Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED
|
|
- Shanon Clyde Hensley
- 5 years ago
- Views:
Transcription
1 Dial : (033) & Tele Fax : (033) Manufacturer of Dry Type Transformers unimag111@gmail.com Office & Factory : 26/5, Sarat Chatterjee Road, Howrah , West Bengal, India. Visit us : Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED The Compact Substation or Prefabricated Substation is a unique technical evolution in the Power Distribution system by installing all three essential equipments namely Ring Main Unit (RMU), Transformer and LV Air Circuit Breaker with Distribution Panel with Fuse Strip or MCCB all installed inside a single corrugated metallic weatherproof enclosure. UNIVERSAL MAGNETICS (wholly own unit of M/s. AKS Power Equipments Pvt. Ltd.) being pioneer in VPI Dry Type Transformers manufacturing over a period of 28 years have served the many prestigious corporate houses like CESC Limited, B.E.S.&T. Undertaking, ITC Limited, BARC - Trombay, Bhushan Power & Steel Limited etc. and designed and developed a unique Prefabricated Compact Substation (PSS) with the following features. Contd.2
2 [ 2 ] 1. 2 mm thick CRCA Sheet Steel Corrugated Enclosure with 4 Nos. of 200 mm Dia, 85 mm Thick M.S. Bi-Directional Roller for easy movement of the equipment. 2. VPI Dry Type Transformer with Class C Insulation. Coils are wound with Nomex Aramid Paper (Type 410) made by DUPONT, USA & Vacuum Pressure Impregnated in Silicone Varnish imported from Dow Corning, USA. Contd..3
3 [ 3 ] 3. 1 No. 11 KV RMU Unit consisting of 1 No. SF 6 Circuit Breaker and 2 Nos. Load Break Switches Nos. 1C x 95 sq.mm 11KV XLPE Copper Cable with Raychem Termination Kit along with cold applied boots for CB feeder & transformer side termination set 2000 A Copper Bus Bar connection between LT terminals of transformer to 2000 A, 4-pole, ACB for controlling the DTR. LT terminals of the transformer to be connected to the said Bus Bar through 2000 A copper flexible with bimetallic joint. 6. Winding Temperature Scanner with 3 Nos. RTD Sensor from Transformer is provided. Contd..4
4 [ 4 ] A Vertical Fuse Strip Units with associated bus connection for the outgoing distributors 8 sets, suitable for connecting 4C x 400/240 sq.mm XLPE Aluminium Cable. Alternately required nos. of MCCB may be installed for LV Distribution System. 8. Separate door is provided for temporary connection of external Generator directly to LV Bus Bars in case of emergency measure with HV supply switched off. Contd..5
5 [ 5 ] Transformer Specification Rating : 990 KVA Voltage Ratio : 11KV/415V Taps : Taps are provided on Primary Side in a fibre glass board and changed manually by copper link at off circuit position. Range of Taps = + 5% to 5% in steps of 2.5% Type : Dry, AN (Air Natural Cooled) Applicable Standard : I.S Dry Type Transformers. No. of Phases : 3 Frequency : 50 Hz. Connection : Dyn11 Class of Insulation : Class C Allowable Temperature Rise 140 C over an ambient of 40 C as per I.S. Guaranteed Winding Temp. Rise : 115 C at Nominal Tap comply with Class H Insulation as per I.S. which is 25 C lower than specified Class C Insulation used in our transformer. Therefore, our transformer shall be capable of operating with 10% Overload Continuously without loosing its Normal Life Expectancy. Type of Insulation : Nomex Aramid Paper (Make DUPONT, USA), Silicone Varnish (Make Dow Corning, USA), Glass Tapes etc. Coils are insulated with Nomex Paper & Glass Tapes and Vacuum Pressure Impregnated in Silicone Varnish. Core Material : C.R.G.O. M-4 with Full Mitred Step Lap Joint Construction. Winding Material : E. C. Grade Copper. L.V. Winding L.V. Windings are made of Copper Foils with Nomex Paper Interlayer which are extremely rugged in construction and also capable of withstanding Short Circuit Current Situations as well as reducing Hottest Spot Temperature more efficiently comparing to Multiple Strip Conductors. H.V. Winding H.V. Windings are made of E.C. Grade Copper Strip/Round with Nomex Paper Covering (50 : 50 Overlap). Test : Type Test The Transformer has successfully passed the following Type Test a) Dynamic Short Circuit Test b) 75 KV Impulse Test c) Temperature Rise Test Routine Test The Transformer has successfully passed all the Routine Test as per IS ********************************************************************
(
(www.xatianhong.com) Introduction to XATH Xi'an Tianhong Electric Co., Ltd. (XATH) is a solely state-owned enterprise, set up by China Shipbuilding Industry Corporation (CSIC). It is one of the largest
More informationCAST RESIN DRY TRANSFORMER
CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,
More informationGE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class
GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date
More informationCONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS
CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased
More informationPURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS
PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY
More informationPES & IAS NY Chapter And NY LMAG June 23 rd, 2015
PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 High Temperature Insulation Systems and their use in Mobile Transformers Myron B. Bell, PE mbell@deltastar.com Delta Star, Inc. June 23 rd 2015 Introduction
More informationMGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide
MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888
More informationSHARDA Make Harmonics Filter
SHARDA Make Harmonics Filter SHARDA offers perfect solution to minimize Harmonics level of industries where non-linear load like, VFD, Electronics load, Convertors, Voltage booster equipment s are present.
More informationTMC Transformers TMC
TMC Product & Technology Presentation Cast Resin Transformer (CRT) History Cast resin transformers first appeared in Germany during the 1960s. This new style of dry type transformer was developed with
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationGroup F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A
Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating
More informationProlific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2
Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II
More informationDATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO
PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %
More informationArild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems
Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -
More informationDISTRIBUTION TRANSFORMERS
DISTRIBUTION TRANSFORMERS OIL IMMERSED up to 6 MVA www.alfanar.com Contents 1 - General Information 4 2 - Applications 10 3 - Product Portfolio 11 4 - Product Breakdown 12 5 - Transformer Classifications
More informationMV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer
PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with
More informationDESIGNED MANUFACTURED TESTED
DESIGNED MANUFACTURED TESTED Utilities Approvals ADWEA, Abu Dhabi ADDC, Abu Dhabi About us AADC, Al Ain DEWA, Dubai Federal Transformers Company LLC (FTC) is an ISO 9001:2008 Company established in January
More informationand cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.
-156 Purpose & Industrial Control Purpose (1000 kva and Below) mounted dry-type transformers of the two-winding type, self-cooled, with ratings and voltages as indicated on the drawings. shall be manufactured
More informationTRAFO ELECTRIC P. LTD.
TRAFO ELECTRIC P. LTD. About Us Trafo Electric P. Ltd. started manufacturing Power & Distribution Transformers in 1974. Originally known as J B Electricals, the unit s entire production was for BSES( Bombay
More informationTECHNICAL SPECIFICATION FOR POWER TRANSFORMER
TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL
More informationIntroduction. Centrado leading-edge transformer. Introduction
Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,
More informationsave energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers
save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationUBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS
More informationCOMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3
CONTENTS COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONSTRUCTION... 4 ~ 5 A. CORE AND FRAME... 4 B. COIL... 5 C. TEMPERATURE INDICATOR... 5 CHARACTERISTICS... 6 MANUFACTURING FACILITIES...
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More informationSPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers
SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.
More informationMESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION
Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:
More informationLiquid-Filled Transformers
Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of
More informationSECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE
SUBSTATION TRANSFORMERS DRY-TYPE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the primary and/or secondary substation transformers as specified herein and as shown
More information2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type
PAGE 2 of 6 2.14 Main Cable Type HO7RN-F4G10-15 Metres each 2.15 (a) O/P Voltage-350V(Max.) (b) O/P Current 150A(Max.) 2.16 Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type 2.17
More informationSiemens Transformer Technology Seminar Insulation & Thermal Design
Customer Technical Meeting Pomona, CA May 24 25, 2016 Siemens Transformer Technology Seminar Insulation & Thermal Design Siemens AG Transformers siemens.com/answers Winding Selection Windings: Page 2 Winding
More informationPRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS
PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established
More informationMEDIUM VOLTAGE COMPACT STARTER TYPE KAE
MEDIUM VOLTAGE COMPACT STARTER TYPE KAE up to 5 MW up to 17,5 kv up to 400 A Mocotech presents the compact motor starter t ype KAE with integrated autotransformer, switches, control and many more advantages.
