Synchronized Phasor Measurement in Protective Relays for Protection, Control, and Analysis of Electric Power Systems

Size: px
Start display at page:

Download "Synchronized Phasor Measurement in Protective Relays for Protection, Control, and Analysis of Electric Power Systems"

Transcription

1 Synchronized Phasor Measurement in Protective Relays for Protection, Control, and Analysis of Electric Power Systems Gabriel Benmouyal, E. O. Schweitzer, and A. Guzmán Schweitzer Engineering Laboratories, Inc. Published in Wide-Area Protection and Control Systems: A Collection of Technical Papers Representing Modern Solutions, 017 Previously presented at the 8th International Conference on Developments in Power System Protection, April 004, 57th Annual Conference for Protective Relay Engineers, March 004, 57th Annual Georgia Tech Protective Relaying Conference, May 003, and InterNational Electrical Testing Association Technical Conference, March 003 Originally presented at the 9th Annual Western Protective Relay Conference, October 00

2 SYNCHRONIZED PHASOR MEASUREMENT IN PROTECTIVE RELAYS FOR PROTECTION, CONTROL, AND ANALYSIS OF ELECTRIC POWER SYSTEMS Gabriel Benmouyal Schweitzer Engineering Laboratories, Inc. Longueuil, PQ CANADA E. O. Schweitzer, A. Guzmán Schweitzer Engineering Laboratories, Inc. Pullman, WA USA ABSTRACT The advent of satellite-based time-keeping systems and advances in computer technology have made possible protective relay sampling synchronization within 1 µs. These relays can now provide synchronized phasor measurements that eliminate the need to have different devices for protection, control, and electric power system analysis for system-wide applications and traditional protection applications. System-wide applications have different sampling and signal processing requirements than do traditional protection applications. These different requirements normally are addressed with different devices, one device for each specific function. This paper proposes combining the aforementioned applications in a single device with a flexible signal processing system. The addition of synchrophasor measurement in a protective relay results in increased power system reliability and provides easier disturbance analysis, protection, and control capabilities than do approaches with different information sources. Keywords: frequency, protective relays, sampling, synchronized phasor measurement, time synchronization INTRODUCTION There may be a historical parallel between fault locating and phasor measurements in digital relays. Two decades ago, stand-alone fault locators were seldom used. They were relatively expensive and were only used on the most critical and troublesome lines. Then, distance relays that included fault locating appeared and were quickly accepted. After a decade, it was impossible to imagine a distance relay without fault-locating capabilities. For some time now, stand-alone synchronized phasor measuring devices have been available. They are not in widespread use, because they too are relatively expensive and find use only on critical systems. Now, a distance relay is available that includes synchronized phasor measurement capabilities. As these relays are becoming widely used, especially on extra highvoltage systems, the phasor-measurement function is proliferating. It is no longer necessary to justify a phasor measurement capability since it comes for free with the line protection. Just as was the case with fault locating, we need to understand how phasor measurement works and what it can do for us. That is the purpose of this paper. We will first carefully define phasors and synchronized phasors. An IEEE standard defines the absolute time reference for phasors as the start of the second. These points in time are known to within a microsecond when satellite clock receivers are available. The standard does not define phase for off-frequency quantities, such as a system operating at 59.8 Hz. This paper clearly defines absolute phase, even at off-nominal frequencies. 1

3 We examine phase as an indicator of the dynamic performance of a power system, as is well appreciated in the dynamic swing equations. The paper is careful to recognize that phasors represent systems assumed to be in steady state. If a system is swinging, or when a fault occurs, there are electrical and mechanical transients, and we must be careful how we calculate magnitude and phase, and equally careful in how we use or interpret these quantities during transients. We will show a method that uses a three-cycle moving average and that implies phase measurement updates 0 times per second, or about every 50ms. This is fast enough to follow the electromechanical action of the system, and slow enough to filter out electrical-transient behavior. We review several methods of sampling and processing signals, and show that the preferred way for phasor measurement is to first sample the signals using a sampling clock which is in absolute time synchrony. Each sample then is taken at a precisely known and absolute time. Phase is calculated from these samples. Magnitude is calculated after a resampling at a multiple of the actual system frequency using Fourier filters. The relay now measures absolute phase, as well as voltage, current, power, and reactive power. The relay therefore is a transducer, too. This transducer measures the state variables and other protective relay-related information. The above, plus advances in affordable, available, fast, dependable wide-area communications, make new approaches to system stability monitoring and control become practical. One might perceive a wide-area system where relays measure and communicate state variables to one or more processing elements, every tenth of a second, for example. The processing elements, in turn, assess the overall system state and exercise wide-area control and other decisions. The 10-minute problem of state estimation is reduced to a 0.1 second exercise of state measurement! The advent and broad deployment of relays having phasor measurement capability is a grand opportunity for providers of state estimators to simplify their calculations, to obtain more accurate state estimates, much more rapidly, probably with smaller, more reliable computing systems. Synchronized measurements also ease analysis of oscillographic records, because all records can be immediately compared. The paper also describes two types of information output: unsolicited binary messages and solicited ASCII messages. The unsolicited messages are generated automatically at a specified rate and could be compared to a transducer output. The solicited messages provide snapshots at instants the user specifies. Finally, we mention the sources of error and conclude that accuracies of much less than one electrical degree are routinely achievable. The largest source of error is CCVT error. Now that phasor measurement is becoming deployed for free, it will be fascinating to see the many creative applications that result and the many serious problems that are solved.

4 VOLTAGE AND CURRENT TIME WAVEFORMS AND PHASOR DEFINITION The Origin of Phasors Originally, phasors were introduced for the purpose of transforming electrical circuit differential equations into ordinary algebraic equations. As an example, consider the circuit of Figure 1. R R V cos (ω t + φ) i(t) V φ I θ L jω L a) Circuit in the time domain b) Circuit in the frequency domain Figure 1 RL electrical circuit in the time and frequency domains The solution of the following differential equation provides the solution for the circuit current: d i(t) V cos ( ω t + φ) = R i(t) + L (1) dt The circuit being linear, the solution for the current has the following form: ( ω + θ) i (t) = I cos t () We can represent voltage and current phasors as complex numbers in exponential form: r V = V e jϕ r and I = I e jθ (3) The Appendix shows that we can express Equation 1 in algebraic form as follows: The solution for the current is: jθ ( R + j ω L) I e jϕ V e = (4) I e jθ jϕ V e = R + jω L (5) From this example, we can infer the following: 1. A phasor is a complex number associated with a sinusoidal wave. The phasor magnitude is the same as the sinusoidal wave magnitude. The phasor phase angle is the phase of the wave at t = 0.. Phasors normally are associated with a single frequency. 3. To be able to remove the time dimension from the solution when applying the phasor transformation (see Appendix), all parameters in the system must be constant. 3

5 4. There is no need to define a time scale or a time reference in theoretical steady-state studies, because the time dimension has been removed from the final phasor-based equations (see Appendix). 5. In power network studies, application of phasors occurs in all problems where the parameters are constant and we have a single frequency. Load-flow or short-circuit programs are examples of such studies. For electromagnetic transient analysis, we usually solve the network differential equations in the time domain. Tools such as EMTP (Electromagnetic Transient Program) or the Power System Blockset [1] are examples of this approach. Theoretically in an actual power network, we could apply phasors only in steady-state conditions. As we will see later, we can still apply the phasor concept in transient conditions and obtain good results. Definition of Synchronized Phasors The definition of a real-time or synchronized phasor provided in the IEEE Standard [] corresponds to the conventional definition described earlier, at least at rated frequency. Outside rated frequency, the standard opens the door for equipment manufacturers to develop their own definition (see Appendix C in Reference []); the standard has no requirement regarding phasor magnitude measurement accuracy outside system nominal frequency (50 Hz or 60 Hz). With real-time waveforms, it is necessary to define a time reference to measure phase angles synchronously [3]. The IEEE Standard [] defines the start of the second as the time reference for establishing the phasor phase angle value. The synchronized phasor measurement convention is shown in Figure. v Start of the second v = V cos (ω t + φ ) φ = 0 V t V 0 V v Start of the second φ = 90 V t V 90 V Figure Synchrophasor measurement convention with respect to time 4

