AFTER an overhead distribution feeder is de-energized for

Size: px
Start display at page:

Download "AFTER an overhead distribution feeder is de-energized for"

Transcription

1 1902 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 A New Technique to Detect Faults in De-Energized Distribution Feeders Part II: Symmetrical Fault Detection Xun Long, Student Member, IEEE, Yun Wei Li, Member, IEEE, Wilsun Xu, Fellow, IEEE, and Chris Lerohl, Student Member, IEEE Abstract To ensure safe re-energizing of an overhead distribution feeder after it is de-energized for an extended period, a novel fault detection technique by controlling a thyristor-based device is proposed in a companion paper. The device connected in parallel with a breaker or recloser can inject electrical pulses with adjustable strength for the downstream fault detection in a de-energized system. The proposed method can effectively detect different kinds of asymmetrical faults based on the unbalanced fault currents. However, the unbalanced current-based fault detection scheme is not effective for three-phase symmetrical faults detection. Furthermore, a stalled motor or a shunt-connected capacitor bank in the downstream may also behaves like a short-circuit. Therefore, a fault detection algorithm based on the analysis of the harmonic impedance of the de-energized system is developed in this paper. This method is very effective for the symmetrical fault detection and for distinguishing a stalled motor and capacitor bank from a fault. Extensive lab test results are provided in the paper to verify the effectiveness of the proposed method. Index Terms De-energized distribution line, fault classification, fault detection, power electronics, safe recloser. I. INTRODUCTION AFTER an overhead distribution feeder is de-energized for an extended period due to events, such as repair, maintenance, or storms, there is always the possibility that humans or animals may be in contact with feeder conductors unknowingly [1], [2]. A re-closing action in such a situation can easily lead to fatality [3], [4]. For this reason, re-energizing a de-energized distribution feeder in a safe manner is a major consideration for utility companies [5] [9]. Therefore, the development of techniques that can detect whether the downstream system is still experiencing a fault before restoring the de-energized system is important, so that operators can re-energize the feeder with confidence. The fault detection in de-energized systems is challenging since it requires the generation and injection of a voltage signal to the de-energized feeder. Available techniques for this signal generation are either self-powered which is based on battery/ca- Manuscript received October 03, 2010; revised January 07, 2011; accepted February 08, Date of publication April 05, 2011; date of current version June 24, This work was supported by the icore. Paper no. TPWRD The authors are with the Department of Electrical and Computer Engineering, University of Alberta, Edmonton, AB T6G 2V4 Canada ( xlong@ualberta.ca; yunwei.li@ece.ualberta.ca; wxu@ualberta.ca; clerohl@ualberta.ca). Color versions of one or more of the figures in this paper are available online at Digital Object Identifier /TPWRD pacitor [10], [11] or by using energy from the upstream [12], [13]. A pulse-recloser technique in [14] can reduce a large inrush current; however, it is hard to distinguish a fault from a stalled motor or a shunt capacitor bank, which behaves like a short circuit. Moreover, all of the available methods cannot produce a signal with adjustable and enough strength that can be used for high-impedance fault detection. Also, these methods cannot detect all types of faults in a single device. Considering the limitations of the existing fault detection methods, a new technique based on a thyristor bridge in parallel with the breaker or recloser was proposed in a companion paper [15]. In the proposed method, a controllable signal is injected into the de-energized downstream to stimulate the electrical response. With adjustable pulse strength by changing the thyristor firing angle, a low-voltage pulse can be created to satisfy the safety requirement and a high-voltage pulse can be produced to break down an insulted gap of a high-impedance fault when necessary. The principle and key features of the proposed idea have been presented in that paper. Moreover, the method and procedure for detecting asymmetrical faults based on the unbalanced fault currents are also discussed. This paper completes [15] by proposing a symmetrical fault detection method and considering situations of downstream stalled motors or shunt capacitor banks. Since a symmetrical fault affects all three phases equally, the method based on the difference of three-phase currents for asymmetrical faults detection is not applicable here. Furthermore, when a voltage pulse is applied to the de-energized circuit, either a stalled motor or a capacitor bank can cause a large current like a short circuit. Thus, it is necessary to explore a new fault detection method that is not only based on the fault current magnitude. In this paper, a fault detection method is developed based on the harmonic impedance characteristics. Combined with the asymmetrical fault detection algorithm developed in [15], a detection scheme that can detect all kinds of faults and can distinguish a fault from a stalled motor or a shunt capacitor bank is then proposed. This paper is organized as follows. The new fault detection criterion based on harmonic impedance is introduced in Section II. In this section, the harmonic impedance characteristics under different situations are first analyzed. Based on the harmonic impedance characteristics, the proposed method for detecting a symmetrical fault and for distinguishing a fault from a stalled motor or a capacitor bank is then developed. Section III presents the lab test results obtained from a /$ IEEE

2 LONG et al.: NEW TECHNIQUE TO DETECT FAULTS IN DE-ENERGIZED DISTRIBUTION FEEDERS PART II 1903 TABLE I PARAMETERS OF A REPRESENTATIVE 25-kV SYSTEM Fig. 1. Proposed scheme for symmetrical faults detection. Fig. 2. Equivalent circuit with a symmetrical fault. single-phase low-voltage system, which verifies the effectiveness of the proposed method. Finally, the work is summarized in Section IV. II. FAULT DETECTION BASED ON HARMONIC IMPEDANCE As shown in Fig. 1, a zero-sequence voltage from one energized phase is fed to all three phases when the thyristors T1, T3, and T5 are fired simultaneously on a certain degree before the voltage cross zero. The corresponding current pulse in each phase depends on the line condition. In a normal condition, the injected currents are very small. However, if there is a symmetrical fault, inrush currents will show up in all phases at the same time. To illustrate this, a representative 25 kv system with a 10 km distribution line is used as shown in Fig. 2, where the parameters of the system are listed in Table I. To compare the difference of the faulted and unfaulted conditions, a symmetrical fault is created at 5 km away from the recloser. When the thyristors are fired at 150, the transient voltage and the transient current are shown in Fig. 3. Apparently, a symmetrical fault increases the current magnitude. However, this fault current magnitude highly depends on the fault resistance.it is therefore difficult to set up an appropriate current magnitude threshold to detect whether a fault exists, especially considering the possibility of a high-impedance fault. Further considering the situations of stalled motors and shunt capacitor banks connected at downstream, where a high current similar to a short circuit may be produced by the detection voltage, a fault detection method not just based on the current magnitude is required. To meet this fault detection requirement, a new method based on the harmonic impedance is introduced in this section. The harmonic impedance can represent the frequency response of power networks. With its unique characteristics, the harmonic impedance can be effectively used to detect a symmetrical fault. Fig. 3. Voltage (dv ) and current (di) in different conditions. Fig. 4. Downstream de-energized lines as a linear network. As will be shown later in this section, the harmonic impedance can also be used to distinguish a stalled motor or a capacitor bank from a fault. A. Study of Harmonic Impedance for Fault Detection Considering the downstream de-energized line as a linear network (Fig. 4), an equation can be established according to the Fourier transform of nonperiodical signals [16] where are the Fourier transforms of transient voltage and current, and is the harmonic impedance. The harmonic impedance can therefore be expressed as (1) (2)

