15 9.! Distances from signs, radio, and TV antennas, tanks or other non-building or non-bridge! structures, clearances, vertical, diagonal and horizontal, shall not be less than feet.! (a) 2! (c) 6! (b) 3! (d) 8 10.!Where buildings exceed 3 stories or 50 feet in height, overhead lines shall be arranged, where! practicable, so that a clear space (or zone) of at least feet wide will be left either adjacent to! the buildings or beginning not over 8 feet from them to facilitate the raising of ladders when! necessary for fire fighting.! (a) 4! (c) 8! (b) 6! (d) !Raceways on the exterior of buildings shall be in wet locations.! (a) watertight and arranged to drain!! (c) arranged to drain and raintight! (b) weatherproof and covered!! (d) rainproof and guarded 12.!Where outdoor lampholders, attached to pendants, have terminals that puncture the insulation! and make contact with the conductors they shall be attached only to.! (a) conductors with rubber insulation!! (c) conductors of the stranded type! (b) solid conductors!! (d) a #12 conductor 13.!Locations of lamps for outdoor lighting shall be generally below.! (a) all energized conductors! (c) electric utilization equipment! (b) transformers! (d) all of these 14.!Vegetation such as trees shall not be used for support of.! (a) lighting fixtures! (c) overhead conductor spans! (b) brackets or clamps! (d) all of these

3 15.!In general, each building, or set of buildings on a single property shall be supplied by only one set! of feeder or branch circuit conductors?! (a) one! (c) three! (b) two! (d) three or more Article 230: Services 16.!Service conductors supplying a building or other structure pass through the interior of! another building or structure.! (a) shall! (c) may! (b) shall not! (d) may not 17.!Conductors shall be considered outside a building.! (a) where installed beneath a building in conduit under at least 18 of earth! (b) where installed beneath a building incased in concrete, or brick, at least 2 thick! (c) where installed within a building incased in concrete, or brick, at least 2 thick! (d) all of these 18.!Conductors other than service conductors shall not be installed in the same service raceway or! service cable except.! (a) grounding conductors! (c) load management control conductors! (b) bonding conductors! (d) all of these 19.!Service conductors run above the top level of a window shall be permitted to be less than the! foot requirement.! (a) 3! (c) 8! (b) 6! (d) !Overhead service-drop conductors run individually shall be.! (a) insulated! (c) bare (for grounded multiconductor cables)! (b) covered! (d) all of these 21.!Overhead service-drop conductors shall have.! (a) adequate mechanical strength! (b) sufficient ampacity to carry the load! (c) computed in accordance with Article 220! (d) all of the above

4 22.!Overhead service-drop conductors supplying only limited loads of a single branch circuit shall not! be smaller than copper.! (a) #8! (c) #12! (b) #10! (d) #14 23.!What is the minimum height of a service drop attachment to a building?! (a) 8 feet! (c) 12 feet! (b) 10 feet! (d) 15 feet 24.!A service drop over a residential driveway shall have a minimum height of feet.! (a) 10! (c) 15! (b) 12! (d) !The minimum clearance for service drops over commercial areas subject to truck traffic is! feet.! (a) 10! (c) 15! (b) 12! (d) !Where a service mast is used for the support of service drop conductors it shall be of adequate! strength or be supported by.! (a) studs! (c) rigid conduit! (b) braces or guys! (d) R.C. beams 27.!Where raceway-type service masts are used all raceway fittings shall be for use with service! masts.! (a) identified! (c) heavy-duty! (b) approved! (d) none of these 28.!A uninsulated copper grounded conductor can be used in an underground service.! (a) where used in a raceway! (b) directly buried where judged suitable for soil conditions! (c) directly buried where part of cable assembly identified for underground use! (d) all of the above 29.!Underground service conductors must have a rating not smaller than AWG.! (a) #3 aluminum! (c) #6 copper! (b) #4 aluminum! (d) #8 copper