More informationDescription. Features and Benefits
KA-108 The General Electric Type KA-108 Bushing Potential Device is a reliable, safe, economical voltage transforming device for the operation of instruments and relays from high-voltage circuits, 115
More informationVOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)
TENDER DOCUMENT NIT No. DLI/C&E/WI-665/535R FOR Tender for Supply of 3CX185 mm2, 11 KV (UE) grade, Power Cable for Augmentation of Raw Material Handling Receipt and Handling Facilities with new OHP Part
More informationNEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :
NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE
More informationPower Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
More informationTECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This
More informationREPORT OF PERFORMANCE TIC
REPORT OF PERFORMANCE TIC 1580-13 OBJECT TYPE Three-core power cable 18/30(36) kv, 3x500 mm2, 2XWY(P)-FR XLPE Rated voltage, U 0/U (U m) 18/30 (36) kv Conductor material Cu Conductor cross-section 3x500
More informationK Factor Power Transformers
Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business
More informationFAQ ON EARTHING STANDARDS 16/08/2018
FAQ ON EARTHING STANDARDS 16/08/2018 This document has been updated to include changes made to substation earthing layouts that have been made necessary due to copper theft. The main changes to be aware
More informationTECHNICAL SPECIFICATION OF 630 KVA, 11/ KV DRY TYPE OUTDOOR TRANSFORMERS.
TECHNICAL SPECIFICATION OF 630 KVA, 11/ 0.415 KV DRY TYPE OUTDOOR TRANSFORMERS. 1. 0 Scope: This specification covers design, manufacture, testing and supply of 630 KVA, 11/0.415 KV, Dry Type Distribution
More informationElectrical Description
History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced
More informationPower transformers for Network, Rectifiers, Furnace
E N G L I S H OTN, OTR, OTF Transformers Power transformers for Network, Rectifiers, Furnace TTR TTO OTN, OTR, OTF reactors TTH OTN, OTR, OTF Transformers Technology Design Our designers experience combined
More informationSOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)
E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION
More informationTECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C
TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationCompliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)
Typical Specification 1.2kV Class Energy Efficient Dry-Type Distribution Transformers Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016) Canada 595 Southgate Drive Guelph, Ontario N1G
More informationTitle Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)
Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control
More informationSTAR ELECTRIC COMPANY
STAR ELECTRIC COMPANY STECO manufacturers a complete range of Energy Efficient Mors conforming IS: 325. Efficiency class Improved efficiency PRODUCT RANGE International Standards 60034-1,5 60072 Rotating
More information500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor
500 kva Dry-type Isolation Transformer - 13200V-Delta to 208Y/120V 3PH - NEMA 1/Indoor Part #: MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Page: 1 The MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Dry-type Isolation
More informationProtection of Electrical Networks. Christophe Prévé
Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé
More informationSCHEDULE OF WORK. Balmer Lawrie Co. Ltd. PRICED BID (PART-II) MMLH
SCHEDULE OF WORK Supply, Installation, Testing & Commissioning (SITC) of 33KV Electrical Substation for Multi Modal Logistics Hub at Visakhapatnam, Andhra Pradesh. Tender No. MMLH /HTELEC/PT /18 dated
More informationNo. COA/BHL/2018/293 Dated: REQUEST FOR QUOTATIONS
College of Agriculture, Maharana Pratap University of Agriculture & Technology, Bhilwara-311001 (Rajasthan) Phone: 01482-246118 (O), Email: coabhilwara@gmail.com, No. COA/BHL/2018/293 Dated: 07.06.2018
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More information51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V
SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without
More informationGeneral Electricity Company of Libya
GES 22214 Technical Specification of GECOL 11/0.4kV Oil Immersed Ground Mounted Three Phase Sealed Type Distribution Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company
More informationISSN: [IDSTM-18] Impact Factor: 5.164
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A REVIEW OF ROUTINE TESTING ON DISTRIBUTION TRANSFORMER Sukhbir Singh 1, Parul Jangra 2, Anoop Bhagat 3, Vipin Saini 4 1 Assistant
More informationTechnical Specifications
Page 1 of 14 INSTITUTE FOR PLASMA RESEARCH Technical Specifications Design/engineering, manufacture, inspection, testing at vendor s site, delivery at site of resin cast dry type Cast Resin Transformer
More informationTransformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications
The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of
More informationRelion 605 series Self-Powered Feeder Protection REJ603 Product Guide
Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4
More informationList of Item Codes of Various Materials Purchased by Materials Management Cell(H.O.,Mumbai) through e-tender website https://cpa1.mahadiscom.
