POWER SYSTEM BACKUP PROTECTION USING SYNCHRONIZED PMU

Size: px
Start display at page:

Download "POWER SYSTEM BACKUP PROTECTION USING SYNCHRONIZED PMU"

Transcription

1 POWER SYSTEM BACKUP PROTECTION USING SYNCHRONIZED PMU LAVUDYA JAYASREE 1 and GAIRABOINA NAGARAJU 2 1,2 Dept. of Electrical And Electronics, Engineering, Christu Jyothi Institute of Technology And Science,Yeshwanthapur, Jangaon, T.S Abstract- Calamity failures in power grid due to mal-function of traditional backup protection system was one of the main causes of unwanted cataract trips. The new technique based on synchronized PMU with fast communication network and GPS system for time transfer have a dynamic adaptation for back-up protection of power system. The goal of the protection scheme is to estimate a new wide area backup protection system to maintain the power system stable by isolating only faulty components from the healthy part of system. The purpose is to boost the overall effectiveness and consistency of the power structure for all power stages via significant dependence on WAPS as distributed intelligence agents with improved monitoring, control and protection capabilities of power network. Introducing the fastest and of course best technique for WAPS as synchronized Phasor measurement unit (PMU).This paper speculates recognition of fault site and protection of power system using PMU also clearance of fault. The protection scheme which is used in this paper depends on the concept of equating positive sequence quantities such as voltage and current angles for every lines connected to the bus to recognize and classify the faulted line. This paper emphasize simulation on 220 KV system by using MATLAB Simulink. Keywords-Phasor Measurement Unit,Backup Protection, Time Synchronization, Global Positioning System. I. INTRODUCTION Nowadays, power systems become very tough and challenging to manage due to fast development to satisfy enormous boost in load demands which leads the power system arrangement to become more complex. So, Electrical networks with adequate power quality and high reliability are preferred. With this admiration, new technologies suchlike smart grids has introduced a new standard for control, protection and monitoring system to improve reliability of electricity, safety of grids,decrease the unwanted blackouts, rapid response to interpretation in the electrical network, spotting of fault and recovery of electrical system as fast as possible. Wide area control, monitoring and protection system is the modern technique for management of electrical system [1].In electrical power system, the different fault occurs which results collapses of the electrical system [2].Collapse of power structure take place due to simple fault, load violation, power fluctuations and islanding. Lots of techniques are used in the power network for safety of transmission line. Distance protection is one of broadly used techniques, as in that protection the distance relay is used for protection purpose. The distance relays are depend on the standalone assessment and each relay operate autonomously corresponding to different region of protection.the distance relay is operating for fault taking place in between the connected relay position and the preferred position [3].Mal-operation of third zone distance protection in conditions such as power sway, voltage volatility and load encroachment may increase to wide area blackouts [4].In July 30th and 31st, 2012 two severe blackouts occurred in India. Here, new technique is provided for protection of wide area using synchronous PMU. This technique is depend on by comparing and equating positive sequence voltage magnitudes for specified areas and positive sequence current phase angles for every coupled lines between the two areas of the system network. The time synchronized phasor measurement technique is used, which gives a view of the dynamic power system and capable for controlling and monitoring of wide area protection. By using a fast GPS and modern conveyed system. DOI: /IJMTER HIIVJ 158

2 II. THE THIRD ZONE MAL-FUNCTION Usually, for the transmission lines the most important protection is done by first and second zones, while the protection done in third zone is recognized as the backup protection. About 80 to 85 percent part of the line without any time delay is covered by the first zone. First zone can be known as the chief protection. Second zone covers the whole length of the line plus 25 to 50percent of the succeeding shortest line and operation time is put about 0.25 to 0.4 seconds. The entire region confined by the both zones plus 25percent of the succeeding long line (third line) is covered by the third zone and for that the delay time is put among 0.6 to 1.5 seconds. The third zone is worked for backup protection. This structure is in general used to defend each line separately. The amplitude and the phase angle of quantities like voltage and current fluctuate, in this third zone, which is the reason of malfunction. Distance protection relays are ready with power sway recognition modules [4]. The very significant obsession in the power network is the need of reactive power and that is main reason of voltage volatility [5].The third zone relay which having a maximum area of protection as backup protection is the reason of Mal function of distance relay in provisions of voltage volatility [6]. When the dynamic load tries beyond the capacity of transmission network line or generation to be used that is most horrible instance of occurring the voltage instability [7]. The various number of methods are used for fault detection from voltage instability are presented. Voltage changes are not always reactive, as step- voltage increase due to switching of capacitors or load shedding.when the network is faulty, derived of voltage close to the voltage collapse is huge and negative. III. CONCEPT OF PMU The device named as PMU is worked to collect and provide instant phasor from desire areas of applications attracted with instantaneous day and time of the measuring called stamped data. Estimated phasor are called as synchro-phasors, here synchronized measurement technique plays very important roles, especially in backup protection. But to send information of PMU from distant parts of the network to main control system is consociated with delay of frequent tens of milliseconds. So it is not enough to use WAPS using PMU for main protection system. PMU measures positive sequence currents and voltages with accurate and exact time synchronization. The measurements are done by using GPS single pulse per second Synchrophasors, provide the phasor demonstration of voltage or current to complete time reference. This absolute reference is given in the form of a common timing signal by using high -accuracy clocks synchronized to corresponding universal time such as the universally used global positioning system (GPS).The synchronized clocks are used as a reference,so PMU creates the complex number of a constant sinusoidal signal phasor representation as presented in Fig. 1. The connection between the reporting moment and the phasor representation is that, the phase angle is equal to the angular division between the reporting peak and the period of the sinusoid. Though, if all PMUs works on the same timing reference, their measurements are comparable, and the differences among the phase angle of phasors are correct. As most applications look for to identify the differences between the phase angles of variety of phasors, the output of PMU provides a valuable input to monitoring, protection, and control operation in a power system. Figure -1 Phasor representation (a) Sinusoidal waveform (b) Phasor All rights Reserved 159

