Protection & Control Challenges with Distributed Generation

Size: px
Start display at page:

Download "Protection & Control Challenges with Distributed Generation"

Transcription

1 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Protection & Control Challenges with Distributed Generation Pankaj Sharma, P Eng. Grid Operations Manager Operating Effectiveness Networks Operating Division Hydro One Networks Inc. July 2015

2 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc OBJECTIVES Identify major Protection & Control (P&C) Challenges with Distributed Generation (DG) Connections Discuss Mitigation of P&C Challenges Acknowledge advantages of Transfer-Trip (TT) Application Foster important role of P&C in enabling DG

3 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc AGENDA Background Impacts on P&C assets, Challenges & Solutions Transmission Side Distribution Side Operating issues and mitigations DG Interconnection Protection Challenges Utility Protection Advantages of the Transfer Trip Example of an Islanding event with UFLS operation Summary

4 2015 Hydro One. All rights reserved. BACKGROUND Ontario T & D Operating Effectiveness Hydro One Networks Inc (P&C) Protection & Control Transmission System (Tx) Above 50kV Distribution System (Dx) 50kV & Below 1. Transmission Station (feeders, buses, transformers etc) 2. Transmission lines 1. Distribution Station Fuses, Transformers, Re-closers etc) 2. Distribution lines

5 Total DG Connected - mid 2015 Total Distributed Generation connected at Distribution: 2865 MW Bio/CoGen 185 MW Solar 1236 MW Gas 362 MW Hydro 383 MW Wind 473 MW Other (Steam) 226 MW Micro 115 MW (Each project < 10 KW) Wind Solar Bio/CoGen Gas Hydro Other (Steam) Micro 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc

6 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Total DG Connected - mid 2015 Total Distributed Generation connected at Transmission: 3395 MW Wind 3255 MW Solar 140 MW Wind Solar

7 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Transmission & Distribution System Transmission Line 2 Transmission System Transmission Line 1 T1 DESN Transformer Station (TS) T 2 Current Transformer Circuit Breaker Transformer Station (TS) Fence Bus A Bus B Feeder M 1 Feeder M 2 Re-closer Feeder M 3 Feeder M 4 Distribution Station (DS) Fuse T4 F 1 Distribution System F 2 DS Fence DS Transformer F 3

8 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Impacts on P&C assets Transmission Side Impacts on the Transformer Station (TS) Feeder protection Bus protection, Line back-up Transformer protection, Automatic Voltage Reg Ground Potential Rise, Neutralizing Transformer, Neutral Grounding Reactor Existing Special Protection Schemes (Load Rejection and Generation Rejection schemes) Network Management System Under Frequency Load Shedding Impacts on the Transmission Line

9 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Feeder Protection Feeder Protection De-Sensitization - Upgrades Feeder Sympathetic trips - Directioning Out of Phase Re-closing of the Feeder Transfer-Trip (TT), and DG End Open Signal (DGEO) Protection Mis-operation due to DG Transformer Magnetizing Currents - Low Set Blocking Signal Protection coordination with downstream devices Ensure capacity of feeder breaker CT is not exceeded

10 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Bus Protection Low impedance Bus differential protection is not affected but may no longer prove to be secure Bus blocking scheme must be reviewed and may need directioning Bus blocking scheme is not affected by DG for faults occurring on the feeder Bus blocking scheme is affected by DG for faults occurring on the bus

11 Bus Blocking Scheme Feeder Fault 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Transmission System Line 2 Line 1 DESN Transformer Station Fault current flows thru feeder protection and bus protection CTs. 50B-Abus 50B-Bbus T1 T2 Bus A Protection I Abus relay = I T1 + I T2 = I F - 32 ms coordination delay - F1 block signal prevents trip Bus A remains in service. Bus A Bus B Feeder protection operates, sends a bus blocking signal to Bus A. F1-21 F2-21 Bus B Protection I Bbus relay = I T2 + -I T2 = 0 - Bus B also remains in service. F1 CB Feeder 1 opens Feeder 2 Forced Outage Feeder Fault on Feeder F1