6 The instantaneous phase angle measurement remains constant at rated frequency when using the start of the second phase reference. If the signal is at off-nominal frequency, the instantaneous phase varies with time. We shall see later that the choice of this reference has an impact on the phasor phase angle measurement at off-nominal frequency. The IEEE Standard [] defines a steady-state waveform where the magnitude, frequency, and phase angle of the waveform do not change. This standard has no requirements regarding phasor measurement performance for a waveform in transient state. Phase Measurement at Off-Nominal Frequencies Let the following function represent the voltage at a bus in a power system network: The argument of the cosine function in Equation 6 is: V(t) = V cos ( π ƒ t + φ) (6) θ(t) = π ƒ t + φ (7) At off-nominal frequencies, we can represent the argument, θ, of the cosine function as follows: where: ƒ = ƒ ƒ NOM θ(t) = π ƒ NOM t + π ƒ t + φ (8) If we subtract from θ the angle measurement resulting from the nominal frequency, π ƒ NOM t, we obtain the angle measurement that includes the angle measurement caused by frequency deviation from nominal frequency, π ƒ t, plus the phase angle at t = 0, φ. Following is the equation representing the new angle measurement: β(t) = π ƒ t + φ (9) At nominal frequency ƒ = 0, β(t) = φ. At off-nominal frequency, β will change with time. Figure 3 shows β for ƒ > 0. β φ t 0 Figure 3 Phase measurement at off-nominal frequency for ƒ > 0 5

7 If we compare the angle measurement, β, at two locations with constant φ, the angle difference, β, is constant and equal to φ, as Figure 4 illustrates, provided that the phase angle comparison occurs at exactly the same time. β( t) =βa (t) βb(t) = φ (10) β β A A X L B φ β B φ A φ B t Figure 4 0 Phase measurement at two locations at off-nominal frequency Phase as Indicator of the Dynamic Performance of a Power System Synchronous machines must adapt to different operating conditions when exchanging real power across a power system [4]. The machines accelerate or decelerate to adapt to changing power transfer requirements that occur during system disturbances. Power system dynamics involve the electrical properties, as well as the mechanical properties, of the electrical machines in the system. For the purpose of this discussion, assume a two-pole synchronous machine where the mechanical and electrical degrees are equal. The difference between shaft torque, T m, and electromechanical torque, T e, in a machine determines the accelerating torque, T a, as shown by Equation 11. In generators, T a > 0 accelerates the machine. T = T T (11) We can represent power, P, as a function of torque, T, according to Equation 1. where: a m e P = T ω (1) T ω is the torque, N m is the angular velocity, rad/s As we see from Equation 13, the change of the angular rotor position, θ, with respect to time determines the angular velocity, ω. 6

8 dθ ω = (13) dt The torque, T, is a function of the moment of inertia, J, and the angular acceleration, α, according to Equation 14. where: J is the moment of inertia, kg m T = J α (14) α is the change of the angular velocity with respect to time, rad/s As in Equation 15, the angular momentum, M, is a function of the moment of inertia, J, and the angular velocity, ω. M = J ω (15) With Equation 16, we can represent the accelerating power, P a, as a function of the angular acceleration, α, and as a function of the angular rotor position, θ. θ d Pa = Ta ω = M α = M (16) dt We can express the rotor angle position with respect to a synchronous reference frame that rotates at synchronous speed, ω syn. The angular rotor position, θ, is equal to the phase angle due to the synchronous rotating reference, ω syn t, plus the angular displacement from the synchronous rotating reference, δ, as shown in Equation 17. The angular velocity, ω, is: θ( t) = ωsyn t + δ (17) dθ dδ ω = = ωsyn + (18) dt dt Taking the derivative of the angular velocity, we can rewrite Equation 16 as a function of δ: d δ Pa = M (19) dt We can express Equation 19 as a function of the constant inertia, H, with power expressed in per unit as follows: H d δ H dω Pa = Pm Pe = = (0) ω dt ω dt syn syn 7

9 where: P m P e H is the mechanical power supplied to the generator, pu is the electrical power supplied to the system, pu is the constant of inertia, s Equation 0 is known as the swing equation; one swing equation per machine is necessary to model the network dynamics. When the load-generation equation is balanced (total load equals total generation), machine speeds are practically equal to synchronous speed. The angular displacements, δ, of machines in a system provide information about the system dynamics. One cannot measure this angular displacement mechanically. By computing the voltage phasor behind the machine transient reactance, one can study the phase angle variations to obtain an image of the machine angular displacement. In practice, machine oscillating modes can be determined by measuring the phase angle of the positive-sequence voltage phasor at the machine terminals. This is demonstrated later in the text. Voltage, Frequency, and Phase Angle Frequency carries a special significance when dealing with the measurement of phasors in real time. Phasors are basically a concept applied at a single frequency. In an actual network, situations could develop in which the frequency is other than the rated value. Equations 18 and 0 determine the speed of a generator, and the generator speed determines the frequency at the generator output. When each generator swing equation reaches equilibrium, the operating frequency is the same on all points of the network, and we can represent a bus voltage, phase angle, and angular velocity with Equations 6, 17, and 18, respectively. During a network disturbance (fault, loss of generation, or major load change), both the angular velocity and the phase angle undergo local changes. We can rewrite Equation 18 as a function of frequency and phase angle as follows: ƒ = ƒ syn + 1 d δ π dt (1) where: ƒ syn is the frequency at synchronous speed, Hz Equation 1 indicates that, during a major disturbance, the local frequency and the local phase angle change simultaneously. We shall see later that this behavior has some direct consequences on the way a phasor measurement is processed in relation to the signal sampling frequency: fixed or adaptive. Phasor Representation in Steady and Transient States On a power network, we can define steady state as the situation where generation and load are practically (within an acceptable margin of error) balanced and the load-frequency regulation has reached a point of balance (i.e., network frequency equals rated frequency). In steady state, therefore, voltage and current time waveforms have constant amplitude, frequency, and phase 8

10 angle. Although we usually assume the constant frequency in steady state to be the system nominal frequency, that assumption is not always true. In steady state, measured real-time phasors, according to the original definition, are the solution of any set of network equations under consideration. As an example, consider the positivesequence voltage (PSV) synchronized phasors at the extremities of a line such as that modeled in Figure 5. P ij Q ij Y ij V i δ ij V j 0 Y sh Figure 5 Line power flow depends on the terminal voltage magnitudes and angles The relationship between the line real and reactive power flows and the PSV phasors at the line buses is provided by the next two equations: P Q ij ij = V i = V real i imag r r r r ( Ysh + Yij ) Vi Vj[ real (Yij) cos δij + imag (Yij) sin δij] r r r r ( Y + Y ) V V [ real (Y ) sin δ imag (Y ) cos δ ] sh ij i j Computation of synchronized phasors in real time occurs through the use of filtering systems [5, 6, 7, 8]. In steady state, a phasor value is independent from the filtering system; different filtering systems provide the same output. We can define transient state on a power network as the condition in which the magnitude, phase angle, or frequency of one or more bus voltages become a function of time. Another definition of transient state could be the network condition existing between two stable states. This means that every time a change occurs on a network, a transient state condition will follow. Phasors, by definition, cannot represent in transient state the exact value of corresponding variables. The amount of transient error will to a great extent depend upon filtering system frequency tracking capability, which in turn depends upon response time and frequency response. In transient state, one has to expect that two different filtering systems will provide different outputs. Although synchronized phasors will exhibit some errors in transient state, the level of errors is usually acceptable; transient state applications should be considered viable and reliable. The situation is similar to that of applying phasors in protective relaying: voltage and current phasors, although computed in transient state, still perform the task of detecting faults. ij ij ij ij () (3) PRESENT SAMPLING AND SIGNAL PROCESSING PRACTICES Following is a brief description of present sampling and signal processing practices for synchronized phasor measurement, oscillography, harmonic analysis, and line distance protection. First, we describe sampling at fixed time intervals (constant number of samples per 9

11 second) without and with an absolute time reference. Then, we discuss sampling at multiples of power system operating frequency (constant number of samples per power system cycle). Sampling at Fixed Time Intervals Traditionally, digital fault recorders (DFRs) acquire data at fixed time intervals to provide voltage and current oscillography and harmonic analysis. For example, DFRs use sampling rates (f S ) of 1 kilosample/second (ksps) or faster. The samples are synchronized to an internal time source or an external time source. In some applications, the external time source is an absolute time reference from a global positioning system (GPS) receiver. Figure 6 shows a typical DFR data acquisition block diagram with traditional DFR applications (such as oscillography and harmonic analysis) using an internal time source. The figure includes a hardware low-pass filter (Hardware LPF) for anti-aliasing and an analog-to-digital (A/D) converter for analog-to-digital conversion. Local Clock Sampling Interval ƒ S V or I Analog Channel Hardware LPF A/D Oscillography Harmonic Analysis Figure 6 Sampling at fixed time intervals with a local clock for oscillography and harmonic analysis The main advantage of this acquisition system is that the data preserve the frequency information of the power system. For example, you can analyze power system frequency excursions during power system disturbances. This data acquisition system is also suitable for synchronized phasor measurement (Figure 7) when an external time source with absolute time reference determines the sampling interval [9]. GPS RCVR Time Synch ƒ S V or I Analog Channel Hardware LPF A/D Synchronized Phasor Measurement Oscillography Harmonic Analysis Figure 7 Sampling at fixed time intervals with an absolute time reference for synchronized phasor measurement, oscillography, and harmonic analysis 10

