RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS
|
|
- Harold Harrell
- 6 years ago
- Views:
Transcription
1 RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM) & Amit Roy Singal, Asst. Director (HE&RM). Presented by: Rakesh Kumar, Director (HE&RM), CEA
2 INTRODUCTION Renovation, Modernization, Uprating and Life Extension (RMU&LE) has been recognized worldwide as a well proven cost effective technique for improving the performance, efficiency and reliability of old Hydro Power Plants (HPPs). Generator Transformer is one of the most important and costly component of power generation next only to the generator. Any discussion on the topic of Life Extension of the generating station will not be complete without discussing the ways and means of Life Extension of the Generator Transformers.
3 AGEING OF GENERATOR TRANSFORMERS Ageing of solid insulation materials like Paper, Press Board,Wood based laminates etc. Ageing and degradation of Insulating Oil. Wear and tear of moving parts like Tap Changing Mechanism, Pressure Relief Device, Monitoring equipments etc. Corrosion of metallic parts exposed to atmosphere. In addition to the above, accelerated ageing taking place in the transformer on account of the following abnormal operating conditions: Overloading of Transformers. Operation under overvoltage conditions. Impact of lightning/ switching surges from the system. Operation under short circuit conditions.
4 TESTS ON GENERATOR TRANSFORMERS Dissolved Gas Analysis (DGA) of transformer oil. Monitoring of water content in transformer oil. Monitoring of Capacitance and Tan-Delta values of Condenser Bushing. Partial Discharge (PD) measurement. Winding Resistance Measurement Percentage Impedance Measurement Insulation Resistance Test Furan Analysis Magnetizing Current Test Sweep Frequency Response Analysis (SFRA) DIRANA Test Harmonics Measurement
5 DISSOLVED GAS ANALYSIS (DGA) Number of gases are produced as by-products of the ageing taking place in the insulating materials 1. Hydrogen 5. Acetylene 2. Methane 6. Carbon Dioxide 3. Ethane 7. Carbon Monoxide 4. Ethylene 8. Oxygen
6 MECHANISM OF GAS GENERATION IN TRANSFORMERS Partial Discharge in Oil Large amount of H 2 and little CH 4 Arcing in Oil (Power Discharge) Large amount of H 2 and C 2 H 2 Oil Overheating CH 4, C 2 H 6, C 2 H 4 are formed in increasing order of severity Traces of C 2 H 2 in case of very high temperatures Cellulose Overheating by Electric Fault Large quantities of CO & CO 2
7 DISSOLVED GAS ANALYSIS (DGA) Method recommended by CIGRE Task force Gas Concentration Ratios Ratio Value Indication C 2 H 2 /C 2 H 6 H 2 / CH 4 CO 2 / CO C 2 H 2 / H 2 >1 >10 >10 <3 >2 (with C 2 H 2 >30) Discharge Partial discharge Cellulose overheating Cellulose degradation by electric fault Fault gases diffusing into main tank from OLTC
8 DISSOLVED GAS ANALYSIS (DGA) Method recommended by IEC (1999) Concentration ratio between gases Case Characteristic fault C 2 H 2 /C 2 H 4 CH 4 /H 2 C 2 H 4 /C 2 H 6 CO 2 /CO C 2 H 2 /H 2 O 2 /N 2 PD Partial discharges (*) < 0.1 < D1 Low energy discharges > > D2 High energy discharges > T1 Thermal fault (<300 o C) (*) (*) < T2 Thermal fault (300,700 o C) <0.1 >1 1, T3 Thermal fault (>700 o C) <0.2 >1 > Cellulose (paper) degradation by electric fault Fault gases diffusing into main tank from OLTC Excessive consumption of oxygen as a result ofoil oxidation and/or paper ageing < >2to <0.3 (*) Not significant Note: In some countries, the ratio CH 4 /H 2 is used instead of C 2 H 4 /C 2 H 6.
9 WATER CONTENT MEASUREMENT Hydrogen generated during ageing combines with the free oxygen present in the oil and forms water. A part of this is absorbed by the cellulose insulation and the balance remains as moisture in oil. As paper is highly hygroscopic in nature, when transformer is filled with oil, it absorbs the moisture from oil, which affects its insulation properties as well as reduces its life System Voltage of Transformer kv Water content ppm, max. Above Up to and including
10 TAN DELTA AND CAPACITANCE ON WINDINGS AND BUSHINGS This test is used to assess the condition of the oil and cellulose in terms of moisture, insulation, etc. The advantage of this method is that it identifies the winding (HV or LV) that has a possible problem. Dissipation factor of 0.5% is considered high whereas value of 1% is considered hazardous for operation of transformer and may require its replacement if completed its normal operating life. Capacitance value of bushing in service need to be compared with factory test result value for deciding the extent of degradation.
