1 DEEP-DECK PANEL INSTALLATION DETAILS
2 INDEX INDEX INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INTRODUCTION TO TYPICAL DETAILS OVERVIEW DD PANEL ASTENER LOCATIONS OAM CLOSURE DETAILS DD-0 DD-1 DD-I-1 DD-I-2 DD-I-3 DD-I-4 DD-2 DD-3 DD-4 DD-5 EAVE DETAIL; EAVE DETAIL; OPEN RAMING EAVE DETAIL; W/WALL PANEL; OPEN RAMING DD-10 DD-11 DD-12 HIP RIDGE; SHED ROO RIDGE HIP RIDGE; OPEN RAMING SHED RIDGE DETAIL RIDGE TERMINATION AT DORMER VALLEY GABLE; GABLE; WITH WALL PANEL; OPEN RAMING DD-20 DD-21 DD-22 DD-23 DD-24 DD-30 DD-31 HEAD WALL; WITH PARAPET HEAD WALL; WITH WALL PANEL HEAD WALL; WITH REGLET RAKE WALL; WITH WALL PANEL RAKE WALL; WITH WALL PANEL RAKE WALL; WITH REGLET SLOPE TRANSITION WITH LASHING DD-40 DD-41 DD-42 DD-50 DD-51 DD-52 DD-60 VALLEY VALLEY; OPEN RAMING DD-70 DD-71 INDEX DATE: DD-0
3 ROO PENETRATION; PIPE PENETRATION ROO PENETRATION; SQUARE (PLAN VIEW) ROO PENETRATION; SIDE A ROO PENETRATION; SIDE B ROO PENETRATION; SIDE C ROO PENETRATION; LARGER THAN 4"; OPEN RAMING DD-80 DD-81 DD-82 DD-83 DD-84 DD-85 GRADE DETAIL; OPEN RAMING GRADE DETAIL OUTSIDE CORNER; OPEN RAMING OUTSIDE CORNER; INSIDE CORNER; OPEN RAMING INSIDE CORNER; DD-100 DD-101 DD-102 DD-103 DD-104 DD-105 HEAD DETAIL; OPEN RAMING HEAD DETAIL; JAMB DETAIL; OPEN RAMING JAMB DETAIL; SILL DETAIL; OPEN RAMING DD-106 DD-107 DD-108 DD-109 DD-110 INDEX DATE: DD-1
4 A. DEEP-DECK PANEL: PANEL IS ACTORY ABRICATED TO A CONSTANT CORRUGATION DEPTH O 1-1/2" PANEL COVERAGE O A NOMINAL 36" PANELS ARE ABRICATED TO A MINIMUM LENGTH O 5'-0" AND A MAXIMUM LENGTH O 40'-0". B. C. MINIMUM SLOPE: THE DEEP-DECK PANELS ARE RECOMMENDED OR ROO SLOPES O 3 ON 12 OR GREATER. SLOPES LESS CONSULT. MATERIAL STORAGE: CAUTION MUST BE EXERCISED IN STORAGE O MATERIAL PRIOR TO INSTALLATION. KEEP ALL PREINISHED MATERIAL IN A DRY LOCATION WITH ADEQUATE VENTILATION AND OUT O DIRECT SUNLIGHT. EXPOSURE TO DIRECT SUNLIGHT AND/OR MOISTURE MAY CAUSE THE ACTORY APPLIED STRIPPABLE PLASTIC ILM TO ADHERE TO THE METAL PERMANENTLY AND DISCOLOR THE INISH. I THIS SHOULD OCCUR THE PAINT WARRANTY WILL BE VOID. D. E. STRIPPABLE ILM: THE STRIPPABLE PLASTIC ILM, WHICH IS APPLIED OVER MOST PREINISHED PRODUCTS, PANELS, LASHINGS, COILS AND LAT SHEETS, PROVIDES PROTECTION O THE INISH DURING ABRICATION AND TRANSIT. THIS ILM MUST BE REMOVED PRIOR TO INSTALLATION. REQUIREMENTS: RECOMMENDS THE USE O EITHER 24 GA. CORRUGATED SHEATHING (NOMINAL 2-1/2" PITCH BY 7/8" DEPTH) OR A MINIMUM O 1/2" PLYWOOD SHEATHING TO PROVIDE SUICIENT HOLDING POWER OR ASTENERS. CONTACT S ENGINEERING DEPARTMENT OR USE O ANY OTHER TYPE O, (# 30 ELT UNDERLAYMENT OR EQUAL MUST BE USED OVER ANY ). DUE TO # 30 ELT TENDENCY TO TEAR WHEN USED OVER CORRUGATED DECKING, RECOMMENDS GRACE ICE AND WATERSHIELD OR EQUAL TO BE USED AS AN UNDERLAYMENT OR ALL CORRUGATED DECKS.. G. SHEATHING INSPECTION: 1. SHEATHING END JOINTS SHOULD BE STAGGERED. 