1 CONTENTS 1 LV MAINS AND SERVICES 1.1 Scope Definitions Introduction Design Information Construction Information 6 Appendix A GA Drawings and Materials Mains 11 Appendix B GA Drawings and Materials Services 30 Appendix C GA Drawings and Materials Pole-Mounted Equipment 39 Appendix D GA Drawings and Materials Earthing 48 Appendix E Data for,, 4 x 120mm 2 52 Appendix F Data for,, 4 x 95mm 2 55 Appendix G Data for,, 2 x 95mm 2 58 Appendix H Data for,, 4 x 35mm 2 61 Appendix I Data for,, 2 x 35mm 2 63 Appendix J Service Spans 66 Appendix K Un-stayed Supports 68

2 1.1 SCOPE All new or substantially altered Aerial Bundled lines shall be designed and constructed to this section. When working on existing lines that are not being substantially altered, legacy design standards will apply. LV structures can be considered as one of three distinct types for design and construction purposes: LV distribution networks supported on wood poles. LV service connections (excludes terminations within property). LV pole-mounted equipment. LV supported on buildings The above types of construction comprise of the number of cores and cross-sectional areas shown below:,, 2x35mm 2.,, 2x95mm 2.,, 4x35mm 2.,, 4x95mm 2.,, 4x120mm 2. Note: This construction section is not an instruction manual for safe erection of an overhead line, nor is it a standalone tender document. It should be used in conjunction with the Overhead Line Craft Manual and in accordance with the relevant specific job instruction. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 1

3 1.2 DEFINITIONS Term CNE EDS ENA TS FoS GA JCs LV IPC Manufacturer MWT NI PME SJI UKPN XLPE Description Aerial Bundled Combined Neutral Earth Every Day Stress Energy Networks Association Technical Specification Factor of Safety General Arrangement Job Cards Low Voltage Insulation Piercing Connector An Organisation Supplying Equipment for use on UK Power Networks Networks Maximum Working Tension Not Illustrated (i.e. item numbers on Figures) Protective Multiple Earthing Specific Job Instructions UK Power Networks Cross-linked Polyethylene Page 2 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

4 1.3 INTRODUCTION This section covers general design and construction requirements. How to construct and maintain is detailed in the Overhead Line Craft Manual. Appendix A to C of this section comprises of General Arrangement (GA) drawings with associated lists of materials for LV structures as follows: Appendix A comprises GAs for LV distribution networks supported on wood poles. Note: 'inside' and 'outside' angles are not as defined in ENA TS 'Insulated Aerial Bundled s Erection Requirements for Low Voltage Overhead Distribution Systems'. Appendix B comprises GAs for LV service connections, followed by a GA summarising and CNE service spans. Appendix C comprises GAs for LV pole-mounted equipment. Appendix D comprises GAs for earthing requirements. Each list of materials identifies the components included in the associated GA and which supplementary items are needed to complete that structure. Variations within each GA for different conductors are covered by different columns in the associated list of materials. Note: The lists of materials for the connections and plant shown in Appendix B and Appendix C do not include the materials for the associated GA structure; many combinations are possible and it is not practical to cover every possible structure/connection variation here (refer to Appendix A for approved GA structures and materials.) Appendices E to K are tables of design data for this section. Each appendix relates to a separate type. This section fits into the overall design and construction process as outlined by the following summary: 1. Carry out a risk assessment. 2. Generate a proposal taking into account the risk assessment. 3. Generate a proposal for a new line. 4. Choose a proposed route and carry out a line survey. 5. Plot pole positions, heights and clearances (clearance shall comply with ENA TS 'OHL Clearances'), and develop a line profile. Note: The development of a line profile will require some data and parameters from Appendix E and subsequent appendices. 6. Compile a list of materials using the GAs and supplementary items identified in this section (Appendix A, Appendix B, Appendix C.) The GAs and supplementary items shall be selected and used in accordance with the design and construction information within this section, and the data given in subsequent appendices. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 3

5 1.4 DESIGN INFORMATION General Practice Risk Assessment Earthing Design Data Constraints on the Lengths of Main Integration with Existing Lines General Practice Lines shall be designed using the GAs and supplementary items from Appendix A, Appendix B, Appendix C and the data from Appendix E to K. The following information shall be taken into account during the design process Risk Assessment A risk assessment shall be carried out at the commencement of the design work to identify the site specific safety hazards. The design shall incorporate mitigation measures to control the risks, identified in the risk assessment, associated with the construction, operation and maintenance of the proposed overhead line and its suitability compared with an underground cable solution Earthing System earthing and bonding shall be in accordance with Section 3 Earthing and Bonding, of the Overhead Line Craft Manual. To provide a PME network, the connection from the neutral of the bundle to the earth electrode(s) shall be installed and connected in accordance with the drawings given in Appendix D (the PME connections are split across two drawings because all pole-mounted equipment GAs incorporate connections from bundle neutral to neutral/earth as mandatory requirements) Design Data Each set of design data (Appendix E to K) contains all the information necessary for the conductor bundle specified, with the exception of poles supporting electrical plant. Design parameters used to construct the tables of design data are given for reference. Note: The basic span for this design is 50m. If is to be installed onto an existing pole, it is then assumed that the pole depth will be 1500mm. The maximum wind span shall then be limited to the figures supplied in each appendix. If an existing pole has to be changed due to decay or clearance problems then refer to tables for planting depth for new build. For poles supporting electrical plant, pole loadings should be re-calculated as necessary. Note: 1000kg additional weight can be approximated to 1000kgf additional loading for this purpose. Data in Appendix E to I are based on the minimum pole diameters included in BS In practice, if it is found that pole loadings exceed the values given in Appendix E to I the minimum pole-top diameter needs to be re-calculated. Maximum service spans shall be in accordance with Figure B5 Concentric Service Spans and Figure B6 Service Spans. Page 4 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

6 1.4.5 Constraints on the Lengths of Main The maximum length of is limited by earth loop impedance, the size of the supplying fuse and the transformer size in order to ensure that faults at the remote end are cleared in correct time. Reference should be made to the EDS 'LV Network Design Standard' for voltage drop and loop impedance constraints when designing LV networks Integration with Existing Lines When a new section of line is installed within an existing line, consideration must be given to the differences in line tensions that may occur. Refer to Section 5 LV Open Wire for legacy conductor data and engineering data. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 5

7 1.5 CONSTRUCTION INFORMATION General Practice Supports Clearances Overview of Clearances Tree Clearences Low Voltage Supports Augering Foundations Stays In-line Connections Plumbing LV Poles Connections to the Bundle Overview of Connections to the Bundle Service Connections Mains Connections Limit on Number of Connections to the Bundle Disconnections from the Bundle Open Points Weak Links and Trees General Practice Construction practices shall be in accordance with this Manual. For reference, phases and neutral shall be identified by the number of ribs on the insulation as follows: Phase L1 1 rib. Phase L2 2 ribs. Phase L3 3 ribs. Neutral fully ribbed. Note: This applies whenever is used e.g. when neutral is run down the pole for connection to the neutral/earth connection mm minimum Page 6 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

8 Supports All fittings supporting the system shall provide an insulating barrier rated at 1000V between the core insulation and the mechanical attachment. The shall be attached in such a manner that it cannot make contact with any steelwork or stays. Weak links will be used on all poles where there is the risk of falling trees, except for the following: Terminal, Section and Angle Poles When crosses highways/carriageways, footpaths, navigable waterways and railway tracks Clearances Overview of Clearances Clearances from external objects and structures (e.g. buildings, trees and roads) shall comply with Section 2 Safety Aspects, Procedures, Tools and Equipment, of the Overhead Line Craft Manual. In addition to this, the following rules shall be followed: 1. Wherever possible, conductors shall not pass directly over buildings and roofs. 2. Wherever it is necessary to over sail a building or roof, the relevant span shall not contain any mid-span joints. 3. Where is attached to a building which has a thatched roof, the attachment shall be a minimum of 0.5m from the thatched roof. 4. Once terminated, shall be converted to concentric cable or insulated and sheathed (mechanically protected) cable within 0.5m of the point of attachment to a building. Service cable lead-ins into the building shall be installed in accordance with the Overhead Line Craft Manual Section 6 Erect s and Pole-top Equipment Tree Clearances Where an system is erected through trees, the following points shall be considered: 1. For additional information regarding overhead line clearances, refer to Overhead Line Craft Manual Section 2 Safety Aspects, Procedures, Tools and Equipment. 2. Risks of the being abraded by trees. 3. Sag variations and conductor swing due to the effects of the wind. 4. The effect of wind and snow loading on trees or branches bearing onto the. 5. The danger of trees providing climbing access. 6. The amount of tree cutting required for compared with conventional open wire systems can be significantly reduced. However, the XLPE insulation is susceptible to abrasion and shall not be allowed to come into contact with tree trunks, mature branches or heavy outer growth, under any circumstances. 7. Clearances through trees shall take account of maximum and minimum conductor sags, conductor swing and the anticipated tree growth rate and cutting periods Low Voltage Supports All supports shall be fitted with a Safety Sign (Danger of Death) in accordance with EDS Safety Sign and Identification labelling of Equipment. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 7

