CHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses

Size: px
Start display at page:

Download "CHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses"

Transcription

1 CHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses 8.1 Introduction The present level of Transmission and Distribution (T & D) losses in Indian power system is estimated to be 23%. The T& D losses in India is very high compared to the losses in the power systems of the developed countries like USA, Canada, USSR, Korea and Japan. The T & D losses in developed countries are as shown in the table 8.1. Table 8.1. T & D Losses in Developed Countries Sl.No Name of Country T & D Losses in % 1 USA 8.8% 2 Canada 8.5% 3 USSR 8.2% 4 Korea 11.0% 5 Japan 6.0% It has been reported that the losses in power system in Japan and Korea were also of the order of 20%. Adopting modern techniques of Distribution system planning and design, they have brought down the losses to the international level of 6 to 8%. There is a need to take up similar excises in respect of Indian power systems to reduce T & D losses, when the country is facing severe power shortages need to emphasis. The typical existing T & D losses break-up is shown in the Table 8.2. Table 8.2. T & D losses Break-up for Indian Power System Sl. No System Break-up of losses In % % of Contribution of each voltage level to total losses 1 EHV System 4.5% 19.6% 2 33 KV System 4.0% 17.4% 3 11 KV System 7.0% 30.4% 4 LV System 7.5% 32.6% Total Losses 23.0% 100.0% Source: 95

2 The 11KV HT Distribution System contributes about 30% of total T & D losses of Indian Power System. The main contributing factor for the losses in the area is the wrong HT Distribution system practice chosen by India coupled with non-adherence to prescribed norms of voltage drops. The 11KV HT Distribution system losses include the losses in 11KV/415 Volts Transformers and 11KV feeders Line Losses. Transformer is the most energy efficient equipment used in industry. The nominal efficiency of the power Transformer is in the order of 99 to 99.5% and for Distribution Transformer is in the order of 98 to 99% though the efficiency of Transformer is very high, it offers a good potential to save energy. An attempt was made to increase the operating efficiency of the Transformer by maintain the voltage profile, proper loading and power factor correction. In Tamilnadu Electricity Board (TNEB) power supply, 11KV HT Distribution voltage varies from Peak to off-peak periods. The voltage variation is due to Demand variation and reactive power variation. To establish the voltage variations, an 11KV HT Distribution feeder named Airport Feeder is taken as sample feeder for analysis purpose and Feeder Voltage are measured in Four Locations. The Airport feeder receives power from an 110KV/11KV 20MVA Sub-station located at a place called Pykara. The approximate length of the Feeder is 5.4 Kilometres. The Airport feeder is a radial feeder and meets a demand of approximately 5MVA during peak hours and 1MVA demand during off-peak hours. The feeder consists of various types of loads like domestic, Institution, industrial and commercial loads. The 11KV HT Distribution feeder Voltage was recorded for 24Hours in four different locations of equal distance at 11KV/433 Volts Distribution Transformer end and the effect of voltage variation on the Distribution Transformer losses and efficiency was studied and concluded. 8.2 Transformer Losses The Transformer losses are mainly governed by the input supply voltage, load factor and power factor of load. Transformer losses are classified as core and copper losses Core Loss Core loss is voltage dependent loss and increase exponentially with respect to voltage. It is associated with power consumed to sustain the magnetic field in the Transformer s steel core, whenever the Transformer energized. Core losses are caused by two factors; Hysteresis and eddy 96

3 current losses. Hysteresis loss is energy loss, last due to reversing the magnetic field in the core as the magnetizing alternating current rises and falls in reverse direction. Eddy current loss is result of induced currents circulating in the core. Total core loss is given by, P c = P e + P h Core loss remains constant and is independent of the load. Figure 8.1. Shows Per unit variation of Core loss with respect to per unit HT input voltage for Distribution Transformer. HT voltage Vs core loss Core loss (pu) HT Voltage (pu) Figure 8.1. Per Unit Variation of Core Loss with respect to Per Unit of HT input voltage Courtesy : Indo-tech Transformers Limited, Chennai, India Copper Loss Copper loss is also called load loss and is associated with full load current flow in the Transformer windings. Copper loss is power lost in primary and secondary windings of a Transformer due to ohmic resistance of the windings. The typical loss values of 11KV / 433 V Distribution Transformers are shown in the Table

4 Table 8.3. Typical Loss values of 11KV/433V Distribution Transformers Transformer Capacity in KVA Iron Loss in Full Load Copper Loss in Courtesy : Indo-tech Transformers Limited, Chennai,India 8.3 Voltage Fluctuation Control in Transformer It is necessary to keep the power supply voltage close to the rated voltage, by using voltage control techniques. Whenever the supply voltage is less than the Rated value there is a chance of nuisance tripping of voltage sensitivity devices. The voltage control is achieved by performing tap changing in Transformer. There are two types of tap-changers. One is called as onload tap changer (OLTC) and another is called as Off-load tap changers Off-load tap changer It is a device fitted in the Distribution Transformer, which is used to vary the voltage transformation ratio. In this type the output voltage can be varied only after isolating the Transformer from power supply. This type of tap changer is commonly used in Distribution Transformer used by TNEB On-load tap changer The voltage levels can vary online with the help of OLTC facility without isolating the connected load to the Transformer to minimize the magnetization losses and to reduce the nuisance tripping. In general, Power Transformers in major sub-stations are provided with OLTC facility. The down stream Distribution Transformers can be provided with off circuit tap changer. 98