3 The synchronized phasor of ac signal is given as the complex quantities as below, x(t) = xr + jxi = ( xm / 2) e jø (1) = xm / 2 (Cos ø + j Sin ø ) (2) Where, xm = amplitude of synchronized vector, phase angle is denoted by ø and xi and xr are imaginary and real components of complex value. The general method for phasors calculation by using sample data is discrete Fourier transform. The high speed communications links used for WAPS are Fiber optic, microwave, PLC, Twisted pair. IV. THE PROJECTED TECHNIQUE The main purpose is to improve the interruption monitoring and system event analysis. Synchronous phasor measurements gives all revelatory state measurements that are phase angle, frequency and voltage magnitude. PMU is used to evaluate bus voltages and all revealing line currents next these measurements are given to PDC at control centre. The technique is WAPS which is accepted to find abnormal or faulty condition and to isolate the faulty area from the overall system. Two components are very important to distinguish the faults on transmission line. One is the drop of voltage and other is due to fault occurrence the change in flow of power direction. The fault current way to be able to resolve by using phase angle through reference to a base quantity. Direction of fault to be able to find out by with the assist of comparing the transmission line phase angle of current and voltage. The PMU, block diagram is as in Fig. 2 below. Figure -2 The block diagram of PMU The analog to digital converter, converts the analog signal from current and potential transformer to digital signal and passed through low pass filter. The GPS receiver detects the single pulse for each second synchronizing signal from GPS satellite. From these data the positive sequence quantities such as voltage and current are calculated. The voltage is viewed as reference polarizing quantity. The fault current Phasor lies inside forward and backward areas with reference to the reference phasor, corresponding to the fault situation [8,9]. Flow of Power in given direction is the effect of phase angle among voltage and current varying around its power factor angle while the power direction the current phase angle, with travels in opposite direction, reference to voltage will be[8]. At the main[8]. At the main place and current angles with supreme differences are measured for organized line with this affected region. By equating this angles with one another, the most value of complete difference is measured as faulted line. This process can be expressed mathematically as follows: Min { 1, 2 m n } (3) The positive sequence voltage magnitude is calculated by PMU for area 1, 2, 3, m, to n. When the fault take place on the network the output of positive sequence voltage magnitude becomes minimum. From this calculation the nearest faulted area can be determined. In this case this area is shown by m. Next there is need of comparing the accurate differences of current angles All rights Reserved 160

4 positive sequence of interrelated lines associated with this area m which is faulted with the interrelated close to area and then by selecting maximum one. This can be expressed as, Max { m1, m2, m3,. mn } (4) Where, m and n are the organized part which shows the positive sequence current angle difference for the transmission network. This can be specified as follows, mn = mn- nm (5) V. SIMULATION AND RESULTS As presented in fig. 3 the five bus network is employed for case study. The interconnected network is taken of 220 KV, 100 km transmission line, one side is connected with generating station and other with load through interconnected lines. Matlab Simulink software is applied to simulate various faults and investigations. As discussed in the paper, lack of a proper technique for the solution of Mal operation in the third zone on 230 KV lines and above [10]. In this way in paper, the projected technique is tested. As displayed in fig 4 the simulation is performed by using the MATLAB Simulink software for five bus test system. The standards given are in per unit at 50Hz on 100MVA base [11]. Figure -3 The five bus system network taken for study The values for system are given in per unit on 100 MVA (base ) in table no.1 Table- 1 The transmission line parameters. 1 Generator MVA,220Kv,50Hz,Synchronous generator pu model 2 Transformer 220 KV/13.8 KV,100 MVA 100 Synchronous KV,100 MVA machine 4 LOAD Kv,50MW,24Mvar,RL load 5 LOAD Kv,100MW,48Mvar,RL load 6 LOAD Kv,80MW,38Mvar,RL All rights Reserved 161

