A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines

Size: px
Start display at page:

Download "A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines"

Transcription

1 A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines M.M. Saha, T. Einarsson, S. Lidström ABB AB, Substation Automation Products, Sweden Keywords: Adaptive distance protection, high speed tripping, numerical simulations, RTDS testing. Abstract This paper describes a new, high-speed protection for EHV transmission lines. The presented scheme also performs well on series compensated lines. The High speed distance protection (ZMFPDIS) function is a six zone full scheme protection with three fault loops for phase-to-phase faults and three fault loops for phase-to-earth faults for each of the independent zones, which makes the function suitable in applications with single-phase auto-reclosing. The zones can operate independently of each other in directional (forward or reverse) or non-directional mode. A new built-in adaptive load compensation algorithm prevents overreaching of the distance zones in the load exporting end during phase-to-earth faults on heavily loaded power lines. It also reduces under-reach in the importing end. The ZMFPDIS function-block itself incorporates a phase-selection element and a directional element, where these elements are represented with separate function-blocks. Implementation of the new distance protection with fast tripping algorithms has been made in a modular line terminal platform. Comprehensive test results on various test systems show the benefits of the scheme. The results with a Real Time Digital Simulator (RTDS) are presented in this paper. The scheme is now in operation under trade name REL Introduction Distance relay is one of the most important components of protection systems available to protection engineers. Distance relays can benefit from ideas in the newly developed field of adaptive protection, and can offer an even more selective and sensitive form of protection, under a variety of system configurations. The benefits of installing series capacitors in the power system include increased power transfer capability, improved power system stability, reduced system losses, improved voltage regulation, and the possibility to regulate power flow. Installation of series capacitors, however, introduces challenges to protection systems with regards for both the series compensated lines and the adjacent lines [1-3]. The protection of systems with series compensated lines is considered one of the most difficult tasks both for relay design and utility engineers. The paper [4] explores such a hybrid solution in order to achieve high speed of operation while maintaining high dependability and security. Direct application of the classic distance protection (designed for traditional lines) to the series-compensated lines results in considerable shortening of the first zone reach and also in poor transient behavior [1]. In order to overcome these difficulties the new distance protection principle for the first zone has been developed [5]. A digital distance relaying algorithm based upon symmetrical components was introduced few decades ago [6]. This protection method utilizes certain relations between voltages and currents in a three-phase post fault power system [6-7], the phase voltages and currents are transformed into symmetrical components by means of digital filtration. Ultra-high speed impedance estimation, in turn, is natural in time domain methods. This group of algorithms based on the resistiveinductive model of the fault loop circuit, usually neglecting shunt capacitances, assumes the appropriate voltages and currents as measured and solves the appropriate differential equation with respect to resistance (R) and reactance (X) of positive sequence. Various approaches to numerical differentiation and solution of relevant equation originate a number of different relaying methods of this kind [8-10]. It is therefore, not possible to use only one algorithm but rather a hybrid solution with parallel and adaptive algorithms have to be implemented. This paper explores such a hybrid solution in order to achieve high speed of operation while maintaining high dependability and security. 2 New Protection Scheme 2.1 Functionality The ZMFPDIS is providing sub-cycle, down towards halfcycle, operate time for basic faults within 60% of the line length and up to around SIR 5. This is a six zone full scheme protection with three fault loops for phase-to-phase faults and three fault loops for phase-to-earth faults for each of the independent zones, which makes the function suitable in applications with single-phase auto-reclosing. The zones can operate independently of each other in directional (forward or reverse) or non-directional mode. This makes them suitable, together with a communication scheme, for protection of power lines and cables in complex network configurations, such as parallel lines, multi-terminal lines, and so on. A new built-in adaptive load compensation algorithm [11] prevents overreaching of the distance zones in the load 1

