1 Slide 1 CIGRÉ AORC Panel B1 Insulated Cables Victorian REFCL Program Update (Rapid Earth Fault Current Limiter) Russell Wheatland : Principal Engineer - Asset Management CIGRE AORC Meeting New Delhi October 2017 New Delhi India Oct 2017
2 REFCL Program Update Where it all began Victorian Regulations REFCL Principles REFCL Zone substation components Operation Network Parameter Challenges Current Program status Slide 2 New Delhi India Oct 2017
3 REFCL : Where it all began Dry Lightning The crime of Arson Black Saturday Feb 2009 Slide 3 New Delhi India Oct 2017
4 REFCL : Where it all began Black Saturday Feb 2009 Slide 4 New Delhi India Oct 2017
5 REFCL : Where it all began Black Saturday Feb people lost their lives 2,100 homes were destroyed 1,100,000 acres of land burnt Over 5,000 volunteer firefighters Over 400 separate fires Slide 5 A Royal Commission was established to learn what went wrong and how not to let this happen again New Delhi India Oct 2017
6 REFCL Introduction What are the Regulatory Requirements? The Electrical Safety (Bushfire Mitigation) Regulations 2013 including REFCL specific requirements to: Install REFCLs at 22 ZSS staged over 7 years in 3 defined Tranches. detect and compensate for 22kV earth faults down to 0.5A or less prove that the REFCL operates as per the regulatory REFCLs will be installed at 22 zone substations over 7 years. The order of Slide requirements 6 annually prior the Tranches was determined through a risk based assessment.
7 REFCL Introduction Where is the REFCL Installed? The ZSS transforms from 66kV to 22kV. Slide 7 500kV* or 220kV 66kV 22kV 415 or 240 V The REFCL is installed in a Zone Substation (ZSS). It works by constantly monitoring the surrounding 22kV high voltage powerlines to detect if there
8 Earthing Summary Types of Earthing Earthing technology advancements have reduced fault current and speed of protection over time. Earthing Typical Fault Speed of Treatment Current Protection Solid Earthing 10,000A sec Low Resistive Earthing (NER) 1,000A sec Resonant Earthing (ASC) < 25A <0.1 sec Enhanced Resonant < 0.5A <0.1 sec Earthing (GFN) Slide 8
9 Earthing Technology How Does Resistive Earthing Work? Resistive Earthing Slide 9 Earth Fault Current Moderate Energy Typical fault current = 1000 Amps Following large fires in 1983 most rural ZSS had a Neutral Earth Resistor installed which reduced the fault energy but could still start a fire. 9
10 Earthing Technology How Does Resonant Earthing (Arc Suppression Coil) Work? Zone Substation Powerline Transformer Arc suppression coil (ASC) Earthing Ground / Earth Slide 10 Ground / Earth Earth Fault Current Low Energy Low Energy Typical fault current = <25 Amps The introduction of Resonant technology in Europe c.1917 further reduces energy: This is new to Australia as Resonant technology was not used in
11 Earthing Technology How Does Enhanced Resonant Earthing (GFN) Work? Earth Fault Current Slide 11 The REFCL limits the amount of energy released within milliseconds thus significantly reducing the possibility of a fire being started.
12 Earthing Technology An Earth Fault on a Network with a REFCL Enhanced Resonant Earthing When an earth fault occurs with the REFCL, within milliseconds, the fault is Slide 12 detected and compensated for with a clear absence of sparking.