5 30.!Buildings of multiple occupancy shall be permitted to have set of service-entrance! conductors for each service of different characteristics run to each occupancy or group of! occupancies.! (a) one! (c) two or more! (b) two! (d) no 31.!Service entrance cables where subject to physical damage shall be protected in.! (a) EMT! (c) Rigid Metal Conduit! (b) IMC! (d) all of these 32.!Service cables mounted in contact with a building shall be supported at intervals not exceeding! feet.! (a) 2-1/2! (c) 4-1/2! (b) 3! (d) !Open individual service conductors in wet locations, maximum 600 volts, supported every!9 feet! should have a minimum clearance between conductors of.! (a) 2-1/2! (c) 6! (b) 3! (d) !Service heads for service conductors shall be.! (a) raintight! (c) rainproof! (b) weatherproof! (d) watertight 35.!Where it is impracticable to locate the service head above the point of attachment the service head! location shall be permitted no further than feet from the point of attachment?! (a) 1! (c) 3! (b) 2! (d) 4 36.!To prevent the entrance of service-entrance conductors shall be connected to the service-! drop conductors (1) below the level of the termination of the service head, or (2) below the level of! the service head.! (a) air! (b) dirt! (c) dust! (d) moisture 37.!The Code has assigned the color to the high-leg of a 4-wire delta connected secondary.! (a) black! (c) orange! (b) red with green tracer! (d) pango pink

6 38.!Which of the following is not considered service equipment:! (a) meter socket enclosure! (c) panelboard! (b) service disconnecting means! (d) all of these 39.!The service disconnecting means shall be installed at a readily accessible location either outside of! a building or structure, or of the service conductors.! (a) inside nearest the point of entrance!! (c) inside within 8 feet! (b) in an inside bathroom!! (d) nearest the point of entrance 40.!Two or three single-pole switches or breakers, capable of individual operation, shall be permitted! on multiwire circuits, one pole for each ungrounded conductor, as one multipole disconnect,! provided they are equipped with handle ties, or a master handle to disconnect all conductors of! the service with no more than operations of the hand.! (a) one! (c) four! (b) two! (d) six 41.!Each service disconnecting means shall disconnect all ungrounded service conductors from! the premises wiring system.! (a) automatically! (c) simultaneously! (b) independently! (d) separately 42.!The service disconnecting means shall plainly indicate.! (a) its voltage rating! (c) the maximum fuse size! (b) the maximum horsepower rating! (d) whether it is in the open or closed position 43.!For an installation consisting of not more than two 2-wire branch circuits, the service! disconnecting means shall have a rating of not less than amperes.! (a) 20! (c) 60! (b) 30! (d) !For a one-family dwelling, the service disconnecting means shall have a rating of not less than! amps, 3-wire.! (a) 15! (c) 60! (b) 30! (d) 100

7 45.!The service conductors shall be connected to the service disconnecting means by or other! approved means.! (a) pressure connectors! (c) other approved means! (b) clamps! (d) all of these 46.! may be connected to the supply side of service disconnect.! (a) Meters! (c) Solar photovoltaic systems! (b) Current-limiting devices! (d) all of these 47.!Where the service overcurrent devices are locked or sealed, or otherwise not readily accessible,! branch-circuit overcurrent devices shall be.! (a) of lower ampere rating than the service overcurrent device! (b) mounted in an readily accessible location! (c) installed on the load side! (d) all of these 48.!Where necessary to prevent, an automatic overcurrent device protecting service conductors! supplying only a specific load, such as a water heater, shall be permitted to be locked or sealed! where located so as to be accessible.! (a) tripping! (c) heat build up! (b) corrosion! (d) tampering 49.!Ground-fault protection of equipment shall be provided for solidly grounded wye electrical! services of more than 150 volts to ground, but not exceeding 600 volts phase-to-phase, for each! service disconnecting means rated amperes or more.! (a) 200! (c) 800! (b) 600! (d) !The maximum setting of the ground-fault protection for a service disconnect shall be 1200! amperes, the maximum time delay shall be for ground-fault currents equal to or greater than! 3000 amperes.! (a) 1/2 second! (c) 3 seconds! (b) 1 second! (d) 100 milliseconds 51.!The ground fault protection system shall be performance tested when it is.! (a) first installed! (c) inspected! (b) energized for the first time! (d) manufactured

8 52.!Ground-fault protection that functions to open the service disconnect protection from faults! on the line side of the protective element.! (a) affords! (c) serves as! (b) affords no! (d) gives adequate 53.!Service conductors on a 600 volt system shall not be smaller than unless in multiconductor! cable.! (a) #6! (c) #2! (b) #4! (d) #1 54.!Isolating switches, over 600 volts, shall be provided with a means for readily connecting the load! side conductors to ground when disconnected from the.! (a) current! (c) service cable! (b) equipment! (d) source of supply 55.!A circuit breaker with a trip setting of not more than times the ampacity of the conductors,! shall be considered as providing the required short-circuit protection.! (a) 3 times! (c) 6 times! (b) 5 times! (d) 8 times Article 240: Overcurrent Protection 56.!Conductor overload protection is not required if.! (a) the conductors are oversized by 125%! (b) the conductors are part of a limited-energy circuit! (c) interruption of the circuit can create a hazard! (d) short circuit protection is provided 57.!If the allowable current carrying capacity of a conductor does not correspond to the rating of a! standard size overcurrent device, the next larger size may be used provided the current does not! exceed amps.! (a) 200! (c) 800! (b) 500! (d) !A #16 fixture wire is considered protected by a 20 amp overcurrent device up to feet.! (a) 25! (c) 75! (b) 50! (d) 100