2 exporting end during phase-to-earth faults on heavily loaded power lines. It also reduces under-reach in the importing end. The ZMFPDIS function-block itself incorporates a phaseselection element and a directional element.the operation of the phase-selection element is primarily based on current change criteria, essentially those of the High-Speed Distance function as in [12]. The directional element utilizes a set of well-established quantities to provide fast and correct directional evaluation during various conditions, including close-in three-phase faults, simultaneous faults and faults with only zero-sequence in-feed. Main Distance Protection The main protection function is a full scheme distance protection with six impedance measuring zones, having a quadrilateral characteristic [13], as shown in figure 1. The setting for each zone are independent for: reactive and resistive reach, resistive reach for single phase to ground and multiphase faults, zero sequence compensation factor and directionally of all zones. This means that the total protection scheme can be seen as a combination of three impedance elements: Phase to phase measuring elements, phase to ground measuring elements and fault detection/phase selection measuring elements for each zone and three phases. can be verified that within the accuracy no operation will occur outside the characteristic. The different measuring criterion can be identified in the characteristic and all of them have to be fulfilled for operation. The characteristic is principally identical for all type of faults. The reactive and resistive reach settings are different for the phase to ground and the phase to phase measuring loops. 2.2 Principles of Operation Filtering Practically all voltage, current and impedance quantities used within ZMFPDIS are derived from fundamental frequency phasors filtered by a half cycle filter. To improve the properties of the filter, it is reset at fault inception. The reset means that just after fault detection the filter size is reduced to sub quarter cycle length and then increased one step for each new sample until the half cycle length is reached. The aim is to only use samples from the fault period in the filter and hereby estimating the properties of the fault signal more quickly. The phasor filter is frequency adaptive in the sense that its coefficients are changed based on the estimated power system frequency. By switching to filter coefficients which are more closely related to the actual power system frequency, the properties of attenuating harmonics are maintained also during off-nominal frequency conditions. Distance Measuring Zones Each quadrilateral distance measuring zone includes six impedance measuring loops; three intended for phase-to-earth faults, and three intended for phase-to-phase as well as threephase faults. It is well-known that transients from CVT s may have a significant impact on the transient overreach of a distance protection. At the same time these transients can be very diverse in nature from one type to the other. Figure 1. Fault detection elements and adaptive expanding characteristic. A filter described in [13] gives initially an underestimation of the current, which increases security of the scheme. The comparison of the currents and voltages gives an impedance circle and the operating time is shorter. The apparent characteristic will increase when the filter factors are adjusted towards a narrower bandwidth and as the estimate of the fault current grows. Basic Characteristic The characteristic can be described by the figure 1. Due to the transient character of the measuring principle static measurement cannot verify the characteristic. Dynamically, it There are basically two types of CVT s from the point of view of ZMFPDIS; the passive and active type, which refers to the type of ferro-resonance suppression device that is employed. The active type requires more rigorous filtering which will inflict negative impact on operate times. However, this will be evident primarily at higher source impedance ratios (SIR s), SIR 5 and above, or close to the reach limit. Circular Characteristic The primary instrument for avoiding overreach and at the same time achieving fast operate times is a supplementary circular characteristic that includes some alternative processing [12]. One such circular characteristic exists for every measuring loop and quadrilateral characteristic. There are no specific reach settings for this circular zone. It uses the normal quadrilateral zone settings to determine a reach that will be appropriate. This implies that the circular characteristic will always have somewhat shorter reach than the quadrilateral zone. 2