3 1904 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 be seen that the harmonic reactance frequency, and the ratio is is proportional to the However, if a symmetrical fault exists, the harmonic impedance will become (6) (7) where is the fault resistance. Thus, the harmonic resistance and harmonic reactance change to and Fig. 5. Harmonic resistance R(f ) in unfaulted and faulted cases. (8) (9) Fig. 6. harmonic reactance X(f ) in unfaulted and faulted cases. or where, and is the fundamental frequency (60 Hz is considered in this paper). These equations imply that the harmonic impedance can be measured by using the DFT of transient voltage and current signals. To implement this approach, the Fourier transforms of the current and voltage are created using an FFT algorithm. Separating harmonic impedance into its resistance and reactance parts gives The basic principle of the proposed idea is to utilize the change of in different conditions to detect a symmetrical fault. In normal conditions, the harmonic impedance of the de-energized downstream as shown in Fig. 2 is where of the load, (3) (4) (5) are the equivalent resistance and inductance (see Fig. 2). From (5), it can The harmonic resistance and reactance in the two conditions (faulted and unfaulted) are compared in Figs. 5 and 6, respectively. Since is much smaller than when the frequency is low, one can obtain from (8) at low frequencies (such as Hz). On the other hand, consists of two parts: the first part is proportional to the frequency but the ratio becomes much smaller as (10) And the second part of decreases with an increase in frequency. Thus, the overall effect of the harmonic reactance is that is much smaller than and it almost has no significant change at low frequencies. Based on the above analysis, harmonic impedance can be utilized for symmetrical fault detection. The decision logic is therefore designed as follows. 1) Measure the currents and voltages of three phases after T1, T3, and T5 are fired simultaneously. 2) Are currents the same? If No, turn to asymmetrical faults analysis. If Yes, estimate the. i) If is proportional to frequency, there is no fault. ii) If has no significant change as frequency increases, there is a symmetrical fault. B. Impact of Stalled Motor A stalled motor behaves like a short circuit in the de-energized system. The equivalent circuit of a stalled motor is shown in Fig. 7 [17]. The parameters and are the motor stator resistance and leakage reactance, and the locked-rotor resistance and leakage reactance referring to the stator side are denoted as and, respectively. The reactance is the magnetizing reactance of the motor. The stator current is, and the rotor current is. The motor slip when the motor is stalled.

4 LONG et al.: NEW TECHNIQUE TO DETECT FAULTS IN DE-ENERGIZED DISTRIBUTION FEEDERS PART II 1905 Fig. 7. Equivalent circuit of a stalled motor. Fig. 10. Harmonic reactance X(f ) with a stalled motor. Fig. 8. stalled motor connected in the downstream system. (Note: the stalled motor: 5000 hp, starting p:f: =0:2, inrush current 700%, fed with a three-phase 5 MVA transformer, 25 kv/4.16 kv, z=0.05). Fig. 11. Shunt capacitor bank connected in the downstream. (Note: a threephase capacitor bank, 2.5 MVar, Yg connected. Fed with a 5 MVA, 25 kv/0.6 kv, Yg/Yg transformer z=0:05 pu. (12) Fig. 9. Effect of a motor on the current pulse. Considering therefore expressed as, the impedance of a stalled motor is (11) Typically, the motor starting power factor is between , and the motor inrush current is 600% 800% of the rated current. Thus, a stalled motor in a de-energized line can cause a large current pulse when a voltage is applied (Fig. 8). The currents in different conditions are illustrated in Fig. 9, in which the current pulse with a stalled motor connected is comparable to the fault current. This also indicates that the current magnitude is not a good indicator to distinguish a fault from a normal condition with a stalled motor. From the aspect of frequency domain, the impedance of a stalled motor is more inductive, and then the resistance in (11) can be ignored in a simplified model. When a stalled motor is connected parallel to a load as shown in Fig. 8, the reactance of the downstream becomes where is the reactance of downstream with a stalled motor, and is the inductance of a stalled motor. The first part of the is proportional to frequency and the ratio ; the second part of the increases with an increase in frequency. In this case, increases significantly as the frequency increases as shown in Fig. 10. This scenario is clearly different from the reactance in a faulted condition. Thus, similar to the detection of symmetrical faults, versus frequency can be used to distinguish a fault from a stalled motor. Note that using the reactance versus frequency criterion can effectively distinguish a fault from a stalled motor situation, but it cannot distinguish a stalled motor from a normal (no fault) condition as they both have a similar X/f ratio. However, detecting the existence of a stalled motor is not really the purpose of this paper. As long as a fault can be effectively detected, the proposed detection scheme can work properly. C. Impact of the Capacitor Bank As shown in Fig. 11, a shunt capacitor is usually connected in a distribution system to provide reactive power compensation and, therefore, improves the quality of the electrical supply and enhances the efficient operation of the power system. However, with its capacitive reactive power compensation, the contribution of a capacitor bank to current pulse is similar to that of a fault. When the voltage pulse is applied to a downstream with a 2.5-Mvar shunt capacitor connected, the produced

