1 Engineering Specification Electrical Networks MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER Version: 1 Issued: November 2015 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical) PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION
2 Approval Amendment Record Approval Date Version Description 09/11/ Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 7
3 Table of Contents 1. Purpose Scope Abbreviation Definitions References & Legislations Material Conductor Characteristics Lay Dimensions Production Test Requirements Quality Assurance Warranty Packing... 6 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 7
4 1. Purpose This document details the specification of 9.6 mm² tin-bearing copper dropper wire for use in the Melbourne Metropolitan Overhead Wiring System. 2. Scope The scope comprises the manufacture, testing and supply of 9.6 mm² tin-bearing copper dropper wire. 3. Abbreviation d Diameter of strand in millimeters 4. Definitions Lay Ratio Ovality The ratio of the lay length to the external diameter of the corresponding layer of wires The difference between the maximum and minimum diameter measurements taken in the same cross-section 5. References & Legislations AS 1391:2007 Metallic Materials Tensile Testing at Ambient Temperature AS 2193:2005 AS 2738:2000 AS 3822:2002 AS/NZS 1574:1996 AS/NZS 2857:1996 AS/NZS ISO 9001 Calibration and Classification of Force Measuring Systems Copper and Copper Alloys - Compositions and Designations of Refinery Products, Wrought Products, Ingots and Castings Test Methods for Bare Overhead Conductors Copper and Copper Alloys - Wire for Electrical Purposes Timber Drums for Insulated Electric Cables and Bare Conductors Quality Management Systems - Requirements. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 7
5 6. Material a. The chemical composition of the material used for the solid conductor shall conform to AS 2738 alloy designation 149 (Tin-bearing copper). b. The maximum resistivity at 20 C is µω.m (equivalent to a conductivity of 73% IACS). c. The minimum ultimate tensile strength is 600 MPa for the individual strands of the hard-drawn copper wire. Although the diameter of the wire is less than 0.5 mm, the ultimate tensile strength is given by d as per alloy designation 149 in AS 1574:1996. d. The Calculated Break Load of the conductor is 90% of the sum of the strengths of the individual strands before stranding e. The wire shall be clean, smooth and free from all defects f. There shall be no joints in the wire. g. The wire density at 20 C shall be 8,890 kg/m³ plus or minus 3%. h. The coefficient of linear expansion is taken as 17x10-6 per C. i. The modulus of elasticity is taken as 123 GPa. This value is taken after the initial stretch of the wire following construction. 7. Conductor Characteristics Strand Dia. (mm) Cross-sectional area (mm²) Mass/km (kg) Calculated breaking load (kn) DC 20 C (ohms) 0.5 (nom) (-1%) Lay Lay ratio and direction of the layers shall be: Primary bunch: 27.6 mm nom Left-hand lay 6-wire layer: 49 mm min, 49.8 mm max Right-hand lay 9. Dimensions Wire size and tolerances shall be in accordance with AS 1574:1996. For a 7/7/0.5 nominal conductor of 9.6 mm² nominal cross-sectional area, the overall wire diameter shall be 4.5 mm +/- 1%. Single wire ovality shall be within 1% of nominal diameter (0.5 mm). PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 7
6 10. Production Test Requirements For the purposes of this specification the metallurgical tests shall be in accordance with AS/NZS 1574:1996. Mechanical and electrical tests shall be in accordance with AS 1574:1996 and AS 3822: Quality Assurance The Supplier should meet the requirements of AS/NZS ISO Warranty The Supplier shall provide a Certificate of Conformance together with a full test report as stipulated in Production Test Requirements. 13. Packing a) The dropper wire shall be wound without twists, or kinks, on drums of approved design and of sufficient size to prevent sharp bends and shall be properly protected against damage in transit. b) Typically approved design is wooden drums lined with sisal-craft in general accordance with AS 2857:1996 and the following Metro Trains Melbourne required dimensions: o Barrel diameter 200 mm minimum o Overall diameter 400 mm maximum o Overall width 250 mm maximum o Round shaft hole diameter 55 mm The free ends of the wire shall be suitably treated to prevent de-stranding. The inner end of the conductor shall be passed through the drum flange to the outside and stapled securely. The outer end of the conductor shall be secured to the inside of the drum flange with staples and bent back on itself to prevent it from working loose. c) Metro Trains Melbourne shall specify the length of the conductor on each drum. d) The following information shall be legibly and indelibly marked on the flange of the drums or a label securely attached thereto: (i) (ii) Supplier s name Supplier s drum serial number (iii) The conductor material and size (Tin-bearing copper, dropper wire 7/7/0.5, 9.6mm 2 ) (iv) (v) Length of conductor Gross mass of conductor and drum PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 6 of 7