List of Item Codes of Various Materials Purchased by Materials Management Cell(H.O.,Mumbai) through e-tender website https://cpa1.mahadiscom.in : M.M. PURCHASE GROUP-I : New Service Connection (N.S.C.)
More informationTECHNICAL SPECIFICATION FOR SELF PROTECTED SINGLE PHASE DISTRIBUTION TRANSFORMERS ( SPECIFICATION NO: DIST/01-N/2004 )
TECHNICAL SPECIFICATION FOR 11/ 3 KV/250V 15 & 25 KVA OUTDOOR TYPE COMPLETELY SELF PROTECTED SINGLE PHASE DISTRIBUTION TRANSFORMERS ( SPECIFICATION NO: DIST/01-N/2004 ) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION
More informationReference Number PPS 05 - (RIC Standard: EP SP)
Discipline Engineering Standard - NSW Category Electrical Title Low Voltage Isolating Transformer Reference Number PPS 05 - (RIC Standard: EP 17 00 00 11 SP) Document Control Status Date Prepared Reviewed
More informationHPS Universal BUCK-BOOST TRANSFORMERS
BUCK-BOOST TRANSFORMERS Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
More informationDry-type Transformer. High Reliability Maintenance-free Environmentally Friendly
Dry-type Transformer High Reliability Maintenance-free Environmentally Friendly Dry-type Transformer Eaton Cooper Power Systems,a global manufacturer, famous for its market leadership and technical innovation,
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More information51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS
SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS This specification is property of SEC and Subject to change or modification without any notice Table of Contents Clause Page 1.0 SCOPE
More informationDRIVIA cabinets LIMOGES Cedex France 1. DESCRIPTION, USE 3. DIMENSIONS 2. RANGE, CAT. NO. EQUIVALENCE TABLE
87045 LIMOGES Cedex France Tel: (+33) 05 55 06 87 87 Fax: (+33) 05 55 06 88 88 DRIVIA cabinets CONTENTS NTS PAGES 1. Description, use....1 2. Range, equivalence table...1 3. Dimensions...1 4. General characteristics...2
More informationPower Commander. Power Commander Plus. Electronic Line Voltage Regulators. 15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE SERIES 900
15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE Power Commander SERIES 900 Power Commander Plus SERIES 900 / 200 Electronic Line Voltage Regulators Precise Electrical Power For Critical Loads Automatic
More informationHigh Votage Module AC/DC/Impulse Test System
TSGADI Series High Votage Module AC/DC/Impulse Test System A digital control and measuring system is used to be control the difference output AC/DC/Impulse and related protection device such as over voltage
More informationTRANSFORMER TECHNOLOGY GPT
Core-Form TRANSFORMER TECHNOLOGY GlobalPT Corporation performs research and engineering developments and co-ordination of works of technical partners in the field of technological progress and commercial
More informationRitz Instrument Transformers GmbH. Welcome
Ritz Instrument Transformers GmbH Welcome About Ritz together with over 200 years of experience in instrument transformer production since 1945 since 1945 since 1945 since 1904 RITZ Group - Organization
More informationMiniature substations: What they are really capable of delivering
Miniature substations: What they are really capable of delivering by Rhett Kelly and Greg Whyte, ACTOM Medium Voltage Switchgear The latest edition of the South African national standard for miniature
More informationAPDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL
PART 1: GENERAL 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, offloading and performance requirements of 11/0.433kV distribution transformers for outdoor
More informationElectrical Design Process
Electrical Design Process Jason Varnell Lead Design Engineer Jason.Varnell@spx.com SPX Transformer Solutions, Inc. September 26, 2018 Agenda 1. Bid Design Process Parameters Affecting Bid Design 2. Final
More informationPOWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS
POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A
More informationTECHNICAL INFORMATION
Single-Phase Low Voltage Dry- Type Transformers 5-400 kva Three-Phase Low Voltage Dry- Type Transformers 7.5-1000 kva TECHNICAL INFORMATION TABLE OF CONTENTS Introduction...3 Technical Explanations...4
More informationELETTROMECCANICA. Since english OIL IMMERSED DISTRIBUTION TRANSFORMERS