2. ALL END JOINTS SHOULD MEET AT EITHER A JOIST OR RATER. 3. BLOCKING O "H" CLIPS SHOULD BE USED O JOINTS DO NOT REMAIN LAT UNDER THE WEIGHT O WORKMEN. 4. USE SHIMS TO KEEP ENTIRE SUBSTRATE EVEN; UNEVEN SUBSTRATE WILL RESULT IN "OIL- CANNING" IN THE PANELS. SUBSTRATE SHOULD BE LEVEL TO 1/4" ON 20'-0". 5. ALL CUTS AT PENETRATIONS SHOULD BE TIGHT, WITHOUT GAPS. 6. USE WOOD RAMED CRICKETS AT LARGE PENETRATIONS. 7. MAKE SURE SUBSTRATE JOINTS ARE TIGHT AT ALL HIPS, VALLEYS AND RIDGES. INSTALLATION OVER OPEN RAMING: OR DIAPHRAGM CAPABILITIES O DEEP-DECK PANEL CONSULT TECHNICAL DEPT. PURLIN OR OTHER STRUCTURAL BRACING IS THE RESPONSIBILITY O OTHERS, INSTALLATION INSTRUCTIONS DATE: DDI-1
5 H. I. J. OPEN RAMING INSPECTION: 1. PURLINS SHOULD BE ALIGNED WITH TOP LANGES IN THE SAME PLANE TO A TOLERANCE O 1/4" IN 20'-0". UNEVENNESS IN THE TOP PLANE O THE PURLINS WILL RESULT IN ABNORMAL "OIL-CANNING" O PANELS. PURLINS SHALL BE ADEQUATELY BRACED. 2. RECOMMENDS IN VALLEY AND AROUND ROO PENETRATIONS. DO NOT APPLY PANELS ON OPEN RAMING AT VALLEYS OR ROO PENETRATIONS WITHOUT REERRING TO DETAILS DD-71 AND DD OOT TRAIC ON THE PANELS MUST BE KEPT TO A MINIMUM. ARCHITECTURAL PANELS ARE DESIGNED OR AESTHETICS AND CAN BE EASILY DAMAGED OR DEORMED I EXTREME CARE IS NOT USED. ASCIA/RAKE INSPECTION: 1. STRIKE A LINE THE ULL LENGTH O THE ASCIA OR RAKE. I NOT STRAIGHT, CORRECT WITH SHIMS. 2. MAKE SURE ASCIA/RAKE IS LUSH WITH SHEATHING ELT UNDERLAYMENT: A SINGLE LAYER O NUMBER THIRTY ELT UNDERLAYMENT (OR EQUAL) MUST BE APPLIED OVER, AS SHOWN IN THE TYPICAL ELTING DETAILS. THE USE O ADDITIONAL LAYERS O NUMBER THIRTY ELT IS RECOMMENDED ON LOW SLOPED ROOS, AT ALL VALLEY CONDITIONS, AT ROO PENETRATIONS AND AT CERTAIN OTHER LASHING CONDITIONS AS DEPICTED IN THE DEEP- DECK PANEL TYPICAL DETAILS. GRACE ICE AND WATERSHIELD MAY BE REQUIRED ON LOW SLOPED ROOS OR AT CERTAIN LASHING CONDITIONS. K. L. M. ELTING INSTALLATION: 1. DO NOT USE RED ROSIN PAPER UNDER METAL ROOING PANELS. 2. SWEEP ROO AREA CLEAN. 3. USE LAT HEAD GALVANIZED ROOING NAILS 1-1/4" LONG WITH GALVANIZED ELT CAPS. 4. INSTALL VALLEY ELT IRST. 5. INSTALL ELT PARALLEL TO THE EAVE, (2 LAYERS REQUIRED AT EAVE) STARTING AT EAVE AND USING MINIMUM 6" LAPS. USE 2 LAYERS O ELT ON ENTIRE ROO DECK I ROO SLOPE IS 3 ON REER TO ELTING DETAILS WHEN VALLEYS OR ROO PENETRATIONS ARE INVOLVED ON OPEN RAMING CONDITIONS. 7. INSULATE BETWEEN WOOD BLOCKING AND METAL WITH ELT OR GRACE ICE AND WATERSHIELD. 8. VERIY CORRECT METHOD O INSTALLING ICE AND WATERSHIED WITH ICE AND WATERSHIELD MANUACTURE. ELECTROLYSIS: AVOID ALLOWING LASHINGS AND PANELS TO COME INTO CONTACT WITH EITHER LEAD, COPPER OR OTHER DISSIMILAR METALS AND PREVENT EXPOSURE TO WATER RUNDOWN ROM COPPER AND/OR LEAD. SEALANT RECOMMENDATIONS: TREMCO, INC. SPECTREM 1 SILICONE SEALANT. DO NOT USE CLEAR CAULK. INSTALLATION INSTRUCTIONS DATE: DDI-2
