DGS Phase 1 COORDINATION DRAWINGS

Size: px
Start display at page:

Download "DGS Phase 1 COORDINATION DRAWINGS"

Transcription

1 SECTION COORDINATION DRAWINGS PART 1 - GENERAL 1.1 STIPULATIONS A. The specifications sections " General Conditions of the Construction Contract ", "Special Conditions", and "Division 1 - General Requirements" form a part of this Section by this reference thereto, and shall have the same force and effect as if printed herewith in full. B. This specification section supersedes the requirements in the "General Conditions of the Construction Contract "; where inconsistencies and/or conflicts occur, the requirements of this section shall prevail. 1.2 SUMMARY A. Where space for installation of essential building services is limited, and to avoid conflicts among the building trades, it is necessary for the Prime Contractors to coordinate the use of shared space, and prepare Coordination Drawings, before commencing the Work. All Prime Contractors and their associated subcontractors, during the coordination process, shall harmoniously plan and/or adjust the location of items as necessary, to avoid such conflicts and to ensure future access to critical items of equipment. All Prime Contractors shall also coordinate the installation sequence as necessary. B. Coordination of the Work, and production of Coordination Drawings, are contractual obligations of all Prime Contractors. The Department will not compensate any Prime Contractor for conflicts arising during installation, should they be the result of improper coordination between Prime Contractors. Nor will the Department extend the Contract duration, due to delays caused by improper coordination. Each Contractor shall be solely responsible to recover any and all construction time lost as a result of such delays. C. In the General Conditions of the Construction Contract, Article 9.5 Coordination Drawings, Section D states that the HVAC Contractor (.2) will be the Lead Contractor for the purposes of the Coordination Drawings and shall facilitate the Coordination Drawing Process between Prime Contractors. 1.3 SUBMITTALS A. Time of submission of Coordination Drawings shall be determined at the initial job conference, and shall be included as a milestone on the Construction Schedule. The HVAC Construction (.2) Contractor shall initiate this action and acquire the necessary dates from the other Prime Contractors as part of their overall scheduling responsibilities. B. All Prime Contractors shall jointly develop and submit dimensioned Coordination Drawings indicating the arrangement of General Construction, HVAC, Plumbing and Electrical work, including but not limited to: all ducts, air-handling equipment, control equipment, piping, conduits, raceways, junction boxes, fixtures, panels, and all associated equipment, which must be coordinated with the General Construction and other equipment or distribution lines. The Coordination Drawings must be signed and dated by all Prime Contractors, indicating concurrence, and transmitted to the HVAC Construction (.2) Contractor (in accordance with DGS Phase 1 COORDINATION DRAWINGS

2 the construction schedule), for who shall submit complete copy sets to the Department and to the Professional. C. The Department s receipt of Coordination Drawings does not in any way constitute approval, or relieve the Prime Contractors of the responsibility to accurately coordinate and install their work. D. The HVAC Construction (.2) Contractor shall submit completed, signed, and dated Coordination Drawings as follows: 1. The Department two (2) prints of each Coordination Drawing. 2. The Professional one (1) reproducible mylar of each Coordination Drawing. 3. The Using Agency - one (1) print of each Coordination Drawing, if requested. 4. Prime Contractors - one (1) reproducible mylar of each Coordination Drawing. E. Note: If determined necessary, Coordination Drawings may be formulated and submitted in partial submittals to facilitate the construction schedule and sequence of work within the Project. This must be jointly discussed and agreed to by all Prime Contractors at the initial job conference, and a priority of sequence must be established that has the concurrence of all parties (including the Department). 1.4 COORDINATION OF WORK A. Each Prime Contractor shall coordinate its construction operations with those of other Prime Contractors and entities to ensure efficient and orderly installation for each part of the Work. Each Prime Contractor shall coordinate its operations with other operations, included in different Sections that depend on each other for proper installations, connection, and operation. All Prime Contractors shall: 1. Schedule construction operations in sequence required to obtain the best results where installation of one part of the Work depends on installation of other components, before or after its own installation. 2. Coordinate installation of all components with other Prime Contractors to ensure adequate accessibility/clearance for required maintenance and service. 3. Make provisions to accommodate items scheduled for later installation. B. Each Prime Contractor shall clearly show, and coordinate with the other Prime Contractors, the following: 1. Arrange for pipe spaces, chases, slots, sleeves, and openings with general construction work, and arrange in building structure during progress of the Work, to allow for and facilitate distribution line and equipment installation. 2. Coordinate installation of required supporting devices for ductwork, piping, and conduit, as well as sleeves, and other structural components, as they are constructed. 3. Coordinate requirements for access panels and doors for HVAC, Plumbing and Electrical items requiring access where concealed behind finished surfaces. 4. Coordinate electrical connections to equipment provided by all Contractors. 5. Sequence, coordinate, and integrate installing materials and equipment for efficient flow of the Work. Coordinate installing large items of equipment requiring positioning before closing in the building. DGS Phase 1 COORDINATION DRAWINGS

3 1.5 COORDINATION DRAWINGS A. Format: All Coordination Drawings shall include X, Y & Z coordinates for all distribution and equipment, which will allow a three-dimensional coordination plan to be created. 1. Indicate ducts, pipes and conduits of dimensions greater than 6 by double lines. 2. Circle and clearly note all deviations from the Contract Documents, with reason for deviation stated. 3. Use scale not less than 1/8 = 1-0. Detail complex areas at larger scale. B. Coordination Procedure: 1. The HVAC Construction (.2) Contractor is responsible for acquiring from all the other Prime Contractors and assembling scaled coordination drawings indicating all new and existing architectural finishes, as well as the locations of all ductwork, piping, conduit, system devices, associated equipment, etc. for this Project. 2. The HVAC Construction (.2) Contractor shall prepare the basic background drawings, showing the existing conditions as well as the new construction items to be installed by this Contractor. The HVAC Construction (.2) Contractor may either produce the required base drawings itself, or obtain them from the Design Professional, at a cost not to exceed 1.2 times the cost of reproduction. 3. After producing its own background drawings or obtaining background drawings from the Professional, the HVAC Construction (.2) Contractor shall put the following information on the Coordination Drawings: HVAC Contract Work, including Control Systems. The HVAC Construction (.2) Contractor shall call attention on the Coordination Drawings to particular areas of conflict, which may affect the architecture or the structure. 4. After adding its specific requirements to these reproducible background drawings, the HVAC Construction (.2) Contractor shall place his signature on each sheet and give the Coordination Drawings to the Plumbing Construction (.3) Contractor. 5. The Plumbing Construction (.3) Contractor shall put the following information on the Coordination Drawings: Plumbing Contract Work, including Sprinkler/ Fire Protection Systems (unless there is a separate Fire Protection contract). 6. After adding its specific requirements to these reproducible background drawings, the Plumbing Construction (.3) Contractor shall place his signature on each sheet and give the Coordination Drawings to the Electrical Construction (.4) Contractor. 7. The Electrical Construction (.4) Contractor shall put the following information on the Coordination Drawings: Electrical Contract Work, including fire alarm, telecommunications and security systems, major conduit runs, lighting and panel locations, and conduit embeds in floor slabs and underground. 8. After adding its specific requirements to these reproducible background drawings, the Electrical Construction (.4) Contractor shall place his signature on each sheet and give the Coordination Drawings to the General Construction (.1) Contractor. 9. The General Construction (.1) Contractor shall put the following information on the Coordination Drawings: Architectural backgrounds, structural work, ceiling systems, and any special work, such as theatre/stage/rigging work. 10. After adding its specific requirements to these reproducible background drawings, the General Construction (.1) Contractor shall place his signature on each sheet and give the Coordination Drawings to the next Prime Contractor (if there are other Prime Contractors not mentioned here), or otherwise return the Coordination Drawings to the DGS Phase 1 COORDINATION DRAWINGS

