Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz

Size: px
Start display at page:

Download "Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz"

Transcription

1 Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz

2 Transformer reliability Ability to perform its required functions under stated conditions for a specified period of time Failure termination of the ability It is often reported as a probability 2

3 Transformer Reliability - based on ANSI C (1986) Definitions: Population: Transformers that have given common specific characteristics Failure: Termination of a transformer to perform its specific functions Failure with forced outage: Failure of a transformer that requires its immediate removal from the system for more than 1 day in conjunction with internal measures Failure Rate FR [%] = (nf / SY) 100 The ration of the number of failures with forced outage of a given population over a given period of time to the number of accumulated service years for all transformers in that period of time Mean Time Between Failures MTBF [years] = 1 / FR Mean Time between failures (MTBF) = 1 / FR (years) N: Number of units in service within evaluation period (floating 10 years) SY: Number of service years accumulated with [N] units in service nf: Number of failures with forced outage of a population within the evolution period 3

4 Transformer Reliability - based on ANSI C (1986) FRe and MTBF as a degree of Reliability: Failure rate and reliability are related in the following way: R = e -λt t... time in year λ failure rate in failures per transformer-years of service (λ=nf/sy) e MTBF is considered to be the reciprocal of failure rate for purpose of estimating reliability: MTB = 1 / λ MTBF and reliability are related in the following way: R = e -t/mtbf Example: Given a constant MTBF of 500 years The reliability R of a transformer surviving t years of service without a failure would be shown as below: λ = t R For a given MTBF of 500 years the probability of a transformer surviving 20 years of service without failure is 96.08% 4

5 CIGRE activities related to Transformer Reliability SC A2 Reliability Advisory Group 2006 Bathtub curve Reliability databases WG A2.37: Reliability Surveys difficult to get reliable data WG A2.43: TR Bushing reliability (Um 72,5 kv) Started in June 2010 Plans to work on topics like post mortem and end of life decision. 5

6 Reliability of main accessories A2 session papers in Paris 2010 showed that accessories cause a significant proportion of the power transformer major failures. new bushing and tap-changer technologies were introduced recently these technologies and their impact on maintenance have to be reviewed Future task of CIGRE Study Committee A2 6

7 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 7

8 Electrical insulation system transformer insulation life [1] total time between initial state (new) and the final state when due to normal service thermal ageing dielectric short-circuit mechanical movement could result in a high risk of electrical failure [1] IEC Loading guide for oil-immersed power transformers 8

9 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 9

10 Thermal es and ageing Caused by the heating due to no-load and load losses Chemical Polymerization Depolymerization Physical Diffusion Expansion/contraction 10

11 Thermal ageing retardation Control possibilities Reduce temp. rises by new cooling stage control (overall loss of life optimization) Hot spot factor determination and control Proper material selection Initial moisture content Air sealing Forced cooling Design know how [1] [1] IEC Loading guide for oil-immersed power transformers 11

12 Manufacturer activities Continue verification cooling calculations Interfaces for dynamic calculation Cooling calculation for alternative insulation fluids Repair experience Post mortem analysis Material tests Supplier control 12

13 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 13

14 Electrical es and ageing Caused by the electrical field and the interaction within the insulation system Increased local temperatures Partial Discharge X-Wax Leakage current Creeping distance Electrical treeing Static electrification could appear 14

15 Electrical ageing retardation Control possibilities Proper material selection Supplier quality control PD free transformers Design and processing know how Calculation possibilities 15

16 Manufacturer activities Continuous adaptation of the transients package to needs of design departments, and to customer Testing and evaluation of new insulation components and materials Basic reproducible test and comparative investigations Optimize technology to ease production and deliver PD-free products 16

17 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 17

18 Ambient Caused by different ambient es the inner & outer systems of a Transformer could be damaged Humidity High/extreme low ambient temperature Altitude Pollution Wind Earthquake 18

19 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 19

20 Mechanical Caused by acceleration during Transport Installation Operation inner & outer systems of a Transformer might be damaged 20

21 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical Real case studies shows a combination of es as well as interactions 21

22 Real case study #1 Sealed GSU Transformer Manufactured in 1952 Power: 8 MVA Rating: 115,5 / 5,25 kv Measurement of Degree of Polymerization (DP-value) in 1982 (after 30 years!!!) Phase 1: HV-winding, shielding ring: DP = 884 Phase 2: HV-winding, leads: DP = 902 Phase 3: HV-winding, winding insulation: DP =