6 N. O. P. Q. R. LASHING: I IS TO SUPPLY LASHING, ALL LASHINGS WILL BE ABRICATED IN 10'-0" LENGTHS WITH SQUARE END CUTS ONLY. THE PURCHASER MUST PROVIDE ALL DIMENSIONS AND DEGREES O ANGLE. LASHING INSTALLATION: 1. REMOVE STRIPPABLE PLASTIC ILM ROM ALL LASHINGS PRIOR TO INSTALLATION. 2. ALWAYS STAGGER JOINTS WHEN ONE LASHING IS INSTALLED OVER OTHER LASHINGS. 3. INSTALL ALL LASHINGS AS PER TYPICAL DETAILS. 4. ALL LASHINGS ARE TO BE DESIGNED AND INSTALLED TO AVOID TRAPPING WATER. PANELS: WILL PROVIDE SQUARE END CUTS ONLY ON ALL DEEP-DECK PANELS. COMPUTATION O ALL QUANTITIES AND DIMENSIONS ARE THE RESPONSIBILITY O THE PURCHASER. PANEL INSTALLATION: 1. REMOVE STRIPPABLE PLASTIC ILM ROM EACH PANEL PRIOR TO INSTALLATION. 2. START AT ONE GABLE END O THE ROO AND WORK TOWARD THE OTHER GABLE. 3. EACH PANEL IS TO BE KEPT TIGHT AGAINST THE ADJOINING PANEL. NEVER PERMIT A GAP BETWEEN VERTICAL LAP. ANY CRIMPS OR BENDS MUST BE STRAIGHTENED PRIOR INSTALLATION. 4. KEEP PANELS ALIGNED TO THAT RIBS MATCH AT HIPS, VALLEYS AND WHERE VERTICAL PANELS ADJOIN ROO PANELS. DO NOT INSTALL LONG CONTINUOUS RUNS O PANELS ALL AT ONE TIME WHERE RIB LINES MUST MATCH. INSTALL EN OR TWELVE PANELS IN ONE ELEVATION AND THEN OLLOW WITH A LIKE NUMBER O PANELS ON THE OTHER ELEVATION. WHEN YOU INSTALL PANELS IN THIS MANNER, YOU WILL BE ABLE TO MAKE ANY ADJUSTMENTS REQUIRED TO INSURE RIB MATCHING. 5. COPPER-COTE, CHAMPAGNE, LEAD-COTE AND PREWEATHERED GALVALUME PANEL INSTALLATION: NOTE THE SERIES O ARROWS PAINTED ON THE UNDERSIDE O THE PANEL. ALL PANELS MUST BE INSTALLED IN A CONSISTENT MANNER, MEANING THAT THE ARROWS ON EVERY PANEL ARE ALL POINTING IN THE SAME DIRECTION. I A PANEL IS REVERSED (ARROWS POINTING OPPOSITE I THOSE ON OTHER PANELS) IT WILL APPEAR, ROM A DISTANCE, A DIERENT SHADE DUE TO THE GRANULAR EECTS O THE PIGMENTS ON THE INISH. METALLIC INISHES ARE MATCH-LOT INISHES. DO NOT MIX LOTS. ASTENERS: INSTALL ASTENERS AS PER TYPICAL DETAILS. USE #10 HEX HEAD ZINC PLATED ASTENER WITH METAL BACKED NEOPRENE ASTENER WHEN ASTENING TO WOOD. USE #12 HEX HEAD ZINC PLATED ASTENER WITH A METAL WHEN ASTENING TO METAL* WHEN USING POP RIVETS ON LASHING, STAINLESS STEEL RIVETS ARE RECOMMENDED TO AVOID RUST STAINS. MAKE SURE ALL ASTENERS ARE DRIVEN STRAIGHT AND SET LAT, DO NOT OVER DRIVE ASTENERS AS THIS WILL CAUSE THE CLIP AND/OR LASHINGS TO BUCKLE OR BECOME RECESSED BELOW THE ELEVATION O THE SUBSTRATE. * CONSULT S ENGINEERING DEPARTMENT REGARDING ASTENER SPACING TO MEET DESIGN CRITERIA AND THE USE O ANY OTHER TYPE O ASTENER. INSTALLATION INSTRUCTIONS DATE: DDI-3
