POWER SYSTEM BACKUP PROTECTION USING SYNCHRONIZED PMU
|
|
- Lambert Gardner
- 5 years ago
- Views:
Transcription
1 POWER SYSTEM BACKUP PROTECTION USING SYNCHRONIZED PMU LAVUDYA JAYASREE 1 and GAIRABOINA NAGARAJU 2 1,2 Dept. of Electrical And Electronics, Engineering, Christu Jyothi Institute of Technology And Science,Yeshwanthapur, Jangaon, T.S Abstract- Calamity failures in power grid due to mal-function of traditional backup protection system was one of the main causes of unwanted cataract trips. The new technique based on synchronized PMU with fast communication network and GPS system for time transfer have a dynamic adaptation for back-up protection of power system. The goal of the protection scheme is to estimate a new wide area backup protection system to maintain the power system stable by isolating only faulty components from the healthy part of system. The purpose is to boost the overall effectiveness and consistency of the power structure for all power stages via significant dependence on WAPS as distributed intelligence agents with improved monitoring, control and protection capabilities of power network. Introducing the fastest and of course best technique for WAPS as synchronized Phasor measurement unit (PMU).This paper speculates recognition of fault site and protection of power system using PMU also clearance of fault. The protection scheme which is used in this paper depends on the concept of equating positive sequence quantities such as voltage and current angles for every lines connected to the bus to recognize and classify the faulted line. This paper emphasize simulation on 220 KV system by using MATLAB Simulink. Keywords-Phasor Measurement Unit,Backup Protection, Time Synchronization, Global Positioning System. I. INTRODUCTION Nowadays, power systems become very tough and challenging to manage due to fast development to satisfy enormous boost in load demands which leads the power system arrangement to become more complex. So, Electrical networks with adequate power quality and high reliability are preferred. With this admiration, new technologies suchlike smart grids has introduced a new standard for control, protection and monitoring system to improve reliability of electricity, safety of grids,decrease the unwanted blackouts, rapid response to interpretation in the electrical network, spotting of fault and recovery of electrical system as fast as possible. Wide area control, monitoring and protection system is the modern technique for management of electrical system [1].In electrical power system, the different fault occurs which results collapses of the electrical system [2].Collapse of power structure take place due to simple fault, load violation, power fluctuations and islanding. Lots of techniques are used in the power network for safety of transmission line. Distance protection is one of broadly used techniques, as in that protection the distance relay is used for protection purpose. The distance relays are depend on the standalone assessment and each relay operate autonomously corresponding to different region of protection.the distance relay is operating for fault taking place in between the connected relay position and the preferred position [3].Mal-operation of third zone distance protection in conditions such as power sway, voltage volatility and load encroachment may increase to wide area blackouts [4].In July 30th and 31st, 2012 two severe blackouts occurred in India. Here, new technique is provided for protection of wide area using synchronous PMU. This technique is depend on by comparing and equating positive sequence voltage magnitudes for specified areas and positive sequence current phase angles for every coupled lines between the two areas of the system network. The time synchronized phasor measurement technique is used, which gives a view of the dynamic power system and capable for controlling and monitoring of wide area protection. By using a fast GPS and modern conveyed system. DOI: /IJMTER HIIVJ 158
2 II. THE THIRD ZONE MAL-FUNCTION Usually, for the transmission lines the most important protection is done by first and second zones, while the protection done in third zone is recognized as the backup protection. About 80 to 85 percent part of the line without any time delay is covered by the first zone. First zone can be known as the chief protection. Second zone covers the whole length of the line plus 25 to 50percent of the succeeding shortest line and operation time is put about 0.25 to 0.4 seconds. The entire region confined by the both zones plus 25percent of the succeeding long line (third line) is covered by the third zone and for that the delay time is put among 0.6 to 1.5 seconds. The third zone is worked for backup protection. This structure is in general used to defend each line separately. The amplitude and the phase angle of quantities like voltage and current fluctuate, in this third zone, which is the reason of malfunction. Distance protection relays are ready with power sway recognition modules [4]. The very significant obsession in the power network is the need of reactive power and that is main reason of voltage volatility [5].The third zone relay which having a maximum area of protection as backup protection is the reason of Mal function of distance relay in provisions of voltage volatility [6]. When the dynamic load tries beyond the capacity of transmission network line or generation to be used that is most horrible instance of occurring the voltage instability [7]. The various number of methods are used for fault detection from voltage