Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System
|
|
- Jason Lawson
- 6 years ago
- Views:
Transcription
1 Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System Ms.Darsana M. Nair Mr. Rishi Menon Mr. Aby Joseph PG Scholar Assistant Professor Principal Engineer Dept. of EEE Dept. of EEE Power Electronics Group Saintgits College Of Engineering Saintgits College of Engineering C-DAC Kottayam, Kerala Kottayam, Kerala Trivandrum, Kerala Abstract Power system is now operating in a more complicated situation and is facing more challenges than ever before. Synchronized phasor measurements have become a prominent technology for real time monitoring of power system. At present PMU is the most sophisticated timesynchronized tool available to power engineers and system operators for wide area applications. It will improve visibility and provide real time monitoring, protection, and control of the system. This tool has been made possible by advancements in computer technology, and availability of GPS signals. This paper describes the modeling and testing of PMU in MATLAB/Simulink. Keywords: - Global positioning systems (GPS), Phasor measurement units (PMU), Wide Area Monitoring Systems (WAMS), Coordinated Universal Time (UTC). 1. INTRODUCTION The power system networks are recently being equipped with the synchrophasor based Wide Area Monitoring System (WAMS). The conventional Remote Terminal Units (RTUs), forming part of the Supervisory Control And Data Acquisition (SCADA) system, provide only unsynchronized root mean square values of the currents and the voltages. A synchrophasor based WAMS, consists of geographically placed Phasor Measurement Units (PMUs), which provide the measurements of both the magnitude and the phase angles of the voltage and the current signals. These measurements are time-synchronized using Global Positioning System (GPS) with an accuracy of 1 ms [5]. The major applications of the phasor measurements include real-time power system monitoring, protection and control. The phasors, measured at the same time instant, provide a snapshot of the power system network and by comparing the snapshots of the consecutive time instants, not only the steady state but also the dynamic states of the critical nodes in the network can be tracked. The Wide Area Monitoring System (WAMS) is primarily used for managing the grid reliability by continuously monitoring the status of the grid through PMU deployed at specific location in the transmission network. The goal of wide area monitoring systems is to make the power system less immune to catastrophic failures and to reduce the severity of such failures when they do occur. PMUs are the main building blocks in the synchrophasor based WAMS. They provide phasor data with faster refreshment rate. The information provided by them, i.e., the voltage and the current phasors, are processed at the Phasor Data Concentrators (PDCs) to extract the relevant information about the system operating condition. PMUs are devices able to sample high speed, timestamped snapshots of voltage and current in phasor format, frequency and rate of change of frequency. Being synchronized to Coordinated Universal Time (UTC) through Global Positioning System (GPS) signal, these devices are able to provide real time measurements recorded from different parts of the power system, giving this way the potential to timealign these measurements and have a precise and representative view of the power system. Phasor Data Concentrators (PDCs) are devices able to concentrate measurements from different PMUs, time-align them and communicate them as a single stream to other PDCs or to monitoring and control devices. In this paper following sections were presented. Section II describes Phasor and PMU functions. Section III focuses the simulation of PMU to perform WAM functions. WAM functions include voltage monitoring, Phase angle monitoring, Frequency monitoring, Rate of Change of Frequency monitoring etc. 1
2 II. PHASOR AND PMU FUNCTIONS A phasor is a vectorial representation of an ac signal with sinusoidal waveform. It is well known that a sinusoid can be written using the equation: X (t) = Xm cos (ωt + Φ) (1) And is commonly represented as the phasor as shown in Equation (2): X = (Xm/ 2) e jφ (2) = (Xm / 2) (cos Φ + j sin Φ) = X r + j X i In the above equation, ω is the angular velocity θ is the initial angle between a reference point and the positive peak. X m is the peak amplitude of the waveform. The magnitude of phasor equals to the root mean square (RMS) value of the waveform which is (X m / 2). The subscripts r and i signify real and imaginary parts of a complex value in rectangular components. The value of Φ depends on the time scale, particularly where t = 0. It is important to note this phasor is defined for the angular frequency ω; evaluation with other phasors must be done with the same time scale and frequency. A phasor representation corresponds to a pure sinusoid. However, in real world situations, ac signals are typically distorted by the presence of harmonics. As the analysis of a signal is always focused on specific frequency components, the extraction of the component of interest is important. In a digital measurement system, this is usually realized by the Discrete Fourier Transform (DFT) or the Fast Fourier Transform (FFT). A time span for the measurement is selected, which is known as the time window. PMUs