5 The on load tap changer can be put in auto mode or manual mode depending on the requirement. The industries availing power supply at 11KV level, preferred to select OLTC for their Distribution Transformers to maintain the LT output voltage constant irrespective of their utility grid voltage variations. The use of OLTC to maintain the LT voltage at constant level helps majority of the industries to minimize energy consumption, by avoiding over voltage during off-peak hours. The OLTC provision in Distribution Transformer is helpful to optimize the LT voltage based on load factor of Induction motor. In State Electricity Board, installing Distribution Transformer with OLTC provision become expensive and requires a little bit increase in maintenance requirements. However the necessity of OLTC below 1000 KVA can be considered after calculating the cost economics. The line drop compensation technique is used to adjust the tap position automatically to maintain the voltage in feeder end in power Transformer with OLTC facility. 8.4 Voltage Variation in 11KV HT Distribution Feeder The 11KV HT Distribution feeder Voltage of State Electricity Board varies from Peak hours to Off-peak hours in a day. Before implementation of ABT, the peak hours HT Distribution voltage goes below 11KV and typical value is 10.2 to 10.8KV at feeder ends. After implementation of ABT, the peak hour s voltage is close to 11KV. But during off-peak hours, the voltage rise to the level of 11.4 to 11.6 KV even at feeder end. The Voltage profile of 11KV HT Distribution system was recorded with the help of Hioki Make Power Quality Analyser in four different locations of 11KV/433 Volts Distribution Transformers and recorded voltage profile data are used to analyse the energy saving purpose. The HT Distribution feeder voltage was first sampled (Sample 1) at an 11KV/433 Volts Distribution Transformer located close to the main 110KV / 11KV 20MVA substation (Pykara Substation) feeding point. The HT Distribution Voltage was second sampled at 1.8 Kilometres away (Pasumalai) from the feeding point. The HT Distribution feeder voltage was third sampled at 3.6 Kilometres away (Thiagarajar College of Engineering) from feeding point. The HT Distribution feeder voltage was fourth sampled at 4.8 Kilometres away (Feeder End point) from feeding point. Figure 8.2 shows all the four HT Distribution feeder voltage samples recorded for 24 Hours in a day at four different locations of Distribution Transformer end. 99

6 Combination of all voltage samples pm HT voltage (kv) time Figure KV HT Distribution Feeder Voltage Samples Profiles Figure 8.2. Shows that majority of the time the 11KV Distribution feeder voltage is above 11.2KV. The feeder voltage varies form 10.8 KV to 11.8 KV. In all samples it s observed that the voltage varies in the band between 11.6 KV and 11.4 KV occurs 65% of time in a day (During Offpeak Hours and Normal Hours). During Peak Hours and part of Normal Hours the voltage varies between 10.8 and 11.4 KV and occurs for 35% of time in a day. After the implementation of Available based Tariff in Indian Power System, the 11KV HT Distribution voltage varies from 11.2 to 11.8 KV even during peak hours (6.00 PM to 9.00 P.M). Before ABT implementation, the 110KV/11KV 20MVA Sub-station tries to maintain 11.4KV at Transformer on 11KV side in order to maintain the Feeder end voltage at 11KV. After the implementation of ABT, due to Reactive VAR compensation, the feeder drop has come down. There is a need to revise the sending end voltage of 11KV Feeder to 11.2 KV to minimize over voltage during off-peak hours. The occurrences of different voltage samples in % of time are shown in the Table

7 Table 8.3. Comparison of the Occurrences of Different Voltage Sample in % of Time Sample1 in % HT time Sample2 in % time Sample3 In % time Sample4 in % time voltage in Voltage Voltage Occurrence Voltage Occurrence Voltage Occurrence KV Occurrence Reasons for Wide Voltage Variation in 11KV HT Distribution System The major reasons for the wide voltage variation in 11KV HT Distribution System were investigated with the help of State Electricity Board Officials and observed the following reasons for the variations. Absence of OLTC Facility in 110 KV / 11KV Power Transformers / Sub-stations Non- Familiar about the reliability of On-load Tap Changing Gear Effect of Installation of Reactive VAR Compensator Effect of Power Factor Incentives to HT and LT Industries Absence of OLTC Facility Majority of the 110KV/11KV power Transformer installed after the year 1980 by state electricity boards are provided with On-Load Tap Changing (OLTC) gear Facility. But the 110KV/11KV power Transformer installed before the year 1980, are provided with off-load tap changers. In Power Transformers provided with off-load tap changing gears, to change the tap from one position to another position requires switching off the power supply and will disturb the operation of power system. Hence maintaining the HT Distribution voltage profile becomes a tough 101