instability are presented. Voltage changes are not always reactive, as step- voltage increase due to switching of capacitors or load shedding.when the network is faulty, derived of voltage close to the voltage collapse is huge and negative. III. CONCEPT OF PMU The device named as PMU is worked to collect and provide instant phasor from desire areas of applications attracted with instantaneous day and time of the measuring called stamped data. Estimated phasor are called as synchro-phasors, here synchronized measurement technique plays very important roles, especially in backup protection. But to send information of PMU from distant parts of the network to main control system is consociated with delay of frequent tens of milliseconds. So it is not enough to use WAPS using PMU for main protection system. PMU measures positive sequence currents and voltages with accurate and exact time synchronization. The measurements are done by using GPS single pulse per second Synchrophasors, provide the phasor demonstration of voltage or current to complete time reference. This absolute reference is given in the form of a common timing signal by using high -accuracy clocks synchronized to corresponding universal time such as the universally used global positioning system (GPS).The synchronized clocks are used as a reference,so PMU creates the complex number of a constant sinusoidal signal phasor representation as presented in Fig. 1. The connection between the reporting moment and the phasor representation is that, the phase angle is equal to the angular division between the reporting peak and the period of the sinusoid. Though, if all PMUs works on the same timing reference, their measurements are comparable, and the differences among the phase angle of phasors are correct. As most applications look for to identify the differences between the phase angles of variety of phasors, the output of PMU provides a valuable input to monitoring, protection, and control operation in a power system. Figure -1 Phasor representation (a) Sinusoidal waveform (b) Phasor All rights Reserved 159
3 The synchronized phasor of ac signal is given as the complex quantities as below, x(t) = xr + jxi = ( xm / 2) e jø (1) = xm / 2 (Cos ø + j Sin ø ) (2) Where, xm = amplitude of synchronized vector, phase angle is denoted by ø and xi and xr are imaginary and real components of complex value. The general method for phasors calculation by using sample data is discrete Fourier transform. The high speed communications links used for WAPS are Fiber optic, microwave, PLC, Twisted pair. IV. THE PROJECTED TECHNIQUE The main purpose is to improve the interruption monitoring and system event analysis. Synchronous phasor measurements gives all revelatory state measurements that are phase angle, frequency and voltage magnitude. PMU is used to evaluate bus voltages and all revealing line currents next these measurements are given to PDC at control centre. The technique is WAPS which is accepted to find abnormal or faulty condition and to isolate the faulty area from the overall system. Two components are very important to distinguish the faults on transmission line. One is the drop of voltage and other is due to fault occurrence the change in flow of power direction. The fault current way to be able to resolve by using phase angle through reference to a base quantity. Direction of fault to be able to find out by with the assist of comparing the transmission line phase angle of current and voltage. The PMU, block diagram is as in Fig. 2 below. Figure -2 The block diagram of PMU The analog to digital converter, converts the analog signal from current and potential transformer to digital signal and passed through low pass filter. The GPS receiver detects the single pulse for each second synchronizing signal from GPS satellite. From these data the positive sequence quantities such as voltage and current are calculated. The voltage is viewed as reference polarizing quantity. The fault current Phasor lies inside forward and backward areas with reference to the reference phasor, corresponding to the fault situation [8,9]. Flow of Power in given direction is the effect of phase angle among voltage and current varying around its power factor angle while the power direction the current phase angle, with travels in opposite direction, reference to voltage will be[8]. At the main[8]. At the main place and current angles with supreme differences are measured for organized line with this affected region. By equating this angles with one another, the most value of complete difference is measured as faulted line. This process can be expressed mathematically as follows: Min { 1, 2 m n } (3) The positive sequence voltage magnitude is calculated by PMU for area 1, 2, 3, m, to n. When the fault take place on the network the output of positive sequence voltage magnitude becomes minimum. From this calculation the nearest faulted area can be determined. In this case this area is shown by m. Next there is need of comparing the accurate differences of current angles All rights Reserved 160
