Effect of Series Capacitor on Line Protection - A Case Study
|
|
- Melinda Davidson
- 5 years ago
- Views:
Transcription
1 112 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 22 Effect of Series Capacitor on Line Protection - A Case Study Anand Mohan, Vikas Saxena, Mukesh Khanna & V.Thiagarajan Abstract: Series compensation is a time tested reliable technology being used successfully to compensate the reactance of transmission lines. The advantage of use of series compensation on long EHV lines is improvement in Transmission System performance and increase in line loadability. This has been well established and implemented for many years world over. For the first time in India fixed series compensation of 35% has been proposed on a 4kV S/c i.e Kanpur - Ballabhgarh 4kV S/c to enhance the line loadability and system stability. The introduction of a series capacitor into the line affects the line distance protection due to abrupt change in line series impedance (which is inductive) at the series capacitor. The paper discusses in detail the effect of series compensation on distance protection and various Short Circuit and EMTP studies carried out. I. INTRODUCTION Indian Power System, presently with more than 1GW installed capacity, is being operated as four independent regional grids - Northern, Southern, Western and Eastern & North-Eastern Regions. Northern region is one of the largest grid with an installed capacity of about 27 GW, consisting of eight states and a Union Territory. Eastern part of Northern Region has major coal reserves and thermal Power Stations like Singrauli, Rihand, Anpara and Obra have been developed to tap this reserve. Power from these stations is transferred to Western part of the grid, where there is a concentration of loads, through long distance 4 kv lines via Kanpur/Panki axis. For transfer of power beyond Kanpur/Panki towards Western part, presently there are mainly three 4kV AC lines i.e. Kanpur - Ballabgarh (395km), Panki-Muradnagar (4km) and Kanpur Agra (25km) (Figure-1). The loading on Kanpur - Agra line remains generally higher and also due to long length of the other two, it has been proposed to install series compensation on Kanpur-Ballabgarh and Panki-Muradnagar lines. Under Phase-I, series capacitor is proposed to be installed on Kanpur-Ballabgarh and under phase-ii, it is proposed to install on Panki-Muradnagar 4kV S/c line. Application of Series compensation increases the line loadability, But the integration of series capacitor into the line makes the line protection complex due to abrupt change in line series impedance at the series capacitor, which changes the fault current, voltage and apparent impedance measured by the line relays. Moreover, the fault current may change from its normal lagging angle, with respect to voltage, to a leading angle. The presence of series capacitor on a line can cause incorrect operation of the relays on that line and relays on adjacent lines. Anand Mohan, Vikas Saxena, Mukesh Khanna & V.Thiagarajan Engineering Division Power Grid Corporation of India Ltd B-9 Qutub Instt. Area, Katwaria Sarai, New Delhi-11 16, India Figure I- Schematic diagram of Series capacitor Protection This paper discusses in detail the studies carried out to study the effect of series compensation on conventional distance relays and remedial action taken. II. SYSTEM DESCRIPTION A. Network configuration Fig. 1 shows the spatial arrangement of proposed Series Compensation, the series capacitor is proposed to be located at Ballabgarh end of Kanpur-Ballabgarh 4kV S/c line. Ballabgarh, other than Kanpur, is connected to Agra and Jaipur by 4kV Single Circuit line while a 4kV Double Circuit line connects it to Dadri. Similarly Kanpur bus is connected to Panki and Allahabad by two numbers of 4kV lines while it is connected to Singrauli and Agra by 4kV Single Circuit line. Agra is connected to both Kanpur and Ballabgarh by 4kV Single Circuit line. B. Series compensation Theoretically, a transmission system can carry power up to its thermal loading, in the case of Kanpur-Ballabgarh line 4km built with twin Moose conductor it is 87 MVA. But loading on a long line is restricted well below its thermal loading due to angular separation been the two buses, which as per Transmission Planning Criteria should be within 3 degrees. For example, a 4km long 4kV line with per unit voltage at both can be loaded upto only 57MW. Provision of series compensation on the line effectively reduces the line impedance and hence the angular separation between the buses. After detailed analysis 35% series compensation has been proposed on Kanpur-Ballabgarh line. The 35% series compensation consists of banks of 27% and 8%, has been considered at Ballabgarh end of Kanpur-Ballabgarh line. The
