Power Quality Improvement using Shunt Passive Filter

Size: px
Start display at page:

Download "Power Quality Improvement using Shunt Passive Filter"

Transcription

1 Power Quality Improvement using Shunt Passive Filter Assistant Professor, Department of Electrical Engineering Bhutta Group of Institutions, India Abstract: The electricity supply would, ideally, show a perfect sinusoidal voltage at every point of the power network. In reality, it is almost impossible to accomplish such desirable conditions. Voltage and current waveforms deviate massively from a sinusoidal. These waveform deviations are described by the use of waveform distortion and usually called harmonic distortion. Even if harmonic distortion is a quite old phenomenon it today presents one of the main concerns for public utilities, distribution system operators as well as their end customers. Already in the first years of operation of power distribution networks, there were first disturbances.. The major concern at this time was the effect that harmonic distortion had for the electric machines itself. Another well-known issue was interference in the telephone lines. But in general it can be said that harmonic distortion in former times did not have the same dangerous potential like it has today. This paper presents the design and formulation of shunt passive filter to lower the harmonics and improve the power quality.. Key Words-Shunt Passive filter, Series Active filter, Hybrid filter I. Literature Background Enjeti et al., 1992), entitled Analysis and design of an active power filter to cancel harmonic currents in low voltage electric power distribution systems, presents active power filter design considerations used for improving current quality in low voltage electric power distribution systems. Among various types of filters, shunt active filter is used for current harmonics removal and improves the power quality in electric power distribution system. (Hirofumi Akagi et al.,1998), entitled The unified power quality conditioners: the integration of series-active and shunt-active filters, In this paper the main purpose of a UPQC is to compensate for voltage flicker/imbalance, reactive power, negative sequence current, and harmonics. In other words, the UPQC has the capability of improving power quality at the point of installation on power distribution systems or industrial power systems. This paper discusses the control strategy of the UPQC, with a focus on the flow of instantaneous active and reactive powers inside the UPQC. Singh, Bhim Al-Haddad et al., 1998), entitled Harmonic elimination, reactive power compensation and load balancing in three-phase, four-wire electric distribution systems supplying non-linear loads In this paper, a new control scheme of a three-phase active power filter (APF) is proposed to eliminate harmonics, to compensate reactive power and neutral currents and to remedy system unbalance, in a three-phase four-wire electric power distribution system, with unbalanced non-linear loads. The APF is realized using three single phase IGBT based PWM- VSI bridges with a common dc bus capacitor. (Bhim singh et al., 1999), entitled A review of active filters for power quality improvements, presents in this paper presents a comprehensive review of active filter (AF)

2 configurations, control strategies, selection of components, other related economic and technical considerations, and their selection for specific applications. It is aimed at providing a broad perspective on the status of AF technology to researchers and application engineers dealing with power quality issues. (Fujita et al., 2000),entitled A hybrid active filter for damping of harmonic resonance in industrial power system, explains the feature of passive filter and active filter in a combined way called hybrid filter for the elimination of harmonic resonance in industries. In a hybrid filter, active filter works for the elimination of voltage harmonics and passive filter is used for the elimination of current harmonics. (Adil M.and Al-Zamil et al.,2001), entitled A Passive Series, Active Shunt Filter for High Power Applications This paper presents a hybrid series passive/shunt active power filter system for high power nonlinear loads. This system is comprised of a three-phase shunt active filter and series ac line smoothing reactance installed in front of the target load. The proposed system significantly reduces the required shunt active filter bandwidth. The space-vector pulse width modulation (PWM) controller is based on a dead-beat control model. It is implemented digitally using a single 16-bit microcontroller. This controller requires only the supply current to be monitored, an approach different from conventional methods II. INTRODUCTION TO PASSIVE FILTERS The passive filters are used to mitigate power quality problems in six-pulse ac-dc converter with R-L load. Moreover, apart from mitigating the current harmonics, the passive filters also provide reactive power compensation, thereby, further improving the system performance. CLASSIFICATION OF PASSIVE FILTERS Depending on the connection of different passive components, the passive filters are classified as below: Passive series filter Passive shunt filter My scope of work is on shunt passive filter PASSIVE SHUNT FILTER Fig.1 shows the schematic diagram of a passive shunt filter connected at input ac mains of sixpulse ac-dc converter with R-L load. This is the most commonly used configuration of passive filters. In this configuration different branches of passive tuned filters (low pass and high pass) tuned for the more dominant harmonics are connected in parallel with the diode rectifier with RL load. It consists of a set of low pass tuned shunt filters tuned at 5th and 7th harmonic frequencies and high pass tuned for 11th harmonic frequency. This passive filter scheme helps in sinking the more dominant 5th and 7th and other higher order harmonics and thus prevents them from flowing into ac mains. The diversion of harmonic current in the passive filter is primarily governed by the source impedance available in the system. The higher value of source impedance offers better performance of the passive filter. 192