4 positive sequence of interrelated lines associated with this area m which is faulted with the interrelated close to area and then by selecting maximum one. This can be expressed as, Max { m1, m2, m3,. mn } (4) Where, m and n are the organized part which shows the positive sequence current angle difference for the transmission network. This can be specified as follows, mn = mn- nm (5) V. SIMULATION AND RESULTS As presented in fig. 3 the five bus network is employed for case study. The interconnected network is taken of 220 KV, 100 km transmission line, one side is connected with generating station and other with load through interconnected lines. Matlab Simulink software is applied to simulate various faults and investigations. As discussed in the paper, lack of a proper technique for the solution of Mal operation in the third zone on 230 KV lines and above [10]. In this way in paper, the projected technique is tested. As displayed in fig 4 the simulation is performed by using the MATLAB Simulink software for five bus test system. The standards given are in per unit at 50Hz on 100MVA base [11]. Figure -3 The five bus system network taken for study The values for system are given in per unit on 100 MVA (base ) in table no.1 Table- 1 The transmission line parameters. 1 Generator MVA,220Kv,50Hz,Synchronous generator pu model 2 Transformer 220 KV/13.8 KV,100 MVA 100 Synchronous KV,100 MVA machine 4 LOAD Kv,50MW,24Mvar,RL load 5 LOAD Kv,100MW,48Mvar,RL load 6 LOAD Kv,80MW,38Mvar,RL All rights Reserved 161
5 7 LOAD Kv,120MW,58Mvar,RL load 8 LOAD Kv,150MW,RL load When different fault appeared on the given transmission line, the faulted signals can be recognized from results. Similarly, various fault situation are simulated on the system using the proposed technique. Type of Fault can be detected and observed by using Fault Analysis Block given in fig. 6 for three phase to Ground Fault but same can be obtained for single line to ground fault and double line to ground fault. Figure- 4 SIMULINK model of 5 Bus 220 kv system Figure -5 MATLAB/Simulink block diagram responsible of the selection of the type of fault & its clearance. Figure- 6 Fault analysis block for three phase to Ground Fault Figure All rights Reserved 162
6 Figure -8 Three phase current signals for entire lines connected to the fault affected area (i.e. area 2). The fault is situated on line 1 connecting area 1 and area 2. When fault occurs, line connected between area 1 and area 2 is exaggerated. Fig. 7displays the output of three phase to ground voltage, whereas fig. 8 shows output of three phase current of the lines linked to faulted part. As well, different fault conditions are simulated on the system with projected procedure Figure -9 Positive sequence voltage magnitudes five different areas during fault on the network Fig. 9 shows the output from the five PMUs, the graph shows the five positive sequence voltage magnitudes (PSVM) for five different areas during fault. The minimum value is selected which is showing the nearest area to the fault (area 2 ). Fig. 10 shows the perfect difference of all positive sequence current angles (PSCA) for every lines interconnected with the faulted region (area 2) with the other adjacent areas (areas1, 3, 4) and the maximum ultimate difference of positive sequence current angle with line 1. Figure- 10 Positive sequence current angle absolute differences for interconnected lines to the faulted All rights Reserved 163
7 REFERENCES [1] Terzija Vladimir, Valvrde Gustavo, Cai Deyu, Regulski Pawel,Madani Vahid, Fitch John, SkokSrdjan,Miroslav M.Begovic & Phadeke A Wide-Are Monitoring,Protection, and Control of Future Electric Power Networks, Presented At Proceedings of the IEEE,VOL. 99, NO. 1, Jan 2011, PP [2] Machowski J, W Bialek J, R Bumby J, Power System Dynamics- Stability & Control, 2 nd Edition2008, Press John Willy & Sons Ltd. [3] S. Horowitz and A. Phake, Power System Ralaying. Taunton, Somerset, U.K., Research Studies Press, 1992 [4] A.R.Motavalian, N.Moadabi and G. B. Gharehpetian, Reliability Assessment of Power [5] System Backup Protection between Smart Grid Control Center Using Phasor Measurement Units International Conference on Renewable Energies and Power Quality ICREPQ 13 [6] Kundur Prabha, Power System Stability and Control, March 1994, Press McGraw-Hill Inc, Chapter 2& 14. [7] Grenor Verbic, Ferdinand Gubina, A New Concept of VoltageCollapse Protection- Based on Local Phasors,IEEE Transactions on Power Delivery, Vol.1 9 No.2, Apr.2006, PP [8] Jonsson Mattias, E. Daalder Jaap, An Adaptive Scheme to Prevent Undesirable Distance- Protection function During Voltage Instability IEEE Transactions on Power Systems Delivery, VOL. 18, NO. 4, Oct 2003, All rights Reserved 164
POWER SYSTEM BACKUP PROTECTION IN SMART GRID USING SYNCHRONIZED PMU 1 BEJJENKI DINESH, 2 PERUMANDLA SADANANDAM
POWER SYSTEM BACKUP PROTECTION IN SMART GRID USING SYNCHRONIZED PMU 1 BEJJENKI DINESH, 2 PERUMANDLA SADANANDAM 1 MTECH, DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING, VAAGDEVI COLLEGE OF ENGINEERING
More informationReliability Assessment of Power System Backup Protection in Smart Grid Control Center Using Phasor Measurement Units (PMU)
International Conference on Renewable Energies and Power Quality (ICREPQ 13) Bilbao (Spain), 20 th to 22 th March, 2013 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 2172-038 X, No.11, March
More informationStudy and Simulation of Phasor Measurement Unit for Wide Area Measurement System
Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System Ms.Darsana M. Nair Mr. Rishi Menon Mr. Aby Joseph PG Scholar Assistant Professor Principal Engineer Dept. of EEE Dept. of
More informationAn Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation
Indonesian Journal of Electrical Engineering and Computer Science Vol., No., April 6, pp. 3 ~ 3 DOI:.59/ijeecs.v.i.pp3-3 3 An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability
More informationSYSTEM-WIDE disturbances in power systems are a challenging