2 INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 72132, DECEMBER 27-29, % bank is proposed to be converted into Thyristor Controlled Series Capacitor in future to improve Dynamic stability. III. CAPACITOR DESCRIPTION BALLABGARH BUS VOLTAGE A Series Capacitor reduces the inductance in a power system leading to higher short circuit currents. It is not feasible to design a series capacitor that has high enough voltage ratings to withstand such high fault currents. Hence to protect the capacitor from damage capacitor banks are bypassed when the current touches the protective level. To protect the Series capacitor banks on Kanpur- Ballabgarh line, a combination of MOV triggered spark gap and Series Capacitor Bypass Circuit Breaker is being provided. With the inception of the fault, MOV bypasses the capacitor carrying the fault current. Energy dissipation capacity of MOV is also limited, therefore triggered spark gap bypasses the MOV. Schematic diagram of the Series capacitor along with protection is shown in Figure-II. The spark gap is triggered within 1msec of MOV conduction, after which bypass circuit breaker will be closed. The effect of series compensation along with its MOV during fault conditions and its effect on line protection need to be studied FAULT CURRENT (NOT TO SCALE) Exhibit-I- Fault Current & Ballabgarh Bus Voltage Exhibit-II- Current thru the capacitor 3 BALLABGARH KANPUR 2 1 8% CAPACITOR BANK 27% CAPACITOR BANK MOV MOV -2 DAMPING CKT SPARK GAP -3-4 Exhibit-III- Current thru the MOV From the above study results, following observations can be made: BYPASS CIRCUIT BREAKER Figure II- Schematic diagram of Series capacitor Protection IV. EMTP SIMULTAION In order to study the behavior of series Capacitor along with its MOV, an EMTP simulation has been carried out. A detailed system upto second level, both from Kanpur and Ballabgarh bus, has been modeled in EMTP. All the bus short circuit has been matched with the expected short circuit level. The powerflow on the lines have been matched with the expected value both in magnitude and direction. The MOV has been modeled in detail as per the V-I characteristics as provided by the manufacturer. A fault was created close to the Capacitor terminal on the line side. The voltage and current monitored are plotted as below. Till the voltage across capacitor builds upto protection level the fault current flows thru the capacitor. (From the Exhibit-II it can be seen that initially the current flows through the series capacitor and increases to the magnitude of about 2kA). When the protective voltage level of MOV is reached, MOV bypasses the capacitor bank and fault current flows thru MOV. (Exhibit-III) Hence the series capacitor remains in service for a definite period and its effect on the relays needs to be studied. The Ballabgarh bus voltage does not reduces to zero even for a fault close to bus. To study the effect of series compensation, till MOV starts conducting a fault was slided along the Ballabgarh-Kanpur line and bus voltage of Ballabgarh bus was monitored, MOV not been modeled. The results are plotted in Exhibit IV
3 NATIONAL POWER SYSTEMS CONFERENCE, NPSC Exhibit-IV- Ballabgarh bus voltage for a sliding fault For a fault at capacitor terminal, the voltage of Ballabgarh bus will rise. And the Voltage varies as the fault slides. The effect of high voltage under fault needs to be studied. Consider a simple system shown in Figure-III, power flows from BUS1 to BUS2 ( Rp>>Xl>>Rl). Under normal condition, the flow on a line is mostly Real power (MW) as the load is predominantly Real/Resistive ( Rp>>jXp) and relay at BUS1 on BUS1-BUS2 line measures a high resistive load ( as Rp >> Xl). Under short circuit condition BUS2 voltage becomes zero and no power will flow thru the load and the entire current will flow thru the low impedance fault to ground. The relay at BUS1 on BUS1-BUS2 will measure the actual line impedance. The line inductance is about 1 times higher than line resistance ( X l >>Rl). Hence the relay will measures a high inductance. BUS1 ( R l +jxl) ( I +ji r x ) ( R p +jx p) BUS2 Figure III- Normal system For a fault at the capacitor line terminal, the voltage at BUS2 does not become zero (rather increases) and hence power will continue to flow through Rp, at the same time as Xc is small compared to Rp there will be reactive current flowing to ground thru Xc. The impedance measured by the relay at BUS1 on BUS1-BUS2 line will depend on the position of the fault. Hence due to installation of series capacitor on Kanpur Ballabgarh 4kV line, the relays on adjacent lines on Ballabgarh bus and on Kanpur Ballabgarh 4kV line which needs to be studied for whether there will be any maloperation for a fault at any location, due to series capacitor is in service. As we are interested when capacitor is conducting, MOV need not be modeled. The study has been carried out on Short Circuit package of Power System Simulator/Engineering (PSS/E), power system software, developed by Power Technologies Inc, USA. Similar studies can be carried out with EMTP, but considering the number of lines and locations on which the faults is to be simulated study has been done on PSS/E A. System Modeling IV. SHORT CIRCUIT STUDIES Detailed system up to 132kV level having about 22GW load has been simulated. The