1 208 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 A Sequential Phase Energization Method for Transformer Inrush Current Reduction Transient Performance and Practical Considerations Sami G. Abdulsalam, Student Member, IEEE, and Wilsun Xu, Fellow, IEEE Abstract This paper presents an improved design method for a novel transformer inrush current reduction scheme. The scheme energizes each phase of a transformer in sequence and uses a neutral resistor to limit the inrush current. Although experimental and simulation results have demonstrated the effectiveness of the scheme, the problem of how to select the neutral resistor for optimal performance has not been fully solved. In this paper, an analytical method that is based on nonlinear circuit transient analysis is developed to solve this problem. The method models transformer nonlinearity using two linear circuits and derives a set of analytical equations for the waveform of the inrush current. In addition to establishing a set of formulas for optimal resistor determination, the results also reveal useful information regarding the inrush behavior of a transformer and the characteristics of the sequential energization scheme. This paper also proposed a method, the use of surge arrester, to solve the main limitation of the sequential phase energization scheme the rise of neutral voltage. Performance of the improved scheme is presented. Index Terms Inrush current, power quality, transformer. I. INTRODUCTION A sequential phase energization-based scheme to reduce transformer inrush currents has been proposed by the authors in [1] and [2] (Fig. 1). The method uses an optimally-sized grounding resistor. By energizing each phase of the transformer in sequence, the neutral resistor behaves as a series-inserted resistor and thereby significantly reduces the energization inrush currents. It was found that a neutral resistor that is 8.5% of the unsaturated magnetizing reactance would lead 80% to 90% inrush currents reduction. However, the resistor sizing issue was not investigated from the transient performance perspective due to difficulties in conducing transient analysis of nonlinear circuits. Our further study of the scheme revealed that a much lower resistor size is equally effective. The steady-state theory developed for neutral resistor sizing [2] is unable to explain this phenomenon. Extensive investigation showed that the phenomenon must be understood using transient analysis. If we select the neutral resistor to minimize the peak of the actual inrush current Manuscript received September 6, 2005; revised March 6, This work was supported by the Alberta Energy Research Institute. Paper no. TPWRD The authors are with the Department of Electrical and Computer Engineering, University of Alberta, Edmonton, AB T6G 2V4 Canada ( sgabr@ece. ualberta.ca; wxu@ece.ualberta.ca). Color versions of Figs. 2, 4 7, and 9 16 are available online at Digital Object Identifier /TPWRD Fig. 1. Sequential phase energization technique for inrush current reduction. directly, we can obtain a much lower resistor value. It was also found that the first phase energization leads to the highest inrush current among the three phases and, as a result, the resistor can be sized according to its effect on the first phase energization. With the help of nonlinear circuit theory [3], we managed to derive an analytical relationship between the peak of the inrush current and the size of the resistor, which results in a transient-analysis based theory for the resistor selection. One of the objectives of this paper is to present the analytical work and the resultant design guide for the scheme. The developed analytical method is an improvement over the one published in the classic Westinghouse T&D Reference Book [4] and can be used to analyze general inrush current phenomenon of transformers and reactors. In addition, this paper also addresses the main limitation of the proposed scheme the rise of neutral voltage. The use of surge arrester is proposed to overcome the limitation. Performance of the improved scheme is presented. The significance of this work is that it is a rigorous analytical study of the transformer energization phenomenon. The results reveal a good deal of information on inrush behavior of transformers and the characteristics of the sequential energization scheme. In addition, the developed analytical method made it possible to accurately estimate energy requirements for the grounding resistor and the voltage limiting surge arrester. II. PERFORMANCE OF THE SEQUENTIAL PHASE ENERGIZATION INRUSH MITIGATION SCHEME Since the scheme adopts sequential switching, each switching stage can be discussed separately. For first phase switching, the scheme performance is straightforward. The neutral resistor is in series with the energized phase and its effect will be similar to a pre-insertion resistor. When the third phase is energized, the voltage across the breaker contacts to be closed is essentially close to zero due to the existence of delta secondary or three /$ IEEE

2 ABDULSALAM AND XU: A SEQUENTIAL PHASE ENERGIZATION METHOD 209 Fig. 3. (a) Transformer electrical equivalent circuit (per-phase) referred to the primary side. (b) Simplified, two slope saturation curve. Fig. 2. Maximum inrush current as affected by the neutral resistor for a 30 kva, 208/208, Y 0 1, 3 limb transformer, [1]. (Top: experimental, bottom: simulation). legged core. So there will be minimal switching transients for when the 3rd phase is energized [1], [2]. The 2nd phase energization is the one most difficult to analyze. Fortunately, we discovered from numerous experimental and simulation studies that the inrush current due to 2nd phase energization is lower than those due to 1st phase energization for the same value of (Fig. 2). This is true for the region where the inrush current of the 1st phase is decreasing rapidly as increases. As a result, we should focus on analyzing the first phase energization to develop more precise sizing criteria for the neutral resistor. linear inductance as function of the operating flux linkages is represented as a linear inductor in unsaturated and saturated modes of operation respectively, Fig. 3(b). Secondary side resistance and leakage reactance as referred to primary side are also shown. and represent the primary and secondary phase to ground terminal voltages, respectively. During first phase energization, the differential equation describing the behavior of the transformer with saturable iron core can be written as follows: In order to represent the highest saturation level without losing generality, switching angle of zero on the applied sinusoidal voltage waveform together with a positive residual flux polarity is assumed throughout the analysis. In this case, saturation takes place at the positive side of the saturation curve. Accordingly, the general inrush current waveform in unsaturated and saturated modes of operation can be given by (1) III. ANALYTICAL STUDY OF FIRST PHASE SWITCHING One of the main focal points of this paper is to develop a solid design methodology for the neutral resistor size. Our approach presented here is based on deriving an analytical expression relating the amount of inrush current reduction directly to the neutral resistor size. Preliminary results have been presented earlier by the authors in [5]. An accurate expression for inrush current will eliminate the requirement of computer simulation on a case-by-case basis. Few investigations in this field have been done and some formulas were given to predict the general wave shape, harmonic content or the maximum peak current [3] [9]. For the presented application, it was required that the expression can accurately present the inrush current waveform over a wide range of neutral resistance values taking into account system impedance, residual flux value and the neutral resistor itself. where (2) A. Inrush Current Expression The transformer behavior during first phase energization can be modeled through the simplified equivalent electric circuit shown in Fig. 3 together with an approximate two-slope saturation curve, [3] [8]. In Fig. 3(a), and present the total primary side resistance and leakage reactance. The iron core non- Generally, transformers operate in unsaturated mode immediately after energization since the initial or residual flux is below the saturation flux level. For small neutral resistor values, the magnetizing impedance of the switched phase will