3 Phase-Selection Element The operation of the phase-selection element is primarily based on current change criteria [12]. The current change criteria itself can however only be relied on for a short period following the fault inception (during what this will call the current change phase). Subsequent switching in the network may render the change in current invalid. So, naturally, the phase-selection element also operates on continuous criteria. 1 1 k Voltage different between phase L1 and L2 (L2 lagging L1) Memorized voltage difference between phase L1 and L2 (L2 lagging L1) Current difference between phase L1 and L2 (L2 lagging L1) Factor determining the amount of memory voltage The phase-selection element can, owing to the current change criteria, distinguish faults with minimum influence from load and fault impedance. In other words, it is not restricted by a load encroachment characteristic during the current change phase. This significantly improves performance for remote phase-to-earth faults on heavily loaded lines. One exception however is three-phase faults, for which the load encroachment characteristic always has to be applied, in order to distinguish fault from load. The continuous criteria will in the vast majority of cases operate in parallel and carry on the fault indication after the current change phase has ended. Only in some particularly difficult faults on heavily loaded lines the continuous criteria might not be sufficient, e.g. when the estimated fault impedance resides within the load area defined by the load encroachment characteristic. In this case, the indication will be restricted to a pulse lasting for one or two power system cycles. Directional Element Several criteria are employed when making the directional decision. The basis is provided by comparing a sum of positive sequence voltage and memory voltage with phase currents. For extra security, especially in making a very fast decision, this method is complemented with an equivalent comparison where, instead of the phase current, the change in phase current is used. Moreover, a basic negative sequence directional evaluation is taken into account as a reliable reference during high load condition.finally, zero sequence directional evaluation is used whenever there is more or less exclusive zero sequence in-feed. Nominally, the directional sectors that represent forward direction, one per measuring loop, are defined by the following equations. 15 < (1 ) < < (1 ) < 120 Where, 1 Positive sequence phase voltage in phase L1 1 Positive sequence memorized phase voltage in phase L1 Phase current in phase L1 2.3 Measuring Principles Fault loop equations use the complex values of voltage, current, and changes in the current. Apparent impedances are calculated and compared with the set limits. The apparent impedances at phase-to-phase faults as follows: (example for a phase L1 to phase L2 fault) = Here U and I represent the corresponding voltage and current phasors in the respective phase Ln (n = 1, 2, 3) The earth return compensation applies in a conventional manner to phase-to-earth faults (example for a phase L1 to earth fault) as: Where: = +, and are the phase voltage, phase current and residual current present to the IED is defined as: Where: 0 1 = = = 1+ 1 R0 is setting of the resistive zero sequence reach X0 is setting of the reactive zero sequence reach R1 is setting of the resistive positive sequence reach X1 is setting of the reactive positive sequence reach Here is a phasor of the residual current in IED point. This results in the same reach along the line for all types of faults. The apparent impedance is considered as an impedance loop with resistance R and reactance X. Measuring elements receive current and voltage information from the A/D converter. The check sums are calculated and compared, and the information is distributed into memory 3

4 locations. For each of the six supervised fault loops, sampled values of voltage (U), current (I), and changes in current between samples (DI) are brought from the input memory and fed to a recursive Fourier filter. The filter provides two orthogonal values for each input. These values are related to the loop impedance according to: illustrated with the full loop reach while the phase-to-phase characteristic presents the per-phase reach. in complex notation, or: = + ( ) = ( )+ ( ) ( ) = ( )+ ( ) =2 where: Re designates the real component of current and voltage, Im designates the imaginary component of current and voltage and designates the rated system frequency. Figure 2. Characteristic for phase-to-earth measuring, ohm/loop domain. The algorithm calculates measured resistance from the equation for the real value of the voltage and substitute it in the equation for the imaginary part. The equation for the measured reactance can then be solved. The final result is equal to: ( ) ( ) = ( ) ( ) ( ) ( ) = ( ) ( ) The calculated and values are updated each sample and compared with the set zone reach. The adaptive tripping counter counts the number of permissive tripping results. This effectively removes any influence of errors introduced by the capacitive voltage transformers or by other factors. The directional evaluations are performed simultaneously in both forward and reverse directions, and in all six fault loops. Positive sequence voltage and a phase locked positive sequence memory voltage are used as a reference. This ensures unlimited directional sensitivity for faults close to the IED point. 2.3 Measuring Zones Settings All zones operate according to the non-directional impedance characteristics presented in figure 2 (phase-to-earth) and figure 3 (phase-to-phase). The phase-to-earth characteristic is Figure 3. Characteristic for phase-to-phase measuring The fault loop reach in relation to each fault type may also be noted as in particular that the setting RFPP always represents the total fault resistance of the loop, even while the fault resistance (arc) may be divided into parts like for three-phase or phase-to-phase faults. The R1 and jx1 represent the positive sequence impedance from the measuring point to the fault location. 3 Implementation Implementation of the new distance protection with fast adaptive features has been made in a modular line terminal platform that is a part of an automated substation concept. The transformer module, the A/D conversion module, the main processing module, the power supply module, the binary I/O module and the communication module are shown in Figure 4. 4

5 The main processing module has CPU logics and a main logic processor. A 1 ms sampling interval has been used. Figure 4. The protection platform 4 Testing Development and evaluation of the new protection schemes has been done within an interactive software environment. The software testing of the protection schemes is accomplished by using EMTP-MATLAB software tools. EMTP/ATP files and recorded data from a real time power system simulator (with a connected disturbance recorder) have been used as input data. To thoroughly evaluate operation of the proposed protection schemes, several network configurations have been simulated. Additional tests have been done using a RTDS real time power system simulator. The simulator test was carried out in accordance with IEC standard [14]. The responses of the protection in terms of operating times for different types of faults and SIR are shown in figure 5. The parameters for the tests are shown in Table 1 in Appendix. Figure 5. Operating times for different fault types and SIR 5