5 1906 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 Fig. 12. Effect of a capacitor on the current pulse. Fig. 14. Harmonic impedance when a 2.5 MVA capacitor and a 5000-hp motor are connected. Fig. 13. Harmonic resistance R(f ) with a capacitor. current pulse is shown in Fig. 12. As it can be seen, the current has a comparable magnitude as the fault current. It is therefore difficult to distinguish a fault from a capacitor bank if only comparing the currents waveforms in the time domain. In the frequency domain, the capacitor almost has no contribution in the dc component (0 Hz) and its harmonic impedance decreases as the frequency increases. After installing a capacitor bank in the system, the harmonic resistance is changed (13) It is obvious that decreases rapidly with the increase of frequency. In contrast to this, the resistance in a faulted condition almost has no change in the low frequencies. When a capacitor is connected to the de-energized system, the harmonic resistance in a faulted condition and a normal condition are compared in Fig. 13. It can be seen that with the increase of frequency, the harmonic resistance decays rapidly when there is a capacitor bank. However, if a fault exists, the change of harmonic resistance in low frequencies is very small. Thus, this difference provides a criterion for distinguishing a fault from a capacitor bank. Furthermore, if a stalled motor and a capacitor bank exist in the downstream, the harmonic impedance will not follow the patterns discussed before since parallel resonance may occur with the motor and the capacitor. For example, if the motor in Fig. 8 and the capacitor in Fig. 11 are both connected to Fig. 15. Harmonic impedance when a 0.25 MVA capacitor and a 5000 hp motor are connected. the de-energized system in parallel, the harmonic impedance will become as shown in Fig. 14. Apparently, the parallel resonance occurs at the frequency 180 Hz. The magnitude of the impedance at resonance frequency is limited due to the existence of the resistance. Generally, the resonance frequency depends on the system capacitance and reactance. If the capacitance is small, the resonance will occur at a higher frequency. Fig. 15 shows the simulation result when the 2.5 MVar capacitor is replaced by a 0.25 MVar capacitor. Within the frequencies between Hz, the scenario of parallel resonance is not observed. However, the difference between the faulted and the unfaulted cases is significant in Figs. 14 and 15. Thus, a symmetrical fault can still be detected even though there is a parallel resonance introduced by a capacitor and a stalled motor. Finally, with the aforementioned analysis for harmonics impedance characteristics under different situations, and combined with the asymmetrical fault detection method in [15], the fault detection procedure including the harmonic impedance analysis can be updated as follows. 1) Measure the currents and voltages of three phases after T1, T3, and T5 are fired simultaneously. 2) Are currents the same?

6 LONG et al.: NEW TECHNIQUE TO DETECT FAULTS IN DE-ENERGIZED DISTRIBUTION FEEDERS PART II 1907 Fig. 17. Diagram of the low-voltage lab test setup. Fig. 16. Overall logic for symmetrical fault detection. If No, turn to asymmetrical faults analysis (as in [15]). If Yes, calculate,, and by using the Fourier transforms of the current and voltage with an FFT algorithm. i) If harmonic resonance is observed in, it indicates that a capacitor and a motor are connected and the line is healthy. ii) Otherwise, if has a large increase with the increase of a frequency and is almost proportional to the frequency, it indicates that a normal condition or a stalled motor exists. iii) Otherwise, if decays as frequency increases, a capacitor is connected without fault. iv) If both and have no significant change as frequency increases in the observed frequencies (0 360 Hz), it indicates that a symmetrical fault exists. The overall logic for symmetrical fault detection based on harmonic impedance is summarized in Fig. 16. III. LAB EXPERIMENT A lab experiment based on a single-phase low-voltage system has been carried out to verify the proposed harmonic impedance-based fault detection method. The laboratory prototype consists of: 1) a thyristor-based signal generator; 2) a NI-DAQ based data-acquisition system; and 3) a lumped model-based equivalent circuit. Since the injected current is zero sequence in the proposed scheme, a single-phase system can effectively represent a balanced three-phase system for the research of symmetrical fault detection. In the DAQ device, six channels are utilized three of them are for voltage measurement and the other three are for current measurement. The sampling rate in the voltages and currents measurement is 1024 points every cycle, and a 1024-point FFT is performed for harmonic impedance analysis based on 60 Hz fundamental. The sampling rate is fast enough in this paper since the signal frequencies of interest are between Hz. In some cases, such as high-impedance fault detection, higher frequencies components are also considered as will be discussed later. Due to the limitations of lab equipment, the transmission lines, transformers, and loads are replaced by equivalent R-L models. The effects of an induction motor, which is connected in parallel to the load, are also investigated. Moreover, to test the performance of the proposed idea on the high-impedance fault detection, a tree branch and a box of dirt are used to simulate high-impedance faults. The parameters of the components in this test are listed as follows, which is scaled down from the computer simulation model (with the same per-unit values preserved): power source: 120 V; transformers: 0.03 p.u., 0.76 mh; signal generator: a thyristor; firing angle is adjustable from 170 to 150 ; feeders:, 0.4 mh; load:, 10 mh; faults: resistance. The equivalent circuit of the lab test is shown in Fig. 17. The fault resistance is adjustable. Three voltage probes and three current probes measure the voltages and current at different locations. The harmonic resistance and reactance are calculated by the measured and. Figs. 18 and 19 show the and in three different conditions: 1) a bolted fault; 2) a fault with resistance ; and 3) no fault. It is seen that with a bolted fault is almost zero at all frequencies, which can be easily detected. On the other hand, increases slowly in both faulted situations but increases fast in unfaulted situations, which is consistent with the theoretical analysis. To prove that the proposed idea has the ability of distinguishing a fault from a stalled motor, a single-phase induction motor is connected to the test circuit and the parameters of the motor are listed in Table II. Since the induction motor is just like a short circuit when it is stalled, it causes a high current which is even larger than the fault current as shown in Fig. 20. To distinguish the stalled motor from a fault, in the two conditions are illustrated in Fig. 21. It is apparent that the reactance of the downstream with a motor increases obviously

7 1908 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 Fig. 18. Comparison of harmonic resistance R(f ). Fig. 21. Harmonic reactance X(f ) with a motor. Fig. 19. Comparison of harmonic reactance X(f ). TABLE II PARAMETERS OF THE INDUCTION MOTOR Fig. 22. High-impedance fault test with a tree branch. Fig. 23. Current waveforms in a tree branch test. Fig. 20. Effect of an induction motor on current waveforms. in a normal condition, while this reactance with a fault is less affected by the increase of frequency. In reality, a fault could occur on any ground condition, like a tree branch, sand, mud, and dirt. The ground conditions affect the characteristics of faults, and changes the fault resistance. Particularly, the high fault impedance is a challenge for fault detection using the electrical signal. To investigate the performance of the proposed idea under a high impedance fault, two experiments have been carried out. One is with a tree branch (Fig. 22). The tree branch is cut off from a live tree and its length is limited to 10 cm to lower the impedance. However, its resistance still reaches 16 k, even though it is wet. Fig. 23 shows the currents obtained from the tree branch test. The resistance of the branch is too high so that the fault current is almost zero. Another high-impedance fault test is with a box of dirt (Fig. 24). The dirt comprises mud, little rocks, dead leaves, and water. The resistance is 5 k, which is lower than the tree branch but is still a high-impedance fault condition. The fault current through a box of dirt is also very low as shown