8 task in Power Transformers with off-load Tap changing facility. The HT Distribution voltage can be maintained within the prescribed limit with the help of OLTC facility in power Transformers Reliability of OLTC The tap changers are designed for operations (to change one tap position to another tap position) during its meaningful life. After that the contacts are replaced to extend it life further. The State Electricity Board operating person feels that the frequent use of OLTC will increase the maintenance in state electricity board. But the cost of savings by maintaining the voltage profile to minimize the Distribution Transformer losses is huge compare to the maintenance cost of the power Transformers. This thesis work recommends utilizing the Automatic mode of operation of the OLTC to maintain feeder voltage during Off-peak hours Effect of Installation of Reactive VAR Capacitor After the implementation of Available based tariff in Indian power system, the state electricity board has taken measures to improve the power factor of the 11KV Distribution System by installing HT capacitors at every Distribution Transformer feeding end. This improves the power factor and minimizes the feeder drop Effect of Power Factor Incentives for HT and LT Industries After the implementation of Available based tariff, the HT industries are penalized when their power factor is below 0.9 Lagging and encouraged by incentives for maintaining power factor above 0.95 Lagging. Similarly the LT industrial units are penalized, when their power factor is below 0.85 Lagging and encouraged by incentives for maintaining power factor above 0.90 lagging. Initial period of power factor penalty and incentive schemes, the HT and LT industries tray to avoid the penalty, after an year majority of the HT and LT industries maintaining the power factor close to unity to avail full incentives. This improves the 11KV Distribution Feeder voltage and minimizes the voltage drop. 8.6 Effect of Automatic OLTC Performance A trail was conducted to record the voltage profile of an 11KV Distribution feeder voltage by putting the OLTC of the 110KV/11KV 20MVA Power Transformer (feeding Sub-station at Pykara) in automatic mode to maintain the voltage at 11.2 KV at the Transformer 11KV Side. The voltage 102

9 profile of the 11KV Distribution feeder is recorded at Sample point 4 (11KV HT Feeder End) for 24Hours in a day. The 11KV Distribution Feeder voltage varies from peak hours to off-peak hours between 10.9 and 11.2 KV at the tail end of the feeder. The HT Distribution voltage recorded by putting the OLTC in Auto mode to maintain feeder voltage between 10.8 and 11.2 KV is shown in Figure 8.3. OLTC performance curve voltage (kv) :26:45 16:31:45 18:36:45 20:41:45 22:46:45 0:51:45 2:56:45 5:01:45 7:06:45 9:11:45 11:16:45 13:21:45 15:26:45 time Figure 8.3. Effect of OLTC performance on 11KV Distribution Feeder Voltage Profile 8.7 Effect of Over Voltage in Transformer Loss When HT Voltage is increased, the core loss of the Transformer will increase but in contrast the HT copper loss will decrease. In Distribution Transformers, the increase in core loss is more than decrease in HT copper loss and leads to increase in total Transformer losses in majority of the cases. A great potential of energy can be saved, if this effect can be nullified or minimized by adjusting the Transformer taps optimally with the help of on-load tap changing facilities in the main power Transformer (110KV/11KV) feeding to the 11KV Distribution feeder lines. Based on the observation made, this thesis work proposes to maintain the HT Distribution feeder Voltage between 10.8 and 11.2 KV. If the Power Transformer step down voltage and maintained at 11.2 KV, then the Distribution Transformer close to main 110KV/11KV Sub-station 103

10 will receive 11.2 KV and the Distribution Transformer at the far end of HT Distribution will receive 10.8KV at the worst cases. The off-load Tap position of Distribution Transformers can be maintained in such a way to receive rated 415 Volts. The Distribution Transformer close to main sub-station can be operate at Tap position No.2 and at middle of the HT feeder can operate at Tap position No.3 and tail end of HT feeder can be operate at Tap position No.4. For a well-designed 11KV system the HT Distribution drop is maximum of 0.2 KV (200Volts) and some of the 11KV Distribution system having voltage drop of less than 0.2KV are still operating with the state electricity board (Especially priority feeders). This clearly indicates there is a possibility to maintaining the 11KV Distribution voltage between 10.8 KV and 11.2KV to minimize the core loss in Distribution Transformers. But it is not feasible in case of main sub-station Transformer feeding to feeder without OLTC provision. The commonly used sizes of Distribution Transformers by the State Electricity Boards are 11KV/ 433V 100KVA, 250KVA and 500KVA. An attempt was made to calculate the savings potential theoretically due to High input 11KV input voltage of Distribution Transformer of the commonly used Size at various loading conditions. The losses at various voltage conditions are shown in the Table 8.5, 8.6 and 8.7. Table 8.5. Losses at various Voltage conditions for 100KVA Distribution Transformer HT HT Copper Voltage Core loss in in KV in