4 HVAC Construction (.2) Contractor, for Submission to the Department, the Professional and the Using Agency. 11. Discrepancies between the Prime Contractors shall be settled by the HVAC Contractor, if no design modifications are required. Where design modifications are required, affected Contractor(s) shall submit them to the Professional for review and resolution, or initiate a Request For Information (RFI). 12. The Prime Contractors, together, are solely responsible for the accuracy and completeness of all Coordination Drawings. C. Distribution: Upon receipt of all fully-coordinated and signed Coordination Drawings from the other Prime Contractors, the Lead Contractor shall make proper distribution, as hereinbefore defined in Paragraph 1.3 D. 1.6 SPECIFIC REQUIREMENTS A. General Construction/Structural Work Information Required: 1. Openings and sleeve locations required in slabs, walls, beams, and other structural elements, including required openings not indicated on the Contract Documents. 2. Slab edge locations. 3. Embed locations, as described above. Note embedded steel angles at edges of sump and sewage ejector pits, to accept basin covers. 4. Wall and chase spaces for housing HVAC, Plumbing, or Electrical items. 5. Other specific/critical conditions unique to this Project, not noted above but necessary to assure proper coordination. B. HVAC Work Information Required: 1. Sizes and bottom elevations of rectangular ductwork, including angle bracing, flanges, and support systems. 2. Sizes and centerline elevations of round ductwork, piping and conduit runs 3. Acoustical lining in ductwork. 4. Identification of ductwork pressure class. 5. Dimensions of major components, such as dampers, valves, diffusers, registers, cleanouts, coils, VAV boxes, HVAC equipment, and electrical distribution equipment. 6. Fire-rated enclosures around ductwork. 7. Access panels required. 8. Other specific/critical conditions unique to this Project, not noted above but necessary to assure proper coordination. C. Plumbing and Fire Protection Work Information Required: 1. Sizes and centerline elevations of piping runs. 2. Locations of plumbing valves, equipment, and fixtures. 3. Locations of standpipes, floor control assemblies, fire hose valves, mains, piping, branch lines, pipe drops, sprinkler heads, fire pumps/controllers, and jockey pumps. 4. Other specific/critical conditions unique to this Project, not noted above but necessary to assure proper coordination. D. Electrical Work Information Required: DGS Phase 1 COORDINATION DRAWINGS

5 1. Runs of vertical and horizontal conduit, 1 ¼ diameter and larger. 2. Light fixture locations. 3. Exit light locations. 4. Smoke detector and other fire alarm locations. 5. Panelboards, switchboards, switchgear, transformers, busways, generators and motor control center, exit signs, and emergency battery pack locations. 6. Locations of pull boxes and junction boxes, dimensioned from column centerlines. 7. Access panels required. 8. Other specific/critical conditions unique to this Project, not noted above but necessary to assure proper coordination. E. Ceiling Systems and Plenum Space Information Required: 1. For HVAC, plumbing, fire protection, fire alarm, electrical, controls, and telecommunications Work penetrating acoustical ceilings, show locations of each item (including sprinkler heads, diffusers, grilles, access doors, light fixtures, smoke detectors, exit signs, speakers, and other visible ceiling-mounted devices) relative to the acoustical ceiling grid. 2. Locate components within ceiling plenums to accommodate layout of light fixtures indicated on Drawings. Clearly indicate areas of conflict between light fixtures and other components on Coordination Drawings. 3. Other specific/critical conditions unique to this Project, not noted above but necessary to assure proper coordination. 1.7 ORGANIZATION OF DRAWINGS A. Organize Coordination Drawings into a set, as follows: Floor Plans, Wall Sections and Building Sections, Mechanical/Plumbing/Electrical Rooms, Structural Penetrations, Imbeds, Curbs, Pads, and Floor Depressions. PART 2 PRODUCTS (Not Applicable) PART 3 EXECUTION (Not Applicable) END OF SECTION DGS Phase 1 COORDINATION DRAWINGS