continuously sample the waveform using a moving time windows and update the value of the phasor that is output on a continuous basis. A phasor is a complex number that represents both the magnitude and phase angle of the sine waves found in electricity. Phasor measurements that occur at the same time are called synchrophasors, as are the PMU devices that allow their measurement. In typical applications phasor measurement units are sampled from widely dispersed locations in the power system network and synchronized from the common time source of a global positioning system (GPS) radio clock. Synchrophasor technology provides a tool for system operators and planners to measure the state of the electrical system and manage power quality. Under this definition, Φ is the offset from a cosine function at the nominal system frequency synchronized to UTC. A cosine has a maximum at t = 0, so the synchrophasor angle is 0 degrees when the maximum of x(t) occurs at the UTC second rollover (1 PPS time signal), and 90 degrees when Fig. 1.Convention for synchrophasor representation 2 the positive zero crossing occurs at the UTC second rollover (sin waveform)[2]. Figure 1 illustrates the phase angle/utc time relationship. Phasor Measurement Unit There is no uniform structure adopted for commercially available PMUs as several companies provide such offerings. However, the functional blocks of a typical PMU are generic, and the common components are shown in figure 2. As shown in Figure.2, analogue input signals, which are derived from a scaled signal from voltage and current transformers are initially passed through anti-aliasing filters. A PMU may collect data from different locations in the system on a simultaneous basis and normally requires data from all three phases to extract the positive sequence component,
3 which is what is normally of interest and contains information that can be used to assess the state of the power system. PMUs are synchronized by satellites through a GPS receiver. The time accuracy of such system is typically in the order of a few hundred nanoseconds. Time stamps are created by the GPS receiver as a label of measurement and for future comparison of measurements. The other important function of the GPS receiver is that it can generate a one pulse-per-second signal to a phase-locked oscillator to synchronise and lock the phase of the sampling clock. Synchrophasors measure voltages and currents at principle intersecting locations (critical substations) on a power grid and can output accurately time-stamped voltage and current phasors. Because these phasors are truly synchronized, synchronized comparison of two quantities is possible, in real time. These comparisons can be used to assess system conditions-such as; frequency Fig 2.Functional block diagram of PMU. III. SIMULATION OF PMU. platform. The system was modeled in LABVIEW For the study of functionality of PMU, its [3][4].MATLAB/ Simulink model of PMU is model is simulated in MATLAB/ Simulink developed as shown in figure 3. Fig. 3. MATLAB/ Simulink Model for WAMS. 3
4 SYSTEM DESCRIPTION Here a three phase source (415V, 50 Hz) is connected to a three phase load. PMU model is placed between the source and load. It measures the voltage phasor, current phasor, frequency and rate of change of frequency. 1. Voltage Phasor Measurement Block: This subsystem receives the three phase voltage signal and extracts each phase voltages V a, V b and V c. Then it converts this voltage signal to its phasor representation, i.e., in magnitude and phase angle form. This is shown in figure Current Phasor Measurement Block: This subsystem receives the three phase current signal and extracts each phase current I a, I b and I c. Then it converts this current signal to its phasor representation, i.e., in magnitude and phase angle form. This is also shown in figure Frequency Measurement Block: This subsystem basically contains a phase locked loop which can be used to synchronize on a set of variable frequency, three-phase sinusoidal signals. It outputs the measured frequency in Hz (ω /2pi) and ramp ω.t varying between 0 and 2*pi, synchronized on zero crossings of the fundamental (positive-sequence) of phase A. This signal is the given to ROCOF block. 4. Rate of Change of Frequency Measurement Block: The output signal from the frequency measurement block is differentiated to obtain the rate of change of frequency (ROCOF). Figure 4a and b shows the subsystem for magnitude and phase angle measurement. Fig.4a. Subsystem for magnitude measurement We can measure frequency and rate of change of frequency through PMU. Change in frequency can shows the change in impedance of power system components. We are able to observe stability of system through rate of change of frequency monitoring. Fig.4b. Subsystem for phase angle measurement According to the convention for phasor representation phase angle φ is the offset from a cosine function at the nominal system frequency synchronized to UTC [2]. Thus a three phase balanced sinusoidal voltage waveform represented as: V a = V m sin ωt V b = V m sin (ωt-120 ) (3) V c = V m sin (ωt+120 ) Can be represented as phasor form (according to IEEE synchrophasor convention) as below. V a = V m / < -90 V b = V m / < 150 (4) V c = V m / < 30 4