6 5 Conclusions This paper describes a new, high speed protection for EHV transmission lines. The presented scheme also performs well on series compensated lines. The distance protection is providing a fast operate time for basic faults within 60% of the line length. The protection is as well designed for extra care during difficult conditions in high voltage transmission networks, like faults on long heavily loaded lines and faults generating heavily distorted signals. A new built-in adaptive load compensation algorithm prevents overreaching of the distance zones in the load exporting end during phase-to-earth faults on heavily loaded power lines. It also reduces under-reach in the importing end. Comprehensive test results on various test systems show the benefits of the scheme. The results with a Real Time Digital Simulator (RTDS) are presented in this paper. The scheme is now in operation in several countries around the world under trade name REL Acknowledgements The authors extend their grateful acknowledgement to the colleagues at the Application Function Development department of ABB AB, Substation Automation Products, Sweden, for their substantial contributions during the basic development of this concept, and colleagues at Application department for the evaluation of the algorithms and testing at RTDS. References [1] Application guide on protection of complex transmission network configurations, CIGRE materials, CIGRE SC 34 WG-04, August, (1990). [2] F. Andersson, W. Elmore, Overview of Series- Compensated Line Protection Philosophies, Western Relay Protective Conference, Washington State University, Spokane, Washington, October, (1990). [3] J. Cheetham, A Newbould, G. Stranne, Series- Compensated Line Protection: System Modelling and Test Results, 15th Annual Western Relay Protective Conference, Washington State University, Spokane, Washington, October, (1988). [4] M.M.Saha, S.Ward, Adaptive Distance Protection For Series Compensated Transmission Lines, 29th Annual Western Protective Relay Conference,Spokane,WA,October 22-24,(2002). [5] M.M. Saha, B. Kasztenny, E. Rosolowski, J. Izykowski, First zone algorithm for protection of series compensated lines, IEEE Trans. on Power Delivery, Vol.16, NO.2, pp , (2001). [6] A.G.Phadke, M.Ibrahim,T.Hlibka, Fundamental basis for distance relaying with symmetrical components, IEEE Trans. Power Appar. Syst. PAS-96 (2) (1977) [7] D.I.Walkar, S.Elagovan,A.C.Liew, Fault impedance estimation algorithm for digital distance relaying, IEEE Trans. Power Deliv., 9 (3) (1994) [8] B.Jeyasurya, W.J.Smolinski, Identification of a best algorithm for digital distance protection of transmission lines, IEEE Trans. Power Appar. Syst. PAS-102 (10) (1963) [9] A.M.Ranjbar, B.J.Cory, An improved method for digital protection of high voltage transmission lines, IEEE Trans. Power Appar. Syst. PAS-91 (2) (1975) [10] M.S.Sachdev, M.A.Baribeau, A new algorithm for digital impedance relays, IEEE Trans. Power Appar. Syst. PAS-98, (1979) [11] M.Akke, B.Westman, Load compensation in distance protection of a three-phase power transmission line, European Patent Specification, EP B1,24 March, (2010). [12] M.M.Saha, K.Wikstrom, S.Lindhal, A new approach to fast distance protection with adaptive features, IEE/DPSP, Nottingham, UK, March, (1997). [13] A. Engqvist, L. Eriksson, Numerical Distance Protection for Sub-transmission lines, Cigré, 34-04, Aug./Sept., (1988). [14] IEC Final draft International Standard, Measuring relays and protection equipment-part 121: Functional requirements for distance protection, IEC ,Ed. 1.0,95/319/FDIS, January 3, (2014) Appendix Tests and settings are for 50 Hz and 1 A. ShortLine-20km RLdFw RLdRv XLd ArgLd LongLine-100km ZoneLinkStar Phase Selection Phase Selection t CVTtype Passive type Passive type INReleasePE X R X R RFPP RFPE Table 1: Test settings for RTDS real time power system simulator. 6

The three zone distance protection, Z(1,2,3)RW is intended for systems.

