SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

Size: px
Start display at page:

Download "SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS"

Transcription

1 SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS A. Nikander*, P. Järventausta* *Tampere University of Technology, Finland, Fax Keywords: High-impedance earth fault, fault indication, distribution network, safety regulations, hazard voltage. Abstract The paper considers the safety aspects of earth fault management and needs for indication and location of highresistance earth faults in medium voltage (MV) electricity distribution networks. Applying the methods available the safety of electricity distribution can be improved and the number and duration of outages to customers can be reduced. Methods for very high-resistance earth fault identification and location in neutral isolated or compensated distribution systems have been developed in Tampere University of Technology. These indication methods are able to detect and locate faults up to some hundreds of kilo-ohms. The indication methods have proven to be very appropriate for the implementation and the results from the field installation and field experiments are promising. Aspects for achieving a compromise between the safety and reliability of the electricity distribution are also highlighted. 1 Introduction The overall target of earth fault management is to indicate, locate and isolate a fault and to restore the healthy part of the network as quickly as possible in order to reduce the outage costs and to maintain the quality of supply and safety requirements. WHY? Safety aspects Protection of network Minimising of the costs due to interruptions HD 637 S1 Fundamental frequency overvoltages - risk of secondary faults Costs for electricity companies and customers Figure 1: Why earth fault management is needed in neutral isolated or compensated system. Unlike short-circuits, earth faults include the ground connection. This matter creates the unbalance in phase-toearth voltages and phase currents during a fault and causes the zero sequence components of the phase-to-earth voltages and phase currents. From the safety point of view the main quantity is the fault current flowing from phase to earth. The flowing path normally includes the fault resistance and earthing resistance. In neutral isolated system the fault circuit is closed via phase-to-earth capacitances. In high reactance earthed system a parallel resonant circuit is composed between earth capacitances and the neutral-to-earth resistor. The fault current produces the earthing voltage (U E ) when flowing through the earthing impedance (Z E ). Part of the earthing voltage appears as a touch or step voltage. These hazard voltages are regulated by pan-european hazard voltage regulations [1]. The touch or step voltage causes the current passing through the human body which is the cause of danger. Medium voltage networks in the Nordic Countries have mainly isolated or compensated neutrals, which leads to very low fault current with high-resistance earth fault. Thus the detection of such faults is a challenging task. In this study a high-resistance earth fault is defined as a fault with fault resistance from 10 kω up to several hundreds of kilo-ohms. Conventional feeder protection cannot even detect an earth fault with very high fault resistance and thus it cannot trip a feeder. Because the phase-to-earth fault current is very low the touch voltage regulations does not presuppose the tripping of the faulty feeder [1]. The major safety risk appears in the situation where the conductor or other live part of the system has an earth contact e.g. directly or via a tree and the fault current is not high enough to lead to tripping. These high-resistance faults tend to evolve gradually into a full-scale earth fault. Thus, early identification and location of such faults is of increasing importance in improving the safety and reliability of electricity distribution. Continuous and accurate monitoring of each separate MV feeder in order to evaluate the electric insulation state of the feeder and enable the early detection of the earth faults becomes more and more important. In the past few years Tampere University of Technology has being studying methods for identifying and locating earth faults [3]. The methods of the paper utilize the same measuring information of modern numerical feeder terminals which is used for normal protection function. All methods