23 #1: Actual Investigations 2011 (after around 60 years of operation) HV leads ~ 300 LV leads ~ 100 DP-distribution over winding height DP average =

24 Real case study #2 Sealed GSU Transformer Manufactured in 1966 Power:103 //51,5 / 51,5 MVA Rating:403// 16 / 16 kv Measurement of T1Q: 642 T1R: 449 T1S: 449 T1T: 704 Samples were taken from LV flexible connector Tests were performed according ISO 14453:

25 #2: Refurbishment Result in 2006 Measurement of De-polymerization (DP value) We expect a transformer rest life time of >13 years under the used load conditions for all 4 transformers. This assessment is based on the results of the performed measurements, the fact that the transformers are new sealed and that the insulation oil is purified. 25

26 In order to create a save energy supply worldwide we as power transformer manufacturers design, build and deliver reliable transformers as a fundamental responsibility Thank you for your attention! 26

Transformer Technology Seminar What to consider at Design Reviews

Transformer Technology Seminar What to consider at Design Reviews Pomona CA, May 24-25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Why to perform Design Review Meetings? To ensure both parties having the same understanding of the

More information

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1 Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector

More information

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site

More information

Presentation of CIGRE activities on Power Transformers. C. Rajotte (CA) Chairman SC A2 "Transformers"

Presentation of CIGRE activities on Power Transformers. C. Rajotte (CA) Chairman SC A2 Transformers CONSEIL INTERNATIONAL DES GRANDS RESEAUX ELECTRIQUES INTERNATIONAL COUNCIL ON LARGE ELECTRIC SYSTEMS STUDY COMMITTEE A2 TRANSFORMERS Presentation of CIGRE activities on Power Transformers C. Rajotte (CA)

More information

Presentation of CIGRE activities on Power Transformers. C. Rajotte (CA) Chairman SC A2 "Transformers"

Presentation of CIGRE activities on Power Transformers. C. Rajotte (CA) Chairman SC A2 Transformers CONSEIL INTERNATIONAL DES GRANDS RESEAUX ELECTRIQUES INTERNATIONAL COUNCIL ON LARGE ELECTRIC SYSTEMS STUDY COMMITTEE A2 TRANSFORMERS Presentation of CIGRE activities on Power Transformers C. Rajotte (CA)

More information

Siemens Transformer Technology Seminar Insulation & Thermal Design

Siemens Transformer Technology Seminar Insulation & Thermal Design Customer Technical Meeting Pomona, CA May 24 25, 2016 Siemens Transformer Technology Seminar Insulation & Thermal Design Siemens AG Transformers siemens.com/answers Winding Selection Windings: Page 2 Winding

More information

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander

More information

Siemens Transformer Technology Seminar Low Partial Discharge Transformers

Siemens Transformer Technology Seminar Low Partial Discharge Transformers West Coast Technical Meeting Pomona CA, May 24-25, 2016 Siemens Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Low Partial Discharge Page 2 Why highlight Low Partial Discharge

More information

Transformer condition assessment with an integrated test van

Transformer condition assessment with an integrated test van Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)

More information

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV

More information

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 High Temperature Insulation Systems and their use in Mobile Transformers Myron B. Bell, PE mbell@deltastar.com Delta Star, Inc. June 23 rd 2015 Introduction

More information

Optimization of power transformers based on operative service conditions for improved performance

Optimization of power transformers based on operative service conditions for improved performance 21, rue d Artois, F-75008 PARIS A2-207 CIGRE 2012 http : //www.cigre.org SUMMARY Optimization of power transformers based on operative service conditions for improved performance A.Prieto, M.Cuesto, P.Pacheco,

More information

ABB Power Products Service

ABB Power Products Service Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?

More information

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa

More information

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONTENTS COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONSTRUCTION... 4 ~ 5 A. CORE AND FRAME... 4 B. COIL... 5 C. TEMPERATURE INDICATOR... 5 CHARACTERISTICS... 6 MANUFACTURING FACILITIES...