7 STRIVES TO PROVIDE ITS CUSTOMERS WITH THE HIGHEST QUALITY STRETCHER LEVELED STEEL AVAILABLE. THE LATEST TECHNOLOGY IS ALSO INCORPORATED IN 'S HIGH-PRECISION COIL HANDLING AND ROLL ORMING EQUIPMENT TO MINIMIZE THE STRESS ON METAL DURING PRODUCTION. URTHERMORE, UTILIZES HEAVIER 24 GAUGE METAL RATHER THAN 26 GAUGE STEEL TO LIGHT GAUGE ALUMINUM AS OERED BY MANY COMPETITORS. ALL THESE MEASURES HAVE BEEN TAKEN TO MINIMIZE THE AMOUNT O "OIL0CANNING" (WAVINESS) WHICH IS NATURALLY INHERENT IN LAT SHEET METAL. MANY TIMES, HOWEVER, THE CAUSE O WAVINESS OR "OIL-CANNING" CAN BE TRACED TO UNEVEN SHEATHING, IMPROPER ELT INSTALLATION OR, IN THE CASE O OPEN RAMING, UNEVENNESS O THE TOP PLANE O THE PURLINS OR OOT TRAIC ON THE PANELS. ALL ARCHITECTURAL PANELS REQUIRE CARE IN HANDLING AND INSTALLATION TO AVOID DAMAGING OR DEORMING THE PANELS. THESE INSTALLATION INSTRUCTIONS AND THE OLLOWING TYPICAL DETAILS ARE INTENDED TO PROVIDE OUR CUSTOMERS WITH THE INORMATION REQUIRED OR AN AESTHETICALLY PLEASING AND UNCTIONAL INSTALLATION O THE DEEP-DECK PANEL SYSTEM. NOTE: ALL PRODUCT SPECIICATIONS, DETAIL AND INSTALLATION INSTRUCTIONS SUBJECT TO CHANGE WITHOUT NOTICE. OR SPECIIC PROJECT DETAILS, CONTACT. INSTALLATION INSTRUCTIONS DATE: DDI-4
8 DEEP DECK PANEL PROPERTIES GA. 24 Tkns/INCH WT PS 1.21 Y KSI 40 TOP IN COMPRESSION BOTTOM IN COMPRESSION Ix In 4 /ft Sx In 3 /ft Ma In-kip/ft Ix In 4 /ft Sx In 3 /ft Ma In-kip/ft SPAN (EET) STRESS DEEP-DECK PANEL LOAD PROILES DEAD + LIVE LOADING (PS) 1-SPAN 2-SPAN 3-SPAN DEL L/240 STRESS DEL L/240 STRESS DEL L/ DEEP-DECK WIND UPLIT LOADING (PS) SPAN (EET) STRESS 1-SPAN 2-SPAN 3-SPAN DEL L/240 STRESS DEL L/240 STRESS DEL L/ NOTES: 1. THE PANEL WEIGHT HAS BEEN DEDUCTED ROM THE ALLOWABLE STRESS VALUES. 2. THE PROPERTIES AND LOAD TABLES ARE OR THE PANEL ALONE: THE PANEL PROILE HAS BEEN ASSUMED TO REMAIN CONSTANT UNDER LOADING. THE CAPACITY O ASTENERS IS NOT INCLUDED. 3. THE PANEL SECTION PROPERTIES HAVE BEEN CALCULATED IN ACCORDANCE WITH THE 2001 AISI SPECIICATION. INSTALLATION INSTRUCTIONS DATE: DDI-5
9 THE DETAILS CONTAINED IN THE OLLOWING PAGES ARE MERELY RECOMMENDATIONS AS TO HOW MATERIALS SHOULD BE INSTALLED. THEY MAY REQUIRE ADAPTATIONS OR MODIICATIONS OR A SPECIIC PROJECT AS CONDITIONS VARY IN BOTH BUILDING DESIGN AND LOCAL WEATHER PECULIARITIES. SHALL BE HELD HARMLESS ROM ANY AND ALL CLAIMS ARISING ROM LACK O WATERTIGHTNESS AS A RESULT O OLLOWING THESE RECOMMENDED DETAILS. ENSURING WATERTIGHTNESS ON ANY GIVEN PROJECT IS THE UNCTION O THE INSTALLER. THE ARCHITECT/GENERAL CONTRACTOR/INSTALLER MUST ACCEPT THE RESPONSIBILITY TO ADAPT THESE DETAILS TO MEET PARTICULAR BUILDING REQUIREMENTS AND TO ASSURE ADEQUATE WATERTIGHTNESS. THE INSTALLER CAN VIRTUALLY ASSURE WATERTIGHTNESS I THESE LASHING DETAILS HAVE BEEN PROPERLY ADAPTED, ADEQUATE LAPS HAVE BEEN PROVIDED, CORRECT TYPE O SEALANT USED, ALL JOINTS ADEQUATELY CAULKED, AND PROESSIONAL WORKMANSHIP EMPLOYED. INTRODUCTION TO TYPICAL DETAILS DD-2