2 operate independently as relay functions. Thus the electric state of all the feeders can be monitored separately. The identification and location of a high-resistance earth fault also include the information on the faulty feeder and faulty phase. This, in addition to better sensitivity, is one major improvement on conventional methods. With permanent low resistance earth faults the overall aim is to indicate the presence of an earth fault and the faulty feeder, to determine the distance to a fault, to isolate and remove a fault in order to reduce outage costs and to ensure as high safety level as possible. The sound part of the feeder is restored as quickly as possible. 2 Safety aspects of earth fault management Standard IECTR gives guidance on the effects of current flowing through the human body due to its magnitude and duration. In practice it is more convenient to refer to touch voltages. Touch voltage limits due to earth faults are given in Figure 2 [1]. The curve represents the value of voltage (U TP ) that can appear across the human body, bare hands to bare feet. No additional resistances have been considered in the calculations. current (R F = 0 Ω) and the worst earthing (highest earthing impedance Z E ). U E IEZE 2 UTP = (1) 3 Safety aspects of earth fault protection and location versus quality of supply Earth faults or secondary faults developing from earth faults form the most common fault group in the MV networks of the Nordic Countries. In overhead line networks automatic reclosing usually clears over 90 % of the faults and below 10 % of the faults remain permanent. Permissible touch voltages defined in [1] depend on the duration of fault. The typical tripping delay used in neutral isolated or compensated system is s. From the safety point of view the short tripping delay is advisable because of the short current-flow duration. Due to the short tripping delay savings in earthing costs can also be achieved. In neutral isolated and especially in neutral compensated system the self-extinction of the earth fault arc is much more likely if the tripping delay and thus the current flow duration is long enough. The lower steepness of the recovery voltage is the main reason why the possibility of arc extinction is much higher in a neutral compensated than in an isolated system [4]. Thus the safety and quality of supply are partly contradictory objectives. In Central Europe it is a long tradition to use neutral compensated MV systems during an earth fault. Operating the MV system during phase-to-earth fault includes a considerably higher risk in Finland than in Central Europe. This is a consequence of considerably higher soil resistivity and extensive usage of overhead line networks. In Central Europe MV systems are maily of underground cable construction. Figure 2: Permissible touch voltages U TP for limited currentflow duration [1]. Every earth fault will be disconnected automatically or manually. Thus touch voltages of very long or indefinite duration do not appear as a consequence of earth faults. The novel residual current compensator systems makes it possible to carry on the electricity distribution during an earth fault because the residual fault current is completely compensated [5]. With these applications the insulation state of the system must be assured with an eye to the risk of a cross-country fault. If the current flow duration is much longer than shown in Figure 2, a value of 75 V can be used for U TP. The highest permissible earthing voltage (U E ) is double compared to voltage U TP (Eq. 1) or quadruple if the touch voltage U TP is proved by measurements to stay below the values of the curve (Fig. 1). Then the longest tripping delay of the feeder relay is determined according to maximum fault Residual current compensation (RCC) devices makes it possible to compensate completely the fundamental frequency fault current [5]. This makes it possible to use a network during an earth fault because no touch or hazard voltage appears at the fault location. In neutral isolated or compensated system phase-to-phase voltages do not change as a consequence of an earth fault. The vector group of 20/0.4 kv transformers is Dyn11. Thus undisturbed power distribution to customers can continue during a fault. The sustained overvoltages due to the rising potential of the healthy phases increase the risk of secondary failure (crosscountry fault or short-circuit), however. With cross-country fault the fault current flowing via earth between fault locations can be of the order of magnitude of a phase-to-phase short-circuit current. This type of fault must be tripped out very quickly because of touch voltage consideration [1] and danger of damage to communication cables and telephone systems which can cause very high costs. By improving the safety and quality of the supply by compensating the residual earth fault current the risk of secondary failure exists,