7 (vi) (vii) (viii) Handling or lifting instructions. The preferred method being by means of a spindle through the spindle holes and a spreader to prevent damage to the flanges An arrow with the words 'ROLL THIS WAY' to indicate the direction in which the drum should be rolled on the flanges The Metro Trains Melbourne contract number, order number and specification number e) Alternative equivalent or superior packing system may be submitted to Metro Trains Melbourne for consideration. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 7 of 7
MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2
Engineering Specification Electrical Networks MESP 130400-07 TECHNICAL SPECIFICATION FOR Version: 1 Issued: February 2017 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical)
More informationMESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2
Engineering Specification Electrical Networks MESP 130400-04 TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/0.70 100mm 2 Version: 2 Issued: February 2016 Owner: Engineering
More informationMESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/2.5 181mm 2 Version: 3 Issued: February 2017 Owner: Engineering Division Approved By: Andrew
More informationMESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/2.14 70mm 2 Version: 1 Issued: January 2015 Owner: Engineering Division Approved By: Pat
More informationTECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2
Engineering Specification Electrical TECHNICAL SPECIFICATION FOR CONTACT WIRE HARD-DRAWN COPPER 161mm2 Version: 2 Issued: May 2018 Owner: Engineering Approved by: Andrew Russack, Head of Engineering Electrical
More informationMGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested
More information012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)
012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0
More informationTECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)
TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +
More informationGURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM
Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted
More information1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)
WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,
More informationTABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES... 4
TITLE SPECIFICATION FOR CRIMPED CONNECTING LUGS AND FERRULES PAGE: 1 OF 29 ISION DATE: SEPTEMBER 2014 TABLE OF CONTENTS Page FOREWORD... 3 INTRODUCTION... 4 1 SCOPE... 4 2 NORMATIVE S... 4 3 REQUIREMENTS...
More informationTechnical Specification. for 1.1 KV Copper Control Cable
WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,
More informationSPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION December 2016 SPECIFICATION 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION
More informationBBD7267 Version 1 PRIEVIEW COPY ONLY
INDEX SECTION CONTENTS PAGE 1.0 SCOPE 3 2.0 REFERENCES 3 3.0 APPENDICES 3 4.0 METHOD OF TENDERING 3 5.0 MATERIAL 3 6.0 MARKING 3 7.0 SIZE AND LENGTH 4 8.0 DRUMS AND WINDING 4 9.0 MARKING OF DRUMS 4 10.0
More information001: 2007 CEB STANDARD
001: 2007 CEB STANDARD ALUMINIUM RE-DRAW RODS FOR ELECTRICAL PURPOSES CEYLON ELECTRICITY BOARD SRI LANKA Specification for ALUMINIUM RE-DRAW RODS FOR ELECTRICAL PURPOSES CEB Standard 001: 2007 CEYLON ELECTRICITY
More information079 : 2000 CEB STANDARD ALUMINIUM BINDING WIRE
079 : 2000 CEB STANDARD ALUMINIUM BINDING WIRE CEYLON ELECTRICITY BOARD SRI LANKA Specification for ALUMINIUM BINDING WIRE CEB Standard 079 : 2000 CEYLON ELECTRICITY BOARD No. 50, Sir Chittampalam A. Gardener
More informationDRAFT UGANDA STANDARD
DRAFT UGANDA STANDARD DUS 193-1 First Edition 2018-09-dd Steel wires and wire products for fencing Part 1: Barbed wires Specification Reference number UNBS 2018 Compliance with this standard does not,
More informationJULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.
FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationREQUEST FOR INFORMATION (RFI) RFI NO: /WJG
(RFI) RFI NO: 15-219/WJG WASHINGTON METROPOLITAN AREA TRANSIT AUTHORITY 600 FIFTH STREET, NW WASHINGTON DC 20001 ( WMATA OR AUTHORITY ) 1 ⅝ INCH RADIATING COAXIAL CABLE DATE: AUGUST 7, 2015 Contents Introduction...
More informationPOLYIMIDE INSULATED WIRES AND CABLES, LOW FREQUENCY, 600V, -200 TO +200 C BASED ON TYPE SPL. ESCC Detail Specification No.
Page 1 of 23 POLYIMIDE INSULATED WIRES AND CABLES, LOW FREQUENCY, 600V, -200 TO +200 C BASED ON TYPE SPL ESCC Detail Specification Issue 3 May 2013 Document Custodian: European Space Agency see https://escies.org
More informationEarthing Requirements for HV Transmission Structures
Engineering Standard Electrical MEST 000002-07 Earthing Requirements for Transmission Structures Version: 1 Issued: February 2015 Owner: Engineering Approved By: Patrick Kelly Head of Electrical Engineering
More informationconductor Extruded Cross - Linked Polyethylene Insulated (XLPE) Power Cable Rated Voltage U 0 /U = 12/20 kv U 0 /U = 18/30 kv
Israel Electric Corporation Ltd. - Customer Division - National Network Unit Issued date: February 2018 THE ISRAEL ELECTRIC CORPORATION LTD. National Network Unit Specification No. NPS - 361 for Single
More informationDESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN
Approval Amendment Record Approval Date Version Description 01/04/2014 1 Initial Issue under MTM PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 7 Table of Contents
More informationTECHNICAL SPECIFICATION FOR G.I. WIRE AND G.I. STAY WIRE
WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED OFFICE OF THE MATERIAL CONTROLLER : CENTRAL STORES & PURCHASE DEPARTMENT VIDYUT BHAVAN (4TH FLOOR) : BIDHANNAGAR : KOLKATA-700091 TECHNICAL SPECIFICATION
More informationWIRE & CABLE. 99 Wire Low fire hazard wire and cable
Applications 99 wire has a dual wall construction of radiation cross-linked modified polyester. This combines excellent mechanical performance and chemical resistance with a range of enhanced fire hazard
More information--> Buy True-PDF --> Auto-delivered in 0~10 minutes. GB/T Translated English of Chinese Standard: GB
Translated English of Chinese Standard: GB706-2008 www.chinesestandard.net Sales@ChineseStandard.net NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA GB ICS 77.140.70 H 44 Replacing GB/T 706-1988, GB/T
More informationWire and Cable. 99 Wire Dual Wall 120ºC rated, Modified Polyester Low fire hazard wire and cable. Features & Benefits
Dual Wall 20ºC rated, Modified Polyester 99 wire has a dual wall construction of radiation crosslinked modified polyester. This combines excellent mechanical performance and chemical resistance with a
More information11-SDMS-03 REV. 02 SPECIFICATIONS FOR
11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice
More informationGovernment Recognized Export House OHSAS 18001:2007 ISO 14001:2004 PED Approved Company.
Government Recognized Export House OHSAS 800:200 ISO 400:2004 PED Approved Company. Phone : +9 22 44 (2 Lines) Fax : +9 22 289 4 Email : export@reliablepipes.com domestic@reliablepipes.com Designation:
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More informationThis Manual Part recommends design criteria for resistors suitable for railway signaling circuits other than electronic.
2016 Part 14.2.15 Recommended Design Criteria for Resistors Revised 2016 (6 Pages) A. Purpose z00381hn 3/12/15 8:34 AM z00381hn 3/12/15 8:37 AM This Manual Part recommends design criteria for resistors
More informationFEDERAL SPECIFICATION WIRE, ELECTRICAL, COPPER (UNINSULATED)
8 April 99 SUPERSEDING QQ-W-343F 9 November 990 FEDERAL SPECIFICATION WIRE, ELECTRICAL, COPPER (UNINSULATED) This specification was approved by the Commissioner, Federal Supply Service, General Services
More informationReinforcing Mesh Product Guide
Reinforcing Mesh Product Guide Reinforcing New Zealand since 1954 Super Ductile 500E & Hard Drawn SOUTH ISLAND Fletcher Reinforcing supplies the reinforcing steel and mesh that provides the strength to
More informationDRAFT TANZANIA STANDARD MEDC 10(5692) P3 - SPECIFICATION FOR HONEY EXTRACTOR, RADIAL TYPE
DRAFT TANZANIA STANDARD MEDC 10(5692) P3 - SPECIFICATION FOR HONEY EXTRACTOR, RADIAL TYPE TBS 2018 Draft Edition 1 0. FOREWORDS Honey extractors enable bee-keepers to extract the maximum quantity of honey
More informationAS Australian Standard STEEL WIRE FOR TENDONS IN PRESTRESSED CONCRETE. This is a free 5 page sample. Access the full version online.