5 7 LOAD Kv,120MW,58Mvar,RL load 8 LOAD Kv,150MW,RL load When different fault appeared on the given transmission line, the faulted signals can be recognized from results. Similarly, various fault situation are simulated on the system using the proposed technique. Type of Fault can be detected and observed by using Fault Analysis Block given in fig. 6 for three phase to Ground Fault but same can be obtained for single line to ground fault and double line to ground fault. Figure- 4 SIMULINK model of 5 Bus 220 kv system Figure -5 MATLAB/Simulink block diagram responsible of the selection of the type of fault & its clearance. Figure- 6 Fault analysis block for three phase to Ground Fault Figure All rights Reserved 162

6 Figure -8 Three phase current signals for entire lines connected to the fault affected area (i.e. area 2). The fault is situated on line 1 connecting area 1 and area 2. When fault occurs, line connected between area 1 and area 2 is exaggerated. Fig. 7displays the output of three phase to ground voltage, whereas fig. 8 shows output of three phase current of the lines linked to faulted part. As well, different fault conditions are simulated on the system with projected procedure Figure -9 Positive sequence voltage magnitudes five different areas during fault on the network Fig. 9 shows the output from the five PMUs, the graph shows the five positive sequence voltage magnitudes (PSVM) for five different areas during fault. The minimum value is selected which is showing the nearest area to the fault (area 2 ). Fig. 10 shows the perfect difference of all positive sequence current angles (PSCA) for every lines interconnected with the faulted region (area 2) with the other adjacent areas (areas1, 3, 4) and the maximum ultimate difference of positive sequence current angle with line 1. Figure- 10 Positive sequence current angle absolute differences for interconnected lines to the faulted All rights Reserved 163

7 REFERENCES [1] Terzija Vladimir, Valvrde Gustavo, Cai Deyu, Regulski Pawel,Madani Vahid, Fitch John, SkokSrdjan,Miroslav M.Begovic & Phadeke A Wide-Are Monitoring,Protection, and Control of Future Electric Power Networks, Presented At Proceedings of the IEEE,VOL. 99, NO. 1, Jan 2011, PP [2] Machowski J, W Bialek J, R Bumby J, Power System Dynamics- Stability & Control, 2 nd Edition2008, Press John Willy & Sons Ltd. [3] S. Horowitz and A. Phake, Power System Ralaying. Taunton, Somerset, U.K., Research Studies Press, 1992 [4] A.R.Motavalian, N.Moadabi and G. B. Gharehpetian, Reliability Assessment of Power [5] System Backup Protection between Smart Grid Control Center Using Phasor Measurement Units International Conference on Renewable Energies and Power Quality ICREPQ 13 [6] Kundur Prabha, Power System Stability and Control, March 1994, Press McGraw-Hill Inc, Chapter 2& 14. [7] Grenor Verbic, Ferdinand Gubina, A New Concept of VoltageCollapse Protection- Based on Local Phasors,IEEE Transactions on Power Delivery, Vol.1 9 No.2, Apr.2006, PP [8] Jonsson Mattias, E. Daalder Jaap, An Adaptive Scheme to Prevent Undesirable Distance- Protection function During Voltage Instability IEEE Transactions on Power Systems Delivery, VOL. 18, NO. 4, Oct 2003, All rights Reserved 164

POWER SYSTEM BACKUP PROTECTION IN SMART GRID USING SYNCHRONIZED PMU 1 BEJJENKI DINESH, 2 PERUMANDLA SADANANDAM

POWER SYSTEM BACKUP PROTECTION IN SMART GRID USING SYNCHRONIZED PMU 1 BEJJENKI DINESH, 2 PERUMANDLA SADANANDAM POWER SYSTEM BACKUP PROTECTION IN SMART GRID USING SYNCHRONIZED PMU 1 BEJJENKI DINESH, 2 PERUMANDLA SADANANDAM 1 MTECH, DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING, VAAGDEVI COLLEGE OF ENGINEERING

More information

Reliability Assessment of Power System Backup Protection in Smart Grid Control Center Using Phasor Measurement Units (PMU)

Reliability Assessment of Power System Backup Protection in Smart Grid Control Center Using Phasor Measurement Units (PMU) International Conference on Renewable Energies and Power Quality (ICREPQ 13) Bilbao (Spain), 20 th to 22 th March, 2013 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 2172-038 X, No.11, March

More information

Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System

Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System Ms.Darsana M. Nair Mr. Rishi Menon Mr. Aby Joseph PG Scholar Assistant Professor Principal Engineer Dept. of EEE Dept. of

More information

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation Indonesian Journal of Electrical Engineering and Computer Science Vol., No., April 6, pp. 3 ~ 3 DOI:.59/ijeecs.v.i.pp3-3 3 An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability

More information

SYSTEM-WIDE disturbances in power systems are a challenging

SYSTEM-WIDE disturbances in power systems are a challenging 270 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010 A Novel Back Up Wide Area Protection Technique for Power Transmission Grids Using Phasor Measurement Unit M. M. Eissa, Senior Member,