9 1.5.4 Augering Augering the pole hole is the preferred method when the ground is suitable. After pole erection, the remaining hole shall be backfilled with suitable material based on soil condition. If there is a risk of movement due to poor soil conditions, then a suitable cement mixture shall be used Foundations Un-stayed angle poles shall be installed 0.5m deeper than the planting depth given in the appendices to this section (care shall be taken when planning un-stayed angle poles, particularly near walls) Stays Generally 7/3.2mm (grade 1150) stay wire and Type 1 stay anchors are suitable for lines designed to this specification. However, on 120 terminal and angle poles over 60 o where the stay spread is less than 35 o then 7/4.0 stay wire and Type 2 stay anchors are required. All stays shall be fitted with a stay insulator. Only the following types of stay are suitable for lines designed to this specification: Load-lock anchors (Light) (50% of Type 1) Screw-in (Type 2 ) Concrete blocks: Type x 300 x 90mm Type x 430 x 140mm Heavy duty stay plates are useful for structures of restricted height: the overall distance between the fixing at the top of the pole and the stay insulator is less than that of an equivalent pole-top make-off. The distance of the stay-base from the pole-base are given in Appendix E I In-line Connections Compression fittings shall be used for all tension and in-line non-tension connections (under no circumstances shall IPCs be used to make in-line connections) Plumbing LV Poles When LV poles are re-conductored they must be squared and fully plumbed level not left off center. Any poles that are leaning greater than 5 o and construction works are being carried out within the vicinity must be re-plumbed to as close to 0 o as possible. Page 8 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

10 1.5.9 Connections to the Bundle Overview of Connections to the Bundle Only to connections to the conductor bundle are permitted Service Connections For single-phase and three-phase connections to 95mm 2 and below, one single-bolt IPC shall be used on each phase conductor and two single-bolt IPCs shall be used on the neutral/earth conductor. For single-phase and three-phase connections to 120mm 2, one double-bolt IPC shall be used on each phase conductor and two double-bolt IPCs shall be used on the neutral/earth conductor (as illustrated in the appropriate GAs). Table 1 Number of IPCs Required for Mains and Service Connections Scenario Phase Neutral 120mm² Mains or Service 1 double bolt IPC 2 double bolt IPCs 95mm² Mains or Service 1 single bolt IPC 2 single bolt IPCs 35mm² Mains or Service 1 single bolt IPC 2 single bolt IPCs Mains Connections For all mains connections to 95mm 2 and below, one single-bolt IPC shall be used on each phase conductor and two single-bolt IPCs shall be used on the neutral/earth conductor. For all mains connections to 120mm 2, one double-bolt IPC shall be used on each phase conductor and two double-bolt IPCs shall be used on the neutral/earth conductor (as illustrated in the appropriate GAs) Limit on Number of Connections to the Bundle Only two single-phase or two three-phase connections to the bundle are permitted at any pole position. If this number of connections is to be exceeded then a distribution box is to be provided Disconnections from the Bundle IPCs shall not be removed from the bundle. Disconnections shall be made on the tail. Refer to Section 6 of the Overhead Lines Craft Manual for method of disconnection Open Points Fuse Links are to be used when creating or replacing an open point. Refer to Figure C2 to via Fuses GA Weak Links and Trees Where is erected within falling distance of adjacent trees, provision shall be made to protect the conductor and pole supports by fitting weak links (stores code 09385F) between the pole hook and the suspension clamp on intermediae poles. Weak Links shall not be fitted on: Terminal, Section and Angle Poles. When crosses highways/carriageways, footpaths, navigable waterways and railway tracks. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 9

11 Table 2 Service Connections Service Connections (Pole End) A B Connector Type Stores Catalogue Description and Code Size Type Size Type 16mm 2 25mm 2 35mm 2 35mm 2 Copper tail Copper tail aerial aerial 25mm 2 25mm 2 35mm 2 25mm 2 Service Connections (Property End) Concentric cable Aluminium Phase Concentric cable Aluminium Phase Concentric cable Aluminium Phase Copper Neutral Concentric cable Aluminium Phase Copper Neutral Bi-Metal Compression Joint Bi-Metal Compression Joint Pre-Insulated Compression Joint Bi-Metal Compression Joint Pre-Insulated Compression Joint Bi-Metal Compression Joint Connector Bimet Service 25 HDAL 16 CU 09209S Joint Bimetal MEP/U25-16/S (100033) 08642K Joint Bimetal MEP/U25-25/S (100035) 08643U 35mm 2 to 35mm 2 Service Compression Fitting (MJPB) 35) 08755F 35mm to 25mm Bare CU Compression Joint 08776H 35mm 2 to 25mm 2 Service Compression Fitting (MJPB 35-25) 08756Q 35mm to 16mm Bare CU Compression Joint 08775X A B Connector Type Stores Catalogue Description and Code Size Type Size Type 35mm 2 35mm 2 aerial aerial 25-35mm 2 22mm 2 25mm 2 Ali tail 22-25mm 2 35mm 2 35mm 2 35mm 2 aerial aerial aerial Concentric lead-in Aluminium Phase Copper Neutral Double Insulated Aluminium Concentric lead-in Double Insulated Aluminium Pre-Insulated Compression Joint Bi-Metal Compression Joint Pre-Insulated Compression Joint Pre-Insulated Compression Joint 16mm 2 Copper Bi-Metal Service Compression Joint 25mm 2 Copper Bi-Metal Service Compression Joint 32mm 2 Copper Bi-Metal Service Compression Joint 35mm 2 to 25mm 2 Service Compression Fitting (MJPB 35-25) 08756Q 35mm 2 to 16mm 2 Service Compression Fitting (MJPB 35-16) 08757A Bimet Service 25 AL 16 CU 08642K 35mm 2 to 25mm 2 Service Compression Fitting (MJPB 35-25) 08756Q 25mm 2 AL-25mm 2 Service Compression Fitting 09213S 35mm to 16mm Bare CU Compression Joint 08775X 35mm to 16mm Bare CU Compression Joint 08765P 35mm to 25MM Bare CU Compression Joint 08776H 35mm to 32mm Bare CU Compression Joint 08766Y Page 10 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

12 APPENDIX A GA DRAWINGS AND MATERIALS MAINS Figure Figure A1 Figure A2 Figure A3 Figure A4 Figure A5 Figure A6 Figure A7 Figure A8 Figure A9 Figure A10 Drawing Title General Drawing Arrangement Stay Arrangement, Make-off (No Auxiliary Pole-Mounted Equipment) Stay Arrangement, Make-off (Restricted Height or Auxiliary Pole-Mounted Equipment) Stay Arrangement, Stay Plate (Restricted Height, Auxiliary Pole-Mounted Equipment or Live Line Working) Intermediate GA (Outside Angle up to 30 o Line Deviation) Intermediate GA (Inside Angle up to 30 o Line Deviation) Angle Section GA (up to 20 o Line Deviation) Angle Section GA (20 o to 90 o Line Deviation) Terminal GA Tee-off Intermediate GA Figure A1 General Drawing Arrangement Bundle Safety Sign Minimum of 1800mm UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 11

13 Figure A2 Stay Arrangement, Make-Off (No Auxiliary Pole-Mounted Equipment) mm , 5 6 Datum 7 Note: For details on stay spreads refer to Appendix E, F, G, H and I. Page 12 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

14 Materials for Figure A2 Ref No. Component Light Duty Arrangement UK Power Networks Stores Code 1 Pole-top make-off (7/3.25mm) 08244Y 1 Galvanised wire staples (NI) ** 13673A 2 Guy grip dead-end (7/3.25mm) 08233F 3 Insulator stay LV ENA TS type 1 110kN 08911W 4 Stay wire 7/3.25mm 1150 grade 13816S 5 Steelwork thimble stay type P 6 Adjustable stay rod (type 1) 09734H 6 Stay marker (NI) *** 08290D 7 Concrete stay block 08101C 6 and 7* 2x Anchor stay load lock 09445D 6 and 7* Anchor stay screw-in 10" single helix 08720F 6 and 7* Turnbuckle assembly 3/4" helix anchor light 08731Y 6 and 7* Anchor stay screw-in 12" single helix 08721Q 6 and 7* Anchor stay screw-in 14" single helix 08730P * The most appropriate anchor system shall be selected. ** Staples shall be used to secure the pole-top make-off to the pole. *** Where required. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 13

15 Figure A3 Stay Arrangement, Make-off (Restricted Height or Auxiliary Pole-Mounted Equipment) mm Minimum 4, 6 7 Datum 8 Note: For details on stay spreads refer to Appendix E, F, G, H and I. Page 14 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

16 Materials for Figure A3 Ref No. Component Light Duty Arrangement UK Power Networks Stores Code 1 Pole-top make-off (7/3.25mm) 08244Y 1 Galvanised wire staples (NI) ** 13673A 2 Splice line stay wire 08246T 3 Stay wire 7/3.25mm 1150 grade 13816S 4 Guy grip dead-end (7/3.25mm) 08233F 5 Insulator stay LV ENA TS type 1 110kN 08911W 6 Steelwork thimble stay type P 7 Adjustable stay rod (type 1) 09734H 7 Stay marker (NI) *** 08290D 8 Concrete stay block 08101C 7 and 8* Anchor stay load lock 09445D 7 and 8* Anchor stay screw-in 10" single helix 08720F 7 and 8* Turnbuckle assembly 3/4" helix anchor light 08731Y 7 and 8* Anchor stay screw-in 12" single helix 08721Q 7 and 8* Anchor stay screw-in 14" single helix 08730P * The most appropriate anchor system shall be selected. ** Staples shall be used to secure the pole-top make-off to the pole. *** Where required. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 15