3 Figure 1Compensation Principle of Passive Shunt Filters A passive shunt filter mainly consists of several LCR branches each tuned at a particular frequency. Fig.2 shows the equivalent circuit diagram of a passive tuned shunt filter. I S I l z s z l I F V S z sh V l Figure 2 Equivalent circuit diagram of a passive shunt filter CONTROL STATERGIES THE DUAL INSTANTANEOUS REACTIVE POWER THEORY SRF CONTROLLER The synchronous reference frame theory or d-q theory is based on time-domain reference signal estimation techniques. It performs the operation in steady-state or transient state as well as for generic voltage and current waveforms. It allows controlling the active power filters in real time system. Another important characteristic of this theory is the simplicity of the calculations, which 193

4 involves only algebraic calculation. The basic structure of SRF controller consists of direct (d-q) and inverse (d-q)- park transformations as shown in fig3. These can useful for the evaluation of a specific harmonic component of the input signals. Figure 3 Synchronous d-q reference frame based compensation algorithm These three phase space vectors stationary coordinates are easily transformed into two axis dq rotating reference frame transformation. This algorithm facilitates deriving id-iq(rotating current coordinate) from three phase stationary coordinate load current ia.ib ic, as shown in equation. The d-q transformation output signals depend on the load current (fundamental and harmonic components) and the performance of the Phase Locked Loop (PLL). The PLL circuit provides the rotation speed (rad/sec) of the rotating reference frame, where ωt is set as fundamental frequency component. The PLL circuit provides sinѳ and cosѳ. The id-iq current are sent through low pass filter (LPF) for filtering the harmonic components of the load current, which allows only the fundamental frequency components. PQ THEORY The instantaneous reactive power theory is the most widely used as a control strategy for the APF. It is mainly applied to compensation equipment in parallel connection. This theory is based on a Clarke coordinate transformation from the phase coordinates (see figure 4). In a three-phase system voltage and current vectors can be defined by v=[ v a v b v c ] T i =[ i a i b i c ] - (1) 194

5 Figure 4 Transformation from the phase reference system (abc) to the (0αβ) system. Instantaneous reactive power theory (IRPT) uses the park transform, to generate two orthogonal rotating Vectors (α and β) from the three phase vectors (a, b and c). This transform is applied to the voltage and current and is given by eqn 2,3 = - (2) = - (3) By looking at instantaneous powers, the harmonic content can be visualized as a ripple upon a DC offset representing the fundamental power. By removing the DC offset and performing the inverse park transform the harmonic current can be determined The supply voltage and load current are transformed into αβ quantities. The instantaneous active and reactive powers p and q are calculated from the transformed voltage and current as given is = - (4) Which gives, Po= vo.io instantaneous zero sequence power p= + instantaneous real power q= instantaneous imaginary power 195

6 The instantaneous active and reactive powers are filtered to leave the AC components. The Compensating currents are determined by taking the inverse and is given by = (5) This current is then multiplied by gain (k) to produce PWM signal. THREE PHASE SYSTEM WITH DIODE RECTIFIER The power circuit is a three-phase system supplied by a sinusoidal balanced three-phase 415V source and 50 Hz frequency with a source inductance of 5.8 mh and a source resistance of 3.6Ω.The three phase system supply is given to a 15kW AC-DC Diode bridge rectifier feeding an RL load. The MATLAB Simulink model of the system is shown in Fig.5. The performance of diode bridge rectifier feeding an RL load without any filter in the system is shown in figure. The system has been simulated under nonlinear balanced source and balanced load conditions. The source current is highly distorted. THREE PHASE SYSTEM WITH PASSIVE FILTER The 5th and 7th order of shunt passive filters are designed to sink in respective harmonic currents. The capacitors for the passive filter are selected to supply the specified percentage of the reactive power requirement of the load. The MATLAB Simulink model of the system with passive filters is shown in Fig 6. The passive filter helps to reduce the major amount of distortions in source current. i.e., the passive filter sinks the 5th and 7th harmonic currents by providing a low impedance path. Table 1 gives the parameter values of passive filter components for compensation. TABLE 1. Parameter values of passive filter Harmonic Inductor Capacitor 5 th 13.5mH 30µF 7 th 6.5mH 50µF FIGURE 5. SIMULINK DIAGRAM OF THREE PHASE SYSTEM 196