More information

Transformer Design: Economics & Reliability

Transformer Design: Economics & Reliability Transformer Design: Economics & Reliability Weidmann-ACTI Inc. Technical Conference New Diagnostic Concepts for Better Asset Management November 8 10, 2004 Holiday Inn Capitol Plaza, Sacramento, CA H.

More information

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER JESSE M LOPEZ CPS ENERGY USA EMILIO MORALES CRUZ QUALITROL USA SUMMARY Power transformers are essential

More information

Transformer Technology Seminar Winding Selection

Transformer Technology Seminar Winding Selection Pomona, CA May 24 25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Windings: Page 2 Example GSU 274/464MVA H0 H1 H2 H3 U U I I H L H L N = N N = N L H H L HV: 405kV ±8x1.25%

More information

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION - S K Mishra & S K Das NHPC Ltd O&M Division 1 PRESENTATION COVERS Introduction DESCRIPTION OF EVENTS INITIAL RESPONSE DETAILED INSPECTION

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

Effective maintenance test techniques for power transformers

Effective maintenance test techniques for power transformers Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure

More information

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)

More information

Power Transformers Basics

Power Transformers Basics Power Transformers Basics Transformer Basic Objective Introduce Basic Transformer Theory as it Relates to Diagnostics Provide a Better Understanding of the Diagnostic Test Environment Identify Important

More information

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...

More information

Performing reliable and reproducible frequency response measurements on power transformers

Performing reliable and reproducible frequency response measurements on power transformers Topic Performing reliable and reproducible frequency response measurements on power transformers Prof. Dr. Stephanie Uhrig, Munich University of Applied Sciences Michael Rädler, OMICRON electronics GmbH

More information

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

PAPER. Dry-type transformer innovation: HiDry 72 for subtransmission lines

PAPER. Dry-type transformer innovation: HiDry 72 for subtransmission lines PAPER Title Dry-type transformer innovation: HiDry 72 for subtransmission lines Registration Nº: (Abstract) Authors of the paper Name Country e-mail Martin Carlen Switzerland martin.carlen@ch.abb.com Mariano

More information

Efacec work every day to anticipate solutions for a sustainable world in the new energy era.

Efacec work every day to anticipate solutions for a sustainable world in the new energy era. Transformers Efacec is the largest industrial portuguese company of the electric and electromechanical sector developing high technology products, solutions and systems used every day by millions of people

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

POWER TRANSFORMERS CATALOGUE

POWER TRANSFORMERS CATALOGUE COMPANY INFORMATION ARTRANS S.A. started off as a small factory in April 2, 1982 located in Mendoza, Argentina. Now, three decades later it is a globally recognized manufacturer of distribution, transmission,

More information

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch. Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON Transformers Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer

More information

Working Group Members

Working Group Members POWER TRANSFORMER - STANDARDISATION MANUAL 6 Chapter - 7 Design Review Working Group Members Mr. M. Vijayakumaran ALSTOM Ltd Mr. S. K. Negi Mr. Y. V. Joshi GETCO GETCO 6 POWER TRANSFORMER - STANDARDISATION

More information

3. COMBINED TRANSFORMERS Oil-paper insulation

3. COMBINED TRANSFORMERS Oil-paper insulation 3. COMBINED TRANSFORMERS Oil-paper insulation 123 kv Combined transformers. 26 Instrument transformers High voltage INTRODUCTION Combined instrument transformers contain a current transformer and an inductive

More information

Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods

Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods Topic Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods Abstract: Bushing diagnosis can include various methods, from a simple visual inspection or a conventional

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60076-7 First edition 2005-12 Power transformers Part 7: Loading guide for oil-immersed power transformers IEC 2005 Copyright - all rights reserved No part of this publication

More information

Energy Division. Bowthorpe LV/MV Surge Arresters

Energy Division. Bowthorpe LV/MV Surge Arresters Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early

More information

Insulation Level and Test Technology of. 1000kV Power Transformer

Insulation Level and Test Technology of. 1000kV Power Transformer Insulation Level and Test Technology of 1000kV Power Transformer Li Guangfan, Wang Xiaoning, Li Peng et al HIMALAYAL - SHANGHAI - CHINA Abstract: The insulation coordination for the first 1000kV UHVAC