13 GFN Components What is a Ground Fault Neutraliser (GFN)? A GFN is the type of REFCL technology currently being installed at AusNet Services substations. A GFN consists of 3 components Slide 13 New Delhi India Oct 2017
14 GFN Components Arc Suppression Coil (ASC) The ASC is connected to the power transformer 22 kv neutral and is located in the switchyard The ASC compensates for the capacitive earth fault current leaving only a low residual fault current In order to compensate for the capacitive current the ASC must be tuned to the network Tuning Capacitor Cabinet Inductor Slide 14 Connection from Residual Current Compensator
15 REFCL Fault Detection & Confirmation Fault Condition For a phase to ground fault on the network, the phase to ground voltage of the faulted phase is brought near to zero volts. The phase to ground voltage of the other two un-faulted phases increase to the full phase to phase value which is typically around 22kV. The ASC is used to compensate for the capacitive fault current which forms the bulk of the fault magnitude. The RCC neutralises the remaining residual fault current by injecting current into the arc suppression coil at 180 out of phase of the residual fault current. The magnitude of the residual fault current is typically less than 0.5 Amps. Slide 15 New Delhi India Oct 2017
16 Fault Detection & Confirmation Fault Confirmation Soft Fault Confirmation Example RCC Fault Confirmation steps Fault Detection ASC Example above is for a fault on red phase. This is a typical behaviour of the GFN. Continuous improvement and optimisation will change this slightly Slide 16 The fault current is reduced from 1500A to practically 0 within 60ms with no arcing. High impedance faults can now be detected No trip for transient faults Faulted phase at nearly 0V. Other 2 phases potentially at 24.2 kv
17 Slide 17 REFCL Operation Capacitance Balancing Network capacitance is important so that fault currents of <0.5 A can be detected Any imbalance decreases the sensitivity of the GFN. This means when the REFCL is monitoring the 22 kv lines for faults it must see that the capacitance of all 3 phases of 22 kv powerlines are the same Our target level of imbalance is <0.1 A. Network capacitive imbalance decreases the sensitivity of the GFN.
18 REFCL Operation Capacitance Magnitude The GFN compensates for the capacitive fault current of the line, the overall capacitance of the line is critical in determining how many lines a single GFN can protect. It is hoped that each station can be protected with a single GFN, to limit the implementation costs. As more overhead lines are transferred to be underground cables, this exponentially increases the overall line capacitance. To limit this increase we have introduced a 22kV Low Capacitance cable aka a 33kV insulated cable but marked as 22kV LC The LC cable looks like and is terminated & tested as 22kV cable Implementing into works practices & store system has been challenging Slide 18 Of course, this is only a stop-gap measure and eventually multiple GFNs
19 Current Program Status One ZSS site commissioned in service 6 months Further 2 sites operational and existing site upgrade by summer 17/18 Further 6 sites by May 2019 Extensive program of Line works Suspect Surge arrestors replacement program Slide 19 Network Hardening checks and asset replacements New Delhi India Oct 2017
20 REFCL : Summary Being implemented as a result of the Royal Commission investigation into Victoria s worst bushfire Based on technology that has been widely used in Europe for many years AusNet has lowered the residual current to <0.5A Already installed and running at one site Another two by Feb 2018 Major impact on asset replacement program Older Slide 20 New Delhi India Oct 2017
21 REFCL : Summary Slide 21 New Delhi India Oct 2017
MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT
MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral
More informationImproving High Voltage Power System Performance. Using Arc Suppression Coils
Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of
More informationHigh voltage engineering
High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency
More information3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]
Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant
More informationCoil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900
Coil Products Coil Products Customer partnership around the globe More than 250,000 coil products delivered to more than 170 countries. More than 60 years of operational experience. 35,000 in Europe 13,000
More informationMV Network Operation Issues and Elimination of Phase Voltage Unbalance
Transactions on Electrical Engineering, Vol. 6 (2017), No. 3 72 MV Network Operation Issues and Elimination of Phase Voltage Unbalance František Žák Analyst and Lecturer of the distribution network operation,
More informationProduct Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.