7 FIGURE 6. SIMULINK DIAGRAM OF THREE PHASE SYSTEM WITH PASSIVE FILTER SIMULATION RESPONSE The system parameters considered for the study of Filter is given below in Table 2. COMPONENTS SPECIFICATIONS AC Source V s =415v, f=50hz, R s =3.6Ω,L S =5.8Mh Non Linear Load R L =40Ω, L L =50mH Passive Filter L 5 =13.5mH C 5 =30F, L 7 =6.75mH C 5 = 50F Table 2Specifications for Test System 197

8 Simulation Response without filters Simulation Response with Passive shunt filter SIMULATION RESPONSE WITHOUT FILTER Figure-7 Waveforms of source voltage without filters Figure-8 Waveforms of source current without filters Figure 7 and 8 shows the waveforms of source voltage and current of the three phase system without compensating. The nonlinear unbalanced load consisted of three phase uncontrolled rectifiers with a capacitor and a resistor connected in parallel at the dc side.figure 5 shows the three source currents. The THD of the current measured is 23% and power factor measured is SIMULATION RESPONSE WITH SHUNT PASSIVE FILTER Figure-9 Waveforms of load voltage with shunt passive filter 198

9 Figure 10 Waveforms of load current with passive shunt filter Figure- 11 Waveforms of source voltage with passive shunt filter 199 Figure-12 Waveforms of source current with passive shunt filter

10 Figure 9 and 10 shows the waveforms of load voltage and current, Figure 11 and 12 shows the waveforms of source voltage and current. When the shunt passive filter is connected have a THD falls from 23.0% to 4.3%. The passive filter was only designed to compensate the source current harmonics; the reactive power was not taken into account. The power factor rises to 0.99 Conclusion This paper proposed shunt passive filter design to enhance the power quality in transmission and distribution system. REFERENCES Third EditionBhim Singh, Kamal Al-Haddad, Senior Member, IEEE, and Ambrish Chandra, Member, IEEE(1999) A Review of Active Filters for Power Quality Improvement IEEE Transactions Industrial Electronics, VOL. 46, NO. 5, OCTOBER Adil M. Al, -Zamil, Member, IEEE, and David A. Torrey, Member, IEEE(2001), A Passive Series, Active Shunt Filter for High Power Applications, Transactions of Power Electronics, Vol. 16 NO. 1, C. Nalini Kiran, Subhransu Sekhar Dash, S.Prema Latha (2011) A Few Aspects of Power Quality Improvement Using Shunt Active Power Filter International Journal of Scientific & Engineering Research Volume 2, Issue 5, May Jinn-Chang, Hurng-Liahng, Kuen-Der, Hsin-Hsing Hsiao (2012), Three-phase fourwire hybrid power filter using a smaller power converter Electric Power Systems Research 87 (2012) Mark F,Roger C.[2012] Electrical Power System Quality Tata Mc Graw-Hill BIOGRAPHY Name - Chamandeep kaur Designation-Assistant Professor in Bhutta College of Institutions, India Qualification-Btech (Electrical Engg) from Guru Nanak Dev Engineering College Mtech(power Engg) from Guru Nanak Dev Engineering College 200

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 651-660 Research India Publications http://www.ripublication.com/aeee.htm Design and Simulation of Three Phase

More information

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction Anju Yadav 1, K. Narayanan 2, Binsy Joseph 3 1, 2, 3 Fr. Conceicao Rodrigues College of Engineering, Mumbai, India

More information

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK IMPROVED CONTROL METHOD OF GUPQC UNDER DISTORTED AND UNBALANCED LOAD CONDITION

More information

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): 2349-784X A Synchronous Reference Frame Theory-Space Vector Modulation (SRF SPVM) based Active

More information

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter B.S.Nalina 1 Ms.V.J.Vijayalakshmi 2 Department Of EEE Department Of EEE 1 PG student,skcet, Coimbatore, India

More information

Power Quality improvement of a three phase four wire system using UPQC

Power Quality improvement of a three phase four wire system using UPQC International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Volume: 2 Issue: 4 July-215 www.irjet.net p-issn: 2395-72 Power Quality improvement of a three phase four wire system

More information

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller J.Venkatesh 1, K.S.S.Prasad Raju 2 1 Student SRKREC, India, venki_9441469778@yahoo.com

More information

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online): 2321-0613 Modeling and Simulation of SRF Control Based Shunt Active Power Filter and Application

More information

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION 5DESIGN PARAMETERS OF SHUNT ACTIE FILTER FOR HARMONICS CURRENT MITIGATION Page 59 A.H. Budhrani 1*, K.J. Bhayani 2, A.R. Pathak 3 1*, 2, 3 Department of Electrical Engineering,..P. Engineering College

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 3, Issue 8 (September 2012), PP. 16-20 Implementation of SRF based Multilevel Shunt