More information

MONITORING AND DETECTION OF FAULT USING PHASOR MEASUREMENT UNITS

MONITORING AND DETECTION OF FAULT USING PHASOR MEASUREMENT UNITS MONITORING AND DETECTION OF FAULT USING PHASOR MEASUREMENT UNITS C.Anil Kumar 1, K.Lakshmi 2 PG Scholar, K.S.Rangasamy College of Technology, Tiruchengode, Tamilnadu, India. 1 Associate Professor, K.S.Rangasamy

More information

Testing of Circuit Breaker and over Current Relay Implementation by Using MATLAB / SIMULINK

Testing of Circuit Breaker and over Current Relay Implementation by Using MATLAB / SIMULINK Testing of Circuit Breaker and over Current Relay Implementation by Using MATLAB / SIMULINK Dinesh Kumar Singh dsdineshsingh012@gmail.com Abstract Circuit breaker and relays are being utilized for secure,

More information

Modelling of Phasor Measurement Unit and Phasor Data Realisation with 2 Bus System

Modelling of Phasor Measurement Unit and Phasor Data Realisation with 2 Bus System Intl J Engg Sci Adv Research 05 Sep;(3):79-83 ling of Phasor Measurement Unit and Phasor Data Realisation with Bus System Chakrapani Mishra Department of Electrical Engineering FET, Rama University, Kanpur,

More information

Synchronised PMU based Cascading Failure Protection Strategy for 220 KV Interconnected Transmission Network

Synchronised PMU based Cascading Failure Protection Strategy for 220 KV Interconnected Transmission Network Synchronised PMU based Cascading Failure Protection Strategy for 220 KV Interconnected Transmission Network Ajay Kumar Lal Student Member, IEEE Abstract: Cascaded events can be attributed to improper operations

More information

Engineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location

Engineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location Engineering Thesis The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location By Yushi Jiao Presented to the school of Engineering and

More information

Voltage Control and Power System Stability Enhancement using UPFC

Voltage Control and Power System Stability Enhancement using UPFC International Conference on Renewable Energies and Power Quality (ICREPQ 14) Cordoba (Spain), 8 th to 10 th April, 2014 Renewable Energy and Power Quality Journal (RE&PQJ) ISSN 2172-038 X, No.12, April

More information

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors

More information

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK SPECIAL ISSUE FOR NATIONAL LEVEL CONFERENCE "Technology Enabling Modernization

More information

In addition to wide-area monitoring systems, synchrophasors offer an impressive range of system benefits, including:

In addition to wide-area monitoring systems, synchrophasors offer an impressive range of system benefits, including: Synchrophasors Before synchrophasor technology and its contributions towards transmission resiliency are discussed, it is important to first understand the concept of phasors. A phasor is a complex number

More information

Measurement tools at heart of Smart Grid need calibration to ensure reliability

Measurement tools at heart of Smart Grid need calibration to ensure reliability Measurement tools at heart of Smart Grid need calibration to ensure reliability Smart grid; PMU calibration position 1 The North American interconnections, or electric transmission grids, operate as a

More information

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third one of Distance Relays M. Azari, M. Ojaghi and K. Mazlumi* Electrical Engineering Department University of anjan anjan,

More information

Analysis of Modern Digital Differential Protection for Power Transformer

Analysis of Modern Digital Differential Protection for Power Transformer Analysis of Modern Digital Differential Protection for Power Transformer Nikhil Paliwal (P.G. Scholar), Department of Electrical Engineering Jabalpur Engineering College, Jabalpur, India Dr. A. Trivedi

More information

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION 23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB

More information

Fault Location Using Sparse Wide Area Measurements

Fault Location Using Sparse Wide Area Measurements 319 Study Committee B5 Colloquium October 19-24, 2009 Jeju Island, Korea Fault Location Using Sparse Wide Area Measurements KEZUNOVIC, M., DUTTA, P. (Texas A & M University, USA) Summary Transmission line

More information

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1 Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load MADHYAMA V. WANKHEDE Department Of Electrical Engineering G. H. Raisoni College of

More information

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current http:// and Detection of Distributed Generation using Negative Sequence Component of Current Doan Van Dong Danang College of Technology, Danang, Vietnam Abstract - There is a renewed interest in the distributed

More information

A Transfer Trip Scheme to Supervise Zone 3 Operation

A Transfer Trip Scheme to Supervise Zone 3 Operation IAEL (26) :9 3 DOI.7/s443-6-2-8 ORIGIAL ARTICLE A Transfer Trip Scheme to Supervise Operation J. Ganeswara Rao Ashok Kumar radhan Received: 25 April 26 / Accepted: 6 ay 26 / ublished online: 9 ay 26 Indian

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by

More information

Synchrophasors and the Smarter Grid

Synchrophasors and the Smarter Grid Synchrophasors and the Smarter Grid Synchrophasor A synchrophasor is a phasor measurement with respect to an absolute time reference. With this measurement we can determine the absolute phase relationship

More information

PHASOR MEASUREMENT UNIT: - A Revolution in Power System

PHASOR MEASUREMENT UNIT: - A Revolution in Power System PHASOR MEASUREMENT UNIT: - A Revolution in Power System Sonal Kumar Singh Electrical engineering, JECRC University, Jaipur -------------------------------------------------------------------------***------------------------------------------------------------------------