5 Fig. 5. Amplitude variation with change in frequency from 50 Hz to Hz Effect of change in frequency Here the nominal frequency of the source is 50 Hz. If there is any change in the frequency from its nominal value there will be a corresponding change in magnitude and phase angle of voltage. For verifying the effect of change in frequency, the frequency of input wave is changed to Hz. The variation in magnitude is shown in figure 5. PMUs create a picture showing the stability status of the nodes in the monitored area. PMUs take this picture at the same reference time. Using real-time information from PMUs and automated controls to predict, identify, and respond to system problems; a smart grid can automatically avoid or diminish power outages, power quality problems and supply disruptions. The relevance of phase angle monitoring comes into picture only when we are able to compare the phase angles of two different nodes in a network. For this we have to place two PMUs at two critical points in a power system network. Then the difference in phase angles obtained from these two points will give a clear idea about the stability of the monitored area. By continuously monitoring, phase angle monitoring enables access in real time to the accurate phase angle difference between any pair of buses. With this we can monitor angle separation or rate-of change of angle separation between two buses or two parts of a grid to determine stress on the system. Another important application of phase angle monitoring is during restoration. The phase angle value of an opened tie line or an opened circuit breaker would help an operator in circuit breaker closing. Closing would take place only if the phase angle was below a preset threshold. For the study of this, a two bus system is modeled in MATLAB/Simulink. Figure 5 shows the model of such a system. Here PMUs are placed at bus 1 and 2 to measure the voltage phasors at nodes 1 and 2 respectively. V a1, V b1, V c1 and V a2,v b2,v c2 are the three phase voltages at bus 1 and 2 respectively. Under normal conditions the phase angles of two buses are as we obtained in the simulation study. If there is any abnormality in any of the buses, there will be a corresponding change in the phase angles of the affected bus. 5
6 Fig. 6. Simulink Model of Two bus system with PMUs placed at each bus IV.CONCLUSION Performance of PMU is simulated and verified in MATLAB/Simulink. The model developed gives phasor information i.e., information about both magnitude and phase angle of the input waveform. The time stamped information obtained from the PMU can be integrated with the conventional SCADA system to make the operation of the grid smarter and efficient. Also this information can be used for the proper selection and coordination of relays to make WAM protection and Control. REFERENCES [1] Ranjana Sodhi, S.C.Srivastava, A simple scheme for wide area detection of impending voltage instability, IEEE Transactions on Smart Grid, Vol. 3, No. 2, June [2] IEEE Standards for Synchrophasors for Power Systems, IEEE Power & Energy Society, Sponsored by the Power System Relaying Committee, IEEE Std C [3] Vipin Krishna R, S. Ashok, Megha G Krishnan, Synchronized Phasor Measurement Unit, International Conference on Power, Signals, Controls and Computation (EPSCICON), 8 10 January [4] S. Mondal, Ch. Murty D. S. Roy, D. K. Mohanta, Simulation of Phasor Measurement Unit (PMU) Using Labview. 14th International Conference on Environment and Electrical Engineering (EEEIC- 2014), Krakow pp , May [5] A.G. Phadke and J.S.Throp, Synchronized Phasor Measurements and their applications, Springer,
Engineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location
Engineering Thesis The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location By Yushi Jiao Presented to the school of Engineering and
More informationTHE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES
THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors
More informationModelling of Phasor Measurement Unit and Phasor Data Realisation with 2 Bus System
Intl J Engg Sci Adv Research 05 Sep;(3):79-83 ling of Phasor Measurement Unit and Phasor Data Realisation with Bus System Chakrapani Mishra Department of Electrical Engineering FET, Rama University, Kanpur,
More informationSYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES. A.G. Phadke
SYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES A.G. Phadke Lecture outline: Evolution of PMUs Standards Development of Phasor Measurement Units Phasor Estimation Off-nominal frequency phasors Comtrade Synchrophasor
More informationEvaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit
Electrical Power and Energy Conference 2012 Resilient Green Energy Systems for a Sustainable Society Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit Dinesh
More informationDevelopment of DFT Based MATLAB and LABVIEW Models for Phasor Measurements
Development of DFT Based MATLAB and LABVIEW Models for Phasor Measurements Alok Jain and M. K. Verma Abstract With the advent of Phasor Measurement Units (PMUs), it has become quite possible to monitor
More informationCoordination of Wind and Hydro Power Plant by Using Optimization Technique
Coordination of Wind and Hydro Power Plant by Using Optimization Technique P.Ranjithkumar 1, Saravana Prabaakar 1, M.Suganya 2, iranjana B 2 UG Scholar, Department of EEE, SKCET, Coimbatore-641008, Tamil
More informationImplementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator
Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator Dinesh Rangana Gurusinghe, Dean Ouellette, and Athula D. Rajapakse Abstract-- Many commercial phasor measurement units (PMUs
More informationBest Assignment of PMU for Power System Observability Y.Moses kagan, O.I. Sharip Dept. of Mechanical Engineering, Osmania University, India
Best Assignment of PMU for Power System Observability Y.Moses kagan, O.I. Sharip Dept. of Mechanical Engineering, Osmania University, India Abstract: Phasor Measurement Unit (PMU) is a comparatively new
More informationIn addition to wide-area monitoring systems, synchrophasors offer an impressive range of system benefits, including:
Synchrophasors Before synchrophasor technology and its contributions towards transmission resiliency are discussed, it is important to first understand the concept of phasors. A phasor is a complex number
More informationSYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011
SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 Baselining using large quantities of historical phasor data to identify and understand patterns in interconnection-wide grid behavior, to
More informationSynchrophasors: Definition, Measurement, and Application
1. Abstract Synchrophasors: Definition, Measurement, and Application Mark Adamiak GE Multilin King of Prussia, PA William Premerlani GE Global Research Niskayuna, NY Dr. Bogdan Kasztenny GE Multilin Markham,
More informationAlgorithms to Improve Performance of Wide Area Measurement Systems of Electric Power Systems
Western University Scholarship@Western Electronic Thesis and Dissertation Repository February 2014 Algorithms to Improve Performance of Wide Area Measurement Systems of Electric Power Systems Sarasij Das
More informationMeasurement tools at heart of Smart Grid need calibration to ensure reliability
Measurement tools at heart of Smart Grid need calibration to ensure reliability Smart grid; PMU calibration position 1 The North American interconnections, or electric transmission grids, operate as a
More informationEnhanced DFT Algorithm for Estimation of Phasor by PMU under Power Quality Events
Volume 114 No. 12 2017, 515-523 ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Enhanced DFT Algorithm for Estimation of Phasor by PMU under Power
More informationPHASOR MEASUREMENT UNIT: - A Revolution in Power System
PHASOR MEASUREMENT UNIT: - A Revolution in Power System Sonal Kumar Singh Electrical engineering, JECRC University, Jaipur -------------------------------------------------------------------------***------------------------------------------------------------------------
More informationFlorida State University Libraries
Florida State University Libraries Electronic Theses, Treatises and Dissertations The Graduate School 2015 Development of Real-Time Voltage Stability Monitoring Tool for Power System Transmission Network
More informationFREQUENCY TRACKED PHASOR ESTIMATION ALGORITHM FOR PMU DURING OFF-NOMINAL FREQUENCY VARIATIONS
TJPRC: International Journal of Power Systems & Microelectronics (TJPRC: IJPSM) Vol. 1, Issue 1, Dec 2016, 51-58 TJPRC Pvt. Ltd. FREQUENCY TRACKED PHASOR ESTIMATION ALGORITHM FOR PMU DURING OFF-NOMINAL
More informationPHASOR TECHNOLOGY AND REAL-TIME DYNAMICS MONITORING SYSTEM (RTDMS) FREQUENTLY ASKED QUESTIONS (FAQS)
PHASOR TECHNOLOGY AND REAL-TIME DYNAMICS MONITORING SYSTEM (RTDMS) FREQUENTLY ASKED QUESTIONS (FAQS) Phasor Technology Overview 1. What is a Phasor? Phasor is a quantity with magnitude and phase (with
More informationPhasor Measurement Unit and Phasor Data Concentrator test with Real Time Digital Simulator
Downloaded from orbit.dtu.dk on: Apr 26, 2018 Phasor Measurement Unit and Phasor Data Concentrator test with Real Time Digital Simulator Diakos, Konstantinos; Wu, Qiuwei; Nielsen, Arne Hejde Published
More informationIJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):
IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online): 2321-0613 Measurement of Power System Oscillation with the use of Synchro Phasor Technology and
More informationSub/super-synchronous harmonics measurement method based on PMUs
The 6th International Conference on Renewable Power Generation (RPG) 19 20 October 2017 Sub/super-synchronous harmonics measurement method based on PMUs Hao Liu, Sudi Xu, Tianshu Bi, Chuang Cao State Key
More informationPOWER SYSTEM BACKUP PROTECTION USING SYNCHRONIZED PMU
POWER SYSTEM BACKUP PROTECTION USING SYNCHRONIZED PMU LAVUDYA JAYASREE 1 and GAIRABOINA NAGARAJU 2 1,2 Dept. of Electrical And Electronics, Engineering, Christu Jyothi Institute of Technology And Science,Yeshwanthapur,
More informationPRECISE SYNCHRONIZATION OF PHASOR MEASUREMENTS IN ELECTRIC POWER SYSTEMS
PRECSE SYNCHRONZATON OF PHASOR MEASUREMENTS N ELECTRC POWER SYSTEMS Dr. A.G. Phadke Virginia Polytechnic nstitute and State University Blacksburg, Virginia 240614111. U.S.A. Abstract Phasors representing
More informationComparative Testing of Synchronized Phasor Measurement Units
Comparative Testing of Synchronized Phasor Measurement Units Juancarlo Depablos Student Member, IEEE Virginia Tech Virgilio Centeno Member, IEEE Virginia Tech Arun G. Phadke Life Fellow, IEEE Virginia
More informationMicrogrid Islanding with a Battery Energy Storage System (BESS) Gabriel Haines
Microgrid Islanding with a Battery Energy Storage System (BESS) Gabriel Haines 27/03/2018 1 INTRODUCTION A microgrid is a small group of generation sources and loads that operate together as one system.
