Harmonic Analysis of a High Speed Automatic Reclosing on a 400 kv Overhead Transmission Line
|
|
- Laureen Harvey
- 6 years ago
- Views:
Transcription
1 Harmonic Analysis of a High Speed Automatic Reclosing on a 400 kv Overhead Transmission Line ANGELA IAGAR, SORIN IOAN DEACONU, CORINA DANIELA CUNTAN, IOAN BACIU Department of Electrotechnical Engineering and Industrial Informatics Politechnica University of Timisoara Revolutiei Street, No.5, Hunedoara, ROMANIA angela.iagar@fih.upt.ro Abstract: - Studies reveal that a vast majority of faults on overhead lines are transient in nature. For this reason are used automatic reclosing devices to maintain system stability and the continuity of the power supply. The paper analyzes a high speed automatic reclosing on a 400 kv overhead transmission line. For data acquisition was used a Compact Digital Recorder (CDR). The data stored in the internal CDR memory were extracted on a PC by CDR Link for Windows program. The fault analysis was performed with Focus for Windows program. Key-Words: - overhead line, single-phase-to-ground fault, automatic reclosing, data acquisition, harmonic analysis 1 Introduction The main function of the power line protections is to minimize the influence of faults on power system operation. On High-Voltage (HV) and Extra-High-Voltage (EHV) transmission lines the majority of faults are typically single-phase-to-ground and around 90% of them are temporary in nature [1, 2]. Transient faults can be successfully cleared by the proper use of tripping and auto-reclosing. This de-energizes the line long enough for the fault source to pass and the fault arc to de-energize, then automatically recloses the line to restore service [3]. The reasons for applying auto-reclosing function can be summarized as follows [1, 4-10]: - minimizing the interruption of the supply to the customer; - maintenance of system stability and synchronism; - restoration of system capacity and reliability with minimum outage and least expenditure of manpower; - restoration of critical system interconnections; - restoration of service to critical loads; - higher probability of some recovery from multiple contingency outages; - reduction of fault duration, resulting in less fault damage and fewer permanent faults; - relief for system operators in restoration during system outages. When applying high speed auto-reclosing (HSAR) to lines with distance protection, simultaneous tripping at the both ends of the line is important. This is normally accomplished using signaling channels [2, 3]. Another method is using zone 1 extension scheme. In this method, zone one reach is normally set to cover 120% of line. When fault occurs anywhere in the protected line breakers at both ends are tripped simultaneously without time delay and reclosed. A contact from reclose relay is used to reset the zone to 80% of line so that if the fault is permanent, the breakers will be tripped based on the respective zone timers when reclosed [3, 8]. Further is analyzed a HSAR on 400 kv overhead transmission line (OTL) Sibiu in Mintia station. At the 400 kv OTL the major protections and automations are unitary incorporated in advanced digital relays: line distance protection terminal REL 521 and distance relay LZ96a. Among the most important functions of REL 521 could be mentioned: distance protection (ZM); teleprotection; automatic switch onto fault logic (SOTF); local acceleration logic (ZCLC); instantaneous non-directional phase overcurrent protection (IOCph); time delayed undervoltage (TUV) and time delayed overvoltge protection (TOV); disturbance recorder (DR); fault locator (FLOC); trip value recorder (TVR); autorecloser 1- and/or 3-phase, single or double circuit breakers [11]. The distance protection zones can operate, independently of each other, in directional mode (forward - zones 1, 2, 4, or reverse - zone 3) or non- ISBN:
2 directional mode (zone 5) [11]. Zone 1, 2 and 3 can issue phase selective signals, such as start and trip. Distance protection zone 5 has shorter operating time than other zones, but also higher transient overreach. It should generally be used as a check zone together with the SOTF or as a time delayed zone with time delay set longer than 100 ms [11]. This variation is recorded by the Compact Digital Recorder during the period: t recording = t pre + t fault + t post, (1) where t pre is the pre-fault recording time, t fault represents fault recording time, and t post is the postfault recording time. Fig. 1. Schematic presentation of the operating characteristic for one distance protection zone in forward direction Fig. 1 presents the operating characteristic for one distance protection zone in forward direction, where: Xph-e represents the reactive reach for phase-to-ground (earth) faults; Xph-ph represents the reactive reach for phase-to-phase faults; Rph-e is the resistive reach for phase-to-ground (earth) faults; Rph-ph is the resistive reach for phase-tophase faults; Zline is the line impedance. Independent reactive reach setting for phase-tophase and for phase-to-ground measurement secures high selectivity in networks. Simplified setting parameters reduce the complexity of necessary setting procedures and make the operating characteristic automatically more adjusted to the needs in combined networks with off-lines and cables. In case of a fault located close to the Sibiu South station, (fig. 2) the distance protection from Sibiu South will frame the fault in step 1 (zone ZM1- adjustment Z1 ) and will issue an impulse by means of the high-frequency installation (IMP ZM1). The distance protection from Mintia station will frame the fault in step 2 (zone ZM2-adjustment Z2) and would trigger delayed ( s). But, at reception of the signal from Mintia (that applies to the input IMP CR) and by checking the framing into zone ZM2, it will command the breaker s rapid triggering. Thus, the fault is rapidly cleared. When a disturbance occurs in electric stations, it takes place a variation of the analogue and numerical parameters. Fig. 2. Principle of the teleprotection permissive scheme Fig. 3. Recording time of the disturbance The data stored in the internal CDR memory were extracted on a PC by CDR Link for Windows program. The fault analysis was performed with Focus for Windows program [12]. 2 Summary of the Fault Report Generated by Focus Program The quantities (analogue and numerical) acquired by CDR can be graphically visualized with Focus for Windows program. The program provides, also, the phasor diagrams of voltages and currents, and their harmonic analysis [12]. Further is presented a summary of the fault report generated by Focus program in case of a HSAR on the 400 kv OTL Sibiu, in Mintia station. 2.1 Values of Pre-fault Quantities The total time allocated to record the pre-fault quantities was ms. ISBN:
3 In fig. 4, at t=-30 ms, the phase differences between the phase voltages are a little modified against the normal operation. The homopolar voltage and the homopolar current have high values (U0=111.8 kv, I0=1.344 ka). Marker 2 (at t=-30 ms) catches the incipient stage of a phase-to-ground fault on phase 2 (L2). 2.2 Values of Fault Quantities Fig. 4. Marker 2: t=-30 ms (pre-fault). Phasor diagrams of voltages and currents Is noticed a slight decrease of the voltage on phase 2 (UL2=218.2 kv) compared with the voltages on the other phases (UL1=236.4 kv, UL3=240.8 kv). The current on phase 2 (IL2=1.314 ka) has a higher value (IL1=331.2 A, IL3=401.2 A). Fig. 5. Analogue quantities in the time period t= ms Fig. 6. Marker 4: t=17 ms (fault). Phasor diagrams of voltages and currents The values measured at the moment t=17 ms (fig. 6) are framed within the fault period of the recording. At this moment is recorded a maximum value of the current on phase 2 (IL2=2.93 ka) and a voltage decrease on phase 2 (UL2=70.02 kv). One can notice a significant increase of the homopolar quantities (I0=3.597 ka, U0=294 kv), up to the limit when the high-voltage breaker s protections of OTL Sibiu are triggered. Analogue quantities in the time period t= ms are presented in fig. 5, and numerical quantities are presented in fig. 7. Markers 1 (t=-60 ms, fig. 7) and 2 (t=-30 ms, fig. 7) show that the OTL protections are in stand-by (pre-fault period). Marker 3 (t=-8 