3 210 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 Fig. 4. Analytical and simulation inrush current waveforms (first cycle) for 30 kva Yg0 1 transformer. Fig. 5. I (R ) compared to the simulation peak current for MVA, 72/13.8 kv Yg limb transformer. be very high compared to other linear elements in the series circuit and the supply voltage will be mainly distributed across the magnetizing branch until saturation is reached. The saturation time can be calculated as follows: The inrush peak expression (3) can be rewritten as follows: where in (5) is a dimensionless factor which depends on transformer saturation characteristics ( and ) as well as the total ratio during saturation (5) (6) where,, and are the nominal peak flux linkages, supply voltage, and angular frequency, respectively. Fig. 4 shows the first cycle, analytical and simulation waveforms for the 30 kva transformer with neutral resistor values of 0.1, 0.5, and 1.0 (Ohm), respectively, and a residual flux of 0.75 (p.u.). The inrush waveform will reach its peak during saturation close to when the sinusoidal term peaks. This assumption is valid for two reasons; first, the exponential term coefficient is fractional as compared to the sinusoidal term amplitude since and. Second, the saturation time constant,, is small as increases which will introduce a small shift in the peak current to appear slightly before the sinusoidal peak value. The saturation current is small as compared to the inrush peak and can be neglected. Accordingly, the peak time and the peak inrush current as function of can be expressed as follows: The analytical and simulation curves for the MVA transformer described in [1] during first phase switching are shown in Fig. 5. B. Neutral Resistor Sizing Based on (3), it is now possible to select a neutral resistor size that can achieve a specific inrush current reduction ratio given by (3) (4) For the maximum inrush current condition, the total energized phase ratio including system impedance is high and accordingly, the damping of the exponential term in (5) during the first cycle can be neglected Typical saturation and residual flux magnitudes for power transformers are in the range and Accordingly, switching at voltage zero instant with a polarity that matches the maximum possible residual flux, the saturation angle w.r.t. instant of switching and are within the following ranges, respectively (7) (8) (9) High values leading to considerable inrush reduction will result in low ratios. It is clear from (6) and (8) that ratios equal to or less than 1 ensure negative dc component factor and hence the exponential term shown in (5) can be conservatively neglected. Accordingly, (5) can be rewritten as follows: (10) Using (7) and (10) to evaluate (4), the neutral resistor size which corresponds to a specific reduction ratio can be given by (11)

4 ABDULSALAM AND XU: A SEQUENTIAL PHASE ENERGIZATION METHOD 211 Equations (9) and (11) reveal that transformers with less severe saturation characteristics high saturation flux and low maximum residual flux values require a higher neutral resistor value to achieve the desired inrush current reduction rate. Based on (9) and (11), the inrush current reduction of 90% can be achieved within the range of (12) Based on (12), a small resistor less than 10 times the saturation series reactance can achieve more than 90% reduction in inrush current. The amount of reduction in flux during the first cycle can be found from (2) as follows: where Fig. 6. Simulation of the MVA, Yg-Y transformer [10], during second phase switching for R = 150:0 (Ohm). (13) function of the primary phase voltage can be given by and the neutral voltage Within the optimum neutral resistor value defined by (12), the total flux reduction during first phase switching is within (14) As the second cycle starts, an initial flux level of will exist. This results in the absence of inrush current after the first cycle since the maximum flux is close to or below the saturation flux. IV. SECOND PHASE SWITCHING Transformer behavior during second phase switching was observed through simulation and experiments to vary with respect to connection and core structure type. However, a general behavior trend exists within low neutral resistor values where the scheme can effectively limit inrush current magnitude. For cases with delta winding or multi-limb core structure, the second phase inrush current is lower than that during first phase switching. Single phase units connected in Yg Y have a different performance as both first and second stage inrush currents has almost the same magnitude until a maximum reduction rate of about 80% is achieved. Generally, based on the well-known saturation characteristics of power transformers, any reduction in inrush current is a result of limiting the maximum flux that can build up in the core. In this section, the performance of the proposed inrush mitigation scheme during second stage switching will be qualitatively analyzed and compared to the first switching stage for small values of. It will be shown that the transformer saturation level during second phase switching is less than that during first phase switching. A. Three Single Phase Units Connected in Yg Y For this condition, the transformer can be modeled using two saturable inductor circuits representing each phase. The coupling between both switched phases is introduced only through the neutral resistor. For any energized phase, the flux as (15) Phase B will start operating in the unsaturated region with its own residual flux. As a result, both phase currents will be low and the neutral voltage remains close to zero,. As soon as Phase B reaches saturation, its current will increase and the neutral voltage will start to build up. The neutral current will be mainly due to the contribution of phase B. Hence, the neutral resistor can be assumed to be in series with phase B and a similar inrush reduction performance, to that of first phase switching, will hold. The process will continue until the neutral voltage integral amount of reduction becomes sufficient to drive Phase A into saturation. With phase A originally in steady state, a disturbance in flux equal to the difference between the rated and saturation flux values is required for phase A to reach saturation. Conservatively assuming that the reduction in flux in Phase B results in an increase of the same amount in phase A, it will be possible to increase to achieve at least 20 to 35% reduction in its flux before disturbing phase A, Fig. 6. As is increased further, more inrush current reduction can be achieved in phase B until both phases reach the same saturation level for a specific value of. As the difference between saturation and rated flux values increases, more reduction in phase B current can be achieved. The same conditions apply during third switching stage. B. Transformers With Delta Winding and/or 3-Limb Structures The performance during sequential switching for this type will be quite different than for single phase,, banks transformers due to the following reasons: dynamic flux will exist in un-energized phases; inrush current can exist in one phase due to external saturation in un-energized phase (return path of the flux). The existence of dynamic flux in un-energized phases will make the initial flux in the switched phase dependent on the instant of switching. In order to maximize the flux of the switched