12 Bus Blocking Scheme Bus Fault 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Transmission System Line 2 Line 1 DESN Transformer Station 50B-Abus 50B-Bbus T1 T 2 CB s open to trip Bus A Bus A Bus B I Abus relay = IT1 + IT2-32 ms coordination delay CTs add fault current for Bus A; Bus A protection operates F1-21 Blocking signal F2-21 was not sent. I Bbus relay = IT2 + -IT2 = 0 - Bus B remains in service. CTs circulates fault current for Bus B; Bus B remains in service. Feeder #1 Feeder #2 Forced outage Bus Fault with no DG

13 2015 Hydro One. All rights reserved. Bus Blocking Bus Fault Operating Effectiveness Hydro One Networks Inc Transmission System Line 2 Line 1 DESN Transformer Station SOLUTION: Directioning of B bus blocking relays will prevent false operation for faults on A bus. This allows faults to be precisely isolated. T1 Bus A 50B-Abus 50B-Bbus Bus B T2 PROBLEM: With DG present, CT at bus tie measures additional DG fault current which creates an imbalance causing the protection for the healthy Bus B to false operate. Bus forced outage is more widespread than necessary. CTs add fault current for Bus A; Bus A protection operates F1-21 F2-21 Feeder #1 Feeder #2 No fault current at Feeders of bus A thus no operation and blocking signal not sent Feeder 2 protection does not operate because directioned thus blocking signal is not sent Bus Fault with DG on feeder F2 Forced outage

14 Line Protections Transfer Trip 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Line Protections Transfer Trip Line Back-Up Protection Station Supplied by Two Transmission Lines Line 1 Line 2 Forced Outage T1 DESN Transformer Station T2 Bus A Line Back-Up Protection Bus B A fault on one transmission line can be fed by the other transmission line because the transformer station creates a path for electric current between the two lines Line Protections detect the fault and respond by taking the line out of service. M 1 M 2 M 3 M 4 Also, a Transfer Trip Signal is sent to the TS so that the LV CB will open. This cuts off the electrical path between the two lines. In case the Transfer Trip fails however, line back-up protection is required. Line back-up is implemented at the station, and can also signal the LV CB to open during a line fault. All TS s fed by two lines are equipped with Line Back-Up Protection.

15 Line Protections Transfer Trip 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Line Protections Transfer Trip Line Back-Up Protection Station Supplied by One Transmission Line Transmission Line Forced Outage Transformer Station T1 T2 Bus A Line Back-Up Protection Bus B M 1 M 2 Transformer Stations (TS) that are supplied by one line and have no DG s connected downstream, do not require Line Back-Up Protection. This is because there is no current sourcing from within the TS that can feed the fault on the transmission line. The fault is managed by the Line Protections. PROBLEM: Once a DG is connected, the line fault can be fed through the TS by the DG. It is therefore necessary to send a Transfer Trip signal to open the DG CB. However, this station does not have Line Back-Up protections to safeguard against a Transfer Trip failure. If the Transfer Trip had failed, the DG would have fed the fault. SOLUTION: Line Back-Up Protections must be installed at TS if DGs are present. This ensures that line fault will not be fed by DG s if there is a failure on the transfer trip.

16 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Transformer P & C Transformer Differential protection at stations having three winding transformers; needs to be upgraded to provide separate restraint windings Transformer LV breaker re-closing scheme may need changes (sync-check may be needed) Restricted ground fault protection may be required if the NGR impedance is increased

17 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Transformer P & C Overload protections, monitoring of reverse flows, total current harmonics and winding temperatures may also be required ULTC voltage regulation may have to be reviewed/changed for reverse P / forward Q flows Volts/Hertz relay may need to be considered for over-fluxing

18 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc GPR, NT, NGR Increased Ground Fault level increases Ground Potential Rise (GPR) requires Neutralizing Transformer (NT) voltage rating and spare communications ports to be reviewed may be replaced with Optical isolator requires Neutral Grounding Reactor (NGR) size to be reviewed ohms may have to be increased to respect TSC limits (Transmission System Code) Location of communication equipment in relay building may have to be re-assessed

19 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Existing SPS Review existing Special Protection System (SPS) Load Rejection (LR) and Generation Rejection (GR) schemes Modifications may be required New Generation Rejection Schemes may be required

20 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Network Management System (NMS) Upgrades needed to match the changes due to DG HMI display changes are required at NMS and LCC Existing Hub sites capacity issue and new sites Unbundle IED relay failure alarms for selectivity