ms, fig. 7) is close to the trigger limit. In fig. 7, marker 4 (t=17 ms) indicates the start of distance protections: START L2 RE 1:1 start for group 1 of protections through the line distance protection terminal REL 521, phase L2; GEN. START 1:1 general start of distance protection REL 521; GEN. TRIP R1:1 trigger impulse sent by the distance protection REL 521 to the highvoltage breaker of OTL Sibiu, in Mintia station; DIST. TRIP 1:1 trigger of distance protection REL 521; START L2 LZ 1:1 start for group 2 of protections through the digital relay LZ96a, phase L2; GEN. START 1:1 general start of digital relay LZ96a; DIST. TRIP 1:1 trigger of digital relay LZ96a. ISBN:
4 Marker 5 (t=34 ms, fig. 7) indicates: PLC REC CH 0:1 trigger impulse issued by the distance protection REL 521 of the teleprotection channel, that sends a trigger impulse to the high-voltage breaker of Sibiu station. frequency impulse through teleprotection. Fig. 8. Marker 7 (t=1065 ms): reclosing impulses to the breakers 2.3 Values of Post-fault Quantities Fig. 9. Marker 10: t=1184 ms (post-fault). Phasor diagrams of voltages and currents Fig. 7. Numerical quantities in the time period t= ms. Start of distance protections Fault locator of REL 521 terminal use for the distance to fault calculation a line modelling algorithm, that takes into account the sources at both ends of the line. In this way, the influence of the load current, the infeed from the remote end and the fault resistance, can be compensated, resulting in a highly accurate calculation. Taking into account the RMS values of the phase currents and voltages, the distance is quantified from the place where the protection is mounted up to the fault place, and is equal by 24.2 km. In fig. 8, marker 7 (t=1065 ms) indicates AR ON REL/R 1:1, with the following functions: - sending of a reclosing impulse to the Sibiu OTL s breaker in Mintia; - sending of a reclosing impulse to the Mintia OTL s breaker in Sibiu, by emitting a high- At the moment t=1184 ms (fig. 9) small differences between RMS values of the phase voltages (UL1=239.6 kv, UL2=242.5 kv, UL3=239.9 kv) and RMS values of the phase currents (IL1=375.8 A, IL2=394.3 A, IL3= A) are noticed. The RMS value of the homopolar quantities are low (U0=37.58 kv, I0=42.23 A). Fig. 9 presents the end of the successful reclosing (+): the breaker is connected, and OTL Sibiu is in operation. Fig. 10. Time variation of harmonic components of the faulted phase voltage (UL2) ISBN:
5 Focus program allows the harmonic analysis of the voltages and currents up to 10-th order. Harmonic analysis of the faulted phase voltage (UL2) reveals the presence of the even and odd harmonics in the waveform (fig. 10 and fig. 11). currents per phases 1 and 3 (IL1 and IL3, fig. 12 and fig. 13) have great values. Fig. 13. Time variation of harmonic components of current IL3 Fig. 11. Time variation of harmonic components of the faulted phase voltage (UL2) Harmonic components of the faulted voltage are sudden increases at the time moments: t=-30 ms (fault occurrence), t=17 ms, t=34 ms (triggering of the line breakers), t=77 ms (secondary arc initiation), t=123 ms, t=320 ms (final arc extinction) and t=1083 ms (closing of the line breakers). In the time periods t= ms and t= ms all harmonics of faulted voltage exceed the compatibility limits [13]. The non-linearity of the electric arc distorts the voltage and current signals on the sound phases, because of electromagnetic and capacitive couplings of the faulted and the sound phases. Fig. 14. Time variation of THD[%] for currents waveforms In the time period t= ms Total Harmonic Distortion (THD) of currents IL1 and IL3 (fig. 14) exceed the compatibility limits [13]. Fig. 12. Time variation of harmonic components of current IL1 In the time period t= ms all harmonics of Fig. 15. Time variation of THD[%] for phase voltages waveforms ISBN:
6 Fig. 15 show that THD of phase voltages UL1 and UL3 have small values; THD of the faulted phase voltage UL2 has very great value, and exceed the compatibility limits, during the time periods t= ms and t= ms [13]. 3 Conclusion Fast clearing of EHV faults is essential to maintain power quality in an area, because events on the EHV system affect the underlying transmission and distribution systems. Benefits of successful high speed reclosing on EHV overhead transmission lines are: improved system stability, reducing the duration of fault arc, respectively disturbance time, and economics in system design. Are noticed especially the facilities offered by Focus program in analyzing the analogue and numerical quantities; the visualization of RMS values, phasor diagrams and harmonic analysis are in real time. Further the analysis of the disturbance report issued by the Focus program, can be determined the causes, amplitude and consequences of the appeared disturbance. References: [1] ***, Automatic Reclosing Transmission Line Applications and considerations ( [2] IEEE Power System Relaying Committee Working Group, Single phase tripping and auto reclosing of transmission lines-ieee Committee Report, IEEE Transactions on Power Delivery, Vol. 7, January 1992, pp [3] G. Kobet, et al., Justifying pilot protection on transmission lines, 63rd Annual Conference for Protective Relay Engineers, College Station, TX, March 29 -April , pp [4] Z. Radojevi, J. Shin, New digital algorithm for adaptive reclosing based on the calculation of the faulted phase voltage total harmonic distortion factor, IEEE Transactions on Power Delivery, Vol. 22, Issue 1, 2007, pp [5] M. E. Hamedani Golshan and N. Golbon, Detecting secondary arc extinction time by analyzing low frequency components of faulted phase voltage or sound phase current waveforms, Electrical Engineering, Vol. 88, 2005, pp [6] M. Jannati, B. Vahidi, S.H. Hosseinian, S.M. Ahadi, A novel approach to adaptive single phase auto-reclosing scheme for EHV transmission lines, International Journal of Electrical Power & Energy Systems, Vol. 33, Issue 3, March 2011, pp [7] R. Aggarwal, A. Johns, Y. Song, R. Dunn, D. Fitton, Neural-network based adaptive singlepole auto re-closure technique for EHV transmission systems, IEE Proceeding on Generation, Transmission and Distribution, Vol. 141, Issue 2, 1994, pp [8] E. A. Frimpong and P. Y. Okyere, A Review of Adaptive Autoreclosure Techniques, Indian Journal of Computer Science and Engineering, Vol. 1, Issue 3, 2010, pp [9] N. Sh. Rasool, M. F. Al-Kababjie, ANN Adapting Auto_Reclosing Relay In a Simulated Iraqi Super Grid, Proceedings of the 11th WSEAS International Conference on Automatic Control, Modelling and Simulation, (ACMOS '09), Istanbul, Turkey, May 30 - June 1, 2009, pp [10] N. Svigir, S. Tesnjak, An Approach to Selection of Basic Parameters Relevant for Automatic Reclosing Technique in Electric Power Systems, 7th WSEAS International Conference on Electric Power Systems, High Voltages, Electric Machines, Venice, Italy, November 21-23, 2007, pp [11] ***, REL 521 Line distance protection terminal, ABB Technical brochure, [12] ***, Focus for Windows v2.0, TELECOMM, [13] IEC/TR , EMC, Part 3-6: Limits Assessment of Harmonic Emission Limits for the Connection of Distorting Installations to MV, HV and EHV Power Systems (revision), ISBN:
Study of a phase-to-ground fault on a 400 kv overhead transmission line
IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Study of a phase-to-ground fault on a 400 kv overhead transmission line To cite this article: A Iagr et al 2018 IOP Conf. Ser.:
More informationImproving Transmission Line Performance using Transient Based Adaptive SPAR
Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON ), Cairo University, Egypt, December 19-21, 2, Paper ID 249. Improving Transmission Line Performance using Transient
More informationNeutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping
Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice
More informationImplementation of a Numerical Distance Relay for the 110kV Electric Lines
Implementation of a Numerical Distance Relay for the 110kV Electric Lines GABRIEL NICOLAE POPA SORIN DEACONU CORINA MARIA DINIŞ ANGELA IAGĂR Department of Electrotechnical Engineering and Industrial Informatics
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationPower System Protection Where Are We Today?
