1 T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved.
2 2 Agenda What is Power Quality? Importance of Power Quality to Industrial Users Power Quality Events & Voltage Sags Voltage Sag Protection
3 3 Power Quality vs. Power Reliability Power Reliability: Continuity of electric power delivery measured by the number and duration of power outages (Zero voltage) Outages are tracked by Utilities Power Reliability can be as high as % availability Power Quality: Related to fluctuations in electricity, such as momentary interruptions, voltage sags or swells, flickering lights, transients, harmonic distortion and electrical noise Fewer such incidents indicate greater power quality Events go mostly untracked by Utilities Sag & Momentary events can take out a process as many as times per year The Grid is designed for Reliability, not Quality
4 Power Quality Frequency is regional Determined by HV & EHV network generators Problems are rare Voltage is area-wide Determined by MV distribution network Problems occur randomly, but with regularity Current is local Determined by facility loads Problem loads can be identified and resolved Source: DTE Energy website 4 Copyright 2012 Rockwell Automation, Inc. All rights reserved.
5 Utility Power Properties of AC Grid Not always ideal sinusoidal voltages! Highly interconnected Transformer and line impedances between generators and loads Terminal voltage drops with load current System faults cause significant voltage sags (dips) Most wiring is overhead Susceptible to lightning, animals, wind-blown tree branches, etc. Source: NPR: Power Hungry: Reinventing The U.S. Electric Grid May 1, 2009 Insulation fails, equipment fails 5 Copyright 2012 Rockwell Automation, Inc. All rights reserved.
6 6 Power Quality Problems All have physical causes
7 7 Agenda What is Power Quality? Importance of Power Quality to Industrial Users Power Quality Events & Voltage Sags Voltage Sag Protection
8 Electrical Equipment Designed Assuming Power Quality Operate with input ac voltage variation of 10% Possible new requirements: Operate through some voltage sags SEMI F47 IEC Present a unity Power Factor: Current phase angle near zero Current harmonic distortion low 8 Copyright 2012 Rockwell Automation, Inc. All rights reserved.
9 Impact of Power Quality Events Possible Agency, Utility, or Facility Requirements Power Factor correction (current phase angle) Harmonic current limits Load equipment mis-operation Voltage sags and momentary interruptions Voltage distortion (harmonics, notching) Voltage imbalance or single-phasing High-frequency voltage transients Load equipment damage High-voltage transients Current inrush following voltage sag Facility infrastructure damage High-voltage transients Current inrush following voltage sag Overheating due to current harmonics 9 Copyright 2012 Rockwell Automation, Inc. All rights reserved.
10 Consumer is Responsible for Power Quality Utility cannot provide perfect power quality and are not required to. (e.g., Wisconsin PSC ) Customers having equipment or operations that are sensitive to such voltage fluctuations may find it necessary to install, at their own expense, power conditioning equipment or other modifications Job is to Keep the lights on. Goals Deliver maximum energy through the existing infrastructure Maintain +/-10% (on average) voltage at service entrance Minimize outages longer than 2-5 minutes Hz, when averaged over 24 hours Keep large industrial customers satisfied Minimize large customers disrupting neighbors power quality The utility is responsible for reliability, not quality of power.the customer is responsible for protecting their sensitive equipment at their own expense 10 Copyright 2012 Rockwell Automation, Inc. All rights reserved.
11 11 Agenda What is Power Quality? Importance of Power Quality to Industrial Users Power Quality Events & Voltage Sags Voltage Sag Protection
12 Power Quality Issues Voltage sag (dip) and Momentary interruption High voltage transients (spikes) Current distortion (harmonics) Voltage distortion and voltage flicker caused by distorted current loads Voltage unbalance EPRI (Electrical Power Research Institute) Monitored 300 sites for 2+ years. 92% of all events were voltage sags under 2 seconds 4% of event interruptions from 2 seconds to 10 minutes Voltage notching Uncommon issues in the U.S. and high-tech. parks: brownout voltage swell frequency variation Poor grounding 12 Copyright 2012 Rockwell Automation, Inc. All rights reserved.