11 WINDING RESISTANCE MEASUREMENT Transformer winding resistance measurement is carried out to calculate the I 2 R losses and to calculate winding temperature at the end of a temperature rise test. Winding resistance result should not vary by 5% with factory test results or duplicate transformer result.
12 PERCENTAGE IMPEDANCE MEASUREMENT The percentage impedance of a transformer is the volt drop on full load due to the winding resistance and leakage reactance expressed as a percentage of the rated voltage. Test results must verify the nameplate rating. Percentage error should be within 3%.
13 INSULATION RESISTANCE TEST Insulation resistance tests are made to determine insulation resistance between individual windings to ground or between individual windings. It shows the condition of insulation.
14 POLARIZATION INDEX TEST It is a ratio of the Insulation Resistance Measured for 10 minutes to the insulation resistance value measured after 1 minute. PI is a good indication of winding contamination, moisture ingress (leakage currents), and/or bulk insulation damage (conduction currents). Acceptable PI for Power Transformers is greater than 1.5. For Distribution Transformer, it should be at least 1.3.
15 DEGREE OF POLYMERISATION (DP) Remnant life of a transformer in service depends mainly on the degree of degradation of the insulating materials DP is the average molecule size and closely relates to the mechanical properties of paper Early and precise diagnosis of degradation not possible through DGA. IEEE C57.91 loading guide mentions that one should be able to operate a transformer well dried, oxygen free, and with 110 deg C hotspot for 135,000 hours until 25% of retained tensile strength (75% loss), or 150,000 hours until a DP of 200 is reached (80% loss of tensile strength).
16 LIFE ASSESSMENT BY DP METHOD
17 Limitations DEGREE OF POLYMERISATION (DP) Test is invasive in nature. Sample can be taken only after taking the equipment out of service. Taking paper sample is a tedious job. Collected sample may not be representative of entire insulation.
18 FURAN ANALYSIS The concentration of furans in the mineral oil of a power transformer is a good indicator of the condition of the cellulose materials such as paper, pressboard and cotton tapes used for insulation. Not an oil quality test. Historically used as a major input for RLA of transformers. Furan analysis is used as a supplement along with DGA & DP tests Limiting value of total furanic content is Good Health : <3mg/Kg Satisfactory health : 3-5 mg/kg Deteriorated health : >5mg/Kg
19 MAGNETIZING CURRENT TEST Magnetizing current test of Transformer is performed to locate defects in the magnetic core structure, shifting of windings, failure in turn-to-turn insulation or problem in tap changers. Useful in distinguishing between severe and less severe cases. An agreement to within 25% of the measured exciting current with the previous test is usually considered satisfactory. If the measured exciting current value is 50% higher than the value measured during pre-commissioning checks, then the winding needs further analysis.
20 SWEEP FREQUENCY RESPONSE ANALYSIS (SFRA) This test passes a range of frequencies (between 10 Hz to 2 MHz) through the transformer and then calculates the transfer function. From these responses, the mechanical condition can be assessed. Reliable and sensitive method to evaluate the mechanical and electrical integrity of transformers active part. FRA is also carried out periodically for detection of deformation of smaller magnitude, when transformer experiences several short circuit forces. Helps in monitoring health and condition assessment of transformers.
21 DIELECTRIC RESPONSE ANALYSER (DIRANA) TEST DIRANA determines the water content in paper without the need of oil sampling. It combines Frequency Domain Spectroscopy (FDS) and Polarization Depolarization Current (PDC+) The power dissipation factor of the insulation is measured over a wide frequency ranging from the µhz to the khz region. The resulting curve contains information about the insulation condition. The very low frequencies contain information on moisture in the solid insulation, while the position of the slope in the mid-range frequencies indicates the conductivity of the liquid insulation. DIRANA is the only device which compensates the influence of ageing byproducts. Otherwise, this would lead to an overestimation of the water content in aged transformers.
22 HARMONICS MEASUREMENT The harmful effects of harmonic voltages and currents on transformer performance often go unnoticed until an actual failure occurs. Application of non-sinusoidal excitation voltages to transformers increase the iron losses in the magnetic core of the transformer. A more serious effect of harmonic loads served by transformers is due to an increase in eddy current losses. The increase in transformer eddy current loss due to harmonics has a significant effect on the operating temperature of the transformer.