system simulated comprises of 37 nodes, 1 branches and 7 generating plants. All generators have been shown behind a Sub transient Reactance. B. Study Approach For a particular fault, the series capacitor affects the input to the relay only if the location of Series capacitors is between the relay measurement point and the fault point. Hence Relay measurement at Ballabgarh end can be done either at Bus or at capacitor line terminal. In the case of Kanpur-Ballabgarh the measurement shall be at line side. With measurement of Relay inputs at Capacitor line terminal, relay at Ballabgarh end of Kanpur-Ballabgarh will be unaffected by series capacitors for any fault at capacitor terminal or fault along Kanpur-Ballabgarh line and will sense the faults correctly, but will be affected by the series capacitor for faults behind the capacitor terminal like fault on Ballabgarh bus or on any adjacent lines of Ballabgarh. Relay at Kanpur end of Kanpur Ballabgarh line will be unaffected for any fault along Kanpur-Ballabgarh line upto Capacitor terminal. Kanpur end relays will be influenced by the series capacitor for fault just after capacitor, and on adjacent lines terminating at Ballabgarh. Relays on Adjacent lines at Ballabgarh end, i.e. Dadri- Ballabgarh 4kV D/c, Dadri-Agra 4kV S/c etc., shall be affected by the series capacitor for faults beyond capacitor line terminal only on Kanpur-Ballabgarh line. For relays on Adjacent lines at Kanpur end i.e. Kanpur Allahabad 4kV S/c, Kanpur Agra 4kV S/c etc, shall be affected by the series capacitor for fault beyond capacitor, on Ballabgarh bus and on adjacent lines from Ballabgarh. As compensation is only for 35%, for faults beyond Ballabgarh the total impedance from Kanpur to fault shall always be inductive. This will be added to actual line impedance, hence the relay operation on adjacent lines at Kanpur end may be affected only in Zone-2 & 3. Hence effect of series compensation on these lines can be ignored. To summarize, following studies need to be carried out to study the effect of Series capacitor: Response of relay on Kanpur Ballabgarh line for fault behind capacitor, on Ballabgarh bus and on adjacent lines of Ballabgarh Adjacent lines at Ballabgarh end for fault at capacitor terminal and along Kanpur-Ballabgarh line
4 INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 72132, DECEMBER 27-29, C. Short Circuit Studies: Relays on adjacent lines at Ballabgarh: The line in adjacent sections which will get affected due to series compensation on Kanpur-Ballabgarh/ lines which may affect the protection of series compensated Kanpur- Ballabgarh line are: Ballabgarh -Dadri 4kV D/c 53km Ballabgarh-Bhiwadi 4kV S/c- 36 km Ballabgarh-Agra 4kV S/c- 181 km Effect on Dadri-Ballabgarh relays A sliding fault was created along Ballabgarh-Kanpur line and the apparent impedance measured by the relay at Dadri end of Dadri-Ballabgarh line was monitored, the results are plotted in Exhibit-V. For a fault at Ballabgarh bus, the relay at Dadri measures impedance equal to the line impedance,.8 p.u. But for fault at capacitor terminals due to current infeed effect it measures an impedance of.23-j.95 as against expected.1-j.272 p.u. Power flows from Dadri to Ballabgarh hence resistive component is always positive. And as the fault moves towards Kanpur the capacitive impedance measured by the relay reduces and for a fault at.1 5 For both the relays the minimum impedance measured is greater than the actual line impedance(.8p.u). Effect on Ballabgarh-Bhiwadi relays Exhibit-7 &8 shows the apparent impedance measured by the relay at Bhiwadi and Ballabgarh end relays of Bhiwadi- Ballabgarh line. Power flows from Ballabgarh to Bhiwadi. Hence the Relay at Bhiwadi sees a negative resistance while the relay at Ballabgarh sees a positive resistance. Only for a small percentage of line length the voltage at the bus is low enough that powerflows from Bhiwadi to Ballabgarh Exhibit-VII: Apparent impedance (R-X) measured by Bhiwadi end relay of Bhiwadi -Ballabgarh line Exhibit-V- Impedance seen by Dadri end relay of Dadri - Ballabgarh line for fault on Ballabgarh-Kanpur line about 32% from Ballabgarh end the measured impedance is nearly resistive. But even this resistive impedance is very high due to In-feed current,.9p.u, more than 1% of line impedance. After 32%, the impedance measured by the relay is inductive The apparent impedance measured by Ballabgarh end relay is shown in Exhibit-VI. For a fault at capacitor terminal, the relay sees an apparent impedance of -.24+j.16 and as the fault slides the inductive component reduces but even at the point were it is almost zero the resistive component is -.9, which is about 1% of line impedance Exhibit-VIII Apparent impedance (R-X) measured by Ballabgarh end relay of Bhiwadi -Ballabgarh line For both relays the minimum measured impedance of Bhiwadi end relay is.35p.u, which is more than twice the line impedance(.17 p.u). Effect on Ballabgarh-Agra relays Exhibit-IX &X shows the apparent impedance measured by the relay at Agra end and Ballabgarh end of Agra-Ballabgarh line. The fault current feed for Agra is mainly from Auraiya, Kanpur and Ballabgarh. Under Normal condition power flows from Agra to Ballabgarh hence Resistive component is positive for Agra end Relay. As the fault slides closer to Kanpur, Ballabgarh-Agra- Kanpur lines act as a parallel path to feed the path hence after about 8% distance X becomes negative for Agra end Relay. The minimum impedance measured by the relay is.48 p.u, which is higher than the line impedance of.37 p.u -.15 Exhibit-VI- Impedance seen by Dadri end relay of Dadri - Ballabgarh line for fault on Ballabgarh-Kanpur line