9 59.!Field assembled flexible cords shall be considered as protected by a 20 amp branch circuit breaker! if it is.! (a) not less than 6 in length! (c) #18 AWG or larger! (b) #20 AWG or larger! (d) #16 AWG or larger 60.!Which of the following is not a standard size fuse?! (b) 601 amp! (a) 110 amp! (d) 125 amp! (c) 75 amp 61.!Which of the following is a standard size fuse?! (a) 75! (c) 601! (b) 95! (d) !The rating of an adjustable trip circuit breaker having means for adjusting the current setting! (long-time pickup setting) shall be the maximum setting possible.! (a) external! (c) readily accessible external! (b) an isolated! (d) accessible 63.!Fuses, circuit breakers, or combinations thereof, shall not be connected in parallel except.! (a) field installed! (b) readily accessible! (c) factory-assembled in parallel, and listed as a unit! (d) all of these 64.!Supplementary overcurrent devices shall.! (a) not be required to be readily accessible! (b) be used as a substitute for branch-circuit overcurrent devices! (c) be readily accessible! (d) rated not over 15 amp 65.!A fuse or an overcurrent trip unit of a circuit breaker shall be connected in series with! each.! (a) ungrounded conductor! (c) overcurrent device!! (b) grounded conductor! (d) transformer

10 66.! devices that provide equivalent overcurrent protection in closed-loop power distribution! systems shall be permitted as a substitute for fuses or circuit breakers.! (a) Approved! (c) Accessible! (b) Listed! (d) Automatic 67.!A feeder tap in a raceway terminating in a single circuit breaker with an ampacity 1/3 of the! feeder conductors may extend not over feet.! (a) 6! (c) 25! (b) 10! (d) !Where a change occurs in the size of the ungrounded conductor, a similar change shall be! permitted in the size of the conductor.! (a) hot! (c) grounded! (b) grounding! (d) none of these 69.!In dwelling units and guest rooms of hotels and motels overcurrent devices shall not be located! in.! (a) bathrooms! (c) were exposed to physical damage! (b) clothes closets! (d) all of these 70.!Overcurrent devices shall be enclosed in.! (a) cabinets! (c) equipment assemblies! (b) cutout boxes! (d) all of the above 71.!Enclosures for overcurrent devices in damp or wet locations shall be identified for use in such! locations and shall be mounted so there is at least inch air space between the enclosure and! the wall.! (a) 1/4! (c) 3/4! (b) 3/8! (d) 1 72.!Fuses and circuit breakers shall be so located or that persons will not be burned or! otherwise injured by their operation.! (a) concealed! (c) shielded! (b) guarded! (d) elevated

11 73.!Handles or levers of circuit breakers and similar parts which may move suddenly in such a way! that persons in the vicinity are likely to be injured by being struck by them shall be.! (a) concealed! (c) isolated! (b) labeled! (d) all of these 74.!Plug fuses and fuseholders can be used in circuits supplied by a system having a grounded! neutral where the line-to-neutral voltage does not exceed volts.! (a) 150! (c) 115! (b) 125! (d) !Plug fuses of 15-ampere and lower rating shall be identified by a configuration.! (a) octagonal! (c) hexagonal! (b) square! (d) round 76.!The maximum rating of an Edison-Base plug fuse is amperes, and shall be used only as a! replacement item in existing installations.! (a) 20! (c) 60! (b) 30! (d) !Fuses shall be plainly marked with.! (a) ampere rating! (c) interrupting rating where other than 10,000 amps! (b) voltage rating! (d) all of these 78.!A circuit breaker shall be of such design that any alteration of its will require dismantling of! the device or breaking of a seal for other than intended adjustments.! (a) trip point! (c) calibration! (b) time required for its operation! (d) all of these 79.!Every circuit breaker having an interrupting rating other than amperes, shall have its! interrupting rating shown on the circuit breaker.! (a) 1000! (c) 5000! (b) 2000! (d) !Where used as switches in 120 volt and 277 volt fluorescent lighting circuits, circuit breakers shall! be listed and shall be marked.! (a) SWD! (c) ULD! (b) UL! (d) any of these