11 Table 8.6. Losses at various Voltage conditions for 250KVA Distribution Transformer HT voltage In KV Core loss in Table 8.7. Losses at various Voltage conditions for 500KVA Distribution Transformer HT voltage in KV Core Loss in

12 8.8 Loading of Transformer Loading plays a major role on Transformer operating efficiency. In any Electrical equipment as the load factor increases towards the capacity the efficiency will be high. In case of Transformer the maximum efficiency occurs well below the rated load. As we are aware by the theory, in case of Transformer the maximum efficiency occurs when the copper loss is equal to the iron loss. In case of a Transformer, maximum efficiency occurs between 40 and 60 % of the load factor. The reason for this is the iron loss is only 10 to 15 % of full load copper loss in case of Distribution Transformer and 15 to 20 % of full load copper loss in case of Power Transformer. At the same time, it is not recommended to go for additional capacity of Transformer to increase operating efficiency and reduce load factor to 40 to 60% because of the very high initial investment for the additional Transformer Effect of Load Factor The load factor of the Distribution Transformer varies from off-peak hours to Peak hours and varies from 25% to 100%. During Peak hours the rise in 11KV Distribution feeder voltage is helpful to minimize the over all Distribution Transformer losses. When the load factor of the Distribution Transformers between 80 and 100%, the increase in core loss due to rise in voltage is less than the decrease in copper loss due to reduction in HT side current. The 80 to 100% Load Factor occurs in Distribution Transformer only during Peak Hours, but the 11KV feeder voltage is more or less equal to the rated voltage. During off-peak hours the voltage raises more than the rated and Load factor of Distribution Transformer is between 25 and 50%. In this case the increase in Core Loss due to rise in voltage is more than the decrease in copper loss due to reduction in HT Side current. The voltage measurements done on 11KV Feeders show that the 11KV voltage varies from 11.4 KV to 11.8KV during off-peak hours. The Load factor of TNEB Distribution Transformer feeding to commercial and domestic load is around 25 to 50% during off-peak hours. Majority of the cases the Distribution Transformer feeding to commercial and domestic load has only 25% load factor during off-peak hours. The effects of 11KV HT Distribution feeder voltage on the Distribution Transformer at various load factors are analysed. The Distribution Transformer losses are high, when the load is less than the rated load. An analysis was carryout to calculate the losses at 25% load and 50% load. Based on the analysis made on this thesis work, the Distribution Transformer losses are less, 106

13 when input voltage is between 10.8 KV and 11.2 KV. An attempt was made to quantify the savings potential in TNEB Distribution Transformer feeding to commercial and domestic load. The saving potential in TNEB Distribution Transformer by maintaining the voltage profile of 11KV supply between 10.8 KV and 11.2KV was calculated assuming 50% Total No. of Transformers are loaded to 25% load factor during off-peak and remaining 50%Transformer loaded to 50% load factor. 8.9 Benefits of Maintaining Voltage Maintaining the 11KV HT Distribution Feeder voltage between 10.8 KV and 11.2 KV will save energy in Distribution Transformers by minimizing the voltage related losses during off-peak hours and normal hours. This also saves the equipment connected to the Distribution Transformer in case of over voltages. In case of a 250 KVA Transformer by keeping the 11KV rated supply voltage between 10.8 and 11.2 KV during off-peak hours (approx. 8 hrs) will yield saving in energy of 0.85 KWH a day. The annual saving estimated by maintaining the voltage in 11KV power supply will save around Indian Rupees.15 Millions in 100 KVA, 250 KVA and 500 KVA Transformers alone. Energy Conservation not only save money, it can also reduce the emission of greenhouse gases such as carbon dioxide (CO 2), which is released when electricity is generated and environment Cost Benefits The Number of Distribution Transformer in operation for supplying power to Commercial, Small Scale Industries and Domestic Load in TNEB, Chennai is as follows: Total number of 11KV/ 433 Volts 100 KVA Transformer = 49,127 Total number of 11KV/433 Volts 250 KVA Transformer = 16,816 Total number of 11KV/ 433 Volts 500 KVA Transformer = 4,780 For estimating the saving potential, the cost of electrical energy is taken as the average generation cost for TNEB. The average generation cost for TNEB is Indian Rupees 1.86/KWH. This was used to calculate the savings potential in TNEB Distribution Transformers to determine the annual cost savings of these three size Transformers. The annual cost savings potential in TNEB due to maintaining the 11KV HT Distribution Voltage within the proposed voltage band of 10.8 KV to 11.2 KV is shown in the Table