1 Power System Protection Where Are We Today? Meliha B. Selak Power System Protection & Control IEEE PES Distinguished Lecturer Program Preceding IEEE PES Vice President for Chapters melihas@ieee.org PES
More informationAdaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers
Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers 70 th Annual Conference for Protective Relay Engineers Siemens AG 2017 All rights reserved. siemens.com/energy-management
More informationA short introduction to Protection and Automation Philosophy
Training Center A short introduction to Protection and Automation Philosophy Philippe Goossens & Cédric Moors Training Center Contents Definitions and basic concepts Differential and distance protection
More informationAutomatic reclosing function for high voltage networks
Automatic reclosing function for high voltage networks Budapest, December 2010. Automatic reclosing function for high voltage networks The HV automatic reclosing function for high voltage networks can
More informationLine distance protection terminal
Line distance protection terminal REL 521*2.0 Page 1 Issued May 2002 Changed since October 1998 Data subject to change without notice (SE 95 02 16) Features Line distance functionality comprises; - simultaneous
More informationVoltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment
s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering
More informationEarth Fault Protection
Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
More informationPSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)
1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationTransmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes
Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes Transmission Line Protection Topics Primary/backup protection Coordination Communication-based
More informationDistance Relay Response to Transformer Energization: Problems and Solutions
1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering
More informationPower Quality and Digital Protection Relays
Power Quality and Digital Protection Relays I. Zamora 1, A.J. Mazón 2, V. Valverde, E. Torres, A. Dyśko (*) Department of Electrical Engineering - University of the Basque Country Alda. Urquijo s/n, 48013
More informationPROTECTION SIGNALLING
PROTECTION SIGNALLING 1 Directional Comparison Distance Protection Schemes The importance of transmission system integrity necessitates high-speed fault clearing times and highspeed auto reclosing to avoid
More informationAdaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers
Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers Jörg Blumschein 1), Yilmaz Yelgin 1), Andrea udwig 2) 1) Siemens AG, Energy Management Division 2) 50Hertz Transmission
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationGrid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017
Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the
More informationSimulation Results on the Currents Harmonics Mitigation on the Railway Station Line Feed
Proceedings of the 7th WSEAS Int. Conf. on Signal Processing, Computational Geometry & Artificial Vision, Athens, Greece, August 4-6, 7 69 Simulation Results on the Currents Harmonics Mitigation on the
More informationUsing a Multiple Analog Input Distance Relay as a DFR
Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at
More informationAn Analogical Distance Relay for the 110kV Electric Lines
An Analogical Distance Relay for the 110kV Electric Lines GABRIEL NICOLAE POPA SORIN DEACONU CORINA MARIA DINIŞ ANGELA IAGĂR Department of Electrotechnical Engineering and Industrial Informatics Politechnica
More informationTransmission Protection Overview
Transmission Protection Overview 2017 Hands-On Relay School Daniel Henriod Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with
More informationE N G I N E E R I N G M A N U A L
1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn
More informationReducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems
Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationSAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS
SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS A. Nikander*, P. Järventausta* *Tampere University of Technology, Finland, ari.nikander@tut.fi,
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities
More informationVALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK
VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK Eduardo MARTÍNEZ eduardo_martinez@fcirce.es Samuel BORROY sborroy@fcirce.es Laura
More informationTS RES - OUTSTANDING ISSUES
TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next
More information- Four step residual overcurrent protection
Page 1 Revision: - Issued: March 2003 Data subject to change without notice )HDWXUHV Open terminal with extensive configuration possibilities and expandable hardware design to meet specific user requirements
More informationA NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *
Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM
More information- Four step residual overcurrent protection
/LQHGLVWDQFHSURWHFWLRQ WHUPLQDO Page 1 Revision: - Issued: March 2003 Data subject to change without notice )HDWXUHV Open terminal with extensive configuration possibilities and expandable hardware design
More informationAnalysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar
Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:
More informationPQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.
General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationII. RESEARCH METHODOLOGY
Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College
More informationPowerful software PC tool-box for monitoring, evalution and user configuration
3URWHFW,7 /LQHGLVWDQFH SURWHFWLRQWHUPLQDO Page 1 Revision: A Issued: October 2003 Data subject to change without notice )HDWXUHV Open terminal with extensive configuration possibilities and expandable
More informationSmart Grid Where We Are Today?