13 13 Voltage Sag (Dip) Characterization Sag - RMS voltage reduction between 1/2 cycle - 60 sec Magnitude and Duration 1 Duration: 4 Cycles Magnitude: 60% Remaining
14 Voltage Sag 90% Magnitude (per unit) Duration (ms) Copyright 2012 Rockwell Automation, Inc. All rights reserved. 14
15 Why mostly brief sags and interruptions? 12 kv 69 kv Radial Distribution F kVA Reclosing breakers 20 MVA " C" 480 VOLTS THREE PHASE FAULT F 2 " B" " A" V = V s Z line *I F 3 Fault results in short voltage sags and interruptions for most customers, affecting up to 200 mile radius VOLTAGE BEGIN FAULT F2 OPENS VOLTAGE AT "C" AND ON F1 & F3 VOLTAGE AT "B" TIME F2 CLOSES V=0.67 p.u. V=0.40 p.u. F2 OPENS FAULT CLEARS F2 CLOSES 15 Copyright 2012 Rockwell Automation, Inc. All rights reserved.
16 Why Sag Durations are short Clearing Time in Cycles Type of Fault Typical Minimum Typical Time Delay Number of Retries Clearing Device Expulsion Fuse to 60 None Current Limiting Fuse 0.25 or less 0.25 to 6 None Electronic Recloser 3 1 to 30 0 to 4 Oil Circuit Breaker 5 1 to 60 0 to 4 SF 6 or Vacuum Breaker to 60 0 to 4 Source: IEEE Std Copyright 2012 Rockwell Automation, Inc. All rights reserved.
17 Sags at High-Tech Mfg. Sites Very few outages, still many sags! 1000 sag events from 15 Semi plants Avg. 5.4 events below CBEMA per year with transmission-level service! SEMI F47 source: International SEMATECH & EPRI, 1999
18 Impact of Voltage Sags Sensitivity of various 3-ph. 4kW drives to single-phase sag (rated speed, torque) [Djokic] 18 Copyright 2012 Rockwell Automation, Inc. All rights reserved.
19 Impact of Voltage Sags AC Relay Voltage Sag Tolerance Curves % of Nominal Voltage Duration of Sag (milliseconds) Upper range Average Lower Range Source: IEEE Std Copyright 2012 Rockwell Automation, Inc. All rights reserved.
20 Data Corruption Source: Djokic
21 IEEE P1668 a new standard Recommended Practice for Voltage Sag and Interruption Ride-through Testing for End-use Electrical Equipment Less than 1,000 Volts A standard for the response of electrical equipment to voltage sags Expected to include: Guidance for evaluation of equipment sensitivity to voltage sags and interruptions Minimum performance criteria to specify during the purchasing process Levels of performance for acceptance of the product Voltage tolerance curves for three-phase equipment: more useful than CBEMA or ITIC
22 22 Effect of Voltage Sags on Equipment Most common effect is equipment drops offline PLC shutdown Open contact or relay (As little as 80% remaining voltage for 1 Cycle) A secondary effect is that when voltage returns, high current inrush can occur because the Softcharge circuit is bypassed RF Amplifiers, Gradient Amplifiers, and Low Voltage Power Supplies subjected to repeated hits Fail. Typical rectifier circuit diagram: Voltage SAGS can shut-down and/or damage equipment!
23 23 Voltage Sags Effect Equipment Example: Inrush current measured for 1kVA electronic load Normal Inrush Inrush after Sag Volts Volts Amps Peak inrush 10A Soft-charge circuit is active Amps Peak inrush 50A Soft-charge circuit bypassed Note the scale change necessary to get the sagged results on the same page!