5 116 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 22 Exhibit-IX Apparent impedance (R-X) measured by Agra end relay for fault on Ballabgarh-Kanpur line Exhibit-X Apparent impedance (R-X) measured by Ballabgarh end relay for fault on Ballabgarh-Kanpur line Relay at Ballabgarh End of Kanpur-Ballabgarh Line : A sliding fault was created on Ballabgarh- Dadri 4kV line and Ballabgarh-Agra 4kV line and the apparent impedance measured by Ballabgarh end relay of Kanpur- Ballabgarh line was monitored to study the effect of series capacitor on the relay. The result of studies are plotted below: Exhibit-XI: Apparent impedance (R-X) measured by Ballabgarh end relay of Ballabgarh -Dadri line Exhibit-XII: Apparent impedance (R-X) measured by Ballabgarh end relay of Ballabgarh -Agra line The Zone setting of Kanpur Ballabgarh relay is.656 p.u Under both the cases for a fault on the line close to bus (at gantry) the relay measures an impedance of.29 p.u, the capacitor impedance less than Zone-1 setting It is seen that the measured X component of Relay at Ballabgarh end for fault on Ballabgarh-Dadri line is always less than its Zone-1 setting. Maximum measured value is.287 p.u, which is at the bus. As power flows from Dadri to Ballabgarh R is always measured as a negative Value, but the magnitude is small and Maximum magnitude measured is.188 p.u Similar to Ballabgarh-Dadri line, Ballabgarh-Agra line measures a very small X component, which also becomes negative for a portion of the line. But the negative R component magnitude increases very rapidly and touches up to.13 p.u. Infact, at 1% R is only about -.34 p.u, by the time the fault is at 2% the magnitude of R is about -.68 p.u, greater than the Zone-1 setting of Kanpur-Ballabgarh line. Relay at Kanpur End of Kanpur-Ballabgarh Line : A sliding fault was created on Ballabgarh- Dadri 4kV line and Ballabgarh-Agra 4kV line and the apparent impedance measured by Kanpur end relay of Kanpur- Ballabgarh line was monitored. The result of studies are plotted below : The Zone setting of Kanpur Ballabgarh relay is.656 p.u Exhibit-XIII: Apparent impedance (R-X) measured by Kanpur end relay of Ballabgarh -Agra line For a fault close to Bus the Kanpur end relay measures a fault impedance of.544 i.e the net impedance of line and the capacitor. For any fault on the adjacent lines power shall always flow from Kanpur to Ballabgarh. Hence the impedance measured by the Kanpur end relay Resistance is always positive Exhibit-XIV: Apparent impedance (R-X) measured by Kanpur end relay of Ballabgarh -Dadri line And as the fault slides further the measured impedance increases. The maximum measured impedance is.27+j.77. And upto about 2% distance from the bus
6 INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 72132, DECEMBER 27-29, the impedance is less than Zone-1 setting. And as the fault approaches Dadri Bus the Fault impedance reduces again. For fault on Ballabgarh Agra line initially the X measured by the Kanpur end relay increases rapidly. For fault at 1% distance from the bus the magnitude of X is about.84p.u. Since Agra-Ballabgarh is a long line (18km), as the fault slides from Ballabgarh the voltage of Ballabgarh bus increase and power flows from Kanpur to Ballabgarh. Hence measured R value increase heavily, maximum magnitude is about.14 p.u. V. ATP SIMULATION: To study the Relay operation with series capacitor and to see if there is any relay malfunction by transients due to MOV conduction, capacitor etc an ATP simulation was carried out. The ASCII values obtained were converted into COMTRADE format and then fed to distance relays of type that are existing on concerned lines, through an automatic relay test kit. Study results are as follows: For a fault on Kanpur-Ballabgarh line the relays on adjacent lines at Ballabgarh did not maloperate. The Kanpur end Relay tripped in Zone-1 for fault, on Ballabgarh-Dadri Line, at Ballabgarh end, at 1% and Dadri end. Similarly the relay tripped in Zone-1 for fault, on Ballabgarh-Agra Line, at Ballabgarh end. The relay did not operate for fault at 1%, 5% and Agra of Ballabgarh-Agra Line The Ballabgarh end Relay tripped in Zone-1 for fault, on Ballabgarh-Dadri Line, at Ballabgarh end, at 1%, 5% and Dadri end. Similarly the relay tripped in Zone-1 for fault, on Ballabgarh-Agra Line, at Ballabgarh end and 1% from Ballabgarh. The relay did not operate for fault at 5% and Agra end of Ballabgarh-Agra