12 81.!A two pole circuit breaker that may be used for protecting a 3-phase corner grounded delta circuit! if it is marked to indicate such suitability.! (a) 1Ø, 120/240v! (c) 1Ø/2Ø/3Ø! (b) 1Ø - 3Ø! (d) 480Y/277v 82.!The protective devices(s) shall be capable of detecting and interrupting all values of current which! can occur at their location in excess of their trip setting or.! (a) boiling point! (c) capacity! (b) melting point! (d) all of these 83.!The long-time trip element setting of a breaker or the minimum trip setting of an electronically! actuated fuse shall not exceed times, the ampacity of the conductor.! (a) 3! (c) 6! (b) 4! (d) 8

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection

More information

Journeyman's Practice Exam

Journeyman's Practice Exam Journeyman's Practice Exam [Time limit 4.0 hrs.] (The test is open book. I've started at the front of the Code Book and worked toward the back for instructional purposes. The real test will not be in order

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

2017 NEC TABLE OF CONTENTS

2017 NEC TABLE OF CONTENTS Article 90 Introduction 90.1 Purpose (A) Practical Safeguarding (B) Adequacy (C) Relation to Other International Standards 90.2 Scope (A Covered (B) Not Covered (C) Special Permission 90.3 Code Arrangement

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 200-215.3 CHANGES FROM 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 200 Use and Identification of Grounded Conductors 200.2 General Grounded Conductors

More information

Electrical Wiring: Commercial, Seventh Canadian Edition

Electrical Wiring: Commercial, Seventh Canadian Edition Electrical Wiring Commercial Canadian 7th Edition Mullin SOLUTIONS MANUAL Full download at: https://testbankreal.com/download/electrical-wiring-commercialcanadian-7th-edition-mullin-solutions-manual/ Unit

More information

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5 Applied Grounding and Bonding Paul Dobrowsky Member NEC Panel 5 1 Introduction This presentation is a representative sample from the following Chapters of Applied Grounding and Bonding. Chapter 1, Introduction

More information

Article 250 Grounding & Bonding

Article 250 Grounding & Bonding Article 250 Grounding & Bonding AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Dr. Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER NOTE: This course is APPROVED for continuing education

More information

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING 1 1 1 1 1 NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING NORTH CAROLINA BUILDING CODE COUNCIL Notice of Rule-making Proceedings is hereby given by NC Building Code Council in accordance with G.S.

More information

2014 NEC Changes Part 1

2014 NEC Changes Part 1 www.garyklinka.com Page 1 of 8 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL PROVINCE.OF BRITISH COLUMBIA ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL Order in Council No. 0640 Approved and Oidered a -1.1995 cieuisvunigott3mor Executive Council Chambers, Victoria On the recommendation

More information

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56 1. Two Electrical Technicians are discussing markings that are required for AC wiring. Tech A says that AC conductors must be rated for 600 volts and must have their jackets and individual conductors marked

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions conduit? 9/8/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Can branch circuits of different services be installed in the same Yes, see 300.3(C)(1) for conductors of different systems

More information

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33 Part VIII Electrical CHAPTER 33 GENERAL REQUIREMENTS < SECTION E3301 GENERAL E3301.1 Scope. The installation of electrical systems, equipment and components indoors and outdoors that are within the scope

More information

A. Product Description: Stranded conductor insulated wire.

A. Product Description: Stranded conductor insulated wire. SECTION 16120CPPR CONDUCTORS AND CABLE PART 1 - GENERAL 1.1 SYSTEM DESCRIPTION A. Product Requirements: Provide products as follows: 1. All building wire shall be stranded copper (no aluminum wire). 2.

More information

1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights

1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights 1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights These 1 Exam Prep Tabs are based on NFPA 70: National Electrical Code, 2011. Each 1 Exam Prep Tabs sheet has five rows of Tabs. Start

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

CHAPTER 2 Wiring and Protection. Article 200 Use and Identification of Grounded Conductors

CHAPTER 2 Wiring and Protection. Article 200 Use and Identification of Grounded Conductors ARTICLE 200 USE AND IDENTIFICATION OF GROUNDED CONDUCTORS 70 35 CHAPTER 2 Wiring and Protection Article 200 Use and Identification of Grounded Conductors 200-1. Scope. This article provides requirements

More information

A. Product Data: For each electrical identification product indicated.

A. Product Data: For each electrical identification product indicated. SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

B. Manufacturers: Square-D, G.E. or Westinghosue.

B. Manufacturers: Square-D, G.E. or Westinghosue. SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

INTELLIMETER REGISTER

INTELLIMETER REGISTER INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

Continued from Part 1 Rules 1 25.