24 Only some machines shut down. Why? Fabrication or Assembly Line Layout: 480-b Machine 1 Machine 2 Machine 3 Machine 4 Machine 5 Machine a Machine power distribution and power supplies vary: L1 L2 L3 :Y Tranf. Rect. L1 N L2 N Tranf. Tranf. Controls Power Rect. Rect. Controls Power Controls Power L1 L2 L2 L3 L3 L1 Tranf. Tranf. Tranf. Rect. Rect. Rect. Controls Power Controls Power Controls Power L3 N Tranf. Rect. Controls Power
25 Detection of Power Quality Events Monitoring is Key to Knowing the Local Power Quality I-Sense, I-Grid Voltage Monitoring I-Sense voltage monitor device I-Grid network of monitors and database servers information and notification service & text message notification in real time Web summary, available from anywhere PDF Reports
26 I-Grid I-Sense monitors record & report PQ event data via the Internet Use Web browser to: View event details Manage accounts and monitors Generate reports and export data I-Sense Owners Internet I-Grid Servers & Database Web Utility Engineer Facility Engineer Real-time notifications Report delivery Other users
27 27 Agenda What is Power Quality? Importance of Power Quality to Industrial Users Power Quality Events & Voltage Sags Voltage Sag Protection
28 28 28 Sag Correction Solutions DySC Protection Stand-by UPS Protection CVT Protection On-Line UPS Protection
29 29 DySC and UPS Correction Capability
30 30 UPS Product Offering
31 31 DySC (Dynamic Sag Corrector) DySC (pronounced Disk ) is an adaptive power supply that optimizes the remaining power during a sag by using patented inverter technology to compensate for the sag thereby maintaining an uninterrupted flow of optimal power to the load thus maximizing uptime, minimizing inventory loss and reducing maintenance costs Up to 5 seconds of ride through U.S. and International voltages available Scalable solution MiniDySC (single-phase; kva) ProDySC (3-phase; kva) MegaDySC (3-phase; kva)
32 32 DySC - Normal Operation Utility DySC Auto By-Pass Static Switch DSP Controller Load Cross- Coupling Transformer Power Conversion Rectifier Inverter Core Component DSP Controller Static Switch (99% efficient) Cross-Coupling Transformer Power Conversion Core Automatic By-Pass Activity Constantly monitors incoming power, system integrity and load Closed. Sends power directly to the load Idle Idle Idle Normal Operation - The DySC monitors power quality continuously, while the power electronics are in standby 99.99% of the time
33 33 DySC - Voltage Event Utility DySC Auto By-Pass Static Switch DSP Controller Load Cross- Coupling Transformer Power Conversion Rectifier Inverter Core Component DSP Controller Static Switch (99% efficient) Cross-Coupling Transformer Power Conversion Core Automatic By-Pass Activity Detects the leading edge of a voltage sag, immediately routing power thru the C-C Transformer and Power Conversion Core Open Pulls additional power from the grid Rectifies and inverts to recreate a true sinusoidal Output Idle DySC is On in under 2 milliseconds and recreates a true sinusoidal output
34 34 DySC Operation Normal Operation (Monitoring) Static Switch ON, Highly efficient Power electronics OFF Capacitors charged & ready No thermal cycling, long life Low maintenance Voltage Sag Correction 1-2 millisec. detection Static switch OFF Power Electronics ON, to produce corrected sinusoidal load voltage Energy from capacitors needed only for sags below 50% V = 100% V = 60% 167% 67% 167% 100% (V = 40%) patented V = 100% 100% LOAD 100% Example: voltage sag to 60%, full load We keep load voltage at 100%, so load power remains 100% Input Current rises briefly to (100% / 60%) = 167% Load energy comes from ac input, not from capacitors! Static bypass 99.99% of the time Corrects voltage by maintaining power flow (P = V x I) Most of the time the DySC is in a monitoring mode
35 35 DySC Sag Correction 330 kva MegaDySC responding to 3-phase 50% voltage sag, duration 4.5 seconds input waveforms output waveforms
36 36 DySC Interruption Correction input rms voltage 330 kva MegaDySC-ER 3-phase interruption for 250 ms (15 cycles) 90% output rms voltage
37 For More Information or Questions Power Quality at Automation Fair 2012 Essential Components (Booth 127): Protection Solutions Energy Management (Booth 541): Power Quality Monitoring Backroom Session: Hands-on DySC and I-Sense / I-Grid More information available at Booths
38 Thank you for your attention. Questions? Follow ROKAutomation on Facebook & Twitter. Connect with us on LinkedIn. Copyright 2012 Rockwell Automation, Inc. All rights reserved.
ECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 7 1 Today Sags and short interruptions Some Homework 2 pointers
More informationMinimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners
Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners IEEE Canada Webinar Presentation May 21, 2008 Bob Hanna, FIEEE, P.Eng. RPM Engineering Ltd. www.rpm-eng.com David
More informationElectric Power Quality: Voltage Sags Momentary Interruptions
Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage
More informationPower Quality Basics. Presented by. Scott Peele PE
Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement
More informationPower Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron
Power Quality and Circuit Imbalances 2015 Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Summary of IEEE 1159 Terms Category Types Typical Duration
More informationPOWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION
POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014
More informationPower Quality Symptoms What Is Normal? Power Quality Approach. Other Power Quality Solutions
April 25, 2017 Mike Carter Power Quality Symptoms What Is Normal? Power Quality Approach Find and fix Ride-through Solutions Protection/Compensation Schemes Other Power Quality Solutions What Can Go Wrong?
More informationECE 528 Understanding Power Quality. Paul Ortmann (voice) Lecture 6
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 6 1 Today more on voltage sags Motor starting mitigation Impacts
More informationManaging Power Quality Issues
Managing Power Quality Issues Questline Academy November 4, 2015 Mike Carter Justin Kale 2 Economic Value Productivity Customer Confidence How often do you deal with power quality problems at your facility?
More informationRoadmap For Power Quality Standards Development
Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel
More informationFundamentals of Power Quality
NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»
More informationPQ Monitoring Standards
Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality
More informationStarSine Power Quality Products
StarSine Power Quality Products Medium Voltage Static Voltage Regulator ( MV SVR ) MV SVR PROTECTS THE WHOLE FACILITY LOADS FROM VOLTAGE SAGS CAUSED BY UTILITY GRID FAULTS Voltage sags, whether due to
More informationIntroduction to Harmonics and Power Quality
NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»
More information1C.6.1 Voltage Disturbances
2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope The purpose of this document is to state typical levels of voltage disturbances, which may be encountered by customers
More informationPQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.
General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand
More informationAn Introduction to Power Quality
1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger
More informationReducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems
Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant
More informationUNDERSTANDING POWER QUALITY
Technical Note No. 1 June 1998 UNDERSTANDING POWER QUALITY This Technical Note describes the range of problems, what causes them, what they affect and what could be done to manage them. Integral Energy,
More informationProtection from Voltage Sags and Swells by Using FACTS Controller
Protection from Voltage Sags and Swells by Using FACTS Controller M.R.Mohanraj 1, V.P.Suresh 2, G.Syed Zabiyullah 3 Assistant Professor, Department of Electrical and Electronics Engineering, Excel College
More informationPower Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss
Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de
More informationPOWER QUALITY MONITORING - PLANT INVESTIGATIONS
Technical Note No. 5 January 2002 POWER QUALITY MONITORING - PLANT INVESTIGATIONS This Technical Note discusses power quality monitoring, what features are required in a power quality monitor and how it
More informationPower Quality Monitoring and Power Metering Tutorial
Power Quality Monitoring and Power Metering Tutorial Power generation and transmission today are accomplished using three phase alternatingcurrent. To understand electrical power quality monitoring and
More informationPOWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER
POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,
More informationEmicon Engineering Consultants L.L.C.
Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com
More informationHarmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.
Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 9 POWER QUALITY Power quality (PQ) problem = any problem that causes
More informationPowerMonitor 5000 Family Advanced Metering Functionality
PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation.
More informationReliability and Power Quality Indices for Premium Power Contracts
Mark McGranaghan Daniel Brooks Electrotek Concepts, Inc. Phone 423-470-9222, Fax 423-470-9223, email markm@electrotek.com 408 North Cedar Bluff Road, Suite 500 Knoxville, Tennessee 37923 Abstract Deregulation
More informationUtility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:
Utility Systems Technologies, Inc. Sag Fighter TM Deep Voltage Sag Protection: D e e p Vo l t a g e S a g P r o t e c t i o n For three phase application: Q u a l i t y P o w e r. B e t t e r B u s i n
More informationPower Quality Analysers
Power Quality Analysers Review of Power Quality Indicators and Introduction to Power Analysers ZEDFLO Australia 6-Mar-2011 www.zedflo.com.au Power Quality Indicators Review of main indicators of electrical
More informationAcknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.