270 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010 A Novel Back Up Wide Area Protection Technique for Power Transmission Grids Using Phasor Measurement Unit M. M. Eissa, Senior Member,
More informationMONITORING AND DETECTION OF FAULT USING PHASOR MEASUREMENT UNITS
MONITORING AND DETECTION OF FAULT USING PHASOR MEASUREMENT UNITS C.Anil Kumar 1, K.Lakshmi 2 PG Scholar, K.S.Rangasamy College of Technology, Tiruchengode, Tamilnadu, India. 1 Associate Professor, K.S.Rangasamy
More informationTesting of Circuit Breaker and over Current Relay Implementation by Using MATLAB / SIMULINK
Testing of Circuit Breaker and over Current Relay Implementation by Using MATLAB / SIMULINK Dinesh Kumar Singh dsdineshsingh012@gmail.com Abstract Circuit breaker and relays are being utilized for secure,
More informationModelling of Phasor Measurement Unit and Phasor Data Realisation with 2 Bus System
Intl J Engg Sci Adv Research 05 Sep;(3):79-83 ling of Phasor Measurement Unit and Phasor Data Realisation with Bus System Chakrapani Mishra Department of Electrical Engineering FET, Rama University, Kanpur,
More informationSynchronised PMU based Cascading Failure Protection Strategy for 220 KV Interconnected Transmission Network
Synchronised PMU based Cascading Failure Protection Strategy for 220 KV Interconnected Transmission Network Ajay Kumar Lal Student Member, IEEE Abstract: Cascaded events can be attributed to improper operations
More informationEngineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location
Engineering Thesis The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location By Yushi Jiao Presented to the school of Engineering and
More informationVoltage Control and Power System Stability Enhancement using UPFC
International Conference on Renewable Energies and Power Quality (ICREPQ 14) Cordoba (Spain), 8 th to 10 th April, 2014 Renewable Energy and Power Quality Journal (RE&PQJ) ISSN 2172-038 X, No.12, April
More informationTHE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES
THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors
More informationINTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY
INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK SPECIAL ISSUE FOR NATIONAL LEVEL CONFERENCE "Technology Enabling Modernization
More informationIn addition to wide-area monitoring systems, synchrophasors offer an impressive range of system benefits, including:
Synchrophasors Before synchrophasor technology and its contributions towards transmission resiliency are discussed, it is important to first understand the concept of phasors. A phasor is a complex number
More informationMeasurement tools at heart of Smart Grid need calibration to ensure reliability
Measurement tools at heart of Smart Grid need calibration to ensure reliability Smart grid; PMU calibration position 1 The North American interconnections, or electric transmission grids, operate as a
More informationAn Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays
An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third one of Distance Relays M. Azari, M. Ojaghi and K. Mazlumi* Electrical Engineering Department University of anjan anjan,
More informationAnalysis of Modern Digital Differential Protection for Power Transformer
Analysis of Modern Digital Differential Protection for Power Transformer Nikhil Paliwal (P.G. Scholar), Department of Electrical Engineering Jabalpur Engineering College, Jabalpur, India Dr. A. Trivedi
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationFault Location Using Sparse Wide Area Measurements
319 Study Committee B5 Colloquium October 19-24, 2009 Jeju Island, Korea Fault Location Using Sparse Wide Area Measurements KEZUNOVIC, M., DUTTA, P. (Texas A & M University, USA) Summary Transmission line
More informationStatic Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1
Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load MADHYAMA V. WANKHEDE Department Of Electrical Engineering G. H. Raisoni College of
More informationIslanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current
http:// and Detection of Distributed Generation using Negative Sequence Component of Current Doan Van Dong Danang College of Technology, Danang, Vietnam Abstract - There is a renewed interest in the distributed
More informationA Transfer Trip Scheme to Supervise Zone 3 Operation
IAEL (26) :9 3 DOI.7/s443-6-2-8 ORIGIAL ARTICLE A Transfer Trip Scheme to Supervise Operation J. Ganeswara Rao Ashok Kumar radhan Received: 25 April 26 / Accepted: 6 ay 26 / ublished online: 9 ay 26 Indian
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationArvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India
e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by
More informationSynchrophasors and the Smarter Grid
Synchrophasors and the Smarter Grid Synchrophasor A synchrophasor is a phasor measurement with respect to an absolute time reference. With this measurement we can determine the absolute phase relationship
More informationPHASOR MEASUREMENT UNIT: - A Revolution in Power System
PHASOR MEASUREMENT UNIT: - A Revolution in Power System Sonal Kumar Singh Electrical engineering, JECRC University, Jaipur -------------------------------------------------------------------------***------------------------------------------------------------------------
More informationPublished in A R DIGITECH
PHASOR MEASUREMENT UNIT : An Overview Vishal Wadkar, Pavan Salunkhe, Ganesh Bhondave *1(PG Student of Electrical Department, R.H.Sapat COE College, Nashik, India) *2(PG Student of Electrical Department,
More informationAnalysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.
Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh** *,**(Department of Electrical Engineering, Walchand College of
More information[Nayak, 3(2): February, 2014] ISSN: Impact Factor: 1.852
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Classification of Transmission Line Faults Using Wavelet Transformer B. Lakshmana Nayak M.TECH(APS), AMIE, Associate Professor,
More informationTransient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme
I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)
More informationProtective Relay Synchrophasor Measurements During Fault Conditions
Protective Relay Synchrophasor Measurements During Fault Conditions Armando Guzmán, Satish Samineni, and Mike Bryson Schweitzer Engineering Laboratories, Inc. Published in SEL Journal of Reliable Power,
More informationIJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):
IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online): 2321-0613 Measurement of Power System Oscillation with the use of Synchro Phasor Technology and
More informationSmart Grid Where We Are Today?
1 Smart Grid Where We Are Today? Meliha B. Selak, P. Eng. IEEE PES DLP Lecturer melihas@ieee.org 2014 IEEE ISGT Asia, Kuala Lumpur 22 nd May 2014 2 Generation Transmission Distribution Load Power System
More informationNOWADAYS, there is much interest in connecting various
IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013 419 Modified Dynamic Phasor Estimation Algorithm for the Transient Signals of Distributed Generators Dong-Gyu Lee, Sang-Hee Kang, and Soon-Ryul
More informationPSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay
PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay Anurag Choudhary Department of Electrical and Electronics Engineering College of Engineering Roorkee, Roorkee
More informationPMUs Placement with Max-Flow Min-Cut Communication Constraint in Smart Grids
PMUs Placement with Max-Flow Min-Cut Communication Constraint in Smart Grids Ali Gaber, Karim G. Seddik, and Ayman Y. Elezabi Department of Electrical Engineering, Alexandria University, Alexandria 21544,
More informationImplementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator
Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator Dinesh Rangana Gurusinghe, Dean Ouellette, and Athula D. Rajapakse Abstract-- Many commercial phasor measurement units (PMUs
More informationPUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:
POWER FLOW CONTROL BY USING OPTIMAL LOCATION OF STATCOM S.B. ARUNA Assistant Professor, Dept. of EEE, Sree Vidyanikethan Engineering College, Tirupati aruna_ee@hotmail.com 305 ABSTRACT In present scenario,
More informationPerformance of DVR & Distribution STATCOM in Power Systems
International Journal on Recent and Innovation Trends in Computing and Communication ISSN: 232-869 Volume: 3 Issue: 2 83 89 Performance of DVR & Distribution STATCOM in Power Systems Akil Ahemad Electrical
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationSIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS
SIMUATION OF D-STATCOM AND DVR IN POWER SYSTEMS S.V Ravi Kumar 1 and S. Siva Nagaraju 1 1 J.N.T.U. College of Engineering, KAKINADA, A.P, India E-mail: ravijntu@gmail.com ABSTRACT A Power quality problem
More informationOptimal sizing of battery energy storage system in microgrid system considering load shedding scheme
International Journal of Smart Grid and Clean Energy Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme Thongchart Kerdphol*, Yaser Qudaih, Yasunori Mitani,
More informationState Estimation Advancements Enabled by Synchrophasor Technology
State Estimation Advancements Enabled by Synchrophasor Technology Contents Executive Summary... 2 State Estimation... 2 Legacy State Estimation Biases... 3 Synchrophasor Technology Enabling Enhanced State
More informationPower Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss
Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de
More informationA Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors
A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors Dinesh Rangana Gurusinghe Yaojie Cai Athula D. Rajapakse International Synchrophasor Symposium March 25,
More informationUse of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation
More informationAnti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage
POWERENG 2007, April 12-14, 2007, Setúbal, Portugal Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage Amin Helmzadeh, Javad Sadeh and Omid Alizadeh
More informationMitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer
Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer Deepa Francis Dept. of Electrical and Electronics Engineering, St. Joseph s College of Engineering and Technology, Palai Kerala, India-686579
More informationInternational Journal of Advance Engineering and Research Development
Scientific Journal of Impact Factor (SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 12,December -2015 E-ISSN (O): 2348-4470 P-ISSN (P): 2348-6406 Detection
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationPROTECTION SIGNALLING
PROTECTION SIGNALLING 1 Directional Comparison Distance Protection Schemes The importance of transmission system integrity necessitates high-speed fault clearing times and highspeed auto reclosing to avoid
More informationDESIGN AND SIMULATION OF WIDE AREA MONITORING WITH SMART GRIDS USING PHASOR MEASUREMENT UNIT WITH DISTRIBUTED GENERATION
DESIGN AND SIMULATION OF WIDE AREA MONITORING WITH SMART GRIDS USING PHASOR MEASUREMENT UNIT WITH DISTRIBUTED GENERATION 1 BEJJENKIDINESH, 2 PERUMANDLA SADANANDAM 1 MTECH, DEPARTMENT OF ELECTRICAL AND
More informationDoãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques
Detection of Distributed Generation Islanding Using Negative Sequence Component of Voltage Doãn Văn Đông, College of technology _ Danang University Abstract Distributed generation in simple term can be
More informationRelay Coordination in the Protection of Radially- Connected Power System Network
Relay Coordination in the Protection of Radially- Connected Power System Network Zankhana Shah Electrical Department, Kalol institute of research centre, Ahemedabad-Mehshana Highway, kalol, India 1 zankhu.shah@gmail.com
More informationAdaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator
Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator Priyanka Sahu Columbia Institute of Engineering and Technology, Raipur,
More informationFAULT CLASSIFICATION FOR DISTANCE PROTECTION
FAULT CLASSIFICATION FOR DISTANCE PROTECTION Magnus Akke, Member IEEE ABB Automation Technology Products AB SE-7 59 Västerås, Sweden E-mail: magnus.akke@se.abb.com Abstract: This paper presents an overview
More informationFAULT AND STABILITY ANALYSIS OF A POWER SYSTEM NETWORK BY MATLAB SIMULINK
FAULT AND STABILITY ANALYSIS OF A POWER SYSTEM NETWORK BY MATLAB SIMULINK 1.Mrs Suparna pal Asst Professor,JIS College of Engineering (Affiliated to West Bengal University of Technology), Nadia, Kalyani,West
More informationAN ANN BASED FAULT DETECTION ON ALTERNATOR
AN ANN BASED FAULT DETECTION ON ALTERNATOR Suraj J. Dhon 1, Sarang V. Bhonde 2 1 (Electrical engineering, Amravati University, India) 2 (Electrical engineering, Amravati University, India) ABSTRACT: Synchronous
More informationComparative Testing of Synchronized Phasor Measurement Units
Comparative Testing of Synchronized Phasor Measurement Units Juancarlo Depablos Student Member, IEEE Virginia Tech Virgilio Centeno Member, IEEE Virginia Tech Arun G. Phadke Life Fellow, IEEE Virginia
More informationAdvancement in Wide Area Monitoring Protection and Control Using PMU s Model in MATLAB/SIMULINK
Smart Grid and Renewable Energy, 2012, 3, 294-307 http://dx.doi.org/10.4236/sgre.2012.34040 Published Online November 2012 (http://www.scirp.org/journal/sgre) Advancement in Wide Area Monitoring Protection
More informationImplementing Re-Active Power Compensation Technique in Long Transmission System (750 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool
Implementing Re-Active Power Compensation Technique in Long Transmission System (75 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool Dabberu.Venkateswara Rao, 1 Bodi.Srikanth 2 1, 2(Department
More informationIDENTIFICATION OF POWER QUALITY PROBLEMS IN IEEE BUS SYSTEM BY USING NEURAL NETWORKS
Fourth International Conference on Control System and Power Electronics CSPE IDENTIFICATION OF POWER QUALITY PROBLEMS IN IEEE BUS SYSTEM BY USING NEURAL NETWORKS Mr. Devadasu * and Dr. M Sushama ** * Associate
More informationAn Efficient Fault Locating Technique with Backup Protection Scheme Using Wide Area Measurement for Power System with Simultaneous Faults
International Journal on Electrical Engineering and Informatics - Volume 9, Number 1, March 2017 An Efficient Fault Locating Technique with Backup Protection Scheme Using Wide Area Measurement for Power
More informationSynchrophasors: Definition, Measurement, and Application
1. Abstract Synchrophasors: Definition, Measurement, and Application Mark Adamiak GE Multilin King of Prussia, PA William Premerlani GE Global Research Niskayuna, NY Dr. Bogdan Kasztenny GE Multilin Markham,