The three zone distance protection, Z(1,2,3)RW is intended for systems. Page 1 Revision: - Issued: December 2002 Data subject to change without notice )HDWXUHV Intended for single or two-phase railway systems (16 2/3, 50 or 60 Hz) Full scheme distance protection, where each

More information

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006 October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date

More information

FAULT CLASSIFICATION FOR DISTANCE PROTECTION

FAULT CLASSIFICATION FOR DISTANCE PROTECTION FAULT CLASSIFICATION FOR DISTANCE PROTECTION Magnus Akke, Member IEEE ABB Automation Technology Products AB SE-7 59 Västerås, Sweden E-mail: magnus.akke@se.abb.com Abstract: This paper presents an overview

More information

Improving Current and Voltage Transformers Accuracy Using Artificial Neural Network

Improving Current and Voltage Transformers Accuracy Using Artificial Neural Network Improving Current and Voltage Transformers Accuracy Using Artificial Neural Network Haidar Samet 1, Farshid Nasrfard Jahromi 1, Arash Dehghani 1, and Afsaneh Narimani 2 1 Shiraz University 2 Foolad Technic

More information

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES N. Perera 1, A. Dasgupta 2, K. Narendra 1, K. Ponram 3, R. Midence 1, A. Oliveira 1 ERLPhase Power Technologies Ltd. 1 74 Scurfield

More information

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated

More information

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner Digital Protective Relay Dr Murari Mohan Saha ABB AB KTH/EH2740 Lecture 3 Introduction to Modern Power System Protection A digital protective relay is an industrial microprocessor system operating in real

More information

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) 7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series

More information

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third one of Distance Relays M. Azari, M. Ojaghi and K. Mazlumi* Electrical Engineering Department University of anjan anjan,

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

Harmonic Distortion Levels Measured at The Enmax Substations

Harmonic Distortion Levels Measured at The Enmax Substations Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned

More information

Analysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms

Analysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms WWWJOURNALOFCOMPUTINGORG 21 Analysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms Bruno Osorno Abstract This paper analyses and explains from the systems point of

More information

S1-3: New and re-discovered theories and practices in relay protection

S1-3: New and re-discovered theories and practices in relay protection (Cheboksary, September 9-13, 27) S1-3: New and re-discovered theories and practices in relay protection Practical experience from multiterminal line differential protection installations Z. GAJIĆ, I. BRNČIĆ,

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK

USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK P Horton, S Swain patricia.horton@ge.com, simon.swain@ge.com UK INTRODUCTION Superimposed techniques

More information

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION 23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

Protection of Extra High Voltage Transmission Line Using Distance Protection

Protection of Extra High Voltage Transmission Line Using Distance Protection Protection of Extra High Voltage Transmission Line Using Distance Protection Ko Ko Aung 1, Soe Soe Ei Aung 2 Department of Electrical Power Engineering Yangon Technological University, Insein Township

More information

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light ) 21, rue d Artois, F-75008 PARIS SECURITY AND RELIABILITY OF ELECTRIC POWER SYSTEMS http : //www.cigre.org CIGRÉ Regional Meeting June 18-20, 2007, Tallinn, Estonia Power System Reliability and Transfer

More information

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Omar G. Mrehel Hassan B. Elfetori AbdAllah O. Hawal Electrical and Electronic Dept. Operation Department Electrical

More information

Distance Protection of Cross-Bonded Transmission Cable-Systems

Distance Protection of Cross-Bonded Transmission Cable-Systems Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay Anurag Choudhary Department of Electrical and Electronics Engineering College of Engineering Roorkee, Roorkee

More information

Line protection REL 100

Line protection REL 100 Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970130) Features Simultaneous phase-phase and phaseearth loop impedance measurement, with individual numerical measuring

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

PROTECTION SIGNALLING

PROTECTION SIGNALLING PROTECTION SIGNALLING 1 Directional Comparison Distance Protection Schemes The importance of transmission system integrity necessitates high-speed fault clearing times and highspeed auto reclosing to avoid

More information

AFTER an overhead distribution feeder is de-energized for

AFTER an overhead distribution feeder is de-energized for 1902 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 A New Technique to Detect Faults in De-Energized Distribution Feeders Part II: Symmetrical Fault Detection Xun Long, Student Member,