12 A small variation of this approach is a sampling system that uses a fixed sampling rate (f S ) that is a multiple of the system nominal frequency (f NOM ). For example, 960 samples/second (SPS) could be the sampling rate. This rate is 16 times the nominal frequency (f NOM ) in a 60 Hz power system. Sampling at constant time intervals is suitable for multiple protection applications such as current differential protection [10], but it introduces unwanted errors in protection applications such as line distance protection. One common approach to obtaining phasor information for protection applications is to calculate the Discrete Fourier Transform (DFT) of the sampled signal. It is well documented in the literature [11] that this phasor calculation is in error when the power system operates at off-nominal frequencies. Figure 8 shows the deviation from ideal of the phasor calculation for angles from 0 to 360. These calculation errors may cause distance element misoperation [1]. The data acquisition system requires information about the power system operating frequency to minimize phasor calculation errors, as we will see later Ideal Phasors 6 4 Imaginary 0 - Calculated Phasors Real Figure 8 Phasor calculation errors at off-nominal frequency Sampling at Multiples of Power System Operating Frequency Sampling at multiples of power system operating frequency minimizes phasor calculation errors when the system operates at off-nominal frequencies. Figure 9 shows this type of data acquisition system. The system calculates the power system operating frequency (f SYS ) and uses this frequency information to obtain the sampling frequency (f S ) as a multiple of the system operating frequency. Reference [13] describes one method of frequency estimation; other frequency estimation approaches accomplish the same task [11]. The sampled data pass through a digital band-pass filter (DBPF), after which the filtered signal is ready for line distance protection applications. This approach reduces errors in phasor calculations; remaining error depends only on frequency estimation error, usually less than 0.01 Hz. A disadvantage of this approach is that the phasor measurement is not referenced to absolute time for synchronized phasor measurement applications. The approach needs an absolute time reference for such applications. 11

13 ƒ sys ƒ sys xk System Frequency Estimation ƒ S V or I Analog Channel Hardware LPF A/D DBPF Line Distance Protection Figure 9 Sampling at multiples of power system operating frequency for line distance protection Sampling at Fixed Time Intervals With Adaptive Filtering We can use samples at fixed time intervals to calculate phasors with minimum error. In this approach (see Figure 10), the data acquisition system estimates the power system operating frequency and uses this frequency information to modify the filter coefficients of the digital bandpass filter. This approach is attractive because it minimizes errors in phasor calculations without needing a constant number of samples per cycle. A disadvantage of this approach is that it does not provide a common time reference for multiple devices connected at different power system locations. The approach is also not suitable for synchronized phasor measurements. US Patent Number 6,141,196 [14] describes one method that uses a similar approach. System Frequency Estimation ƒ sys V or I Analog Channel Hardware LPF A/D Adaptive DBPF Line Distance Protection ƒ S Sampling Interval Oscillography Harmonic Analysis Local Clock Figure 10 Sampling at fixed time intervals with adaptive filtering for oscillography, harmonic analysis, and line distance protection 1

14 SAMPLING AND SIGNAL PROCESSING FOR SYNCHRONIZED PHASOR MEASUREMENT AND LINE DISTANCE PROTECTION (PATENT PENDING) The data acquisition methods we discussed earlier provide solutions suitable for either synchronized phasor measurement applications, which require sampling referenced to an absolute time reference, or line distance protection applications, which require sampling at multiples of the power system operating frequency. Figure 11 shows data acquisition and data processing suitable for both kinds of applications. This data acquisition and processing system is part of a multiple power system applications device that we describe in the following sections. Sampling and Signal Processing for Multiple Power System Applications The multiple applications device acquires data at fixed time intervals; the sampling frequency (f S ) depends on an external clock signal (GPS receiver) with absolute time reference. For synchronized phasor measurement applications, the device uses the GPS time reference. After the A/D converter acquires the data, the data are calibrated to compensate for hardware data acquisition errors. The calibrated data are available at a high sampling rate (e.g. 8 ksps); these data are suitable for synchronized phasor measurements, oscillography, and harmonic analysis applications. The high sampling rate data pass through a digital low-pass filter (DLPF) before down sampling and resampling. The down sampler outputs data at a lower rate for frequency estimation. One of the inputs to the resampler (RSMP) is the filtered signal. The second input to the resampler is the power system operating frequency (f SYS ). The resampler outputs data at a rate that is a multiple of the operating frequency (f SYS ), e.g., 3 f SYS. The resampled data pass through a digital band-pass filter (DBPF). The DBPF has fixed coefficients that do not depend on the power system operating frequency (f SYS ). The filtered data are ready for distance protection applications such as Reference [15] describes. The filtered data are also available to calculate the magnitude of the synchronized phasor, as we will see later. Figure 1 shows a variation of this sampling and signal-processing system, in which the sampling is based on the local clock. Resampling in this variation uses the absolute time reference from the GPS receiver and the system operating frequency to resample the data at a specific frequency depending on application requirements. 13

15 V or I Analog Channel Hardware LPF GPS RCVR Time Synch ƒ S Down Sample Frequency Estimation ƒ SYS A/D CAL DLPF RSMP DBPF Synchronized Phasor Measurement Oscillography Harmonic Analysis LPF = Hardware Low-Pass Filter A/D = Analog-to-Digital Converter CAL = Calibration DLPF = Digital Low-Pass Filter RSMP = Resampler DBPF = Digital Band-Pass Filter Line Distance Protection Figure 11 Sampling with an absolute time reference for synchronized phasor measurement applications and resampling at multiples of the power system operating frequency for line distance protection applications 14

16 Local Clock GPS RCVR Sampling Interval Time Synch V or I Analog Channel Hardware LPF System Frequency Estimation ƒ S A/D ƒ SYS RSMP Synchronized Phasor Measurement Line Distance Protection Figure 1 Sampling at fixed time intervals with a local clock, and resampling according to the absolute time reference and power system operating frequency An Algorithm Decoupling Phasor Magnitude and Phase Angle Measurements Considering that a system with adaptive sampling allows measurement of a phasor magnitude over a broad frequency interval and that a system with a fixed sampling frequency allows avoidance of the local frequency measurement, combination of these two systems would optimize phasor measurement performance. Such a system is shown in Figure 13. Consider the voltage waveform of Equation 6 and assume multiplication of this waveform by a time-synchronized unit phasor, according to the following equation: r V = V cos jπf t ( π f t + φ) e NOM NOM (4) which can be otherwise expressed as Equation 5: r V V = f t j j f t j j f t [ e j π NOM φ e + π e NOM φ π e ] e NOM (5) or as Equation 6: r V V j π φ [ φ j4 f t e + e NOM e ] = j (6) If we filter out the double-frequency component, we finally obtain Equation 7: V jφ V r = e (7) The computed phasor is the original waveform phasor with the magnitude divided in half. Because we use a signal at synchronous speed to demodulate the input signal, the magnitude of the computed phasor will not represent properly the magnitude of the incoming signal at offnominal frequency. To obtain a phasor magnitude evaluation independent of frequency, we use the magnitude of the phasor calculation for protective functions that has been processed through a system with adaptive sampling frequency. The final phasor combines the two outputs: magnitude on one side and phase angle on the other. The unit exponential function that multiplies the signal has a fixed sampling frequency of 1 khz and is time synchronized. 15

