1 1 Smart Grid Where We Are Today? Meliha B. Selak, P. Eng. IEEE PES DLP Lecturer 2014 IEEE ISGT Asia, Kuala Lumpur 22 nd May 2014
2 2 Generation Transmission Distribution Load
3 Power System Transmission 3
4 Power Transfer P1 Vs Pt Vr 0 P2 L1 For power balance P1+P2=L1+L2 L2 For power flow Pt = P1 L1 = L2 P2 Vs x Vr x Sin(q) XL
5 Transmission Line Model Electrical Behavior of Transmission Line [dv/dx]=[z][i] [di/dx] = jω[c][v] Series impedance matrix [Z] Z Z Z ii ik R( ) j L( ) R c ii j L j L ik ii
6 jb a P r h L i i o ii 2 ln 2 jd c d D L ik ik o ik ' ln 2 j o o P Transmission Line Inductance
7 c R ii f h r d i i D ik ' ik a.c. resistance of conductor i, 2f, angular frequency, frequency in Hz, average height above ground of conductor i, radius of conductor i, direct distance between conductors i and k, distance between conductor i and image Formula Quantities Z Z o o ii ik at complex depth of conductor k, earth resistivity, earth permeability. R c ii j ( a jb ) ( R j ( c jd ) d jc c ii b) R ik ja L ik. R ii jl ii,
8 8 Building Complex Power Systems Power system is very complex and is built to satisfy increasing demand of electrical power supply The trend in electric power production is toward an interconnected network of transmission lines linking generators and load into large integrated system
9 9 Power System Operation Operation of an electrical power systems involves continues electromechanical and electromagnetic distribution of energy. During normal operation the system behavior is presented by voltage and current pasors in frequency domain. During system disturbances the circuit components have higher stress, resulting in excessive currents or voltage variations that cause power system transients.
10 Power System Studies Steady State Study Dynamic State Simulation Transient Simulation
11 11 Simulations Outputs Steady State Short Circuit Fault Level Equipment Selection (isolation level) Reference for Protection Settings Dynamic State Simulation Speed of the fault clearing time Transients Simulation Tripping Priority regarding to: Overvoltage's conditions and Power Quality (harmonics)
12 12 Power System Disturbances and Faults Inadequate supply equipment Result of inadequate planning or unexpected rapid load demand Exceeding supply capability results in load losses Many blackouts caused by operating systems too close to stability limits
13 13 Protection Duties Protection system or relay must detect the fault and signal circuit breaker to isolate the fault reliably and as fast as possible.
14 Relaying Fundamentals 14
15 Example reaches and time coordination 15
16 16 Stepped Distance Note: NOT communications assisted, but good background for other schemes Z2a Z1a Z1b Z2b
17 17 Adding large generating units With adding large generating units of high capacity to the power grid endangers the normal operation of power system and might lead to outages and system collapse. The convention power system protection schemes, designed to detect the fault and signal circuit breaker to isolate the fault reliably and as fast as possible, but cannot prevent from the system collapse.
18 18 Telecommunications infrastructure Nowadays, the modernized networks and telecommunications infrastructure together with Intelligent Electronic Devices (IED), and allow optimizing the existing electrical power system operation.