21 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Network Management System (NMS) Review existing RTU capacities: Protection alarm points Telemetry (Amp / MW) and directioning of quantities Operator control tripping of DG RTU may not be adequate; upgrades, expansion or even replacements may be required Upgrade PCMIS to include DG relay settings (Protection & Control Management Information System)

22 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Under Frequency Load Shedding (UFLS) Review existing UFLS scheme Re-configure feeder selection in UFLS Feeders with DG - to be excluded, or Real time intelligence in selecting feeder under UFLS (dynamic arming), or Extending UFLS to DS and re-closer level

23 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Impacts on Transmission Lines Transmission line protection issues Consideration of: Changes due to on-going protection relay replacement programs and/or Tx connected generations Telecom changes Impacts on re-closing circuit Re-closing schemes & timing Keying of T/T and receiving of DGEO signal

24 Transmission Lines Protection Issues Non-Overlapping Zone 1 Protections Enlarged apparent impedance Current Out feed (Current Reversal) 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc

25 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Non-Overlapping Zone 1 Protections New Generator Terminal Station 1 Zone 1 Zone 1 Terminal Station 2 Existing customers If zone 1 elements are required not to trip fault beyond new tapped generation CB, the instantaneous zone 1 protection will not be overlapping. The gap area between the reaches of two zone 1s must be protected by teleprotection scheme.

26 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Enlarged apparent impedance Terminal Station 1 New Generator I G Z 1 Z 2 Terminal Station 2 I 1 I 2 Z App V 1 I 1 Z I Z I I Z Z I I G 1 L 2

27 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Current Out feed (Current Reversal) New Generator Existing Generator Terminal Station 1 I G_1 I G_2 Z 1 Z 2 I 1 I 2 Z 3 L 1 Terminal Station 2 I 3 When a paralleling path exists, the tapped generation may cause current reversal. The distance element will sense a fault close to the remote station as a backward fault. L 2

28 2015 Hydro One. All rights reserved. P & C Planning, Network Development & Regional Panning Impacts on P&C assets Distribution Side Feeder re-closer controller settings, protection coordination & fuse saving? Need for HV side automatic interrupting device at DS? Incorporate blocking scheme? Un-cleared low level faults between existing HV fuse and station re-closer section? Sympathetic Tripping - false tripping of a healthy feeder on adjacent feeder faults? Need for communications at re-closers?

29 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Operating issues and mitigations ISLANDING Transmission Line 2 Transmission Line 1 DESN T1 Transformer Station (TS) T 2 Planned Outage Current Transformer Circuit Breaker Transformer Station (TS) Fence DG Bus A Bus B Feeder M 1 Feeder M 2 DG Re-closer Feeder M 3 Feeder M 4 Distribution Station (DS) DG DG Fuse T4 F 1 F 2 DG DS Fence DS Transformer F 3

30 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc DG Interconnection Protection Challenges Overcurrent Protection difficult to set at DG locations. Inverters - Maximum current about 1.2 p.u., less if DG running at less than max capacity, so there is not enough difference between load and fault for relay to distinguish using over-current Rely on undervoltage element to trip DG. Does not always work!! Faults far away from PCC not visible to DG.

31 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Challenges What about Distance Protection? Zone 1 = 75-80% of Z1 (Instantaneous fault clearance for overlap zone, and high speed trip for rest). Zone 2 (P) = % of Max Apparent Impedance. (High speed or Fast trip for entire line and backed-up with Time Delay trip, usually 400ms). By setting Zone 2 to 120% of the Max Apparent Impedance for remote 3 phase fault, the relay reach becomes huge. With interface transformer HV winding ungrounded the ground distance protection not applicable

32 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Challenges Inverters limit fault current & maintain constant power factor dynamically. Inverters behaviour during fault is important before determining the suitability of the relaying at the DG. Inverters modeled as a current limiting source

33 2015 Hydro One. All rights reserved. DG Interconnection Protection Typical shortcomings Operating Effectiveness Hydro One Networks Inc DG in-feed to a fault anywhere on the Dx can be virtually identical for inverters. All Dx/Tx faults are in the same direction. Direction cannot be used to avoid tripping for faults on adjacent feeders. Current only, voltage only or distance cannot be used to avoid tripping for faults on adjacent feeders. However, distance offers greater precision compared to overcurrent when reach discrimination is required.