More information

2. Group Discussion Meeting in Paris Session 2014

2. Group Discussion Meeting in Paris Session 2014 CIGRE 2014 A2-00 SPECIAL REPORT FOR GROUP A2 (Transformer) Pawel WARCZYNSKI Energopomiar Elektryka - Poland - PS1 Gerhard GREVE - ABB AG Germany - PS2 Raj AHUJA SPX Corporation United States of America

More information

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of

More information

Winding Temperature Measurement in a 154 kv Transformer Filled with Natural Ester Fluid

Winding Temperature Measurement in a 154 kv Transformer Filled with Natural Ester Fluid J Electr Eng Technol Vol. 8, No. 1: 156-162, 2013 http://dx.doi.org/10.5370/jeet.2013.8.1.156 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Winding Temperature Measurement in a 154 kv Transformer Filled

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

Mots clés Power Transformer, Condition Assessment, On-line Monitoring Internet. Par S. Tenbohlen *, T. Stirl, M. Rösner * * ALSTOM T&D, Germany

Mots clés Power Transformer, Condition Assessment, On-line Monitoring Internet. Par S. Tenbohlen *, T. Stirl, M. Rösner * * ALSTOM T&D, Germany Benefit of sensors for on-line monitoring systems for power transformers Mots clés Power Transformer, Condition Assessment, On-line Monitoring Internet Par S. Tenbohlen *, T. Stirl, M. Rösner * * ALSTOM

More information

HOW TO SAFE GUARD THE TRANSFORMER..???

HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various

More information

Transformer Shunt Fault Detection using Two Techniques

Transformer Shunt Fault Detection using Two Techniques Transformer Shunt Fault Detection using Two Techniques Swathy Sasikumar 1, Dr. V. A. Kulkarni 2 P.G. Student, Department of Electrical Engineering, Government College of Engineering, Aurangabad, Maharashtra,

More information

Liquid-Filled Transformers

Liquid-Filled Transformers Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of

More information

Federal Power Transformers LLC based in Abu Dhabi, UAE

Federal Power Transformers LLC based in Abu Dhabi, UAE www.fpt.ae Federal Power Transformers LLC based in Abu Dhabi, UAE CONTENTS The Company...03 Design Process...05 Manufacturing...07 Testing...11 Quality...13 After Sales Support & Other Services...15 Satisfied

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

CIGRE Liaison Report

CIGRE Liaison Report Agenda October 22nd, 2012 CIGRE Liaison Report Overview of CIGRE 44 th Session U.S. Representation in CIGRÉ Study Committees Details on A2 Study Committee Details on B3 Study Committee Details on D1 Study

More information

Transformer Technology Seminar GIC Capability of Power Transformers

Transformer Technology Seminar GIC Capability of Power Transformers Pomona CA, May 24-25, 2016 Transformer Technology Seminar GIC Capability of Power Transformers Siemens AG Transformers siemens.com/answers Geo-magnetic Induced Current GIC resistant Transformers page 2

More information

Acoustic Emission in power transformers. Ajusco 15, Colonia Portales, Delegación Benito Juárez, C.P , México, D.F.

Acoustic Emission in power transformers. Ajusco 15, Colonia Portales, Delegación Benito Juárez, C.P , México, D.F. Acoustic Emission in power transformers 1 More expensive equipment in the substation Many years of operation First indication of a problem: Dissolved Gases Begin investigation to determine the origin of

More information

The measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation

The measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation DIAGNOSIS The measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation Introduction The Dielectric Dissipation Factor (DDF) is known as the loss factor or

More information

Revision of C Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components. Mike Spurlock Chairman

Revision of C Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components. Mike Spurlock Chairman Revision of C57.143-2012 Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components Mike Spurlock Chairman All participants in this meeting have certain obligations under

More information

CAST RESIN DRY TRANSFORMER

CAST RESIN DRY TRANSFORMER CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Arc Suppression Coils

Arc Suppression Coils Arc Suppression Coils (22kV Arc Suppression Coils ) Introduction Resonance grounding by Petersen coils (Arc Suppression Coils) has been used in Scandinavia and other European countries for some eighty

More information

Transformer Factory Testing

Transformer Factory Testing Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification

More information

Dielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction

Dielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction DIAGNOSIS ABSTRACT Dielectric tests have been used for decades for diagnosis of power transformers and bushings. In addition to the traditional tests at line frequency, modern types of dielectric tests