3 however. The longer the duration of an earth fault is, the more likely is the occurrence of a secondary failure, especially a cross-country fault. Nowadays the fault distance of short-circuit faults can be calculated very accurately using the measured fault current. Permanent phase-to-earth faults are still problematic in neutral isolated and compensated networks. The longitudinal impedance of the line between the fault location and the substation has practically no influence on the magnitude of the fundamental frequency fault current. One possibility to arrange the earth fault distance calculation is to increase the fault current by connecting a low impedance to the neutral point of the system temporarily during a fault. When the safety aspect is considered the following question arises. Which is more important from the safety point of view: Low duration of high fault current and quick calculatory earth fault distance estimation, or Low fault current and several sequential current-flow periods (tripping delays and trial switchings used for locating the earth fault). Using trial switchings the fault location is determined by dividing the faulty feeder into sections by a disconnector and closing the substation circuit breaker against the fault until the faulty line section is found. This is laborious and time consuming. The other disadvantage of trial switchings is that the voltage is connected against the fault. This causes switching overvoltages and temporary overvoltages between healthy phases and the earth and may lead to a secondary failure e.g. to a cross-country fault. Every opening of the circuit breaker with the trial switchings causes an interruption to customers supplied by the feeder concerned. Trial switchings may also cause unsafe situations when the fault location is situated in an urban environment. In addition to fundamental frequency current the fault current normally includes harmonic components. In neutral compensated systems harmonics are generated by saturated components of the fault circuit such as neutral-to-earth coil and main transformer. In the case of temporary faults the earth fault arc generates harmonics to the fault current. Figure 3 presents the fault current measured with a real fault case in neutral isolated system. The fault is of the arc type. The fault current interrupts and restrikes causing high harmonic content of a fault current. Figure 3 presents wave shape of the fault current. The horizontal uniform lines represent the fundamental frequency component, 3 th, 5 th, 7 th and 9 th harmonics from top to bottom. The harmonic content of the fault current may be significant compared to the fundamental frequency component with earth fault arc. This fact should be noted when touch voltages are considered. In unearthed and neutral compensated systems the possible overvoltages due to successive current interruptions and resrikings should also be considered. These may happen in the case of low fault currents, typically below 10 A. These overvoltages may cause a secondary failure. Figure 3: Earth fault current and harmonic content with restriking fault. 4 Identification and location of very highresistance earth faults In overhead line networks high-resistance earth faults may occur due to trees leaning against a conductor or when the conductor falls to the ground with very high resistivity. Such faults also develop due to conductor break when the load side end of the conductor has an earth contact. Faults with covered conductors or other network component faults (e.g. metal oxide surge arresters, overhead line pin insulator) often have very high impedance. These faults tend to evolve gradually into a full scale earth fault. Thus, early identification and location of such faults is of increasing importance in improving the reliability of electricity distribution. Although the touch voltage regulations do not require the tripping of the faults with very high fault resistance such faults may cause unsafe situations. Falls and breaks in the conductor when the load side end of the conductor has an earth contact are especially dangerous if the live parts can be touched by the public. Faults with covered conductors may be latent for a long time before a tripping of the feeder protection. The typical resistance of an unseasoned tree is in the range kω [2]. These resistance values are valid in those seasons when the earth is not frozen. In wintertime much higher resistances, ranging up to several hundreds of kiloohms or some megohms can be found. Most faults of this type are out of neutral voltage overvoltage relays or monitoring of the neutral voltage. 4.1 A method for monitoring the shunt resistance of a feeder The method detects the magnitude of the fault resistance of the faulty phase of the faulty feeder. In the case of a healthy feeder the magnitude of the fault resistance is theoretically infinite.