14 Table 8.8. Annual Cost Savings due to maintaining the 11KV HT Distribution Voltage Savings in case of Savings in case of Annual Cost of 25% Load Factor in Indian 50% Load Factor in Indian Savings Rupees/year Rupees/year 100 KVA 4,479,137 2,801, KVA 3,287,918 2,009, KVA 1,713,434 1,129, Summary In this chapter, the need of maintaining 11KV HT Distribution System Feeder Voltage between 10.8KV and 11.2KV is discussed to minimize the Distribution Transformers losses during off-peak hours by State Electricity Board with the help of OLTC facility in Transformer. The targeted value of feeder voltage from 10.8 KV to 11.2 KV can be regulated with the help of OLTC provided in the Power Transformers. There is a need to revise the 11KV Distribution feeder sending end voltage due to implementation of ABT in the Regional grid. A trail was conducted to record the voltage profile of an 11KV power supply by putting the OLTC in automatic mode in the Power Transformer to maintain the voltage at 11.2 at the Transformer 11KV Side. The 11KV Distribution Feeder voltage varies between 10.9 and 11.2 KV at the tail end of the feeder. This voltage is ideal for the 11KV HT Distribution system. This also reduces the core saturation and increases the life span of the Distribution Transformers. The annual savings potential by maintaining the 11KV power supply voltage profile between 10.8KV and 11.2 KV for the 100 KVA, 250 KVA and 500KVA Transformers is Indian Rupees.15.7 Millions. The On-load tap-changing gear plays a major role in maintaining the voltage profile of the 11KV HT Distribution Feeder voltage. But the usage of OLTC was limited due to lag of awareness in maintaining the voltage during off-peak hours. This thesis work recommends operating the OLTC in automatic voltage correction mode especially during off-peak hours. The trail taken in a 110KV sub-station operating the Power Transformer with OLTC in Automatic mode has maintain the voltage of 11KV power supply between 10.8 KV and 11.2 KV. This can helpful to minimize the T & D losses of India. Hence it is strongly recommended to maintain the 11KV Distribution feeder voltage preferably ± 2 to 3 %, to minimize the Distribution losses in the power system in India and developing countries. 108

148 Electric Machines

148 Electric Machines 148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional

More information

AUTO-TRANSFORMER. This is having only one winding; part of this winding is common to both primary and secondary.

AUTO-TRANSFORMER. This is having only one winding; part of this winding is common to both primary and secondary. AUTO-TRANSFORMER This is having only one winding; part of this winding is common to both primary and secondary. In 2-winding transformer both primary and secondary windings are electrically isolated, but

More information

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits CS 36 HOSP 14 36 Abstract A leading hospital in southern India faced chronic problems in terms of humming noise in capacitor bank, its failure, high temperature in transformer, and disturbances on the

More information

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K UNIT II TRANSFORMERS PART A 1. Define a transformer? A transformer is a static device which changes the alternating voltage from one level to another. 2. What is the turns ratio and transformer ratio of

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

2 METHODOLOGY. The method of reactive power compensation, proposed in this research is suitable

2 METHODOLOGY. The method of reactive power compensation, proposed in this research is suitable 2 METHODOLOGY 2.1 BASE LOAD REACTIVE POWER REQUIREMENT The method of reactive power compensation, proposed in this research is suitable to meet the base reactive power requirement of the network. The base

More information

How to maximize reliability using an alternative distribution system for critical loads

How to maximize reliability using an alternative distribution system for critical loads White Paper WP024001EN How to maximize reliability using an alternative distribution system for critical loads Executive summary The electric power industry has several different distribution topologies

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Phase Shifter Application Workshop. Siemens Energy, Inc.

Phase Shifter Application Workshop. Siemens Energy, Inc. Phase Shifter Application Workshop Siemens Energy, Inc. PJM Power Pool, March, 2015 siemens.com/energy Phase Shifter Application Workshop Phase Shifting Transformers Principles, Design Aspects and Operation

More information

Constant Terminal Voltage. Working Group Meeting 4 19 th September 2014

Constant Terminal Voltage. Working Group Meeting 4 19 th September 2014 Constant Terminal Voltage Working Group Meeting 4 19 th September 014 Overview Options summary System under investigation Options analysis Discussion Options Option 1 Constant Terminal Voltage controlled

More information

Methods of secondary short circuit current control in single phase transformers

Methods of secondary short circuit current control in single phase transformers 2015; 1(8): 412-417 ISSN Print: 2394-7500 ISSN Online: 2394-5869 Impact Factor: 5.2 IJAR 2015; 1(8): 412-417 www.allresearchjournal.com Received: 17-05-2015 Accepted: 20-06-2015 Parantap Nandi A/2, Building

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1 LV PFC Basics Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1 What are the different types of loads? Ohmic loads Lighting bulbs Iron Resistive heating Capacative loads Capacitors Underground

More information

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION Important Instructions to examiners: 1) The answers should be examined by key words and not as word-to-word as given in the model answer scheme. 2) The model answer and the answer written by candidate

More information

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing

More information

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs Mr. P. Biswas, ABB ABSTRACT The Indian Railways employ single phase 25 kv Traction sub-station (TSS) for supplying power

More information

~=E.i!=h. Pre-certification Transformers

~=E.i!=h. Pre-certification Transformers 7 Transformers Section 26 of the electrical code governs the use and installations of transformers. A transformer is a static device used to transfer energy from one alternating current circuit to another.