Continued from Part 1 Rules 1 25. Continued from Part 1 Rules 1 25. 26 225.32 Disconnect Location The disconnecting means for a building or structure must be installed at a readily accessible location, either outside the building or structure

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings SOLAR MICROINVERTER/M STANDARD PLAN - COMPREHENSIVE Microinverter and M Systems for One- and Two- Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters or Modules

More information

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL BELL SYSTEM PRACTICES Plant Series SECTION 508-100-100 Issue 3, October 1970 AT&TCo Standard ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL I. GENERAL 1.01 This section is reissued to: Revise

More information

ECET Fall 2017 Name: _ Lab Assignment #01

ECET Fall 2017 Name: _ Lab Assignment #01 ECET 4520 - Fall 2017 Name: _ Lab Assignment #01 General Instructions: This assignment is to be completed individually. All answers/work required for each problem should be neatly written in the space

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

We have 3 ways to help you prepare

We have 3 ways to help you prepare P a g e 2 Texas Electrical Excel is your source for obtaining your license state exam. Call us if you have questions regarding your applications, exam preparation, exam registration and more. We have reached

More information

SECTION 5 TRANSFORMERS

SECTION 5 TRANSFORMERS SECTION 5 TRANSFORMERS Necessary transformers will be installed and maintained by The City of Aspen. The City of Aspen will not furnish transformers unless they are of standard size and voltage as established

More information

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes FINAL - ER 70 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.

More information

Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians.

Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians. Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians. The following test is for Continuing Education Credits for the abovementioned

More information

Page Electric Utility Service Specifications

Page Electric Utility Service Specifications T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum - UG-1 Sheet 1 of 3 87 T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum

More information

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS Residential Pool Permit Requirements FEES: A nonrefundable permit application fee of $25.25 and a nonrefundable plan review fee of $40.40 will be

More information

UNITY/I TM. Installation Manual. UT3K, UT4K, UT5K and UT8K. Single-Phase Uninterruptible Power Systems

UNITY/I TM. Installation Manual. UT3K, UT4K, UT5K and UT8K. Single-Phase Uninterruptible Power Systems UNITY/I TM UT3K, UT4K, UT5K and UT8K Single-Phase Uninterruptible Power Systems Installation Manual MLS-0351C-OL Copyright 1994-1997 Best Power. All rights reserved. å IMPORTANT SAFETY INSTRUCTIONS! SAVE

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 11 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // -- // if not applicable to project. Also delete any other item or paragraph

More information

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit. ECET4520 Exam II Sample Exam Problems Instructions: This exam is closed book, except for the reference booklet provided by your instructor and one (8.5 x11 ) sheet of handwritten notes that may not contain

More information

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition Jake Leahy s Electrical Code Connection A look at Grounding and Bonding of Electrical Services Article 250 2014 Florida Building Code 5 th Edition Wiring Integrity. Completed wiring installations shall

More information

Code Check Electrical is a field guide to common code issues in residential

Code Check Electrical is a field guide to common code issues in residential INTRODUCTION u CODES u ABBREVIATIONS Code 3Check Electrical 5th Edition By Redwood Kardon & DOUGLAS HANSEN Illustrations & Layout: Paddy Morrissey 2008 by The Taunton Press, Inc. ISBN 978-1-60085-012-7

More information

Customer Connection Guide Updates Effective May 2017

Customer Connection Guide Updates Effective May 2017 This document provides a list of the updates to the EPCOR Distribution and Transmission Inc. (EDTI) Customer Connection Guide. If you have any questions, please contact EDTI Customer Engineering Services

More information

RADIO AND TELEVISION SATELLITE EQUIPMENT

RADIO AND TELEVISION SATELLITE EQUIPMENT ARTICLE 810 RADIO AND TELEVISION SATELLITE EQUIPMENT Introduction to Article 810 Radio and Television Satellite Equipment This article covers transmitter and receiver (antenna) equipment and the wiring

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 13 DISTRIBUTION SWITCHBOARDS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Module 2 Unit 6, 7, 8

Module 2 Unit 6, 7, 8 Module 2 Unit 6, 7, 8 1. What is the definition of an ideal conductor? Material that will carry the greatest current with the lowest temperature rise 2. How much does copper weigh compared to aluminum?