19 19 Intelligent Electronic Devices (IED) IEDs which are used now widely for Power System Protection allow us an implementation of almost all the functionalities needed to protect and control the power system components more efficiently: Fundamental protections (Over Current, Over Voltage, Over Frequency, Distance, Differential Protections) Breaker Failure protection (BFPN) Autoreclose (AR) Automatic switching of protection settings Overload protection Wide area special protection schemes (SPS) or remedial action scheme (RAS) Synchronized Phasor Measurement
20 20 Wide area special protection schemes Wide area special protection schemes (SPS) or remedial action scheme (RAS) are designed to detect the system conditions that can cause instability overload voltage collapse Prevent propagation of disturbances for severe system emergencies caused by un planned operating conditions Last line of defense to improve system security and prevent disturbance propagation Could help better utilize system margins Stabilize System for Equipment Outages, N 2 or beyond Initiate pre planned separation of the power system Prevent overloading of the lines Arrest voltage decline
21 21 Synchronized Phasor Measurement Two key elements of synchronized phasor measurement are data that are provided how that data are referenced Synchronized phasor measurement system requires a high-precision timing reference (Global Positioning Satellite Clock system) to synchronize all devises across a system-now available from monitors called phasor measurement units (PMUs) Voltage waveforms from remote measurement units are compared on realtime basis. This capability is used to: evaluate system conditions compered them to the system model facilitates analysis in system-wide disturbances system operation control generation dispatch
22 22 Permissive Overreaching Transfer Trip Z2a Z1a Z1b Z2b Sending Permissive Trip = fault is in front of me Received Permissive Trip + local Zone 2 = local trip
23 23 Why communication assisted line protection? Speed, speed, speed Selectivity problem (ie: is the fault between the two ends of the line?) Adding communications allows cooperation between both line terminals, which improves speed by improving selectivity
24 24 Power Distribution System Distribution system is designed to serve radial load. (Power flows from higher voltage levels down to customers)
25 25 Distribution Protection Relay characteristics are plotted on a time current characteristic (TCC) diagram. Non directional protection is needed because of radial system configuration
26 Electrical Power System Today G Generation G Supply Transmission Traditional one-way supply system Bi-directional supply system G Distribution Loads Generation G Generation Transmission Distribution Loads Demand Generation Interconnections
27 27 Concerns related to the distribution system operation and planning With DG increases, Distribution Systems are becoming more like transmission system: double or multiple feed circuits having significant changes in operation will have to accommodate bi directional power flows safety of public and equipment as the network was not designed to accommodate larger numbers of DG protection system becomes more complex due to changes in system behavior and power flow under shortcircuit conditions
28 28 Need for directional protection F1 R1 faster than R2 F2 R2 faster than R1
29 29 Distribution Systems Today Today, the power distribution systems are designed to provide participating customers a new level of choice and control over their energy use through advanced technology, with the goals of empowering customers to: save energy increasing electric service reliability improving response to power outages.
30 30 Distribution Systems Today Advanced communications technologies Smart meters Devices for electrical system automation Energy management tools ALL provide the significant benefits for energy customers. The new global communications platforms support the future innovation: wide and local area networks telecommunications services voice services video conferencing
Power System Protection Where Are We Today?
1 Power System Protection Where Are We Today? Meliha B. Selak Power System Protection & Control IEEE PES Distinguished Lecturer Program Preceding IEEE PES Vice President for Chapters melihas@ieee.org PES
More informationGRID RELIABILITY MONITORING
GRID RELIABILITY MONITORING Using Smart Grids WASS TM - A SynchroPhasor Technology based Real Time Wide Area Situational Awareness Software for Monitoring, Detection and Diagnosis of Power System Issues
More informationSYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011
SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 Baselining using large quantities of historical phasor data to identify and understand patterns in interconnection-wide grid behavior, to
More informationIntroduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow
Module 1 : Fundamentals of Power System Protection Lecture 3 : Protection Paradigms - System Protection Objectives In this lecture we will: Overview dynamics in power systems. Introduce system protection
More informationPower System Stability. Course Notes PART-1
PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationMeasurement tools at heart of Smart Grid need calibration to ensure reliability
Measurement tools at heart of Smart Grid need calibration to ensure reliability Smart grid; PMU calibration position 1 The North American interconnections, or electric transmission grids, operate as a
More informationTHE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES
THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationSystem Protection Schemes in Power Network based on New Principles
System Protection Schemes in Power Network based on New Principles Daniel Karlsson, ABB Automation Products AB S-721 59 Västerås, SWDN daniel.h.karlsson@se.abb.com Abstract This report describes how a
More informationMassive Transient Stability Based Cascading Analysis and On-line Identification of Critical Cascades
1 Massive Transient Stability Based Cascading Analysis and On-line Identification of Critical Cascades Paper Number: 16PESGM2419 Marianna Vaiman, V&R Energy marvaiman@vrenergy.com 2016 IEEE PES General
More informationSequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network
Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria
More informationSHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP
SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,
More informationPhasor Measurements for Blackout Prevention
Phasor Measurements for Blackout Prevention Anjan Bose Washington State University Pullman, WA, USA i-pcgrid 2013 San Francisco, CA March 26-28, 2013 Monitoring the Power Grid (SCADA) Visualization Tables
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationROSE - Real Time Analysis Tool for Enhanced Situational Awareness
ROSE - Real Time Analysis Tool for Enhanced Situational Awareness Marianna Vaiman V&R Energy Copyright 1997-2013 V&R Energy Systems Research, Inc. All rights reserved. WECC JSIS Salt Lake City, UT October
More informationTransmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes
Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes Transmission Line Protection Topics Primary/backup protection Coordination Communication-based
More informationAppendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS
Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements
More informationHydro-Québec s Defense Plan: Present and Future
Hydro-Québec s Defense Plan: Present and Future Annissa Heniche Innocent Kamwa Hydro-Québec IREQ Varennes, Canada Abstract Recent cascading failures in several power systems worldwide have highlighted
More informationEducation & Training
Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through
More informationMicrogrid Protection
Panel: Microgrid Research and Field Testing IEEE PES General Meeting, 4-8 June 7, Tampa, FL Microgrid Protection H. Nikkhajoei, Member, IEEE, R. H. Lasseter, Fellow, Abstract In general, a microgrid can
More informationPerformance of Relaying During Wide-area Stressed Conditions
Performance of Relaying During Wide-area Stressed Conditions IEEE Power Systems Relaying Committee C12 Working Group Report Presented by Pratap Mysore HDR Engineering Inc. July 25, 2012, San Diego, CA
More informationEngineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location
Engineering Thesis The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location By Yushi Jiao Presented to the school of Engineering and
More informationA short introduction to Protection and Automation Philosophy
Training Center A short introduction to Protection and Automation Philosophy Philippe Goossens & Cédric Moors Training Center Contents Definitions and basic concepts Differential and distance protection
More informationA New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated
More informationStudy and Simulation of Phasor Measurement Unit for Wide Area Measurement System
Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System Ms.Darsana M. Nair Mr. Rishi Menon Mr. Aby Joseph PG Scholar Assistant Professor Principal Engineer Dept. of EEE Dept. of
More informationCombination of Adaptive and Intelligent Load Shedding Techniques for Distribution Network
Combination of Adaptive and Intelligent Load Shedding Techniques for Distribution Network M. Karimi, Student Member, IEEE, H. Mokhlis, Member, IEEE, A. H. A. Bakar, Member, IEEE, J. A. Laghari, A. Shahriari,
More informationTransmission Protection Overview
Transmission Protection Overview 2017 Hands-On Relay School Daniel Henriod Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with