10 DEEP-DECK PANEL SCREW WITH STEEL AND NEOPRENE WASHER 1" TAPE SEALER CONTINUOUS 36" 7.2" 1.94" 42 1" 1.5" OVERVIEW DEEP-DECK PANEL 1.94" 1.34" DEEP-DECK PANEL SCREW WITH STEEL AND NEOPRENE WASHER 1" TAPE SEALER CONTINUOUS SIDE LAP DETAIL (TYPICAL) OVERVIEW DD-3
11 36" 5 ASTENERS LOCATED AS SHOWN ASTENERS SPACING AT END LAP DEEP-DECK PANEL SCREW WITH STEEL AND NEOPRENE WASHER 6" 1" TAPE SEALER CONTINUOUS SCREW WITH STEEL AND NEOPRENE WASHER PANEL END LAP 36" 5 ASTENERS LOCATED AS SHOWN INTERMEDIATE ASTENER SPACING DEEP-DECK PANEL SCREW WITH STEEL AND NEOPRENE WASHER SCREW WITH STEEL AND NEOPRENE WASHER 1" TAPE SEALER CONTINUOUS SIDE LAP DETAIL (TYPICAL) 36" 10 ASTENERS LOCATED AS SHOWN ASTENERS SPACING AT EAVE DEEP-DECK PANEL ASTENERS AT RIB 6" O.C. OR IRST 5'-0" UP ROO SCREW WITH STEEL AND NEOPRENE WASHER ASTENER LOCATIONS DD-4
12 DEEP-DECK PANEL INSIDE OAM CLOSURE WITH TAPE SEALER TOP & BOTTOM PANEL ASTENER WITH METAL EAVE LASHING, 4" END LAPS WITH CONTINUOUS CAULK AT LAPS # 30 ELT UNDERLAYMENT ASTENERS, 20" O.C. MAX. 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. MIN. 1" = INISH SIDE 1/2" EAVE LASHING EAVE DETAIL DD-10
13 DEEP-DECK PANEL INSIDE OAM CLOSURE WITH TAPE SEALER TOP & BOTTOM PANEL ASTENER WITH METAL 30# ELT UNDERLAYMENT EAVE LASHING, 4" END LAPS WITH CONTINUOUS CAULK AT LAPS WALL PANEL ASTENERS, 20" O.C. MAX. 30# ELT UNDERLAYMENT 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. MIN. 1" = INISH SIDE 1/2" EAVE LASHING EAVE DETAIL DD-11
14 DEEP-DECK PANEL INSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM PANEL ASTENER WITH METAL OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM ASTENER WITH METAL 20" O.C. EAVE LASHING, 4" END LAPS WITH CONTINUOUS CAULK AT LAPS EAVE STRUT ASTENERS, 20" O.C. MAX. DEEP-DECK PANEL 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. MIN. 1" = INISH SIDE 1/2" EAVE LASHING EAVE DETAIL OPEN RAMING DD-12
15 RIDGE/HIP CAP; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS. POP RIVET AT LAPS AND CAULK RIVET HEADS. DEEP-DECK PANEL PANEL ASTENER WITH METAL BACKED NEOPRENE WASHER ASTENERS WITH METAL BACKED NEOPRENE WASHER 20" O.C. OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. USE EXPANDABLE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM AT HIPS # 30 ELT UNDERLAYMENT 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELTING UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1/2" 1/2" RIDGE/HIP CAP RIDGE AND HIP DETAIL DD-20
16 RIDGE CAP; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS. POP RIVET AT LAPS AND CAULK RIVET HEADS. DEEP-DECK PANEL ASTENERS WITH METAL BACKED NEOPRENE WASHER 20" O.C. OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM PANEL ASTENER WITH METAL BACKED NEOPRENE WASHER ASTENER WITH METAL BACKED NEOPRENE WASHER. 40" O.C. MAX # 30 ELT UNDERLAYMENT LAP ELT OVER RIDGE 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELTING UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1/2" RIDGE CAP 1/2" SHED ROO RIDGE CAP DETAIL DD-21