4 The measuring accuracy does not allow the accurate determination of the phase-to-earth conductance of the feeder. Instead, according to experiences from field tests, the calculated phase-to-earth susceptance has a reliable value representing the electric length of the feeder. Thus more reliable values for leakage resistances and thereby more sensitive fault indication compared to earlier known methods can be achieved if the phase-to-earth admittances are assumed to be pure capacitances. The following presents a method for the monitoring of the shunt resistance of the MV feeder. Every feeder is monitored separately. Only neutral voltage and sum currents due to an earth fault are considered. The method can be applied with isolated and compensated systems. 3 U 3 ' U 2 ' U 2F U 3F U 3 U 0M U 2 U 0 U 0 ' U 1 ' U 1 U 1F 1 The most sensitive fault indicator is the change of the neutral voltage of the network. The indication process starts when the absolute value of the change of the neutral voltage U 0 exceeds the specified threshold value. If the change of the neutral voltage is due to an earth fault, U 0 refers to the neutral-to-earth voltage caused by an earth fault (Fig. 4). When the specified threshold value U th is exceeded, the determination process of the faulty feeder and calculation of the fault resistance start in every feeder. The phasor U 0 is used as a reference. I 0i represents the sum current of the feeder due to an earth fault. The influence of the capacitive unbalance on the sum current is eliminated. Phase-to-earth voltages U ν are also referenced to U 0. The phase angle of U ν is equal to the phase angle of the earth fault current if the fault impedance is supposed to be purely resistive. ' U = U 0M U 0 > U th 0 (2) where U 0 ' is measured neutral voltage before a change U 0M is measured neutral voltage after a change U th is specified threshold value of the neutral voltage. When Formula 2 has been fulfilled, the faulty phase is determined. The inference of the faulty phase occurs in a slightly different way in isolated and compensated systems. 2 Figure 4: Voltage phasors of an isolated system when Phase 1 is faulty. Calculation of fault resistance. When information on the faulty phase is available, the fault resistance of Feeder i can be calculated using Formula 3. Neutral voltage, phase-toearth voltages and sum currents of feeders are known as measured values at all 110/20 kv substations. UνF sinϕu F R Fi = ν I 0i sin (3) ϕ I + B i U 0i 0 0 where U 0 is change of neutral voltage U νf is phase-to-earth voltage of a faulty phase ϕu νf is phase angle of phasor U νf referenced to U 0 I 0i is change of the sum current of Feeder i ϕ I 0i is phase angle of phasor I 0i referenced to U 0 B 0i is phase-to-earth susceptance of Feeder i. The fault resistance can also be calculated also during an earth fault which is presented in the following Figure 5. Indication of a faulty phase in isolated system. Figure 4 illustrates balanced phase-to-earth voltages (U 1, U 2, U 3 ), unbalanced phase-to-earth voltages of healthy state (U 1 ', U 2 ', U 3 '), unbalanced phase-to-earth voltages during an earth fault (U 1F, U 2F, U 3F ), neutral voltage due to a healthy state (U 0 '), neutral voltage caused by an earth fault ( U 0 ) and neutral voltage measured during an earth fault (U 0M ). In isolated system neutral voltage ( U 0 ) and the phase-to-earth voltage of the faulty phase (U 1F ) draw a semicircle as a function of the fault resistance. This means that with an isolated system phasor U νf leads 90 phasor U 0 during an earth fault irrespective of the fault resistance. Phase-to-earth voltages of healthy state (U 1 ', U 2 ', U 3 ') are unbalanced and result from capacitive unbalance of the system. Figure 5: Sum current and fault resistance of faulty feeder.

5 5 Conclusions Methods for very high-resistance earth fault identification and location in neutral isolated or compensated distribution systems have been developed in Tampere University of Technology. Applying these patented methods the safety of electricity distribution can be improved and the number and duration of outages to customers can be reduced. By applying earth fault current compensation and residual current compensation the touch voltages can be considerably reduced. These applications do not eliminate the risk of secondary failure (cross-country faults) as a consequence of sustained overvoltages. In neutral compensated system the risk may be even higher compared to neutral isolated system because the fault must not be tripped as quickly as with higher fault current. In many cases the safety and quality of supply are partly contradictory objectives with earth faults. The harmonic content of the fault current may be significant compared to the fundamental frequency component with earth fault arc. This fact should be noted when touch voltages are considered. References [1] Anon. Harmonization document HD 637 S1: Power installations exceeding 1 kv a.c. European Committee for Electrotechnical Standardization (CENELEC). 107 p. (1999) [2] S. Hänninen, M. Lehtonen, Method for detection and location of very high resistive earth faults. European Transactions on Electrical Power Engineering (ETEP), Vol. 9, No. 5, pp , (1999) [3] A. Nikander, P. Järventausta, J. Myllymäki. Novel algorithms for earth fault indication based on monitoring of shunt resistance of MV feeder as a part of relay protection. Proceedings of the Seventh International Conference on Developments in Power System Protection, IEE Conference Publication, No. 479, Amsterdam, The Netherlands, pp , (2001). [4] A. Nikander, E. Lakervi. A philosophy and algorithms for extinguishing earth fault arcs in suppressed medium voltage networks. Proceedings of the 14th International Conference on Electricity Distribution (CIRED), Birmingham, UK, June 1997, pp , (1997) [5] K. Winter. Swedish distribution networks A new method for earth fault protection in cable and overhead systems, Proceedings of the Fifth International Conference on Developments In Power System Protection, IEE Conference Publication, No.368, UK, 3 p., (1993).