More informationVOLTAGE CONTROL IN MEDIUM VOLTAGE LINES WITH HIGH PENETRATION OF DISTRIBUTED GENERATION
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http: //www.cigre.org 2013 Grid of the Future Symposium VOLTAGE CONTROL IN MEDIUM VOLTAGE LINES WITH HIGH PENETRATION OF DISTRIBUTED GENERATION
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationReal-time Monitoring of Power Oscillations and Modal Damping in the European ENTSO-E System
Mats Larsson, ABB CRC Switzerland; Luis-Fabiano Santos, ABB SAS Switzerland; Galina Antonova, AB B SA Canada, Reynaldo Nuqui, ABB CRC USA NASPI meeting, February 20, 2013 Real-time Monitoring of Power
More informationAnti-IslandingStrategyforaPVPowerPlant
Global Journal of Researches in Engineering: F Electrical and Electronics Engineering Volume 15 Issue 7 Version 1.0 Type: Double Blind Peer Reviewed International Research Journal Publisher: Global Journals
More informationPSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)
1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationModeling insulation in high-voltage substations
38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other
More informationControlled Islanding Followed by Load Shedding Based on Rate of Frequency Decline
Controlled Islanding Followed by Load Shedding Based on Rate of Frequency Decline Internet Seminar October 1, 2002 Vijay Vittal Students: Haibo You, Zhong Yang 2002 Iowa State University EPRI/DoD Initiative
More informationElectrical Protection System Design and Operation
ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection
More informationHVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN
HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN Summary Capacitor Commutated Converters (CCC) were introduced to the HVDC market
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationVisualization and Animation of Protective Relay Operation
Visualization and Animation of Protective Relay Operation A. P. Sakis Meliopoulos School of Electrical and Computer Engineering Georgia Institute of Technology Atlanta, Georgia 30332 George J. Cokkinides
More informationPhase Angle Monitoring:
Phase Angle Monitoring: Industry Experience Following the 2011 Pacific Southwest Outage Recommendation 27 Ryan D. Quint, PhD, PE NERC SMS Coordinator NASPI Work Group Meeting October 2016 Background Purpose:
More informationA New Approach Applied to Adaptive Centralized Load Shedding Scheme
A New Approach Applied to Adaptive Centralized Load Shedding Scheme HAMID BENTARZI*, ABDERRAHMANE OUADI*, NADIR GHOUT*, FARID MAAMRI* and NIKOS E.MASTORAKIS** *Signals and Systems Laboratory (SiSyLAB)
More informationGeneration Interconnection Requirements at Voltages 34.5 kv and Below
Generation Interconnection Requirements at Voltages 34.5 kv and Below 2005 March GENERATION INTERCONNECTION REQUIREMENTS AT 34.5 KV AND BELOW PAGE 1 OF 36 TABLE OF CONTENTS 1. INTRODUCTION 5 1.1. Intent
More informationECE 692 Advanced Topics on Power System Stability 5 - Voltage Stability
ECE 692 Advanced Topics on Power System Stability 5 - Voltage Stability Spring 2016 Instructor: Kai Sun 1 Content Basic concepts Voltage collapse and Saddle-node bifurcation P-V curve and V-Q curve Causes
More informationApplication for A Sub-harmonic Protection Relay. ERLPhase Power Technologies
Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic
More informationBED INTERCONNECTION TECHNICAL REQUIREMENTS
BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2
More informationHybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation
Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603
More informationLoss of Mains Protection
Loss of Mains Protection Summary All generators that are connected to or are capable of being connected to the Distribution Network are required to implement Loss of Mains protection. This applies to all
More informationUse of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation
More informationThe Effect of Various Types of DG Interconnection Transformer on Ferroresonance
The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:
More informationIn addition to wide-area monitoring systems, synchrophasors offer an impressive range of system benefits, including:
Synchrophasors Before synchrophasor technology and its contributions towards transmission resiliency are discussed, it is important to first understand the concept of phasors. A phasor is a complex number
More informationNERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series
More informationA REVIEW OF SELF HEALING SMART GRIDS USING THE MULTIAGENT SYSTEM
A REVIEW OF SELF HEALING SMART GRIDS USING THE MULTIAGENT SYSTEM Mr.Mohit Haridas Tapase Student, Department of Electronics and Telecommunication, D.Y.Patil College of Engineering, Shivaji University,
More informationTable of Contents. Introduction... 1
Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...