ELETTROMECCANICA P I O S S A S C O Since 1962 english OIL IMMERSED DISTRIBUTION TRANSFORMERS ELETTROMECCANICA PIOSSASCO was created from the transformation of Elettromeccanica Luparia established in the
More informationSDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01
SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice
More informationA compact, integrated solution for medium voltage connection, transformer and low voltage distribution
Low to medium voltage distribution M2L integrated power distribution system A compact, integrated solution for medium voltage connection, transformer and low voltage distribution Turnkey solution medium
More informationBrown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS
SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600
More informationDry-Type Transformers
Dry-Type Transformers 600 Volt Class Bulletin 7700-99 ISO 9002 Registered 1 Federal Pacific Federal Pacific History During 1987, the Electro-Mechanical Corporation acquired the dry-type transformer division
More informationTechnical Specifications SECTION C
Page 1 of 19 INSTITUTE FOR PLASMA RESEARCH Technical Specifications SECTION C Design/engineering, manufacture, inspection, testing at vendor s site, delivery, handling at site, erection, precommissioning
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationTratos High Voltage cables
March 2013 Tratos High Voltage cables Cables for a moving world www.tratos.eu Introduction High Voltage Cables Tratos is an international manufacturer and supplier of High & Extra High Voltage cable up
More informationVARIABLE FREQUENCY RESONANT TEST SYSTEM
VARIABLE FREQUENCY RESONANT TEST SYSTEM 400kV,1200kVA Tank Type Reactor for Outdoor Cable Test Field 650kV, 5850kVA, Cylinder Type Reactors for Onsite Testing of GIS and Cable PHENIX Variable Frequency
More informationSGB at a glance. One of the leading manufacturers. for transformers worldwide
SGB at a glance One of the leading manufacturers SGB Regensburg for transformers worldwide 50 kva up to 1.200 MVA turnover (2010): ~ EUR 580 million 1.309 employees Headquarters: Regensburg, Germany 5
More informationVI 3 - i TABLE OF CONTENTS
VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3
More informationFederal Pacific Engineered and Specialty Transformer Catalog
Federal Pacific Engineered and Specialty Transformer Catalog Federal Pacific History In 1987, Electro-Mechanical Corporation acquired the dry-type transformer division of Federal Pacific Electric in Des
More informationHOW TO SAFE GUARD THE TRANSFORMER..???
CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various
More information15 years of experience
Wires and Cables 15 years of experience APS supplies standard and special copper and fiber optic cables based on its 15 years of experience in the sector, 8 of which in designing and manufacturing. Since
More informationReactor and inductor are names used interchangeably for this circuit device.
Recommended Design Criteria for Air-Cooled Reactor for Line and Track Circuits Revised 2015 (7 Pages) A. Purpose This Manual Part recommends design criteria for an air-cooled reactor for line and track
More informationBasic Principles and Operation of Transformer
Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core
More informationVIRGINIA TRANSFORMER CORP. Drive & Rectifier. Transformersrs
VIRGINIA TRANSFORMER CORP Individual solutions from a global perspective Drive & Rectifier Transformersrs Oil Drilling Paper Mill Virginia Transformer Commitment to our Customers Industry s Shortest Production
More informationSECTION ELECTRICAL IDENTIFICATION
SECTION-16075 ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SECTION INCLUDES A. Electrical identification to identify all electrical items for easy operation and maintenance including, but not limited
More informationCable connection. 58 RM6 catalogue schneider-electric.com
Cable connection 58 RM6 catalogue schneider-electric.com Selecting bushings and connectors 60 Compatible cable connections 61 Other types of compatible connections 63 schneider-electric.com RM6 catalogue
More informationMichigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE
PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More information