5 212 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 Fig. 7. Simulation of the 30 kva transformer during second phase switching condition showing the phase fluxes and effect of delta winding current for small values of R =0:1 (Ohm). phase and consequently represent highest saturation condition, the critical switching instant should be found. The flux in phase B after switching can be calculated as follows: Fig. 8. Modeling the delta winding during the saturation condition of phase C. instant of switching The maximum theoretical flux that can be reached in phase B can accordingly be given by For the maximum flux condition and (16) The switching angle of on phase B voltage waveform corresponds to a zero initial flux value in phase A and, as a result, no initial flux exists when the second phase is energized. This finding is of importance since it proves that the maximum theoretical saturation level during second phase energization will be lower than that during the energization of the first phase which equals. Immediately after 30 of the switching instant, the fluxes in phases A and B are both positive and determined by the terminal voltage integral of both phases. This will lead phase C which represents the return path of both fluxes to saturate first. As shown in Figs. 7 and 8, the saturation of phase C will drive a delta winding current equal to the magnetizing current of phase C under saturation. The induced delta winding current will be reflected as zero sequence current of the same magnitude flowing through phases A and B and a neutral current equal to twice the delta current. For phase B, both integrals of the terminal and the neutral voltages have the same polarity and hence the delta winding will help reducing saturation level further in phase B. For phase A, the supply voltage waveform will have opposite polarity to the neutral voltage, however, due to the difference between the saturation and rated flux values, the disturbance in phase A will be less than that observed in switched phase B. In case of multi limb transformers with no delta winding, the second and third switching stages behavior depends on the number of core limbs. For 3-Limb transformers, the flux in the two energized limbs will add up into the third limb. As the third limb saturates, the return flux path of phase A and B will experience saturation and as a result a neutral current equals twice the phase current will flow. This will result in a similar effect to that from a delta winding. On the other hand, for transformers with 4 or 5 limbs, and shell form cores, the return path of the flux from phases A and B will be unsaturated to some degree and the performance of the scheme will be similar to that of three single phase units connected in Yg Y. V. NEUTRAL VOLTAGE RISE: STANDARD REQUIREMENTS AND MITIGATION TECHNIQUES From simulation studies carried out on various transformer types and connections, it was found that the peak neutral voltage will reach values up to 1 (p.u.) rapidly as the neutral resistor value is increased. Typical neutral voltage peak profile against neutral resistor size is shown in Fig. 9 for the MVA transformer during 1st and 2nd phase switching. The scheme performance during the complete switching sequence is shown in Fig. 10 with optimum neutral resistor of 50. A delay of one second between each switching stage is

6 ABDULSALAM AND XU: A SEQUENTIAL PHASE ENERGIZATION METHOD 213 Fig. 9. Neutral voltage peak as a function of R switching stages for the MVA transformer. during the first and second Fig. 11. I (R )=I (0) percentage inrush current peak for different arrester saturation voltages R = 50 (). Fig. 10. Phase currents, neutral current and neutral voltage during complete switching sequence for the 132.8, 72/13.8 kv, Yg-D transformer R =50(). required to allow phase fluxes to lose most of the dc component. The neutral voltage during the first cycle will reach 85% of the rated phase voltage. Quickly after the first cycle, the transformer is unsaturated and the neutral voltage is negligible since. The unsaturated magnetizing reactance is about 900 times the saturation reactance of a transformer, [11]. Accordingly, with the transformer operating in unsaturated mode, the neutral resistor voltage is negligible. Within the optimum resistor value, the neutral voltage peak is less than 0.5 (p.u.) during second phase energization. As soon as the third phase is switched in, the neutral voltage will remain close to zero. It is a common industry practice to grade the insulation over the Yg winding for solidly grounded transformers [11] [14]. This can introduce limitations to the applicability of the proposed scheme at high voltage levels. The following section addresses the standard requirements and limitations for the application of the proposed scheme to both dry-type and liquid immersed transformers. A. IEEE Standards Requirements A review of the IEEE/ANSI standards [12] [14] has been carried out in order to evaluate the acceptable neutral voltage rise limit on different power transformer types. The main application of the proposed scheme is the generator s step up transformers for IPP Independent Power Producer which are interconnected to the system at the distribution or sub transmission levels. The interconnection transformer is preferably Wyegrounded on the system side and Delta connected on the generator side [15], [16]. According to [12], the minimum low fre- quency insulation level at neutral for liquid immersed transformers at system voltages of 25 kv or below is 10 kv but not less than the nominal line voltage. In this case, the proposed scheme can be applied without modification for this type at interconnection levels of 25 kv or below. For voltages higher than 25 kv and up to 69 kv, the neutral voltage rise need to be limited to 50% of the nominal line voltage in order to comply with the insulation requirement at neutral, [12]. In case of dry type transformers, the minimum insulation level at neutral should be at least 4 kv at system voltages of 1.2 kv and extends to 10 kv at higher voltage levels. If the transformer is designed for ungrounded Y connection, the neutral insulation level should be the same as the line terminal level [13]. B. Neutral Resistor With Neutral Voltage Limiting Arrester Arrester(s) connected in parallel with the neutral resistor could limit the neutral voltage rise to the standard level. Actually, the resistor-arrester arrangement presents a nonlinear resistor saturating at the arrester s saturation voltage. According to (15), limiting the neutral voltage rise will reduce the neutral voltage integral and hence, reduce the technique s efficiency. Limiting the neutral voltage rise to 0.5 (p.u.) will have effect only during first phase switching, Figs. 9 and 10 which is more desirable in order to limit the energy dissipated through the arrester. The curves of the arrester-neutral resistor arrangement is shown in Fig. 11 for the MVA transformer. A similar deduction procedure to the one presented in section III leads to the following inrush expression: (17) Accordingly, the peak inrush current during arrester operation can be expressed as (18) From (18), the amount of reduction in current will depend on how fast the arrester will become saturated,. However, since the neutral voltage will start rising after the transformer