23 Insulation section TYPICAL CASE STUDY Test Results RLA Study on 5.888MVA, 6.6/66kV Generator Transformer in about 40 Year Old Hydro Power Plant Insulation Resistance 60sec (G ) Polarization Index Tan (%) Moisture content (%) HV Winding versus LV Winding connected to Grounded Tank HV Winding versus LV Winding (Ungrounded) LV Winding versus HV Winding connected to Grounded Tank Oil Test DGA Furan Analysis Parameters within permissible limits High concentration of ethylene 4.8 mg/kg
24 OBSERVATIONS ON TEST RESULTS Insulation Resistance shows poor condition of insulation. PI values less than 1 are questionable. Limit of Tan Delta for aged transformer is 1%. Tan Delta values for this transformer are very poor. Results largely exceed normal limits as per service life and indicate over ageing of transformers. Moisture content shows that the transformer is in wet condition. The oil test results are normal and the oil parameters are within permissible limits as per IS 1866:2000. The DGA results exhibits high concentration of ethylene gas indicating possible overheating or thermal fault in the transformer. Furan analysis shows presence of high quantity (4.8 mg/kg) of furanic compounds. This shows poor health of paper insulation.
25 Thank You
Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa
More informationInnovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander
More informationEffective maintenance test techniques for power transformers
Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure
More informationCASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division
CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION - S K Mishra & S K Das NHPC Ltd O&M Division 1 PRESENTATION COVERS Introduction DESCRIPTION OF EVENTS INITIAL RESPONSE DETAILED INSPECTION
More informationChapter 7 Conclusion 7.1 General
Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due
More informationCholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service
Cholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service Andrew Morin, Richard Barnes, Kyle Wiedeman, Scott Lederhos, Kenneth
More informationIdentification of Overheating in Transformer Solid Insulation by Polarization Depolarization Current Analysis
2013 Electrical Insulation Conference, Ottawa, Ontario, Canada, 2 to 5 June 2013 Identification of Overheating in Transformer Solid Insulation by Polarization Depolarization Current Analysis S.A. Bhumiwat
More informationTesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis
feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationPower transformer failure management on the Eskom distribution network in Limpopo
Power transformer failure management on the Eskom distribution network in Limpopo MM Sako*, A Wessels** and JHC Pretorius*** *Eskom Holdings SOC Ltd, Distribution, Gobie Street, Menlopark, South Africa
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,
More informationTECHNIQUES AND STANDARD
TRANSFORMER TESTING TECHNIQUES AND STANDARD DEVELOPMENT BY DIEGO M. ROBALINO, PhD, PMP, MEGGER-AVO Training Institute Transformer manufacturers and field operators have always benefitted when new technologies
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationUnderstanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques
Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion
More informationPower Transformer Condition Assessment Based on Standard Diagnosis
Power Transformer Condition Assessment Based on Standard Cattareeya Suwanasri Abstract The diagnostic techniques of electrical and insulating oil testing are proposed to assess the internal condition of
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More informationOMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates
OMICRON Seminar on Substation Testing and Diagnosis October 23, 2017 Dubai, United Arab Emirates October 24, 2017 Abu Dhabi, United Arab Emirates Time Optimized Substation Asset Testing and Diagnosis Agenda
More informationMatz Ohlen Director Transformer Test Systems. Megger Sweden
Matz Ohlen Director Transformer Test Systems Megger Sweden Frequency response analysis of power transformers Measuring and analyzing data as function of frequency, variable frequency diagnostics Impedance
More informationBenefits of SFRA - Case Studies
6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO
More informationWe can classify test failure modes in power transformers according to transformer components
ON-SITE TESTS We can classify test failure modes in power transformers according to transformer components ABSTRACT To prevent unexpected outages it is necessary to implement a field test programme. It
More informationUsing the Frequency Response Analysis (FRA) In Transformers Internal Fault Detection
Using the Frequency Response Analysis (FRA) In Transformers Internal Fault Detection JALAL ABDALLAH Department of Engineering Tafila Technical University P.O. Box: 851229, code 11185-Amman JORDAN e-mail:
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationMonitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers
in cooperation with Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers BZ-MS/1 pazifik power Complete Transformer Monitoring System (TMS) ZVCM-1001 Bushing Monitoring
More informationPower Transformers Basics
Power Transformers Basics Transformer Basic Objective Introduce Basic Transformer Theory as it Relates to Diagnostics Provide a Better Understanding of the Diagnostic Test Environment Identify Important
More informationSERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT
SERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT Page TABLE OF CONTENTS POWER SYSTEM STUDY: 5 DATA COLLECTION AND NETWORK MODELLING 5 LOAD FLOW STUDY 5 SHORT CIRCUIT
More informationAssesment of health of transformer: a survey
Volume 114 No. 7 2017, 281-291 ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Assesment of health of transformer: a survey Ravi Kumar Jalli 1 Saptarshi
More informationHealth indexes for power transformers: A case study
Health indexes for power transformers: A case study Félix Ortiz, Inmaculada Fernández, Alfredo Ortiz, Carlos J. Renedo, Fernando Delgado, Cristina Fernández Electrical and Energy Engineering Department,
More informationIDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy
IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy 1 Frequency Domain Spectroscopy Hi V A Lo Ground C HL Measure at several frequencies Use
More informationREPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD.
REPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD. (DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/2015-16/Mgr(T)O&M-E-2/22
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON Transformers Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer
More informationApplication of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation
CIGRE SC A1 & D1 JOINT COLLOQUIUM October 24, 2007 Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation S. A. BHUMIWAT Independent Consultant
More informationCHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES
CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES 3.1. Introduction Power Transformer is the nerve centre of any power distribution system. The capacity of power transformers is generally decided
More informationIN ELECTRICAL ENGINEERING - I C M E T CRAIOVA
Taking into account that power transformer is the major item of equipment in power systems, its correct operation is vital to system operation. It is well known that transformer failures are sometimes
More informationTransformers handling and transport
Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary
More informationTransformer Shunt Fault Detection using Two Techniques
Transformer Shunt Fault Detection using Two Techniques Swathy Sasikumar 1, Dr. V. A. Kulkarni 2 P.G. Student, Department of Electrical Engineering, Government College of Engineering, Aurangabad, Maharashtra,
More informationPower Measurements and Basic Electrical Diagnostic Tests
Power Measurements and Basic Electrical Diagnostic Tests Instrument Basics Burden VA Sources V and I Meters V and I KVL and KCL Kelvin Connection KVL and KCL Kelvin Connection 4-Wire Technique Exclude
More informationVariation in SFRA plot due to design and external parameter
Chapter 6 Variation in SFRA plot due to design and external parameter 6.1 Introduction As the experience grows with Sweep Frequency Response Analysis in world, it is useful to discuss the measurements
More informationABB Power Products Service
Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?
More informationDiscipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1
Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationA Novel Technique to Precise the Diagnosis of Power Transformer Internal Faults
A Novel Technique to Precise the Diagnosis of Power Transformer Internal Faults U. Mohan Rao 1 & D.Vijay Kumar 2 1 Department of Electrical Engineering, National Institute of Technology, Hamirpur, H.P,
More informationTRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING
Training Title TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING Training Duration 5 days Training Date Transformer Operational Principles, Selection & Troubleshooting 5 15 19 Nov $4,250
More informationEFFECETIVE TRANSFORMER CONDITION ASSESSMENT
EFFECETIVE TRANSFORMER CONDITION ASSESSMENT Luwendran Moodley, Doble Engineering Africa Abstract. This paper details a novel approach to transformer condition assessment. This method has proven itself
More informationHands-On Transformer Testing and Maintenance
Hands-On Course Description This Hands-On course will teach you how to prioritize your transformer maintenance strategy, stretch your maintenance budget and at the same time maximize the life and condition
More informationEPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY
EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY EPS AUSTRALIA SERVICES COMPANY OVERVIEW EPS is a recognised company specialising in Electrical, Instrumentation, Structural, Mechanical and
More informationVallabh Vidyanagar, Anand, INDIA
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 1 Ver. V (Feb. 2014), PP 01-06 Interpretation of Sweep Frequency Response Analysis
More informationFIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.