More information(Refer Slide Time: 3:11)
Digital Communication. Professor Surendra Prasad. Department of Electrical Engineering. Indian Institute of Technology, Delhi. Lecture-2. Digital Representation of Analog Signals: Delta Modulation. Professor:
More informationVOLTAGE MULTISTABILITY FOR DISTRIBUTION SYSTEM
VOLTAGE MULTISTABILITY FOR DISTRIBUTION SYSTEM D.Arun kumar*, S.Hari prasath*, B.Manikandan*, Mrs,Dr,G.Indira** *Student, EEE, Prince Shri VenkateshwaraPadmavathy Engineering College, Tamilnadu, India
More informationQualitrol s PMU Technologies
Qualitrol s PMU Technologies IDM NASPI Conference June 2008 BEN 6000 Agenda 1. Qualitrol s experience 2. Recording functions that compliment Phasor Measurement 3. A Multi function PMU 4. PMU Case Study
More informationBest Assignment of PMU for Power System Observability Y.Moses kagan, O.I. Sharip Dept. of Mechanical Engineering, Osmania University, India
Best Assignment of PMU for Power System Observability Y.Moses kagan, O.I. Sharip Dept. of Mechanical Engineering, Osmania University, India Abstract: Phasor Measurement Unit (PMU) is a comparatively new
More informationAnalysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar
Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:
More informationOptimal PMU Placement on Network Branches for Intentional Islanding to Prevent Blackouts
Optimal PMU Placement on Network Branches for Intentional Islanding to Prevent Blackouts Mohd Rihan 1, Mukhtar Ahmad 2, M. Salim Beg 3, Anas Anees 4 1,2,4 Electrical Engineering Department, AMU, Aligarh,
More informationSub/super-synchronous harmonics measurement method based on PMUs
The 6th International Conference on Renewable Power Generation (RPG) 19 20 October 2017 Sub/super-synchronous harmonics measurement method based on PMUs Hao Liu, Sudi Xu, Tianshu Bi, Chuang Cao State Key
More informationSERIES (OPEN CONDUCTOR) FAULT DISTANCE LOCATION IN THREE PHASE TRANSMISSION LINE USING ARTIFICIAL NEURAL NETWORK
1067 SERIES (OPEN CONDUCTOR) FAULT DISTANCE LOCATION IN THREE PHASE TRANSMISSION LINE USING ARTIFICIAL NEURAL NETWORK A Nareshkumar 1 1 Assistant professor, Department of Electrical Engineering Institute
More informationKeywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer
Vol. 3 Issue 2, February-2014, pp: (69-75), Impact Factor: 1.252, Available online at: www.erpublications.com Modeling and Simulation of Modern Digital Differential Protection Scheme of Power Transformer
More informationMitigating Voltage Sag Using Dynamic Voltage Restorer
Mitigating Voltage Sag Using Dynamic Voltage Restorer Sumit A. Borakhade 1, R.S. Pote 2 1 (M.E Scholar Electrical Engineering, S.S.G.M.C.E. / S.G.B.A.U. Amravati, India) 2 (Associate Professor, Electrical
More informationPRECISE SYNCHRONIZATION OF PHASOR MEASUREMENTS IN ELECTRIC POWER SYSTEMS
PRECSE SYNCHRONZATON OF PHASOR MEASUREMENTS N ELECTRC POWER SYSTEMS Dr. A.G. Phadke Virginia Polytechnic nstitute and State University Blacksburg, Virginia 240614111. U.S.A. Abstract Phasors representing
More informationDesign and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side
Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side Jaykant Vishwakarma 1, Dr. Arvind Kumar Sharma 2 1 PG Student, High voltage and Power system, Jabalpur Engineering College,
More informationCoordination of Wind and Hydro Power Plant by Using Optimization Technique
Coordination of Wind and Hydro Power Plant by Using Optimization Technique P.Ranjithkumar 1, Saravana Prabaakar 1, M.Suganya 2, iranjana B 2 UG Scholar, Department of EEE, SKCET, Coimbatore-641008, Tamil
More informationBhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)
ISSN: 2349-7637 (Online) RESEARCH HUB International Multidisciplinary Research Journal (RHIMRJ) Research Paper Available online at: www.rhimrj.com Modeling and Simulation of Distribution STATCOM Bhavin
More informationSIMULATION OF D-STATCOM IN POWER SYSTEM
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) SIMULATION OF D-STATCOM IN POWER SYSTEM Akil Ahemad 1, Sayyad Naimuddin 2 1 (Assistant Prof. Electrical Engineering Dept., Anjuman college
More informationSpoofing GPS Receiver Clock Offset of Phasor Measurement Units 1
Spoofing GPS Receiver Clock Offset of Phasor Measurement Units 1 Xichen Jiang (in collaboration with J. Zhang, B. J. Harding, J. J. Makela, and A. D. Domínguez-García) Department of Electrical and Computer