More informationHarmonic Analysis of a High Speed Automatic Reclosing on a 400 kv Overhead Transmission Line
Harmonic Analysis of a High Speed Automatic Reclosing on a 400 kv Overhead Transmission Line ANGELA IAGAR, SORIN IOAN DEACONU, CORINA DANIELA CUNTAN, IOAN BACIU Department of Electrotechnical Engineering
More informationENHANCEMENT OF POWER FLOW USING SSSC CONTROLLER
ENHANCEMENT OF POWER FLOW USING SSSC CONTROLLER 1 PRATIK RAO, 2 OMKAR PAWAR, 3 C. L. BHATTAR, 4 RUSHIKESH KHAMBE, 5 PRITHVIRAJ PATIL, 6 KEDAR KULKARNI 1,2,4,5,6 B. Tech Electrical, 3 M. Tech Electrical
More informationSouthern Company Interconnection Requirements for Inverter-Based Generation
Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection
More informationUProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy
UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected
More informationResearch on State Estimation and Information Processing Method for Intelligent Substation
, pp.89-93 http://dx.doi.org/10.14257/astl.2015.83.17 Research on State Estimation and Information Processing Method for Intelligent Substation Tongwei Yu 1, Xingchao Yang 2 1 Electric Power Research Institute,
More informationRAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements
RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying
More informationModule 9. Fault Type Form 4.X RELIABILITY ACCOUNTABILITY
Module 9 Fault Type Form 4.X 1 M9 Fault Type The descriptor of the fault, if any, associated with each Automatic Outage of an Element. 1. No fault 2. Phase-to-phase fault (P-P) 3. Single phase-to-ground
More informationEnhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)
Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute
More informationPROTECTION SIGNALLING
PROTECTION SIGNALLING 1 Directional Comparison Distance Protection Schemes The importance of transmission system integrity necessitates high-speed fault clearing times and highspeed auto reclosing to avoid
More informationPQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.
General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand
More informationSynchronous Measurement, Control, & Protection of Electric Power Systems. Dr. Edmund O. Schweitzer, III February 29, 2012
Synchronous Measurement, Control, & Protection of Electric Power Systems Dr. Edmund O. Schweitzer, III February 29, 2012 Copyright SEL 2011 The Future of Power Systems No Blackouts New Sources Better Control
More informationISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS
ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS INDO-US Workshop October 2009, I.I.T. Kanpur INTRODUCTION Electric Power Systems are very large, spread over a wide geographical area
More informationA Review of Adaptive Under Frequency Load Shedding Scheme on Islanded Distribution System Using MATLAB/SIMULINK
A Review of Adaptive Under Frequency Load Shedding Scheme on Islanded Distribution System Using MATLAB/SIMULINK Dhananjay 1, Vijay Garg 2 1 M.Tech Scholar, Electrical Engineering, U.I.E.T, Kurukshetra,
More informationENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES
ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES N. Perera 1, A. Dasgupta 2, K. Narendra 1, K. Ponram 3, R. Midence 1, A. Oliveira 1 ERLPhase Power Technologies Ltd. 1 74 Scurfield
More informationENOSERV 2014 Relay & Protection Training Conference Course Descriptions
ENOSERV 2014 Relay & Protection Training Conference Course Descriptions Day 1 Generation Protection/Motor Bus Transfer Generator Protection: 4 hours This session highlights MV generator protection and
More informationTesting and Validation of Synchrophasor Devices and Applications
Testing and Validation of Synchrophasor Devices and Applications Anurag K Srivastava The School of Electrical Engineering and Computer Science Smart Grid Demonstration and Research Investigation Lab Washington
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationHarmonic Distortion Levels Measured at The Enmax Substations
Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned
More informationExperiences of Using Synchrophasors at Duke Energy
1 Experiences of Using Synchrophasors at Duke Energy Tim Bradberry, Megan Vutsinas, Kat Sico Duke Energy IEEE PES Tutorial July 19 th, 2016 Duke Energy s Phasor Plans Carolinas West Currently have 125
More informationState Estimation Advancements Enabled by Synchrophasor Technology
State Estimation Advancements Enabled by Synchrophasor Technology Contents Executive Summary... 2 State Estimation... 2 Legacy State Estimation Biases... 3 Synchrophasor Technology Enabling Enhanced State
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationA Transfer Trip Scheme to Supervise Zone 3 Operation