8 LONG et al.: NEW TECHNIQUE TO DETECT FAULTS IN DE-ENERGIZED DISTRIBUTION FEEDERS PART II 1909 Fig. 24. High-impedance fault test with a box of mud and dirt. Fig. 26. Harmonic reactance X(f ) in the high-impedance fault tests. IV. CONCLUSION Fig. 25. Current waveforms in a mud and dirt test. in Fig. 25. In this case, most of the injected current flows through the connected loads rather than the box of dirt with high impedance. The harmonic reactance in the high-impedance fault tests is shown in Fig. 26. Since there is no electrical response on the tree branch, the measured harmonic reactance in the faulted line and the unfaulted line has almost no difference. The main reason for the tree branch test not being effective is due to the low-voltage test limitation. At higher voltage levels in a typical distribution system, a stronger voltage pulse could cause actual fault arcs through a tree branch, which essentially reduces the fault impedance and, therefore, helps the high-impedance fault detection. To the contrary, the mud and dirt measurements had better results despite the fault current s low magnitude. The harmonic reactance of the faulted line follows a flatter trend than the unfaulted line within a range of frequencies, such as between Hz. The distinction would likely improve in an actual situation, considering that the dirt had a much higher resistance than the rest of the scaled down circuit. Compared to the tree branch test, we can see that the harmonic impedance becomes more effective if there is current flowing through the fault. Once again, the situation can be expected to improve at a higher voltage level due to the arcs produced by the voltage detection signal. This paper focuses on the development of a symmetrical three-phase fault detection technique in a de-energized system, where the existence of a stalled motor or shunt capacitor bank makes the fault detection even more challenging as they behave like short circuits. Compared to the asymmetrical fault detection, the aforementioned situations require a detection technique other than simply comparing the three-phase currents. Thus, a new detection method based on the harmonic impedance characteristics under the downstream circuit is developed. The proposed method can be effectively used for symmetrical fault detection and for distinguishing a fault from a stalled motor or capacitor bank. Finally, the fault detection procedure, including symmetrical and asymmetrical faults and with consideration of possible stalled motor or capacitor banks at downstream, is presented. The proposed method has been verified in computer simulations and lab tests. This paper is supplementary to a companion paper [15], which presents the basic principle of the proposed power-electronics-based fault detection technique and discusses the procedure of asymmetrical faults detection. Combining the findings in both papers, all different types of faults in the de-energized system can be identified. REFERENCES [1] V. L. Buchholz, M. Nagpal, and J. B. Neilson, High impedance fault detection device tester, IEEE Trans. Power Del., vol. 11, no. 1, pp , Jan [2] S. P. Ahn, C. H. Kim, R. K. Aggarwal, and A. T. Aggarwal, An alternative approach to adaptive single pole auto-reclosing in high voltage transmission systems based on variable dead time control, IEEE Trans. Power Del., vol. 16, no. 4, pp , Oct [3] M. M. Eissa and O. P. Malik, A novel approach for auto-reclosing EHV/UHV transmission lines, IEEE Trans. Power Del., vol. 15, no. 3, pp , Jul [4] C. G. Wester, High impedance fault detection on distribution systems, in Proc. 42nd Rural Elect. Power Conf., St. Louis, MO, 1998, pp. C [5] IEEE Guide for Automatic Reclosing of Line Circuit Breakers for AC Distribution and Transmission Lines, IEEE Std. C , Apr

9 1910 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 [6] G. D. Rockefeller, C. L. Rockefeller, J. L. Linders, K. L. Hicks, and D. T. Rizy, Adaptive transmission relaying concepts for improved performance, IEEE Trans. Power Del., vol. 3, no. 4, pp , Oct [7] M. M. Eissa and O. P. Malik, A new digital directional transverse differential current protection technique, IEEE Trans. Power Del., vol. 11, no. 3, pp , Jul [8] J. F. Witte, S. R. Mendis, M. T. Bishop, and J. A. Kischefsky, Computer-aided recloser applications for distribution systems, IEEE Comput. Appl. Power, vol. 5, no. 3, pp , Jul [9] A. T. Johns, R. K. Aggarwal, and Y. H. Song, Improved techniques for modeling fault arcs on faulted EHV transmission systems, in Proc. Inst. Elect. Eng., Gen., Transm. Distrib., 1994, pp [10] A. T. Trihus, Cable tester, U.S. Patent , Mar. 3, [11] D. A. Rhein and L. R. Beard, Fault Detection System Including a Capacitor for Generating a Pulse and a Processor for Determine Admittance Versus Frequency of a Reflected Pulse, U.S. Patent , Jul. 22, [12] D. D. Wilson and Hedman, Fault Isolator for Electrical Utility Distribution Systems, U.S. Patent , Jan. 25, [13] R. Maier and W. Roethlingshoefer, Method and Arrangement for Detecting Short-Circuit in Circuit Branches of Electrical Power System Networks, U.S. Patent , Sep. 6, [14] S&C, S&C IntelliRupter PulseCloser: Outdoor distribution 15.5 kv and 27 kv, S&C Descriptive Bull , Mar. 22, [15] X. Long, W. Xu, and Y. Li, A power electronics based fault detection technique in a de-energized distribution system for safe recloser operation, IEEE Trans. Power Del., submitted for publication. [16] W. Wang, E. E. Nino, and W. Xu, Harmonic impedance measurement using a thyristor-controlled short-circuit, Inst. Eng. Technol.. Gen., Transm. Distrib., vol. 1, no. 5, pp , Sep [17] J. C. Gomez and M. M. Morcos, A simple methodology for estimating the effect of voltage sags produced by induction motor starting cycles on sensitive equipment, in Proc. 36th Ind. Appl. Soc. Annu. Meeting, Chicago, IL, Oct. 2001, pp Xun Long (S 08) received the B.E. and M.Sc. degrees in electrical engineering from Tsinghua University, Beijing, China, in 2004 and 2007, respectively, and is currently pursuing the Ph.D. degree in electrical and computer engineering at the University of Alberta, Edmonton, AB, Canada. His main research interests include power-line signaling, distributed generation, and fault detection. Yun Wei Li (S 04 M 05) received the B.Sc. degree in engineering degree from Tianjin University, Tianjin, China, in 2002, and the Ph.D. degree from Nanyang Technological University, Singapore, in In 2005, he was a Visiting Scholar with the Institute of Energy Technology, Aalborg University, Denmark. From 2006 to 2007, he was a Postdoctoral Research Fellow in the Department of Electrical and Computer Engineering, Ryerson University, Toronto, ON, Canada. After working with Rockwell Automation Canada in 2007, he joined the Department of Electrical and Computer Engineering, University of Alberta, Edmonton, AB, Canada, as an Assistant Professor. His research interests include distributed generation, microgrid, power converters, and electric motor drives. Wilsun Xu (F 05) received the Ph.D. degree from the University of British Columbia, Vancouver, BC, Canada, in From 1989 to 1996, he was an Electrical Engineer with BC Hydro,Vancouver, and Surrey, BC, respectively. Currently, he is with the Department of Electrical and Computer Engineering, University of Alberta, where he has been since His research interests are power quality and distributed generation. Chris Lerohl (S 08) received the B.Sc. degree in electrical engineering from the University of Alberta, Edmonton, AB, Canada, in 2009, where he is currently pursuing the M.Sc. degree in power systems. His main research interests include transmission-line signaling, distributed generation, and power system harmonics.