Preface p. xv Acknowledgements p. xix Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p. 6 Power Quality Monitoring p. 7 Power
More informationCase studies from operation of a nationwide PQ&R monitoring system
Case studies from operation of a nationwide PQ&R monitoring system BY WILLIAM E. BRUMSICKLE, DEEPAK M. DIVAN, GLEN A. LUCKJIFF, JOHN W. FREEBORG, & ROGER L. HAYES 48 DIGITALVISION, LTD. I NDUSTRIAL AND
More informationGrid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017
Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the
More informationAnalysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar
Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:
More informationEE 2028 POWER QUALITY
A Course Material on EE 2028 POWER QUALITY By Mr. R.RAJAGOPAL ASSISTANT PROFESSOR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING SASURIE COLLEGE OF ENGINEERING VIJAYAMANGALAM 638 056 QUALITY CERTIFICATE
More informationahead of time SAG Compensator
ahead of time VOLTAGE IS NEVER PERFECT Modern industry is becoming more automated and the sensitivity of processes to power quality events is increasing. It is generally recognized that quality is an important
More informationMitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)
Research Journal of Engineering Sciences ISSN 2278 9472 Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Abstract Srishti Verma * and Anupama Huddar Electrical Engineering
More informationAnalysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 36-41 Analysis, Modeling and Simulation of Dynamic Voltage
More informationEffects of Transformer Connection on Voltage Sag Characterization
Effects of Transformer Connection on Voltage Sag Characterization Parijat Deb 1, Amit Gupta 2 ¹PG Scholar, Gyan Ganga College of Technology, Jabalpur, M.P (India) 2 Asst.Professor, Gyan Ganga College of
More informationNotes 1: Introduction to Distribution Systems
Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission
More informationENGINEERING DATA SUBMITTAL For the Interconnection of Generation System
WHO SHOULD FILE THIS SUBMITTAL: Anyone in the final stages of interconnecting a Generation System with Nodak Electric Cooperative, Inc. This submittal shall be completed and provided to Nodak Electric
More informationPower Quality: Is my power good or bad?
How to use the PowerSight PS4500 Power Quality Analyzer to check your power quality. At Summit Technology we are often asked for advice on how to check power quality. Often the situation begins with a
More informationAmelioration of Power Quality in Isolated Power Systems
International Journal of Scientific and Research Publications, Volume 2, Issue 4, April 2012 1 Amelioration of Power Quality in Isolated Power Systems I.Kumaraswamy, W.V.Jahnavi, P.Ramesh Department of
More informationEFFICIENT POWER QUALITY: AN APPROACH TO ENERGY CONSERVATION
EFFICIENT POWER QUALITY: AN APPROACH TO ENERGY CONSERVATION Nirmal Singh 1, Manish Kumar Jain 2 Neeru Goyal 3, Prashant Kumar Tayal 4 1,4 Faculty,Department of Electrical Engg., Dr.K.N. Modi University,
More informationPOWER QUALITY AND SAFETY
POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION
More informationPower Quality Improvement using Hysteresis Voltage Control of DVR
Power Quality Improvement using Hysteresis Voltage Control of DVR J Sivasankari 1, U.Shyamala 2, M.Vigneshwaran 3 P.G Scholar, Dept of EEE, M.Kumarasamy college of Engineering, Karur, Tamilnadu, India
More informationII. RESEARCH METHODOLOGY
Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College
More informationThere s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI
There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI OVERVIEW In the present business climate, companies are under constant pressure to increase profitability by increasing productivity, maximizing
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationMITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)
VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim
More informationThe development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08
The development of the SA grid code on Power Quality emission Dr. Gerhard Botha 2017/08/08 Overview What is the Grid Code? What is Power Quality? Power Quality Management Principles Differences Challenges
More informationECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 19 1 Today Flicker Power quality and reliability benchmarking
More informationGeneration Interconnection Requirements at Voltages 34.5 kv and Below
Generation Interconnection Requirements at Voltages 34.5 kv and Below 2005 March GENERATION INTERCONNECTION REQUIREMENTS AT 34.5 KV AND BELOW PAGE 1 OF 36 TABLE OF CONTENTS 1. INTRODUCTION 5 1.1. Intent
More informationThe seven types of power problems
Computing & Software The seven types of power problems by Joseph Seymour and Terry Horsley, APC, USA Many of the mysteries of equipment failure, downtime, software and data corruption are the result of
More informationPower Quality Notes 2-2 (AK)
Power Quality Notes 2-2 (AK) Marc Thompson, Ph.D. Senior Managing Engineer Exponent 21 Strathmore Road Natick, MA 01760 Alex Kusko, Sc.D, P.E. Vice President Exponent 21 Strathmore Road Natick, MA 01760
More informationOutline. Power Quality in Electrical Systems. Alexander Kusko, Sc.D., P.E. Marc T. Thompson, Ph.D.