34 2015 Hydro One. All rights reserved. DG Interconnection Protection Typical shortcomings Operating Effectiveness Hydro One Networks Inc DG never is certain of the fault location and whether it needs to trip or ride through. Without TT - DG need to delay tripping (at least 150ms) after the utility trips. Even with the longer delays it is difficult to avoid DG nuisance trips for adjacent feeder permanent faults that are cleared by timed protection elements. Delay may be too long due to declining fault infeeds risk asynchronous reclosing into DG + feeder island.

35 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Utility Protection Utility protection has visibility of entire feeder. Utility feeder protections are capable of selective detection and isolation of all faults on the feeder. With fault location discrimination it is determined whether or not the DG needs to be tripped for a feeder fault condition.

36 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Utility Protection Where current magnitude alone is not sufficient, utility feeder protection use direction to avoid tripping for DG back-feeds to source-side faults (adjacent feeder) Transfer Trip (TT) can extend utility protection to the DG for fast clearing. Sequential delay is unavoidable when DG is not capable of detecting feeder faults & there is no TT

37 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Utility Protection Adaptive Relaying Distribution Generation Control Protection (DGCP) Real Time Automation Controller (RTAC) can provide the mechanism to reconfigure both the sending and receiving protection signals to/from remote field devices and feeder breakers whenever changes occur in the feeder topologies. The Distribution Management System (DMS) sends topology changes to the DGCP and the DGCP automatically re-configures the protection signals based on the new topology. Automatically switching setting groups and summing CTs prior to entering or after exiting back-to-back parallel of feeders.

38 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Utility Protection Adaptive Relaying Blocking the tripping for 44kV reclosers for a loss-of-protection. Ground backup protection at the DS to open the 44kV recloser at the station for a 27.6/13.8/8.2 kv station recloser failure condition. The UFLS infrastructure to allow adaptive relaying by evaluating feeder loading conditions by the DMS and having DMS automatically arm selections in real-time at the TS station, 44kV reclosers and 27.6/13.8/8.2 kv DS station reclosers based on the DG generation and loading to satisfy the target load rejection requirement at the TS. The 27.6/13.8/8.2 kv capacitor banks and voltage regulators can be provided with new controllers and remote control but still switch automatically based on the voltage but with the added remote control switching capability.

39 2015 Hydro One. All rights reserved. Advantages of Transfer Trip Operating Effectiveness Hydro One Networks Inc TIMELESS Deterministic, Most Reliable & Safest NO Non-Detection-Zone Operates for Inadvertent Trips TRANSFER TRIP Facilitates DGEO, LSBS Fault Ride- Through Possible (LVRT, LFRT) Provides Rapid Fault Clearance, Fuse Saving, Power Quality Expedites Restoration Efforts

40 2015 Hydro One. All rights reserved. Example of an Islanding Event Operating Effectiveness Hydro One Networks Inc Sidney TS Configuration P4S (Tx line) L1L4 P3S (Tx line) B1S (Tx line) Q6S (Tx line) L6L4 L6L3 TL3 TL1 T2 T1 T2Q BQ T1B M1 M4 M3 M5 M7 R9S M6 R8S SC1 SC1Q SC2B SC2

41 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Pre-Fault Condition P4S (Tx line) L1L4 P3S (Tx line) B1S (Tx line) Q6S (Tx line) L6L4 L6L3 TL3 TL1 DG: 13MW Total Station Load: 58MW, 30MVAR T2 T2Q 45MW+j9MVar BQ 45.5k V T1 Planned Outage on T1 T1B G/L: A 111A M1 M3 M4 M5 253A 179A SC1 76A 27A SC1Q M7 R9S M6 R8S SC2B 33A 65A SC2 j21mvar