17 Figure A4 Stay Arrangement, Stay Plate (Restricted Height, Auxiliary Pole-Mounted Equipment or Live-line Working) 1 2, mm Minimum 2, 3 6 Datum 7 Note: For details on stay spreads refer to Appendix E, F, G, H and I. Page 16 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

18 Materials for Figure A4 Ref No. Component Light Duty Arrangement UK Power Networks Stores Code 1 Stay plate 08161E 1 Bolt M20 length 260mm c/w hex full nut (NI) 13632F 1 Washer square curved M20 (NI) 13801K 2 Guy grip dead-end (7/3.25mm) 08233F 3 Steelwork thimble stay type P 4 Stay wire 7/3.25mm 1150 grade 13816S 5 Insulator stay LV ENA TS type 1 110kN 08911W 6 Adjustable stay rod (type 1) 09734H 6 Stay marker (NI) *** 08290D 7 Concrete stay block 08101C 6 and 7* Anchor stay load lock **** 09445D 6 and 7* Anchor stay screw-in 10" single helix 08720F 6 and 7* Turnbuckle assembly 3/4" helix anchor light 08731Y 6 and 7* Anchor stay screw-in 12" single helix 08721Q 6 and 7* Anchor stay screw-in 14" single helix 08730P * The most appropriate anchor system shall be selected. ** Staples shall be used to secure the pole-top make-off to the pole. *** Where required. **** Two Load Lock anchors and staywires are required to match the rating of a concrete block or screw-in anchor. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 17

19 Figure A5 Intermediate GA (Outside Angle up to 60 o Line Deviation) 7 Alternative arrangement showing weak link to be used on Alternative arrangement showing weak link on straight line unstayed intermediate poles only intermediate poles only. 1 Note: Refer to for guidance on applications MAX Page 18 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

20 Materials for Figure A5 Ref No. Component UK Power Networks Stores Code 4x120mm 2 4x95mm 2 4x35mm 2 2x95mm 2 1 Nut M20 open-ended hook 09375W Universal suspension clamp 08869L Washer square curved M K Bolt M20 * Wood pole * Weak Link 09385F Notice danger of death (NI) 20010P Supplementary Components Needed to Complete the Structure 6 Stay * As required Notices (NI) * As required * Select to fit size of pole and conductor to be erected. 2x35mm 2 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 19

21 Figure A6 Intermediate GA (Inside Angle up to 30 o Line Deviation) MAX Page 20 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

22 Materials for Figure A6 Ref No. Component UK Power Networks Stores Code 4x120mm 2 4x95mm 2 4x35mm 2 2x95mm 2 1 Steelwork hook outrigger pole 09376G Universal suspension clamp 08869L Washer square curved M C Bolt M20 320mm 13341G Wood pole * Notice danger of death (NI) 20010P Supplementary Components Needed to Complete the Structure 6 Stay * As required Notices (NI) e.g. pole number * As required * Select to fit size of pole and conductor to be erected. 2x35mm 2 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 21

23 Figure A7 Angle Section GA (up to 20 o Line Deviation) , 5 10 MAX Page 22 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

24 Materials for Figure A7 Ref No. Component UK Power Networks Stores Code 4x120mm 2 4x95mm 2 4x35mm 2 2x95mm /50mm 2&4 Core Anchor Clamp 08853T /95mm 2&4 Core Anchor Clamp 08854D mm 4 Core Anchor Clamp 08861H Bolt eye M20 300mm 13652X mm 2 compression splice non-tension 95mm 2 compression splice non-tension 120mm 2 compression splice non-tension 08740X C M Washer square curved M K Nut eye M W Wood pole * Notice danger of death (wood poles) (NI) Supplementary Components Needed to Complete the Structure 7 Stay * As required 8 Plastic cleat * As required Notices (NI) e.g. pole number * As required * Select to fit size of pole and conductor to be erected P x35mm 2 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 23

25 Figure A8 Angle Section GA (20 o to 90 o Line Deviation) Page 24 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

26 Materials for Figure A8 Ref No. Component UK Power Networks Stores Code 4x120mm 2 4x95mm 2 4x35mm 2 2x95mm /50mm 2&4 Core Anchor Clamp 08853T /95mm 2&4 Core Anchor Clamp 08854D mm 4 Core Anchor Clamp 08861H Bolt eye M20 300mm 08052X Washer square curved M C Wood pole * Notice danger of death (wood poles) (NI) Supplementary Components Needed to Complete the Structure 5 Stay * As required Notices (NI) e.g. pole number * As required * Select to fit size of pole and conductor to be erected P x35mm 2 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 25

27 Figure A9 Terminal GA Page 26 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

28 Materials for Figure A9 Ref No. Component UK Power Networks Stores Code 4x120mm 2 4x95mm 2 4x35mm 2 2x95mm /50mm 2&4 Core Anchor Clamp 08853T /95mm 2&4 Core Anchor Clamp 08854D mm 4 Core Anchor Clamp 08861H Bolt eye M20 300mm 08052X heatshrink end cap (35 to 120mm 2 ) 08881A Washer square curved M C Wood pole * Notice danger of death (wood poles) (NI) Supplementary Components Needed to Complete the Structure 6 Stay * As required Notices (NI) e.g. pole number * As required * Select to fit size of pole and conductor to be erected P x35mm 2 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 27

29 Figure A10 Tee-off Intermediate GA Note: This drawing illustrates connections for a 120mm 2. For connections of 95mm 2 and below refer to the material lists , 6 Page 28 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

30 Materials for Figure A10 Ref No. Component UK Power Networks Stores Code 4x120mm 2 4x95mm 2 4x35mm 2 2x95mm 2 2x35mm 2 1 Universal suspension clamp 08869L Nut M20 open-ended hook 09375W mm 2 to 35mm 2 single bolt IPC connector 95mm 2 to 95mm 2 single bolt IPC connector 120mm 2 to 120mm 2 double bolt IPC connector 08845E P J /50mm 2&4 Core Anchor Clamp 08853T /95mm 2&4 Core Anchor Clamp 08854D mm 4 Core Anchor Clamp 08861H Bolt eye M20 300mm 13652X Washer square curved M K Wood pole * Notice danger of death (wood poles) (NI) 20010P Supplementary Components Needed to Complete the Structure 8 Stay * As required Cable tie (NI) 03552P As required Plastic cleat (NI) * As required Notices (NI) e.g. pole number * As required * Select to fit size of pole and conductor to be erected. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 29

31 APPENDIX B GA DRAWINGS AND MATERIALS SERVICES Figure Figure B1 Figure B2 Figure B3 Figure B4 Figure B5 Figure B6 Drawing Title Service Connection (Three-phase) GA Concentric Service Connection GA Insulated Open Wire Service Connection GA Street Lighting Service Connection GA Concentric Service Spans Service Spans Figure B1 Service Connection (Three-phase) GA Note: This drawing illustrates connections for 95mm 2 and below. For connections of 120mm 2 and below refer to the material lists Page 30 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

32 Materials for Figure B1 Ref No. Component UK Power Networks Stores Code 4x120mm 2 4x95mm 2 1 heatshrink end cap (35 to 120mm 2 ) 08881A mm 2 to 35mm 2 single bolt IPC connector 08845E mm 2 to 95mm 2 single bolt IPC connector 08846P mm 2 to 120mm 2 double bolt IPC connector 08848J Pole hook M20 x 320mm 09372S /50mm 2&4 Core Anchor Clamp 08853T /95mm 2&4 Core Anchor Clamp 08854D mm 4 Core Anchor Clamp 08861H Supplementary Components Needed to Complete the Structure 5 Plastic cleat * As required 6 Cable tie 03552P As required 4x35mm 2 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 31

33 Figure B2 Concentric Service Connection GA (3ph service cable shown) Note: This drawing illustrates connections for 95mm 2 and below. For connections of 120mm 2 refer to the material lists Materials for Figure B2 (Single Phase) Ref No. Component UK Power Networks Stores Code 1 heatshrink end cap (35 to 120mm 2 ) 08881A mm 2 to 95mm 2 service single bolt IPC connector 08845E 3** 50mm 2 to 150mm 2 service single bolt IPC connector 08847Y 3** 3 fitting non-tension * 2 4 Cable termination break-out kit 2-core 02164H mm 2 single phase service cable 05886L L* 6 fitting helical dead-end CNE 1-phase * 1 7 Insulator coach screw service 08927P 1 L* Length as required. * Select to match and service cable conductor size. ** Select to fit. CNE 1-phase 35mm 2 Page 32 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