More information

UNIT II MEASUREMENT OF POWER & ENERGY

UNIT II MEASUREMENT OF POWER & ENERGY UNIT II MEASUREMENT OF POWER & ENERGY Dynamometer type wattmeter works on a very simple principle which is stated as "when any current carrying conductor is placed inside a magnetic field, it experiences

More information

Techniques for the Control of Steady State Voltage in MV and LV Networks

Techniques for the Control of Steady State Voltage in MV and LV Networks Techniques for the Control of Steady State Voltage in MV and LV Networks by Dr Robert Barr, Electric Power Consulting Pty Ltd Prof. Vic Gosbell, University of Wollongong Mr Chis Halliday, Electrical Consulting

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION Important Instructions to examiners: 1) The answers should be examined by key words and not as word-to-word as given in the model answer scheme. 2) The model answer and the answer written by candidate

More information

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765

More information

Transformer & Induction M/C

Transformer & Induction M/C UNIT- 2 SINGLE-PHASE TRANSFORMERS 1. Draw equivalent circuit of a single phase transformer referring the primary side quantities to secondary and explain? (July/Aug - 2012) (Dec 2012) (June/July 2014)

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Mitigation of Negative Sequence Currents and Effect of Magnetic Inrush Currents in Indian Railway Traction System

Mitigation of Negative Sequence Currents and Effect of Magnetic Inrush Currents in Indian Railway Traction System ISSN (Print) : 2347-671 (An ISO 3297: 27 Certified Organization) Vol. 4, Special Issue 6, May 215 Mitigation of Negative Sequence Currents and Effect of Magnetic Inrush Currents in Indian Railway Traction

More information

CHAPTER 4. Distribution Transformers

CHAPTER 4. Distribution Transformers CHAPTER 4 Distribution Transformers Introduction A transformer is an electrical device that transfers energy from one circuit to another purely by magnetic coupling. Relative motion of the parts of the

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation Harag Margossian 1, Florin Capitanescu 2, Juergen Sachau 3 Interdisciplinary Centre for Security, Reliability

More information

PROBLEMS on Transformers

PROBLEMS on Transformers PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary

More information

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

VOLTAGE MANAGEMENT BY THE APPORTIONMENT OF TOTAL VOLTAGE DROP IN THE PLANNING AND OPERATION OF COMBINED MEDIUM AND LOW VOLTAGE DISTRIBUTION SYSTEMS

VOLTAGE MANAGEMENT BY THE APPORTIONMENT OF TOTAL VOLTAGE DROP IN THE PLANNING AND OPERATION OF COMBINED MEDIUM AND LOW VOLTAGE DISTRIBUTION SYSTEMS 66 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS Vol.97(1) March 2006 VOLTAGE MANAGEMENT BY THE APPORTIONMENT OF TOTAL VOLTAGE DROP IN THE PLANNING AND OPERATION OF COMBINED MEDIUM AND LOW VOLTAGE DISTRIBUTION

More information

SECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University

SECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University SECTION 4 TRANSFORMERS Yilu (Ellen) Liu Associate Professor Electrical Engineering Department Virginia Tech University Analysis of Transformer Turns Ratio......................... 4.2 Analysis of a Step-Up

More information

CHAPTER 3 DEVELOPMENT OF DISTRIBUTION SIMULATION PACKAGE FOR LOAD ANALYSIS OF LV NETWORK

CHAPTER 3 DEVELOPMENT OF DISTRIBUTION SIMULATION PACKAGE FOR LOAD ANALYSIS OF LV NETWORK 78 CHAPTER 3 DEVELOPMENT OF DISTRIBUTION SIMULATION PACKAGE FOR LOAD ANALYSIS OF LV NETWORK 3.1 INTRODUCTION Distribution loads vary in response to temperature, time of the day, day of the week and other

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

Impact of Distributed Generation on Network Voltage Levels

Impact of Distributed Generation on Network Voltage Levels EEE8052 Distributed Generation Taster Material Impact of Distributed Generation on Network Voltage Levels Steady-state rise in network voltage levels Existing practice is to control distribution voltage

More information

Electrical Machines I : Transformers

Electrical Machines I : Transformers UNIT TRANSFORMERS PART A (Q&A) 1. What is step down transformer? The transformer used to step down the voltage from primary to secondary is called as step down transformer. (Ex: /11).. Draw the noload

More information

Voltage Level Management of Low Voltage Radial Distribution Networks with High Penetration of Rooftop PV Systems

Voltage Level Management of Low Voltage Radial Distribution Networks with High Penetration of Rooftop PV Systems Voltage Level Management of Low Voltage Radial Distribution Networks with High Penetration of Rooftop PV Systems Piyadanai Pachanapan and Surachet Kanprachar Abstract The increasing of rooftop photovoltaic

More information

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric

More information

INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H.

INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H. INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H. Aliche 1,2 nnamdi azikiwe university, awka, anambra state, nigeria.