Line The test results match with the results obtained through Short circuit studies for conventional distance relays. The same tests were also simulated on new generation numerical distance relays of different makes compatible with series capacitor. It was observed that these relays are able to give correct directional discrimination. VI. REMEDIAL MEASURES The conventional Ballabgarh end relay of Kanpur Ballabgarh end line has lost its sense of direction and trips for behind the bus fault. The Relay has been replaced with new generation numerical distance relays compatible with series capacitors. To overcome the over reach of Kanpur end relay for fault beyond the capacitor following zone settings were made. Z1=.8*(1-k)*ZL Z2=1.2*ZL Where k is the degree of compensation ZL is the uncompensated line impedance Permissible Over-Reach scheme (POR) has been adopted. VII. CONCLUSION This paper presented in detail application of Short Circuit studies carried out to examine the effect of installation of series capacitor on Kanpur-Ballabgarh 4kV line on line protection on principle as well as adjacent lines. The study results indicate requirement for replacement of conventional distance relays at Ballabgarh end with numerical relays compatible with series capacitor and change in Zone setting of Kanpur end relay and adoption of permissible Overreach Scheme. While Short circuit studies are helpful in identifying faults and distance relay locations which are of concern, it is necessary to make ATP simulation test on actual relays to ascertain performance and adequacy of protection scheme provided. VIII. ACKNOWLEDGEMENT The authors wish to thank POWERGRID for granting permission to present the paper. Views expressed in this paper are of the authors and need not necessarily be of the management of POWERGRID. IX. REFERENCES [1] Application guide on protection of complex transmission network: working group of CIGRE-34 [2] Series compensation of Power system P.M.Anderson and F.G Farmer [3] Limits to conventional distance relaying in series compensated transmission lines-case study by V.K.Prashar, Vikas Saxena, P.Jayachandran & V.Thiagarajan : Integrated Protection, Control and Communication Experience, Benefits and Trends, CBIP, 21
I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X
2017 IJSRST Volume 3 Issue 2 Print ISSN: 2395-6011 Online ISSN: 2395-602X National Conference on Advances in Engineering and Applied Science (NCAEAS) 16 th February 2017 In association with International
More informationTransient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines
Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Presenter Mark McVey C4/B5.41 INTERNATIONAL COUNCIL ON LARGE
More informationAgenda Notes for 4 th Meeting of Sub Group in respect of Preparation of Reliability Standards for Protection System and Communication System
Agenda Notes for 4 th Meeting of Sub Group in respect of Preparation of Reliability Standards for Protection System and Communication System Meeting Date: 27.03.2017 Time: 1430 Hrs Venue: NRPC Conference
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationSteady-State Protection Study for the Application of Series Capacitors in the Empangeni 400 kv Network
Steady-State Protection Study for the Application of Series Capacitors in the Empangeni 4 kv Network Graeme Topham Eskom Enterprises Technology Services International Edmund Stokes-Waller Schweitzer Engineering
More informationFixed Series Compensation
Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and
More informationLine Loadability in Indian Perspective
Line Loadability in Indian Perspective P.Pentayya, U.K Verma, P. Mukhopadhyay, Gopal Mitra, GM (WRLDC) GM (ERLDC) AGM (ERLDC) DGM (ERLDC) S.Bannerjee M.Thakur, S.Sahay CM (ERLDC Sr.Eng, (ERLDC) Eng, (ERLDC)
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationHigh Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur
High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur Module No. # 01 Lecture No. # 02 Comparison of HVAC and HVDC Systems Welcome
More informationCourse ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation
Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission
More informationCork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)
Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:
More informationAspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks
Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks Diptargha Chakravorty Indian Institute of Technology Delhi (CES) New Delhi, India diptarghachakravorty@gmail.com Jan
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationAUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME
AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell
More informationSIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER
SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER S. Tara Kalyani 1 and G. Tulasiram Das 1 1 Department of Electrical Engineering, Jawaharlal Nehru Technological University, Hyderabad,
More informationUnit Auxiliary Transformer (UAT) Relay Loadability Report
Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC
More informationTransient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme
I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)
More informationSwitching and Fault Transient Analysis of 765 kv Transmission Systems
Third International Conference on Power Systems, Kharagpur, INDIA December >Paper #< Switching and Transient Analysis of 6 kv Transmission Systems D Thukaram, SM IEEE, K Ravishankar, Rajendra Kumar A Department
More informationAdaptive Settings Of Distance Relay For MOV- Protected Series Compensated Line With Distributed Capacitance Considering Wind Power
Clemson University TigerPrints All Theses Theses 5-216 Adaptive Settings Of Distance Relay For MOV- Protected Series Compensated Line With Distributed Capacitance Considering Wind Power Oleg Viktorovich
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationSimulations of open phase conditions on the high voltage side of YNd05-power plant transformers
Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,
More informationSHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP
SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,
More informationPower System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)
Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationMODEL POWER SYSTEM TESTING GUIDE October 25, 2006
October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date
More informationNERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June
More informationDC current interruption tests with HV mechanical DC circuit breaker
http: //www.cigre.org CIGRÉ A3/B4-124 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 DC current interruption tests with HV mechanical DC circuit
More informationCOMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)
7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series
More informationFRIENDS Devices and their Coordination
INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 721302, DECEMBER 27-29, 2002 425 FRIENDS Devices and their Coordination R. L. Meena, Arindam Ghosh and Avinash Joshi Abstract-- The paper discusses various aspects
More informationDetermination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System
ISSN (e): 2250 3005 Vol, 04 Issue, 5 May 2014 International Journal of Computational Engineering Research (IJCER) Determination of Optimal Account and Location of Series Compensation and SVS for an AC
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationDynamic Model Of 400 Kv Line With Distance Relay. Director Research, The MRPC Company, Hyderabad, India 2
Dynamic Model Of 400 Kv Line With Distance Relay Ramleela Khare 1, Dr Filipe Rodrigues E Melo 2 1 Director Research, The MRPC Company, Hyderabad, India 2 Assoc. Professor Commerce, St. Xavier s College
More informationIn power system, transients have bad impact on its
Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014
More informationStability Enhancement for Transmission Lines using Static Synchronous Series Compensator
Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India
More informationEast-South HVDC Interconnector II, India : in commercial operation since 2003
8006/0 5 HVDC / FACTS Highlights http://www.siemens.com/facts http://www.siemens.com/hvdc NEW! >>> Welcome to Siemens Highlights & Innovations in Transmission and Distribution East-South HVDC Interconnector
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationImpact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT
Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT Babar Noor 1, Muhammad Aamir Aman 1, Murad Ali 1, Sanaullah Ahmad 1, Fazal Wahab Karam. 2 Electrical
More informationArvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India
e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationAnalysis of Single and Multi Resonance Point in Reactance Characteristics of TCSC Device
Analysis of Single and Multi Resonance Point in Reactance Characteristics of TCSC Device Manojkumar Patil 1, Santosh Kompeli 2 1 Student (M.E.) Electrical Engineering Department, MSS S COE, Jalna, Maharashtra,
More informationAnalysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar
Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:
More informationCONTENTS. 1. Introduction Generating Stations 9 40
CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific
More informationA New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated
More informationIntegration of Wind Generation into Weak Grids
Integration of Wind Generation into Weak Grids Jason MacDowell GE Energy Consulting NERC ERSTF Atlanta, GA December 10-11, 2014 Outline Conventional and Power Electronic (PE) Sources Stability limitations
More informationNERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1
NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,
More informationChapter 10: Compensation of Power Transmission Systems
Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome
More informationPower Quality enhancement of a distribution line with DSTATCOM
ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical
More informationDesign and Simulation of Passive Filter
Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt
More informationIncreasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)
Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC) K. Manoz Kumar Reddy (Associate professor, Electrical and Electronics Department, Sriaditya Engineering College, India)
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationApplication for A Sub-harmonic Protection Relay. ERLPhase Power Technologies
Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic
More informationR10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours
Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions
More informationA New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines
A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines M.M. Saha, T. Einarsson, S. Lidström ABB AB, Substation Automation Products, Sweden Keywords: Adaptive distance protection,
More informationGeneration Interconnection Study Data Sheet Synchronous Machines
FOR INTERNAL USE ONLY GTC Project Number: Queue Date: Generation Interconnection Study Data Sheet Synchronous Machines Customers must provide the following information in its entirety. GTC will not proceed
More informationA. df/dt Measurement principle by relays
Adaptive df/dt Relay-A case study with reference to the Indian Power System P.Pentayya, U.K Verma, P. Mukhopadhyay, Gopal Mitra, S.Bannerjee, M.Thakur*, S.Sahay Abstracts: df/dt relays are used in the
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationIn Class Examples (ICE)
In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6
More informationAdaptive Relaying of Radial Distribution system with Distributed Generation
Adaptive Relaying of Radial Distribution system with Distributed Generation K.Vijetha M,Tech (Power Systems Engineering) National Institute of Technology-Warangal Warangal, INDIA. Email: vijetha258@gmail.com
More informationProtection Challenges for Transmission Lines with Long Taps
Protection Challenges for Transmission Lines with Long Taps Jenny Patten, Majida Malki, Quanta Technology, Matt Jones, American Transmission Co. Abstract Tapped transmission lines are quite common as they
More informationImpact of Distributed Generation on Network Voltage Levels
EEE8052 Distributed Generation Taster Material Impact of Distributed Generation on Network Voltage Levels Steady-state rise in network voltage levels Existing practice is to control distribution voltage
More informationPower flow improvement using Static Synchronous Series Compensator (SSSC)
Page14 Power flow improvement using Static Synchronous Series Compensator (SSSC) Gandla Saraswathi*, Dr.N.Visali ** & B. Narasimha Reddy*** *P.G Student, Department of Electrical and Electronics Engineering,JNTUACEP,
More informationEXPERIENCES IN SETTING PROTECTIONS OF SERIES CAPACITOR COMPENSATED LINES. O.Trad G.Ratta M.Torres
EXPERIENCES IN SETTING PROTECTIONS OF SERIES CAPACITOR COMPENSATED LINES O.Trad G.Ratta M.Torres Instituto de Energía Eléctrica Universidad Nacional de San Juan Argentina Av. Libertador San Martín 119
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationApplication Of Artificial Neural Network In Fault Detection Of Hvdc Converter
Application Of Artificial Neural Network In Fault Detection Of Hvdc Converter Madhuri S Shastrakar Department of Electrical Engineering, Shree Ramdeobaba College of Engineering and Management, Nagpur,
More informationApplication of SVCs to Satisfy Reactive Power Needs of Power Systems
1 Application of SVCs to Satisfy Reactive Power Needs of Power Systems H. K. Tyll, Senior Member, IEEE Abstract In the early days of power transmission problems like voltage deviation during load changes
More informationFGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI
FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown
More informationPROTECTION of electricity distribution networks
PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of
More informationDistance Protection of Cross-Bonded Transmission Cable-Systems
Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th
More informationConventional Paper-II-2013
1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine
More information(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in
A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-3 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability
More informationAddress for Correspondence
Research Paper COMPENSATION BY TCSC IN OPEN LOOP CONTROL SYSTEM 1* Sunita Tiwari, S.P. Shukla Address for Correspondence 1* Sr. Lecturer, Polytechnic,Durg Professor, Bhilai Institute of Technology, Durg
More informationG. KOEPPL Koeppl Power Experts Switzerland
PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland
More informationINTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY
INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK SPECIAL ISSUE FOR NATIONAL LEVEL CONFERENCE "Technology Enabling Modernization