More informationPower System Stability Improvement in Multi-machine 14 Bus System Using STATCOM
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-676,p-ISSN: 232-333, Volume, Issue 3 Ver. II (May Jun. 25), PP 43-47 www.iosrjournals.org Power System Stability Improvement
More informationEnhancement of Power Quality by Improving Voltage Stability Using D-STATCOM
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 3 Ver. II (May Jun. 2015), PP 48-54 www.iosrjournals.org Enhancement of Power Quality
More informationDesign and Implementation for Wide Area Power System Monitoring and Protection using Phasor measuring Units
Design and Implementation for Wide Area Power System Monitoring and Protection using Phasor measuring Units WAHEED UR RAHMAN, MUHAMMAD ALI,CHAUDHRY A. MEHMOOD, ASADULLAH KHAN Electrical Engineering Department
More informationSPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES
SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES Smt N. Sumathi M.Tech.,(Ph.D) 1, P. Krishna Chaitanya 2 1 Assistant Professor, Department of
More informationImprovement of Power system transient stability using static synchronous series compensator
Improvement of Power system transient stability using static synchronous series compensator 1 Dharmendrasinh Chauhan, 2 Mr.Ankit Gajjar 1 ME Student, 2 Assistant Professor Electrical Engineering Department,
More informationImprovement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System
Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System 1 Ramesh Gantha 1, Rasool Ahemmed 2 1 eee Kl University, India 2 AsstProfessor, EEE KL University,
More informationStability Enhancement for Transmission Lines using Static Synchronous Series Compensator
Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India
More informationII. RESEARCH METHODOLOGY
Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College
More informationSYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011
SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 Baselining using large quantities of historical phasor data to identify and understand patterns in interconnection-wide grid behavior, to
More information[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech
More informationPower Quality Improvement using Hysteresis Voltage Control of DVR
Power Quality Improvement using Hysteresis Voltage Control of DVR J Sivasankari 1, U.Shyamala 2, M.Vigneshwaran 3 P.G Scholar, Dept of EEE, M.Kumarasamy college of Engineering, Karur, Tamilnadu, India
More informationControl of grid connected inverter system for sinusoidal current injection with improved performance
Control of grid connected inverter system for sinusoidal current injection with improved performance Simeen. S. Mujawar. Electrical engineering Department, Pune University /PVG s COET, Pune, India. simeen1990@gmail.com
More informationEvaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit
Electrical Power and Energy Conference 2012 Resilient Green Energy Systems for a Sustainable Society Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit Dinesh
More informationDelayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines
Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,
More informationTransmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection
Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed
More informationREACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS
Chapter 2 REACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS Peter W. Sauer University of Illinois at Urbana-Champaign sauer@ece.uiuc.edu Abstract This chapter was prepared primarily for
More informationMitigation of the Statcom with Energy Storage for Power Quality Improvement
Mitigation of the Statcom with Energy Storage for Power Quality Improvement Mohammed Shafiuddin 1, Mohammed Nazeeruddin 2 1 Royal institute of Engineering & Technology (Affliated to JNTUH), India 2 Nawab
More informationGrid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017
Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the
More informationMitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)
ABHIYANTRIKI Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) An International Journal of Engineering & Technology (A Peer Reviewed & Indexed Journal) Vol.
More informationPERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER
International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN 2250-155X Vol. 3, Issue 2, Jun 2013, 309-318 TJPRC Pvt. Ltd. PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID
More information