17 RIDGE/HIP CAP; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS. DEEP-DECK PANEL OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. USE EXPANDABLE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM AT HIPS PANEL ASTENER WITH METAL BACKED NEOPRENE WASHER ASTENERS WITH METAL BACKED NEOPRENE WASHER 20" O.C. SUB LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS PURLINS 1. ALL CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1/2" 1/2" SUB LASHING RIDGE/HIP CAP RIDGE AND HIP DETAIL OPEN RAMING DD-22
18 1/2" METAL BUILDING RIDGE CAP; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS. SUB LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS DEEP-DECK PANEL PANEL ASTENER WITH METAL BACKED NEOPRENE WASHER ASTENERS WITH METAL BACKED NEOPRENE WASHER 20" O.C. ASTENER 20" O.C. OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. PANEL ASTENER WITH METAL BACKED NEOPRENE WASHER ASTENER 20" O.C. DEEP-DECK PANEL 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1/2" SUB LASHING RIDGE CAP SHED RIDGE DETAIL OPEN RAMING DD-23
19 SECTION VIEW IELD ORM END O RIDGE LASHING AND EXTEND UNDER UPPER PANEL DEEP-DECK PANEL RIDGE LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS IELD TAPERED OUTSIDE CLOSURE EXPANDABLE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM DD-20 # 30 ELT UNDERLAYMENT VALLEY LASHING; 12" LAPS WITH CONTINUOUS CAULK AT LAPS PANEL ASTENER WITH METAL BACKED NEOPRENE WASHER PLAN VIEW MAIN ROO PANELS RIDGE LASHING INSIDE OAM CLOSURE VALLEY LASHING DORMER PANEL RIDGE TERMINATION AT DORMER VALLEY DD-24
20 GABLE CHANNEL 4" END LAPS WITH CONTINUOUS CAULK AT LAPS CONTINUOUS BEAD O CAULK ASTENER WITH METAL BACKED NEOPRENE WASHER 20" O.C. DEEP-DECK PANEL ASTENERS; 20" O.C. MAX. 1/2" GABLE LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS # 30 ELT UNDERLAYMENT TOP LAYER O ELT TO BE PARALLEL WITH ROO SLOPE ASTENERS; 20" O.C. MAX. 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1/2" 1/2" GABLE CHANNEL GABLE LASHING GABLE DETAIL DD-30
21 ASTENER WITH METAL 20" O.C. GABLE LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS PANEL ASTENER WITH METAL OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM ASTENER WITH METAL 20" O.C. PURLIN CONTINUOUS BEAD O CAULK ASTENERS, AT EVERY PURLIN DEEP-DECK PANEL STRUCTURAL ANGLE DEEP-DECK PANEL 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. 1/2" = INISH SIDE 1/2" GABLE LASHING GABLE DETAIL OPEN RAMING DD-31