Title Grounding System Introduction Date October, 2016 Related Products Key words All industrial automation products Grounding, Earthing, TN, TT, IT, Introduction The automation industry of today has adopted
More informationPrinciples for Controlling Harmonics
Principles for Controlling Harmonics Harmonic distortion is present to some degree on all power systems. Fundamentally, one needs to control harmonics only when they become a problem. There are three common
More informationSummary of the Impacts of Grounding on System Protection
Summary of the Impacts of Grounding on System Protection Grounding System grounding big impact on ability to detect ground faults Common ground options:» Isolated ground (ungrounded)» High impedance ground»
More informationSAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS
SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS A. Nikander*, P. Järventausta* *Tampere University of Technology, Finland, ari.nikander@tut.fi,
More informationDC current interruption tests with HV mechanical DC circuit breaker
http: //www.cigre.org CIGRÉ A3/B4-124 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 DC current interruption tests with HV mechanical DC circuit
More informationDistribution Network Capacitor Resonance A Case Study
Distribution Network Capacitor Resonance A Case Study Authors: Chris Halliday Frank Iannelli Dr Robert Barr Director of Technical Services Power Quality Technician Director and Training Electrical Consulting
More informationHVDC High Voltage Direct Current
HVDC High Voltage Direct Current Typical HVDC Station BACK TO BACK CONVERTER STATION MONO POLAR WITH GROUND RETURN PA Back to Back Converters indicates that the Rectifiers & Inverters are located in the
More informationIMP/007/011 - Code of Practice for the Application of Lightning Protection
Version 1.1 of Issue Aug 2006 Page 1 of 11 IMP/007/011 - Code of Practice for the Application of Lightning Protection 1.0 Purpose The purpose of this document is to ensure the company achieves its requirements
More informationImproving High Voltage Power System Performance. Using Arc Suppression Coils
Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of
More informationTab 2 Voltage Stresses Switching Transients
Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles
More informationFGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI
FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown
More informationthepower to protect the power to protect i-gard LITERATURE Low and medium voltage
thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors
More informationOnline Assessment of Capacitor Banks Using Circuit Health Monitoring Technology
Online Assessment of Capacitor Banks Using Circuit Health Monitoring Technology Jeffrey Wischkaemper (Presenter) B. Don Russell Carl L. Benner Karthick Muthu Manivannan Texas A&M University College Station,
More informationMinimising the Risk of Cross-Country Faults in Systems using Arc Suppression Coils R. Burgess
Minimising the Risk of Cross-Country Faults in Systems using Arc Suppression Coils R. Burgess A. Ahfock University of Southern Queensland University of Southern Queensland West St West St Toowoomba Toowoomba
More information2 Grounding of power supply system neutral
2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the
More informationField Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.
8.3 Induced Voltage Purpose The purpose of this instruction is to provide awareness of Electrostatic and Electromagnetic induced voltages and the method required to reduce or eliminate it. An induced voltage
More informationAMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS
AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published
More informationIn power system, transients have bad impact on its
Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014
More informationGIS Disconnector Switching Operation VFTO Study
GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,
More informationFINAL - ET 60 - Electrician Theory Examination Marking Schedule
FINAL - ET 60 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions.
More informationImpact of Distributed Generation on Network Voltage Levels
EEE8052 Distributed Generation Taster Material Impact of Distributed Generation on Network Voltage Levels Steady-state rise in network voltage levels Existing practice is to control distribution voltage
More informationProblems connected with Commissioning of Power Transformers
Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.
More informationArc Suppression Coils
Arc Suppression Coils (22kV Arc Suppression Coils ) Introduction Resonance grounding by Petersen coils (Arc Suppression Coils) has been used in Scandinavia and other European countries for some eighty
More informationElectromagnetic and Radio Frequency Interference (EMI/RFI) Considerations For Nuclear Power Plant Upgrades
Electromagnetic and Radio Frequency Interference (EMI/RFI) Considerations For Nuclear Power Plant Upgrades November 9, 2016 Presented to: Presented by: Chad Kiger EMC Engineering Manager ckiger@ams-corp.com
More informationTECHNICAL BULLETIN 004a Ferroresonance
May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques
More informationA Study on Ferroresonance Mitigation Techniques for Power Transformer
A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation
More informationScienceDirect. Simulation Models for Various Neutral Earthing Methods in Medium Voltage Systems
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 1 (15 ) 118 1191 5th DAAAM International Symposium on Intelligent Manufacturing and Automation, DAAAM 1 Simulation Models for
More informationA Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid
A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid 1 Arpan K. Rathod, 2 Chaitanya H. Madhekar Students Electrical Engineering, VJTI, Mumbai, India
More informationOvervoltage Protection
Overvoltage Protection S T U D E N T M A N U A L March 31, 2005 2 STUDENT TRAINING MANUAL Prerequisites: Single-Phase Transformer Load Checks Objectives: From memory, you will be able to describe the electrical
More informationSafety through proper system Grounding and Ground Fault Protection
Safety through proper system Grounding and Ground Fault Protection November 4 th, 2015 Presenter: Mr. John Nelson, PE, FIEEE, NEI Electric Power Engineering, Inc. Event to start shortly Scheduled time:
More informationElectrical Power and Energy Systems
Electrical Power and Energy Systems 33 (2011) 1536 1541 Contents lists available at ScienceDirect Electrical Power and Energy Systems journal homepage: www.elsevier.com/locate/ijepes Analysis of lightning-caused
More informationPhilosophies for the best method
HEMP Filter Design To Meet MIL-STD-188-125 PCI Test Requirements Figure 1. E1 pulse injection testing. Antoni Jan nalborczyk Technical Director MPE Limited Liverpool, United Kingdom Philosophies for the
More informationTHE RCC GROUND FAULT NEUTRALIZER
REPRINT 18TH INTERNATIONAL CONFERENCE AND EXHIBITION ON ELECTRICITY DISTRIBUTION LINGOTTO CONFERENCE CENTRE, TURIN 6-9 JUNE 2005 THE RCC GROUND FAULT NEUTRALIZER A NOVEL SCHEME FOR FAST EARTH-FAULT PROTECTION
More informationAdi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN
Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures- Field measurements and comparison with Transient study results Pratap G. Mysore, P.E Pratap Consulting
More informationTab 8 Surge Arresters
s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.