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 1893 A New Technique to Detect Faults in De-Energized Distribution Feeders Part I: Scheme and Asymmetrical Fault Detection Xun Long, Student

More information

ANEW, simple and low cost scheme to reduce transformer

ANEW, simple and low cost scheme to reduce transformer 950 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 A Sequential Phase Energization Technique for Transformer Inrush Current Reduction Part II: Theoretical Analysis and Design Guide Wilsun

More information

EMERGING distributed generation technologies make it

EMERGING distributed generation technologies make it IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005 1757 Fault Analysis on Distribution Feeders With Distributed Generators Mesut E. Baran, Member, IEEE, and Ismail El-Markaby, Student Member,

More information

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL 2011 799 Practical Power Quality Charts for Motor Starting Assessment Xiaoyu Wang, Member, IEEE, Jing Yong, Member, IEEE, Wilsun Xu, Fellow, IEEE,

More information

HARMONIC distortions can have significant adverse

HARMONIC distortions can have significant adverse 1710 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 3, JULY 2009 An Investigation on the Selection of Filter Topologies for Passive Filter Applications Alexandre B. Nassif, Student Member, IEEE, Wilsun

More information

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer Ms. Kanchan S.Patil PG, Student kanchanpatil2893@gmail.com Prof.Ajit P. Chaudhari Associate Professor ajitpc73@rediffmail.com

More information

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component International Journal Of Computational Engineering Research (ijceronline.com) Vol. 3 Issue. 3 Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component 1, Mr. R.V.KATRE,

More information

A Resonant Tertiary Winding-Based Novel Air-Core Transformer Concept Pooya Bagheri, Wilsun Xu, Fellow, IEEE, and Walmir Freitas, Member, IEEE

A Resonant Tertiary Winding-Based Novel Air-Core Transformer Concept Pooya Bagheri, Wilsun Xu, Fellow, IEEE, and Walmir Freitas, Member, IEEE IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012 1519 A Resonant Tertiary Winding-Based Novel Air-Core Transformer Concept Pooya Bagheri, Wilsun Xu, Fellow, IEEE, and Walmir Freitas, Member,

More information

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION International Journal of Electrical, Electronics and Data Communication, ISSN: 23284 Volume, Issue-4, April14 INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION 1 V.S.VENKATESAN, 2 P.CHANDHRA

More information

AS the power distribution networks become more and more

AS the power distribution networks become more and more IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 1, FEBRUARY 2006 153 A Unified Three-Phase Transformer Model for Distribution Load Flow Calculations Peng Xiao, Student Member, IEEE, David C. Yu, Member,

More information

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS 24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 97 RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS Pengfei WEI Yonghai XU Yapen WU Chenyi

More information

Detection of Fault in Fixed Series Compensated Transmission Line during Power Swing Using Wavelet Transform

Detection of Fault in Fixed Series Compensated Transmission Line during Power Swing Using Wavelet Transform International Journal of Scientific and Research Publications, Volume 4, Issue 5, May 24 Detection of Fault in Fixed Series Compensated Transmission Line during Power Swing Using Wavelet Transform Rohan

More information

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES N. Perera 1, A. Dasgupta 2, K. Narendra 1, K. Ponram 3, R. Midence 1, A. Oliveira 1 ERLPhase Power Technologies Ltd. 1 74 Scurfield

More information

NOWADAYS, there is much interest in connecting various

NOWADAYS, there is much interest in connecting various IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013 419 Modified Dynamic Phasor Estimation Algorithm for the Transient Signals of Distributed Generators Dong-Gyu Lee, Sang-Hee Kang, and Soon-Ryul

More information

HARMONIC and interharmonic measurements are one of

HARMONIC and interharmonic measurements are one of IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 2, APRIL 2012 971 A Method to Improve the Interharmonic Grouping Scheme Adopted by IEC Standard 61000-4-7 Jin Hui, Honggeng Yang, Member, IEEE, Wilsun

More information

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute

More information

ATYPICAL high-power gate-turn-off (GTO) currentsource

ATYPICAL high-power gate-turn-off (GTO) currentsource 1278 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 6, NOVEMBER/DECEMBER 1998 A Novel Power Factor Control Scheme for High-Power GTO Current-Source Converter Yuan Xiao, Bin Wu, Member, IEEE,

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

DISTRIBUTED GENERATION (DG) has recently gained

DISTRIBUTED GENERATION (DG) has recently gained 1758 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007 A Power Line Signaling Based Technique for Anti-Islanding Protection of Distributed Generators Part I: Scheme and Analysis Wilsun Xu,