17 *cos( π 60 t ) Voltage input sampled at 1 khz *-sin( π 60 t ) 3-Cycles Moving Average 3-Cycles Moving Average *Time-synchronized reference signals LPF Butterworth 4th Order, ƒ c = 18 Hz LPF Butterworth 4th Order, ƒ c = 18 Hz j Angle Calculation 1 φ V V φ Magnitude From a Cosine Filter With Adaptive Sampling Frequency Phasor Figure 13 Principle of decoupled-phasor measurement Performance of the Decoupled Algorithm We first evaluate the capability of the decoupled algorithm to perform phase angle measurement outside rated frequency. Equation 8 and Equation 9 define two waveforms v 1 (t) and v (t): v 1 (t) = cos ( π 59.5 t + π/4) (8) v (t) = cos ( π 59.5 t) (9) These waveforms are processed through the decoupled algorithm, and the resulting phase angles are shown in Figure 14. One can see that, in both cases, the rate of change of the phase angles is constant and equal to 180 /s: d φ 1 dφ = = π rad/s = 180 /s dt dt (30) After the transient response has faded away, Equation 31 provides the steady-state phase angle difference between the two phasors at any synchronous time: π φ1 φ = rad = 45 (31) Angle in Degrees Angle of ratio v 1 / v Angle of v Angle of v Time (s) Figure 14 Phase angle difference between two phasors at off-nominal frequency 16

18 To evaluate the dynamic performance of the decoupled algorithm, we will revisit the classic problem of a generator connected to an infinite bus through a transmission line for different operating and fault conditions. Figure 15 shows the network, which has been modeled with the Power System Blockset [1]. Both the power-frequency and the field supply-regulation loops have been modeled as shown in Figure 16. The speed-droop characteristic (percent change in frequency that would cause the output power of the unit to change by 100 percent) has been set to 5 percent. Three-phase faults of different durations applied at the output of a generator induce frequency oscillations on the machine. Frequency oscillations resulting from a difference between the mechanical and electrical power (Equation 0) are known to be stable (the frequency returns to a stable and constant value) or unstable (the frequency steadily increases or decreases). We could use the equal-area algorithm [4] to analyze this example theoretically. We will demonstrate, instead, that by measuring the difference in phase angle between the PSV phasor at the output of the generator (Bus 1) and the same phasor at the infinite bus (Bus 3), it is possible to detect transient stability or instability conditions. Note that although this application of synchronized phasors is in transient state (the frequency close to the generator is a function of time), it nevertheless achieves the primary goal of measuring the phase angle between two bus voltages. A three-phase short circuit is applied at Bus for 50 ms, with the resulting machine speed shown in Figure 17. Ultimately, the machine speed returns to its synchronous value. The frequency disturbance is reflected in the voltage phase angle close to the machine. Figure 18 shows the phase angle difference between the two synchronized PSV phasors measured at Bus 1 and 3 using the phasor-decoupling algorithm. Obviously, the phase angle disturbance is also stable. Figure 19 and Figure 0 show the results of the same simulation with a three-phase fault applied for 00 ms. The speed and PSV phasor phase angle difference time waveforms reflect a stable disturbance for a second time, although the excursion amplitudes are much larger than the previous example. Hydraulic Generator Bus 1 Bus Bus 3 X ' d 00 MVA 13.8 kv H = 3. s = 0.96 pu 10 MVA 13.8/30 kv Y Z T = 0.15 pu Z 1 = ohms Z 0 = ohms Figure 15 Generator and infinite-bus network model 17

19 V ref = 1.0 pu Exciter System E f ω ref P ref = 0.75 pu Hydraulic Turbine and Governor Generator V t Network P e Figure 16 Generator voltage and hydraulic-turbine regulators model Figure 1 and Figure show the machine speed and the phase angle difference between the PSV phasors measured at Bus 1 and Bus 3, respectively, for a 300 ms fault. This fault duration is longer than the critical clearing time. In this case, the system becomes unstable; the phase difference corresponds to an increasing exponential with a positive time constant. The plot of the machine speed shows a linearly increasing angular velocity, which indicates loss of machine synchronism with respect to the infinite bus frequency. The generator rotor swing equation for this particular system is provided by Equation 0, which can be otherwise expressed as Equation 3: H ω syn d δ = P dt m P max sin δ (3) where the following provides maximum power P max : where: P E E 1 3 max = (33) X13 E 1 E 3 X 13 is the generator voltage magnitude behind the transient reactance X d is the infinite bus voltage source magnitude is the reactive impedance magnitude between the two voltage sources We can use Equation 34 to calculate the reactive impedance between the two sources: where: X = + (34) 13 Xd + XT + XL XS X d X T X L X S is the generator transient reactance is the transformer reactance is the line reactance is the infinite bus source reactance with the following circuit values: 18

20 X 13 = = pu (35) Given that the mechanical power supplied to the generator is 0.75 pu, and with the magnitude of the two sources equal to unity, we can use Equation 36 to compute the swing equation at the point of balance: H ω syn d δ = sin 3.70 dt (36) During a disturbance, the oscillation frequency of the generator rotor is provided by [4]: ƒ n 1 ωs Sp = = = Hz (37) π H π 3. where S p is the synchronizing power coefficient calculated by Equation 38: dpe Sp = = Pmax cos δ0 dt δ=δ 0 = cos 3.70 = pu (38) The theoretical period, 1/f n, of oscillation is 0.66 seconds. The measured period of oscillation for the 50 ms fault is seconds, while the period for the 00 ms fault is seconds. In both cases, the error is less than 3 percent. This example demonstrates the following: 1. Although the example can be considered a transient-state condition, the synchronized phasor measurement provides fairly good accuracy for measurement of the phase angles.. The accuracy achieved in computing the phase angle of the phasors shows that the fixed sampling frequency (1 khz) is particularly efficient for resolving the phase angle difference between signals that are not at rated frequency Time (s) Figure 17 Machine speed or frequency for a 50 ms fault Angle in Degrees Time (s) Figure 18 PSV phasors phase angle difference between buses for a 50 ms fault 19

21 Time (s) Figure 19 Machine speed or frequency for a 00 ms fault Angle in Degrees Time (s) Figure 0 PSV phasors phase angle difference between buses for a 00 ms fault Angle in Degrees Time (s) Figure 1 Machine speed or frequency for a 300 ms fault Time (s) Figure PSV phasors phase angle difference between buses for a 300 ms fault SYNCHRONIZED PHASOR APPLICATIONS Real-Time Monitoring of State Variables V 1 δ 1 jx 1 V 0 P 1 Q 1 Figure 3 Elementary single-line network Real-time implementation of synchronized phasors allows for the fast measurement of PSV phasors at network buses. The phase angles of these quantities constitute the most important network state variables, because these angles are related to the network transient stability margin, line power flows, and voltage security [16, 17]. 0

22 For the elementary line represented in Figure 3, the equation for the real power flow at the left bus is given by the conventional real power flow equation: P V V and by the conventional reactive power flow equation: Q 1 1 = sin δ1 (39) X1 V1 V1 V 1 = cos δ1 (40) X1 X1 Equations 39 and 40 are identical to Equations and 3, except that the shunt admittance and line resistance are considered negligible. To establish the relationship among the voltage regulation (expressed as the ratio of the two voltage magnitudes at the line extremities), the reactive power supplied to the line, and the phase angle between the voltage phasors, Equation 40 takes the form of Equation 41: We can express the remote voltage, V, in per unit for V r 1 V V V1 X1 Q1 = (41) 1 V1 cos δ1 1 1 δ1 = 1 0 as follows: 1 X Q V = (4) cos Monitoring of network state variables allows also for verification and calibration of network studies. Phase Transducer and Dynamic Recording of Phases Any change occurring on an electrical network (i.e., network fault), topological change such as the opening or closing of a line, step changes in generation-load equilibrium (loss of a generation block or addition of a major load), tie-line or inter-area stable or unstable power oscillations, etc., will be reflected in the measurement of the magnitude and the phase angle of the network state variables. Recording of strategically located phase angle state variables prior and after the disturbance provides valuable information about the power system response and the capacity of the power system to respond to adverse events. Special Protection Systems and Network Out-Of-Step Relaying A number of utilities have ongoing projects or have already used synchronized phasor principles to monitor network transient stability or to implement special protection systems based on out-ofstep protection. When a number of network generators start to run at different speeds, loss of synchronism might occur. When one portion of a network becomes unsynchronized with respect to another, the voltage phase at the buses close to the generators causing the disturbance reflects changes in rotation speed. When a protection system detects instability, remedial action schemes can involve network separation or load shedding. 1