More informationSynchrophasors and the Smarter Grid
Synchrophasors and the Smarter Grid Synchrophasor A synchrophasor is a phasor measurement with respect to an absolute time reference. With this measurement we can determine the absolute phase relationship
More informationState Estimation Advancements Enabled by Synchrophasor Technology
State Estimation Advancements Enabled by Synchrophasor Technology Contents Executive Summary... 2 State Estimation... 2 Legacy State Estimation Biases... 3 Synchrophasor Technology Enabling Enhanced State
More informationPublished in A R DIGITECH
PHASOR MEASUREMENT UNIT : An Overview Vishal Wadkar, Pavan Salunkhe, Ganesh Bhondave *1(PG Student of Electrical Department, R.H.Sapat COE College, Nashik, India) *2(PG Student of Electrical Department,
More informationINSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE
INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of
More informationComparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying
Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying V.S.Kale S.R.Bhide P.P.Bedekar Department of Electrical Engineering, VNIT Nagpur, India Abstract
More informationPhasor Measurement Unit Testing
Delft University of Technology Faculty of Electrical Engineering, Mathematics and Computer Science Master of Science Thesis Phasor Measurement Unit Testing by Nhi Nguyen Delft, The Netherlands August 212
More informationPMU Implementation Issues
1 PMU Implementation Issues Experiences in Incorporating PMUs in Power System State Estimation July 29, 2015 Denver, CO Historical Overview of PMU Implementation 1988 First Academic PMU installed at substation
More informationMarch 27, Power Systems. Jaime De La Ree ECE Department
March 27, 2015 Power Systems Jaime De La Ree ECE Department Early History The first generator was developed by Michael Faraday in 1831 John Woolrich patents magneto-electric generator in 1842 (for electrotyping)
More informationLine outage detection using phasor angle measurement ENG470 Engineering Honours Thesis
Line outage detection using phasor angle measurement ENG470 Engineering Honours Thesis Abdullah Aljeri 16/10/2015 Abstract A continuous power supply is a pre-requisite to maintenance of successful economic
More informationAn Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation
Indonesian Journal of Electrical Engineering and Computer Science Vol., No., April 6, pp. 3 ~ 3 DOI:.59/ijeecs.v.i.pp3-3 3 An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability
More informationJean-Pierre Braun obtained the B.E. degree from the Ecole d'ingénieurs de Genève, Switzerland, in 1980; the M.E.M. degree from the University of
Jean-Pierre Braun obtained the B.E. degree from the Ecole d'ingénieurs de Genève, Switzerland, in 1980; the M.E.M. degree from the University of Technology Sydney, Australia, in 1993; and the M.Eng.Sc.
More informationSYNCHRONIZED PHASOR MEASUREMENTS ~ Measurement techniques, Applications, and Standards. A.G. Phadke Virginia Tech, Blacksburg, Virginia USA
SYNCHRONIZED PHASOR MEASUREMENTS ~ Measurement techniques, Applications, and Standards A.G. Phadke Virginia Tech, Blacksburg, Virginia USA SUMMARY Synchronized phasor measurements have been a revolutionary
More informationImproving Monitoring, Control and Protection of Power Grid Using Wide Area Synchro-Phasor Measurements
Improving Monitoring, Control and Protection of Power Grid Using Wide Area Synchro-Phasor Measurements HAMID BENTARZI Signals and Systems Laboratory (SiSyLAB) DGEE, FSI, Boumerdes University e-mail: sisylab@yahoo.com
More informationAlgorithms for the synchrophasor measurement in steady-state and dynamic conditions
Ph.D. in Electronic and Computer Engineering Dept. of Electrical and Electronic Engineering University of Cagliari Algorithms for the synchrophasor measurement in steady-state and dynamic conditions Paolo
More informationNew Standards for Test and Calibration of Phasor Measurement Units
New Standards for Test and Calibration of Phasor Measurement Units Jack Somppi Fluke Calibration NCSLI Conference Sacramento, CA August 2, 2012 2012 Fluke Corporation NCSLI PMU 20120802 1 Stability of
More informationHysteresis Controller and Delta Modulator- Two Viable Schemes for Current Controlled Voltage Source Inverter
Hysteresis Controller and Delta Modulator- Two Viable Schemes for Current Controlled Voltage Source Inverter B.Vasantha Reddy, B.Chitti Babu, Member IEEE Department of Electrical Engineering, National
More informationEstimation of the Short Circuit Ratio and the Optimal Controller Gains Selection of a VSC System
Estimation of the Short Circuit Ratio and the Optimal Controller Gains Selection of a VSC System J Z Zhou, A M Gole Abstract-- The optimal control gains of the VSC HVDC converter are very dependent on
More informationUNIT II: WIDE AREA MONITORING SYSTEM
UNIT II: WIDE AREA MONITORING SYSTEM Fundamentals of Synchro phasor Technology - concept and benefits of wide area monitoring system-structure and functions of Phasor Measuring Unit (PMU) and Phasor Data
More informationWide Area Monitoring with Phasor Measurement Data