Phase earthing system - method for faulty phase selection with phase-to-earth faults. Ari Nikander Tampere University of Technology

Phase earthing system - method for faulty phase selection with phase-to-earth faults. Ari Nikander Tampere University of Technology Phase earthing system - method for faulty phase selection with phase-to-earth faults Ari Nikander Tampere University of Technology - 2 - Preface This report has been done as a part of the research work

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS

LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS Witold Hoppel, Józef Lorenc!" ph.+48 61 8782279 - FAX + 48 61 8782280 Jerzy Andruszkiewicz

More information

ScienceDirect. Simulation Models for Various Neutral Earthing Methods in Medium Voltage Systems

ScienceDirect. Simulation Models for Various Neutral Earthing Methods in Medium Voltage Systems Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 1 (15 ) 118 1191 5th DAAAM International Symposium on Intelligent Manufacturing and Automation, DAAAM 1 Simulation Models for

More information

APPLICATION OF MULTI-FREQUENCY ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK

APPLICATION OF MULTI-FREQUENCY ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK 24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 967 APPLICATION OF MULTI-FREQUENC ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK Janne

More information

MV Network Operation Issues and Elimination of Phase Voltage Unbalance

MV Network Operation Issues and Elimination of Phase Voltage Unbalance Transactions on Electrical Engineering, Vol. 6 (2017), No. 3 72 MV Network Operation Issues and Elimination of Phase Voltage Unbalance František Žák Analyst and Lecturer of the distribution network operation,

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

Grounding for Power Quality

Grounding for Power Quality Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

Fault Location in MV Unearthed Distribution Network Using the Undamped Frequency of the Transient Signal

Fault Location in MV Unearthed Distribution Network Using the Undamped Frequency of the Transient Signal Fault Location in MV Unearthed Distribution Network Using the Undamped Frequency of the Transient Signal MOHD RAFI ADZMAN, MATTI LEHTONEN Department of Electrical Engineering, School of Science and Technology

More information

Summary of the Impacts of Grounding on System Protection

Summary of the Impacts of Grounding on System Protection Summary of the Impacts of Grounding on System Protection Grounding System grounding big impact on ability to detect ground faults Common ground options:» Isolated ground (ungrounded)» High impedance ground»

More information

CONTENTS. 1. Introduction Generating Stations 9 40

CONTENTS. 1. Introduction Generating Stations 9 40 CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific

More information

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Improving High Voltage Power System Performance. Using Arc Suppression Coils Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

Single Phase Earth Fault Location in the Medium Voltage Distribution Networks

Single Phase Earth Fault Location in the Medium Voltage Distribution Networks 1.2478/v1144-9-2-6 SCINTIFIC PROCDINGS OF RIG TCHNICL UNIVRSITY TH 5TH INTRNTIONL SCINTIFIC CONFRNC POWR ND LCTRICL NGINRING, OCTOBR 29 Single Phase arth Fault Location in the Medium Voltage Distribution

More information

Grounding System Theory and Practice

Grounding System Theory and Practice Grounding System Theory and Practice Course No. E-3046 Credit: 3 PDH Grounding System Theory and Practice Velimir Lackovic, Electrical Engineer System grounding has been used since electrical power systems