7 214 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 Fig. 12. Phase currents, neutral current, and neutral voltage during complete switching sequence R =50(). Arrester saturation voltage is 0.5 (p.u.). Fig. 14. Accumulated energy during different switching stages. Results for the MVA transformer with infinite system. sorbed by the neutral resistor during the complete switching sequence for the MVA transformer for the case shown in Fig. 10. It is clear from Figs. 14 and 10 that negligible neutral voltage will exist after the first cycle of the 1st phase energization and the energy dissipated through the resistor can accordingly be calculated as follows: Fig. 13. Phase currents, fluxes, neutral current and neutral voltage during complete switching sequence for the MVA with 1000 MVAsc system. saturates at, the neutral voltage integral will have a maximum limit as the arrester saturation time approaches. This clarifies the almost steady profile of the inrush current as increases shown in Fig. 11. The resistor-arrester arrangement performance during complete switching sequence is shown in Fig. 12. The results shown in Figs. 10 and 12 were obtained assuming an infinite system bus. The scheme performance with 1000 MVA short circuit impedance, assuming 10% of this impedance to be resistive is shown in Fig. 13. It is shown that inrush current reduction to less than 3 times the nominal current can be achieved considering a relatively small source impedance and at the same time limiting the neutral voltage to 0.5 (p.u.). In addition, the scheme will have much better performance with regards to the settling time of inrush currents. C. Energy Requirements Simulation studies can provide an accurate calculation of energy requirement level for the scheme. In this section, approximate formulas will be given for a quick but accurate estimate of the energy withstand capability for both the resistor and the resistor-arrester arrangements. As mentioned earlier, there will be negligible neutral voltage across the resistor after the third phase switching. Accordingly, our focus will be on the assessment of energy requirements during first and second phase switching stages. Fig. 14 shows the accumulated energy ab- (19) For the second phase, as can be seen from Figs. 6 and 7, the neutral current can be presented using two sinusoidal half-waves of twice the frequency. Since the neutral voltage rise during second phase is around 0.5 (p.u.) with the same neutral resistor, the energy during 60-cycle period of the second phase switching can be calculated as follows: (20) As can be seen from (20), most of the energy absorbed by the grounding resistor will be during second phase switching. After the third phase is switched in, the neutral current will be very close to zero and energy dissipation through the resistor can be neglected. For the resistor-arrester arrangement, the arrester will be active only during the first cycle of the first switching stage. As shown in (17) the total current through the switched phase will be composed of a dc component through the resistor and an ac component through the arrester. Accordingly, the energy dissipated through the resistor and the arrestor can be calculated, respectively, as follows: (21)