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23 FC-1 RTU-3 RTU-5 RTU-1 RTU-2 RTU-4 ROOF 3" CWS/R 2" 3" 2 1/2" 2" 2 1/2" 4" 6" 4" 4" 6" 4" 3" 3" 2" 1 1/2" 1" 6" HWS HWS HWS HWS HWS HWR HWR HWR HWR HWR 3/4" 3/4" 3/4" 3/4" 1" 3/4" 1" 1" 1" 3/4" 3/4" 1" 1 1/4" 1 1/4" 1 1/4" 1 1/4" 1" 1" 1" 3/4" 3/4" 3/4" 1" 1" 1" 3/4" 1" 3/4" 3/4" ROOF 6" HWS VAV 1-11 VAV 1-10 FP 1-9 FP 1-8 FP 1-7 FP 1-6 VAV 1-4 FP 1-5 VAV 1-2 FP 1-3 VAV 1-1 VAV 2-7 VAV 2-6 VAV 2-5 VAV 2-4 VAV 4-1 FP 4-2 VAV 2-3 FP 4-4 FP 4-5 VAV 4-8 VAV 4-3 FP 4-6 FP 4-11 VAV 4-1 VAV 4-7 VAV 4-9 FP 4-10 HWR HWR HWR HWR 6" UPPER LEVEL REFER TO ENLARGED MECHANICAL ROOM PLAN THIS DWG FOR CONTINUATION HWR 6" HWS 6" 3" CWS/R 6" HWR HWS HWR 3" 3/4" 3/4" 1" 1" 1 1/4" 1 1/4" 1 1/2" 1 1/2" 3" 2" 2 1/2" 2" 2 1/2" 2 1/2" 2" 2" 1 1/2" 2 1/2" 3" 1 1/2" 1 1/4" 1 1/4" 1" 3" HWS HWS HWS HWS HWS HWS HWR HWR HWR HWR HWR HWR HWR 1" 1" 3/4" 1 1/4" 1" 3" 3" 3/4" 3/4" 3/4" 3/4" 1" 3/4" 3/4" 3/4" 1" 3/4" 1" 3/4" 1" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 1" 3/4" 3/4" 1" 3/4" 3/4" 3/4" 3/4" 3/4" VAV 4-24 VAV 4-12 VAV 4-21 VAV 4-22 VAV 4-20 VAV 4-23 VAV 4-16A UH-1 VAV 4-18 FP 4-19 VAV 4-17 VAV 2-2 VAV 4-14 VAV 4-16 VAV 4-15 VAV 1-14 FP 1-15 FP 1-16 FP 1-18 FP 1-19 VAV 1-13 VAV 1-17 VAV 1-21 VAV 1-23 FP 1-20 FP 1-24 FP 1-25 FP 1-26 VAV 1-22 VAV 1-27 VAV 1-12 VAV 1-28 FP 1-29 VAV 1-30 VAV 1-31 VAV 4-25 VAV /4" 4" 1" HWR HWR HWR HWR 2 1/2" HWS/R 3" HWR 1 1/4" HWS/R DHU-1 UPPER LEVEL GROUND LEVEL 4" "HOT SIDE" PIPING. 200 GPM. SEE DETAIL 3/M4.02 FOR ADDITIONAL INFORMATION. UH-2 UH-3 "COLD SIDE" PIPING BY POOL CONTRACTOR. HX-1 SEE POOL MECHANICAL PIPING SCHEMATICS THIS DWG FOR ADDITIONAL INFORMATION. VAV /4" HWS HWR 3/4" 1" 3/4" 3/4" VAV 1-34 VAV 1-33 VAV /4" HWS/R BASE BID 1 GROUND LEVEL 3/4" 1" BASEMENT LEVEL VAV 1-32 VAV 1-33 BASE BID 2 & 3 BASEMENT LEVEL 1 PIPING FLOW DIAGRAM - BASE BIDS NO.1 SCALE: N.T.S. CAP EXT'G 2"HPS CONNECT TO EXT'G 6"LPS CAP EXT'G 1-1/2"LPS CONNECT TO EXT'G 3"PC 16x10 EXHAUST UP. INSTALL FIRE DAMPER AT FLOOR PENETRATION. SEE DWG H1.14 FOR CONTINUATION. 16x10 EXHAUST DUCT. OPEN ENDED. COVER OPENING WITH WIRE MESH. CP-1 6" LPS EXT'G 10" SAFTEY RELIEF VENT TO REMAIN 3" PC 4" CONC. HOUSEKEEPING PAD BY G.C. (TYP) 3" 3" HX-1 BY P.C. 6" HX-2 BY P.C. 1" 1" 6" BY PC SWHX-1 2" BY MC 1" 3" LPR 1" HEADER 6" 3/4" MU SWHX-2 14x10 RA HWR 6" HWS 6" 2" 20x14 4" HWR 6" 6" AS-1 HWP-1 6" HWR DN FROM 2ND LEVEL 4" HWS VAV x10 RA ET-1 HWP-2 1-1/4" 3" HWS 18x8 SA 4" CONC. HOUSEKEEPING PAD ET-2 6" HWS UP TO 2ND LEVEL 4" CONC. HOUSEKEEPING PAD GRADE EXISTING COOLING TOWER REMOVE EXISTING BELOW GRADE CONDENSER SUPPLY AND RETURN PIPING. CWS 6" 2 1/2" FC-2 CWR CTP-1 NEW 3" HPS AND 2" PD DIRECT BURY STEAM PIPING. SEE DWG. H0.11 FOR CONTINUATION. HPS 3" 2" PD EXISTING CWS/R PIPING TO REMAIN. REMOVE EXISTING SECTION OF CWS/R PIPING. STEAM PRESSURE REDUCING STATION TO REMAIN EXISTING CONDENSATE RETURN UNIT TO REMAIN. TO MECH STM COILS TO MECH HW HT EXCH. TO DOM HW HT EXCH ST COND 1" LPR 3" LPS SWHX-3 3" AS-2 CT ET-3 CHEM FEED 3" HWR HWS HWS HWP-3 4" FINNED TUBE 350 BTUH/LF HWP-4 3" 3" HWR 1 1/2" 2" "COLD SIDE" TO REC POOL SYSTEM BY POOL CONTRACTOR. HX-2 SEE POOL MECHANICAL PIPING SCHEMATICS THIS DWG FOR ADDITIONAL INFORMATION. HWS HWR HWS 2 1/2" "COLD SIDE" TO SPA SYSTEM BY POOL CONTRACTOR. HX-3 SEE POOL MECHANICAL PIPING SCHEMATICS THIS DWG FOR ADDITIONAL INFORMATION. 1 3/4" HWS/R 2" HWS/R DHU-2 1 REVISIONS 2 ENLARGED MECHANICAL ROOM PLAN BASE BIDS NO.1-3 SCALE: 1/4" = 1'-0" 2 REC CENTER MECHANICAL PIPING DIAGRAM SCALE: N.T.S. F:\Loftus LLC Project Files\_2012\ DLA - Tippin Gynasium - Clarion\b. Drawings\Mech\H4.02.dwg 1/8/2015 3:29 PM TO POOL BY POOL CONTRACTOR 5'-0" MAX. CPVC POOL CONTRACTOR STOPPING POINT HEATER BOOSTER PUMP AND FLOW INTERLOCK 5'-0" MAX. CPVC POOL CONTRACTOR STOPPING POINT FROM TO ** FROM TO * * TO DEHUMIDIFICATION SYSTEM DHU-1, 90 GPM, 35 FT HEAD, 2 HP, 460 V-3Ø-60 HZ ** TO WATER TO WATER HEAT EXCHANGER. COLD SIDE GPM AND TEMPERATURE TO BE SPECIFIED BY POOL CONTRACTOR. HOT SIDE WATER FLOW FROM BUILDING HEATING SYSTEM. 200 GPM, 180 ENTERING WATER, 160 LEAVING WATER. COMPETITION POOL/ MECHANICAL PIPING SCHEMATIC HEATER BOOSTER PUMP AND FLOW INTERLOCK FROM FILTRATION EQUIPMENT BY POOL CONTRACTOR TO POOL BY POOL CONTRACTOR 5'-0" MAX. CPVC POOL CONTRACTOR STOPPING POINT HEATER BOOSTER PUMP AND FLOW INTERLOCK 5'-0" MAX. CPVC POOL CONTRACTOR STOPPING POINT FROM TO ** FROM TO * * TO DEHUMIDIFICATION SYSTEM DHU-2, 75 GPM, 35 FT HEAD, 1 1/2 HP, 460 V-3Ø-60 HZ ** TO WATER TO WATER HEAT EXCHANGER. COLD SIDE GPM AND TEMPERATURE TO BE SPECIFIED BY POOL CONTRACTOR. HOT SIDE WATER FLOW FROM BUILDING HEATING SYSTEM. 20 GPM, 180 ENTERING WATER, 140 LEAVING WATER. RECREATIONAL POOL/ MECHANICAL PIPING SCHEMATIC 3 SCALE: N.T.S. 4 SCALE: N.T.S. 5 SCALE: N.T.S. HEATER BOOSTER PUMP AND FLOW INTERLOCK FROM FILTRATION EQUIPMENT BY POOL CONTRACTOR TO SPA BY POOL CONTRACTOR 5'-0" MAX. CPVC POOL CONTRACTOR STOPPING POINT FROM TO * HEATER BOOSTER PUMP AND FLOW INTERLOCK * TO WATER TO WATER HEAT EXCHANGER. COLD SIDE GPM AND TEMPERATURE TO BE SPECIFIED BY POOL CONTRACTOR. HOT SIDE WATER FLOW FROM BUILDING HEATING SYSTEM. 40 GPM, 180 ENTERING WATER, 140 LEAVING WATER. SPA SYSTEM/ MECHANICAL PIPING SCHEMATIC FROM FILTRATION EQUIPMENT BY POOL CONTRACTOR DRAWN BY CHECKED BY COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF GENERAL SERVICES HARRISBURG, PENNSYLVANIA PROJECT NO. D.G.S PHASE 1 Renovation and Expansion of Tippin Gymnasium Clarion University, Clarion, Clarion County, Pennsylvania DATE SCALE Consultant's Signature PARTNERSHIP Joint Venture FOSTER PLAZA 9, SUITE HOLIDAY DRIVE PITTSBURGH, PA ENLARGED MECHANICAL ROOM & PIPING SCHEMATICS BASE BIDS NO.1-3 August 1, 2014 DRAWING NO. H4.02 Date Proj. No:

24 WC-1 1 1/2" CW, 3/4" HW UP 2" VENT UP WC-1 EX 4" WASTE UP FD-1 L-2 4" UR-1 L-2 FD-1 EX 4" F:\Loftus LLC Project Files\_2012\ DLA - Tippin Gynasium - Clarion\b. Drawings\Plumb\P1.09.dwg EX 4" EX 4" EX 4" EX 4" EX SAN 1 DN CONNECT TO EXISTING SANITARY PIPING FOUNDATION WEST BASE BID NO.1 SCALE: 1/8" = 1'-0" (UPPER LEVEL ELEV 1490'-0" LOWER BASECMENT 1453'-8") 1/9/2015 4:37 PM DLA/ GUND PARTNERSHIP Joint Venture FOSTER PLAZA 9, SUITE HOLIDAY DRIVE PITTSBURGH, PA TEL TIPPIN GYM Proj. No:

25 3" VENT UP 2" 1 1/4" 1/2" 1 1/4" 1/2" HW & 1/2" CW UP TO SINK 140 TBALL KERS 3B 3/4" 3/4" 1 1/2" 1 1/2" WRESTLING LOCKERS 246B 2" 2" 1 1/2" 3/4" ATSW OFFICE ATSW 247 3/4" ATSW OFFICE F:\Loftus LLC Project Files\_2012\ DLA - Tippin Gynasium - Clarion\b. Drawings\Plumb\P1.12.dwg EWC-1 PD STORAGE H 244 2" UP HPE OFFICE " 1 JAN. 245 MR-1 HPE RECEPTION 233 2" VESTIBULE 246A 2" PUMPED DISCHARGE FROM SP-2 HPE OFFICE GROUND LEVEL WEST BASE BID NO.1 SCALE: 1/8" = 1'-0" (ELEV 1478'-8") 2" HPE OFFICE " VENT DN 1 1/9/2015 4:41 PM DLA/ GUND PARTNERSHIP Joint Venture FOSTER PLAZA 9, SUITE HOLIDAY DRIVE PITTSBURGH, PA TEL TIPPIN GYM Proj. No:

26

27 K.8 K.3 K F36 F36 T/FTG. = 1478'-0" T/FTG. = 1478'-0" F36 P1 P1 1/8/2015 8:25:46 AM FILE: C:\01 - AES Revit Projects\12080_00^R14 CLARION TIPPIN STRUCT - CF_Brian Smith.rvt 23.5 DLA/ GUND PARTNERSHIP Joint Venture FOSTER PLAZA 9, SUITE HOLIDAY DRIVE PITTSBURGH, PA TEL T/FTG. = 1473'-6" F36 T/PIER = 1478'-0" T/FTG. = 1478'-0" TIPPIN GYM BULLETIN NO.5 D.G.S. PROJ. NO.: , PHASE 1 DATE: F36 DLA+ PROJECT NO: F36 T/PIER = 1478'-0" T/FTG. = 1473'-6" T/FTG. = 1478'-0" PARTIAL FOUNDATION PLAN - BASEMENT LEVEL - EAST - 1/8" BASE BID NO. 1, NO. 2 & NO. 3 1/8" = 1'-0" FOUNDATION PLAN CUAC PROJECT # SCALE: Project Number SKETCH NO. 1/8" = 1'-0" SSK-004

28 UP TYP. 4 SIDES 125 S BACKWASH CATCH BASIN 8" CONC. WALL REINF. PER SECT. 125/S4.2 1/8/2015 8:26:09 AM FILE: C:\01 - AES Revit Projects\12080_00^R14 CLARION TIPPIN STRUCT - CF_Brian Smith.rvt 23 DLA/ GUND PARTNERSHIP Joint Venture FOSTER PLAZA 9, SUITE HOLIDAY DRIVE PITTSBURGH, PA TEL K.8 TIPPIN GYM K.3 PARTIAL GROUND FLOOR PLAN EAST -1/8 BASE BID NO. 1, NO. 2 & NO. 3 1/8" = 1'-0" BULLETIN NO.5 D.G.S. PROJ. NO.: , PHASE 1 DATE: DLA+ PROJECT NO: K GROUND FLOOR CUAC PROJECT # SCALE: Project Number SKETCH NO. 1/8" = 1'-0" SSK-005

29 L.7 M M.3 M.5 M BACKWASH CATCH BASIN 8" CONC. WALL REINF. PER SECT. 125/S S4.2 TYP. 6 SIDES 8.3 1/8/2015 7:21:26 AM FILE: C:\01 - AES Revit Projects\12080_02^R14 CLARION REC STRUCT - CF_Brian Smith.rvt 8.8 DLA/ GUND PARTNERSHIP Joint Venture FOSTER PLAZA 9, SUITE HOLIDAY DRIVE PITTSBURGH, PA TEL TIPPIN GYM BULLETIN NO.5 D.G.S. PROJ. NO.: , PHASE 1 PARTIAL GROUND FLOOR PLAN - REC POOL 1/8" = 1'-0" GROUND FLOOR DATE: DLA+ PROJECT NO: CUAC PROJECT # SCALE: Project Number SKETCH NO. 1/8" = 1'-0" SSK-006

30

31 S1 ELEV. T/SLAB = 1478'-8" S1 ELEV. T/SLAB = 1474'-0" 14'-6 7/8" 1/8/ :02:39 AM FILE: C:\01 - AES Revit Projects\12080_00^R14 CLARION TIPPIN STRUCT - CF_Brian Smith.rvt A 4 DLA/ GUND PARTNERSHIP Joint Venture FOSTER PLAZA 9, SUITE HOLIDAY DRIVE PITTSBURGH, PA TEL '-11 5/8" C8X11.5 C8X11.5 C8X '-0 3/8" MC12X10.6 STAIR STRINGER MC12X S4.1 MC12X /8" MW1 TYP. 4 SIDES NOTE 8 J.2 J J.5 K K.6 PARTIAL GROUND FLOOR PLAN - WEST - 1/8" BASE BID NO. 1, NO. 2 & NO. 3 1/8" = 1'-0" TIPPIN GYM BULLETIN NO.5 D.G.S. PROJ. NO.: , PHASE 1 DATE: DLA+ PROJECT NO: C8X18.75 MC12X10.6 GROUND FLOOR BPL 1/2X6X6 TYP. CUAC PROJECT # SCALE: Project Number SKETCH NO. 1/8" = 1'-0" SSK-008

32 K.6 K1 L M 1/8/ :02:00 AM FILE: C:\01 - AES Revit Projects\12080_00^R14 CLARION TIPPIN STRUCT - CF_Brian Smith.rvt DLA/ GUND PARTNERSHIP Joint Venture FOSTER PLAZA 9, SUITE HOLIDAY DRIVE PITTSBURGH, PA TEL TIPPIN GYM BULLETIN NO.5 D.G.S. PROJ. NO.: , PHASE 1 4" CONC. SLAB ON RIGID INSULATION SUPPORTED BY EXIST. SLAB ON GRADE ELEV. T/NEW SLAB = 1469'-4" ELEV. T/ EXIST. SLAB = 1468'-0"+/- SLAB OCCURS BENEATH STAIR FRAMING & EXIST. FLOOR SHOWN PARTIAL GROUND FLOOR PLAN - WEST - 1/8" BASE BID NO. 1, NO. 2 & NO. 3 1/8" = 1'-0" GROUND FLOOR DATE: DLA+ PROJECT NO: CUAC PROJECT # SCALE: Project Number SKETCH NO. 1/8" = 1'-0" SSK-009

33

A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following:

A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following: SECTION 01 31 00 PROJECT MANAGEMENT AND COORDINATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

SECTION PROJECT COORDINATION VIA BIM

SECTION PROJECT COORDINATION VIA BIM SECTION 01 31 13 PROJECT COORDINATION VIA BIM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

SECTION PROJECT MANAGEMENT AND COORDINATION

SECTION PROJECT MANAGEMENT AND COORDINATION SECTION 013100 - PROJECT MANAGEMENT AND COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION 01 3100 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

SECTION D BIM COORDINATION DRAWINGS - CONTRACTORS

SECTION D BIM COORDINATION DRAWINGS - CONTRACTORS END OF SECTION 01 30 00 SECTION 01 31 21-3D BIM COORDINATION DRAWINGS - CONTRACTORS PART 1 - GENERAL 1.01 RELATED DOCUMENTS Attention is directed to Bidding and Contract Requirements, and to Division 1,

More information

University of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL SECTION 23 00 10 - MECHANICAL SCOPE OF WORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01

More information

PROGRAMMING SCHEMATIC DESIGN DESIGN DEVELOPMENT CONSTRUCTION DOCUMENTS. room) Scalable bubble diagrams schedules describing programmatic

PROGRAMMING SCHEMATIC DESIGN DESIGN DEVELOPMENT CONSTRUCTION DOCUMENTS. room) Scalable bubble diagrams schedules describing programmatic GENERAL SITE PROGRAMMING SCHEMATIC DESIGN DESIGN DEVELOPMENT CONSTRUCTION DOCUMENTS Scope of work narrative Building code review Description of construction Documentation on drawings as List of applicable

More information

U of I Facilities Standards Updates for 2017

U of I Facilities Standards Updates for 2017 U of I Facilities Standards Updates for 2017 Updates to the U of I Facilities Standards will occur on a periodic basis (typically all standards will be reviewed for accuracy & completeness every 3 years),

More information

SECTION SUBMITTALS. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION SUBMITTALS. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 013300 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

FIRE STATION NO TH STREET NORTH ST. PETERSBURG, FL M-1 SCOPE OF WORK SYMBOL DESCRIPTION SYMBOL DESCRIPTION HVAC SYMBOL LEGEND