More informationEarthing of Electrical Devices and Safety
Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This
More informationEVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION
EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech
More informationDrives 101 Lesson 5. Power Input Terminology for a VFD
Drives 101 Lesson 5 Power Input Terminology for a VFD This lesson covers the terminology associated with the incoming power to a Variable Frequency Drive (VFD) and the efforts to protect both the VFD and
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More informationThe Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.
The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why
More informationElectric Stresses on Surge Arrester Insulation under Standard and
Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems
More informationThe Research on Neutral Grounding Scheme of Fengxian 35 kv and 10 kv Power Grid
Energy and Power Engineering, 2013, 5, 897-901 doi:10.4236/epe.2013.54b172 Published Online July 2013 (http://www.scirp.org/journal/epe) The Research on Neutral Grounding Scheme of Fengxian 35 kv and 10
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationExperimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions
PQ20 June 16-18, 2010 Kuressaare Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions A. Shirkovets, A. Vasilyeva, A. Telegin LLC BOLID, Novosibirsk, Russia
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationUpgrading Your Electrical Distribution System To Resistance Grounding
Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding
More informationFERRORESONANCE SIMULATION STUDIES USING EMTP
FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in
More informationWHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems
WHITE PAPER Medium Voltage On-Site Generation Overview BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems INTRODUCTION It seems that just about everyone is looking for more power. As our
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationEarthing Guidance Notes
Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head
More informationOvervoltages While Switching Off a HV- Transformer with Arc-Suppression Coil at No-Load
Overvoltages While Switching Off a HV- Transformer with Arc-Suppression Coil at No-Load K. Teichmann, M. Kizilcay Abstract--This paper presents the results of the calculation of overvoltages that occur
More informationResults of earth fault measurements in an earth fault compensated 110-kV-system. P. Märtel H.-J. Radtke P. Schegner O. Seifert
Results of earth fault measurements in an earth fault compensated 11-kV-system P. Märtel H.-J. Radtke P. Schegner O. Seifert ESAG - Energieversorgung Sachsen Ost AG DREWAG - Stadtwerke Dresden GmbH Technology
More informationDo Capacitor Switching Transients Still Cause Problems?
Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution
More informationGreat Northern Transmission Line: Behind the (Electrical) Design
Great Northern Transmission Line: Behind the (Electrical) Design November 8, 2017 Christian Winter, P.E. Minnesota Power Sivasis Panigrahi, P.E. POWER Engineers, Inc. What is the Great Northern Transmission
More informationPOWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION
POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014
More informationDEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What
More informationPower Quality Basics. Presented by. Scott Peele PE
Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement
More informationA Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment
International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV
More informationInsulation Co-ordination For HVDC Station
Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating
More informationAn Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks
An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks Mohammad Tavakoli Bina, G.N.Alexandrov and Mohammad Golkhah Abstract A new shunt reactive power compensator,
More informationProtection of Electrical Networks. Christophe Prévé
Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé
More informationFundamental Concepts of Dynamic Reactive Compensation. Outline
1 Fundamental Concepts of Dynamic Reactive Compensation and HVDC Transmission Brian K. Johnson University of Idaho b.k.johnson@ieee.org 2 Outline Objectives for this panel session Introduce Basic Concepts
More informationConsiderations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits
1 Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits M. N. Moschakis, E. A. Leonidaki, Student Member, IEEE, N. D. Hatziargyriou, Senior
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationDETUNED INDUCTORS FOR PF IMPROVEMENT CAPACITORS
DETUNED INDUCTORS FOR PF IMPROVEMENT CAPACITORS Electrical supply systems harmonics is like a cancer on supply systems and causes extreme bad effects on the supply system component and connected electrical
More informationUtility System Lightning Protection
Utility System Lightning Protection Many power quality problems stem from lightning. Not only can the high-voltage impulses damage load equipment, but the temporary fault that follows a lightning strike
More informationA NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS
A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS Georg Achleitner, Clemens Obkircher, Lothar Fickert, Manfred Sakulin Graz University of Technology Inffeldgasse
More informationTransmission Availability Data System Definitions
Table of Contents Transmission Availability Data System Definitions February 1, 2018 1 of 31 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560 www.nerc.com Table of Contents
More informationPOWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER
POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,
More informationPower Quality and Reliablity Centre
Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview
More informationANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES
ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES Authors: Joe Perez, P.E.: SynchroGrid, College Station, Texas Hung Ming Chou, SynchroGrid, College Station, Texas Mike McMillan, Bryan
More informationAC Voltage- Pipeline Safety and Corrosion MEA 2015
AC Voltage- Pipeline Safety and Corrosion MEA 2015 WHAT ARE THE CONCERNS ASSOCIATED WITH AC VOLTAGES ON PIPELINES? AC concerns Induced AC Faults Lightning Capacitive coupling Safety Code Induced AC Corrosion
More informationRelay Communication Misoperations. Southwest Power Pool System Protection and Control Working Group
Relay Communication Misoperations Southwest Power Pool System Protection and Control Working Group Relay Misoperations The fundamental objective of power system protection schemes is to quickly provide
More informationA DUMMIES GUIDE TO GROUND FAULT PROTECTION
A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding
More informationSession Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages
Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction
More informationIn order to minimise distribution (11 and 22 kv) feeder breaker
Lightning protection for equipment on MV feeders By WJD van Schalkwyk and M du Preez, Eskom This article presents the influence of lightning on MV feeders supplying small power users (400/230 V) with focus
More informationEarth Fault Protection
Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
More informationGrounding System Theory and Practice
Grounding System Theory and Practice Course No. E-3046 Credit: 3 PDH Grounding System Theory and Practice Velimir Lackovic, Electrical Engineer System grounding has been used since electrical power systems
More informationEPR Fundamentals of Calculation of Earth Potential Rise in the Underground Power Distribution Cable Network by Ashok K.
EPR Fundamentals of Calculation of Earth Potential Rise in the Underground Power Distribution Cable Network by Ashok K. Parsotam (1997) available free from NZCCPTS website (companion paper to Cable Sheath
More informationThe InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.
The InterNational Electrical Testing Association Journal FEATURE PROTECTION GUIDE 64S Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency
More informationCalculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS
Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering
More informationGrounding for Power Quality
Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states
More informationSingle Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):
Single Earthed Neutral and Multi Earthed Neutral. SEPTEMBER 6, 2011 5 COMMENTS Single Earthed Neutral and Multi Earthed Neutral: In Distribution System Three Phase load is unbalance and non linear so The
More informationStatistical analysis of overvoltages due to the energisation of a 132 kv underground cable
University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2009 Statistical analysis of overvoltages due to
More informationModern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions
1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution
More informationCHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT
CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the
More informationEM-100 Controller. Installation Precautions. July 2016
EM-100 Controller Installation Precautions July 2016 Table of Contents 1 Overview... 3 2 The Issue... 3 3 Configuration Tutorial... 3 3.1 Working Principle... 3 3.2 Design... 5 3.3 Induction at the Opening
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationSwitching Induced Transients:
Switching Induced Transients: Transformer switching is the most commonly performed operation in any power delivery system and most of the times this operation can be performed without any undesirable consequences.
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationHarmonic control devices. ECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)
More informationHIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24
LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should
More informationProtecting Large Machines for Arcing Faults
Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating
More information