More information

THE RCC GROUND FAULT NEUTRALIZER

THE RCC GROUND FAULT NEUTRALIZER REPRINT 18TH INTERNATIONAL CONFERENCE AND EXHIBITION ON ELECTRICITY DISTRIBUTION LINGOTTO CONFERENCE CENTRE, TURIN 6-9 JUNE 2005 THE RCC GROUND FAULT NEUTRALIZER A NOVEL SCHEME FOR FAST EARTH-FAULT PROTECTION

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

Distance Protection of Cross-Bonded Transmission Cable-Systems

Distance Protection of Cross-Bonded Transmission Cable-Systems Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th

More information

System grounding of wind farm medium voltage cable grids

System grounding of wind farm medium voltage cable grids Downloaded from orbit.dtu.dk on: Apr 23, 2018 System grounding of wind farm medium voltage cable grids Hansen, Peter; Østergaard, Jacob; Christiansen, Jan S. Published in: NWPC 2007 Publication date: 2007

More information

Minimising the Risk of Cross-Country Faults in Systems using Arc Suppression Coils R. Burgess

Minimising the Risk of Cross-Country Faults in Systems using Arc Suppression Coils R. Burgess Minimising the Risk of Cross-Country Faults in Systems using Arc Suppression Coils R. Burgess A. Ahfock University of Southern Queensland University of Southern Queensland West St West St Toowoomba Toowoomba

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION 23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB

More information

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN): Single Earthed Neutral and Multi Earthed Neutral. SEPTEMBER 6, 2011 5 COMMENTS Single Earthed Neutral and Multi Earthed Neutral: In Distribution System Three Phase load is unbalance and non linear so The

More information

Intermittent transient earth fault protection

Intermittent transient earth fault protection Intermittent transient earth fault protection The directional intermittent transient earth fault protection is used to detect short intermittent transient faults in compensated cable networks (figure 3).

More information

In order to minimise distribution (11 and 22 kv) feeder breaker

In order to minimise distribution (11 and 22 kv) feeder breaker Lightning protection for equipment on MV feeders By WJD van Schalkwyk and M du Preez, Eskom This article presents the influence of lightning on MV feeders supplying small power users (400/230 V) with focus

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

Towards a transient earth fault clearing scheme for medium voltage networks

Towards a transient earth fault clearing scheme for medium voltage networks Towards a transient earth fault clearing scheme for medium voltage networks by Jan Scholtz, Eskom This paper describes the design principles and physical implementation of an improved transient earth fault

More information

IMP/007/011 - Code of Practice for the Application of Lightning Protection

IMP/007/011 - Code of Practice for the Application of Lightning Protection Version 1.1 of Issue Aug 2006 Page 1 of 11 IMP/007/011 - Code of Practice for the Application of Lightning Protection 1.0 Purpose The purpose of this document is to ensure the company achieves its requirements

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Improving High Voltage Power System Performance. Using Arc Suppression Coils Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL

ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL REPRINT 19TH INTERNATIONAL CONFERENCE AND EXHIBITION ON ELECTRICITY DISTRIBUTION REED MESSE WIEN CONGRESS CENTER, VIENNA MAY 21-24, 2007 ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL Kristian Winter,

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

Harmonic Distortion Levels Measured at The Enmax Substations

Harmonic Distortion Levels Measured at The Enmax Substations Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned

More information

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering

More information

Webinar: An Effective Arc Flash Safety Program

Webinar: An Effective Arc Flash Safety Program Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of

More information

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Neutral Earthing. For permanent or temporary neutral earthing in HV systems Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection

More information

Our Brands. Where we are?

Our Brands. Where we are? CATALOG 2019 Our Brands Aktif trade mark for Measuring, Protection, Automatic Meter Reading, Billing and Energy Management Software. by Aktif Aktif trade mark for Measuring, Protection, Control and Power

More information

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices M. Sanaye-Pasand, R. Aghazadeh Applied Electromagnetics Research Excellence Center, Electrical & Computer Engineering

More information

ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK

ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK Masters of Science Thesis Examiner: Professor Pertti Järventausta and Dr Tech. Ari Nikander Examiner and topic