1 Smart Grid Where We Are Today? Meliha B. Selak, P. Eng. IEEE PES DLP Lecturer melihas@ieee.org 2014 IEEE ISGT Asia, Kuala Lumpur 22 nd May 2014 2 Generation Transmission Distribution Load Power System
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationGRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS
GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS Hannu LAAKSONEN ABB Oy Finland hannu.laaksonen@fi.abb.com ABSTRACT Medium-voltage (MV) network short-circuit protection operation time delays have
More informationUNIT-4 POWER QUALITY MONITORING
UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and
More informationFunctioning Analysis of a High Frequency Electro Thermal Installation with Electromagnetic Induction Using PSCAD-EMTDC Tool
Functioning Analysis of a High Frequency Electro Thermal Installation with Electromagnetic Induction Using PSCAD-EMTDC Tool RALUCA ROB *, IOAN SORA **, CAIUS PANOIU *, MANUELA PANOIU *, * Electrical Engineering
More informationData. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner
Digital Protective Relay Dr Murari Mohan Saha ABB AB KTH/EH2740 Lecture 3 Introduction to Modern Power System Protection A digital protective relay is an industrial microprocessor system operating in real
More informationUPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS
UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS 1 B. RAMESH, 2 K. P. VITTAL Student Member, IEEE, EEE Department, National Institute of Technology Karnataka,
More informationELECTROMAGNETIC POLLUTION PRODUCED BY THE INDUSTRIAL FREQUENCY CRUCIBLE INDUCTION FURNACES IN THE POWER SUPPLY NETWORK
1 2 ELECTROMAGNETIC POLLUTION PRODUCED BY THE INDUSTRIAL FREQUENCY CRUCIBLE INDUCTION FURNACES IN THE POWER SUPPLY NETWORK Angela IAGĂR 1, Ioan ŞORA 2, Caius PĂNOIU 1, Cristian ABRUDEAN 1 1 POLITEHNICA
More informationUV3 _ Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High)
1MRS752333-MUM Issued 10/1997 Version: H/23.06.2005 Data subject to change without notice Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High) Contents 1. Introduction...
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationPower Quality Requirements for Connection to the Transmission System
Power Quality Requirements for Connection to the Transmission System Revision: 1.0 Date: September 2015 Introduction and Purpose of this Document The purpose of this document is to provide clarity to Customers
More informationProtection of Extra High Voltage Transmission Line Using Distance Protection
Protection of Extra High Voltage Transmission Line Using Distance Protection Ko Ko Aung 1, Soe Soe Ei Aung 2 Department of Electrical Power Engineering Yangon Technological University, Insein Township
More informationPhase earthing system - method for faulty phase selection with phase-to-earth faults. Ari Nikander Tampere University of Technology
Phase earthing system - method for faulty phase selection with phase-to-earth faults Ari Nikander Tampere University of Technology - 2 - Preface This report has been done as a part of the research work
More informationT 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers
Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory
More informationWhat s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines
What s New in C37.113 TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines This paper is a product of the IEEE PSRC D36 Working Group. The working group consisted of the following
More informationTable of Contents. Introduction... 1
Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...
More informationStarSine Power Quality Products
StarSine Power Quality Products Medium Voltage Static Voltage Regulator ( MV SVR ) MV SVR PROTECTS THE WHOLE FACILITY LOADS FROM VOLTAGE SAGS CAUSED BY UTILITY GRID FAULTS Voltage sags, whether due to
More informationTransient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines
Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Presenter Mark McVey C4/B5.41 INTERNATIONAL COUNCIL ON LARGE
More informationMODEL POWER SYSTEM TESTING GUIDE October 25, 2006
October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date
More informationTD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers
Secondary Injection Relay Test Set Designed for testing relays and transducers Two current outputs to test differential relays Convertible current and voltage generator With phase angle shifter Frequency
More informationEARTH-FAULT ANALYSIS OF THE MEDIUM VOLTAGE NETWORK GROUNDED WITH LOW VALUE RESISTANCE
EARH-FAUL ANALYSIS OF HE MEDIUM VOLAGE NEWORK GROUNDED WIH LOW VALUE RESISANCE Zoran Ristanovic EPS - JP Eletrovojvodina Bul. Oslobodjenja 100, Novi Sad(Yugoslavia) el: 381 1 7 64 - Fax: 381 1 3 668 -
More informationProtection of Electrical Networks. Christophe Prévé
Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé
More informationIslanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current
http:// and Detection of Distributed Generation using Negative Sequence Component of Current Doan Van Dong Danang College of Technology, Danang, Vietnam Abstract - There is a renewed interest in the distributed
More informationCatastrophic Relay Misoperations and Successful Relay Operation
Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations
More informationImprovement of Electricity Distribution Services Using a DVR with a Constant DC Voltage Source Instaled in MV Connection Substations
Improvement of Electricity Distribution Services Using a DVR with a Constant DC Voltage Source Instaled in MV Connection Substations Gheorghe Ioan Nicolaescu, Horia Andrei, Stefan Radulescu Electrical
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationINTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs
INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection
More informationA New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines
A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines M.M. Saha, T. Einarsson, S. Lidström ABB AB, Substation Automation Products, Sweden Keywords: Adaptive distance protection,
More informationEVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION
EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech
More informationTransformer protection IED RET 670
Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth
More informationRenewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA
Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std
More informationT-68 Protecting Your Equipment through Power Quality Solutions
T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. 2 Agenda What
More informationSECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED
SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014
More informationDynamic Model Of 400 Kv Line With Distance Relay. Director Research, The MRPC Company, Hyderabad, India 2
Dynamic Model Of 400 Kv Line With Distance Relay Ramleela Khare 1, Dr Filipe Rodrigues E Melo 2 1 Director Research, The MRPC Company, Hyderabad, India 2 Assoc. Professor Commerce, St. Xavier s College
More informationProtective Relaying for DER
Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed
More information- 1 - NEUTRAL CONNECTION TO EARTH IN MEDIUM VOLTAGE NETWORKS: OPERATION EXPERIENCE IN ENEL
NEUTRAL CONNECTION TO EARTH IN MEDIUM VOLTAGE NETWORKS: OPERATION EXPERIENCE IN ENEL B. Ceresoli CESI S.p.A. - Italy A. Cerretti ENEL Distribuzione S.p.A - Italy E. De Berardinis CESI S.p.A - Italy A.