Wide Area Monitoring with Phasor Measurement Data Dr. Markus Wache Siemens E D EA, Nuremberg, Germany Content Content Basics of Phasor Measurement Realization of PMUs Power System Stability Standard IEEE
More informationCHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE
98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems
More informationPERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER
International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN 2250-155X Vol. 3, Issue 2, Jun 2013, 309-318 TJPRC Pvt. Ltd. PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationMONITORING AND DETECTION OF FAULT USING PHASOR MEASUREMENT UNITS
MONITORING AND DETECTION OF FAULT USING PHASOR MEASUREMENT UNITS C.Anil Kumar 1, K.Lakshmi 2 PG Scholar, K.S.Rangasamy College of Technology, Tiruchengode, Tamilnadu, India. 1 Associate Professor, K.S.Rangasamy
More informationCHAPTER 9. Sinusoidal Steady-State Analysis
CHAPTER 9 Sinusoidal Steady-State Analysis 9.1 The Sinusoidal Source A sinusoidal voltage source (independent or dependent) produces a voltage that varies sinusoidally with time. A sinusoidal current source
More informationIntroduction to micropmu. PSL Australasian Symposium 2017 September 29 Thomas Pua Product Engineer
Introduction to micropmu PSL Australasian Symposium 2017 September 29 Thomas Pua Product Engineer What are synchrophasors? What are synchrophasors? Synchrophasors compare the phase angle of the voltage
More informationFault Location Using Sparse Wide Area Measurements
319 Study Committee B5 Colloquium October 19-24, 2009 Jeju Island, Korea Fault Location Using Sparse Wide Area Measurements KEZUNOVIC, M., DUTTA, P. (Texas A & M University, USA) Summary Transmission line
More informationAnalysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms
WWWJOURNALOFCOMPUTINGORG 21 Analysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms Bruno Osorno Abstract This paper analyses and explains from the systems point of
More informationSynchronized Phasor Measurement in Protective Relays for Protection, Control, and Analysis of Electric Power Systems
Synchronized Phasor Measurement in Protective Relays for Protection, Control, and Analysis of Electric Power Systems Gabriel Benmouyal, E. O. Schweitzer, and A. Guzmán Schweitzer Engineering Laboratories,
More informationChapter 25 PMU Deployment in Power System Oscillation Monitoring
Chapter 25 PMU Deployment in Power System Oscillation Monitoring Abdelmadjid Recioui, Hamid Bentarzi and Mohamed Tsebia Abstract Oscillatory events at low frequencies are commonly witnessed in interconnected
More informationINVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER
IOSR Journal of Electronics & Communication Engineering (IOSR-JECE) ISSN(e) : 2278-1684 ISSN(p) : 2320-334X, PP 68-73 www.iosrjournals.org INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE
More informationRT- HIL Implementation of Hybrid Synchrophasor and GOOSE- based Passive Islanding Schemes
RT- HIL Implementation of Hybrid Synchrophasor and - based Passive Islanding Schemes M. Shoaib Almas E- mail: msalmas@kth.se PhD Candidate Electric Power Systems Department KTH Royal Institute of Technology
More informationImplementation and Performance of Synchrophasor Function within Microprocessor Based Relays
Implementation and Performance of Synchrophasor Function within Microprocessor Based Relays Bogdan Kasztenny GE Multilin Mark Adamiak GE Multilin 1. Introduction Synchronized phasor measurements have come
More informationANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE
ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE KARTIK TAMVADA Department of E.E.E, V.S.Lakshmi Engineering College for Women, Kakinada, Andhra Pradesh,
More informationThe Effect of Delays on Wide-Area Damping Control of Electromechanical Oscillations
Introduction The Effect of Delays on Wide-Area Damping Control of - R. Karppanen AS-0.3100 Automaatio- ja systeemitekniikan seminaari, 2015 Outline Introduction 1 Introduction 2 3 4 Master s Thesis. 1
More informationDESIGN AND SIMULATION OF WIDE AREA MONITORING WITH SMART GRIDS USING PHASOR MEASUREMENT UNIT WITH DISTRIBUTED GENERATION
DESIGN AND SIMULATION OF WIDE AREA MONITORING WITH SMART GRIDS USING PHASOR MEASUREMENT UNIT WITH DISTRIBUTED GENERATION 1 BEJJENKIDINESH, 2 PERUMANDLA SADANANDAM 1 MTECH, DEPARTMENT OF ELECTRICAL AND
More informationCircuit Analysis-II. Circuit Analysis-II Lecture # 2 Wednesday 28 th Mar, 18
Circuit Analysis-II Angular Measurement Angular Measurement of a Sine Wave ü As we already know that a sinusoidal voltage can be produced by an ac generator. ü As the windings on the rotor of the ac generator
More informationA New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated
More informationMicro-synchrophasors (µpmus) in Electric Power Distribution Systems 5/29/15 SF PES Chapter Workshop
Micro-synchrophasors (µpmus) in Electric Power Distribution Systems 5/29/15 SF PES Chapter Workshop Dr. Alexandra (Sascha) von Meier Co-Director, Electric Grid Research, California Institute for Energy
More informationAnalysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.
Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh** *,**(Department of Electrical Engineering, Walchand College of
More informationSmart Grid Where We Are Today?
1 Smart Grid Where We Are Today? Meliha B. Selak, P. Eng. IEEE PES DLP Lecturer melihas@ieee.org 2014 IEEE ISGT Asia, Kuala Lumpur 22 nd May 2014 2 Generation Transmission Distribution Load Power System
More informationSmart Transmission Grids Operation and Control
INSTITUTE OF PHYSICAL ENERGETICS Smart Transmission Grids Operation and Control Dr.sc.ing. Anna Mutule Northern Region 2017 Workshop Information, 7-8 December, Latvia Timeline and Project Partners October
More informationChapter 1. Electronics and Semiconductors
Chapter 1. Electronics and Semiconductors Tong In Oh 1 Objective Understanding electrical signals Thevenin and Norton representations of signal sources Representation of a signal as the sum of sine waves
More informationPerformance Evaluation and Operation of PMUs in Power System
Performance Evaluation and Operation of PMUs in Power System K. Sundararaju 1, A.Nandhakumar 2, S.Jeeva 3 Department of Electrical and Electronics Engineering, M. Kumarasamy College of Engineering, Karur
More informationA Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors
A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors Dinesh Rangana Gurusinghe Yaojie Cai Athula D. Rajapakse International Synchrophasor Symposium March 25,
More informationAc fundamentals and AC CIRCUITS. Q1. Explain and derive an expression for generation of AC quantity.
Ac fundamentals and AC CIRCUITS Q1. Explain and derive an expression for generation of AC quantity. According to Faradays law of electromagnetic induction when a conductor is moving within a magnetic field,
More informationUse of Synchronized Phasor Measurements for Model Validation in ERCOT
Use of Synchronized Phasor Measurements for Model Validation in ERCOT NDR Sarma, Jian Chen, Prakash Shrestha, Shun-Hsien Huang, John Adams, Diran Obadina, Tim Mortensen and Bill Blevins Electricity Reliability
More informationSinusoids and Phasors (Chapter 9 - Lecture #1) Dr. Shahrel A. Suandi Room 2.20, PPKEE
Sinusoids and Phasors (Chapter 9 - Lecture #1) Dr. Shahrel A. Suandi Room 2.20, PPKEE Email:shahrel@eng.usm.my 1 Outline of Chapter 9 Introduction Sinusoids Phasors Phasor Relationships for Circuit Elements
More informationHarmonics Elimination Using Shunt Active Filter
Harmonics Elimination Using Shunt Active Filter Satyendra Gupta Assistant Professor, Department of Electrical Engineering, Shri Ramswaroop Memorial College of Engineering and Management, Lucknow, India.
More informationSymmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines
Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India
More informationSIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC
SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC 1 G.ANNAPURNA, 2 DR.G.TULASIRAMDAS 1 G.Narayanamma Institute Of Technology And Science (For Women) Hyderabad, Department Of EEE 2
More informationPostprint. This is the accepted version of a paper presented at IEEE PES General Meeting 2016, Boston.