More information

TN, TT & IT Earthing Arrangements

TN, TT & IT Earthing Arrangements TN, TT & IT Earthing Arrangements In IT and TN-C networks, residual current devices are far less likely to detect an insulation fault. In a TN-C system, they would also be very vulnerable to unwanted triggering

More information

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection) Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection) FIGURE 1.2 Fig.1 Earth fault loop path. Figure 1 shows the earth fault system which provides

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha

SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha EE2402 - PROTECTION & SWITCHGEAR SYLLABUS ELECTRIC POWER SYSTEM Electricity is generated at a power plant (1), voltage

More information

Why the IT system is often the best choice for power supply systems of all types

Why the IT system is often the best choice for power supply systems of all types Why the IT system is often the best choice for power supply systems of all types Let us start initially with a clear commitment: the IT system ("unearthed system") is a type of system infrequently used

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

Double Criteria Feeder-Selection Method for Single-Phase Ground Fault of Resonant Grounding System Based on Multi-State Components

Double Criteria Feeder-Selection Method for Single-Phase Ground Fault of Resonant Grounding System Based on Multi-State Components American Journal of Electrical and Electronic Engineering, 207, Vol. 5, No. 4, 44-5 Available online at http://pubs.sciepub.com/ajeee/5/4/4 Science and Education Publishing DOI:0.269/ajeee-5-4-4 Double

More information

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES White Paper Tim Wylie, Ampcontrol s Chief Technology Officer discusses the impact of Variable Speed Drives (VSDs) on earth fault limited networks.

More information

GIS Disconnector Switching Operation VFTO Study

GIS Disconnector Switching Operation VFTO Study GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,

More information

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK Eduardo MARTÍNEZ eduardo_martinez@fcirce.es Samuel BORROY sborroy@fcirce.es Laura

More information

Arc Suppression Coils

Arc Suppression Coils Arc Suppression Coils (22kV Arc Suppression Coils ) Introduction Resonance grounding by Petersen coils (Arc Suppression Coils) has been used in Scandinavia and other European countries for some eighty

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

Index. b back-flashover 245 biomass 207 breakers 74 buchholz protection 235 busbar sectionalizer 193 business enterprises 18

Index. b back-flashover 245 biomass 207 breakers 74 buchholz protection 235 busbar sectionalizer 193 business enterprises 18 331 Index a activity plan 318 agricultural enterprise 21 annual increase factor 12 annuity factor 44, 156 annuity method 38 ANSI code numbers 237 arrester, protection level 245 assessment of losses 38

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations A.R. Sultan, M.W. Mustafa, M.Saini Faculty of Electrical Engineering Universiti Teknologi Malaysia (UTM)

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS 29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar

More information

Industrial and Commercial Power Systems Topic 7 EARTHING

Industrial and Commercial Power Systems Topic 7 EARTHING The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 7 EARTHING 1 INTRODUCTION Advantages of earthing (grounding): Limitation

More information

FAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS

FAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS The BEST Group THE BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP -Winter Lecture Series FAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS Presented by: Syed Khundmir T Department of Electrical Engineering

More information

PROTECTION APPLICATION HANDBOOK

PROTECTION APPLICATION HANDBOOK BOOK No 6 Revision 0 Global Organization Innovative Solutions Product & Substation System Business Business PROTECTION APPLICATION HANDBOOK BA THS / BU Transmission Systems and Substations LEC Support

More information

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer Vol. 3 Issue 2, February-2014, pp: (69-75), Impact Factor: 1.252, Available online at: www.erpublications.com Modeling and Simulation of Modern Digital Differential Protection Scheme of Power Transformer

More information

RISK MANAGEMENT IN A LOW VOLTAGE NETWORK ON SAFETY ISSUES FROM ASSET MANAGEMENT PERSPECTIVE

RISK MANAGEMENT IN A LOW VOLTAGE NETWORK ON SAFETY ISSUES FROM ASSET MANAGEMENT PERSPECTIVE RISK MANAGEMENT IN A LOW VOLTAGE NETWORK ON SAFETY ISSUES FROM ASSET MANAGEMENT PERSPECTIVE Sharmistha BHATTACHARYYA Endinet The Netherlands sharmirb@yahoo.com Thijs van DAEL Endinet The Netherlands thijs.van.dael@endinet.nl