AS 1310 1987 Australian Standard STEEL WIRE FOR TENDONS IN PRESTRESSED CONCRETE This Australian Standard was prepared by Committee BD/23, Structural Steel. It was approved on behalf of the Council of the
More informationMESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION
Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:
More informationENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 177 2012 Specification for Braided 75 Ω, Mini-Series Quad Shield Coaxial Cable for CMTS and SDI cables NOTICE
More informationSteel wire for general fencing purposes
BRITISH STANDARD BS 4102:1998 ICS 77.140.65 NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW Specification for Steel wire for general fencing purposes Committees responsible for this
More informationISO INTERNATIONAL STANDARD. Steel wire ropes Vocabulary, designation and classification
INTERNATIONAL STANDARD ISO 17893 First edition 2004-02-15 Steel wire ropes Vocabulary, designation and classification Câbles en acier Vocabulaire, désignation et classification Reference number ISO 2004
More informationData sheet MC GC1000 pro23 Cat.7 S/FTP 4P LSHF-FR 1640 ft
Page 1/6 MC GC0 pro23 Cat.7 S/FTP 4P LSHF-FR 1640 ft 18427034141 Illustrations Principle diagram Product specification 10 GBit installation cable, simplex installation cable Cat.7 AWG 23 S/FTP with wires
More informationTECHNICAL SPECIFICATION FOR G. I. WIRE (4MM)
1. SCOPE: TECHNICAL SPECIFICATION FOR G. I. WIRE (4MM) This Specification provides for manufacture, testing before dispatch at manufacturer's work and supply and delivery of 4mm solid heavily coated Galvanized
More information2. CONDUCTORS. 2.1 Strand Types. 2.2 Coatings Tensile Strength of Copper Wire Copper Strand Properties. 2.5 Aluminum Strand Properties
2. CONDUCTORS 2.1 Strand Types 2.1.1 Concentric Strand 7 2.1.2 Bunch Strand 7 2.1.3 Rope Strand 8 2.1.4 Sector Conductor 8 2.1.5 Segmental Conductor 8 2.1.6 Annular Conductor 8 2.1.7 Compact Strand 8 2.1.8
More informationCERTIFICATE OF CONFORMANCE
CERTIFICATE OF CONFORMANCE This is to confirm that Honeywell Airports Business have verified Tinned Copper Braided Screened Primary Cable supplied by PT Jembo Cable Company Tbk (Indonesia) for airfield
More informationNPS/001/010 Technical Specification for Fasteners and Fixings for Wood Pole Overhead Lines and General Construction Works
Version:- 4.0 Date of Issue:- August 2014 Page 1 of 13 NPS/001/010 Technical Specification for Fasteners and Fixings for Wood Pole Overhead Lines and General Construction Works 1. Purpose The purpose of
More informationOptical Ground Wires (OPGW)
Optical Ground Wires (OPGW) Presented by NSW (Norddeutsche Seekabelwerke GmbH) 4-Nov-13 / 1 NSW The Company Plant Overview 4-Nov-13 / 2 NSW Ground Wire History Our Experience Ground Wire Cables production
More information015 : 1993 CEB STANDARD
015 : 1993 CEB STANDARD UNGALVANIZED STAY ASSEMBLIES CEYLON ELECTRICITY BOARD SRI LANKA Specification for UNGALVANIZED STAY ASSEMBLIES CEB Standard 015 : 1993 CEYLON ELECTRICITY BOARD No. 50, Sir Chittampalam
More informationDETAIL SPECIFICATION SHEET CONNECTORS AND ASSEMBLIES, ELECTRICAL, AIRCRAFT GROUNDING: TYPE IV JUMPER CABLE ASSEMBLY, LEAD, ELECTRICAL
INCH-POUN 10 June 2015 SUPRSING MIL-TL-83413/8 w/amendment 1 30 July 2014 TAIL SPCIFICATION SHT CONNCTORS AN ASSMBLIS, LCTRICAL, AIRCRAFT GROUNING: TYP IV JUMPR CABL ASSMBLY, LA, LCTRICAL This specification
More informationDraft for comments only Not to be cited as East African Standard