34 Materials for Figure B2 (Three Phase) Ref No. Component UK Power Networks Stores Code 1 heatshrink end cap (35 to 120mm 2 ) 08881A mm 2 to 95mm 2 service single bolt IPC connector 08845E 3** 50mm 2 to 150mm 2 service single bolt IPC connector 08847Y 3** 3 fitting non-tension * 4 4 Cable termination break-out kit 4-core 02317J mm 2 3-phase service cable 05903U L* 6 fitting helical dead-end CNE 3-phase 08243P 1 7 Insulator coach screw service 08927P 1 Supplementary Components Needed to Complete the Structure for 3phase and Single 1phase Services CNE 3-phase 35mm 2 8 Plastic cleat * As required 9 Cable tie 03552P As required L* Length as required. * Select to match and service cable conductor size. ** Select to fit. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 33

35 Figure B3 Insulated Open Wire Service Connection GA Note: This drawing illustrates connections for 95mm 2 and below. For connections of 120mm 2 refer to the material lists Page 34 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

36 Materials for Figure B3 Ref No. Component UK Power Networks Stores Code 1 2x35mm R L* 2x95mm L L* 4x35mm Q L* 4x95mm K L* 4x120mm U L* 2 35mm 2 to 35mm 2 single bolt IPC connector 08845E ** 95mm 2 to 35mm 2 single bolt IPC connector 08847Y ** 95mm 2 to 95mm 2 single bolt IPC connector 08846P ** 120mm 2 to 35mm 2 double bolt IPC connector 08848J ** 120mm 2 to 95mm 2 double bolt IPC connector 08848J ** 120mm 2 to 120mm 2 double bolt IPC connector 08848J ** 3 heatshrink end cap (35 to 120mm 2 ) 08881A mm 2 tail 400mm long transformed insulated wire non-tension 95mm 2 tail 400mm long transformed insulated wire non-tension 120mm 2 tail 400mm long transformed insulated wire non-tension * *** * *** * *** 5 Insulator coach screw service 08927P 4 6 fitting helical dead-end * 4 Supplementary Components Needed to Complete the Structure Insulated Open-wire 7 Plastic cleat * As required 8 Cable tie 03552P As required L* Length as required. * Select to fit insulated wire. ** Select to fit (5 required for three-phase; 3 required for single-phase). *** 4 required for three-phase; 2 required for single-phase. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 35

37 Figure B4 Street Lighting Service Connection GA Note: This drawing illustrates connections for 95mm 2 and below. For connections of 120mm 2 refer to the material lists. The lamp, control gear and tails are the property of the local Street Lighting Authority Page 36 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

38 Materials for Figure B4 Ref No. Component UK Power Networks Stores Code 1 heatshrink end cap (35 to 120mm 2 ) 08881A mm 2 to 95mm 2 single bolt IPC connector 08845E * 120mm 2 to 35mm 2 double bolt IPC connector 08848J * 3 2x35mm R L* 4 35mm 2 to 16mm 2 bare Cu compression splice 08765P 1 35mm 2 to 16mm 2 service compression splice 08757A 1 5 Cable termination break-out kit 2-core 02164H 1 6 4mm 2 Cu Concentric 1-phase service Cable 05860K L* 16mm 2 Al Concentric 1-phase service Cable 05574K L* 7 Service box cut-out (diamond) 08361U 1 Cut-Out Street Lighting PME 25 Amp 12000K 1 Supplementary Components Needed to Complete the Structure All 8 Plastic cleat * As required 9 Local Authority Street Light Tails * As required L* Length as required. * Select to fit. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 37

39 Figure B5 Concentric Service Spans 30m (maximum) Single Phase 20m (maximum) 3 Phase 30m (maximum) Single Phase 20m (maximum) 3 Phase Figure B6 Service Spans 30m (maximum) Single Phase 30m (maximum) 3 Phase 70m (maximum) Single Phase 70m (maximum) 3 Phase Service Clearances Table Service Clearances Location Along the line of hedgerows, fences and boundary walls etc. 4.0 Domestic driveways with an access width of 2.5m or less, which is defined by gateposts, hedges or other fixed features Between buildings where there is no vehicular access 3.5 Normal ground 3.5 Minimum Clearance (m) 4.3 Page 38 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

40 5.3 APPENDIX INSTALLING C GA AUGER DRAWINGS STAYSAND MATERIALS POLE-MOUNTED EQUIPMENT Figure Figure C1 Figure C2 Figure C3 Figure C4 Drawing Title to Two Distribution Boxes to via Fuses GA Intermediate with Cable Termination and LV Fuses GA Terminal with Cable Termination and LV Fuses GA UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 39

41 Figure C1 to Two Distribution Boxes Note: This drawing illustrates connections for 120mm 2. For connections of 95mm 2 and below refer to the material lists. Ensure that droppers (Ref. No.3) are adequately cleated to the pole, as the drawing is for illustration purposes only Page 40 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

42 Materials for Figure C1 Ref No. Component UK Power Networks Stores Code 1 heatshrink end cap (35 to 120mm 2 ) 08881A mm 2 to 95mm 2 single bolt IPC connector 08846P 8 120mm 2 to 95mm 2 double bolt IPC connector 08848J 8 3 4x95mm 2 (line to distribution box) 06207K L* 4 4x95mm 2 (line to distribution box) 06207K L* 5 Distribution box overhead 3-phase 08360K 2 Supplementary Components Needed to Complete the Structure L* Length as required. 4x95mm 2 Cable tie (NI) 03552P As required Plastic cleat (NI) * As required UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 41

43 Figure C2 to via Fuses GA Note: This drawing illustrates connections for 120mm 2. For connections of 95mm 2 and below refer to the material lists. Ensure that droppers are adequately cleated to the pole, as the drawing is for illustration purposes only Bi-metallic earthing connections to be made at the base of the pole, behind the cable guard Page 42 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

44 Materials for Figure C2 Ref No. Component UK Power Networks Stores Code, 4x120mm 2, 4x95mm 2, 4x35mm mm 2 to 35mm 2 single bolt IPC connector 08845E mm 2 to 95mm 2 single bolt IPC connector 08846P mm 2 to 95mm 2 double bolt IPC connector 08848J mm 2 compression none tension splice 08740X mm 2 compression none tension splice 08743C mm 2 compression none tension splice 08744M Pole Mounted 400A cut-out (PC400) 12050D mm 2 to 35mm 2 bare Cu compression splice 08766Y mm 2 to Cu 35mm 2 compression non-tension 08770Y mm 2 Cu 35mm 2 compression non-tension 08954L Earthing components* * Supplementary Components Needed to Complete the Structure Cable tie (NI) 03552P As required Plastic cleat (NI) * As required * Refer to Figure D2. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 43

45 Figure C3 Intermediate with Cable Termination and LV Fuses GA Note: This drawing illustrates connections for 120mm 2. For connections of 95mm 2 and below refer to the material lists. Ensure that droppers (Ref. No.3) are adequately cleated to the pole, as the drawing is for illustration purposes only Bi-metallic earthing connections to be made at the base of the pole, behind the cable guard 4 Page 44 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

46 Materials for Figure C3 Ref No. Component UK Power Networks Stores Code, 4x120mm 2, 4x95mm 2, 2x95mm mm 2 to 95mm 2 single bolt IPC connector 08846P mm 2 to 95mm 2 double bolt IPC connector 08848J heatshrink end cap (35 to 120mm 2 ) 08881A x95mm 2 (main to fuse) 06202L - - L* 4x95mm 2 (main to fuse) 06207K - L* - 4x120mm 2 (main to fuse) 06208U L* PVC Cable guard (64mm) 08172X mm 2 to 35mm 2 Cu compression non-tension splice 08770Y As supplied in underground cable pole termination kit Pole Mounted 400A cut-out (PC400) 12050D Earthing components** ** Supplementary Components Needed to Complete the Structure Cable tie (NI) 03552P As required Plastic cleat (NI) * As required L* Length as required. ** Refer to Figure D2. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 45

47 Figure C4 Terminal with Cable Termination and LV Fuses GA Note: This drawing illustrates connections for 120mm 2. For connections of 95mm 2 and below refer to the material lists. Ensure that droppers are adequately cleated to the pole, as the drawing is for illustration purposes only Bi-metallic earthing connections to be made at the base of the pole, behind the cable guard 2 Page 46 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

48 Materials for Figure C4 Ref No. Component UK Power Networks Stores Code, 4x120mm 2, 4x95mm 2, 2x95mm 2 1 Pole Mounted 400A cut-out (PC400) 12050D PVC Cable guard (64mm) 08171N mm 2 to 35mm 2 Cu compression non-tension splice 08770Y As supplied in underground cable pole termination kit mm 2 to 95mm 2 single bolt IPC connector 08846P mm 2 to 95mm 2 double bolt IPC connector 08848J heatshrink end cap (35 to 120mm 2 ) 08881A Earthing components* * Supplementary Components Needed to Complete the Structure Cable tie (NI) 03552P As required Plastic cleat (NI) * As required * Refer to Figure D2 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 47

49 APPENDIX D GA DRAWINGS AND MATERIALS EARTHING Figure Figure D1 Figure D2 Drawing Title Earthing Bundle to PME Earth Earthing PME Earth Page 48 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