8 ABDULSALAM AND XU: A SEQUENTIAL PHASE ENERGIZATION METHOD 215 Fig. 15. Accumulated energy during different switching stages (J). Arrester set at 0.5 (p.u.) saturation voltage with the 1000 MVAsc system. Fig. 16. Voltage at the primary side of a 22/0.48, 160 kva, Y-D transformer due to energizing Phase A. Top: isolated neutral. Bottom: neutral grounding. VII. CONCLUSIONS (22) The arrester will not be active for saturation voltages of 0.5 (p.u.) or higher within the optimal neutral resistor value. The neutral resistor energy is the same as that of the original scheme during second switching stage for the same. As shown in Fig. 15, the total energy absorbed by the resistor during all switching stages is about 1.30 MJ, and 250 kj for the surge arrester(s). Neutral grounding resistors capable of handling A root mean square (rms) continuous current for 10 s at voltage levels of 33 kv or more are commercially available today. Arresters can handle less energy dissipation (absorption) than resistors. This is due to the fact that they are originally designed for short period operation duration. However, a way of stacking a number of arresters in parallel in order to handle a higher energy rating has been suggested in [17]. Typical energy capability for arrester class up to 48 kv is 4 to 4.9 kj/kv [11] and [17] [19]. VI. CONSIDERATIONS ON FERRORESONANCE The proposed sequential energization scheme could expose a transformer to ferroresonance. Fortunately, the neutral resistor is in series of the resonant circuit and will provide sufficient damping to prevent ferroresonance from happening. In fact, [20] proposed the idea of using a neutral resistor to mitigate ferroresonance. Based on numerous TNA studies, [20] found that a neutral resistor less than 0.05 is sufficient to prevent the occurrence of ferroresonance in Yg D transformer banks. Based on the finding, we can conclude that the proposed scheme will not experience ferroresonance problem. Our simulation studies on 22/0.48 kv, 4.5%, 160 kva, Y D transformer, also confirmed this conclusion. Fig. 16 shows the voltage waveforms at the energizing side of the transformer due to energizing phase A. It is clear that using the optimal resistor successfully damped the overvoltage at un-energized phases B and C within one cycle. This paper presented an improved and more complete design criterion for a novel transformer inrush current reduction scheme. It was shown that a small neutral resistor size of less than ten times the transformer series saturation reactance can achieve 80 90% reduction in inrush currents among the three phases. The transient performance of the scheme was presented and it was demonstrated through detailed analysis that the first phase switching leads to the highest inrush current level. The paper has also addressed the main practical limitation of the scheme as the permissible rise of neutral voltage. A feasible application range for both dry type and liquid immersed transformer has been proposed and the use of surge arresters to extend the application range of the scheme has also been presented. Formulas were also given to estimate the required energy withstand capability for both the neutral resistor and the arrestor if applicable. REFERENCES [1] Y. Cui, S. G. Abdulsalam, S. Chen, and W. Xu, A sequential phase energization method for transformer inrush current reduction part I: Simulation and experimental results, IEEE Trans. Power Del., vol. 20, no. 2, pt. 1, pp , Apr [2] W. Xu, S. G. Abdulsalam, Y. Cui, S. Liu, and X. Liu, A sequential phase energization method for transformer inrush current reduction part II: Theoretical analysis and design guide, IEEE Trans. Power Del., vol. 20, no. 2, pt. 1, pp , Apr [3] A. Boyajian, Mathematical analysis of nonlinear circuits, General Electric Rev., pp , , Sep. and Dec [4] Westinghouse Electric Corporation, Electric Transmission and Distribution Reference Book, 4th ed. East Pittsburgh, PA, [5] S. G. Abdulsalam and W. Xu, Analytical study of transformer inrush currents and its applications, in Proc. Int. Conf. Power System Transients, Montreal, QC, Canada, [6] B. Holmgrem, R. S. Jenkins, and J. Riubrugent, Transformer inrush current CIGRE paper 12-03, CIGRE. Paris, France, pp. 1-13, [7] H. A. Peterson, Transients in Power Systems. New York: General Publishing Co., General Electric, [8] L. F. Blume, G. Camilli, S. B. Farnham, and H. A. Peterson, Transformer magnetizing inrush currents and influence on system operation, AIEE Trans. Power App. Syst., vol. 63, pp , Jan [9] P. C. Y. Ling and A. Basak, Investigation of magnetizing inrush current in a single-phase transformer, IEEE Trans. Magn., vol. 24, no. 6, pp , Nov

9 216 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 [10] X. Chen, Negative inductance and numerical instability of the saturable transformer component in EMTP, IEEE Trans. Power Del., vol. 15, no. 4, pp , Oct [11] A. Greenwood, Electrical Transients in Power Systems, 2nd ed. New York: Wiley, [12] IEEE Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers, IEEE Std. C , 2000, pp [13] IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers Including Those With Solid Cast and/or Resin- Encapsulated Windings, IEEE Std. C , Dec. 31, [14] IEEE standard requirements, terminology, and test procedure for neutral grounding devices, ANSI/IEEE Std , [15] British Columbia Transmission Corporation, 69 kv to 500 kv interconnection requirements for power generators, May [16] BC Hydro, 35 kv and below interconnection requirements for power generators, Jun [17] J. J. Lee and M. S. Cooper, High-energy solid-state electrical surge arrestor, IEEE Trans. Parts, Hybrids Packag., vol. PHP-13, no. 4, pp , Dec [18] M. L. B. Martinez and L. C. Zanetta, Jr., A proposal to evaluate the energy withstand capacity of metal oxide resistors, in Proc. 11th Int. Symp. High Voltage Engineering, Aug , 1999, vol. 2, pp [19] M. Martinez and L. Zanetta, On modeling and testing metal oxide resistors to evaluate the arrester withstanding energy, presented at the IEEE Dielectr. Mater., Meas. Appl. Conf., 2000, Publ. No [20] R. H. Hopkinson, Ferroresonant overvoltage control based on TNA tests on three-phase wye-delta transformer banks, IEEE Trans. Power App. Syst., vol. PAS-87, no. 2, pp , Feb Sami G. Abdulsalam (S 03) received the B.Sc. and M.Sc. degrees in electrical engineering from El-Mansoura University, El-Mansoura, Egypt, in 1997 and 2001, respectively. He is currently pursuing the Ph.D. degree in electrical and computer engineering from the University of Alberta, Edmonton, AB, Canada. Currently, he is with the Enppi Engineering Company, Cairo, Egypt. His research interests are in electromagnetic transients in power systems and power quality. Wilsun Xu (M 90 SM 95 F 05) received the Ph.D. degree from the University of British Columbia, Vancouver, BC, Canada, in He was an Engineer with BC Hydro, Burnaby, BC, Canada, from 1990 to Currently, he is a Professor with the University of Alberta, Edmonton, AB, Canada, and a Changjiang Professor of Shangdong University, Shangdong, China. His research interests are power quality and harmonics.

ANEW, simple and low cost scheme to reduce transformer

ANEW, simple and low cost scheme to reduce transformer 950 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 A Sequential Phase Energization Technique for Transformer Inrush Current Reduction Part II: Theoretical Analysis and Design Guide Wilsun

More information

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

Three-Phase/Six-Phase Conversion Autotransformers

Three-Phase/Six-Phase Conversion Autotransformers 1554 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER 2003 Three-Phase/Six-Phase Conversion Autotransformers Xusheng Chen, Member, IEEE Abstract The first commercial demonstration of six-phase

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher

More information

HARMONIC distortions can have significant adverse

HARMONIC distortions can have significant adverse 1710 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 3, JULY 2009 An Investigation on the Selection of Filter Topologies for Passive Filter Applications Alexandre B. Nassif, Student Member, IEEE, Wilsun

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

A Resonant Tertiary Winding-Based Novel Air-Core Transformer Concept Pooya Bagheri, Wilsun Xu, Fellow, IEEE, and Walmir Freitas, Member, IEEE