More information

Published in A R DIGITECH

Published in A R DIGITECH PHASOR MEASUREMENT UNIT : An Overview Vishal Wadkar, Pavan Salunkhe, Ganesh Bhondave *1(PG Student of Electrical Department, R.H.Sapat COE College, Nashik, India) *2(PG Student of Electrical Department,

More information

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh** *,**(Department of Electrical Engineering, Walchand College of

More information

[Nayak, 3(2): February, 2014] ISSN: Impact Factor: 1.852

[Nayak, 3(2): February, 2014] ISSN: Impact Factor: 1.852 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Classification of Transmission Line Faults Using Wavelet Transformer B. Lakshmana Nayak M.TECH(APS), AMIE, Associate Professor,

More information

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)

More information

Protective Relay Synchrophasor Measurements During Fault Conditions

Protective Relay Synchrophasor Measurements During Fault Conditions Protective Relay Synchrophasor Measurements During Fault Conditions Armando Guzmán, Satish Samineni, and Mike Bryson Schweitzer Engineering Laboratories, Inc. Published in SEL Journal of Reliable Power,

More information

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online): 2321-0613 Measurement of Power System Oscillation with the use of Synchro Phasor Technology and

More information

Smart Grid Where We Are Today?

Smart Grid Where We Are Today? 1 Smart Grid Where We Are Today? Meliha B. Selak, P. Eng. IEEE PES DLP Lecturer melihas@ieee.org 2014 IEEE ISGT Asia, Kuala Lumpur 22 nd May 2014 2 Generation Transmission Distribution Load Power System

More information

NOWADAYS, there is much interest in connecting various

NOWADAYS, there is much interest in connecting various IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013 419 Modified Dynamic Phasor Estimation Algorithm for the Transient Signals of Distributed Generators Dong-Gyu Lee, Sang-Hee Kang, and Soon-Ryul

More information

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay Anurag Choudhary Department of Electrical and Electronics Engineering College of Engineering Roorkee, Roorkee

More information

PMUs Placement with Max-Flow Min-Cut Communication Constraint in Smart Grids

PMUs Placement with Max-Flow Min-Cut Communication Constraint in Smart Grids PMUs Placement with Max-Flow Min-Cut Communication Constraint in Smart Grids Ali Gaber, Karim G. Seddik, and Ayman Y. Elezabi Department of Electrical Engineering, Alexandria University, Alexandria 21544,

More information

Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator

Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator Dinesh Rangana Gurusinghe, Dean Ouellette, and Athula D. Rajapakse Abstract-- Many commercial phasor measurement units (PMUs

More information

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER  CSEA2012 ISSN: ; e-issn: POWER FLOW CONTROL BY USING OPTIMAL LOCATION OF STATCOM S.B. ARUNA Assistant Professor, Dept. of EEE, Sree Vidyanikethan Engineering College, Tirupati aruna_ee@hotmail.com 305 ABSTRACT In present scenario,

More information

Performance of DVR & Distribution STATCOM in Power Systems

Performance of DVR & Distribution STATCOM in Power Systems International Journal on Recent and Innovation Trends in Computing and Communication ISSN: 232-869 Volume: 3 Issue: 2 83 89 Performance of DVR & Distribution STATCOM in Power Systems Akil Ahemad Electrical

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS SIMUATION OF D-STATCOM AND DVR IN POWER SYSTEMS S.V Ravi Kumar 1 and S. Siva Nagaraju 1 1 J.N.T.U. College of Engineering, KAKINADA, A.P, India E-mail: ravijntu@gmail.com ABSTRACT A Power quality problem

More information

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme International Journal of Smart Grid and Clean Energy Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme Thongchart Kerdphol*, Yaser Qudaih, Yasunori Mitani,

More information

State Estimation Advancements Enabled by Synchrophasor Technology

State Estimation Advancements Enabled by Synchrophasor Technology State Estimation Advancements Enabled by Synchrophasor Technology Contents Executive Summary... 2 State Estimation... 2 Legacy State Estimation Biases... 3 Synchrophasor Technology Enabling Enhanced State

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors

A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors Dinesh Rangana Gurusinghe Yaojie Cai Athula D. Rajapakse International Synchrophasor Symposium March 25,

More information

Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files

Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation

More information

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage POWERENG 2007, April 12-14, 2007, Setúbal, Portugal Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage Amin Helmzadeh, Javad Sadeh and Omid Alizadeh

More information

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer Deepa Francis Dept. of Electrical and Electronics Engineering, St. Joseph s College of Engineering and Technology, Palai Kerala, India-686579

More information

International Journal of Advance Engineering and Research Development

International Journal of Advance Engineering and Research Development Scientific Journal of Impact Factor (SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 12,December -2015 E-ISSN (O): 2348-4470 P-ISSN (P): 2348-6406 Detection