Regional Technical Seminar FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC. Field Electrical Testing Applications Key Purposes of Field Electrical Testing: Receiving inspection Acceptance testing/commissioning
More informationOperational Management of Grid Transformers An Experience of POWERGRID
Operational Management of Grid Transformers An Experience of POWERGRID 1.0 Introduction P.N. Dixit, GM; S. Victor, AGM; V.K. Bhaskar, CM; Gunjan Agrawal, Manager Operation Services Department Power Grid
More informationIMPORTANCE & PROCESS OF RLA STUDIES IN ASSESSMENT OF NEED FOR R&M - A CASE STUDY. CPRI, Bengaluru
IMPORTANCE & PROCESS OF RLA STUDIES IN ASSESSMENT OF NEED FOR R&M - A CASE STUDY CPRI, Bengaluru What is RLA? RLA is a technique to examine systematically and monitor the plant, during and after service
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationWhy is water killing power transformer insulation? Water is a slow but deadly poison for power transformers
Table of Contents Why is water killing power transformer insulation? Water is a slow but deadly poison for power transformers Dielectric frequency response analysis is a powerful tool used to determine
More informationON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS
ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT
More informationB3-102 THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV SUBSTATIONS
21, rue d'artois, F-75008 Paris http://www.cigre.org B3-102 Session 2004 CIGRÉ THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV
More informationPower transformer maintenance. Field Testing.
Power transformer maintenance. Field Testing. Andrés Tabernero García Hardware Project Manager Unitronics, S.A. andres@unitronics.es www.unitronics.es Introduction The politic change in some companies
More informationDielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction
DIAGNOSIS ABSTRACT Dielectric tests have been used for decades for diagnosis of power transformers and bushings. In addition to the traditional tests at line frequency, modern types of dielectric tests
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationPresenting New Idea for Circumstance Monitoring of Transformers in Power Lines
American Journal of Electrical and Electronic Engineering, 2017, Vol. 5, No. 2, 64-68 Available online at http://pubs.sciepub.com/ajeee/5/2/5 Science and Education Publishing DOI:10.12691/ajeee-5-2-5 Presenting
More informationDEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER
DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER JESSE M LOPEZ CPS ENERGY USA EMILIO MORALES CRUZ QUALITROL USA SUMMARY Power transformers are essential
More informationField Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis
Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis Ambuj Kumar, Sunil Kumar Singh, Shrikant Singh Abstract Sweep frequency response analysis has been turning out a
More informationTransformer condition assessment with an integrated test van
Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)
More informationN S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon
N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon POWER TRANSFORMERS Factory condition POWER TRANSFORMERS Site condition POWER TRANSFORMER FAULTS Faults in a Transformer 1. Internal Faults
More informationCase Studies of Electric Power Equipment Diagnostics Using Acoustic Emission
17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission Oswaldo G. SANTOS FILHO 1, Sergio L. ZAGHETTO
More informationTransformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications
The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of
More informationBasic Principles and Operation of Transformer
Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core
More informationAndy Morin & Associates PO BOX Bellemont, AZ 86015
Andy Morin & Associates PO BOX 16115 Bellemont, AZ 86015 Boyd Davis Sr. Electrical Engineer Cholla Power Plant 4801 Frontage Road Joseph City, AZ 86032 Dear Mr. Davis, On behalf of Northern Arizona University,
More informationAdvanced Diagnostic Testing Services. Provides detailed and reliable results
Advanced Diagnostic Testing Services Provides detailed and reliable results Advanced Diagnostic Testing Services from the world s leading manufacturer of power transformers ABB leadership begins with our
More informationPrimary Test Manager (PTM) Testing and management software for primary assets
Primary Test Manager (PTM) Testing and management software for primary assets Asset diagnostics now easier than ever How well do you know your assets? High-voltage assets are subjected to aging and wear
More informationIJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):
IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): 2321-0613 Conditioning Monitoring of Transformer Using Sweep Frequency Response for Winding Deformation
More informationDiagnostic measurements on instrument transformers. Part II. A classification and overview of diagnostic measurements DIAGNOSIS EVENTS ABSTRACT
EVENTS DIGNOSIS BSTRCT Part 1 of this article, published in Vol ume 3 Issue 4, pages 100ff, describes the measurements of excitation, wind ing resistance, turns ratio and accu racy as the most common diagnostic
More informationDiagnostic measurements on instrument transformers
Diagnostic measurements on instrument transformers A classification and overview of diagnostic measurements ABSTRACT The article presents the most common diagnostic measurements on instrument transformers
More informationSAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.
Keep Powering On SAMPLE Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs. Overheating, arcing, partial discharge, and other active or slow-evolving
More informationA New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol
A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to
More informationInvestigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)
Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA) Priti G 1*, Sindekar AS 2 P.G. Scholar, Department of Electrical Engineering, Government College of
More informationTesting and Diagnostic of Power Transformers & Distribution Transformers
Testing and Diagnostic of Power Transformers & Distribution Transformers APT Power Technology Co., Ltd. Xi an FOREWORD Transformers play an very important role in power transmission and distribution system.