A Resonant Tertiary Winding-Based Novel Air-Core Transformer Concept Pooya Bagheri, Wilsun Xu, Fellow, IEEE, and Walmir Freitas, Member, IEEE IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012 1519 A Resonant Tertiary Winding-Based Novel Air-Core Transformer Concept Pooya Bagheri, Wilsun Xu, Fellow, IEEE, and Walmir Freitas, Member,

More information

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute

More information

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation

More information

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 22, NO. 4, NOVEMBER

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 22, NO. 4, NOVEMBER TRANSACTIONS ON POWER SYSTEMS, VOL. 22, NO. 4, NOVEMBER 2007 1 A Harmonically Coupled Admittance Matrix Model for AC/DC Converters Yuanyuan Sun, Guibin Zhang, Wilsun Xu, Fellow,, Julio G. Mayordomo, Member,

More information

160 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 1, JANUARY /$ IEEE

160 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 1, JANUARY /$ IEEE 160 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 1, JANUARY 2009 Dual Three-Winding Transformer Equivalent Circuit Matching Leakage Measurements Francisco de León, Senior Member, IEEE, and Juan A.

More information

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices M. Sanaye-Pasand, R. Aghazadeh Applied Electromagnetics Research Excellence Center, Electrical & Computer Engineering

More information

Improving Passive Filter Compensation Performance With Active Techniques

Improving Passive Filter Compensation Performance With Active Techniques IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan

More information

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy W. Piasecki, M. Stosur, T. Kuczek, M. Kuniewski, R. Javora Abstract-- Evaluation

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

VOLTAGE sag and interruption are the most important

VOLTAGE sag and interruption are the most important 806 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 2, MAY 2005 Voltage Sag State Estimation for Power Distribution Systems Bin Wang, Wilsun Xu, Senior Member, IEEE, and Zhencun Pan Abstract The increased

More information

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus 1592 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus Ahmed Faheem Zobaa, Senior Member, IEEE Abstract A

More information

A NOVEL METHOD FOR ENERGIZING TRANSFORMERS FOR REDUCING INRUSH CURRENTS

A NOVEL METHOD FOR ENERGIZING TRANSFORMERS FOR REDUCING INRUSH CURRENTS A OVEL METHOD FOR EERGIZIG TRASFORMERS FOR REDUCIG IRUSH CURRETS M.B.B. Sharifian, Farhad Shahnia, Ali Shasvand 3, Iraj hasanzadeh 4,3,4 Faculty of Electrical and Computer Engineering, University of Tabriz,

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

MATHEMATICAL MODELING OF POWER TRANSFORMERS

MATHEMATICAL MODELING OF POWER TRANSFORMERS MATHEMATICAL MODELING OF POWER TRANSFORMERS Mostafa S. NOAH Adel A. SHALTOUT Shaker Consultancy Group, Cairo University, Egypt Cairo, +545, mostafanoah88@gmail.com Abstract Single-phase and three-phase

More information

Methodology Utilized in Black-Start Studies on EHV Power Networks

Methodology Utilized in Black-Start Studies on EHV Power Networks Methodology Utilized in Black-Start Studies on EHV Power Networks C. Saldaña / G. Calzolari Av. Millán 4016 - Montevideo 11700 - Uruguay gracclau@adinet.com.uy Abstract - This article presents the methodology

More information

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL 2011 799 Practical Power Quality Charts for Motor Starting Assessment Xiaoyu Wang, Member, IEEE, Jing Yong, Member, IEEE, Wilsun Xu, Fellow, IEEE,

More information

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events Transformer Thermal Impact Assessment White Paper TPL-007-2 Transmission System Planned Performance for Geomagnetic Disturbance Events Background Proposed TPL 007 2 includes requirements for entities to

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system

More information

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 969 Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies Taku Noda, Member, IEEE, Hiroshi Nakamoto,

More information

Energization of a no-load transformer for power restoration purposes: Impact of the sensitivity to parameters.

Energization of a no-load transformer for power restoration purposes: Impact of the sensitivity to parameters. Energization of a no-load transformer for power restoration purposes: Impact of the sensitivity to parameters. Michel Rioual, Senior Member, IEEE Christophe Sicre EDF / R&D Division ALTRAN TECHNOLOGIES

More information

TO LIMIT degradation in power quality caused by nonlinear

TO LIMIT degradation in power quality caused by nonlinear 1152 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 6, NOVEMBER 1998 Optimal Current Programming in Three-Phase High-Power-Factor Rectifier Based on Two Boost Converters Predrag Pejović, Member,

More information

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies T.G. Martinich, M. Nagpal, A. Bimbhra Abstract-- Technological advancements in high-power

More information

Long lasting transients in power filter circuits

Long lasting transients in power filter circuits Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.

More information

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS Seminar / Workshop on Controlled Switching Possible Benefits for Transformers Applications PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS Esteban Portales Yvon Filion André Mercier

More information

AS the power distribution networks become more and more

AS the power distribution networks become more and more IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 1, FEBRUARY 2006 153 A Unified Three-Phase Transformer Model for Distribution Load Flow Calculations Peng Xiao, Student Member, IEEE, David C. Yu, Member,

More information

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System M.S.B Subrahmanyam 1 T.Swamy Das 2 1 PG Scholar (EEE), RK College of Engineering, Kethanakonda,

More information

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 569 Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System Li-Ming Zhou, Senior Member, IEEE,

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer

Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer C.GOPI*, M.KISHOR** *(Department. of Electrical and Electronics Engineering, SVPCET, Puttur)

More information

The study of ferroresonance effects in electric power equipment

The study of ferroresonance effects in electric power equipment O.A. Ezechukwu, J.O. Ikelionwu / Journal of Engineering and Applied Sciences 6 () 7-77 Journal of Engineering and Applied Sciences 6 () 7-77 JOURNAL OF ENGINEERING AND APPLIED SCIENCES The study of ferroresonance