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

PROTECTION SIGNALLING

PROTECTION SIGNALLING PROTECTION SIGNALLING 1 Directional Comparison Distance Protection Schemes The importance of transmission system integrity necessitates high-speed fault clearing times and highspeed auto reclosing to avoid

More information

DESIGN AND SIMULATION OF WIDE AREA MONITORING WITH SMART GRIDS USING PHASOR MEASUREMENT UNIT WITH DISTRIBUTED GENERATION

DESIGN AND SIMULATION OF WIDE AREA MONITORING WITH SMART GRIDS USING PHASOR MEASUREMENT UNIT WITH DISTRIBUTED GENERATION DESIGN AND SIMULATION OF WIDE AREA MONITORING WITH SMART GRIDS USING PHASOR MEASUREMENT UNIT WITH DISTRIBUTED GENERATION 1 BEJJENKIDINESH, 2 PERUMANDLA SADANANDAM 1 MTECH, DEPARTMENT OF ELECTRICAL AND

More information

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques Detection of Distributed Generation Islanding Using Negative Sequence Component of Voltage Doãn Văn Đông, College of technology _ Danang University Abstract Distributed generation in simple term can be

More information

Relay Coordination in the Protection of Radially- Connected Power System Network

Relay Coordination in the Protection of Radially- Connected Power System Network Relay Coordination in the Protection of Radially- Connected Power System Network Zankhana Shah Electrical Department, Kalol institute of research centre, Ahemedabad-Mehshana Highway, kalol, India 1 zankhu.shah@gmail.com

More information

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator Priyanka Sahu Columbia Institute of Engineering and Technology, Raipur,

More information

FAULT CLASSIFICATION FOR DISTANCE PROTECTION

FAULT CLASSIFICATION FOR DISTANCE PROTECTION FAULT CLASSIFICATION FOR DISTANCE PROTECTION Magnus Akke, Member IEEE ABB Automation Technology Products AB SE-7 59 Västerås, Sweden E-mail: magnus.akke@se.abb.com Abstract: This paper presents an overview

More information

FAULT AND STABILITY ANALYSIS OF A POWER SYSTEM NETWORK BY MATLAB SIMULINK

FAULT AND STABILITY ANALYSIS OF A POWER SYSTEM NETWORK BY MATLAB SIMULINK FAULT AND STABILITY ANALYSIS OF A POWER SYSTEM NETWORK BY MATLAB SIMULINK 1.Mrs Suparna pal Asst Professor,JIS College of Engineering (Affiliated to West Bengal University of Technology), Nadia, Kalyani,West

More information

AN ANN BASED FAULT DETECTION ON ALTERNATOR

AN ANN BASED FAULT DETECTION ON ALTERNATOR AN ANN BASED FAULT DETECTION ON ALTERNATOR Suraj J. Dhon 1, Sarang V. Bhonde 2 1 (Electrical engineering, Amravati University, India) 2 (Electrical engineering, Amravati University, India) ABSTRACT: Synchronous

More information

Comparative Testing of Synchronized Phasor Measurement Units

Comparative Testing of Synchronized Phasor Measurement Units Comparative Testing of Synchronized Phasor Measurement Units Juancarlo Depablos Student Member, IEEE Virginia Tech Virgilio Centeno Member, IEEE Virginia Tech Arun G. Phadke Life Fellow, IEEE Virginia

More information

Advancement in Wide Area Monitoring Protection and Control Using PMU s Model in MATLAB/SIMULINK

Advancement in Wide Area Monitoring Protection and Control Using PMU s Model in MATLAB/SIMULINK Smart Grid and Renewable Energy, 2012, 3, 294-307 http://dx.doi.org/10.4236/sgre.2012.34040 Published Online November 2012 (http://www.scirp.org/journal/sgre) Advancement in Wide Area Monitoring Protection

More information

Implementing Re-Active Power Compensation Technique in Long Transmission System (750 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool

Implementing Re-Active Power Compensation Technique in Long Transmission System (750 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool Implementing Re-Active Power Compensation Technique in Long Transmission System (75 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool Dabberu.Venkateswara Rao, 1 Bodi.Srikanth 2 1, 2(Department

More information

IDENTIFICATION OF POWER QUALITY PROBLEMS IN IEEE BUS SYSTEM BY USING NEURAL NETWORKS

IDENTIFICATION OF POWER QUALITY PROBLEMS IN IEEE BUS SYSTEM BY USING NEURAL NETWORKS Fourth International Conference on Control System and Power Electronics CSPE IDENTIFICATION OF POWER QUALITY PROBLEMS IN IEEE BUS SYSTEM BY USING NEURAL NETWORKS Mr. Devadasu * and Dr. M Sushama ** * Associate

More information

An Efficient Fault Locating Technique with Backup Protection Scheme Using Wide Area Measurement for Power System with Simultaneous Faults

An Efficient Fault Locating Technique with Backup Protection Scheme Using Wide Area Measurement for Power System with Simultaneous Faults International Journal on Electrical Engineering and Informatics - Volume 9, Number 1, March 2017 An Efficient Fault Locating Technique with Backup Protection Scheme Using Wide Area Measurement for Power