More information

Comparison of Control Algorithms for Shunt Active Filter for Harmonic Mitigation

Comparison of Control Algorithms for Shunt Active Filter for Harmonic Mitigation Comparison of Control Algorith for Shunt Active Filter for Harmonic Mitigation A.Giri Prasad¹,K.Dheeraj²,A.Naveen Kumar³, Electrical and Electronics Engineering Department ST.Peter s Engineering college,

More information

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER Bhargav R. Gamit 1, Sanjay R. Vyas 2 1PG Scholar, EE Dept., LDRP-ITR, Gandhinagar, Gujarat, India. 2Head of Department, EE Dept.,

More information

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, PP 20-26 www.iosrjournals.org Shunt Active Power Filter based on SRF theory and Hysteresis Band Current

More information

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Modeling and Simulation of SRF and P-Q based Control DSTATCOM International Journal of Engineering Research and Development ISSN: 2278-067X, Volume 1, Issue 10 (June 2012), PP.65-71 www.ijerd.com Modeling and Simulation of SRF and P-Q based Control DSTATCOM Kasimvali.

More information

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink Parag Datar 1, Vani Datar 2, S. B. Halbhavi 3, S G Kulkarni 4 1 Assistant Professor, Electrical and Electronics Department,

More information

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS George Adam, Alina G. Stan (Baciu) and Gheorghe Livinţ Department of Electrical Engineering Technical University of Iaşi 700050, Iaşi, Romania E-mail:

More information

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Control Of Shunt Active Filter Based On Instantaneous Power Theory B.Pragathi Department of Electrical and Electronics Shri Vishnu Engineering College for Women Bhimavaram, India Control Of Shunt Active Filter Based On Instantaneous Power Theory G.Bharathi Department

More information

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF) DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF) Rosli Omar, Mohammed Rasheed, Zheng Kai Low and Marizan Sulaiman Universiti Teknikal Malaysia

More information

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 4 (2013), pp. 473-483 International Research Publication House http://www.irphouse.com A Simple Control Algorithm for Three-Phase

More information

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller Rekha Soni Department of EEE C.V.R.U. Kota, Bilaspur (C.G.) soni.rekha25@gmail.com Durga

More information

ABSTRACT I. INTRODUCTION

ABSTRACT I. INTRODUCTION International Journal of Scientific Research in Computer Science, Engineering and Information Technology 2017 IJSRCSEIT Volume 2 Issue 6 ISSN : 2456-3307 Design of Shunt Active Power Filter for Power Quality

More information

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System International Journal of Electrical Engineering. ISSN 0974-2158 Volume 5, Number 7 (2012), pp. 853-862 International Research Publication House http://www.irphouse.com A Novel FPGA based PWM Active Power

More information

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current BUSINESS AND TECHNOLOGY (IJSSBT), Vol., No., June 05 ISSN (Print) 77 76 Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current Mr. S.

More information

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation A.Jeraldine viji Associate Professor, EEE department, Mailam Engineering College, Tamil Nadu E-mail: jeraldrovan@gmail.com Dr.M.Sudhakaran

More information

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Comparison

More information

Literature Review for Shunt Active Power Filters

Literature Review for Shunt Active Power Filters Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller

More information

Harmonics Elimination Using Shunt Active Filter

Harmonics Elimination Using Shunt Active Filter Harmonics Elimination Using Shunt Active Filter Satyendra Gupta Assistant Professor, Department of Electrical Engineering, Shri Ramswaroop Memorial College of Engineering and Management, Lucknow, India.

More information

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER P. SWEETY JOSE JOVITHA JEROME Dept. of Electrical and Electronics Engineering PSG College of Technology, Coimbatore, India.

More information

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems

More information

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement Amaljith M K, Senthil kumar R Abstract This paper presents a three-phase, four-wire, four-leg

More information

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates 1Mandadi Surender Reddy, 2 Vigrahala Srikanth 1 Asst Professor, Department of Electrical and Electronics

More information

Enhancement of Power Quality Using Advanced Series Active Power Filters

Enhancement of Power Quality Using Advanced Series Active Power Filters Enhancement of Power Quality Using Advanced Series Active Power Filters Manoj siva kumar 1, P.Rayalakshmi 2 Associate Professor, Dept. of EEE, PBRVITS, Kavali, SPSR Nellore, A.P, India 1 M.Tech Student,

More information

International Journal of Advance Research in Engineering, Science & Technology

International Journal of Advance Research in Engineering, Science & Technology Impact Factor (SJIF): 3.632 International Journal of Advance Research in Engineering, Science & Technology e-issn: 2393-9877, p-issn: 2394-2444 (Special Issue for ITECE 2016) Harmonic Mitigation of Fluctuating