More information

FTTH ENGINEERING AND INSTALLATION INTRODUCTION

FTTH ENGINEERING AND INSTALLATION INTRODUCTION 1 FTTH ENGINEERING AND INSTALLATION INTRODUCTION GROUNDING FTTH SYSTEMS AT THE HOME. By Dean Mischke, P.E., V.P. Grounding and bonding. Why are we worried about such an old school concept in the modern

More information

Department of Labor and Industry Electrical Licensing

Department of Labor and Industry Electrical Licensing Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

CATALOG OF PRODUCTS. Your Best Supplier of Electrical Cables

CATALOG OF PRODUCTS. Your Best Supplier of Electrical Cables CATALOG OF PRODUCTS Isolated Copper Wire THHN/MTW/THWN-2 600V, single conductor having flame-retardant and heat-resistant thermoplastic insulation with a jacket of extruded nylon or equivalent material.

More information

Grounding for Power Quality

Grounding for Power Quality Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states

More information

Residential Construction Checklist Single and Two Family Construction

Residential Construction Checklist Single and Two Family Construction DATE: _ Building Inspection Submittal Requirements Residential Construction Checklist Single and Two Family Construction Submit a City of Big Spring Permit Application, checklist, and 3 complete hard copy

More information

The Variable Threshold Neutral Isolator (VTNI)

The Variable Threshold Neutral Isolator (VTNI) The Variable Threshold Isolator (VTNI) Installation Instructions INTRODUCTION The is designed specifically for installation between the primary neutral of a power utility distribution system and the secondary

More information

SECTION BUILDING WIRE AND CABLE

SECTION BUILDING WIRE AND CABLE SECTION 260519 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wire and cable. 2. Wiring connectors and connections. B. RELATED SECTIONS 1. Section 26 05 53 Electrical Identification. 2. Section

More information

Electrical IP Red Seal Practice Exam

Electrical IP Red Seal Practice Exam Electrical IP Red Seal Practice Exam PRACTICE EXAM-3 1. What size 2 pole breaker must you use on a 3HP, 115V single phase motor? A. 40A B. 50A C. 80A. D. 100A. 2. An electrical equipment approved for use

More information

POWER SERVICE DETAILS

POWER SERVICE DETAILS POWER SOURCE # POLE MOUNTED SERVICE TRANSFORMER BY POWER HANDHOLE 0/0V, -PHASE, SERVICE CONDUCTORS; -# AWG SERVICE CONDUCTOR AND -# AWG GROUNDED SERVICE CONDUCTOR (NEUTRAL) SERVICE XFMR SECONDARY. A 0V

More information

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4 SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: 16.10 Document Number: KUCSH0039 Rev: 4 16.10.1 INTRODUCTION 16.10.1.1 The intent of this standard is to ensure that continuity

More information

6B.6 Substation Grounding

6B.6 Substation Grounding 1 No v 1 6 1 No v 1 6 Iu d a Mo r a r a n d ma n a g e r R a c h e le Ha n n o n Vo l.6 -S u b s ta tio n a n d Hig h Vo lta g e E q u ip me n t;p a r tb -S u b s ta tio n Co n fig u r a tio n s 1. Scope

More information

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION SECTION 16715 COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION PART 1 - GENERAL 1.01 SECTION DESCRIPTION AND BASIC REQUIREMENTS A. The Electrical Power Distribution System provides power distribution from

More information

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER GROUNDED ELECTRICAL POWER DISTRIBUTION Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER .0 Conductors for Electrical Power Distribution For single-phase transmission of AC power or

More information

Article 700: Emergency Systems. 2.! Audible and visual signal devices shall be provided, where practicable to indicate.

Article 700: Emergency Systems. 2.! Audible and visual signal devices shall be provided, where practicable to indicate. Part N: Code Book Questions Article 700: Emergency Systems 1.! For emergency systems, the authority having jurisdiction shall conduct or witness a test on the! complete system upon installation and periodically

More information

Electrical Occupations

Electrical Occupations Job Ready Assessment Blueprint Electrical Occupations Test Code: 3029 / Version: 01 Copyright 2011. All Rights Reserved. General Assessment Information Blueprint Contents General Assessment Information

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice

More information

Wiring Methods, Components, and Equipment for General Use -- OSHA Standard

Wiring Methods, Components, and Equipment for General Use -- OSHA Standard ABE285 Wiring Methods, Components, and Equipment for General Use -- OSHA Standard 1910.305 1 Carol J. Lehtola, Charles M. Brown, and William J. Becker 2 The Impact of Safety on Florida Agriculture Florida

More information

SECTION TRANSFORMERS

SECTION TRANSFORMERS SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section

More information

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP) Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.