23 Two approaches have been described to implement a network out-of-step application [18, 19, 0, 1]: 1. To the extent that a two-machine system equivalent can represent a network, one approach consists of synchronous measurement of the phase angle between the transient reactances of the two machines. When a disturbance occurs, the new phase angle between the two machines is computed and the equal area algorithm is implemented in real time to determine whether the new point of operation is stable [19, 0].. A second approach consists of measuring the PSV phasors at two or more strategically located buses. During a disturbance, the phase angle between the signal pairs is computed in real time, and a predictive algorithm is used to establish whether the disturbance will be stable. One application uses a model of the phase angle time waveform in the form of an exponentially damped sine wave [1]: αt δ(t) = δ0 + A e sin ( ωt + β) (43) where δ 0 is the initial phase difference, α is a damping constant, ω is the angular frequency of the phase difference, and A is the oscillation amplitude. A predictive algorithm is used to identify the phase angle variation parameters and to determine stability or instability conditions. State Estimation The purpose of a state estimation program [, 3] in a Network Management Center is to provide a statistical real-time estimate of network state variables in the form of bus voltage magnitudes and phase angles. A state estimator can detect and correct gross measurement errors. State estimation is a steady-state application and a slow process, with a time frame on the order of a few minutes. A number of synchronous measurements are taken in real time on the network. The state variables are computed from the set of nonlinear equations linking the measurements to the state variables. The process is statistical because there are normally more measurements than state variables, and an increased number of measurements improves the accuracy of the result. As an example, consider the network of Figure 3. It is clear that actual networks and the extent of computations will be much larger than the example shows. First, a state variable vector is defined as the PSV phasor magnitude of the two buses and the phase angle between these buses [3]: x1 δ1 x = x = V1 (44) x 3 V Then, vector z of the measurements is defined. The measurements include the magnitude of the two PSV phasors and the line power flows, P 1 and Q 1. Assuming that synchronous phasors are available on this network, the phase angle between the bus voltages, δ 1, is now available, and the measurement vector is as shown in Equation 45:

24 δ1 ε1 V1 ε z = V + ε 3 (45) P1 ε4 Q1 ε5 The ε vector represents an assumed error between the measurement and the true value. The relationship between the measurement and the state variables is provided by a set of non-linear equations h(x) as in Equation 46 (after application of Equations 39 and 40): x1 ε x 1 x ε 3 z = h(x) + ε = x + ε x3 sin x1 3 (46) X1 ε4 x x x3 cos x1 ε5 X1 It is beyond the scope of this paper to discuss the solution (minimize ε) for this type of nonlinear set of equations. Let us just mention that one possible solution is the Weighted Least Squares technique, which, after assuming an initial state variable vector, uses the following recursive formula to repetitively compute the final result [4]: x k+ 1 = x k + k T 1 k 1 k 1 k [ H(x ) R H(x )] H(x ) R [ z h(x )] In this equation, R is the measurement diagonal covariance matrix, and H(x k ) is the measurement Jacobian matrix. Following initialization of the state variable vector, the computation uses the measured values of the phase angles as starting values. (47) SYSTEM CONSIDERATIONS Synchronously sampled event records simplify system-wide disturbance analysis. These records include system dynamic information that can be used to evaluate system conditions and compare these conditions to system models. Synchronized phasor measurement reports that include phasor information at specific instants of time allow a host computer to parse the measurements from different system locations for system-wide control and protection applications automatically. Synchronously Sampled Data Recording for System-Wide Disturbance Analysis To provide synchronously sampled event records, the multiple applications device generates a time stamp for each acquired sample. The device requires two signals from the GPS receiver: the one kilo-pulse per second (1kPPS) signal and the IRIG-B signal [5]. The 1kPPS signal is a periodic pulse train at a rate of one pulse per millisecond (1 khz), and the IRIG-B signal is a periodic pulse train at a rate of one time mark per second that includes the start of the second time value. The 1kPPS signal determines when to acquire the sample of the voltage or current signal, and the IRIG-B signal provides the time stamp for the acquired sample. The device uses the sampling clock signal (a signal with a frequency that is a multiple of the 1kPPS signal frequency) and the IRIG-B signal to generate the sample time stamp (see Figure 4). The samples and 3

25 corresponding time stamps are available from the communications ports in COMTRADE format [6]. With these multiple applications devices, we can acquire event reports at different power system locations with simultaneously acquired samples, as Figure 5 shows. We can use these synchronously sampled event records to analyze system-wide disturbances faster than if we tried to synchronize the event records manually. V or I Analog Channel Hardware LPF A/D Amplitude Generate COMTRADE Report COMTRADE via Comm. Ports Sampling Clock (ƒ S ) Time GPS RCVR 1kPPS x m Generate Time Stamp Demodulated IRIG-B Figure 4 Synchronously sampled event recording time stamping and report generation Figure 5 Synchronous sampling at different power system locations simplifies power system disturbance analysis Data Reporting for Synchronized Phasor Measurement Applications The multiple applications device reports the synchronized phasor measurement data in two ways: unsolicited binary messages at specific time intervals and solicited ASCII reports at specific instants of time. 4

26 Unsolicited Binary Messages Figure 6 shows two relays with synchronized phasor measurement capabilities at different power system locations connected to a remote host computer through communications channels. The host computer enables, disables, and accepts unsolicited binary messages from the relays. The host computer determines the data transfer rate, which depends on the communications bandwidth and the amount of data the relays transmit. The unsolicited binary message contains the following data [7]: 1. Address of the synchronized phasor measurement data. The host computer uses this address to determine the data source.. Sample number according to []. 3. Data acquisition time stamp in Second-of-Century []. 4. Power system estimated frequency. 5. Phase and positive-sequence voltages (IEEE 3-bit floating point number). 6. Phase and positive-sequence currents (IEEE 3-bit floating point number). 7. Indication that time-synchronization is OK. 8. Indication that the data packet is OK. 9. Fourteen general purpose bits. 10. CRC-16 error detection code to validate the message. 5

27 Satellite GPS RCVR Host Computer GPS RCVR Relay 1 Relay TX/RX TX/RX TX/RX TX/RX A B Figure 6 Relay and host computer connections for synchronized phasor measurement applications 6

28 The host computer parses the received data from the different network relays according to the time stamp and sample number of the data packet. Solicited ASCII Messages The relays respond to the METER PM TIME command by reporting synchronized phasor measurement at specific times. We can use this command to take snapshots of the phasor at specific times across the power system. Figure 7 shows a sample report. =>>MET PM 6:05 Synchronized Phasor Measurement Data Will be Displayed at 6:05: =>> Relay 1 Date: 01/01/00 Time: 06:05: Station A Serial Number: Synchrophasors Phase Currents Phase Voltages IA IB IC VA VB VC MAG (A/kV) ANG (DEG) Pos. Sequence Current (A) Pos. Sequence Voltage (kv) I1 V1 MAG ANG (DEG) FREQ (Hz) PSV57 PSV58 PSV59 PSV60 PSV61 PSV6 PSV63 PSV =>> Figure 7 Solicited ASCII synchronized phasor measurement report SOURCES OF ERRORS IN PHASOR ESTIMATION Synchronized phasor measurement applications such as state estimation and out-of-step relaying require phasor estimation errors on the order of tenths of a degree [9]. Typical sources of these errors include GPS transmitters and receivers, instrument transformers, and phasor estimation devices. We can divide errors from these sources into two categories: time synchronization errors and data acquisition errors. GPS transmitters, GPS receivers, and phasor estimation devices determine time synchronization errors; instrument transformers and phasor estimation devices determine data acquisition errors. Table 1 summarizes these errors and includes typical corresponding values that we must consider in these applications. Table 1 Errors in Synchronized Phasor Estimation and Typical Corresponding Values Error Cause Error in Degrees Error in µs Time Synchronization ± ± 1 Instrument Transformers (Class 0.3) [8] ± 0.3 ± 14 Phasor Estimation Device ± 0.1 ± 5 7

29 We can see from Table 1 that instrument transformers are the main contributors to synchronized phasor estimation error. In the near future, we will see technological advances that will minimize these errors. CONCLUSIONS 1. Phasors were introduced to transform differential equations, modeling electrical circuits, into common algebraic equations and speed up the solution in steady state.. Digital fault recorders acquire data at fixed time intervals. These data retain power system frequency information during off-nominal frequency system operations that can occur during system disturbances. 3. Synchronized phasor measurement devices require an absolute time reference for power system-wide applications. Traditionally, this capability is part of a dedicated device for these applications. These devices are not suitable for protection applications such as line distance protection. 4. The 1kPPS signal provides an absolute time reference for fixed frequency sampling. In synchronized phasor measurement applications, all network waveforms are compared to a time-based phase reference. 5. Phasor calculations using DFT introduce errors when the power system operates at offnominal frequency. These calculation errors may cause distance element misoperations. 6. Traditionally, numerical relays for line distance protection applications sample voltage and current signals at multiples of the operating power system frequency (f SYS ) to minimize phasor calculation errors. 7. Data-acquisition systems that acquire data at fixed time intervals and use adaptive filtering minimize phasor calculation errors, but these systems do not sample with a system-wide time reference. 8. A method to acquire and process voltage and current signals for applications such as fault recording, synchronized phasor measurement, and line distance protection samples the signals at fixed time intervals with respect to an absolute time reference and resamples these signals at multiples of power system operating frequency. A simple digital band-pass filter with fixed coefficients provides filtering for the resampled data. Synchronized phasor measurement uses the sampled data with the absolute time reference. Distance protection uses filtered resampled data that minimize phasor calculation errors. 9. In a variation of the approach in Conclusion 8, sampling is based on the local clock. Resampling uses the absolute time reference from the GPS receiver and the system operating frequency to resample the data at a specific frequency depending on the application requirements. 10. Decoupling the magnitude and phase angle measurement provides for an accurate phasor magnitude over a broad frequency interval. 11. Careful calculation of real-time phasors achieves viable accuracy, even in transient states. 1. The multiple-applications device uses unsolicited binary messages and solicited ASCII messages to report synchronized phasor measurement data. 8