More information

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Harmonics Reduction using 4-Leg Shunt Active Power Filters Harmonics Reduction using 4-Leg Shunt Active Power Filters K Srinivas Assistant Professor & Department of EEE & JNTUH CEJ Telangana, India. Abstract Harmonics in power system are caused by highly non-linear

More information

Harmonic Analysis in Non-linear Load by using Hybrid UPQC

Harmonic Analysis in Non-linear Load by using Hybrid UPQC IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 06 November 2016 ISSN (online): 2349-6010 Harmonic Analysis in Non-linear Load by using Hybrid UPQC Anupsingh

More information

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

Assessment of Different Compensation Strategies in Hybrid Active Power Filters Assessment of Different Compensation Strategies in Hybrid Active Power Filters Rashed Bahrekazemi Electrical Engineering Department Iran University of Science & Technology (IUST) Tehran, Iran rbahrkazemi@ee.iust.ac.ir

More information

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory 1 R.V.L. Narayana Divakar, 2 P.Kishore, 3 CH.Ravi Kumar, 4 V.Madhu Kishore, 5 V.Pradeep Kumar 1 Assistant Professor, 2,3,4,5

More information

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013 Power Quality Enhancement Using Hybrid Active Filter D.Jasmine Susila, R.Rajathy Department of Electrical and electronics Engineering, Pondicherry Engineering College, Pondicherry Abstract This paper presents

More information

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER Rajesh Kr. Ahuja 1, Aasha Chauhan 2, Sachin Sharma 3 Rajesh Kr. Ahuja Faculty, Electrical & Electronics Engineering Dept.

More information

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2 IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online): 2321-0613 Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive

More information

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN 2250-155X Vol. 3, Issue 2, Jun 2013, 309-318 TJPRC Pvt. Ltd. PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID

More information

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive B. Mohan Reddy 1, G.Balasundaram 2 PG Student [PE&ED], Dept. of EEE, SVCET, Chittoor

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory American Journal of Management Science and Engineering 27; 2(3): 4-5 http://www.sciencepublishinggroup.com/j/ajmse doi:.648/j.ajmse.2723.2 Comparison of Shunt Active Power Filter Control Strategies for

More information

Indirect Current Control of LCL Based Shunt Active Power Filter

Indirect Current Control of LCL Based Shunt Active Power Filter International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 3 (2013), pp. 221-230 International Research Publication House http://www.irphouse.com Indirect Current Control of LCL Based

More information

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1 International Journal of Engineering & Science Research ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1 1 M.Tech

More information

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side 1 Jaykant Vishwakarma, 2 Dr. Arvind Kumar Sharma 1 PG Student, High voltage and Power system, Jabalpur

More information

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Application of Fuzzy Logic Controller in Shunt Active Power Filter IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 11 April 2016 ISSN (online): 2349-6010 Application of Fuzzy Logic Controller in Shunt Active Power Filter Ketan

More information

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 2 Ver. II (Mar Apr. 2014), PP 59-67 Mitigation of Line Current Harmonics Using Shunt

More information

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011 Design of Shunt Active Power Filter to eliminate the harmonic currents and to compensate the reactive power under distorted and or imbalanced source voltages in steady state Sangu Ravindra #1, Dr.V.C.Veera

More information

A Comparative Study on Four Time-Domain Harmonic Detection Methods for Active Power Filters Serving in Distorted Supply

A Comparative Study on Four Time-Domain Harmonic Detection Methods for Active Power Filters Serving in Distorted Supply A Comparative Study on Four Time-Domain Harmonic Detection Methods for Active Power Filters Serving in Distorted Supply Mahmoud F.Shousha *,Member, IAENG,Sherif A. Zaid **, and Osama A.Mahgoub *** Abstract

More information

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter ISSN (Online) : 19-875 ISSN (Print) : 47-6710 International Journal of Innovative Research in Science, Engineering and Technology Volume, Special Issue, March 014 014 International Conference on Innovations

More information

Power Control and Quality Management in DG Grid Interfaced Systems

Power Control and Quality Management in DG Grid Interfaced Systems Power Control and Quality Management in DG Grid Interfaced Systems B. Raghava Rao 1, N. Ram Mohan 2 1 PG Student, Dept. of EEE, V.R.Siddhartha Engineering College, A.P. (state), India. 2 Associate Professor,

More information

Unified Power Quality Conditioner (UPQC) using MATLAB Hiya Divyavani, Prof.(Dr.)Mohd.Muzzam Noida International University ----------------------------------------------------------------- Abstract: The

More information

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality P.Padmavathi, M.L.Dwarakanath, N.Sharief, K.Jyothi Abstract This paper presents an investigation

More information

KKR &KSR institute of Technology and sciences,vinjanampadu(v),vatticherukuru(m) Guntur(D) , Andhra Pradesh,India. I.