IAEL (26) :9 3 DOI.7/s443-6-2-8 ORIGIAL ARTICLE A Transfer Trip Scheme to Supervise Operation J. Ganeswara Rao Ashok Kumar radhan Received: 25 April 26 / Accepted: 6 ay 26 / ublished online: 9 ay 26 Indian
More informationNOWADAYS, there is much interest in connecting various
IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013 419 Modified Dynamic Phasor Estimation Algorithm for the Transient Signals of Distributed Generators Dong-Gyu Lee, Sang-Hee Kang, and Soon-Ryul
More informationUltra-High-Speed Relaying for Transmission Lines
Ultra-High-Speed Relaying for Transmission Lines Copyright SEL 2015 Focus for Today Benefits of faster line protection Limitations of present-day phasor-based protection Principles of time-domain protection
More informationProtection of Microgrids Using Differential Relays
1 Protection of Microgrids Using Differential Relays Manjula Dewadasa, Member, IEEE, Arindam Ghosh, Fellow, IEEE and Gerard Ledwich, Senior Member, IEEE Abstract A microgrid provides economical and reliable
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationTransmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection
Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed
More informationTask Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team Matthew Rhodes 3/22/16
NASPI White Paper: Integrating Synchrophasor Technology into Power System Protection Applications Update Report Task Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team
More informationCapstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:
Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation
More informationNERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1
NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationDifferential Protection Optimal differential protection for phase shifter transformers and special transformers
Differential Protection Optimal differential protection for phase shifter transformers and special transformers Due to the energy transition, a demand for renewable energy sources integration into power
More informationSummary of the Impacts of Grounding on System Protection
Summary of the Impacts of Grounding on System Protection Grounding System grounding big impact on ability to detect ground faults Common ground options:» Isolated ground (ungrounded)» High impedance ground»
More informationAdvantages and Disadvantages of EHV Automatic Reclosing
Technical Reference Document Advantages and Disadvantages of EHV Automatic Reclosing NERC System Protection and Control Subcommittee December 2009 Table of Contents 1. Introduction...1 2. Significant Autoreclosing
More informationDigital Fault Recorder Deployment at HVDC Converter Stations
Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic
More informationThe Coupling of Voltage and Frequecncy Response in Splitting Island and Its Effects on Load-shedding Relays *
Energy and Power Engineering, 2013, 5, 661-666 doi:10.4236/epe.2013.54b128 Published Online July 2013 (http://www.scirp.org/journal/epe) The Coupling of Voltage and Frequecncy Response in Splitting Island
More informationANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES
ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES Authors: Joe Perez, P.E.: SynchroGrid, College Station, Texas Hung Ming Chou, SynchroGrid, College Station, Texas Mike McMillan, Bryan
More informationFault Localization using Wavelet Transforms in 132kV Transmission Lines
ENGINEER - Vo). XXXXII, No. 04, pp. [95-104], 2009 The Institution of Engineers, Sri Lanka Fault Localization using Wavelet Transforms in 132kV Transmission Lines J.V.U.P. Jayatunga, P.S.N. De Silva and
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationUse of Synchrophasors to Detect Control System and Circuit Breaker Reclosing Issues
Use of Synchrophasors to Detect Control System and Circuit Breaker Reclosing Issues Pramila Nirbhavane Senior Grid Operations Engineer September 26, 2017 Outline PMUs Locations in NYISO PMU Applications
More informationWebinar: An Effective Arc Flash Safety Program
Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of
More informationPublished in A R DIGITECH
PHASOR MEASUREMENT UNIT : An Overview Vishal Wadkar, Pavan Salunkhe, Ganesh Bhondave *1(PG Student of Electrical Department, R.H.Sapat COE College, Nashik, India) *2(PG Student of Electrical Department,
More informationITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/
ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...
More informationInternational Journal of Advance Engineering and Research Development
Scientific Journal of Impact Factor (SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 12,December -2015 E-ISSN (O): 2348-4470 P-ISSN (P): 2348-6406 Detection
More information