More information

D-UPFC Application as the Series Power Device in the Massive Roof-top PVs and Domestic Loads

D-UPFC Application as the Series Power Device in the Massive Roof-top PVs and Domestic Loads Current Photovoltaic Research 4(4) 131-139 (2016) pissn 2288-3274 DOI:https://doi.org/10.21218/CPR.2016.4.4.131 eissn 2508-125X D-UPFC Application as the Series Power Device in the Massive Roof-top PVs

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013 Investigating the Effect of Using Capacitorsin the Pumping Station on the Harmonic Contents (Case Study: Kafr El-Shikh Governorate, Egypt) Khaled M. Fetyan Abstract Power Factor (PF) is one of the most

More information

Sensitivity Analysis for 14 Bus Systems in a Distribution Network With Distributed Generators

Sensitivity Analysis for 14 Bus Systems in a Distribution Network With Distributed Generators IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 3 Ver. I (May Jun. 2015), PP 21-27 www.iosrjournals.org Sensitivity Analysis for

More information

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids

More information

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES UNIVERSITY OF TECHNOLOGY DEPARTMENT OF ELECTRICAL ENGINEERING Year: Second 2016-2017 By: Fadhil A. Hasan ELECTRICAL MACHINES І Module-II: AC Transformers o Single phase transformers o Three-phase transformers

More information

EH2741 Communication and Control in Electric Power Systems Lecture 2

EH2741 Communication and Control in Electric Power Systems Lecture 2 KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur Lecture - 10 Transmission Line Steady State Operation Voltage Control (Contd.) Welcome

More information

Energy Saving Using Bifurcation of Distribution Transformer

Energy Saving Using Bifurcation of Distribution Transformer Energy Saving Using Bifurcation of Distribution Transformer Tamizharasi.P Asha. N Deepalakshmi.U Asst. professor, Department of EEE, UG Scholar, Department of EEE, UG Scholar, Department of EEE, Adhiparasakthi

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Power Quality Regulations for Distribution of Electricity in India

Power Quality Regulations for Distribution of Electricity in India Power Quality Regulations for Distribution of Electricity in India Presentation to Forum of Indian Regulators (FOIR) 1 st Dec 2015 New Delhi Asia Power Quality Initiative (APQI) Asia Power Quality Initiative

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

Transformers. gpmacademics.weebly.com

Transformers. gpmacademics.weebly.com TRANSFORMERS Syllabus: Principles of operation, Constructional Details, Losses and efficiency, Regulation of Transformer, Testing: OC & SC test. TRANSFORMER: It is a static device which transfers electric

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

Parallel tap-changer controllers under varying load conditions (Part 1)

Parallel tap-changer controllers under varying load conditions (Part 1) Parallel tap-changer controllers under varying load conditions (Part 1) by Prof. B S Rigby, T Modisane, University of KwaZulu-Natal This paper investigates the performance of voltage regulating relays

More information

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers Department of Electrical Engineering Lecture Basic Operating Principles of Transformers In this Lecture Basic operating principles of following transformers are introduced Single-phase Transformers Three-phase

More information

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Assessment of the Impact of GMD on the TVA 500 kv Grid & Power Transformers Part II:

More information

GRid connected PV inverters are gaining popularity at. Adaptive Reactive Power Injection by Solar PV Inverter to Minimize Tap Changes and Line Losses

GRid connected PV inverters are gaining popularity at. Adaptive Reactive Power Injection by Solar PV Inverter to Minimize Tap Changes and Line Losses Adaptive Reactive Power Injection by Solar PV Inverter to Minimize Tap Changes and Line Losses Anubrata Das, Ankul Gupta, Saurav Roy Choudhury and Sandeep Anand Department of Electrical Engineering, Indian

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical

More information

Power Transformer Ratings' Calculation and Analysis - IEEE C

Power Transformer Ratings' Calculation and Analysis - IEEE C Power Transformer Ratings' Calculation and Analysis - IEEE C57.91-1995 Course No. E-3058 Credit: 3 PDH 2017 Decatur Professional Development, LLC. All rights reserved. Power Transformer Ratings Calculation

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

ELEC Transmission i and

ELEC Transmission i and ELEC-1104 Lecture 5: Transmission i and Distribution ib ti Power System Layout Transmission and Distribution The transmission system is to transmit a large amount of energy from the power stations s to

More information

Module 7. Transformer. Version 2 EE IIT, Kharagpur

Module 7. Transformer. Version 2 EE IIT, Kharagpur Module 7 Transformer Lesson 28 Problem solving on Transformers Contents 28 Problem solving on Transformer (Lesson-28) 4 28.1 Introduction. 4 28.2 Problems on 2 winding single phase transformers. 4 28.3

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Influence of Wind Generators in Voltage Dips

Influence of Wind Generators in Voltage Dips Influence of Wind Generators in Voltage Dips E. Belenguer, N. Aparicio, J.L. Gandía, S. Añó 2 Department of Industrial Engineering and Design Universitat Jaume I Campus de Riu Sec, E-27 Castelló (Spain)