More information

Distance Element Performance Under Conditions of CT Saturation

Distance Element Performance Under Conditions of CT Saturation Distance Element Performance Under Conditions of CT Saturation Joe Mooney Schweitzer Engineering Laboratories, Inc. Published in the proceedings of the th Annual Georgia Tech Fault and Disturbance Analysis

More information

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems T. C. Dias, B. D. Bonatto, J. M. C. Filho Abstract-- Isolated industrial power systems or with high selfgeneration,

More information

Chapter 10: Compensation of Power Transmission Systems

Chapter 10: Compensation of Power Transmission Systems Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome

More information

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM N.Shakeela Begum M.Tech Student P.V.K.K Institute of Technology. Abstract This paper presents a modified instantaneous

More information

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT * Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN Summary Capacitor Commutated Converters (CCC) were introduced to the HVDC market

More information

Review of Performance of Impedance Based and Travelling Wave Based Fault Location Algorithms in Double Circuit Transmission Lines

Review of Performance of Impedance Based and Travelling Wave Based Fault Location Algorithms in Double Circuit Transmission Lines Journal of Electrical and Electronic Engineering 2015; 3(4): 65-69 Published online July 3, 2015 (http://www.sciencepublishinggroup.com/j/jeee) doi: 10.11648/j.jeee.20150304.11 ISSN: 2329-1613 (Print);

More information

Performance Evaluation of Mho and Quadrilateral Characteristic Relays on UPFC Incorporated Transmission Line

Performance Evaluation of Mho and Quadrilateral Characteristic Relays on UPFC Incorporated Transmission Line International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 7, Number 8 (2014), pp. 827-835 International Research Publication House http://www.irphouse.com Performance Evaluation

More information

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

Differential Protection Optimal differential protection for phase shifter transformers and special transformers Differential Protection Optimal differential protection for phase shifter transformers and special transformers Due to the energy transition, a demand for renewable energy sources integration into power

More information

NEW DESIGN OF GROUND FAULT PROTECTION

NEW DESIGN OF GROUND FAULT PROTECTION NEW DESIGN OF GROUND FAULT PROTECTION J. Blumschein*, Y. Yelgin* *SIEMENS AG, Germany, email: joerg.blumschein@siemens.com Keywords: Ground fault protection, directional element, faulted phase selection

More information

Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis

Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis IJEEE, Volume 3, Spl. Issue (1) Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis Meenakshi Sahu 1, Mr. Rahul Rahangdale 1, Department of ECE, School of Engineering

More information

Teaching Distance Relay Using Matlab/Simulink Graphical User Interface

Teaching Distance Relay Using Matlab/Simulink Graphical User Interface Available online at www.sciencedirect.com Procedia Engineering 53 ( 2013 ) 264 270 Malaysian Technical Universities Conference on Engineering & Technology 2012, MUCET 2012 Part 1 - Electronic and Electrical

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Effect of Series Capacitor on Line Protection - A Case Study

Effect of Series Capacitor on Line Protection - A Case Study 112 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 22 Effect of Series Capacitor on Line Protection - A Case Study Anand Mohan, Vikas Saxena, Mukesh Khanna & V.Thiagarajan Abstract: Series compensation is a time

More information

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation Indonesian Journal of Electrical Engineering and Computer Science Vol., No., April 6, pp. 3 ~ 3 DOI:.59/ijeecs.v.i.pp3-3 3 An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability

More information

Modeling and Performance Analysis of Mho-Relay in Matlab

Modeling and Performance Analysis of Mho-Relay in Matlab Modeling and Performance Analysis of Mho-Relay in Matlab Purra Sai Kiran M.Tech Student, Padmasri Dr. B V Raju Institute of Technology, Narsapur, Medak, Telangana. ABSTRACT: This paper describes the opportunity

More information

Innovative Solutions Improve Transmission Line Protection

Innovative Solutions Improve Transmission Line Protection Innovative Solutions Improve Transmission Line Protection Daqing Hou, Armando Guzmán, and Jeff Roberts Schweitzer Engineering Laboratories, Inc. Presented at the 1998 Southern African Conference on Power

More information

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? What Is a Distance Protection Element?