More information

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv) Outdoor Transmission (69 kv through 230 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The circuit-switcher shall conform to the following specification. 1.02 The circuit-switcher shall be

More information

Steps for Selecting the Proper Transformer

Steps for Selecting the Proper Transformer SECTION I Page 4 Steps for Selecting the Proper Transformer SINGLE PASE LOADS 1. Determine electrical load A. Voltage required by load. B. Amperes or KVA capacity required by load. C. Frequency in z (cycles

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

ELPT 1429 RESIDENTIAL WIRING

ELPT 1429 RESIDENTIAL WIRING SYLLABUS ELPT 1429 RESIDENTIAL WIRING INDUSTRIAL AND COMMERCIAL ELECTRICITY BRAZOSPORT COLLEGE LAKE JACKSON TEXAS PREPARED BY: Larry Grable DATE: September 13, 2005 INSTRUCTOR RECOMMENDED BY: RECOMMENDED

More information

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents.

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. SECTION 26 05 19 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. 1.2 CONTRACTOR SUBMITTALS A. The

More information

GENERAL SUBSCRIBER SERVICES TARIFF Pembroke Telephone Company, Inc. Third Revised Contents Sheet 1 Cancels Second Revised Contents Sheet 1

GENERAL SUBSCRIBER SERVICES TARIFF Pembroke Telephone Company, Inc. Third Revised Contents Sheet 1 Cancels Second Revised Contents Sheet 1 GENERAL SUBSCRIBER SERVICES TARIFF Pembroke Telephone Company, Inc. Section N Third Revised Contents Sheet 1 Cancels Second Revised Contents Sheet 1 N. CONNECTION WITH CERTAIN FACILITIES AND/OR EQUIPMENT

More information

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102 G e m i n i high RESISTANCE GROUNDING SYSTEM the power to protect Instruction Manual C-102 HIGH RESISTANCE GROUNDING SYSTEM Gemini is a unique, fail safe, all-in-one neutral grounding system, combining

More information

TECHNICAL BRIEF North America

TECHNICAL BRIEF North America TECHNICAL BRIEF North America Planning for a Commercial IQ Microinverter System The Enphase IQ Microinverter system is inexpensive to install and provides a wide range of new installation options to solar

More information

Basic Information Required for Photovoltaic Plan Check Submittal *Informational Purposes Only* 2013 CEC

Basic Information Required for Photovoltaic Plan Check Submittal *Informational Purposes Only* 2013 CEC BUILDING AND SAFETY DIVISION 1685 MAIN STREET, SANTA MONICA, CA 90401 310-458-2201 Basic Information Required for Photovoltaic Plan Check Submittal *Informational Purposes Only* 2013 CEC ADMINISTRATIVE

More information

Education & Training

Education & Training Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through

More information

Short-Circuit Current Calculations

Short-Circuit Current Calculations Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.

More information

120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITS. Excerpt from G4 InverCharge Series Manual BY: VIJAY SHARMA ENGINEER

120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITS. Excerpt from G4 InverCharge Series Manual BY: VIJAY SHARMA ENGINEER 120 / 240 VC SILE SPLIT PHSE & MULTI-WIRE RCH CIRCUITS Excerpt from 4 InverCharge Series Manual Y: VIJY SHRM EIEER 120 / 240 VC SILE SPLIT PHSE & MULTI-WIRE RCH CIRCUITS i IFO For purposes of explaining

More information

St. Monica Food Pantry Low Voltage (600V and less) Conductors and Cables sys-tek No

St. Monica Food Pantry Low Voltage (600V and less) Conductors and Cables sys-tek No St. Monica Food Pantry 26 0519-1 ELECTRICAL WORK DIVISION 26 SECTION 260519 LOW VOLTAGE (600V AND LESS) PART 1. GENERAL 1.1 WIRES (SINGLE CONDUCTOR) AND CABLES (MULTI-CONDUCTOR ASSEMBLIES) USED FOR THE

More information

IC800SSD Hardware Manual Pub 348R5. for models. A publication of

IC800SSD Hardware Manual Pub 348R5. for models. A publication of IC800SSD Hardware Manual Pub 348R5 for models IC800SSD104S1A IC800SSD104RS1A IC800SSD107S1A IC800SSD107RS1A IC800SSD407RS1A IC800SSD216S1A IC800SSD216RS1A IC800SSD420RS1A IC800SSD228S1A IC800SSD228RS1A