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION IEC TS 60076-14 First edition 2004-11 Power transformers Part 14: Design and application of liquid-immersed power transformers using high-temperature insulation materials This English-language

More information

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS AS 60044.1 2007 AS 60044.1 2007 Australian Standard Instrument transformers Part 1: Current transformers (IEC 60044-1 Ed.1.2 (2003) MOD) This Australian Standard was prepared by Committee EL-013, Measurement

More information

Convincing technology creates compact performance

Convincing technology creates compact performance siemens.com/energy Convincing technology creates compact performance The GEAFOL Basic: the optimum foundation for power distribution Answers for energy. Contents The GEAFOL Basic: A true GEAFOL and more

More information

Regional Technical Seminar

Regional Technical Seminar Regional Technical Seminar TRANSFORMER 101 Transformer 101 Dharam Vir Vice President of Engineering Dharam.Vir@spx.com Agenda 1.Review transformers: How they work (textbook vs reality) 2.How do we build

More information

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT

More information

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications: SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument

More information

Onsite Mobile AC High Voltage Test System

Onsite Mobile AC High Voltage Test System TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument

More information

Regional Technical Seminar SHORT CIRCUIT FORCES

Regional Technical Seminar SHORT CIRCUIT FORCES Regional Technical Seminar SHORT CIRCUIT FORCES Short Circuit Forces Wallace Exum Electrical Design Engineer wallace.exum@spx.com Agenda 1. What is Short Circuit 2. Types of Faults 3. How to Calculate

More information

Maintenance & Diagnosis Strategies. for. High Voltage Substations

Maintenance & Diagnosis Strategies. for. High Voltage Substations Maintenance & Diagnosis Strategies for High Voltage Substations 1/ 52 Robin Fischer, 28 April 2004 Diagnosis of Substation Equipment Power Transformers Instrument Transformers Switch-Gears Breakers Coils

More information

- Continuous real-time measurement and PD trend analysis; not multiplexed data collection.

- Continuous real-time measurement and PD trend analysis; not multiplexed data collection. QTMS The transformer monitor shall provide data integration platform, cooling supervision & monitoring. User configurable without need of a technician, a 100% configurable to specific customer requirement.

More information

Cholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service

Cholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service Cholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service Andrew Morin, Richard Barnes, Kyle Wiedeman, Scott Lederhos, Kenneth

More information

Life Prediction of Mold Transformer for Urban Rail

Life Prediction of Mold Transformer for Urban Rail , pp.13-18 http://dx.doi.org/10.14257/astl.2014.48.03 Life Prediction of Mold Transformer for Urban Rail Hyun-il Kang and Won-seok Choi Department of Electrical Engineering, Hanbat National University,

More information

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual

More information

Automatic Transformer Winding Analyser

Automatic Transformer Winding Analyser 2293 Automatic Transformer Winding Analyser The 2293 is an automatic winding analyser, optimized for three phase power and distribution transformer measurements. It uniquely combines winding resistance

More information

HOT SPOT STUDIES FOR SHEET WOUND TRANSFORMER WINDINGS

HOT SPOT STUDIES FOR SHEET WOUND TRANSFORMER WINDINGS HOT SPOT STUDIES FOR SHEET WOUND TRANSFORMER WINDINGS Sheldon P. Kennedy, Thomas Gordner Niagara Transformer Jean-Noel Bérubé Qualitrol / Neoptix Robert Ringlee, Jacques Aubin Consultant ABSTRACT Application

More information

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation CIGRE SC A1 & D1 JOINT COLLOQUIUM October 24, 2007 Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation S. A. BHUMIWAT Independent Consultant

More information

Variation in SFRA plot due to design and external parameter

Variation in SFRA plot due to design and external parameter Chapter 6 Variation in SFRA plot due to design and external parameter 6.1 Introduction As the experience grows with Sweep Frequency Response Analysis in world, it is useful to discuss the measurements

More information

AS/NZS :2013 (IEC , , MOD)

AS/NZS :2013 (IEC , , MOD) AS/NZS 60076.7:2013 (IEC 60076-7, Ed. 1.0 2005, MOD) Australian/New Zealand Standard Power transformers Part 7: Loading guide for oil-immersed power transformers AS/NZS 60076.7:2013 AS/NZS 60076.7:2013