EAST AFRICAN STANDARD Tangential type honey extractor Specification EAST AFRICAN COMMUNITY CD/K/655:2010 ICS 65.140 EAC 2010 First Edition 2010 Foreword Development of the East African Standards has been
More informationISO INTERNATIONAL STANDARD. Welding Studs and ceramic ferrules for arc stud welding
INTERNATIONAL STANDARD ISO 13918 Second edition 2008-02-15 Welding Studs and ceramic ferrules for arc stud welding Soudage Goujons et bagues céramiques pour le soudage à l'arc des goujons Reference number
More informationReinforcing Mesh Product Guide
Reinforcing Mesh Product Guide Reinforcing New Zealand since 1954 Super Ductile 500E & Hard Drawn NORTH ISLAND Fletcher Reinforcing supplies the reinforcing steel and mesh that provides the strength to
More informationSPECIFICATION FOR HIGH STRENGTH STRUCTURAL BOLTS
UDC 621.882.211 [669.14.018.291] IS : 3757-1985 (Reaffirmed 2003) Edition 3.2 (1989-07) Indian Standard SPECIFICATION FOR HIGH STRENGTH STRUCTURAL BOLTS ( Second Revision ) (Incorporating Amendment Nos.
More informationData sheet MC GC1200 pro22 Cat.7A S/FTP 4P LSHF-FR, class Dca s2 d2
Page 1/7 Illustrations Principle diagram See enlarged drawings at the end of document Product specification 10 GBit installation cable, simplex installation cable Cat.7A AWG 22 S/FTP with wires shielded
More informationSecurifor Polyester Coated Welded Mesh Panels
1 Scope This specification specifies requirements for panels made out of galvanised steel wires, welded and subsequently polyester coated for fencing. The panels are used for fencing, schools, public buildings,
More informationDetailed Specifications & Technical Data
For more Information please call 1-800-Belden1 General Description: PTZ (CCTV+Control+Power) Cable, Rated-CM, 1-RG59 20 AWG solid bare copper with foam polyolefin, 95% bare copper braid, 1-22 AWG stranded
More informationContents DIN 50125:
14 Contents Foreword... 3 1 Scope... 4 2 Normative references... 4 3 Terms and definitions... 4 4 Types, dimensions, and designation... 4 4.1 General... 4 4.2 Type A test pieces... 6 4.3 Type B test pieces...
More informationAluminum-clad Steel Wire
AS Wire/GS Wire AS WIRE Aluminum-clad Steel Wire GS WIRE Galvanized Steel Wire Made in the U.S.A. Development of Aluminumclad Steel (AS) Wire Conex Cable, LLC, under the original name of Conex, started
More informationSignal converter for electromagnetic flowmeters
Quick Start Signal converter for electromagnetic flowmeters Electronic revision: ER 3.0.xx The documentation is only complete when used in combination with the relevant documentation for the flow sensor.
More informationSECTION-I (G.I.PLAIN WIRE) TECHNICAL SPECIFICATION FOR G. I. WIRE
SECTION-I (G.I.PLAIN WIRE) TECHNICAL SPECIFICATION FOR G. I. WIRE 1. SCOPE :- This Specification provides for manufacture, testing before dispatch at manufacturer's work and supply and delivery of 3.15mm
More informationISO INTERNATIONAL STANDARD. Fasteners Torque/clamp force testing. Éléments de fixation Essais couple/tension. First edition
Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 16047 First edition 2005-02-01 Fasteners Torque/clamp force testing Éléments de fixation Essais couple/tension Reference number ISO 16047:2005(E)
More informationSchluter -DITRA-HEAT Repair procedure for the DHE-HK Heating Cable
Schluter -DITRA-HEAT Repair procedure for the DHE-HK Heating Cable 555758 03/2018 2018 Schluter Systems L.P. DITRA and HEAT E are registered trademarks of Schluter Systems CONTENTS 3 List of tools required
More informationTru products are now under the Tru-Win brand from Winchester Interconnect.