More information

EFCOG BEST PRACTICE # 211. Best Practice Title: Managing Hazards of Multiwire Branch Circuits Installed Before the 2008 NEC

EFCOG BEST PRACTICE # 211. Best Practice Title: Managing Hazards of Multiwire Branch Circuits Installed Before the 2008 NEC EFCOG BEST PRACTICE # 211 Best Practice Title: Managing Hazards of Multiwire Branch Circuits Installed Before the 2008 NEC Facility: DOE Complex Point of Contact: John (Jackie) McAlhaney, Savannah River

More information

University of Central Florida Main Campus. Electric. Service and Meter Installations Requirements. Issued January 26 th, 2017.

University of Central Florida Main Campus. Electric. Service and Meter Installations Requirements. Issued January 26 th, 2017. University of Central Florida Main Campus Electric Service and Meter Installations Requirements Issued January 26 th, 2017 1 P a g e Table of Contents 1. GENERAL INFORMATION... 3 2. DEFINITIONS... 3 3.

More information

Lumewave and LumInsight IoT. Gateway and Base Station Installation Guide

Lumewave and LumInsight IoT. Gateway and Base Station Installation Guide Lumewave and LumInsight IoT Gateway and Base Station Installation Guide P/N 055-0121-01B 8/9/2018 Contents Installation Planning 3 Gateway Types 3 Gateways 4 Base Stations 4 Antenna Specification 4 Antenna

More information

3Ø Short-Circuit Calculations

3Ø Short-Circuit Calculations 3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

PLOT PLAN INSTRUCTIONS ROOF MOUNT SOLAR AN ACCURATE PLOT PLAN IS NECESSARY TO PROCESS YOUR PERMIT

PLOT PLAN INSTRUCTIONS ROOF MOUNT SOLAR AN ACCURATE PLOT PLAN IS NECESSARY TO PROCESS YOUR PERMIT PLOT PLAN INSTRUCTIONS ROOF MOUNT SOLAR Building Division 1855 Placer Street, Suite 102 Redding, California 96001 Phone: (530) 225-5761 Fax: (530) 245-6468 Inspection Request Line: (530) 244-5068 Web:

More information

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Chapter 6. WIRING SYSTEMS Safe Electrical Design Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

TABLE of CONTENTS ############################# Revised Rule Revised Rule 91.3-B 14. Revised Rule 92.1-F(2). 15

TABLE of CONTENTS ############################# Revised Rule Revised Rule 91.3-B 14. Revised Rule 92.1-F(2). 15 This document contains new GO 95 Rule 94 Antennas (currently pending in Proceeding R.05-02-023), proposed changes to Rule 94, and three associated rule changes developed by the GO 95 / 128 Rules Committee

More information

3.1 Overview of ATCO Electric s URD System Design

3.1 Overview of ATCO Electric s URD System Design Page: 3-1 3.0 URD DESIGN GUIDELINES 3.1 Overview of ATCO Electric s URD System Design ATCO Electric s design for distribution power supply to URD areas is a primary looped supply system. This is generically

More information

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of: 1 PAPER 5 Sample Questions A- C&G 2382 17th Edition Paper A 1 o/c1 BS 7671 does not apply to a equipment of aircraft b photovoltaic systems c marinas d fairgrounds. 2 o/c1 Where protection for persons

More information

Ground Fault Location. Turbo Sleuth. Instruction Manual

Ground Fault Location. Turbo Sleuth. Instruction Manual Ground Fault Location Turbo Sleuth Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR 737-4787 www.ipc-resistors.com

More information

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011 NATIONAL RULES FOR ELECTRICAL INSTALLATIONS Fourth Edition ET 101:2008 Extracts from Amendment No.1:2011 22 June 2011 Page vi: Insert after 1 st Paragraph: Section 710: Medical Locations was prepared by

More information

SECTION EQUIPMENT WIRING

SECTION EQUIPMENT WIRING PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 26 27 17 EQUIPMENT WIRING A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General Provisions,

More information

Ameritron RCS-10 INTRODUCTION

Ameritron RCS-10 INTRODUCTION Ameritron RCS-10 INTRODUCTION The RCS-10 is a versatile antenna switch designed for 50-ohm systems. It handles high power, and sealed relays offer excellent life and connection reliability. It requires

More information