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

TRANSFORMER THEORY. Mutual Induction

TRANSFORMER THEORY. Mutual Induction Transformers Transformers are used extensively for AC power transmissions and for various control and indication circuits. Knowledge of the basic theory of how these components operate is necessary to

More information

Active Harmonic Filter (AF3)

Active Harmonic Filter (AF3) Active Harmonic Filter (AF3) Active Harmonic Filter Improving the Efficiency and Life of System by use of Digital Active Power Conditioner HARMONICS 50 Hz, fundamental 100 Hz, 2nd Harmonic 150 Hz, 3rd

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

VOLTECHNOTES. Turns Ratio iss 4 Page 1 of 7

VOLTECHNOTES. Turns Ratio iss 4 Page 1 of 7 VOLTECHNOTES Turns Ratio 104-113 iss 4 Page 1 of 7 Introduction Transformers are used in a wide array of electrical or electronic applications, providing functions that range from isolation and stepping

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

ADVANCEMENT IN STATE GRASPING METHOD OF MV DISTRIBUTION NETWORK FOR SHORT-TERM AND MID-TERM PLANNING

ADVANCEMENT IN STATE GRASPING METHOD OF MV DISTRIBUTION NETWORK FOR SHORT-TERM AND MID-TERM PLANNING PV capacity [GW] ADVANCEMENT IN STATE GRASPING METHOD OF MV DISTRIBUTION NETWORK FOR SHORT-TERM AND MID-TERM PLANNING Hiroyuki ISHIKAWA Ishikawa.Hiroyuki@chuden.co.jp Takukan YAMADA Yamada.Takukan@chuden.co.jp

More information

Effects of GIC on Power Transformers and Power Systems

Effects of GIC on Power Transformers and Power Systems Effects of GIC on Power Transformers and Power Systems Prepared by Dr. Ramsis Girgis and Kiran Vedante (USA) in the name of CIGRE SC A2 Background There has been some misconception in the electric power

More information

TRANSFORMER OPERATION

TRANSFORMER OPERATION Chapter 3 TRANSFORMER OPERATION 1 A transformer is a static device (no moving parts) used to transfer energy from one AC circuit to another. This transfer of energy may involve an increase or decrease

More information

Walchand Institute of Technology. Basic Electrical and Electronics Engineering. Transformer

Walchand Institute of Technology. Basic Electrical and Electronics Engineering. Transformer Walchand Institute of Technology Basic Electrical and Electronics Engineering Transformer 1. What is transformer? explain working principle of transformer. Electrical power transformer is a static device

More information

Medium-voltage in-phase regulator system Energy Management

Medium-voltage in-phase regulator system Energy Management Medium-voltage in-phase regulator system Energy Management Challenges Distributed power generation can have an enormous impact on grid performance. The challenge of equalizing voltage fluctuations is especially

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

Regional Technical Seminar

Regional Technical Seminar Regional Technical Seminar LOAD TAP CHANGERS (LTCS) DESIGN, OPERATION, AND MAINTENANCE CONSIDERATIONS SPX Dallas Facility Damon Jones General Manager SPX Transformer Solutions Components Group Cell: 214-422-8979

More information

86 chapter 2 Transformers

86 chapter 2 Transformers 86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

3Ø Short-Circuit Calculations

3Ø Short-Circuit Calculations 3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective

More information

Chapter L Power factor correction and harmonic filtering

Chapter L Power factor correction and harmonic filtering Chapter L Power factor correction and 1 2 3 4 5 6 7 8 9 10 Contents Reactive energy and power factor 1.1 The nature of reactive energy L2 1.2 Equipment and appliances requiring reactive energy L2 1.3 The

More information

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant CASE STUDY Implementation of Ford Motor Company SA Silverton Plant 1 SCENARIO Ford Motor Company is a global automotive and mobility company based in Dearborn, Michigan. Ford Motor Company of Southern

More information

Connection Impact Assessment Application

Connection Impact Assessment Application Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

Single-Phase Transformation Review

Single-Phase Transformation Review Single-Phase Transformation Review S T U D E N T M A N U A L March 2, 2005 2 STUDENT TRAINING MANUAL Prerequisites: None Objectives: Given the Construction Standards manual and a formula sheet, you will

More information

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES C.E.T. Foote*, G.W. Ault*, J.R. McDonald*, A.J. Beddoes *University of Strathclyde, UK EA Technology Limited, UK c.foote@eee.strath.ac.uk

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 00 03 ELECTRICAL AND ELECTRONICS ENGINEERING ASSIGNMENT Course Name : ELECRICAL MACHINES - II Course Code : A0 Class : II B.TECH-II

More information

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation TSAI-HSIANG CHEN a NIEN-CHE YANG b Department of Electrical Engineering National Taiwan University

More information

Calculating and compensating for power transformer and cable (or line) losses - standard methods

Calculating and compensating for power transformer and cable (or line) losses - standard methods Guidance Calculating and compensating for power transformer and cable (or line) losses - standard methods Foreword This guidance sets out basic standard methods for calculating electrical loss compensation

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information