6/1/05 Outline Power Quality in Electrical Systems by Alexander Kusko, Sc.D., P.E. Marc T. Thompson, Ph.D. Authors Alexander Kusko, Sc.D, Corporate Vice President, Exponent Failure Analysis Associates,
More informationOperational Experience with a Nationwide Power Quality and Reliability Monitoring System
Submitted for: IEEE-IAS 2003 Annual Meeting, Salt Lake City, UT 1 Operational Experience with a Nationwide Power Quality and Reliability Monitoring System William E. Brumsickle, PhD, Member, IEEE; Deepak
More informationQUESTION BANK PART - A
QUESTION BANK SUBJECT: EE6005-Power Quality SEM / YEAR: VII SEMESTER / ACADEMIC YEAR 08-09 UNIT I - INTRODUCTION TO POWER QUALITY Terms and definitions: Overloading - under voltage - over voltage. Concepts
More informationEst Static Frequency Converter. SFX 10kVA - 10MVA
Est.1968 Static Frequency Converter SFX 10kVA - 10MVA Static Frequency Converter SFX 10kVA - 10MVA A Concept Thycon Static Frequency Converters (SFX) convert supply frequency to load requirement frequency.
More informationPrimary Metering. What is Primary Metering?
NWEMS Primary Metering August 22, 2018 Bill Unbehaun, Tacoma Power Exchanging Expertise Since 1893 What is Primary Metering? Metering energy flow past a point at high voltage above 600v Both PTs and CTs
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationAPQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)
APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute
More informationState of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company
Engineering data submittal Page 1 WHO SHOULD FILE THIS SUBMITTAL : Anyone in the final stages of in terconnecting a Generation System with Otter Tail Power. This submittal shall be completed and provided
More informationSection 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services
Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality
More informationSIMPLE RULES FOR SOLVING POWER QUALITY MYSTERIES
SIMPLE RULES FOR SOLVING POWER QUALITY MYSTERIES Prepared for the Conference on Protecting Electrical Networks and Quality of Supply Heathrow, UK, 22-23 January 1997 Prepared by, Richard P. Bingham Dranetz
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationthepower to protect the power to protect i-gard LITERATURE Low and medium voltage
thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors
More informationPhase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.