TRUflex PWR Series TRUflex PWR Series cable assemblies offers an extensive line of flexible RF cable assembly and connector solutions for applications that require RF high power/voltage capability as well
More informationMaterials. Density, Hooke's law, Young modulus. 174 minutes. 174 marks. Page 1 of 29
Materials Density, Hooke's law, Young modulus 174 minutes 174 marks Page 1 of 29 Q1. A uniform wooden beam of mass 35.0 kg and length 5.52 m is supported by two identical vertical steel cables A and B
More informationStandard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables
Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES ( Data Sheets ) 11 kv XLPE-Insulated Three-Core Underground Cables (3x240 mm 2 ) ADWEA/ADDC/AADC STANDARD : D-AAA-CAB-11-3Cx240
More informationLow Loss Pre-Connectorized Cable Sets, LL58 Series, DC-3.5GHz
Low Loss Pre-Connectorized Cable Sets, LL58 Series, DC-3.5 reliable performance, dependable service Replace traditional RG types for benefit of: lower loss better shielding > - 90dB Drop in replacement
More informationJ O I N T I N D U S T R Y S T A N D A R D. Requirements for Soldering Pastes J Standard 005A. December 2011
J O I N T I N D U S T R Y S T A N D A R D Requirements for Soldering Pastes J Standard 005A December 2011 Requirements for Soldering Pastes 1.0 SCOPE 1.1 Scope This standard prescribes general requirements
More informationStandards Update Notice (SUN) Issued: June 6, 2017
Standard Information Standard Number: UL 758 Standard Name: Standard for Safety for Appliance Wiring Material Standard Edition and Issue Date: 3 rd Edition Dated May 2, 2014 Date of Revisions: 2 nd Ed.
More informationSPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES
KP/3CB/TSP/0/00 04-09-9 Page of 9 TABLE OF CONTENTS 0. Circulation List 0. Amendment Record FOREWORD. SCOPE. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING, LABELLING
More informationStandard Specification for High-Strength Bolts for Structural Steel Joints [Metric] 1
Designation: A 325M 00 METRIC An American National Standard Standard Specification for High-Strength Bolts for Structural Steel Joints [Metric] 1 This standard is issued under the fixed designation A 325M;
More informationAVA5-50FX. Product Classification. Standards And Qualifications. Construction Materials. Dimensions. Electrical Specifications
AVA5RK-50FX, HELIAX Andrew Virtual Air Coaxial Cable, corrugated copper, 7/8 in, black, Non-halogenated, fire retardant polyolefin jacket B2ca-s1b,d1 Product Classification Brand Product Series Product
More information1. Enumerate the most commonly used engineering materials and state some important properties and their engineering applications.