More informationCondition monitoring and diagnostic of large power transformers to improve its reliability and life cycle management
1 Condition monitoring and diagnostic of large power transformers to improve its reliability and life cycle management Diogo Fernando Ferreira da Silva diogo.da.silva@ist.utl.pt Técnico Lisboa Novembro
More informationImportance of Transformer Demagnetization
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Importance
More informationInsulation Assessment of Oil Impregnated Paper Condenser Bushings using Dielectric Frequency Response Technique
Indian Journal of Science and Technology, Vol 10(21), DOI: 10.17485/ijst/2017/v10i21/114368, June 2017 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 Insulation Assessment of Oil Impregnated Paper
More informationPARTIAL DISCHARGE MEASUREMENT
PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of
More informationTransformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018
Transformer Testing & Maintenance Fundamentals 1 AVO Training Institute, Inc. 2018 Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the
More informationUse of On and Offline Oil Analysis on the ESB, Distribution and Generation Networks
Reliability Ireland Conference 2016, Grand Hotel Malahide, 12-13 April 2016, Dublin, Ireland. Use of On and Offline Oil Analysis on the ESB, Distribution and Generation Networks J. Carpenter*, ESB International,
More informationCONTENTS. 1. Introduction Generating Stations 9 40
CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific
More informationCHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN
75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.
More informationTIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M
SL. NO NOMINAL DIAMETER "D" mm GASKETED JOINT (Nm) WOODEN CORE CLAMP (Nm) STEEL FIXING STUD FOR BUSHING (Nm) BUSHING STEM (Nm) (BRASS /COPPER) COPPER BUSBAR (Nm) 1 M6 5 - - - - 2 M8 12 - - 10-3 M10 22
More informationA Comparative Diagnosis Approach on Transformer s Insulating Oil Ming-Jong Lin
Information Technology and Mechatronics Engineering Conference (ITOEC 2015) A Comparative Approach on Transformer s Insulating Oil Ming-Jong Lin No. 11 North Road Nanke, Shanhua District, Tainan City,
More informationPower Transformer Testing
Power Transformer Testing Course No: E03-041 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)
More informationHIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24
LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should
More informationUsing DFR to determine dissipation factor temperature dependence
Using DFR to determine dissipation factor temperature dependence by Matz Ohlen and Peter Werelius, Megger With an aging power component population, today s electrical utility industry faces a tough challenge
More informationCorrelation between time and frequency domain polarisation measurements for transformer moisture assessment
Australasian Universities Power Engineering Conference (AUPEC 24) 26-29 September 24, Brisbane, Australia Correlation between time and frequency domain polarisation measurements for transformer moisture
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationSoftware System for Finding the Incipient Faults in Power Transformers
Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationA Study of Winding Failure Modes in Laboratory Scale Transformers
The University of Western Australia School of Mechanical and Chemical Engineering A Study of Winding Failure Modes in Laboratory Scale Transformers Li Zhu B.E. Mechanical Engineering Submitted for the
More informationHOW TO SAFE GUARD THE TRANSFORMER..???
CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various
More informationBachelor s thesis in Technology for the degree of Bachelor of Science in Technology submitted for inspection in Vaasa, 7 th of September, 2010.
UNIVERSITY OF VAASA FACULTY OF TECHNOLOGY ELECTRICAL ENGINEERING Markku Taikina-aho SURVEY OF TRANSFORMER FAILURE CAUSES AND CONSEQUENCES Bachelor s thesis in Technology for the degree of Bachelor of Science
More informationAcoustic Emission in power transformers. Ajusco 15, Colonia Portales, Delegación Benito Juárez, C.P , México, D.F.
Acoustic Emission in power transformers 1 More expensive equipment in the substation Many years of operation First indication of a problem: Dissolved Gases Begin investigation to determine the origin of
More informationHOLISTIC APPROACH TO ON-LINE TRANSFORMER MONITORING: KNOWLEDGE MANAGEMENT FIRST!
HOLISTIC APPROACH TO ON-LINE TRANSFORMER MONITORING: KNOWLEDGE MANAGEMENT FIRST! M. Tozzi, E. Savorelli, A. Mudryk, M. Skelton Camlin Power Ltd N. Ireland SUMMARY This paper describes a method to convert
More information