More information

VOLTAGE sag and interruption are the most important

VOLTAGE sag and interruption are the most important 806 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 2, MAY 2005 Voltage Sag State Estimation for Power Distribution Systems Bin Wang, Wilsun Xu, Senior Member, IEEE, and Zhencun Pan Abstract The increased

More information

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 22, NO. 4, NOVEMBER

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 22, NO. 4, NOVEMBER TRANSACTIONS ON POWER SYSTEMS, VOL. 22, NO. 4, NOVEMBER 2007 1 A Harmonically Coupled Admittance Matrix Model for AC/DC Converters Yuanyuan Sun, Guibin Zhang, Wilsun Xu, Fellow,, Julio G. Mayordomo, Member,

More information

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM G.SUNDAR, S.RAMAREDDY Research Scholar, Bharath University Chenna Professor Jerusalam College of Engg. Chennai ABSTRACT This paper deals with simulation

More information

Three-Phase/Six-Phase Conversion Autotransformers

Three-Phase/Six-Phase Conversion Autotransformers 1554 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER 2003 Three-Phase/Six-Phase Conversion Autotransformers Xusheng Chen, Member, IEEE Abstract The first commercial demonstration of six-phase

More information

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer.

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer. 208 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 A Sequential Phase Energization Method for Transformer Inrush Current Reduction Transient Performance and Practical Considerations

More information

Online Monitoring of Substation Grounding Grid Conditions Using Touch and Step Voltage Sensors

Online Monitoring of Substation Grounding Grid Conditions Using Touch and Step Voltage Sensors IEEE TRANSACTIONS ON SMART GRID, VOL. 3, NO. 2, JUNE 2012 761 Online Monitoring of Substation Grounding Grid Conditions Using Touch and Step Voltage Sensors Xun Long, Student Member, IEEE, MingDong, Student

More information

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads Ponananthi.V, Rajesh Kumar. B Final year PG student, Department of Power Systems Engineering, M.Kumarasamy College of

More information

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System M.S.B Subrahmanyam 1 T.Swamy Das 2 1 PG Scholar (EEE), RK College of Engineering, Kethanakonda,

More information

International Journal of Current Research and Modern Education (IJCRME) ISSN (Online): & Impact Factor: Special Issue, NCFTCCPS -

International Journal of Current Research and Modern Education (IJCRME) ISSN (Online): & Impact Factor: Special Issue, NCFTCCPS - GSM TECHNIQUE USED FOR UNDERGROUND CABLE FAULT DETECTOR AND DISTANCE LOCATOR R. Gunasekaren*, J. Pavalam*, T. Sangamithra*, A. Anitha Rani** & K. Chandrasekar*** * Assistant Professor, Department of Electrical

More information

RECENTLY, the harmonics current in a power grid can

RECENTLY, the harmonics current in a power grid can IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 2, MARCH 2008 715 A Novel Three-Phase PFC Rectifier Using a Harmonic Current Injection Method Jun-Ichi Itoh, Member, IEEE, and Itsuki Ashida Abstract

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by

More information

Improving Passive Filter Compensation Performance With Active Techniques

Improving Passive Filter Compensation Performance With Active Techniques IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan

More information

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems A New Network Proposal for Fault-Tolerant HVDC Transmission Systems Malothu Malliswari 1, M. Srinu 2 1 PG Scholar, Anurag Engineering College 2 Assistant Professor, Anurag Engineering College Abstract:

More information

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits 1 Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits M. N. Moschakis, E. A. Leonidaki, Student Member, IEEE, N. D. Hatziargyriou, Senior

More information

COMMON mode current due to modulation in power

COMMON mode current due to modulation in power 982 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 5, SEPTEMBER 1999 Elimination of Common-Mode Voltage in Three-Phase Sinusoidal Power Converters Alexander L. Julian, Member, IEEE, Giovanna Oriti,

More information

IN HIGH-POWER (up to hp) ac motor drives using

IN HIGH-POWER (up to hp) ac motor drives using 878 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 4, JULY/AUGUST 1998 A Dual GTO Current-Source Converter Topology with Sinusoidal Inputs for High-Power Applications Yuan Xiao, Bin Wu, Member,

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

Dynamic Response of Wound Rotor Induction Generator for. Wind Energy Application

Dynamic Response of Wound Rotor Induction Generator for. Wind Energy Application Dynamic Response of Wound Rotor Induction Generator for Wind Energy Application Saurabh Gupta Kishor Thakre Gaurav Gupta Research scholar Research scholar Research Scholar UIT-RGPV BHOPAL UIT-RGPV BHOPAL

More information

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 16, NO. 5, SEPTEMBER 2001 603 A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

More information

Analysis of Modern Digital Differential Protection for Power Transformer

Analysis of Modern Digital Differential Protection for Power Transformer Analysis of Modern Digital Differential Protection for Power Transformer Nikhil Paliwal (P.G. Scholar), Department of Electrical Engineering Jabalpur Engineering College, Jabalpur, India Dr. A. Trivedi

More information

VOLTAGE SAG MITIGATION USING A NEW DIRECT CONTROL IN D-STATCOM FOR DISTRIBUTION SYSTEMS

VOLTAGE SAG MITIGATION USING A NEW DIRECT CONTROL IN D-STATCOM FOR DISTRIBUTION SYSTEMS U.P.B. Sci. Bull., Series C, Vol. 7, Iss. 4, 2009 ISSN 454-234x VOLTAGE SAG MITIGATION USING A NEW DIRECT CONTROL IN D-STATCOM FOR DISTRIBUTION SYSTEMS Rahmat-Allah HOOSHMAND, Mahdi BANEJAD 2, Mostafa

More information

Improved differential relay for bus bar protection scheme with saturated current transformers based on second order harmonics

Improved differential relay for bus bar protection scheme with saturated current transformers based on second order harmonics Journal of King Saud University Engineering Sciences (2016) xxx, xxx xxx King Saud University Journal of King Saud University Engineering Sciences www.ksu.edu.sa www.sciencedirect.com ORIGINAL ARTICLES

More information

AN ANN BASED FAULT DETECTION ON ALTERNATOR

AN ANN BASED FAULT DETECTION ON ALTERNATOR AN ANN BASED FAULT DETECTION ON ALTERNATOR Suraj J. Dhon 1, Sarang V. Bhonde 2 1 (Electrical engineering, Amravati University, India) 2 (Electrical engineering, Amravati University, India) ABSTRACT: Synchronous