Protective Relay Synchrophasor Measurements During Fault Conditions

Protective Relay Synchrophasor Measurements During Fault Conditions Protective Relay Synchrophasor Measurements During Fault Conditions Armando Guzmán, Satish Samineni, and Mike Bryson Schweitzer Engineering Laboratories, Inc. Published in SEL Journal of Reliable Power,

More information

Engineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location

Engineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location Engineering Thesis The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location By Yushi Jiao Presented to the school of Engineering and

More information

PRECISE SYNCHRONIZATION OF PHASOR MEASUREMENTS IN ELECTRIC POWER SYSTEMS

PRECISE SYNCHRONIZATION OF PHASOR MEASUREMENTS IN ELECTRIC POWER SYSTEMS PRECSE SYNCHRONZATON OF PHASOR MEASUREMENTS N ELECTRC POWER SYSTEMS Dr. A.G. Phadke Virginia Polytechnic nstitute and State University Blacksburg, Virginia 240614111. U.S.A. Abstract Phasors representing

More information

SYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES. A.G. Phadke

SYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES. A.G. Phadke SYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES A.G. Phadke Lecture outline: Evolution of PMUs Standards Development of Phasor Measurement Units Phasor Estimation Off-nominal frequency phasors Comtrade Synchrophasor

More information

Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System

Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System Ms.Darsana M. Nair Mr. Rishi Menon Mr. Aby Joseph PG Scholar Assistant Professor Principal Engineer Dept. of EEE Dept. of

More information

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by

More information

Chapter 10: Compensation of Power Transmission Systems

Chapter 10: Compensation of Power Transmission Systems Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome

More information

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)

More information

A Real-Time Platform for Teaching Power System Control Design

A Real-Time Platform for Teaching Power System Control Design A Real-Time Platform for Teaching Power System Control Design G. Jackson, U.D. Annakkage, A. M. Gole, D. Lowe, and M.P. McShane Abstract This paper describes the development of a real-time digital simulation

More information

CHAPTER 9. Sinusoidal Steady-State Analysis

CHAPTER 9. Sinusoidal Steady-State Analysis CHAPTER 9 Sinusoidal Steady-State Analysis 9.1 The Sinusoidal Source A sinusoidal voltage source (independent or dependent) produces a voltage that varies sinusoidally with time. A sinusoidal current source

More information

ANALYTICAL AND SIMULATION RESULTS

ANALYTICAL AND SIMULATION RESULTS 6 ANALYTICAL AND SIMULATION RESULTS 6.1 Small-Signal Response Without Supplementary Control As discussed in Section 5.6, the complete A-matrix equations containing all of the singlegenerator terms and

More information

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC) International Journal of Scientific and Research Publications, Volume 2, Issue 5, May 2012 1 Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC) K. Manoz

More information

Synchrophasors: Definition, Measurement, and Application

Synchrophasors: Definition, Measurement, and Application 1. Abstract Synchrophasors: Definition, Measurement, and Application Mark Adamiak GE Multilin King of Prussia, PA William Premerlani GE Global Research Niskayuna, NY Dr. Bogdan Kasztenny GE Multilin Markham,

More information

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC) Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC) K. Manoz Kumar Reddy (Associate professor, Electrical and Electronics Department, Sriaditya Engineering College, India)

More information

Real-time Math Function of DL850 ScopeCorder

Real-time Math Function of DL850 ScopeCorder Real-time Math Function of DL850 ScopeCorder Etsurou Nakayama *1 Chiaki Yamamoto *1 In recent years, energy-saving instruments including inverters have been actively developed. Researchers in R&D sections

More information

Phasor. Phasor Diagram of a Sinusoidal Waveform

Phasor. Phasor Diagram of a Sinusoidal Waveform Phasor A phasor is a vector that has an arrow head at one end which signifies partly the maximum value of the vector quantity ( V or I ) and partly the end of the vector that rotates. Generally, vectors

More information

MANY protective relaying functions use the phasors

MANY protective relaying functions use the phasors 1 Phasor Estimation Using a Modified Sine Filter Combined with an Adaptive Mimic Filter Kleber M. Silva and Bernard F. Küsel Abstract This paper presents a phasor estimation algorithm, which combines a

More information

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit

Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit Electrical Power and Energy Conference 2012 Resilient Green Energy Systems for a Sustainable Society Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit Dinesh

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

Chapter 2 Analog-to-Digital Conversion...

Chapter 2 Analog-to-Digital Conversion... Chapter... 5 This chapter examines general considerations for analog-to-digital converter (ADC) measurements. Discussed are the four basic ADC types, providing a general description of each while comparing

More information

A New Approach to Current Differential Protection for Transmission Lines

A New Approach to Current Differential Protection for Transmission Lines A New Approach to Current Differential Protection for Transmission Lines CURRENT DIFFERENTIAL MODEL Normal Condition: I 1 + I 2 = I C - the line charging current Fault Condition: I 1 + I 2 = I C Can be

More information

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh** *,**(Department of Electrical Engineering, Walchand College of

More information

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS INDO-US Workshop October 2009, I.I.T. Kanpur INTRODUCTION Electric Power Systems are very large, spread over a wide geographical area

More information

Chapter 2 MODELING AND CONTROL OF PEBB BASED SYSTEMS

Chapter 2 MODELING AND CONTROL OF PEBB BASED SYSTEMS Chapter 2 MODELING AND CONTROL OF PEBB BASED SYSTEMS 2.1 Introduction The PEBBs are fundamental building cells, integrating state-of-the-art techniques for large scale power electronics systems. Conventional

More information

Dynamic Phasors for Small Signal Stability Analysis

Dynamic Phasors for Small Signal Stability Analysis for Small Signal Stability Analysis Chandana Karawita (Transgrid Solutions) for Small Signal Stability Analysis Outline Introduction 1 Introduction Simulation and Analysis Techniques Typical Outputs Modelling

More information

ELEC3242 Communications Engineering Laboratory Frequency Shift Keying (FSK)

ELEC3242 Communications Engineering Laboratory Frequency Shift Keying (FSK) ELEC3242 Communications Engineering Laboratory 1 ---- Frequency Shift Keying (FSK) 1) Frequency Shift Keying Objectives To appreciate the principle of frequency shift keying and its relationship to analogue

More information

Wide-Area Measurements to Improve System Models and System Operation

Wide-Area Measurements to Improve System Models and System Operation Wide-Area Measurements to Improve System Models and System Operation G. Zweigle, R. Moxley, B. Flerchinger, and J. Needs Schweitzer Engineering Laboratories, Inc. Presented at the 11th International Conference

More information

Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying

Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying V.S.Kale S.R.Bhide P.P.Bedekar Department of Electrical Engineering, VNIT Nagpur, India Abstract

More information

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

Comparative Testing of Synchronized Phasor Measurement Units

Comparative Testing of Synchronized Phasor Measurement Units Comparative Testing of Synchronized Phasor Measurement Units Juancarlo Depablos Student Member, IEEE Virginia Tech Virgilio Centeno Member, IEEE Virginia Tech Arun G. Phadke Life Fellow, IEEE Virginia

More information

Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator

Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator Dinesh Rangana Gurusinghe, Dean Ouellette, and Athula D. Rajapakse Abstract-- Many commercial phasor measurement units (PMUs

More information

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1 Module 5 DC to AC Converters Version 2 EE IIT, Kharagpur 1 Lesson 37 Sine PWM and its Realization Version 2 EE IIT, Kharagpur 2 After completion of this lesson, the reader shall be able to: 1. Explain

More information

Module 1: Introduction to Experimental Techniques Lecture 2: Sources of error. The Lecture Contains: Sources of Error in Measurement

Module 1: Introduction to Experimental Techniques Lecture 2: Sources of error. The Lecture Contains: Sources of Error in Measurement The Lecture Contains: Sources of Error in Measurement Signal-To-Noise Ratio Analog-to-Digital Conversion of Measurement Data A/D Conversion Digitalization Errors due to A/D Conversion file:///g /optical_measurement/lecture2/2_1.htm[5/7/2012

More information

Bakiss Hiyana binti Abu Bakar JKE, POLISAS BHAB

Bakiss Hiyana binti Abu Bakar JKE, POLISAS BHAB 1 Bakiss Hiyana binti Abu Bakar JKE, POLISAS 1. Explain AC circuit concept and their analysis using AC circuit law. 2. Apply the knowledge of AC circuit in solving problem related to AC electrical circuit.