42 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Pre-fault Statuses of Generators on LV feeders Trent Severn TT: Yes 0/5 Sonoco NUG TT: No 6.68/7.2 T2 T2Q BQ T1 T1B M1 M4 M3 M5 Sills Island TT: No 0.65/2.215 Glen Miler TT: Yes 1.6/7.2 Frankford TT: No 0.67/2.4 Sidney GS TT: Yes 0.87/2.8 M7 M6 Hakkesteegt /0.2 Glenburne Farm /0.25 R8S R9S 416 Hwy 33 /0.2 Hagues Reach TT: No 0.3/3.3 SC1 SC1Q SC2B SC2 Meyersburg TT: No 0.84/6 Ranney Falls TT: No 1.43/10.9

43 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Fault Condition P4S L1L4 P3S B1S Q6S L6L4 L6L3 TL3 TL1 T2 T1 T2Q BQ T1B M1 M4 M3 M5 M7 R9S M6 R8S SC1 SC1Q SC2B SC2

44 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Effect of UFLS on Islanding Event I (R Φ), Feeder M1 Time (ms) 1 0 f U (Hz) (p.u.) P (MW) Events 115kV Line Q6S Fault cleared, Islanding started OPG Generators 81U Pickup 3 I 0 (System, transformers neutral currents) UFLS Stage 1 Pickup V (R W, Φ - Φ), LV Bus UFLS Stage 2 Pickup P, Feeder M Glen Miler DG Tripped (81U setting: 58.4Hz, 0s) Q, Feeder M1 Frequency Feeder M4, M3, M5, M6, M7 tripped due to UFLS All DG tripped except Sills Island Island Collapsed

45 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc SUMMARY and Important Points Identify P&C upgrades at Tx and Dx Detailed P&C assessment should be carried out Adequate feeder characteristics must be provided to customer to determine relay settings at DG end DG inter-tie protection design and relay setting must be reviewed for acceptance Change controls Feeder Model & Configuration, Short circuit levels and DG equipment changes etc.

46 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc SUMMARY and Important Points Challenges in DG protections relay settings Depending upon DG type/locations feeder faults may not be visible to DG protections, issues with O/C & Distance Protection DG protections have inherent disadvantages Difficult trade off between DG protection sensitivity and selective may suffer high number of nuisance trips Utility feeder protections have advantages Sensitive, Selective and Deterministic Advantages of Transfer Trip and Adaptive Relaying to improve DG availability when not required to trip and ensure effective tripping of DGs when required to trip.

47 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc Thank You follow-up questions: (Tel) (Mobile)

48 2015 Hydro One. All rights reserved. Operating Effectiveness Hydro One Networks Inc DISCLAIMER The purpose of this presentation is to provide information about some of the issues that Hydro One Networks Inc. ( Hydro One ) has encountered during the process of connection generation facilities to Hydro One s distribution system. The particular concerns that must be addressed by a generation proponent in respect of the connection of its generation facility to Hydro One s distribution system will be set out in the Connection Impact Assessment that Hydro One performs or has performed, as the case may be, for such proposed connections and this presentation is not intended to amend, modify or replace same. Hydro One will not be liable or be responsible for any consequences of the use or reliance on the information contained in this presentation.

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection) Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving

More information

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 Prepared by System Planning Division Transmission Planning Department PJM 2016 Table of Contents Table of Contents Approval...6

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

Electrical Systems - Course 135 COMPOSITE ELECTRICAL PROTECTIVE SCHEMES: PART I

Electrical Systems - Course 135 COMPOSITE ELECTRICAL PROTECTIVE SCHEMES: PART I Electrical Systems - Course 135 COMPOSTE ELECTRCAL PROTECTVE SCHEMES: PART BUSES AND TRANSFORMERS L.0 ntroducton Following on from lesson 135.03-1, this lesson shows componte protective schemes for buses

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application General Application Information Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application Hydro One Remote Communities Inc. Lori.Rice@hydroone.com 1-807-474-2828 This Application

More information

Hamdy Faramawy Senior Application Specialist ABB Sweden

Hamdy Faramawy Senior Application Specialist ABB Sweden Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection Engineered Solutions for Power System Protection, Automaton and Control APPLICATION NOTE Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection 180622 Abstract This

More information

Power Plant and Transmission System Protection Coordination

Power Plant and Transmission System Protection Coordination Technical Reference Document Power Plant and Transmission System Protection Coordination NERC System Protection and Control Subcommittee Revision 1 July 2010 Table of Contents 1. Introduction... 1 1.1.