50 Figure D1 Earthing Bundle to PME Earth to be used from the IPC to the bi-metallic connection at the base of the pole. (See Figure D2) Materials for Figure D1 Ref No. Component UK Power Networks Stores Code, 4x120mm 2, 4x95mm 2, 4x35mm 2, 2x95mm 2 1 heatshrink end cap (35 to 120mm 2 ) 08881A mm 2 to 35mm 2 single bolt IPC connector 95mm 2 to 35mm 2 single bolt IPC connector 120mm 2 to 35mm 2 double bolt IPC connector 08845E Y J mm 2 1C Earth Wire 06209E Earthing components * * * Refer to Figure D2., 2x35mm 2 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 49

51 Figure D2 Earthing PME Earth 1 2 Aluminium to Copper bi-metallic splice ( mm above ground) 4 (Note: Splice is behind cable guard) Requirement for Additional Earth Electrodes Depends on Measured Resistance See EDS for guidance 500mm Minimum 3 Nominal Resistance 100 ohms Page 50 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

52 Materials for Figure D2 Ref No. Component UK Power Networks Stores Code 1 35mm 2 1C Earth Wire 06209E 6m 2 PVC Cable guard (20mm) 09000P 1 All 3 Extensible earth rod (1.2m) 02472U As required 4 35mm 2 to 35mm 2 bare Cu compression splice 08766Y 1 Supplementary Components Needed to Complete the Structure Earth rod coupling ** 02475Y As required Earth rod bulldog clamp ** 02474P As required C Crimp 70mm copper conductor ** 08614D As required C Crimp 35mm copper conductor ** 08612J As required Earth rod driving point ** 02479N As required L* Length as required. ** For use with earth electrode as required. UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 51

53 APPENDIX E DATA FOR CONDUCTOR,, 4x120MM 2 Data Summary:,, 4 X 120mm 2 (Recommended Span = 50m) In-line Structures Medium Poles 9m x m x m x m x 250 Angle and Terminal Structures Medium Poles Line Deviation (Degrees) Number/Category of Stays and Spread at Ground Level (m) (L = Light Stay Type 1 H = Heavy Stay Type 2) 9m x m x m x m x 250 Up to m L@ m m N/A 90m N/A N/A 90m N/A N/A 90m Terminal m Stout Poles Line Deviation (Degrees) Number/Category of Stays and Spread at Ground Level (m) (L = Light Stay Type 1 H = Heavy Stay Type 2) 9m x m x m x m x 305 Up to m m L@ L@ L@ m m m Terminal m Max Span Length 60m 60m 60m 60m Max Span Length 90m 90m Max Span Length 90m 90m 90m Page 52 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

54 Design Table Sag/Tension:,, 4x120mm Basic Span 50m Temp ( o C) Tension (kgf) Design Sag (m) for Span Length (m) Design Data for 4 x 120 weight 1.6kg/m Cross Sectional Area of s 480mm 2 overall diameter 42mm Coefficient of Linear Expansion 2.3 x 10-5 Modulus of Elasticity 6000kg/mm 2 Rated Breaking Strength of Bundle kgf Basic Span 50m Wind Pressure 380N/mm 2 Radial Ice Thickness 4.75mm Ice Density 1420kg/m 3 Changed from 913 to allow for ice within bundle) Maximum Working Tension (MWT) 1345kgf Temperature at MWT Limit -5.6 O C Maximum Everyday Tension (EDT) 610.7kgf (conductor mass/m x 1000 / 2.62) Temperature at EDT Limit 10 O C Max Tension at -5.6 OC 1345kgf Maximum Weight 2.541kgf/m (including ice) Maximum Pressure 1.996kgf /m (including 4.75mm radial ice) Freezing Point Tension 712.7kgf Factor of Safety 6.02 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 53

55 Pole Data (Ground Good/Average):,, 4x120mm 2 Length (m) Grade Dia. 1.5m from Butt (mm) Planting Depth (mm) Single pole pole strength SWL (kgf) 9 Medium Medium Medium Medium Medium Medium Stout Stout Stout Stout Stout Stout Maximum wind load span (m) Pole Data (Ground Good/Average):,, 4x120mm 2 Length (m) Grade Dia. 1.5m from Butt (mm) Planting Depth (mm) Single pole pole strength SWL (kgf) 9 Medium Medium Medium Medium Medium Medium Stout Stout Stout Stout Stout Stout Maximum wind load span (m) Page 54 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

56 APPENDIX F DATA FOR CONDUCTOR,, 4x95MM 2 Data Summary:,, 4 X 95mm 2 (Recommended Span = 50m) In-line Structures Medium Poles 9m x m x m x m x 250 Angle and Terminal Structures Medium Poles Line Deviation (Degrees) Number/Category of Stays and Spread at Ground Level (m) (L = Light Stay Type 1, H = Heavy Stay Type 2) 9m x m x m x m x 250 Up to m m m m m m N/A 90m N/A 90m Terminal m Stout Poles Line Deviation (Degrees) Number/Category of Stays and Spread at Ground Level (m) (L = Light Stay Type 1, H = Heavy Stay Type 2) 9m x m x m x m x 305 Up to m m m m m m Terminal m Max Span Length 60m 60m 60m 60m Max Span Length Max Span Length 90m 90m UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 55

57 Design Table Sag/Tension:,, 4x95mm 2 Basic Span 50m Temp ( o C) Tension (kgf) Design Sag (m) for Span Length (m) Design Data for 4 x 95 weight 1.3 kg/m Cross Sectional Area of s 380mm 2 Overall Diameter 39mm Coefficient of Linear Expansion 2.3 x 10-5 Modulus of Elasticity 5600kg/mm 2 Rated Breaking Strength of Bundle kgf Basic Span 50m Wind Pressure 380N/mm 2 Radial Ice Thickness 4.75mm Ice Density 1370kg/m 3 (Changed from 913 to allow for ice within bundle) Maximum Working Tension (MWT) 1156kgf Temperature at MWT Limit -5.6 o C Maximum Everyday Tension (EDT) 496.2kgf (conductor mass/m x 1000 / 2.62) Temperature at EDT Limit 10 o C Max Tension at -5.6 OC 1146kgf Maximum Weight 2.19kgf/m (including ice) Maximum Pressure 1.88kgf /m (including 4.75mm radial ice) Freezing Point Tension 580kgf Factor of Safety 5.4 Page 56 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

58 Pole Data (Ground Good/Average):,, 4x95mm 2 Length (m) Grade Dia. 1.5m from Butt (mm) Planting Depth (mm) Stores Code 9 Medium K 10 Medium U 11 Medium E 12 Medium P 9 Stout H 10 Stout S 11 Stout C 12 Stout M UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015 Section 1 I Page 57

59 APPENDIX G DATA FOR CONDUCTOR,, 2x95MM 2 Data Summary:,, 2x95mm 2 (Recommended Span = 50m) In-line Structures Medium Poles 9m x m x m x m x 250 Angle and Terminal Structures Medium Poles Max Span Length 60m 60m 60m 60m Line Deviation (Degrees) Number/Category of Stays and Spread at Ground Level (m) (L = Light Stay Type 1, H = Heavy Stay Type 2) 9m x m x m x m x 250 Up to m m m m m m m m Terminal m Stout Poles Line Deviation (Degrees) Number/Category of Stays and Spread at Ground Level (m) (L = Light Stay Type 1, H = Heavy Stay Type 2) 9m x m x m x m x 275 Up to m m m m m m m m Terminal m Max Span Length Max Span Length Page 58 I Section 1 UK POWER NETWORKS OVERHEAD LINES CONSTRUCTION MANUAL I 2015

NSP/004/107 (OHI 7) Guidance on the selection of conductor jumpers and non-tension connections

NSP/004/107 (OHI 7) Guidance on the selection of conductor jumpers and non-tension connections Version:- 3.0 Date of Issue:- September 2015 Page 1 of 12 NSP/004/107 (OHI 7) Guidance on the selection of conductor jumpers and non-tension connections 1. Purpose The purpose of this document is to provide

More information

IMP/010/011 Code of Practice for Earthing LV Networks and HV Distribution Substations

IMP/010/011 Code of Practice for Earthing LV Networks and HV Distribution Substations Version:- 3.0 Date of Issue:- January 2018 Page 1 of 70 IMP/010/011 Code of Practice for Earthing LV Networks and HV Distribution Substations 1. Purpose The purpose of this document is to ensure the company

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

NPS/001/010 Technical Specification for Fasteners and Fixings for Wood Pole Overhead Lines and General Construction Works

NPS/001/010 Technical Specification for Fasteners and Fixings for Wood Pole Overhead Lines and General Construction Works Version:- 4.0 Date of Issue:- August 2014 Page 1 of 13 NPS/001/010 Technical Specification for Fasteners and Fixings for Wood Pole Overhead Lines and General Construction Works 1. Purpose The purpose of

More information

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS ENGINEERING DESIGN STANDARD EDS 08-2109 LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS Network(s): Summary: EPN, LPN, SPN This standard provides guidance on the installation of

More information

Collection of standards in electronic format (PDF) 1. Copyright

Collection of standards in electronic format (PDF) 1. Copyright Collection of standards in electronic format (PDF) 1. Copyright This standard is available to staff members of companies that have subscribed to the complete collection of SANS standards in accordance

More information

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The

More information

Earthing Guidance Notes

Earthing Guidance Notes Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head

More information

CONTENTS EARTHING AND BONDING

CONTENTS EARTHING AND BONDING CONTENTS 3 EARTHING AND BONDING 3.1 General 1 3.2 HV Earthing System 3 3.3 LV Earthing Sysyem 18 3.4 Earth Electrode Arrangements 21 3.5 Siting of Earthing Systems 24 3.6 Installing an Earthing System

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

Article 250 Grounding & Bonding

Article 250 Grounding & Bonding Article 250 Grounding & Bonding AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Dr. Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER NOTE: This course is APPROVED for continuing education

More information

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP 1 1 1 0 1 0 1 0 1 SECTION 1 1 CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP BASED ON DFD MASTER SPECIFICATION DATED /01/ P A R T 1 - G E N E R A L SCOPE The work under this section shall consist of

More information

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

Busbar and Modular Wiring Systems

Busbar and Modular Wiring Systems Chapter 11 Busbar and Modular Wiring Systems 11.1 BUSBAR SYSTEM The wide range of busbar system is available and can be used for single or three-phase distribution to many types of applications ranging

More information

Pole Line Hardware. Heavy-Duty Spool Rack (200 A) No. of Wires. Anti-Vibration Kit for Spool Rack. Heavy-Duty Spool Rack (400 A) No.