KKR &KSR institute of Technology and sciences,vinjanampadu(v),vatticherukuru(m) Guntur(D) , Andhra Pradesh,India. I. Power Quality Enhancement by Using Multilevel Shunt Active Power Filter with Renewable Energy Sources B.Raju 1, Mr.Y.Rajesh babu 2 1 M.tech Student, 2 Assiatant professor, Department of EEE KKR &KSR institute

More information

SCIENCE & TECHNOLOGY

SCIENCE & TECHNOLOGY Pertanika J. Sci. & Technol. 25 (S): 249-256 (217) SCIENCE & TECHNOLOGY Journal homepage: http://www.pertanika.upm.edu.my/ Synchronous Reference Frame Fundamental Method in Shunt Active Power Filter for

More information

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER IOSR Journal of Electronics & Communication Engineering (IOSR-JECE) ISSN(e) : 2278-1684 ISSN(p) : 2320-334X, PP 68-73 www.iosrjournals.org INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE

More information

Mitigation of Voltage Sag/Swell Using UPQC

Mitigation of Voltage Sag/Swell Using UPQC Mitigation of Voltage Sag/Swell Using UPQC 1 Rajat Patel, 2 Prof.Maulik A. Chaudhari 1 PG Scholar, 2 Assistant Professor Electrical Department, Government engineering college, Bhuj Gujarat Technological

More information

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions 10 th International Symposium Topical Problems in the Field of Electrical and Power Engineering Pärnu, Estonia, January 10-15, 2011 A Static Synchronous Compensator for Reactive Power Compensation under

More information

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm Parameter control scheme for active power filter based on NARX neural network A. Y. HATATA, M. ELADAWY, K. SHEBL Department of Electric Engineering Mansoura University Mansoura, EGYPT a_hatata@yahoo.com

More information

Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter

Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter V.Balasubramanian 1, T.Rajesh 2, T.Rama Rajeswari 3 P.G. Student,

More information

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter A.Ilakkia 1, R.Rajalakshmi 2 PG Student [PED], Dept of EEE, PSNA College of Engg and Tech, Dindigul, Tamilnadu, India 1 Assistant

More information

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating P.Ankineedu Prasad 1, N.Venkateswarlu 2. V.Ramesh 3, L.V.Narasimharao 4 Assistant Professor 12 & Professor 4& Research Scholar

More information

Shunt Active Power Filter for Compensation of System Harmonics

Shunt Active Power Filter for Compensation of System Harmonics Volume 5, Issue 1 (February, 018) E-ISSN : 48-7 P-ISSN : 454-1 Shunt Active Power Filter for of System Harmonics Badal Devanand Umare 1, A. S. Sindekar 1 PG Scholar, HOD, Department of Electrical Engineering,

More information

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter Swapnil S. Motaphale Affiliation TSSM S BSCOER, Pune ME Electrical (Power System) Savitribai Phule

More information

Improvement of Power Quality by using Active Filter based on Vectorial Power Theory Control Strategy on the MATLAB-Simulink Platform

Improvement of Power Quality by using Active Filter based on Vectorial Power Theory Control Strategy on the MATLAB-Simulink Platform Improvement of Power Quality by using Active Filter based on Vectorial Power Theory Control Strategy on the MATLAB-Simulink Platform Metkari Archana Subhash ElectricalEngg., Government college of engg.,

More information

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER Dr.V.Parimala 1, Dr.D.GaneshKumar 2 1 Asst.Prof (SG)-Dept of EEE, P.A College of Engineering and Technology. 2 Prof, Dept of ECE, P.A

More information

Chapter 4. Hybrid series active filter. 4.1 Introduction

Chapter 4. Hybrid series active filter. 4.1 Introduction Chapter 4 Hybrid series active filter 4.1 Introduction The lowest harmonics in the source current spectrum of a 12-pulse converter are theoretically the 11 th and the 13 th harmonics but some residual

More information

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION N.VANAJAKSHI Assistant Professor G.NAGESWARA RAO Professor & HOD Electrical & Electronics Engineering Department Chalapathi Institute of

More information

HYBRID ACTIVE FILTER WITH VARIABLE CONDUCTANCE FOR HARMONIC RESONANCE SUPPRESSION USING ANN

HYBRID ACTIVE FILTER WITH VARIABLE CONDUCTANCE FOR HARMONIC RESONANCE SUPPRESSION USING ANN HYBRID ACTIVE FILTER WITH VARIABLE CONDUCTANCE FOR HARMONIC RESONANCE SUPPRESSION USING ANN 1 M.Shyamala, 2 P.Dileep Kumar 1 Pursuing M.Tech, PE Branch, Dept of EEE. 2 Assoc.Prof,EEE,Dept,Brilliant Institute