More information

SERIES ACTIVE power filters have proved to be an interesting

SERIES ACTIVE power filters have proved to be an interesting 928 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 5, SEPTEMBER 1999 A Fault Protection Scheme for Series Active Power Filters Luis A. Morán, Senior Member, IEEE, Ivar Pastorini, Juan Dixon, Senior

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

AFTER an overhead distribution feeder is de-energized for

AFTER an overhead distribution feeder is de-energized for 1902 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 A New Technique to Detect Faults in De-Energized Distribution Feeders Part II: Symmetrical Fault Detection Xun Long, Student Member,

More information

The Fault Level Reduction in Distribution System Using an Active Type SFCL

The Fault Level Reduction in Distribution System Using an Active Type SFCL www.ijecs.in International Journal Of Engineering And Computer Science ISSN: 2319-7242 Volume 5 Issues 8 Aug 2016, Page No. 17392-17396 The Fault Level Reduction in Distribution System Using an Active

More information

In power system, transients have bad impact on its

In power system, transients have bad impact on its Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014

More information

EMERGING distributed generation technologies make it

EMERGING distributed generation technologies make it IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005 1757 Fault Analysis on Distribution Feeders With Distributed Generators Mesut E. Baran, Member, IEEE, and Ismail El-Markaby, Student Member,

More information

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers International Conference on Power System Transients IPST 23 in New Orleans, USA Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

More information

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Switching and Fault Transient Analysis of 765 kv Transmission Systems Third International Conference on Power Systems, Kharagpur, INDIA December >Paper #< Switching and Transient Analysis of 6 kv Transmission Systems D Thukaram, SM IEEE, K Ravishankar, Rajendra Kumar A Department

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of Hz zero sequence continuous voltage S. Nishiwaki, T. Nakamura, Y.Miyazaki Abstract When an one line grounding fault in a transmission

More information

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 21, NO. 1, JANUARY

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 21, NO. 1, JANUARY IEEE TRANSACTIONS ON POWER ELECTRONICS, OL. 21, NO. 1, JANUARY 2006 73 Maximum Power Tracking of Piezoelectric Transformer H Converters Under Load ariations Shmuel (Sam) Ben-Yaakov, Member, IEEE, and Simon

More information

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit Validation of a Power Transformer Model for Ferroresonance with System Tests on a 4 kv Circuit Charalambos Charalambous 1, Z.D. Wang 1, Jie Li 1, Mark Osborne 2 and Paul Jarman 2 Abstract-- National Grid

More information

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by

More information

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation)

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation) Transformer Thermal Impact Assessment White Paper Project 2013-03 (Geomagnetic Disturbance Mitigation) TPL-007-1 Transmission System Planned Performance for Geomagnetic Disturbance Events Background On

More information

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events Transformer Thermal Impact Assessment White Paper TPL-007-2 Transmission System Planned Performance for Geomagnetic Disturbance Events Background Proposed TPL-007-2 includes requirements for entities to

More information

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:

More information

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Modeling Ferroresonance Phenomena on Voltage Transformer (VT) Modeling Ferroresonance Phenomena on Voltage Transformer (VT) Mohammad Tolou Askari Department of Electrical Faculty of Engineering Universiti Putra Malaysia 43400 UPM Serdang, Selangor, Malaysia Abstract

More information

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee

More information

Pre-insertion Resistor of Switching Shunt Capacitor Banks

Pre-insertion Resistor of Switching Shunt Capacitor Banks Pre-insertion Resistor of Switching Shunt Capacitor Banks Tien-Ting Chang Wei-Hsiang Chen Department of Electrical Engineering Department of Electrical Engineering National Chin-Yi University of Technology

More information

Innovative Science and Technology Publications

Innovative Science and Technology Publications Innovative Science and Technology Publications Manuscript Title SATURATION ANALYSIS ON CURRENT TRANSFORMER Thilepa R 1, Yogaraj J 2, Vinoth kumar C S 3, Santhosh P K 4, 1 Department of Electrical and Electronics

More information

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer Ms. Kanchan S.Patil PG, Student kanchanpatil2893@gmail.com Prof.Ajit P. Chaudhari Associate Professor ajitpc73@rediffmail.com

More information

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM G.SUNDAR, S.RAMAREDDY Research Scholar, Bharath University Chenna Professor Jerusalam College of Engg. Chennai ABSTRACT This paper deals with simulation

More information

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN A novel control strategy for Mitigation of Inrush currents in Load Transformers using Series Voltage source Converter Pulijala Pandu Ranga Rao *1, VenuGopal Reddy Bodha *2 #1 PG student, Power Electronics

More information

Demagnetization of Power Transformers Following a DC Resistance Testing

Demagnetization of Power Transformers Following a DC Resistance Testing Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.

More information

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems December 2010/AT301 by Reza Tajali, P.E. Square D Power Systems Engineering Make the most of your energy SM Revision

More information

RECENTLY, the harmonics current in a power grid can

RECENTLY, the harmonics current in a power grid can IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 2, MARCH 2008 715 A Novel Three-Phase PFC Rectifier Using a Harmonic Current Injection Method Jun-Ichi Itoh, Member, IEEE, and Itsuki Ashida Abstract

More information

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System Engr.Kavitha Vasantha 1 Lecturer, BSIE, College of Engineering, Salmabad, Kingdom of Bahrain 1 Abstract: As end

More information

Direct Harmonic Analysis of the Voltage Source Converter

Direct Harmonic Analysis of the Voltage Source Converter 1034 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003 Direct Harmonic Analysis of the Voltage Source Converter Peter W. Lehn, Member, IEEE Abstract An analytic technique is presented for