Pole Line Hardware. Heavy-Duty Spool Rack (200 A) No. of Wires. Anti-Vibration Kit for Spool Rack. Heavy-Duty Spool Rack (400 A) No. Heavy-Duty Spool Rack (200 A) SS401E - SS802E - SS803E - SS804E No. of Wires Overall Length SS401E 1 9-1/2 300 136.3 10 SS802E 2 17-1/2 520 236.3 SS803E 3 25-1/2 780 354.5 5 SS804E 4 33-1/2 1040 472.7

More information

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards. 8.3 Induced Voltage Purpose The purpose of this instruction is to provide awareness of Electrostatic and Electromagnetic induced voltages and the method required to reduce or eliminate it. An induced voltage

More information

BSR A300 Part 3 Draft 1 Version 1, a

BSR A300 Part 3 Draft 1 Version 1, a Standards & Regulations Cabling and Bracing Standard Proposed Revision This is an excerpt from the draft version of the ANSI standard for supplemental support systems cabling and bracing used in tree care

More information

Guidance for UK Fire and Rescue Services. Dealing with incidents on or near National Grid high voltage overhead lines

Guidance for UK Fire and Rescue Services. Dealing with incidents on or near National Grid high voltage overhead lines Guidance for UK Fire and Rescue Services Dealing with incidents on or near National Grid high voltage overhead lines This document offers guidance to the UK s Fire and Rescue Services for dealing with

More information

SOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department

SOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department SOUTH DUBLIN COUNTY COUNCIL Roads (Traffic and Transportation) Department TECHNICAL SPECIFICATION 2 SDCC-TS-02 INDUCTIVE LOOPS & ABOVE GROUND DETECTION REQUIREMENTS FOR THE DESIGN AND INSTALLATION OF TRAFFIC

More information

EDS LV WAVEFORM MAINS CABLE RATINGS

EDS LV WAVEFORM MAINS CABLE RATINGS Document Number: EDS 02-0033 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 02-0033 LV WAVEFORM MAINS CABLE RATINGS EPN, LPN, SPN This standard details the technical and practical information required

More information

INSTRUCTION MANUAL. Model 18AVQII Five Band Vertical Antenna 10, 15, 20, 40, 80 Meter. General Description. Theory of Operation

INSTRUCTION MANUAL. Model 18AVQII Five Band Vertical Antenna 10, 15, 20, 40, 80 Meter. General Description. Theory of Operation Model 18AVQII Five Band Vertical Antenna 10, 15, 20, 40, 80 Meter 308 Industrial Park Road Starkville, MS 39759 (662) 323-9538 Fax: (662) 323-5803 INSTRUCTION MANUAL General Description The Hy-Gain 18AVQII

More information

Section 808. FENCING

Section 808. FENCING 808.01 Section 808. FENCING 808.01. Description. This work consists of providing and erecting, or moving existing, woven wire fence, temporary fence, protective fence, chain link fence, high-tensile wire

More information

INSTALLATION & TESTING OF UNDERGROUND PRIMARY AND SECONDARY POWER CABLES PRIOR TO ENERGIZATION

INSTALLATION & TESTING OF UNDERGROUND PRIMARY AND SECONDARY POWER CABLES PRIOR TO ENERGIZATION TITLE: RECOMMENDED: P. Lemay NO: APPROVED: C. Malone, P.Eng. REV. DATE: 2015-11-02 Working Procedure GCG0001 REV: 3 INSTALLATION & TESTING OF UNDERGROUND PRIMARY AND SECONDARY POWER CABLES PRIOR TO ENERGIZATION

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice

More information

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation 2394 EXAM PAPER 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation 2. There are various documents that are relevant to the Inspection and

More information

PART MATERIALS. Section Fencing Materials. Description

PART MATERIALS. Section Fencing Materials. Description PART 03000 - MATERIALS Section 03010 - Fencing Materials Description 03010.00 Scope - This section consists of the test requirements, specifications and tolerances for barbed wire, woven wire and chain

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

kv AC substation

kv AC substation 132-400 kv AC substation Outdoor AC substations Earthing systems ETS-50-08-01, Rev. 0 technical standard Document no. 13/90592-127 ETS-50-08-01 v. 0 REVISION VIEW Document no.: 13/90592-127 Version Author

More information

MDOTProjectwise\Documents\Reference Documents\Traffic Reference\Statewide Special Details\Develop

MDOTProjectwise\Documents\Reference Documents\Traffic Reference\Statewide Special Details\Develop 500 460 MDOTProjectwise\Documents\Reference Documents\Traffic Reference\Statewide Special Details\Develop Check if Applicable TRAFFIC SIGNAL SPECIAL DETAILS INDEX/CHECKLIST *One completed checklist required

More information

Cable Hanging Instruction Manual

Cable Hanging Instruction Manual Tri-States Grain Conditioning, Inc. Cable Hanging Instruction Manual There are several types of grain storage tanks and bins. Parts of these instructions may be modified to fit the circumstances. Care

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

Click to edit Master title style. Click to edit Master title style. Northern Powergrid Asset Recording Guidance

Click to edit Master title style. Click to edit Master title style. Northern Powergrid Asset Recording Guidance Click to edit Master title style Click to edit Master title style Northern Powergrid Asset Recording Guidance Rules for ICP & IDNO Version 1.0 April 2017 Introduction Accurate records for all assets are

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

HV Substation Earthing Design for Mines

HV Substation Earthing Design for Mines International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 4, Issue 6 (October 2012), PP. 100-107 HV Substation Earthing Design for Mines M.

More information

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE. Contents

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE. Contents Document Number: EOS 09-0100a Contents 1 Introduction... 2 2 Cable Routes/Joints... 2 3 Cable Details... 2 4 Cable Warning Markers... 4 5 Cable Drum Numbers... 4 6 Ducts - Including those used in a Directional

More information

What you should have. 1. Telescopic Pole (1) 2. Arc tubing (4) for Lower Ring. 3. Numbered bars or spokes(8) 4. Center plate (1)

What you should have. 1. Telescopic Pole (1) 2. Arc tubing (4) for Lower Ring. 3. Numbered bars or spokes(8) 4. Center plate (1) 20 ft RGB Pole Tree What you should have 1. Telescopic Pole (1) 2. Arc tubing (4) for Lower Ring 3. Numbered bars or spokes(8) 4. Center plate (1) 5. Top Ring (1) 6. Hardware and wrenchs a. Hardware i.

More information

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks MESP 130400-07 TECHNICAL SPECIFICATION FOR Version: 1 Issued: February 2017 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical)

More information

GENERAL INSPECTION AND MAINTENANCE PROCEDURE FOR FIXED HF ANTENNA SYSTEMS

GENERAL INSPECTION AND MAINTENANCE PROCEDURE FOR FIXED HF ANTENNA SYSTEMS Bulletin 7591056,Revision A 1. SCOPE GENERAL INSPECTION AND MAINTENANCE PROCEDURE FOR FIXED HF ANTENNA SYSTEMS It is the intent of this procedure that all equipment and components of the antenna system

More information

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence MILWAUKIE OR #3144-00 ADDENDUM #5 NARRATIVE: 11-08-12 WAL-MART SUPERCENTER #3144-00; Milwaukie, OR: SPECIFICATIONS SPECIFICATIONS Revisions to Specification 02822 Fence Spec division 02822 has been revised

More information

FAQ ON EARTHING STANDARDS 16/08/2018

FAQ ON EARTHING STANDARDS 16/08/2018 FAQ ON EARTHING STANDARDS 16/08/2018 This document has been updated to include changes made to substation earthing layouts that have been made necessary due to copper theft. The main changes to be aware

More information

METRIC LIGHTNING PROTECTION PRODUCTS

METRIC LIGHTNING PROTECTION PRODUCTS Section 11 Metric Description... Page # 11.1 Taper Pointed Air Rods, Air Terminals & Attachments...270 11.2 Saddles & Attachments...271-272 11.3 s...273-275 11.4 Attachments...276-279 11.5 Clamps...280

More information

Introduction 3. System Overview 3. Before Installation 3. Limitations and Warnings 4. Safety Statements 4. Parts Identification 5.