More information

2020 P a g e. Figure.2: Line diagram of series active power filter.

2020 P a g e. Figure.2: Line diagram of series active power filter. Power Quality Improvement By UPQC Using ANN Controller Saleha Tabassum 1, B.Mouli Chandra 2 (Department of Electrical & Electronics Engineering KSRM College of Engineering, Kadapa.) (Asst. Professor Dept

More information

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality enhancement of a distribution line with DSTATCOM ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical

More information

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy Design of Shunt Active Power Filter by using An Advanced Current Control Strategy K.Sailaja 1, M.Jyosthna Bai 2 1 PG Scholar, Department of EEE, JNTU Anantapur, Andhra Pradesh, India 2 PG Scholar, Department

More information

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads Vol.2, Issue.2, Mar-Apr 2012 pp-431-435 ISSN: 2249-6645 Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads M. CHANDRA SEKHAR 1, B. KIRAN BABU

More information

ISSN Vol.03,Issue.07, August-2015, Pages:

ISSN Vol.03,Issue.07, August-2015, Pages: WWW.IJITECH.ORG ISSN 2321-8665 Vol.03,Issue.07, August-2015, Pages:1276-1281 Comparison of an Active and Hybrid Power Filter Devices THAKKALAPELLI JEEVITHA 1, A. SURESH KUMAR 2 1 PG Scholar, Dept of EEE,

More information

A Study of Various Filters for Power Quality Improvement

A Study of Various Filters for Power Quality Improvement A Study of Various Filters for Power Quality Improvement Dharmendra Gour 1, Devendra Dohare 2, Abhishek Saxena 3 PG (Student), Department of Electrical Engineering, Maharana Pratap College of Technology,

More information

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 86 CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 5.1 INTRODUCTION Distribution systems face severe power quality problems like current unbalance, current harmonics, and voltage unbalance,

More information

Active Power Filter with Fast PI Controller Using Matlab/simulink

Active Power Filter with Fast PI Controller Using Matlab/simulink Active Power Filter with Fast PI Controller Using Matlab/simulink Dipak Badgujar,Anil Kumar Chaudhary,C.Veeresh, Email:dipakbadgujar84@gmail.com,anilkumar6352@gmail.com Abstract In a modern power system,

More information

Review on Shunt Active Power Filter for Three Phase Four Wire System

Review on Shunt Active Power Filter for Three Phase Four Wire System 2014 IJEDR Volume 2, Issue 1 ISSN: 2321-9939 Review on Shunt Active Power Filter for Three Phase Four Wire System 1 J. M. Dadawala, 2 S. N. Shivani, 3 P. L. Kamani 1 Post-Graduate Student (M.E. Power System),

More information

Power Control Scheme of D-Statcom

Power Control Scheme of D-Statcom ISSN : 48-96, Vol. 4, Issue 6( Version 3), June 04, pp.37-4 RESEARCH ARTICLE OPEN ACCESS Power Control Scheme of D-Statcom A. Sai Krishna, Y. Suri Babu (M. Tech (PS)) Dept of EEE, R.V.R. & J.C. College

More information

PLL Synchronization with PID Controller Based Shunt Active Power Line Conditioners

PLL Synchronization with PID Controller Based Shunt Active Power Line Conditioners International Journal of Computer and Electrical Engineering, Vol.3, No., February, PLL Synchronization with PID Controller Based Shunt Active Power Line Conditioners Karuppanan P and Kamala Kanta Mahapatra

More information

DESIGN OF A HYBRID ACTIVE FILTER FOR HARMONICS SUPPRESSION WITH VARIABLE CONDUCTANCE IN INDUSTRIAL POWER SYSTEMS USING FUZZY

DESIGN OF A HYBRID ACTIVE FILTER FOR HARMONICS SUPPRESSION WITH VARIABLE CONDUCTANCE IN INDUSTRIAL POWER SYSTEMS USING FUZZY DESIGN OF A HYBRID ACTIVE FILTER FOR HARMONICS SUPPRESSION WITH VARIABLE CONDUCTANCE IN INDUSTRIAL POWER SYSTEMS USING FUZZY K.REDDI THULASI 1 MR B. SREENIVAS REDDY 2 V.VEERA NAGI REDDY 3 M.Tech (EPS),

More information

Reactive Power Compensation of LC Coupling Hybrid Active Power Filters by DC Link Voltage Controls

Reactive Power Compensation of LC Coupling Hybrid Active Power Filters by DC Link Voltage Controls Volume-5, Issue-5, October-2015 International Journal of Engineering and Management Research Page Number: 129-133 Reactive Power Compensation of C Coupling Hybrid Active Power Filters by DC ink Voltage