FIRE STATION NO TH STREET NORTH ST. PETERSBURG, FL M-1 SCOPE OF WORK SYMBOL DESCRIPTION SYMBOL DESCRIPTION HVAC SYMBOL LEGEND HVAC SYMBOL LEGEND HVAC PIPING AND VALVES LEGEND HVAC GENERAL NOTES SCOPE OF WORK SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION PHASING OF WORK HVAC ABBREVIATIONS ABBREVIATION

More information

Design Deliverables. Summary. A. Expectations for Design Deliverables:

Design Deliverables. Summary. A. Expectations for Design Deliverables: Design Deliverables Summary A. Expectations for Design Deliverables: The Design Team is obligated to advance and deliver the project with a professional manner and standard of care that meets the expectations

More information

4. Special Systems Design: including Fire Alarm and Security. C. Electrical and Telecommunications Ductbanks: Refer to Section 16118

4. Special Systems Design: including Fire Alarm and Security. C. Electrical and Telecommunications Ductbanks: Refer to Section 16118 PART 1: GENERAL This section of the design standard outlines general requirements for electrical and telecommunications designs to be performed for the University of Texas at Austin. This standard is intended

More information

03/7/12 Issuance UTD Section Page 1 of 5 Electrical General

03/7/12 Issuance UTD Section Page 1 of 5 Electrical General SECTION 26 01 00 ELECTRICAL GENERAL PART 1: GENERAL 1.1 Electrical/Telecommunications Design 1.1.1 This section of the design and construction standard outlines general requirements for electrical and

More information

Residential Construction Checklist Single and Two Family Construction

Residential Construction Checklist Single and Two Family Construction DATE: _ Building Inspection Submittal Requirements Residential Construction Checklist Single and Two Family Construction Submit a City of Big Spring Permit Application, checklist, and 3 complete hard copy

More information

2. Electrical rooms shall be centrally located and stacked so that feeder conduits and bus duct are run as straight and short as possible.

2. Electrical rooms shall be centrally located and stacked so that feeder conduits and bus duct are run as straight and short as possible. PART 1: GENERAL 1.01 Electrical/Telecommunications Design A. This section of the design and construction standard outlines general requirements for electrical and telecommunications designs to be performed

More information

BUILDING PLAN REVIEW REQUIREMENTS

BUILDING PLAN REVIEW REQUIREMENTS TOWNSHIP OF NORTH FAYETTE BUILDING DEPARTMENT COMMERCIAL PLAN REVIEW REQUIREMENTS BUILDING PLAN REVIEW REQUIREMENTS In order to perform a thorough Building Plan Review, the following specifications, drawings

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections:

More information

ADDENDUM #1. April 29, 2009

ADDENDUM #1. April 29, 2009 April 29, 2009 Re: HACC, Central Pennsylvania s Community College Midtown 1 CCTA Phase 2 Solicitation # 09-17 From: Eastern pcm, LLC Construction Manager HACC 212 Locust Street, Suite 604 Harrisburg, PA

More information

ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Electrical/Telecommunications Design

ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Electrical/Telecommunications Design PART 1: GENERAL 1.01 Electrical/Telecommunications Design A. This section of the design and construction standard outlines general requirements for electrical and telecommunications designs to be performed

More information

ADDENDUM #2 September 12, 2018

ADDENDUM #2 September 12, 2018 Physical Plant Services Project Management 1000 Rim Drive Phone: (970) 247-7523 Fax: (970) 247-7555 Project No. 2007-130P18 Whalen Gymnasium Expansion and Renovation for Exercise Science Request for Qualifications

More information

Facility Services Subgroup Preface for Divisions 21` through 28

Facility Services Subgroup Preface for Divisions 21` through 28 Facility Services Subgroup Preface for Divisions 21` through 28 1.1 EXECUTIVE SUMMARY A. This document provides standards for the Consultants and Contractors producing mechanical and electrical design

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending

More information

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe Markers. 2. Valve Tags. 3. Equipment Nameplates. 4. Underground Marking Tape. 5. Duct

More information

Industrial Pipe Marking

Industrial Pipe Marking Industrial Pipe Marking Pipe and Valve Identification Specialists SPECIFICATIONS ASME (ANSI) Standard A13.1-2007 The ASME (ANSI) Standard for pipe identification is a widely used guideline in determining

More information

ADDENDUM NO. 2. The Bid Opening has not changed it remains December 8, 2016 AT 1:30 P.M.

ADDENDUM NO. 2. The Bid Opening has not changed it remains December 8, 2016 AT 1:30 P.M. ADDENDUM NO. TO: PLANS AND SPECIFICATIONS FOR STATE OF MISSOURI Health Center Renovation Missouri School for the Blind NO. E60-0 The Bid Opening has not changed it remains December 8, 06 AT :30 P.M. GENERAL

More information

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT 1 CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT Facilities Planning & Management Department August 11, 2010 Addendum No. 2 INVITATION FOR BID NO.: 11-07 Industrial Technology Center, Buildings 1400/1600

More information

TO WHOM IT MAY CONCERN:

TO WHOM IT MAY CONCERN: TO WHOM IT MAY CONCERN: A lot of questions are asked throughout the year as to when a building permit is required. This list may help identify some of the instances when a permit would be required: Permit

More information

A/E REVIEW CHECKLIST PLUMBING/FIRE PROTECTION/SANITARY

A/E REVIEW CHECKLIST PLUMBING/FIRE PROTECTION/SANITARY A/E REVIEW CHECKLIST PLUMBING/FIRE PROTECTION/SANITARY Reviewers should - Use Checklists when reviewing any type of VA construction project for the following disciplines: Site and Landscape, Architectural,

More information

Bidders and Others to Whom Bidding Documents have been issued by the Architect and/or CM.

Bidders and Others to Whom Bidding Documents have been issued by the Architect and/or CM. ADDENDUM NO. March 3, 202 Re: MCC Student Center Addition, Manchester, NH To: Bidders and Others to Whom Bidding Documents have been issued by the Architect and/or CM. All items in this Addendum shall

More information

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing).

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing). SECTION 15047 - IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Identification including necessary accessories indicated on Construction Documents and specified in this section or as required

More information

A/E REVIEW CHECKLIST HVAC

A/E REVIEW CHECKLIST HVAC A/E CHECKLIST HVAC Reviewers should - Use Checklists when reviewing any type of VA construction project for the following disciplines: Site and Landscape, Architectural, Structural, Plumbing, Fire Protection,

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION Buebtel/Perlcins Community Learning Center GPD - 2001271.15 SECTION 15075 MECHANICAL IDENTIFICATION PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

PMA ONLINE TRAINING. Commercial Drawings. One Hour Continuing Education

PMA ONLINE TRAINING. Commercial Drawings. One Hour Continuing Education PMA ONLINE TRAINING Commercial Drawings One Hour Continuing Education PMA training disclaimer The information provided in this document is intended for use as a guideline and is not intended as, nor does

More information

ADDENDUM NO. TWO. To the Plans and Specifications for: PALM COAST READINESS CENTER PALM COAST, FL For FLORIDA DEPT. OF MILITARY AFFAIRS

ADDENDUM NO. TWO. To the Plans and Specifications for: PALM COAST READINESS CENTER PALM COAST, FL For FLORIDA DEPT. OF MILITARY AFFAIRS ADDENDUM NO. TWO To the Plans and Specifications for: PALM COAST READINESS CENTER PALM COAST, FL For FLORIDA DEPT. OF MILITARY AFFAIRS Prepared By: ARCHITECT Bhide & Hall Architects, P.A. 1329-C Kingsley

More information

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to

More information

ADDENDUM NO. 4 November 15, Page 1

ADDENDUM NO. 4 November 15, Page 1 ADDENDUM NO. 4 November 15, 201 8 Page 1 PROJECT MANUAL FOR CONSTRUCTION OF HVAC REPLACEMENT FOR NORTH OCONEE HIGH SCHOOL FOR OCONEE COUNTY SCHOOLS WATKINSVILLE, GEORGIA DATED: SEPTEMBER 14, 2018 CUNNINGHAM,

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 SUBMITTALS A.