22 CAP LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS. POP RIVET TO COUNTER LASHING 40" O.C. MAX. CAULK ALL RIVET HEADS ASTENERS; 20" O.C. MAX. COUNTERLASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS SUB-LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS # 30 ELT UNDERLAYMENT OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM DEEP-DECK PANEL 1 ON 12 ASTENERS AT LAPS AND STAGGERED; 20" O.C. AND CAULK ASTENER HEADS # 30 ELT UNDERLAYMENT ASTENERS; WITH METAL BACKED NEOPRENE WASHER. 40" O.C. MAX. PANEL ASTENERS; WITH METAL BACKED NEOPRENE WASHER. ASTENERS; WITH METAL BACKED NEOPRENE WASHER. 20" O.C. MAX. 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1 ON 12 1/2" COUNTERLASHING SUB-LASHING CAP LASHING PARAPET DETAIL DD-40
23 DEEP-DECK PANEL COUNTERLASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS. SUB-LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS INSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. ASTENERS; 20" O.C. MAX. OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. ASTENERS; WITH METAL BACKED NEOPRENE WASHER. 20" O.C. DEEP-DECK PANEL PANEL ASTENERS; WITH METAL BACKED NEOPRENE WASHER PANEL ASTENERS; WITH METAL BACKED NEOPRENE WASHER 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1/2" COUNTERLASHING SUB-LASHING HEAD WALL DETAIL OPEN RAMING DD-41
24 REGLET LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS ASTENERS; 20" O.C. MAX. COUNTERLASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS. REGLET CONTINUOUS CAULK AT REGLET SUB-LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS DEEP-DECK PANEL OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. CONTINUOUS BEAD O CAULK PANEL ASTENERS WITH METAL BACKED NEOPRENE WASHER. ASTENERS WITH METAL BACKED NEOPRENE WASHER. 20" O.C. 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1/2" COUNTERLASHING SUB-LASHING REGLET LASHING HEAD WALL DETAIL OPEN RAMING DD-42
25 # 30 ELT UNDERLAYMENT ASTENERS 20" O.C. MAX. CONTINUOUS SUB LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS WALL PANEL COUNTER LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS SPECIAL CHANNEL CLOSURE BUTT END JOINTS OR WEEP ASTENER WITH METAL 20" O.C. CONTINUOUS BEAD O CAULK DEEP-DECK PANEL TOP LAYER O ELT TO BE PARALLEL WITH ROO SLOPE ASTENER 20" O.C. # 30 ELT UNDERLAYMENT 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE SPECIAL CHANNEL SUB LASHING COUNTER LASHING RAKE WALL WITH WALL PANEL DD-50
26 DEEP-DECK PANEL ASTENERS 20" O.C. MAX PANEL ASTENER WITH METAL ASTENERS 20" O.C. MAX PURLIN INSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM COUNTER LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS ASTENER WITH METAL BACKED NEOPRENE WASHER 20" O.C. CONTINUOUS BEAD O CAULK DEEP-DECK PANEL SUB LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS PURLIN ASTENERS 20" O.C. MAX 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE SUB LASHING COUNTER LASHING RAKE WALL DETAIL OPEN RAMING DD-51