Code No: R05310305 Set No. 1 III B.Tech I Semester Regular Examinations, November 2008 DESIGN OF MACHINE MEMBERS-I ( Common to Mechanical Engineering and Production Engineering) Time: 3 hours Max Marks:
More informationThickness tolerances of steel plates and wide flats
(1981) (Rev.1 1989) (Rev.2 1992) (Rev.3 1995) (Rev.4 Oct 2009) (Rev.5 Feb 2012) Thickness tolerances of steel plates and wide flats.1 Scope.1.1 These requirements apply to the tolerance on thickness of
More informationISO INTERNATIONAL STANDARD. Plain bearings Wrapped bushes Part 2: Test data for outside and inside diameters
INTERNATIONAL STANDARD ISO 3547-2 Second edition 2006-10-15 Plain bearings Wrapped bushes Part 2: Test data for outside and inside diameters Paliers lisses Bagues roulées Partie 2: Données d'essai pour
More informationMETRIC FASTENERS 1520 METRIC FASTENERS
1520 METRIC FASTENERS METRIC FASTENERS A number of American National Standards covering metric bolts, screws, nuts, and washers have been established in cooperation with the Department of Defense in such
More informationEurocode EN Eurocode 3: 3 Design of steel structures. Part 1-1: General rules and rules for buildings
Eurocode EN 1993-1-1 Eurocode 3: 3 Design of steel structures Part 1-1: General rules and rules for buildings Eurocode EN 1993-1-1 Eurocode 3 applies to the design of buildings and civil engineering works
More information2001 HSC Engineering Studies Marking Guidelines
00 HSC Engineering Studies Marking Guidelines Question (a) ( marks) Outcomes assessed: H. States a valid material once used extensively, and a valid material that has replaced it, and gives a valid reason
More informationSPECIFICATION FOR SINGLE-MODE OPTICAL FIBRES
SINGLE-MODE OPTICAL FIBRES SPECIFICATION FOR SINGLE-MODE OPTICAL FIBRES SPC-00571 JUNE 2006 Revision 3.00 NON-DISCLOSURE OF INFORMATION Information contained in this document is proprietary in nature and/or
More informationCOIL WINDING ISSUES P. Fabbricatore INFN Genova LCD - Magnet 13Oct09. Coil winding issues
Coil winding issues Based on experience acquired with CMS coil construction, some preliminary considerations about the envisaged winding (and in general manufacturing) issues of a large superconducting
More informationDESIGN OF MACHINE MEMBERS-I
Code No: R31035 R10 Set No: 1 JNT University Kakinada III B.Tech. I Semester Regular/Supplementary Examinations, Dec - 2014/Jan -2015 DESIGN OF MACHINE MEMBERS-I (Mechanical Engineering) Time: 3 Hours
More informationEXTRUDED, CROSS-LINKED FLUOROPOLYMER INSULATED WIRES AND CABLES ON SILVER-PLATED COPPER CONDUCTOR, LOW FREQUENCY, 600V, -100 TO +200 C
Page 1 of 24 ETRUDED, CROSS-LINKED FLUOROPOLYMER INSULATED WIRES AND CABLES ON SILVER-PLATED COPPER CONDUCTOR, LOW FREQUENCY, 600V, -100 TO +200 C ESCC Detail Specification Issue 4 March 2013 Document
More informationNPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations
Version: 3.1 Date of Issue: September 2016 Page: 1 of 21 NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations 1. Purpose The purpose of this document is to detail the technical requirements
More informationH155A02. Product Description. Product Specifications. Technical Specifications. Application. Bend Radius. CCB-Sub-Crush Resistance.
H155A02 Part Number: H155A02 COAX RF H155 FRNC Product Description COAX RF H155 FRNC Product Specifications Application Application 1: Application 2: 50 Ohm low loss coaxial transmission cable designed
More informationENERGY CORDAFLEX (SMK) (N)SHTOEU Low Voltage Reeling Cable
ENERGY (N)SHTOEU Low Voltage Reeling Cable Technical Data Type Type designation Approvals/standards Application (N)SHTOEU-J/-O DIN VDE 0250, Part 814; VDE-Reg.-Nr. 7519; GOST R Flexible reeling cable for
More informationSection 914. JOINT AND WATERPROOFING MATERIALS
914.01 Section 914. JOINT AND WATERPROOFING MATERIALS 914.01. General Requirements. Joint and waterproofing material for use in concrete construction must meet the requirements of this section. 914.02.