More information

HAYES VALLEY PLAYGROUND AND CLUBHOUSE PROJECT NO.: SAN FRANCISCO PARKS AND RECREATIONS SAN FRANCISCO, CA

HAYES VALLEY PLAYGROUND AND CLUBHOUSE PROJECT NO.: SAN FRANCISCO PARKS AND RECREATIONS SAN FRANCISCO, CA HAYES VALLEY PLAYGROUND AND CLUBHOUSE PROJECT NO.: 08012.00 SAN FRANCISCO PARKS AND RECREATIONS SAN FRANCISCO, CA ADDENDUM NUMBER 1 to the BID SET August 10, 2009 General This Addendum will become part

More information

DOCUMENT SUBMITTAL REQUIREMENTS FOR A NEW MULTI-FAMILY DWELLING

DOCUMENT SUBMITTAL REQUIREMENTS FOR A NEW MULTI-FAMILY DWELLING INFORMATION BULLETIN / GENERAL INFORMATION REFERENCE NO.: None DOCUMENT NO. P/GI 2014-007 Previously Issued As: P/GI 2011-007 Effective: 01-01-2014 Revised: DOCUMENT SUBMITTAL REQUIREMENTS FOR A NEW MULTI-FAMILY

More information

December 31, 2015 A. THE BID OPENING DATE IS UNCHANGED. B. Questions, Additions, and Deletions

December 31, 2015 A. THE BID OPENING DATE IS UNCHANGED. B. Questions, Additions, and Deletions December 31, 2015 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA Y16-721-MM / ADDENDUM No. 1 ORANGE COUNTY CONVENTION CENTER PHASE III VALENCIA BALLROOM RENOVATION Bid Opening Date: January 12, 2016

More information

Piping & Equipment Identification

Piping & Equipment Identification Piping & Equipment Identification Part 1 General 1.01 Description of Work A. Work in this section includes: Identification materials, including necessary accessories indicated on Contract Documents and

More information

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT Henderson Engineers, Inc. PART 1 - GENERAL REQUIREMENTS 1.1 SUMMARY A. Extent of Plumbing work to be identified as required by this Section

More information

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D HOSKINS ARCHITECTURE, LLC 1721 4 th AVENUE NORTH, SUITE 101 BIRMINGHAM, ALABAMA 35203 205.321.4122 ADDENDUM NO. 7 PROJECT: BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D HOSKINS

More information

MSU Barnard Hall 105 Cleanroom Installation PPA # Page 1

MSU Barnard Hall 105 Cleanroom Installation PPA # Page 1 ADDENDUM NUMBER 1 DATE: February 10, 2017 PROJECT: MSU Barnard Hall Room 105 Cleanroom Installation PPA# 16-0002 (Consulting Design Solutions, Inc. Project # 1613) BID DATE: February 23, 2017 2:00 PM,

More information

SPARTAN DAY CAMP 4814 FREEDOM RING RD

SPARTAN DAY CAMP 4814 FREEDOM RING RD 484 FREEDOM RING RD PROJECT DATA GENERAL PROJECT NOTES: LOCATION:. DIMENSIONS ARE TO FACE OF STUD OR TO COLUMN CENTERLINE UNLESS NOTED OTHERWISE. VERIFY ALL EXISTING CONDITIONS AND ADJUST WALL DIMENSIONS

More information

Hall of Waters List of Historic Drawings

Hall of Waters List of Historic Drawings List of Historic Drawings The following represents the historic drawings of the PROJECT PWA PROJECT NUMBER JOB NUMBER SHEET NUMBER SHEET TITLE DATE NOTES 1935 Drawing Piping Layout at Tank Room for Mineral

More information

SECTION CONTRACTOR SUBMITTALS. A. All submittals by the CONTRACTOR shall be submitted to the ENGINEER.

SECTION CONTRACTOR SUBMITTALS. A. All submittals by the CONTRACTOR shall be submitted to the ENGINEER. SECTION 01300 - PART 1 - GENERAL 1.1 GENERAL A. All submittals by the CONTRACTOR shall be submitted to the ENGINEER. B. Unless otherwise noted, within 14 days after the date of commencement as stated in

More information

This Revision No. 01 becomes as fully a part of the first issued documents as if originally issued therewith or originally contained therein.

This Revision No. 01 becomes as fully a part of the first issued documents as if originally issued therewith or originally contained therein. Revision No. 01 Issued February 19, 2016 Page 1 This Revision No. 01 becomes as fully a part of the first issued documents as if originally issued therewith or originally contained therein. This Revision

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017 SECTION 23 0553 - MECHANICAL SYSTEMS IDENTIFICATION GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Marshall Truck Station Laboratory Addition Project No. TZ MnDOT

Marshall Truck Station Laboratory Addition Project No. TZ MnDOT Marshall Truck Station Laboratory Addition Project No. TZ-91523 MnDOT 13-6574 ADDENDUM NUMBER 2 DATED September 19, 2013 Marshall Truck Station Laboratory Addition Project No. TZ-91523 MnDOT 13-6574 Architect:

More information

Wayne State University. Prentis Building Renovation. NM Project Number: Niagara Murano 2215 Cole Street Birmingham, Michigan, 48009

Wayne State University. Prentis Building Renovation. NM Project Number: Niagara Murano 2215 Cole Street Birmingham, Michigan, 48009 ADDENDUM NO 2 OWNER: Wayne State University DATE: January 4 th, 2019 PROJECT: NM Project Number: 18113.0 ARCHITECT: ENGINEER: Niagara Murano 2215 Cole Street Birmingham, Michigan, 48009 IMEG 26200 Town

More information

National BIM Standard - United States Version 3

National BIM Standard - United States Version 3 National BIM Standard - United States Version 3 5 Practice Documents 5.5 Mechanical, Electrical, Plumbing, And Fire Protection Systems (MEP) Spatial Coordination Requirements for Construction Installation

More information

Element Z General Design Requirements Standards and Other Requirements

Element Z General Design Requirements Standards and Other Requirements P AR T 1 - GENERAL 1.01 OVERVIEW A. The Table identified in Part 2 of this document summarizes A/E deliverables and minimum level of information to be depicted on construction documents at 100 percent

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS FEBRUARY 29, 2012

UNIVERSITY OF ROCHESTER DESIGN STANDARDS FEBRUARY 29, 2012 SECTION 01950 - RECORD DRAWINGS & SPACE FLOOR PLANS 1.1 RECORD DRAWINGS MATERIAL AND FORMAT A. Definition 1. Final record drawings, or as-builts, are drawings, which are revised to reflect the changes

More information

Addition and Renovations to Upper Bucks County Technical School

Addition and Renovations to Upper Bucks County Technical School Additions and Renovations to Upper Bucks County Technical School SECTION 00 91 14 - ADDENDUM NUMBER 2 23 April 2014 RE: From: To: Addition and Renovations to Upper Bucks County Technical School Godshall

More information

RIT CAD Specifications

RIT CAD Specifications RIT CAD Specifications The design team shall provide RIT with Revit, AutoCAD, and PDF files that capture the construction conditions of the associated project. This document outlines requirements for submitting

More information

05BDB ADDENDUM 002. Thomas W. Wathen Business Division Building Renovation GENERAL ITEMS:

05BDB ADDENDUM 002. Thomas W. Wathen Business Division Building Renovation GENERAL ITEMS: ADDENDUM 002 Addendum - 002 to the Drawings and Specifications dated, March, 2019, for Vincennes University, located at the Vincennes Campus in Vincennes, Indiana, as prepared by Andrew Young, Campus Architect,

More information

Bidders for the Oak Brook Park District Family Locker Room Renovation

Bidders for the Oak Brook Park District Family Locker Room Renovation BIDDING & CONTRACT REQUIREMENTS Document 00901 Addendum No. 1 Date: June 1, 2017 From: To: Wight Construction Services, Inc. 2500 Frontage Road Darien, IL 60561 Bidders for the Oak Brook Park District

More information

SECTION ADMINISTRATIVE REQUIREMENTS SECTION ADMINISTRATIVE REQUIREMENTS

SECTION ADMINISTRATIVE REQUIREMENTS SECTION ADMINISTRATIVE REQUIREMENTS PART 1 GENERAL 1.01 SECTION INCLUDES A. Project Coordination. B. Preconstruction meeting. C. Progress meetings. D. Preinstallation conferences. E. Requests for information (RFI). F. Coordination drawings.