More information

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system

More information

Downloaded from

Downloaded from Proceedings of The Intl. Conf. on Information, Engineering, Management and Security 2014 [ICIEMS 2014] 330 Power Quality Improvement Using UPQC Chandrashekhar Reddy S Assoc.Professor, Dept.of Electrical

More information

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality enhancement of a distribution line with DSTATCOM ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical

More information

NOWADAYS, the proliferation and development of

NOWADAYS, the proliferation and development of IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 4, OCTOBER 2008 2513 Voltage Swell and Overvoltage Compensation With Unidirectional Power Flow Controlled Dynamic Voltage Restorer Chi-Seng Lam, Member,

More information

Wavelet Based Fault Detection, Classification in Transmission System with TCSC Controllers

Wavelet Based Fault Detection, Classification in Transmission System with TCSC Controllers ISSN: 2248-9622, Vol. 5, Issue 8, (Part - 3) August 215, pp.25-29 RESEARCH ARTICLE OPEN ACCESS Wavelet Based Fault Detection, Classification in Transmission System with TCSC Controllers 1 G.Satyanarayana,

More information

Harmonic Distortion Levels Measured at The Enmax Substations

Harmonic Distortion Levels Measured at The Enmax Substations Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned

More information

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 969 Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies Taku Noda, Member, IEEE, Hiroshi Nakamoto,

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

1842 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009

1842 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009 1842 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009 Phasor Estimation in the Presence of DC Offset and CT Saturation Soon-Ryul Nam, Member, IEEE, Jong-Young Park, Sang-Hee Kang, Member,

More information

Fault Location Technique for UHV Lines Using Wavelet Transform

Fault Location Technique for UHV Lines Using Wavelet Transform International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 1 (2013), pp. 77-88 International Research Publication House http://www.irphouse.com Fault Location Technique for UHV Lines

More information

IN MANY industrial applications, ac machines are preferable

IN MANY industrial applications, ac machines are preferable IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 46, NO. 1, FEBRUARY 1999 111 Automatic IM Parameter Measurement Under Sensorless Field-Oriented Control Yih-Neng Lin and Chern-Lin Chen, Member, IEEE Abstract

More information

ENHANCEMENT OF POWER QUALITY BY INJECTING SERIES VOLTAGE USING DVR

ENHANCEMENT OF POWER QUALITY BY INJECTING SERIES VOLTAGE USING DVR ENHNEMENT OF POWER QULITY Y INJETING SERIES VOLTGE USING DVR Praksh Patil 1, Prof. Sunil hatt 2 1 PG Scholar, Department of Electrical Engineering, entral India Institute of Technology Indore- 452016,

More information

SEVERAL static compensators (STATCOM s) based on

SEVERAL static compensators (STATCOM s) based on 1118 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 35, NO. 5, SEPTEMBER/OCTOBER 1999 A New Type of STATCOM Based on Cascading Voltage-Source Inverters with Phase-Shifted Unipolar SPWM Yiqiao Liang,

More information

MMC based D-STATCOM for Different Loading Conditions

MMC based D-STATCOM for Different Loading Conditions International Journal of Engineering Research And Management (IJERM) ISSN : 2349-2058, Volume-02, Issue-12, December 2015 MMC based D-STATCOM for Different Loading Conditions D.Satish Kumar, Geetanjali

More information

Bahram Amin. Induction Motors. Analysis and Torque Control. With 41 Figures and 50 diagrams (simulation plots) Springer

Bahram Amin. Induction Motors. Analysis and Torque Control. With 41 Figures and 50 diagrams (simulation plots) Springer Bahram Amin Induction Motors Analysis and Torque Control With 41 Figures and 50 diagrams (simulation plots) Springer 1 Main Parameters of Induction Motors 1.1 Introduction 1 1.2 Structural Elements of

More information

White Rose Research Online URL for this paper:

White Rose Research Online URL for this paper: This is a repository copy of Improved transient simulation of salient-pole synchronous generators with internal and ground faults in the stator winding. White Rose Research Online URL for this paper: http://eprints.whiterose.ac.uk/865/

More information

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy Abstract This paper presents a new unified power-quality conditioning system (MC-UPQC), capable

More information

Solving Customer Power Quality Problems Due to Voltage Magnification

Solving Customer Power Quality Problems Due to Voltage Magnification PE-384-PWRD-0-11-1997 Solving Customer Power Quality Problems Due to Voltage Magnification R. A. Adams, Senior Member S. W. Middlekauff, Member Duke Power Company Charlotte, NC 28201 USA E. H. Camm, Member

More information

Power Quality Improvement by DVR

Power Quality Improvement by DVR Power Quality Improvement by DVR K Rama Lakshmi M.Tech Student Department of EEE Gokul Institute of Technology and Sciences, Piridi, Bobbili Vizianagaram, AP, India. Abstract The dynamic voltage restorer

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Identification of weak buses using Voltage Stability Indicator and its voltage profile improvement by using DSTATCOM in radial distribution systems

Identification of weak buses using Voltage Stability Indicator and its voltage profile improvement by using DSTATCOM in radial distribution systems IOSR Journal of Electrical And Electronics Engineering (IOSRJEEE) ISSN : 2278-1676 Volume 2, Issue 4 (Sep.-Oct. 2012), PP 17-23 Identification of weak buses using Voltage Stability Indicator and its voltage

More information

The unified power quality conditioner: the integration of series and shunt-active filters

The unified power quality conditioner: the integration of series and shunt-active filters Engineering Electrical Engineering fields Okayama University Year 1997 The unified power quality conditioner: the integration of series and shunt-active filters Hideaki Fujita Okayama University Hirofumi

More information

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Dr. Jagdish Kumar, PEC University of Technology, Chandigarh Abstract the proper selection of values of energy storing

More information

IOCL Electrical Engineering Technical Paper

IOCL Electrical Engineering Technical Paper IOCL Electrical Engineering Technical Paper 1. Which one of the following statements is NOT TRUE for a continuous time causal and stable LTI system? (A) All the poles of the system must lie on the left

More information

A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors

A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors 452 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors Ying-Hong Lin,

More information

II. RESEARCH METHODOLOGY

II. RESEARCH METHODOLOGY Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College

More information

International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July ISSN

International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July ISSN International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July-2013 377 Self-Healing Framework for Distribution Systems Fazil Haneef, S.Angalaeswari Abstract - The self healing framework