More information

Synchrophasors: Definition, Measurement, and Application

Synchrophasors: Definition, Measurement, and Application 1. Abstract Synchrophasors: Definition, Measurement, and Application Mark Adamiak GE Multilin King of Prussia, PA William Premerlani GE Global Research Niskayuna, NY Dr. Bogdan Kasztenny GE Multilin Markham,

More information

(Refer Slide Time: 3:11)

(Refer Slide Time: 3:11) Digital Communication. Professor Surendra Prasad. Department of Electrical Engineering. Indian Institute of Technology, Delhi. Lecture-2. Digital Representation of Analog Signals: Delta Modulation. Professor:

More information

VOLTAGE MULTISTABILITY FOR DISTRIBUTION SYSTEM

VOLTAGE MULTISTABILITY FOR DISTRIBUTION SYSTEM VOLTAGE MULTISTABILITY FOR DISTRIBUTION SYSTEM D.Arun kumar*, S.Hari prasath*, B.Manikandan*, Mrs,Dr,G.Indira** *Student, EEE, Prince Shri VenkateshwaraPadmavathy Engineering College, Tamilnadu, India

More information

Qualitrol s PMU Technologies

Qualitrol s PMU Technologies Qualitrol s PMU Technologies IDM NASPI Conference June 2008 BEN 6000 Agenda 1. Qualitrol s experience 2. Recording functions that compliment Phasor Measurement 3. A Multi function PMU 4. PMU Case Study

More information

Best Assignment of PMU for Power System Observability Y.Moses kagan, O.I. Sharip Dept. of Mechanical Engineering, Osmania University, India

Best Assignment of PMU for Power System Observability Y.Moses kagan, O.I. Sharip Dept. of Mechanical Engineering, Osmania University, India Best Assignment of PMU for Power System Observability Y.Moses kagan, O.I. Sharip Dept. of Mechanical Engineering, Osmania University, India Abstract: Phasor Measurement Unit (PMU) is a comparatively new

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

Optimal PMU Placement on Network Branches for Intentional Islanding to Prevent Blackouts

Optimal PMU Placement on Network Branches for Intentional Islanding to Prevent Blackouts Optimal PMU Placement on Network Branches for Intentional Islanding to Prevent Blackouts Mohd Rihan 1, Mukhtar Ahmad 2, M. Salim Beg 3, Anas Anees 4 1,2,4 Electrical Engineering Department, AMU, Aligarh,

More information

Sub/super-synchronous harmonics measurement method based on PMUs

Sub/super-synchronous harmonics measurement method based on PMUs The 6th International Conference on Renewable Power Generation (RPG) 19 20 October 2017 Sub/super-synchronous harmonics measurement method based on PMUs Hao Liu, Sudi Xu, Tianshu Bi, Chuang Cao State Key

More information

SERIES (OPEN CONDUCTOR) FAULT DISTANCE LOCATION IN THREE PHASE TRANSMISSION LINE USING ARTIFICIAL NEURAL NETWORK

SERIES (OPEN CONDUCTOR) FAULT DISTANCE LOCATION IN THREE PHASE TRANSMISSION LINE USING ARTIFICIAL NEURAL NETWORK 1067 SERIES (OPEN CONDUCTOR) FAULT DISTANCE LOCATION IN THREE PHASE TRANSMISSION LINE USING ARTIFICIAL NEURAL NETWORK A Nareshkumar 1 1 Assistant professor, Department of Electrical Engineering Institute

More information

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer Vol. 3 Issue 2, February-2014, pp: (69-75), Impact Factor: 1.252, Available online at: www.erpublications.com Modeling and Simulation of Modern Digital Differential Protection Scheme of Power Transformer

More information

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Mitigating Voltage Sag Using Dynamic Voltage Restorer Mitigating Voltage Sag Using Dynamic Voltage Restorer Sumit A. Borakhade 1, R.S. Pote 2 1 (M.E Scholar Electrical Engineering, S.S.G.M.C.E. / S.G.B.A.U. Amravati, India) 2 (Associate Professor, Electrical

More information

PRECISE SYNCHRONIZATION OF PHASOR MEASUREMENTS IN ELECTRIC POWER SYSTEMS

PRECISE SYNCHRONIZATION OF PHASOR MEASUREMENTS IN ELECTRIC POWER SYSTEMS PRECSE SYNCHRONZATON OF PHASOR MEASUREMENTS N ELECTRC POWER SYSTEMS Dr. A.G. Phadke Virginia Polytechnic nstitute and State University Blacksburg, Virginia 240614111. U.S.A. Abstract Phasors representing

More information

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side Jaykant Vishwakarma 1, Dr. Arvind Kumar Sharma 2 1 PG Student, High voltage and Power system, Jabalpur Engineering College,