More informationTECHNICAL DATA SHEET FOR Single Mode Optical Fibre Cable Direct Burial Application
TECHNICAL DATA SHEET FOR Single Mode Optical Fibre Cable Direct Burial Application (SM 12 Fibers) Product: Single Mode Optical Fiber Cable Customer: Date: Write by: Kevin Zhou / technical engineer International
More informationCrimping Instructions
Fischer Connectors SA SaintPrex, Switzerland Phone +41 21 00 9 9 Fax +41 21 00 39 24 www.fischerconnectors.com mail@fischerconnectors.ch Crimping Instructions Assembly Instructions CONTENTS Page Scope
More informationSBCA Industry Standards Subcommittee. Specification for 75 Ω Flexible RF Coaxial Drop Cable for Direct Broadcast Satellite (DBS) Installations
SBCA Industry Standards Subcommittee Document: SBCA Series 6 Recommended Practices Date of Issue: Specification for 75 Ω Flexible RF Coaxial Drop Cable for Direct Broadcast Satellite (DBS) Installations
More informationAustralian/New Zealand Standard
AS/NZS 1167.2:1999 Australian/New Zealand Standard Welding and brazing Filler metals Part 2: Filler metal for welding AS/NZS 1167.2:1999 This Joint Australian/New Zealand Standard was prepared by Joint
More informationApplication Specification Releasable Poke-in Connector 08JUL 2015 REV:A
Application Specification 114-137055 Releasable Poke-in Connector 08JUL 2015 REV:A 1. INTRODUCTION This specification covers the requirements for application of Releasable Poke-in connector for use on
More informationHigh Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems
High Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems Summary for Call for Nominations 1. Background and scope ITER will be the world's largest experimental facility to demonstrate
More informationCOPPERCLAD STEEL WIRE. Dead Soft Annealed Jacketed High Strength. Extra High Strength Composite Conductors Guy Wire
COPPERCLAD STEEL WIRE Dead Soft Annealed Jacketed High Strength Extra High Strength Composite Conductors Guy Wire Founded in 1984, AFL is an international manufacturer providing end-to-end solutions to
More informationEDICT ± OF GOVERNMENT
EDICT ± OF GOVERNMENT Inordertopromotepubliceducationandpublicsafety,equal justiceforal,abeterinformedcitizenry,theruleoflaw,world tradeandworldpeace,thislegaldocumentisherebymade availableonanoncommercialbasis,asitistherightofal
More informationDRAFT TANZANIA STANDARD. TBS/CDC-2(4970) P3- Carbolic Soap - Specification (Revision of TZS 221:1984)
DRAFT TANZANIA STANDARD TBS/CDC-2(4970) P3- Carbolic Soap - Specification (Revision of TZS 221:1984) TANZANIA BUREAU OF STANDARDS Foreword This Draft Tanzania Standard is being developed by the Soap and
More informationASSEMBLY TOOLS FOR SCREWS & NUTS. Part 1: Insulated hand operated socket drive wrenches and screw drivers
Doc. KP1/3CB/TSP/09/088-1 1 Page 1 of 21 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6.
More informationDETAIL SPECIFICATION SHEET CABLES, RADIO FREQUENCY, SEMIRIGID, COAXIAL, SEMI-AIR-DIELECTRIC,.875 TO INCHES OUTSIDE DIAMETER, 50 OHMS
INCH-POUND MIL-DTL-22931/11B 21 August 2013 SUPERSEDING MIL-C-22931/11A 20 January 1972 DETAIL SPECIFICATION SHEET CABLES, RADIO FREQUENCY, SEMIRIGID, COAXIAL, SEMI-AIR-DIELECTRIC,.875 TO 1.005 INCHES
More informationAll the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.
1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred
More informationCrimping Instructions
Fischer Connectors SA SaintPrex, Switzerland Phone +41 21 800 95 95 Fax +41 21 800 39 24 www.fischerconnectors.com mail@fischerconnectors.ch Crimping Instructions Assembly Instructions CONTENTS Page Section
More informationINSTRUCTIONS FOR THE SAFE APPLICATION OF CABLES
THE SAFE APPLICATIO OF CABLES The cables manufactured by S are only appropriate for the transmission of electric energy for supply and signalling purposes. First of all the valid construction and installation
More informationStandard Specification for Copper-Clad Steel Wire for Electronic Application 1
Designation: B 45 0 Standard Specification for Copper-Clad Steel Wire for Electronic Application 1 This standard is issued under the fixed designation B 45; the number immediately following the designation
More informationINCH-POUND. MIL-DTL June 2008 DETAIL SPECIFICATION WIRE ROPE, 1.5 INCH DIAMETER, GALVANIZED, COMPACTED STRAND, FOR AIRCRAFT ELEVATOR
INCH-POUND 2 June 2008 DETAIL SPECIFICATION WIRE ROPE, 1.5 INCH DIAMETER, GALVANIZED, COMPACTED STRAND, FOR AIRCRAFT ELEVATOR This specification is approved for use by all Departments and Agencies of the
More information