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? What Is a Distance Protection Element? Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? Edmund O. Schweitzer, III and Bogdan Kasztenny Schweitzer Engineering Laboratories Copyright SEL 2017

More information

A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage

A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage 21, rue d Artois, F-758 PARIS B4_16_212 CIGRE 212 http : //www.cigre.org A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant

More information

FAULT CLASSIFICATION AND LOCATION ALGORITHM FOR SERIES COMPENSATED POWER TRANSMISSION LINE

FAULT CLASSIFICATION AND LOCATION ALGORITHM FOR SERIES COMPENSATED POWER TRANSMISSION LINE I J E E S R Vol. 3 No. 2 July-December 2013, pp. 67-72 FULT CLSSIFICTION ND LOCTION LGORITHM FOR SERIES COMPENSTED POWER TRNSMISSION LINE Shibashis Sahu 1, B. B. Pati 2 & Deba Prasad Patra 3 2 Veer Surendra

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor

Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor Durga Prasad Ananthu Assistant Professor, EEE dept. Guru Nanak Dev Engg College, Bidar adp.ananthu@gmail.com Rami Reddy

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

PROTECTION of electricity distribution networks

PROTECTION of electricity distribution networks PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of

More information

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis 1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current

More information

A C. Wallner Siemens AG Berlin, (Germany)

A C. Wallner Siemens AG Berlin, (Germany) 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-115 Session 2004 CIGRÉ A Algorithm for the Three-Pole Controlled Auto-Reclosing of Shunt Compensated Transmission Lines with a Optimization for the

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

IMPORTANCE OF VSC IN HVDC

IMPORTANCE OF VSC IN HVDC IMPORTANCE OF VSC IN HVDC Snigdha Sharma (Electrical Department, SIT, Meerut) ABSTRACT The demand of electrical energy has been increasing day by day. To meet these high demands, reliable and stable transmission

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions 10 th International Symposium Topical Problems in the Field of Electrical and Power Engineering Pärnu, Estonia, January 10-15, 2011 A Static Synchronous Compensator for Reactive Power Compensation under

More information

DESIGN AND DEVELOPMENT OF ADVANCED NUMERICAL DISTANCE RELAYING TECHNIQUES

DESIGN AND DEVELOPMENT OF ADVANCED NUMERICAL DISTANCE RELAYING TECHNIQUES SYNOPSIS OF DESIGN AND DEVELOPMENT OF ADVANCED NUMERICAL DISTANCE RELAYING TECHNIQUES A THESIS to be submitted by C. VENKATESH for the award of the degree of DOCTOR OF PHILOSOPHY DEPARTMENT OF ELECTRICAL

More information

Volume I Issue VI 2012 September-2012 ISSN

Volume I Issue VI 2012 September-2012 ISSN A 24-pulse STATCOM Simulation model to improve voltage sag due to starting of 1 HP Induction-Motor Mr. Ajay Kumar Bansal 1 Mr. Govind Lal Suthar 2 Mr. Rohan Sharma 3 1 Associate Professor, Department of

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors

A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors 452 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors Ying-Hong Lin,

More information

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Dr. Jagdish Kumar, PEC University of Technology, Chandigarh Abstract the proper selection of values of energy storing

More information

MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS

MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS 1 MADHAVI G, 2 A MUNISANKAR, 3 T DEVARAJU 1,2,3 Dept. of EEE, Sree Vidyanikethan Engineering College,

More information

Protective Relaying of Power Systems Using Mathematical Morphology

Protective Relaying of Power Systems Using Mathematical Morphology Q.H. Wu Z. Lu T.Y. Ji Protective Relaying of Power Systems Using Mathematical Morphology Springer List of Figures List of Tables xiii xxi 1 Introduction 1 1.1 Introduction and Definitions 1 1.2 Historical

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

Defining and Measuring the Performance of Line Protective Relays

Defining and Measuring the Performance of Line Protective Relays Defining and Measuring the Performance of Line Protective Relays Edmund O. Schweitzer, III, Bogdan Kasztenny, Mangapathirao V. Mynam, Armando Guzmán, Normann Fischer, and Veselin Skendzic Schweitzer Engineering

More information

ACCURATE location of faults on overhead power lines for

ACCURATE location of faults on overhead power lines for IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 4, OCTOBER 2007 2099 A Fault-Location Method for Application With Current Differential Relays of Three-Terminal Lines Jan Izykowski, Senior Member, IEEE,

More information

LIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK

LIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK LIMITS FOR TEMPORARY OEROLTAGES IN ENGLAND AND WALES NETWORK This document is for internal and contract specific use only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept

More information

PROTECTION APPLICATION HANDBOOK

PROTECTION APPLICATION HANDBOOK BOOK No 6 Revision 0 Global Organization Innovative Solutions Product & Substation System Business Business PROTECTION APPLICATION HANDBOOK BA THS / BU Transmission Systems and Substations LEC Support

More information

Voltage Sag Index Calculation Using an Electromagnetic Transients Program

Voltage Sag Index Calculation Using an Electromagnetic Transients Program International Conference on Power Systems Transients IPST 3 in New Orleans, USA Voltage Sag Index Calculation Using an Electromagnetic Transients Program Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER S. Tara Kalyani 1 and G. Tulasiram Das 1 1 Department of Electrical Engineering, Jawaharlal Nehru Technological University, Hyderabad,

More information

DETECTION OF HIGH IMPEDANCE FAULTS BY DISTANCE RELAYS USING PRONY METHOD

DETECTION OF HIGH IMPEDANCE FAULTS BY DISTANCE RELAYS USING PRONY METHOD DETECTION OF HIGH IMPEDANCE FAULTS BY DISTANCE RELAYS USING PRONY METHOD Abilash Thakallapelli, Veermata Jijabai Technological Institute Abstract Transmission lines are usually suspended from steel towers

More information

Engineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location

Engineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location Engineering Thesis The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location By Yushi Jiao Presented to the school of Engineering and

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Distance protection closed-loop testing using RTDS

Distance protection closed-loop testing using RTDS Energy Equip. Sys./ Vol. 5/No.2/ June 2017/197-210 Energy Equipment and Systems http://energyequipsys.ut.ac.ir www.energyequipsys.com Distance protection closed-loop testing using RTDS Authors Zahra Moravej

More information

High Voltage DC Transmission 2

High Voltage DC Transmission 2 High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion

More information

MMC based D-STATCOM for Different Loading Conditions

MMC based D-STATCOM for Different Loading Conditions International Journal of Engineering Research And Management (IJERM) ISSN : 2349-2058, Volume-02, Issue-12, December 2015 MMC based D-STATCOM for Different Loading Conditions D.Satish Kumar, Geetanjali

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

Designing Of Distributed Power-Flow Controller

Designing Of Distributed Power-Flow Controller IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) ISSN: 2278-1676 Volume 2, Issue 5 (Sep-Oct. 2012), PP 01-09 Designing Of Distributed Power-Flow Controller 1 R. Lokeswar Reddy (M.Tech),

More information

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer Ms. Kanchan S.Patil PG, Student kanchanpatil2893@gmail.com Prof.Ajit P. Chaudhari Associate Professor ajitpc73@rediffmail.com

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

Power Quality Improvement using Shunt Passive Filter

Power Quality Improvement using Shunt Passive Filter Power Quality Improvement using Shunt Passive Filter Assistant Professor, Department of Electrical Engineering Bhutta Group of Institutions, India Abstract: The electricity supply would, ideally, show

More information

Harmonic resonances due to transmission-system cables

Harmonic resonances due to transmission-system cables International Conference on Renewable Energies and Power Quality (ICREPQ 14) Cordoba (Spain), 8 th to 1 th April, 214 Renewable Energy and Power Quality Journal (RE&PQJ) ISSN 2172-38 X, No.12, April 214

More information

MV Network Operation Issues and Elimination of Phase Voltage Unbalance

MV Network Operation Issues and Elimination of Phase Voltage Unbalance Transactions on Electrical Engineering, Vol. 6 (2017), No. 3 72 MV Network Operation Issues and Elimination of Phase Voltage Unbalance František Žák Analyst and Lecturer of the distribution network operation,

More information

Transmission Line Models Part 1

Transmission Line Models Part 1 Transmission Line Models Part 1 Unlike the electric machines studied so far, transmission lines are characterized by their distributed parameters: distributed resistance, inductance, and capacitance. The

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes Transmission Line Protection Topics Primary/backup protection Coordination Communication-based

More information

Performance of Relaying During Wide-area Stressed Conditions

Performance of Relaying During Wide-area Stressed Conditions Performance of Relaying During Wide-area Stressed Conditions IEEE Power Systems Relaying Committee C12 Working Group Report Presented by Pratap Mysore HDR Engineering Inc. July 25, 2012, San Diego, CA

More information