More information

Coordination of Wind and Hydro Power Plant by Using Optimization Technique

Coordination of Wind and Hydro Power Plant by Using Optimization Technique Coordination of Wind and Hydro Power Plant by Using Optimization Technique P.Ranjithkumar 1, Saravana Prabaakar 1, M.Suganya 2, iranjana B 2 UG Scholar, Department of EEE, SKCET, Coimbatore-641008, Tamil

More information

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India) ISSN: 2349-7637 (Online) RESEARCH HUB International Multidisciplinary Research Journal (RHIMRJ) Research Paper Available online at: www.rhimrj.com Modeling and Simulation of Distribution STATCOM Bhavin

More information

SIMULATION OF D-STATCOM IN POWER SYSTEM

SIMULATION OF D-STATCOM IN POWER SYSTEM IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) SIMULATION OF D-STATCOM IN POWER SYSTEM Akil Ahemad 1, Sayyad Naimuddin 2 1 (Assistant Prof. Electrical Engineering Dept., Anjuman college

More information

Spoofing GPS Receiver Clock Offset of Phasor Measurement Units 1

Spoofing GPS Receiver Clock Offset of Phasor Measurement Units 1 Spoofing GPS Receiver Clock Offset of Phasor Measurement Units 1 Xichen Jiang (in collaboration with J. Zhang, B. J. Harding, J. J. Makela, and A. D. Domínguez-García) Department of Electrical and Computer

More information

Power System Stability Improvement in Multi-machine 14 Bus System Using STATCOM

Power System Stability Improvement in Multi-machine 14 Bus System Using STATCOM IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-676,p-ISSN: 232-333, Volume, Issue 3 Ver. II (May Jun. 25), PP 43-47 www.iosrjournals.org Power System Stability Improvement

More information

Enhancement of Power Quality by Improving Voltage Stability Using D-STATCOM

Enhancement of Power Quality by Improving Voltage Stability Using D-STATCOM IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 3 Ver. II (May Jun. 2015), PP 48-54 www.iosrjournals.org Enhancement of Power Quality

More information

Design and Implementation for Wide Area Power System Monitoring and Protection using Phasor measuring Units

Design and Implementation for Wide Area Power System Monitoring and Protection using Phasor measuring Units Design and Implementation for Wide Area Power System Monitoring and Protection using Phasor measuring Units WAHEED UR RAHMAN, MUHAMMAD ALI,CHAUDHRY A. MEHMOOD, ASADULLAH KHAN Electrical Engineering Department

More information

SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES

SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES Smt N. Sumathi M.Tech.,(Ph.D) 1, P. Krishna Chaitanya 2 1 Assistant Professor, Department of

More information

Improvement of Power system transient stability using static synchronous series compensator

Improvement of Power system transient stability using static synchronous series compensator Improvement of Power system transient stability using static synchronous series compensator 1 Dharmendrasinh Chauhan, 2 Mr.Ankit Gajjar 1 ME Student, 2 Assistant Professor Electrical Engineering Department,

More information

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System 1 Ramesh Gantha 1, Rasool Ahemmed 2 1 eee Kl University, India 2 AsstProfessor, EEE KL University,

More information

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India

More information

II. RESEARCH METHODOLOGY

II. RESEARCH METHODOLOGY Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College

More information

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 Baselining using large quantities of historical phasor data to identify and understand patterns in interconnection-wide grid behavior, to

More information

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech

More information

Power Quality Improvement using Hysteresis Voltage Control of DVR

Power Quality Improvement using Hysteresis Voltage Control of DVR Power Quality Improvement using Hysteresis Voltage Control of DVR J Sivasankari 1, U.Shyamala 2, M.Vigneshwaran 3 P.G Scholar, Dept of EEE, M.Kumarasamy college of Engineering, Karur, Tamilnadu, India

More information

Control of grid connected inverter system for sinusoidal current injection with improved performance

Control of grid connected inverter system for sinusoidal current injection with improved performance Control of grid connected inverter system for sinusoidal current injection with improved performance Simeen. S. Mujawar. Electrical engineering Department, Pune University /PVG s COET, Pune, India. simeen1990@gmail.com

More information

Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit

Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit Electrical Power and Energy Conference 2012 Resilient Green Energy Systems for a Sustainable Society Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit Dinesh

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

REACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS

REACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS Chapter 2 REACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS Peter W. Sauer University of Illinois at Urbana-Champaign sauer@ece.uiuc.edu Abstract This chapter was prepared primarily for

More information

Mitigation of the Statcom with Energy Storage for Power Quality Improvement

Mitigation of the Statcom with Energy Storage for Power Quality Improvement Mitigation of the Statcom with Energy Storage for Power Quality Improvement Mohammed Shafiuddin 1, Mohammed Nazeeruddin 2 1 Royal institute of Engineering & Technology (Affliated to JNTUH), India 2 Nawab

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) ABHIYANTRIKI Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) An International Journal of Engineering & Technology (A Peer Reviewed & Indexed Journal) Vol.

More information

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN 2250-155X Vol. 3, Issue 2, Jun 2013, 309-318 TJPRC Pvt. Ltd. PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID

More information