More information

Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers

Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers 70 th Annual Conference for Protective Relay Engineers Siemens AG 2017 All rights reserved. siemens.com/energy-management

More information

RCTrms Technical Notes

RCTrms Technical Notes RCTrms Technical Notes All measuring instruments are subject to limitations. The purpose of these technical notes is to explain some of those limitations and to help the engineer maximise the many advantages

More information

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS 24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 97 RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS Pengfei WEI Yonghai XU Yapen WU Chenyi

More information

Relevant Factors to a Statistical Analysis of Overvoltages - Application to Three-Phase Reclosing of Compensated Transmission Lines

Relevant Factors to a Statistical Analysis of Overvoltages - Application to Three-Phase Reclosing of Compensated Transmission Lines Energy and Power Engineering, 2013, 5, 1165-1171 doi:10.4236/epe.2013.54b221 Published Online July 2013 (http://www.scirp.org/journal/epe) Relevant Factors to a Statistical Analysis of Overvoltages - Application

More information

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids

More information

New solution for feeder earth-fault protection

New solution for feeder earth-fault protection Application Note New solution to feeder earth-fault protection 1 (8) APPLICATION NOTE New solution for feeder earth-fault protection AQ-200 IED series Application Note New solution to feeder earth-fault

More information

A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS

A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS Georg Achleitner, Clemens Obkircher, Lothar Fickert, Manfred Sakulin Graz University of Technology Inffeldgasse

More information

Končar TMS - Bushing monitoring

Končar TMS - Bushing monitoring Končar TMS - Bushing monitoring Many recent studies have shown that bushing failure is one of the most common causes of transformer failure. Thus need for bushing diagnostic and monitoring system has risen.

More information

GOOD GROUNDING PRACTICES. A Brief Introduction to the Basics of Electrical Grounding for Power Systems

GOOD GROUNDING PRACTICES. A Brief Introduction to the Basics of Electrical Grounding for Power Systems GOOD GROUNDING PRACTICES A Brief Introduction to the Basics of Electrical Grounding for Power Systems Introduction to Grounding TABLE OF CONTENTS 1.0 Introduction to Grounding 2.0 Standard Industrial Grounding

More information

Slide 1. New Delhi India Oct CIGRE AORC Meeting New Delhi October 2017

Slide 1. New Delhi India Oct CIGRE AORC Meeting New Delhi October 2017 Slide 1 CIGRÉ AORC Panel B1 Insulated Cables Victorian REFCL Program Update (Rapid Earth Fault Current Limiter) Russell Wheatland : Principal Engineer - Asset Management CIGRE AORC Meeting New Delhi October

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Power Systems Modelling and Fault Analysis

Power Systems Modelling and Fault Analysis Power Systems Modelling and Fault Analysis Theory and Practice Nasser D. Tleis BSc, MSc, PhD, CEng, FIEE AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD PARIS SAN DIEGO SAN FRANCISCO SINGAPORE SYDNEY

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy W. Piasecki, M. Stosur, T. Kuczek, M. Kuniewski, R. Javora Abstract-- Evaluation

More information

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority S. Songsiri * and S. Sirisumrannukul Abstract This paper presents an application

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

Capacitor protection relay

Capacitor protection relay Capacitor Protection Relay FEATURES Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent

More information

LOW-RESISTANCE grounding resistors (LRGs) appear

LOW-RESISTANCE grounding resistors (LRGs) appear IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 44, NO. 5, SEPTEMBER/OCTOBER 2008 1311 Grounding the Neutral of Electrical Systems Through Low-Resistance Grounding Resistors: An Application Case Massimo

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

Electrical Protection System Design and Operation

Electrical Protection System Design and Operation ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection

More information