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems

More information

Active Vibration Isolation of an Unbalanced Machine Tool Spindle

Active Vibration Isolation of an Unbalanced Machine Tool Spindle Active Vibration Isolation of an Unbalanced Machine Tool Spindle David. J. Hopkins, Paul Geraghty Lawrence Livermore National Laboratory 7000 East Ave, MS/L-792, Livermore, CA. 94550 Abstract Proper configurations

More information

State Estimation Advancements Enabled by Synchrophasor Technology

State Estimation Advancements Enabled by Synchrophasor Technology State Estimation Advancements Enabled by Synchrophasor Technology Contents Executive Summary... 2 State Estimation... 2 Legacy State Estimation Biases... 3 Synchrophasor Technology Enabling Enhanced State

More information

ELEMENTS OF FACTS CONTROLLERS

ELEMENTS OF FACTS CONTROLLERS 1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are

More information

Generator Operation with Speed and Voltage Regulation

Generator Operation with Speed and Voltage Regulation Exercise 3 Generator Operation with Speed and Voltage Regulation EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the speed governor and automatic voltage regulator used

More information

HISTORY: How we got to where we are. March 2015 Roy Boyer 1

HISTORY: How we got to where we are. March 2015 Roy Boyer 1 HISTORY: How we got to where we are March 2015 Roy Boyer 1 Traditional Stability Analysis: 1. Maintain synchronism of synchronous machines 2. Simplifying assumptions: 1. Balanced positive sequence system

More information

IGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004

IGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004 IGEE 40 Power System Analysis FINAL EXAMINATION Fall 004 Special instructions: - Duration: 150 minutes. - Material allowed: a crib sheet (double sided 8.5 x 11), calculator. - Attempt 4 out of 7 questions.

More information

PAPER-II (Subjective)

PAPER-II (Subjective) PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use

More information

ELE636 Communication Systems

ELE636 Communication Systems ELE636 Communication Systems Chapter 5 : Angle (Exponential) Modulation 1 Phase-locked Loop (PLL) The PLL can be used to track the phase and the frequency of the carrier component of an incoming signal.

More information

Transient Stability in Low Frequency Railways with Mixed Electronic and Rotational Generation

Transient Stability in Low Frequency Railways with Mixed Electronic and Rotational Generation LICENTIATE T H E SIS Transient Stability in Low Frequency Railways with Mixed Electronic and Rotational Generation John Laury Electric Power Engineering Transient Stability in Low Frequency Railways with

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

Application Of Power System Stabilizer At Serir Power Plant

Application Of Power System Stabilizer At Serir Power Plant Vol. 3 Issue 4, April - 27 Application Of Power System Stabilizer At Serir Power Plant *T. Hussein, **A. Shameh Electrical and Electronics Dept University of Benghazi Benghazi- Libya *Tawfiq.elmenfy@uob.edu.ly

More information

Investigation of D-Statcom Operation in Electric Distribution System

Investigation of D-Statcom Operation in Electric Distribution System J. Basic. Appl. Sci. Res., (2)29-297, 2 2, TextRoad Publication ISSN 29-434 Journal of Basic and Applied Scientific Research www.textroad.com Investigation of D-Statcom Operation in Electric Distribution

More information

MEM01: DC-Motor Servomechanism

MEM01: DC-Motor Servomechanism MEM01: DC-Motor Servomechanism Interdisciplinary Automatic Controls Laboratory - ME/ECE/CHE 389 February 5, 2016 Contents 1 Introduction and Goals 1 2 Description 2 3 Modeling 2 4 Lab Objective 5 5 Model

More information

Laboratory Investigation of Variable Speed Control of Synchronous Generator With a Boost Converter for Wind Turbine Applications

Laboratory Investigation of Variable Speed Control of Synchronous Generator With a Boost Converter for Wind Turbine Applications Laboratory Investigation of Variable Speed Control of Synchronous Generator With a Boost Converter for Wind Turbine Applications Ranjan Sharma Technical University of Denmark ransharma@gmail.com Tonny

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

Experiment 7: Frequency Modulation and Phase Locked Loops

Experiment 7: Frequency Modulation and Phase Locked Loops Experiment 7: Frequency Modulation and Phase Locked Loops Frequency Modulation Background Normally, we consider a voltage wave form with a fixed frequency of the form v(t) = V sin( ct + ), (1) where c

More information

Chapter 2 Shunt Active Power Filter

Chapter 2 Shunt Active Power Filter Chapter 2 Shunt Active Power Filter In the recent years of development the requirement of harmonic and reactive power has developed, causing power quality problems. Many power electronic converters are

More information

UNIT-4 POWER QUALITY MONITORING

UNIT-4 POWER QUALITY MONITORING UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and

More information

Implementation and Performance of Synchrophasor Function within Microprocessor Based Relays

Implementation and Performance of Synchrophasor Function within Microprocessor Based Relays Implementation and Performance of Synchrophasor Function within Microprocessor Based Relays Bogdan Kasztenny GE Multilin Mark Adamiak GE Multilin 1. Introduction Synchronized phasor measurements have come

More information

A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor. S.H.Haggag, Ali M. El-Rifaie,and Hala M.

A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor. S.H.Haggag, Ali M. El-Rifaie,and Hala M. Proceedings of the World Congress on Engineering 013 Vol II,, July 3-5, 013, London, U.K. A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor S.H.Haggag, Ali M. El-Rifaie,and

More information

Contingency Analysis using Synchrophasor Measurements

Contingency Analysis using Synchrophasor Measurements Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 1), Cairo University, Egypt, December 19-21, 21, Paper ID 219. Contingency Analysis using Synchrophasor Measurements

More information

Circuit Analysis-II. Circuit Analysis-II Lecture # 2 Wednesday 28 th Mar, 18

Circuit Analysis-II. Circuit Analysis-II Lecture # 2 Wednesday 28 th Mar, 18 Circuit Analysis-II Angular Measurement Angular Measurement of a Sine Wave ü As we already know that a sinusoidal voltage can be produced by an ac generator. ü As the windings on the rotor of the ac generator

More information

Synchrophasors and the Smarter Grid

Synchrophasors and the Smarter Grid Synchrophasors and the Smarter Grid Synchrophasor A synchrophasor is a phasor measurement with respect to an absolute time reference. With this measurement we can determine the absolute phase relationship

More information

In Class Examples (ICE)

In Class Examples (ICE) In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6

More information

Sinusoids and Phasors (Chapter 9 - Lecture #1) Dr. Shahrel A. Suandi Room 2.20, PPKEE

Sinusoids and Phasors (Chapter 9 - Lecture #1) Dr. Shahrel A. Suandi Room 2.20, PPKEE Sinusoids and Phasors (Chapter 9 - Lecture #1) Dr. Shahrel A. Suandi Room 2.20, PPKEE Email:shahrel@eng.usm.my 1 Outline of Chapter 9 Introduction Sinusoids Phasors Phasor Relationships for Circuit Elements

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM 3.1 INTRODUCTION Static synchronous compensator is a shunt connected reactive power compensation device that is capable of generating or

More information

Address for Correspondence

Address for Correspondence Research Paper COMPENSATION BY TCSC IN OPEN LOOP CONTROL SYSTEM 1* Sunita Tiwari, S.P. Shukla Address for Correspondence 1* Sr. Lecturer, Polytechnic,Durg Professor, Bhilai Institute of Technology, Durg

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Volume I Issue VI 2012 September-2012 ISSN

Volume I Issue VI 2012 September-2012 ISSN A 24-pulse STATCOM Simulation model to improve voltage sag due to starting of 1 HP Induction-Motor Mr. Ajay Kumar Bansal 1 Mr. Govind Lal Suthar 2 Mr. Rohan Sharma 3 1 Associate Professor, Department of