http://www.diva-portal.org Postprint This is the accepted version of a paper presented at IEEE PES General Meeting 2016, Boston. Citation for the original published paper: Almas, M S., Vanfretti, L. (2016)
More informationModelling, Simulation and Fault Detection for a Transmission Lines by Synchronized Phasor Measurement
International Journal of Emerging Research in Management &Technology Research Article July 2014 Modelling, Simulation and Fault Detection for a Transmission Lines by Synchronized Phasor Measurement Abstract
More informationA Novel Four Switch Three Phase Inverter Controlled by Different Modulation Techniques A Comparison
Volume 2, Issue 1, January-March, 2014, pp. 14-23, IASTER 2014 www.iaster.com, Online: 2347-5439, Print: 2348-0025 ABSTRACT A Novel Four Switch Three Phase Inverter Controlled by Different Modulation Techniques
More informationISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS
ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS INDO-US Workshop October 2009, I.I.T. Kanpur INTRODUCTION Electric Power Systems are very large, spread over a wide geographical area
More informationImprovement of Voltage Profile using D- STATCOM Simulation under sag and swell condition
ISSN (Online) 232 24 ISSN (Print) 232 5526 Vol. 2, Issue 7, July 24 Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition Brijesh Parmar, Prof. Shivani Johri 2, Chetan
More informationGrid Power Quality Analysis of 3-Phase System Using Low Cost Digital Signal Processor
Grid Power Quality Analysis of 3-Phase System Using Low Cost Digital Signal Processor Sravan Vorem, Dr. Vinod John Department of Electrical Engineering Indian Institute of Science Bangalore 56002 Email:
More informationTraceable Synchrophasors
Traceable Synchrophasors The calibration of PMU calibration systems March 26 2015 i-pcgrid, San Francisco, CA Allen Goldstein National Institute of Standards and Technology Synchrometrology Lab U.S. Department
More informationUnder-Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF
Under-Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF Asja Derviškadić, Yihui Zuo, Guglielmo Frigo and Mario Paolone Swiss Federal Institute of Technology (EPFL) Distributed Electrical
More informationWide-Area Measurements to Improve System Models and System Operation
Wide-Area Measurements to Improve System Models and System Operation G. Zweigle, R. Moxley, B. Flerchinger, and J. Needs Schweitzer Engineering Laboratories, Inc. Presented at the 11th International Conference
More informationSynchrophasors for Distribution Applications
1 Synchrophasors for Distribution Applications Greg Hataway, PowerSouth Energy Cooperative Bill Flerchinger, Schweitzer Engineering Laboratories, Inc. Roy Moxley, formerly of Schweitzer Engineering Laboratories,
More informationPower Quality Improvement using Hysteresis Voltage Control of DVR
Power Quality Improvement using Hysteresis Voltage Control of DVR J Sivasankari 1, U.Shyamala 2, M.Vigneshwaran 3 P.G Scholar, Dept of EEE, M.Kumarasamy college of Engineering, Karur, Tamilnadu, India
More informationNOWADAYS, there is much interest in connecting various
IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013 419 Modified Dynamic Phasor Estimation Algorithm for the Transient Signals of Distributed Generators Dong-Gyu Lee, Sang-Hee Kang, and Soon-Ryul
More informationThe Virginia Tech Calibration System
The Virginia Tech Calibration System Javier O. Fernandez Thesis submitted to the faculty of the Virginia Polytechnic Institute and State University in partial fulfillment of the requirements for the degree
More informationPhasor. Phasor Diagram of a Sinusoidal Waveform
Phasor A phasor is a vector that has an arrow head at one end which signifies partly the maximum value of the vector quantity ( V or I ) and partly the end of the vector that rotates. Generally, vectors
More informationMITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)
VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim
More informationUse of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation
More informationDistribution Fault Location
Distribution Fault Location 1. Introduction The objective of our project is to create an integrated fault locating system that accurate locates faults in real-time. The system will be available for users
More informationPractical PMU Applications for Utilities
Practical PMU Applications for Utilities University of Washington EE Graduate Seminar November 1 st, 2012 Manu Parashar Douglas Wilson SynchroPhasor Technology Phasor Measurement Units (PMUs) Next generation
More informationWide Area Visualization & SynchroPhasors
Wide Area Visualization & SynchroPhasors January 12, 2012 Manu Parashar Anil Jampala Principal Engineer GRID Holistic Generalized Grid Security Analysis Traditional MODEL-BASED Analysis (EMS) PMU MEASUREMENT-BASED
More informationImprovement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive
Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive B. Mohan Reddy 1, G.Balasundaram 2 PG Student [PE&ED], Dept. of EEE, SVCET, Chittoor
More informationPMU-based Voltage Instability Detection through Linear Regression
PMU-based Voltage Instability Detection through Linear Regression Rujiroj Leelaruji and Prof. Luigi Vanfretti Smart Transmission Systems Lab. Electric Power Systems Department KTH Royal Institute of Technology,
More informationTesting and Validation of Synchrophasor Devices and Applications
Testing and Validation of Synchrophasor Devices and Applications Anurag K Srivastava The School of Electrical Engineering and Computer Science Smart Grid Demonstration and Research Investigation Lab Washington
More informationTask Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team Matthew Rhodes 3/22/16
NASPI White Paper: Integrating Synchrophasor Technology into Power System Protection Applications Update Report Task Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team
More informationDynamic PMU Compliance Test under C aTM-2014
Downloaded from orbit.dtu.dk on: Apr, Dynamic PMU Compliance Test under C7..aTM- Ghiga, Radu; Wu, Qiuwei; Martin, K.; El-Khatib, Walid Ziad; Cheng, Lin; Nielsen, Arne Hejde Published in: Proceedings of
More information