More informationPower System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)
Vol. 3, Issue. 4, Jul - Aug. 2013 pp-2530-2536 ISSN: 2249-6645 Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC) B. M. Naveen Kumar Reddy 1, Mr. G. V. Rajashekar 2,
More informationECE 692 Advanced Topics on Power System Stability 5 - Voltage Stability
ECE 692 Advanced Topics on Power System Stability 5 - Voltage Stability Spring 2016 Instructor: Kai Sun 1 Content Basic concepts Voltage collapse and Saddle-node bifurcation P-V curve and V-Q curve Causes
More informationEarth Fault Protection
Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationImproving High Voltage Power System Performance. Using Arc Suppression Coils
Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationConstant Terminal Voltage. Working Group Meeting 4 19 th September 2014
Constant Terminal Voltage Working Group Meeting 4 19 th September 014 Overview Options summary System under investigation Options analysis Discussion Options Option 1 Constant Terminal Voltage controlled
More informationPUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:
POWER FLOW CONTROL BY USING OPTIMAL LOCATION OF STATCOM S.B. ARUNA Assistant Professor, Dept. of EEE, Sree Vidyanikethan Engineering College, Tirupati aruna_ee@hotmail.com 305 ABSTRACT In present scenario,
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationVoltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)
Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti
More informationDesign of SVPWM Based Inverter for Mitigation of Harmonics in Power System
Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System 1 Leena N C, 2 B. Rajesh Kamath, 3 Shri Harsha 1,2,3 Department of EEE, Sri Siddhartha Institute of Technology, Tumkur-572105,
More informationIMPACT OF SERIES COMPENSATION ON THE PERFOMANCE OF DISTANCE PROTECTION ON ESKOM TRANSMISSION GRID. Sihle Qwabe
i IMPACT OF SERIES COMPENSATION ON THE PERFOMANCE OF DISTANCE PROTECTION ON ESKOM TRANSMISSION GRID Sihle Qwabe The dissertation submitted in fulfillment of the requirements for the degree of Master of
More informationEFFECTS OF SERIES COMPENSATION ON DISTANCE PROTECTION OF HIGH VOLTAGE TRANSMISSION LINES UNDER FAULT CONDITIONS
International Journal of Electrical Engineering & Technology (IJEET) Volume 9, Issue 6, November-December 218, pp. 57-66, Article ID: IJEET_9_6_6 Available online at http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=9&itype=6
More informationExercises on overhead power lines (and underground cables)
Exercises on overhead power lines (and underground cables) 1 From the laws of Electromagnetism it can be shown that l c = 1 v 2 where v is the speed of propagation of electromagnetic waves in the environment
More informationImproving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)
International Journal of Scientific and Research Publications, Volume 2, Issue 5, May 2012 1 Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC) K. Manoz
More informationEFFECT OF SFCL ON DISTRIBUTION POWER QUALITY
EFFECT OF SFCL ON DISTRIBUTION POWER QUALITY by Shahram Najafi, Prof. Vijay K. Sood, Ahmed Hosny University of Ontario Institute of Technology, Oshawa, Ontario Electrical Power and Energy Conference (London-Canada)
More informationA Case Study of Resonance in 11kV Network in the Presence of Series Current Limiting Reactors, VSDs and Power Factor Improvement Capacitors
International Journal of Electrical Energy, Vol. 2, No., December 201 A Case Study of Resonance in 11kV Network in the Presence of Series Limiting s, VSDs and Power Factor Improvement s Yadavalli Venkata
More informationNotes 1: Introduction to Distribution Systems
Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission
More informationOptimal Location of Series FACTS Device using Loss Sensitivity Indices. 3.2 Development of Loss Sensitivity Indices
Chapter 3 Optimal Location of Series FACTS Device using Loss Sensitivity Indices 3.1 Introduction The location and sizing of series FACTS devices constitute a major step in the application of FACTS devices.
More informationANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stability
ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stility Subir Datta and Anjan Kumar Roy Abstract The paper presents a new ANFIS-based controller for enhancement of voltage stility
More informationElectromagnetic Transient Simulation for Study on Commutation Failures in HVDC Systems
Electromagnetic Transient Simulation for Study on Commutation Failures in HVDC Systems Xia Chengjun, Xu Yang, Shan Yuanda Abstract--In order to improve reliability of HVDC transmission system, commutation
More informationDRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER
DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER P. SWEETY JOSE JOVITHA JEROME Dept. of Electrical and Electronics Engineering PSG College of Technology, Coimbatore, India.
More informationMV network design & devices selection EXERCISE BOOK
MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester
More information