More information

Line Protection Roy Moxley Siemens USA

Line Protection Roy Moxley Siemens USA Line Protection Roy Moxley Siemens USA Unrestricted Siemens AG 2017 siemens.com/digitalgrid What is a Railroad s Biggest Asset? Rolling Stock Share-holders Relationships Shipping Contracts Employees (Engineers)

More information

Transmission System Phase Backup Protection

Transmission System Phase Backup Protection Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need

More information

Adaptive Protection in Medium Voltage Maritime Applications. Nordic Workshop on Relay Protection, 25 May 2016, Trondheim, NORWAY

Adaptive Protection in Medium Voltage Maritime Applications. Nordic Workshop on Relay Protection, 25 May 2016, Trondheim, NORWAY Adaptive Protection in Medium Voltage Maritime Applications Nordic Workshop on Relay Protection, 25 May 2016, Trondheim, NORWAY Adaptive Protection in Medium Voltage Maritime Applications PhD. Fellow Catalin

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

Power Plant and Transmission System Protection Coordination

Power Plant and Transmission System Protection Coordination Agenda Item 5.h Attachment 1 A Technical Reference Document Power Plant and Transmission System Protection Coordination Draft 6.9 November 19, 2009 NERC System Protection and Control Subcommittee November

More information

Bus Protection Fundamentals

Bus Protection Fundamentals Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT

More information

Power System Protection Where Are We Today?

Power System Protection Where Are We Today? 1 Power System Protection Where Are We Today? Meliha B. Selak Power System Protection & Control IEEE PES Distinguished Lecturer Program Preceding IEEE PES Vice President for Chapters melihas@ieee.org PES

More information

Central Hudson Gas & Electric Corporation. Transmission Planning Guidelines

Central Hudson Gas & Electric Corporation. Transmission Planning Guidelines Central Hudson Gas & Electric Corporation Transmission Planning Guidelines Version 4.0 March 16, 2016 Version 3.0 March 16, 2009 Version 2.0 August 01, 1988 Version 1.0 June 26, 1967 Table of Contents

More information

Power Station Electrical Protection A 2 B 2 C 2 Neutral C.T E M L } a 2 b 2 c 2 M M M CT Restricted E/F Relay L L L TO TRIP CIRCUIT Contents 1 The Need for Protection 2 1.1 Types of Faults............................

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED

More information

NERC Protection Coordination Webinar Series June 23, Phil Tatro

NERC Protection Coordination Webinar Series June 23, Phil Tatro Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection NERC Protection Coordination Webinar Series

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 22 1 Today Homework 5 questions Homework 6 discussion More on

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection System Protection and Control Subcommittee

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

Detecting and Managing Geomagnetically Induced Currents With Relays

Detecting and Managing Geomagnetically Induced Currents With Relays Detecting and Managing Geomagnetically Induced Currents With Relays Copyright SEL 2013 Transformer Relay Connections Voltage Current Control RTDs Transformer Protective Relay Measures differential current

More information

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS CONNECTED TO THE DISTRIBUTION SYSTEM ORANGE AND ROCKLAND

More information

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase

More information

Differential Protection for Microgrids with Embedded Generations

Differential Protection for Microgrids with Embedded Generations Differential Protection for Microgrids with Embedded Generations Paul Moroke Dept. of Electrical Engineering Tshwane University of Technology Pretoria, South Africa paulmoroke@gmail.com Abstract The permeation

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Switch-on-to-Fault Schemes in the Context of Line Relay Loadability

Switch-on-to-Fault Schemes in the Context of Line Relay Loadability Attachment C (Agenda Item 3b) Switch-on-to-Fault Schemes in the Context of Line Relay Loadability North American Electric Reliability Council A Technical Document Prepared by the System Protection and

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan Mark Hackney October 5-8, 2009 Amman, Jordan Energy Control Center Layout 2 Energy Control

More information

Appendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD

Appendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD A. Introduction Appendix C-1 Protection Requirements & Guidelines to Okanogan PUD The protection requirements identified in this document apply to Non-Utility Generating (NUG) facilities, Independent Power

More information

Connection Impact Assessment Application

Connection Impact Assessment Application Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

Southern Company Interconnection Requirements for Inverter-Based Generation

Southern Company Interconnection Requirements for Inverter-Based Generation Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