Introduction 3. System Overview 3. Before Installation 3. Limitations and Warnings 4. Safety Statements 4. Parts Identification 5. June 2015 Table of Contents Introduction 3 System Overview 3 Before Installation 3 Limitations and Warnings 4 Safety Statements 4 Parts Identification 5 Preparation 7 Soil Conditions 7 Tools Required 7

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard NSW Category Electrical Title Reference Number PDS 05 (RIC Standard: EP 12 10 00 11 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION SECTION R507 DECKS R507.1 Application. The provisions of this section shall provide prescriptive requirements for the design and construction of all uncovered, wood-framed, single-span exterior decks.

More information

Company Directive STANDARD TECHNIQUE: TP21D/2. 11kV, 6.6kV and LV Earthing

Company Directive STANDARD TECHNIQUE: TP21D/2. 11kV, 6.6kV and LV Earthing Company Directive STANDARD TECHNIQUE: TP21D/2 11kV, 6.6kV and LV Earthing Policy Summary This document specifies requirements for earthing 11kV and 6.6kV and LV equipment and systems. NOTE: The current

More information

GROUP OF COMPANIES. MERLIN STEALTH Electric Fence Energizer INSTALLERS MANUAL

GROUP OF COMPANIES. MERLIN STEALTH Electric Fence Energizer INSTALLERS MANUAL GROUP OF COMPANIES MERLIN STEALTH Electric Fence Energizer INSTALLERS MANUAL Revision 1.5 23 February 2007 : INSTALLERS MANUAL Table of Contents 2 INTRODUCTION.. 3 INSTALLER OPTIONS...... 4-11 ALARM SETTING

More information

Company Directive STANDARD TECHNIQUE: SD5F. Relating to connecting multiple small low voltage connections with limited network analysis

Company Directive STANDARD TECHNIQUE: SD5F. Relating to connecting multiple small low voltage connections with limited network analysis Company Directive STANDARD TECHNIQUE: SD5F Relating to connecting multiple small low voltage connections with limited network analysis Policy Summary This document specifies the procedure for connecting

More information

AGILITY. ROTA WEB CLIMBER 3.3m PROD. CODE SIZE AGE RANGE F/ FALL HEIGHT HEAVIEST PART TOTAL WEIGHT ROTAWEB33. 8 TO mm 73kg 115kg

AGILITY. ROTA WEB CLIMBER 3.3m PROD. CODE SIZE AGE RANGE F/ FALL HEIGHT HEAVIEST PART TOTAL WEIGHT ROTAWEB33. 8 TO mm 73kg 115kg AGILITY ROTA WEB CLIMBER.m PROD. CODE SIZE AGE RANGE F/ FALL HEIGHT HEAVIEST PART TOTAL WEIGHT Dia. m x.m High 8 TO 4 00mm 7kg 5kg SPECIFICATION Centre Upright: Made from 6" diameter aluminium tube to

More information

Article 225: Outside Branch Circuits And Feeders

Article 225: Outside Branch Circuits And Feeders Part C: Code Book Questions Article 225: Outside Branch Circuits And Feeders 1.! Open (individual) aerial overhead conductors shall be insulated or covered when within! feet of a building.! (a) 10! (c)

More information

Technical Guarantees No. WP_85

Technical Guarantees No. WP_85 Gaza Electricity Distribution Corporation LTD. Technical Guarantees No. WP_85 Wooden Pole 8.5 m Long Top Diameter 150-180 mm Impregnated No Description Unit Requirements Offered Data 1 Name of Manufacturer

More information

POLE LINE HARDWARE POLE LINE HARDWARE. HI-LINE UTILITY SUPPLY CO. Phone: Fax:

POLE LINE HARDWARE POLE LINE HARDWARE. HI-LINE UTILITY SUPPLY CO. Phone: Fax: 146 MACHINE BOLTS w/ square nut Rolled threads; s six inches or longer have con-type points. Hot dip galvanized. 860412 3/8" 4.5" 3" 250 8706 6" 3" 100 8707 7" 3" 100 8708 1/2" 8" 4" 100 8710 10" 4" 50

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

Verge Flashing. Verge Flashing. Only use if flashings requirements can be site measured before ordering. Verge Clip

Verge Flashing. Verge Flashing. Only use if flashings requirements can be site measured before ordering. Verge Clip Tolerance Detail (recommended) Verge Closure Verge Channel Verge Clip Verge Flashing VERGE CHANNEL RIVETTED TO EUROSEAM AT APPROX 400MM CENTRES USING 4.8 X 12MM RIVETS. NB: DO NOT RIVET AT HALTER POSITION

More information

Guideline for Creating Disconnection Points and Establishing a Not Electrically Connected Area

Guideline for Creating Disconnection Points and Establishing a Not Electrically Connected Area Guideline for Creating Disconnection Points and Establishing a Not Document Number: Authorised by: Issue Date: 29 June 2012 Previous Document: 12 February 2010 Principal Authors: J Dohmen Powerlink D Brown

More information

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Construction Specification for Watermain and Water Service Tracer Wire

Construction Specification for Watermain and Water Service Tracer Wire Engineering and Construction Services Division Standard Specifications for Sewers and Watermains TS 7.40 April 2013 for Watermain and Water Service Tracer Wire Table of Contents TS 7.40.01 SCOPE... 2 TS

More information

Not including the type of fabric used (clear pvc or shade mesh), there are three main types of side screen.

Not including the type of fabric used (clear pvc or shade mesh), there are three main types of side screen. installation Outrigger side screens are installed as a single stage job when the screens are fitted to a existing structure. However, two stages may be necessary if, for whatever reason, reliable measurements

More information

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33 Part VIII Electrical CHAPTER 33 GENERAL REQUIREMENTS < SECTION E3301 GENERAL E3301.1 Scope. The installation of electrical systems, equipment and components indoors and outdoors that are within the scope

More information

CITY OF PITTSBURG ENGINEERING DEPARTMENT CONTRACT NO A WATER TREATEMENT PLANT CAPITAL IMPROVEMENTS PHASE 1A ADDENDUM #1 FENCE AND DITCH AUGUST

CITY OF PITTSBURG ENGINEERING DEPARTMENT CONTRACT NO A WATER TREATEMENT PLANT CAPITAL IMPROVEMENTS PHASE 1A ADDENDUM #1 FENCE AND DITCH AUGUST CITY OF PITTSBURG ENGINEERING DEPARTMENT CONTRACT NO. 2012-16A WATER TREATEMENT PLANT CAPITAL IMPROVEMENTS PHASE 1A ADDENDUM #1 FENCE AND DITCH AUGUST 2014 CHAIN LINK FENCE SPECIFICATIONS Chain link fence,

More information

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2 Engineering Specification Electrical TECHNICAL SPECIFICATION FOR CONTACT WIRE HARD-DRAWN COPPER 161mm2 Version: 2 Issued: May 2018 Owner: Engineering Approved by: Andrew Russack, Head of Engineering Electrical

More information

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL BELL SYSTEM PRACTICES Plant Series SECTION 508-100-100 Issue 3, October 1970 AT&TCo Standard ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL I. GENERAL 1.01 This section is reissued to: Revise

More information

TABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES... 4

TABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES... 4 TITLE SPECIFICATION FOR CRIMPED CONNECTING LUGS AND FERRULES PAGE: 1 OF 29 ISION DATE: SEPTEMBER 2014 TABLE OF CONTENTS Page FOREWORD... 3 INTRODUCTION... 4 1 SCOPE... 4 2 NORMATIVE S... 4 3 REQUIREMENTS...