More information

Autotransformer Condition Monitoring Systems

Autotransformer Condition Monitoring Systems Autotransformer Condition Monitoring Systems The Bidders shall offer separately the following systems of par.1 Integrated Condition Monitoring System and par.2 UHF PD Monitoring System. Two systems following

More information

We can classify test failure modes in power transformers according to transformer components

We can classify test failure modes in power transformers according to transformer components ON-SITE TESTS We can classify test failure modes in power transformers according to transformer components ABSTRACT To prevent unexpected outages it is necessary to implement a field test programme. It

More information

PD Diagnostic Applications and TechImp solutions

PD Diagnostic Applications and TechImp solutions PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006

More information

N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon

N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon POWER TRANSFORMERS Factory condition POWER TRANSFORMERS Site condition POWER TRANSFORMER FAULTS Faults in a Transformer 1. Internal Faults

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

TECHIMP Power Transformer Monitoring

TECHIMP Power Transformer Monitoring TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power

More information

Substation Preventive Maintenance

Substation Preventive Maintenance Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS

More information

Design Improvement by Diagnostics of Transformers still in Operation and of Apparatuses taken out of Service

Design Improvement by Diagnostics of Transformers still in Operation and of Apparatuses taken out of Service Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006 "New Diagnostic Concepts for Better Asset Management" Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque,

More information

Matz Ohlen Director Transformer Test Systems. Megger Sweden

Matz Ohlen Director Transformer Test Systems. Megger Sweden Matz Ohlen Director Transformer Test Systems Megger Sweden Frequency response analysis of power transformers Measuring and analyzing data as function of frequency, variable frequency diagnostics Impedance

More information

INCREASE TRANSFORMER RELIABILITY AND AVAILBILITY: FROM CONDITION ASSESSMENT TO SITE REPAIR

INCREASE TRANSFORMER RELIABILITY AND AVAILBILITY: FROM CONDITION ASSESSMENT TO SITE REPAIR INCREASE TRANSFORMER RELIABILITY AND AVAILBILITY: FROM CONDITION ASSESSMENT TO SITE REPAIR Pierre Lorin Pravin Khanna Peter Werle Lars Eklund pravin.t.khanna@us.abb.com peter.werle@de.abb.com ABB Transformers

More information

Power Factor Insulation Diagnosis: Demystifying Standard Practices

Power Factor Insulation Diagnosis: Demystifying Standard Practices Power Factor Insulation Diagnosis: Demystifying Standard Practices Dinesh Chhajer, PE 4271 Bronze Way, Dallas Tx Phone: (214) 330 3238 Email: dinesh.chhajer@megger.com ABSTRACT Power Factor (PF) testing

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

MV Power Cable Testing Training

MV Power Cable Testing Training MV Power Cable Testing Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Since power cables are used

More information

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA Taking into account that power transformer is the major item of equipment in power systems, its correct operation is vital to system operation. It is well known that transformer failures are sometimes

More information

B3-102 THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV SUBSTATIONS

B3-102 THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV SUBSTATIONS 21, rue d'artois, F-75008 Paris http://www.cigre.org B3-102 Session 2004 CIGRÉ THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

Technical recommendation for the purchase of Real Time Thermal Rating for transformers

Technical recommendation for the purchase of Real Time Thermal Rating for transformers Version: 1.0 Date of Issue: December 2014 1 Technical recommendation for the purchase of Real Time Thermal Rating for transformers 1 Purpose The purpose of this document is to set out and describe the

More information

EE223D: Distribution Power Transformer

EE223D: Distribution Power Transformer EE223D: Distribution Power Transformer Aug 07-09, 2018 / Dubai EE223 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: This intensive course is designed to provide participants with the skills

More information

Power transformers for Network, Rectifiers, Furnace

Power transformers for Network, Rectifiers, Furnace E N G L I S H OTN, OTR, OTF Transformers Power transformers for Network, Rectifiers, Furnace TTR TTO OTN, OTR, OTF reactors TTH OTN, OTR, OTF Transformers Technology Design Our designers experience combined

More information

Primary Test Manager (PTM) Testing and management software for primary assets

Primary Test Manager (PTM) Testing and management software for primary assets Primary Test Manager (PTM) Testing and management software for primary assets Asset diagnostics now easier than ever How well do you know your assets? High-voltage assets are subjected to aging and wear

More information