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

ENHANCEMENT IN WORKING PERFORMANCE OF CUSTOM POWER DEVICE USING DIFFERENT CONTROLLING METHODS

ENHANCEMENT IN WORKING PERFORMANCE OF CUSTOM POWER DEVICE USING DIFFERENT CONTROLLING METHODS ENHANCEMENT IN WORKING PERFORMANCE OF CUSTOM POWER DEVICE USING DIFFERENT CONTROLLING METHODS 1 M. KALYANASUNDARAM, 2 Dr. S. SURESHKUMAR 1 Assistant Professor, Department of Electrical & Electronics Engineering,

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

POWER QUALITY IMPROVEMENT BY HARMONIC REDUCTION USING THREE PHASE SHUNT ACTIVE POWER FILTER WITH p-q & d-q CURRENT CONTROL STRATEGY

POWER QUALITY IMPROVEMENT BY HARMONIC REDUCTION USING THREE PHASE SHUNT ACTIVE POWER FILTER WITH p-q & d-q CURRENT CONTROL STRATEGY POWER QUALITY IMPROVEMENT BY HARMONIC REDUCTION USING THREE PHASE SHUNT ACTIVE POWER FILTER WITH p-q & d-q CURRENT CONTROL STRATEGY DIBYENDU BHADRA (111EE0429) RAJNISH KUMAR MEENA (111EE0449) Department

More information

Design of Unified Power Quality Conditioner (UPQC) Connected To Three Phase Four Wire System

Design of Unified Power Quality Conditioner (UPQC) Connected To Three Phase Four Wire System Design of Unified Power Quality Conditioner (UPQC) Connected To Three Phase Four Wire System Paduchuri.Chandra Babu and Subhransu.Sekhar.Dash Abstract In this paper presents a Design of a Unified Power

More information

Chapter 2 Shunt Active Power Filter

Chapter 2 Shunt Active Power Filter Chapter 2 Shunt Active Power Filter In the recent years of development the requirement of harmonic and reactive power has developed, causing power quality problems. Many power electronic converters are

More information

P.CHAITHANYAKUMAR, T.VARAPRASAD/

P.CHAITHANYAKUMAR, T.VARAPRASAD/ Design of Unified Power Quality Conditioner (UPQC) to Improve the Power Quality Problems by Using P-Q Theory P.CHAITHANYAKUMAR * T.VARAPRASAD** *PG Student Department Of Electrical & Electronics Engineering

More information

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control Prof. D.S.Chavan 1, Mukund S.Mahagaonkar 2 Assistant professor, Dept. of ELE, BVCOE, Pune, Maharashtra, India 1

More information

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory Emílio F. Couto, Júlio S. Martins, João L. Afonso Department of Industrial Electronic University of Minho Campus de Azurém

More information

Active Harmonics Filtering of Distributed AC System

Active Harmonics Filtering of Distributed AC System Active Harmonics Filtering of Distributed AC System M.S.Priya M.Sivaram Krishnan S.Sri ragavi P.G Scholar, Dept. of EEE P.G Scholar, Dept. of ECE P.G Scholar, Dept. of EEE Dr.Sivanthi Aditanar College

More information

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

Design of Shunt Active Filter to Improve Power Quality using Pq Theory Design of Shunt Active Filter to Improve Power Quality using Pq Theory Miss. Dhanshri sarjerao Pawar Department of Electrical engineering Dr. Babasabeb Ambedakar Technological University Lonere, Raigad

More information

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL Journal of Engineering Science and Technology Vol. 10, No. 4 (2015) 420-433 School of Engineering, Taylor s University PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT

More information

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 78-676,p-ISSN: -, Volume, Issue Ver. II (Jan Feb. 5), PP 68-74 www.iosrjournals.org Implementation of Instantaneous Reactive Power

More information

Performance Improvement of Active Power Filter using a New Control Strategy under Unbalanced Grid Voltage

Performance Improvement of Active Power Filter using a New Control Strategy under Unbalanced Grid Voltage 8 Performance Improvement of Active Power Filter using a New Control Strategy under Unbalanced Grid Voltage Mouna Tali1, Tamou Nasser2 and Ahmed Essadki 3 1 Laboratory :Electrical Engineering University

More information

Unit Vector Theory based Unified Power Quality Conditioner for Power Quality Improvement

Unit Vector Theory based Unified Power Quality Conditioner for Power Quality Improvement Unit Vector Theory based Unified Power Quality Conditioner for Power Quality Improvement N.C.Kotaiah 1, Dr.K.Chandra Sekhar 2 Associate Professor, Department of Electrical & Electronics Engineering, R.V.R

More information