More information

Fourier Signal Analysis

Fourier Signal Analysis Part 1B Experimental Engineering Integrated Coursework Location: Baker Building South Wing Mechanics Lab Experiment A4 Signal Processing Fourier Signal Analysis Please bring the lab sheet from 1A experiment

More information

Signals A Preliminary Discussion EE442 Analog & Digital Communication Systems Lecture 2

Signals A Preliminary Discussion EE442 Analog & Digital Communication Systems Lecture 2 Signals A Preliminary Discussion EE442 Analog & Digital Communication Systems Lecture 2 The Fourier transform of single pulse is the sinc function. EE 442 Signal Preliminaries 1 Communication Systems and

More information

EE 742 Chapter 9: Frequency Stability and Control. Fall 2011

EE 742 Chapter 9: Frequency Stability and Control. Fall 2011 EE 742 Chapter 9: Frequency Stability and Control Fall 2011 Meeting demand with generation Large and slow changes (24 hr) in power demand are met by unit commitment Medium and relatively fast changes (30

More information

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY Department of Electrical Engineering Senior Design Project ELEC 499 DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY Student Names: Chresteen Baraket Marina Messiha Supervised

More information

EE-4022 Experiment 3 Frequency Modulation (FM)

EE-4022 Experiment 3 Frequency Modulation (FM) EE-4022 MILWAUKEE SCHOOL OF ENGINEERING 2015 Page 3-1 Student Objectives: EE-4022 Experiment 3 Frequency Modulation (FM) In this experiment the student will use laboratory modules including a Voltage-Controlled

More information

B.Tech II Year II Semester (R13) Supplementary Examinations May/June 2017 ANALOG COMMUNICATION SYSTEMS (Electronics and Communication Engineering)

B.Tech II Year II Semester (R13) Supplementary Examinations May/June 2017 ANALOG COMMUNICATION SYSTEMS (Electronics and Communication Engineering) Code: 13A04404 R13 B.Tech II Year II Semester (R13) Supplementary Examinations May/June 2017 ANALOG COMMUNICATION SYSTEMS (Electronics and Communication Engineering) Time: 3 hours Max. Marks: 70 PART A

More information

A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors

A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors Dinesh Rangana Gurusinghe Yaojie Cai Athula D. Rajapakse International Synchrophasor Symposium March 25,

More information

Testing Power Sources for Stability

Testing Power Sources for Stability Keywords Venable, frequency response analyzer, oscillator, power source, stability testing, feedback loop, error amplifier compensation, impedance, output voltage, transfer function, gain crossover, bode

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

UNDERSTANDING SUB-HARMONICS

UNDERSTANDING SUB-HARMONICS UNDERSTANDING SUB-HARMONICS Joe Perez, P.E., SynchroGrid, College Station, TX 77845, jperez@synchrogrid.com Introduction: Over the years, engineers have employed fundamental principles of electrical engineering

More information

METHODS TO IMPROVE DYNAMIC RESPONSE OF POWER FACTOR PREREGULATORS: AN OVERVIEW

METHODS TO IMPROVE DYNAMIC RESPONSE OF POWER FACTOR PREREGULATORS: AN OVERVIEW METHODS TO IMPROE DYNAMIC RESPONSE OF POWER FACTOR PREREGULATORS: AN OERIEW G. Spiazzi*, P. Mattavelli**, L. Rossetto** *Dept. of Electronics and Informatics, **Dept. of Electrical Engineering University

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Using a Multiple Analog Input Distance Relay as a DFR

Using a Multiple Analog Input Distance Relay as a DFR Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at

More information

Lab S-3: Beamforming with Phasors. N r k. is the time shift applied to r k

Lab S-3: Beamforming with Phasors. N r k. is the time shift applied to r k DSP First, 2e Signal Processing First Lab S-3: Beamforming with Phasors Pre-Lab: Read the Pre-Lab and do all the exercises in the Pre-Lab section prior to attending lab. Verification: The Exercise section

More information

Latest Control Technology in Inverters and Servo Systems

Latest Control Technology in Inverters and Servo Systems Latest Control Technology in Inverters and Servo Systems Takao Yanase Hidetoshi Umida Takashi Aihara. Introduction Inverters and servo systems have achieved small size and high performance through the

More information

Current Rebuilding Concept Applied to Boost CCM for PF Correction

Current Rebuilding Concept Applied to Boost CCM for PF Correction Current Rebuilding Concept Applied to Boost CCM for PF Correction Sindhu.K.S 1, B. Devi Vighneshwari 2 1, 2 Department of Electrical & Electronics Engineering, The Oxford College of Engineering, Bangalore-560068,

More information

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78) Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,

More information

Fundamentals of Servo Motion Control

Fundamentals of Servo Motion Control Fundamentals of Servo Motion Control The fundamental concepts of servo motion control have not changed significantly in the last 50 years. The basic reasons for using servo systems in contrast to open

More information

DC and AC Circuits. Objective. Theory. 1. Direct Current (DC) R-C Circuit

DC and AC Circuits. Objective. Theory. 1. Direct Current (DC) R-C Circuit [International Campus Lab] Objective Determine the behavior of resistors, capacitors, and inductors in DC and AC circuits. Theory ----------------------------- Reference -------------------------- Young

More information

MATHEMATICAL MODELING OF POWER TRANSFORMERS

MATHEMATICAL MODELING OF POWER TRANSFORMERS MATHEMATICAL MODELING OF POWER TRANSFORMERS Mostafa S. NOAH Adel A. SHALTOUT Shaker Consultancy Group, Cairo University, Egypt Cairo, +545, mostafanoah88@gmail.com Abstract Single-phase and three-phase

More information

10. Introduction and Chapter Objectives

10. Introduction and Chapter Objectives Real Analog - Circuits Chapter 0: Steady-state Sinusoidal Analysis 0. Introduction and Chapter Objectives We will now study dynamic systems which are subjected to sinusoidal forcing functions. Previously,

More information

BSNL TTA Question Paper Control Systems Specialization 2007

BSNL TTA Question Paper Control Systems Specialization 2007 BSNL TTA Question Paper Control Systems Specialization 2007 1. An open loop control system has its (a) control action independent of the output or desired quantity (b) controlling action, depending upon

More information

CHAPTER 2 PID CONTROLLER BASED CLOSED LOOP CONTROL OF DC DRIVE

CHAPTER 2 PID CONTROLLER BASED CLOSED LOOP CONTROL OF DC DRIVE 23 CHAPTER 2 PID CONTROLLER BASED CLOSED LOOP CONTROL OF DC DRIVE 2.1 PID CONTROLLER A proportional Integral Derivative controller (PID controller) find its application in industrial control system. It

More information

TRANSIENT STABILITY ENHANCEMENT OF POWER SYSTEM USING INTELLIGENT TECHNIQUE

TRANSIENT STABILITY ENHANCEMENT OF POWER SYSTEM USING INTELLIGENT TECHNIQUE TRANSIENT STABILITY ENHANCEMENT OF POWER SYSTEM USING INTELLIGENT TECHNIQUE K.Satyanarayana 1, Saheb Hussain MD 2, B.K.V.Prasad 3 1 Ph.D Scholar, EEE Department, Vignan University (A.P), India, ksatya.eee@gmail.com

More information

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1 Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load MADHYAMA V. WANKHEDE Department Of Electrical Engineering G. H. Raisoni College of

More information

DSP First. Laboratory Exercise #2. Introduction to Complex Exponentials

DSP First. Laboratory Exercise #2. Introduction to Complex Exponentials DSP First Laboratory Exercise #2 Introduction to Complex Exponentials The goal of this laboratory is gain familiarity with complex numbers and their use in representing sinusoidal signals as complex exponentials.

More information

THE SINUSOIDAL WAVEFORM

THE SINUSOIDAL WAVEFORM Chapter 11 THE SINUSOIDAL WAVEFORM The sinusoidal waveform or sine wave is the fundamental type of alternating current (ac) and alternating voltage. It is also referred to as a sinusoidal wave or, simply,

More information

DOUBLE-ENDED FAULT LOCATORS

DOUBLE-ENDED FAULT LOCATORS The InterNational Electrical Testing Association Journal FEATURE END-TO-END TESTING OF DOUBLE-ENDED FAULT LOCATORS BY STEVE TURNER, Beckwith Electric Company, Inc.. www.netaworld.org FOR HIGH VOLTAGE,

More information

MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS

MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS 1 MADHAVI G, 2 A MUNISANKAR, 3 T DEVARAJU 1,2,3 Dept. of EEE, Sree Vidyanikethan Engineering College,

More information