More information

PLAN SUBMITTAL REQUIREMENTS

PLAN SUBMITTAL REQUIREMENTS DEPARTMENT OF ECONOMIC AND COMMUNITY DEVELOPMENT BUILDING DIVISION PLAN SUBMITTAL REQUIREMENTS Residential and Commercial Projects Welcome to the South San Francisco Building Division. We are providing

More information

State College Area School District

State College Area School District State College Area School District The following is a guideline for project design submittals to the Facility Committee of the State College Area School District. During the design process the committee

More information

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section. SECTION 23 31 13 METAL HVAC DUCTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in

More information

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Assign unit identification numbers to operating units of equipment within a class or subclass during the design phase of new buildings, additions,

More information

OCPS Submittal Register for Product Data and Shop Drawing Reviews

OCPS Submittal Register for Product Data and Shop Drawing Reviews OCPS mittal Register for Product Data and Shop Drawing s Project ification Drawings - D Shop Drawings - Product Data - Test - TR Test Data - TD Calculations - Calc Certification - Cert 02 22 27 Pre-demolition

More information

ADDENDUM NO: 1 IFB/RFP No: NKU Commodity: Kentucky Hall Renovation Date: 12/7/2017 Due Date: 12/18/2017

ADDENDUM NO: 1 IFB/RFP No: NKU Commodity: Kentucky Hall Renovation Date: 12/7/2017 Due Date: 12/18/2017 Procurement Services Lucas Administrative Center, 617 1 Nunn Drive Highland Heights, KY 41099 859.572.6605 FAX 859.572.6995 ADDENDUM NO: 1 IFB/RFP No: NKU-22-18 Commodity: Kentucky Hall Renovation Date:

More information

Address: South Elgin, IL Phone: ( ) - Fax: ( ) - Cell: ( ) - Contractor Type: Phone: ( ) - Fax: ( ) - Cell: ( ) - Contact Type:

Address: South Elgin, IL Phone: ( ) - Fax: ( ) - Cell: ( ) - Contractor Type: Phone: ( ) - Fax: ( ) - Cell: ( ) - Contact Type: Community Development Department 10 N. Water Street Monday Friday 847 741 3894 8:30 a.m. 5:00 p.m. 847 741 3959 FAX www.southelgin.com BASEMENT REMODEL APPLICATION PROPERTY INFORMATION South Elgin, IL

More information

RENOVATION OF THE FARMERS MARKET Reference Number:

RENOVATION OF THE FARMERS MARKET Reference Number: RENOVATION OF THE FARMERS MARKET Reference Number: 13-098 A D D E N D U M NO. 1 The following shall form part of the tender documents issued by the City of Guelph s Purchasing Department, June, 2013. NOTE:

More information

B. Samples: For color, letter style, and graphic representation required for each identification material and device.

B. Samples: For color, letter style, and graphic representation required for each identification material and device. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL DISTRIBUTION SYSTEMS PRESENTED BY: Ray Chow Duct Design Level 1 Fundamentals Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Introduction

More information

CANUTILLO INDEPENDENT SCHOOL DISTRICT 7710 Cap Carter Rd. Canuillo,TX DESIGN CHECKLIST

CANUTILLO INDEPENDENT SCHOOL DISTRICT 7710 Cap Carter Rd. Canuillo,TX DESIGN CHECKLIST CANUTILLO INDEPENDENT SCHOOL DISTRICT 7710 Cap Carter Rd. Canuillo,TX 79835 DESIGN CHECKLIST Reviewers should - Use Checklists when reviewing any type of CISD construction project for the following disciplines:

More information

Tri-County Commercial Application Checklist

Tri-County Commercial Application Checklist TRI-COUNTY SERVICE CENTER TRI-COUNTY SERVICE CENTER State of Oregon Clackamas Multnomah Washington C O U N T I E S Tri-County Commercial Application Checklist Department of Consumer & Business Services

More information

Travis County ESD #1. Building Plan Submittals. Information Bulletin. Fire Marshal Hancock

Travis County ESD #1. Building Plan Submittals. Information Bulletin. Fire Marshal Hancock Travis County ESD #1 Information Bulletin Building Plan Submittals Fire Marshal Hancock Effective Date 12/12/2018 Table of Contents INTRODUCTION 3 SECTION I. SUPPORTING DOCUMENTATION 4 SECTION II. GENERAL

More information

List of Figures. List of Forms

List of Figures. List of Forms City of Columbia Engineering Regulations PART 1: SUBMISSION OF PLANS Table of Contents Paragraph Description Page No. 1.1 General 1-1 1.2 Engineer s Report 1-1 1.3 Plans 1-3 1.4 Revisions to Approved Plan

More information

City of Lompoc Building & Safety Services Section 100 Civic Center Plaza Lompoc, CA Phone: Fax:

City of Lompoc Building & Safety Services Section 100 Civic Center Plaza Lompoc, CA Phone: Fax: City of Lompoc Building & Safety Services Section 100 Civic Center Plaza Lompoc, CA 93436 Phone: 805-875-8220 Fax: 805-875-8198 RESIDENTIAL BUILDING PLANS SUBMITTAL REQUIREMENTS A. APPLICATION PROCESS

More information

CRAFTSMAN EXAMINATION, JUNE 2008 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

CRAFTSMAN EXAMINATION, JUNE 2008 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours Affix label with Candidate Code Number here. If no label, enter candidate Number if known No. 9195 CRAFTSMAN EXAMINATION, JUNE 2008 PLUMBING INSTRUCTIONS QUESTION AND ANSWER BOOKLET Time allowed THREE

More information

BUILDING DEPARTMENT CURRENT

BUILDING DEPARTMENT CURRENT CITY OF LAPEER FEE SCHEDULE EFFECTIVE 7-1-2018 BUILDING DESCRIPTION BUILDING DEPARTMENT CURRENT FEE Administrative Plan Review Fees Plan Review $81.00 per hour; 1 hr minimum Commercial Plan Review Deposit

More information

Residential Room Addition / Remodel Submittal Requirement Checklist

Residential Room Addition / Remodel Submittal Requirement Checklist City of Elko Building Department 1753 College Avenue Elko, Nevada 89801 (775) 777-7220 fax (775) 777-7229 Residential Room Addition / Remodel Submittal Requirement Checklist TWO COMPLETE SETS OF PROPERLY

More information

TELEPHONE: (215) Addendum No Cooling Plant Replacement SDP Contracts No. B-080C, B-081C and B-082 of 2017/18

TELEPHONE: (215) Addendum No Cooling Plant Replacement SDP Contracts No. B-080C, B-081C and B-082 of 2017/18 THE SCHOOL DISTRICT OF PHILADELPHIA SCHOOL REFORM COMMISSION Office of Capital Programs 440 North Broad Street, 3 rd Floor Suite 371 Philadelphia, PA 19130 TELEPHONE: (215) 400-4730 Addendum No. 001 Subject:

More information

SUBMITTAL REQUIREMENTS FOR COMMERCIAL BUILDING PROJECTS

SUBMITTAL REQUIREMENTS FOR COMMERCIAL BUILDING PROJECTS SUBMITTAL REQUIREMENTS FOR COMMERCIAL BUILDING PROJECTS When submitting your application for Commercial projects please include the following: 1. Completed Building Permit Application with page 2 stamped