More information

Item 550 Chain Link Fence

Item 550 Chain Link Fence Item Chain Link Fence 1. DESCRIPTION 2. MATERIALS Furnish, install, remove, repair, or replace chain link fence and gates. Furnish certification from the chain link fence materials manufacturer stating

More information

Rollerscreen ENG. Installation Instructions

Rollerscreen ENG. Installation Instructions Rollerscreen Instructions Introduction Figure 1, System Overview and Individual Components -2- Introduction INTRODUCTION Parts List REFERANCE QTY PRODUCT DESCRIPTION A1 2 Top and Bottom Tubes B1 1 Screen

More information

GENERAL SUBSCRIBER SERVICES TARIFF Pembroke Telephone Company, Inc. Third Revised Contents Sheet 1 Cancels Second Revised Contents Sheet 1

GENERAL SUBSCRIBER SERVICES TARIFF Pembroke Telephone Company, Inc. Third Revised Contents Sheet 1 Cancels Second Revised Contents Sheet 1 GENERAL SUBSCRIBER SERVICES TARIFF Pembroke Telephone Company, Inc. Section N Third Revised Contents Sheet 1 Cancels Second Revised Contents Sheet 1 N. CONNECTION WITH CERTAIN FACILITIES AND/OR EQUIPMENT

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

CURVED ROOF ASSEMBLY INSTRUCTIONS ATTACHED VERANDAH. Your supplementary guide to building an ATTACHED CURVED ROOF VERANDAH or PATIO BEFORE YOU START

CURVED ROOF ASSEMBLY INSTRUCTIONS ATTACHED VERANDAH. Your supplementary guide to building an ATTACHED CURVED ROOF VERANDAH or PATIO BEFORE YOU START ROOF ATTACHED VERANDAH ASSEMBLY INSTRUCTIONS Your supplementary guide to building an ATTACHED ROOF VERANDAH or PATIO This set of instructions should be used in conjunction with the Stratco instruction

More information

Company Directive STANDARD TECHNIQUE: SD5R/2. Earth Fault Loop Impedances and Phase to Neutral Loop Impedances at LV Installations

Company Directive STANDARD TECHNIQUE: SD5R/2. Earth Fault Loop Impedances and Phase to Neutral Loop Impedances at LV Installations Company Directive STANDARD TECHNIQUE: SD5R/2 Earth Fault oop Impedances and Phase to Neutral oop Impedances at V Installations NOTE: The current version of this document is stored in the WPD Corporate

More information

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Chapter 6. WIRING SYSTEMS Safe Electrical Design Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous

More information

MSP-WRTIDSKY1 Light Weight Suspended Ceiling Kit for use with Island Display Skybox

MSP-WRTIDSKY1 Light Weight Suspended Ceiling Kit for use with Island Display Skybox INSTALLATION INSTRUCTIONS MSP-WRTIDSKY1 Light Weight Suspended Ceiling Kit for use with Island Display Skybox The MSP-WRTIDSKY1 Light Weight Suspended Ceiling Kit provides a sturdy support for LCD displays

More information

Project: # Solano Community College District

Project: # Solano Community College District ADDENDUM #02 Project: #16 007 Solano Community College District Horticulture Site Improvements Date: April 26, 2016 The following clarifications are provided based on questions received or changes in District

More information

Cisco Aironet 2.4-GHz/5-GHz 8-dBi Directional Antenna (AIR-ANT2588P3M-N)

Cisco Aironet 2.4-GHz/5-GHz 8-dBi Directional Antenna (AIR-ANT2588P3M-N) Cisco Aironet.4-GHz/5-GHz 8-dBi Directional Antenna (AIR-ANT588P3M-N) This document outlines the specifications for the Cisco Aironet AIR-ANT588P3M-N.4/5-GHz 8-dBi 3-Port Directional Antenna with N-connectors

More information

Reference Number PDS 04 (RIC Standard: EP SP)

Reference Number PDS 04 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Reference Number PDS 04 (RIC Standard: EP 12 10 00 10 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

Telephone Cable Locating Techniques

Telephone Cable Locating Techniques Chapter 2 Telephone Cable Locating Techniques Introduction Read Chapter One of this manual to learn more general information about each of the following signal application methods. The following paragraphs

More information

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA) ER 87 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The

More information

Pow-R-Feed Systems Service Manual

Pow-R-Feed Systems Service Manual Pow-R-Feed Systems Service Manual Important Safety Instructions Please read this manual carefully and follow its instructions. Improper use or failure to follow these instructions could result in serious

More information

Outline. Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions

Outline. Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions www.we-llc.com Outline Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions Bonding & Grounding Grounding Terms Equipment Grounding: The National Electrical

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION-16075 ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SECTION INCLUDES A. Electrical identification to identify all electrical items for easy operation and maintenance including, but not limited

More information

Wire Mesh Cable Tray System for Channeling of Cable Wiring

Wire Mesh Cable Tray System for Channeling of Cable Wiring Wire Mesh Cable Tray System for Channeling of Cable Wiring A Simple-to-Install basket for safe and proper installation of facility wiring in the ceiling and under the floor. Wall Mount Ceiling Mount s

More information

X-350 Guardrail End Terminal

X-350 Guardrail End Terminal X-350 Guardrail End Terminal Tangent and Flared Step by Step Instructions for the Tangent and Flared Applications Ph 0800 655 200 or visit www.csppacific.co.nz August 2011 / Page 1 Table of Contents Introduction

More information

Instructions For Installing A Pig Fence

Instructions For Installing A Pig Fence Instructions For Installing A Pig Fence A Multi-wire Fence on a Single Line of Posts Height: 18 Inches Polywire for seasonally removable fences Aluminum wire for permanent fences These pages provide the

More information

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of: 1 PAPER 5 Sample Questions A- C&G 2382 17th Edition Paper A 1 o/c1 BS 7671 does not apply to a equipment of aircraft b photovoltaic systems c marinas d fairgrounds. 2 o/c1 Where protection for persons

More information

INSTRUCTION MANUAL for MODEL TH6-DX "THUNDERBIRD" (389)

INSTRUCTION MANUAL for MODEL TH6-DX THUNDERBIRD (389) INSTRUCTION MANUAL for MODEL TH6-DX "THUNDERBIRD" (389) HY-GAIN ELECTRONICS CORPORATION, N. E. Hwy #6 at Stevens Creek, Lincoln, Nebraska 65801 Telephone 434-6331 INTRODUCTION Ely-Gain's new Model TH6-DX

More information

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS. 1 Definitions. 2 Scope of Work. 3 Extent of Work

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS. 1 Definitions. 2 Scope of Work. 3 Extent of Work SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation 7 Backfilling

More information

CONTINUOUS COUNTERPOISE ON POLES

CONTINUOUS COUNTERPOISE ON POLES Project Procedure CONTINUOUS COUNTERPOISE ON POLES 07/25/2011 PAGE 1 OF 5 1.0 PURPOSE The purpose of this procedure is to provide guidance and direction for the installation of continuous counterpoise

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING PART I - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/2.14 70mm 2 Version: 1 Issued: January 2015 Owner: Engineering Division Approved By: Pat

More information

Session: Introduction to PPE and T&P

Session: Introduction to PPE and T&P Session: Introduction to PPE and T&P Learning Objectives Explain what safety PPE, tools and plants are, their purpose and their uses Evaluation Criteria Interactive Questioning Duration Resources Facilitator

More information

MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER 7/7/ mm 2

MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER 7/7/ mm 2 Engineering Specification Electrical Networks MESP 130400-02 TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER Version: 1 Issued: November 2015 Owner: Engineering Division Approved By:

More information

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested

More information

Earthing Requirements for HV Transmission Structures

Earthing Requirements for HV Transmission Structures Engineering Standard Electrical MEST 000002-07 Earthing Requirements for Transmission Structures Version: 1 Issued: February 2015 Owner: Engineering Approved By: Patrick Kelly Head of Electrical Engineering

More information

Cutting. Contents. Cutting. Cutting Introduction B.2 B.1. Cutting tools B.4. Front cable cutter B.6. Cable cutter B.7. Cutting and releasing tools B.

Cutting. Contents. Cutting. Cutting Introduction B.2 B.1. Cutting tools B.4. Front cable cutter B.6. Cable cutter B.7. Cutting and releasing tools B. Contents Introduction.2 tools.4 Front cable cutter.6 Cable cutter.7 and releasing tools.9 Mounting rail cutter.11 Sheet holes.12 Electrician s knives/electrician s scissors.14.1 Introduction A large number

More information

TZ-RD-1740 Rotary Dipole Instruction Manual

TZ-RD-1740 Rotary Dipole Instruction Manual TZ-RD-1740 17/40m Rotary Dipole Instruction Manual The TZ-RD-1740 is a loaded dipole antenna for the 40m band and a full size rotary dipole for the 17m band. The antenna uses an aluminium radiating section

More information

Medium Voltage Power Cables

Medium Voltage Power Cables N2XSY 6/0, /20, /30 NA2XSY 6/0, /20, /30 N2XS2Y 6/0, /20, /30 NA2XS2Y 6/0, /20, /30 N2XS(F)2Y 6/0, /20, /30 NA2XS(F)2Y 6/0, /20, /30 N2XSEY 3 x 6/0 Medium Voltage Power Cables Photo: HELUKABEL Q 47 Medium

More information

Installation Instructions Hustler 6-BTV Trap Vertical

Installation Instructions Hustler 6-BTV Trap Vertical Installation Instructions Hustler 6-BTV Trap Vertical ASSEMBLY 1. Check the package contents against the parts list on page 2. 2. WARNING. Installation of this product near power lines is dangerous. For

More information

RUBBISH CHUTE TECHNICAL NOTE

RUBBISH CHUTE TECHNICAL NOTE RUBBISH CHUTE TECHNICAL NOTE HAEMMERLIN - CDH GROUP 28 RUE DE STEINBOURG - BP 30045-67701 1 SAVERNE CEDEX - FRANCE Tel. + 33 (0)3 88 01 85 00 - Fax + 33 (0)3 88 01 85 39 welcome@haemmerlin.com - www.haemmerlin.com

More information

CONTENTS CABLE MANAGEMENT AND

CONTENTS CABLE MANAGEMENT AND CONTENTS CABLE MANAGEMENT SECTION 9 SECTION 9 CABLE MANAGEMENT AND ASSOCIATED PRODUCTS.................................91 PIN CLIPS H335B SERIES.......................................92 COPPER EARTH RODS.........................................92

More information