More information

New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications

New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 1, JANUARY/FEBRUARY 2002 131 New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications Sewan Choi,

More information

WITH THE advent of advanced power-electronics technologies,

WITH THE advent of advanced power-electronics technologies, IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 4, AUGUST 2014 1859 Impact of Unified Power-Quality Conditioner Allocation on Line Loading, Losses, and Voltage Stability of Radial Distribution Systems

More information

A Multilevel Diode Clamped SVPWM Based Interline Dynamic Voltage Restorer with Sag & Swell Limiting Function

A Multilevel Diode Clamped SVPWM Based Interline Dynamic Voltage Restorer with Sag & Swell Limiting Function International Journal of Electronics Engineering Research. ISSN 0975-6450 Volume 9, Number 5 (2017) pp. 751-760 Research India Publications http://www.ripublication.com A Multilevel Diode Clamped SVPWM

More information

Power-Quality Improvement with a Voltage-Controlled DSTATCOM

Power-Quality Improvement with a Voltage-Controlled DSTATCOM Power-Quality Improvement with a Voltage-Controlled DSTATCOM R.Pravalika MTech Student Paloncha, Khammam, India V.Shyam Kumar Associate Professor Paloncha, Khammam, India. Mr.Chettumala Ch Mohan Rao Associate

More information

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Phanikumar.Ch, M.Tech Dept of Electrical and Electronics Engineering Bapatla Engineering College, Bapatla,

More information

The Fault Level Reduction in Distribution System Using an Active Type SFCL

The Fault Level Reduction in Distribution System Using an Active Type SFCL www.ijecs.in International Journal Of Engineering And Computer Science ISSN: 2319-7242 Volume 5 Issues 8 Aug 2016, Page No. 17392-17396 The Fault Level Reduction in Distribution System Using an Active

More information

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System Amin Safari Department of Electrical Engineering, Ahar Branch, Islamic Azad University, Ahar, Iran a-safari@iau-ahar.ac.ir

More information

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) ABHIYANTRIKI Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) An International Journal of Engineering & Technology (A Peer Reviewed & Indexed Journal) Vol.

More information

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti

More information

THE third-harmonic current injection is a method to reduce

THE third-harmonic current injection is a method to reduce 96 IEEE POWER ELECTRONICS LETTERS, VOL. 3, NO. 3, SEPTEMBER 2005 Low-Harmonic, Three-Phase Rectifier That Applies Current Injection and a Passive Resistance Emulator Predrag Pejović, Predrag Božović, and

More information

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis M. N. Moschakis* N. D. Hatziargyriou National Technical University of Athens Department of Electrical and Computer Engineering 9, Iroon

More information

Online Optimal Transmission Line Parameter Estimation for Relaying Applications Yuan Liao, Senior Member, IEEE, and Mladen Kezunovic, Fellow, IEEE

Online Optimal Transmission Line Parameter Estimation for Relaying Applications Yuan Liao, Senior Member, IEEE, and Mladen Kezunovic, Fellow, IEEE 96 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 1, JANUARY 2009 Online Optimal Transmission Line Parameter Estimation for Relaying Applications Yuan Liao, Senior Member, IEEE, and Mladen Kezunovic,

More information

Performance Analysis of Various Types of Fault Current Limiters Using PSCAD

Performance Analysis of Various Types of Fault Current Limiters Using PSCAD Performance Analysis of Various Types of Fault Current Limiters Using PSCAD Anurag.G 1, Sudhagar.V 2 PG student,[pse] Dept. of EEE, Valliammai Engineering College, Chennai, Tamilnadu, India 1 Assistant

More information

A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor. S.H.Haggag, Ali M. El-Rifaie,and Hala M.

A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor. S.H.Haggag, Ali M. El-Rifaie,and Hala M. Proceedings of the World Congress on Engineering 013 Vol II,, July 3-5, 013, London, U.K. A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor S.H.Haggag, Ali M. El-Rifaie,and

More information

Designing Of Distributed Power-Flow Controller

Designing Of Distributed Power-Flow Controller IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) ISSN: 2278-1676 Volume 2, Issue 5 (Sep-Oct. 2012), PP 01-09 Designing Of Distributed Power-Flow Controller 1 R. Lokeswar Reddy (M.Tech),

More information

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants 4th International Conference on Machinery, Materials and Information Technology Applications (ICMMITA 2016) Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants Chen-Xin

More information

Power Quality Improvement By Using DSTATCOM Controller

Power Quality Improvement By Using DSTATCOM Controller Power Quality Improvement By Using DSTATCOM Controller R.Srikanth 1 E. Anil Kumar 2 Assistant Professor, Assistant Professor, Dept. of EEE, BITS Vizag Dept. of EEE, BITS Vizag Email id : srikanthreddypalli@gmail.com

More information

Direct Harmonic Analysis of the Voltage Source Converter

Direct Harmonic Analysis of the Voltage Source Converter 1034 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003 Direct Harmonic Analysis of the Voltage Source Converter Peter W. Lehn, Member, IEEE Abstract An analytic technique is presented for

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

A Simple Technique for Islanding Detection with Negligible Nondetection Zone

A Simple Technique for Islanding Detection with Negligible Nondetection Zone A Simple Technique for Islanding Detection with Negligible Nondetection Zone The MIT Faculty has made this article openly available. Please share how this access benefits you. Your story matters. Citation

More information

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab University of Jordan School of Engineering Electrical Engineering Department EE 219 Electrical Circuits Lab EXPERIMENT 7 RESONANCE Prepared by: Dr. Mohammed Hawa EXPERIMENT 7 RESONANCE OBJECTIVE This experiment

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

Voltage Quality Enhancement in an Isolated Power System through Series Compensator International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 12, Issue 6 (June 2016), PP.20-26 Voltage Quality Enhancement in an Isolated Power

More information

Power Factor & Harmonics

Power Factor & Harmonics Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics

More information

Power Quality Improvement in Fourteen Bus System using UPQC

Power Quality Improvement in Fourteen Bus System using UPQC International Journal of Electrical Engineering. ISSN 0974-2158 Volume 8, Number 4 (2015), pp. 419-431 International Research Publication House http://www.irphouse.com Power Quality Improvement in Fourteen

More information

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control International Journal of Scientific Engineering and Research (IJSER) Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control Rahul Kumar Patel 1, S. Subha 2 Abstract:

More information