More informationT 1000 PLUS Secondary Injection Relay Test Set
Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory
More informationEvaluating the activation of auto recloser relays in power distribution grid of Masjed Soleiman City
EUROPEAN ACADEMC RESEARCH Vol. V, ssue 2/ May 2016 SSN 2286-4822 www.euacademic.org mpact Factor: 3.4546 (UF) DRJ Value: 5.9 (B+) Evaluating the activation of auto recloser relays in power distribution
More informationT 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers
Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator High power outputs Large graphical display Compact
More informationHamdy Faramawy Senior Application Specialist ABB Sweden
Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy
More informationIntermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)
Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities
More informationDRTS-6. DRTS-6 has been designed to test: DRTS-6. Advanced Protection Relay Test Set and Measurement System
DRTS-6 Advanced Protection Relay Test Set and Measurement System MULTI-TASKING EQUIPMENT DESIGNED FOR TESTING PROTECTION RELAYS, ENERGY METERS, TRANSDUCERS POWERFUL AND LIGHTWEIGHT HIGH ACCURACY: BETTER
More informationSequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network
Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria
More informationDC current interruption tests with HV mechanical DC circuit breaker
http: //www.cigre.org CIGRÉ A3/B4-124 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 DC current interruption tests with HV mechanical DC circuit
More informationPower Quality Basics. Presented by. Scott Peele PE
Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement
More informationAPPLICATION OF MULTI-FREQUENCY ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK
24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 967 APPLICATION OF MULTI-FREQUENC ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK Janne
More informationBED INTERCONNECTION TECHNICAL REQUIREMENTS
BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2
More informationRESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS
24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 97 RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS Pengfei WEI Yonghai XU Yapen WU Chenyi
More informationHow to maximize reliability using an alternative distribution system for critical loads
White Paper WP024001EN How to maximize reliability using an alternative distribution system for critical loads Executive summary The electric power industry has several different distribution topologies
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationHarmonic Distortion Levels Measured at The Enmax Substations
Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned
More informationApplication for A Sub-harmonic Protection Relay. ERLPhase Power Technologies
Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic
More informationCOPYRIGHTED MATERIAL. Index
Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,
More informationNo. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A
SHINSUNG Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A Enhanced Self Healing System General SILO is 3 phase, solid insulated load break switch (LBS) and vacuum interruption
More informationHV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point
2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION
More informationTexas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event
Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event
More informationManjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3
Application of to alleviate voltage sag and swell Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3 123 (Electrical Engineering, AGPCE Nagpur/ RTMNU, INDIA) ABSTRACT : This paper deals with modelling
More informationFault Location Using Sparse Wide Area Measurements
319 Study Committee B5 Colloquium October 19-24, 2009 Jeju Island, Korea Fault Location Using Sparse Wide Area Measurements KEZUNOVIC, M., DUTTA, P. (Texas A & M University, USA) Summary Transmission line
More informationKončar TMS - Bushing monitoring
Končar TMS - Bushing monitoring Many recent studies have shown that bushing failure is one of the most common causes of transformer failure. Thus need for bushing diagnostic and monitoring system has risen.
More information