Loss of Mains Protection

Loss of Mains Protection Loss of Mains Protection Summary All generators that are connected to or are capable of being connected to the Distribution Network are required to implement Loss of Mains protection. This applies to all

More information

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A SHINSUNG Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A Enhanced Self Healing System General SILO is 3 phase, solid insulated load break switch (LBS) and vacuum interruption

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

EH2741 Communication and Control in Electric Power Systems Lecture 2

EH2741 Communication and Control in Electric Power Systems Lecture 2 KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment

More information

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme International Journal of Smart Grid and Clean Energy Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme Thongchart Kerdphol*, Yaser Qudaih, Yasunori Mitani,

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/ ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...

More information

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES U AJMAL, GE Grid Solutions UK Ltd, usman.ajmal@ge.com S SUBRAMANIAN, GE Grid Solutions UK Ltd, sankara.subramanian@ge.com H Ha GE Grid Solutions

More information

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org

More information

System Protection and Control Seminar

System Protection and Control Seminar System Protection and Control Seminar Desirable Protection We want to detect a fault within 100% of the zone of protection. We want to avoid interrupting non-faulted zones of protection. We want to clear

More information

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 PRC-025-1 Generator Relay Loadability A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS Hannu LAAKSONEN ABB Oy Finland hannu.laaksonen@fi.abb.com ABSTRACT Medium-voltage (MV) network short-circuit protection operation time delays have

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Electrical Protection System Design and Operation

Electrical Protection System Design and Operation ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS 1 B. RAMESH, 2 K. P. VITTAL Student Member, IEEE, EEE Department, National Institute of Technology Karnataka,

More information

Protection of Microgrids Using Differential Relays

Protection of Microgrids Using Differential Relays 1 Protection of Microgrids Using Differential Relays Manjula Dewadasa, Member, IEEE, Arindam Ghosh, Fellow, IEEE and Gerard Ledwich, Senior Member, IEEE Abstract A microgrid provides economical and reliable

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

Transmission Interconnection Requirements for Inverter-Based Generation

Transmission Interconnection Requirements for Inverter-Based Generation Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional

More information

Protection of power systems with distributed generation State of the art Martin Geidl

Protection of power systems with distributed generation State of the art Martin Geidl Research Collection Monograph Protection of power systems with distributed generation State of the art Martin Geidl Author(s): Geidl, Martin Publication Date: 2005-07 Permanent Link: https://doi.org/10.3929/ethz-a-005009366

More information

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,

More information

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage POWERENG 2007, April 12-14, 2007, Setúbal, Portugal Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage Amin Helmzadeh, Javad Sadeh and Omid Alizadeh

More information

Smart Grid Where We Are Today?

Smart Grid Where We Are Today? 1 Smart Grid Where We Are Today? Meliha B. Selak, P. Eng. IEEE PES DLP Lecturer melihas@ieee.org 2014 IEEE ISGT Asia, Kuala Lumpur 22 nd May 2014 2 Generation Transmission Distribution Load Power System

More information

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges. APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring

More information

E N G I N E E R I N G M A N U A L

E N G I N E E R I N G M A N U A L 1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

Power Plant and Transmission System Protection Coordination Fundamentals

Power Plant and Transmission System Protection Coordination Fundamentals Power Plant and Transmission System Protection Coordination Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell Agenda 2 Objective Introduction to Protection Generator and

More information

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

Adaptive Relaying of Radial Distribution system with Distributed Generation

Adaptive Relaying of Radial Distribution system with Distributed Generation Adaptive Relaying of Radial Distribution system with Distributed Generation K.Vijetha M,Tech (Power Systems Engineering) National Institute of Technology-Warangal Warangal, INDIA. Email: vijetha258@gmail.com

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS Abdelrahman AKILA Ahmed HELAL Hussien ELDESOUKI SDEDCO Egypt AASTMT Egypt AASTMT Egypt Abdurrahman.akela@gmail.com ahmedanas@aast.edu hdesouki@aast.edu

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Connection Impact Assessment Application Form

Connection Impact Assessment Application Form Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information

More information

Impedance protection on power transformer.

Impedance protection on power transformer. Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application

More information

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter 1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes Transmission Line Protection Topics Primary/backup protection Coordination Communication-based

More information