More information

ADDENDUM THREE SPECIFICATIONS. Vincennes University Renovations of the Curtis G. Shake Learning Resources Center

ADDENDUM THREE SPECIFICATIONS. Vincennes University Renovations of the Curtis G. Shake Learning Resources Center ADDENDUM THREE Addendum Three (AD.03) to the drawings and specifications prepared by Gibraltar Design for Curtis G. Shake Learning Resources Center for Vincennes University, Vincennes, Indiana. All Contractors

More information

Quality Control Checklist - Design Drawings

Quality Control Checklist - Design Drawings Quality Control Checklist - Design Drawings Date Company Name Address Telephone Fax Email Job Number 1) Drawing Set a) Drawing one is site/location/incoming power i) Should contain location map if not

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018 SECTION 01 7839 - PROJECT RECORD DOCUMENTS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

City of Thousand Oaks

City of Thousand Oaks TENANT IMPROVEMENT SUBMITTAL CHECKLIST SUBMIT THREE SETS OF SCALED DRAWINGS (ONE TO BE A BLACKLINE SET) WITH THE FOLLOWING INFORMATION: 1. 2. 3. 4. 5. 6. 7. 8. 9. SITE PLAN: Show building location (vicinity

More information

Wendell Smith Elementary School

Wendell Smith Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Single-Family Dwelling Submittal Requirements

Single-Family Dwelling Submittal Requirements Single-Family Dwelling Submittal Requirements The purpose of this guideline is to assist our customers in preparing for plan submittal. The items listed must be included before your plans can be accepted

More information

To the Drawings and/or Specifications for. Board of Education of Harford County Lancaster, PA 17603

To the Drawings and/or Specifications for. Board of Education of Harford County Lancaster, PA 17603 ENDUM NO. 2 To the Drawings and/or Specifications for Gilbert Architects Youth s Benefit Elementary School - #0729 626 N. Charlotte St. Board of Education of Harford County Lancaster, PA 17603 June 2,

More information

TRIBAL BUILDING AND DEVELOPMENT Plan Check Submittal

TRIBAL BUILDING AND DEVELOPMENT Plan Check Submittal TRIBAL BUILDING AND DEVELOPMENT Plan Check Submittal Complete sets of plans are required. Plans shall be stamped and wet signed by the architect or engineer. (signed and accompanied with letter from Homeowners

More information

(Larry D. Svitak, PE) License No

(Larry D. Svitak, PE) License No ADDENDUM NO. engineering design initiative north 5 th Street minneapolis, mn 55 Phone: () 33-55 AX: () 33-58 or Project: Nobles County Government Center AHU- Replacement EDI Project No.: 7-075 Owner: Nobles

More information

Autodesk Revit MEP Learning Essentials Training Course Outline

Autodesk Revit MEP Learning Essentials Training Course Outline Module 00 Revit in a Nutshell Interactive exercise on creating and documenting a basic building Module 01 Introduction to the Principles of BIM Simple Truths Behind the hype The benefits of BIM What will

More information

This Addendum is hereby made a part of the Contract Documents to the same extent as though it were originally included therein.

This Addendum is hereby made a part of the Contract Documents to the same extent as though it were originally included therein. SALK MIDDLE SCHOOL REPLACEMENT PHASE ADDENDUM NO. Spokane Public Schools February, 04 NAC Architecture, -087 Page A- 4 5 6 7 8 9 0 4 5 6 7 8 9 0 4 5 6 7 8 9 0 4 5 6 7 8 9 40 4 4 4 44 45 46 47 48 49 50

More information

New Multi-Family Buildings & Additions Plan Intake Submittal Checklist. Project Name: Site Address:

New Multi-Family Buildings & Additions Plan Intake Submittal Checklist. Project Name: Site Address: #506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION SECTION 15190 MECHANICAL IDENTIFICATION PART 1 GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. Nameplates. 2. Tags. 3. Stencils. 4. Pipe Markers. 1.02 SUBMITTALS A. Submit valve chart and schedule,

More information

DOCUMENT SUBMITTAL REQUIREMENTS FOR AN ALTERATION OR ADDITION TO AN EXISTING SINGLE-FAMILY DWELLING OR MULTI-FAMILY DWELLING

DOCUMENT SUBMITTAL REQUIREMENTS FOR AN ALTERATION OR ADDITION TO AN EXISTING SINGLE-FAMILY DWELLING OR MULTI-FAMILY DWELLING INFORMATION BULLETIN / PUBLIC - GENERAL INFORMATION REFERENCE NO.: Effective: 10-01-99 DOCUMENT NO. P/GI 2002-008 Revised: 11-01-02 Previously Issued As: IB ST-4 DOCUMENT SUBMITTAL REQUIREMENTS FOR AN

More information

BUILDING STANDARDS BUILDING AND DEVELOPMENT PERMIT APPLICATION DRAWING REQUIREMENTS

BUILDING STANDARDS BUILDING AND DEVELOPMENT PERMIT APPLICATION DRAWING REQUIREMENTS Building and Development Permit Applications Definitions: Type A Residential Projects: All projects related to one and two unit dwellings Type B Residential Projects: All projects related to Apartments,

More information

ADMINISTRATION DEPARTMENT Plant Management Division. An Inventory of Its State Office Building Drawings

ADMINISTRATION DEPARTMENT Plant Management Division. An Inventory of Its State Office Building Drawings MINNESOTA HISTORICAL SOCIETY Minnesota State Archives ADMINISTRATION DEPARTMENT Plant Management Division An Inventory of Its State Office Building Drawings OVERVIEW OF THE RECORDS Agency: Minnesota. Dept.

More information

CHAPTER 5 ARCHITECTURE

CHAPTER 5 ARCHITECTURE CHAPTER 5 ARCHITECTURE 5.1 GENERAL... 4 5.2 CONCEPT/PROJECT DEFINITION DESIGN (30%) SUBMITTAL REQUIREMENTS... 4 5.2.1 DESIGN ANALYSIS... 4 5.2.1.1 Design Criteria... 4 5.2.1.2 Narratives... 4 5.2.1.2.1

More information

Dimension Below are the critical settings in AutoCAD. Other software should follow the same settings.

Dimension Below are the critical settings in AutoCAD. Other software should follow the same settings. 8.1 Drawing Standard 8.1.1 Introduction This drawing standard applies to all building drawings being prepared for the University of Calgary (UCalgary) by external consultants or vendors and internal staff

More information

INVITATION TO TENDER ITT No. PS FIRE HALL 5 + HOUSING CONSTRUCTION. ADDENDUM No. 2 and AMENDMENT No. 2

INVITATION TO TENDER ITT No. PS FIRE HALL 5 + HOUSING CONSTRUCTION. ADDENDUM No. 2 and AMENDMENT No. 2 FINANCE, RISK AND BUSINESS PLANNING Supply Chain Management May 17, 2016 INVITATION TO TENDER ITT No. PS20160468 FIRE HALL 5 + HOUSING CONSTRUCTION ADDENDUM No. 2 and AMENDMENT No. 2 RE: Various additions

More information

HAMMEL ASSOCIATES ARCHITECTS, LLC 2 5 E A S T G R A N T S T R E E T, S U I T E L A N C A S T E R, P E N N S Y L V A N I A

HAMMEL ASSOCIATES ARCHITECTS, LLC 2 5 E A S T G R A N T S T R E E T, S U I T E L A N C A S T E R, P E N N S Y L V A N I A CHL ASSOCIATES ARCHITECTURE 1 5 7 0 R I V E R R O A D, M A R I E T T A, P E N N S Y L V A N I A 1 7 5 4 7 HAMMEL ASSOCIATES ARCHITECTS, LLC 2 5 E A S T G R A N T S T R E E T, S U I T E 1 0 2 L A N C A

More information

Addendum No. 1 page 1

Addendum No. 1 page 1 Addendum No. 1 page 1 Project: Proj. No: 1634.02 Scottsburg High School HVAC Renovation 2017 Scott County School District 2 Scottsburg, Indiana Date: November 22, 2016 This addendum is a part of the bid

More information