Summary Of Interconnection Technical Guidelines for Renewable Energy Systems 0-100 kw under Standard Offer Contract (Extract from JPS Guide to Interconnection of Distributed Generation) This document is
More informationElectric Power Distribution Handbook. Voltage Sags and Momentary Interruptions
This article was downloaded by: 1.3.98.93 On: 26 Dec 218 Access details: subscription number Publisher: CRC Press Informa Ltd Registered in England and Wales Registered Number: 172954 Registered office:
More informationPOWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:
POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION
More informationUsing smart grid sensors and advanced software applications as an asset management tool at Hydro Ottawa
24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 1: Network components Using smart grid sensors and advanced software applications as an asset management
More informationUninterruptible Power System (UPS) 20 to 320 kva
Large-capacity Uninterruptible Power System (UPS) 20 to 320 kva All IGBT type UPS 7000F Series REC 82-5 Fuji's UPS for today's computerized On-line support for all applications Data communication devices
More informationE S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --
D.,.,.,. E S C R I P T I V E B U L L E T I N Bulletin DB-106 Square D Company October, 1990 ---1 I SQU ARED COMPANY -- Electrical Power Distribution System - The Heart of the Business From small commercial
More informationPower Quality Starts At the Load
Power Quality Starts At the Load Richard P. Bingham, Dranetz-BMI, Edison, NJ, USA Abstract The definition of power quality is becoming another one of those terms whose definition gets stretched so far
More informationTOSHIBA International Corp
TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification
More informationResearch Article Challenges and Trends in Analyses of Electric Power Quality Measurement Data
Hindawi Publishing Corporation EURASIP Journal on Advances in Signal Processing Volume 2007, Article ID 57985, 5 pages doi:10.1155/2007/57985 Research Article Challenges and Trends in Analyses of Electric
More informationE N G I N E E R I N G M A N U A L
1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn
More informationECET Modern Power
ECET 273000 Modern Power Course Instructors Course Philosophy This course is an introduction to a wide range of electrical energy systems technologies. Topics include fundamentals of energy conversion,
More informationThe power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner
conditioning products Electronic voltage regulator -Sure 700 & 800 -Suppress T7 & 100 Harmonic correction unit Sag ride-through power conditioner The power to work Basics of power quality The partner you
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationHarmonic Filters for Single Phase Equipment
POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics
More informationWelcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008
Welcome to the rd Annual Northern Ohio 3 rd Energy Management Conference September 30, 2008 Recover Lost Dollars Demand Side Electrical Energy Savings By Improving Distribution System Efficiency, Capacity
More informationOVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT
OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT Shyam V. Alaspure 1, Snehal G. Vinchurkar 2, Swapnil D. Raut 1 Electronics & Telecommunication 2 Electronics & Power 3 Computer 1 Lecturer, G.H. Raisoni Polytechnic
More informationVoltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment
s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering
More informationPower Analysis Summary
Power Analysis Summary Introduction This is a summary of the power conditions measured with these setup parameters: Measurement File: C:\Users\fhealy\Documents\Fluke\Power Analyze\Core 2 Recording.odn
More informationUse of Advanced Monitoring Technology to Detect Incipient Failure of Line Equipment
Use of Advanced Monitoring Technology to Detect Incipient Failure of Line Equipment 71st Annual Conference for Protective Relay Engineers Texas A&M University College Station, Texas USA 26-29 March 2018
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationIntermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)
Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected
More informationREDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum
International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher
More informationAPPENDIX B: Generation Interconnection Application Form
2 APPENDIX B: Generation Interconnection Application Form WHO SHOULD FILE THIS APPLICATION: Anyone expressing interest to install generation which will interconnect with Xcel Energy (Local electric utility)
More informationUnit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203
Unit.2-Voltage Sag D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203 13/09/2012 Unit.2 Voltage sag 1 Unit-2 -Voltage Sag Mitigation Using
More informationImpact of High PV Penetration on Grid Operation. Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas
Impact of High PV Penetration on Grid Operation Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas Overview Introduction/Background Effects of High PV Penetration on Distribution
More informationApplication for A Sub-harmonic Protection Relay. ERLPhase Power Technologies
Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic
More information3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.
MAIN TOPICS DISCUSSED Electric Rates Electrical system utilization ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K Power quality Harmonics Power factor (Cos phi) improvement Section K - 2 ELECTRIC
More informationReliable Power Meters Multipoint Power Recorder
Reliable Power Meters Multipoint Power Recorder High-speed capability for permanent installation Technical Data What is Full Disclosure Technology? Full Disclosure Technology is built into all Fluke and
More informationDISCRIMINATION AND ASSESSMENT OF VOLTAGE SAG IN DISTRIBUTION NETWORKS
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 58 DISCRIMINATION AND ASSESSMENT OF VOLTAGE SAG IN DISTRIBUTION NETWORKS Emad eldeen A. Alashaal, Sabah I. Mohammed North
More informationTexas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event
Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationA DUMMIES GUIDE TO GROUND FAULT PROTECTION
A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding
More information