More information

Parameter Study of Ferro-Resonance with Harmonic Balance Method

Parameter Study of Ferro-Resonance with Harmonic Balance Method Parameter Study of Ferro-Resonance with Harmonic Balance Method ALI ERBAY Degree project in Electric Power Systems Second Level, Stockholm, Sweden 2012 XR-EE-ES 2012:010 PARAMETER STUDY OF FERRO RESONANCE

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Assessment of the Impact of GMD on the TVA 500 kv Grid & Power Transformers Part II:

More information

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation)

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation) Transformer Thermal Impact Assessment White Paper (Draft) Project 2013-03 (Geomagnetic Disturbance Mitigation) TPL-007-1 Transmission System Planned Performance during Geomagnetic Disturbances Background

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

Voltage and Current Waveforms Enhancement using Harmonic Filters

Voltage and Current Waveforms Enhancement using Harmonic Filters Voltage and Current Waveforms Enhancement using Harmonic Filters Rajeb Ibsaim rabsaim@yahoo.com, Azzawia University, Libya Amer Daeri ibnjubair1@yahoo.co.uk Azzawia University, Libya Abstract The demand

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS 24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 97 RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS Pengfei WEI Yonghai XU Yapen WU Chenyi

More information

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Abstract: A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Vijay Bendre, Prof. Pat Bodger, Dr. Alan Wood. Department of Electrical and Computer Engineering, The University of

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

More information

Ferroresonance on Transformer 13-kV Ungrounded Tertiary at Arab

Ferroresonance on Transformer 13-kV Ungrounded Tertiary at Arab Ferroresonance on Transformer 13-k Ungrounded Tertiary at Arab Gary L. Kobet, P.E. Tennessee alley Authority In October 1997, at TA s Arab AL 161k Substation, a distributor built a 13k switchyard to load

More information

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT * Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM

More information

TOROIDAL transformers for low-frequency applications

TOROIDAL transformers for low-frequency applications 6776 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 10, OCTOBER 2016 Letters Reduction of Inrush Currents in Toroidal Transformers by Sector Winding Design Saeed Jazebi, Member, IEEE, Rasim Doğan,

More information

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS A.Raghu Ram 1, P.Swaraj 2 1,2 Associate Professor, PG Scholar, Department of Electrical and Electronics Engineering, JNTUH

More information

Evaluating the Response of Surge Arresters

Evaluating the Response of Surge Arresters 1 Jens Schoene Chandra Pallem Tom McDermott Reigh Walling Evaluating the Response of Surge Arresters to Temporary Overvoltages Panel Session of the IEEE Wind and Solar Collector Design Working Group 2014

More information

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM Dolly Chouhan 1, Kasongo Hyacinthe Kapumpa 2, Ajay Chouhan 3 1 M. Tech. Scholar, 2

More information

Abstract- At the time of transformer energization, a high current will be drawn by the transformer. The mentioned current

Abstract- At the time of transformer energization, a high current will be drawn by the transformer. The mentioned current A Case Study of Reduction of Single-Phase Transformer Magnetizing Inrush Current Kunal Wakode 1,Shaikh Sabir 2, Nishant Adhau 3, Abuzar Khan 4, Prof. P. B. Shelke 5 Department of Electrical Engineering

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

PWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS

PWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS PWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS Copyright Material IEEE Paper No. PCIC Paul Buddingh, P.Eng. MEMBER, IEEE ANDRITZ AUTOMATION Ltd. 13700 International Place, Suite 100 Richmond, BC

More information

IN THE high power isolated dc/dc applications, full bridge

IN THE high power isolated dc/dc applications, full bridge 354 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 21, NO. 2, MARCH 2006 A Novel Zero-Current-Transition Full Bridge DC/DC Converter Junming Zhang, Xiaogao Xie, Xinke Wu, Guoliang Wu, and Zhaoming Qian,

More information

ATYPICAL high-power gate-turn-off (GTO) currentsource

ATYPICAL high-power gate-turn-off (GTO) currentsource 1278 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 6, NOVEMBER/DECEMBER 1998 A Novel Power Factor Control Scheme for High-Power GTO Current-Source Converter Yuan Xiao, Bin Wu, Member, IEEE,

More information

Beyond the Knee Point: A Practical Guide to CT Saturation

Beyond the Knee Point: A Practical Guide to CT Saturation Beyond the Knee Point: A Practical Guide to CT Saturation Ariana Hargrave, Michael J. Thompson, and Brad Heilman, Schweitzer Engineering Laboratories, Inc. Abstract Current transformer (CT) saturation,

More information

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779.

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779. Transformer Thermal Impact Assessment White Paper Project 2013-03 (Geomagnetic Disturbance Mitigation) TPL-007-12 Transmission System Planned Performance for Geomagnetic Disturbance Events Background On

More information

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org

More information

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC 1 A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC Ramsis Girgis, Kiran Vedante, and Gary Burden ABB Power Transformers Abstract: There has been

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018 Electrical Theory Power Principles and Phase Angle PJM State & Member Training Dept. PJM 2018 Objectives At the end of this presentation the learner will be able to: Identify the characteristics of Sine

More information

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation

More information

HARMONIC contamination, due to the increment of nonlinear

HARMONIC contamination, due to the increment of nonlinear 612 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 44, NO. 5, OCTOBER 1997 A Series Active Power Filter Based on a Sinusoidal Current-Controlled Voltage-Source Inverter Juan W. Dixon, Senior Member,

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

ARC FLASH HAZARD ANALYSIS AND MITIGATION

ARC FLASH HAZARD ANALYSIS AND MITIGATION ARC FLASH HAZARD ANALYSIS AND MITIGATION J.C. Das IEEE PRESS SERIES 0N POWER ENGINEERING Mohamed E. El-Hawary, Series Editor IEEE IEEE PRESS WILEY A JOHN WILEY & SONS, INC., PUBLICATION CONTENTS Foreword

More information