27 CONTINUOUS CAULK AT REGLET SAW CUT REGLET # 30 ELT UNDERLAYMENT ASTENERS 20" O.C. MAX CONTINUOUS SUB LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS REGLET LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS CONTINUOUS BEAD O CAULK COUNTER LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS ASTENER WITH METAL 20" O.C. CONTINUOUS BEAD O CAULK DEEP-DECK PANEL TOP LAYER O ELT TO BE PARALLEL WITH ROO SLOPE ASTENER 20" O.C. # 30 ELT UNDERLAYMENT 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE SUB LASHING COUNTER LASHING RAKE WALL DETAIL WITH REGLET REGLET LASHING DD-52
28 DEEP-DECK PANEL UPPER PANEL PANEL ASTENERS; WITH METAL INSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM 1 ON 12 MIN. SLOPE AWAY ROM UPER PANEL TRANSITION LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS DEEP-DECK LOWER PANEL ASTENERS; 40" O.C. # 30 ELT UNDERLAYMENT ASTENER 20" O.C. PLACE A DAB O CAULK AT ASTENER LOCATION, DRIVE ASTENER THROUGH CAULK AND CAULK ASTENER HEADS. SUB-LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS PANEL ASTENERS; WITH METAL ASTENERS; WITH METAL. 20" O.C. OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. 1/2" 10" MIN. = INISH SIDE TRANSITION LASHING SUB-LASHING SLOPE TRANSITION DETAIL DD-60
29 DEEP-DECK PANEL CONTINUOUS BEAD O CAULK BETWEEN VALLEY LASHING AND ELT UNDERLAYMENT EXPANDABLE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM ASTENERS 20" O.C. MAX. 9" MIN. # 30 ELT UNDERLAYMENT VALLEY LASHING 12" END LAPS WITH (2) CONTINUOUS BEADS CAULK AT LAPS PANEL ASTENER WITH METAL BACKED NEOPRENE WASHER 1. (BY OTHERS) TO BE A MINIMUM O 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1/2" 20-1/2" MIN. VALLEY LASHING VALLEY DETAIL DD-70
30 DEEP-DECK PANEL CONTINUOUS BEAD O CAULK BETWEEN VALLEY LASHING AND ELT UNDERLAYMENT EXPANDABLE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM ASTENERS 20" O.C. MAX. 9" MIN. GRACE ICE AND WATERSHIELD VALLEY LASHING 12" END LAPS WITH (2) CONTINUOUS BEADS CAULK AT LAPS LAT SHEET VALLEY SUB-LASHING CORRUGATED S-DECK PANEL ASTENER WITH METAL BACKED NEOPRENE WASHER GRACE ICE AND WATER SHIELD RUN RIDGE TO EAVE LAT SHEET VALLEY SUB-LASHING RUN RIDGE TO EAVE SEE SECTION SLOPE LAT SHEET VALLEY SUB-LASHING GRACE ICE AND WATER SHIELD CORRUGATED S-DECK RIDGE EACH SIDE 16 GA. HAT SECTION PURLIN EAVE CORRUGATED S-DECK SECTION SLOPE 16 GA. HAT SECTION SIZED TO IT OVER PURLIN AND TO ACCOMMODATE THE DEPTH O THE CORRUGATED S-DECK. PURLINS ROOS WITH A SLOPE O 4:12 OR LESS 6'-0" MIN. ROOS ABOVE 4:12 3'-0" MIN. VALLEY DETAIL OPEN RAMING DD-71
31 ROO PIPE PENETRATION O 4" IN DIA. OR LESS RUBBERIZED BOOT LASHING CONTINUOUS CAULK PIPE PENETRATION NOT TO BE AT PANEL SIDE LAP DEEP-DECK PANEL SET RUBBERIZED BOOT INTO CONTINUOUS BEAD O CAULK. USE ASTENERS AS SPECIIED BY BOOT MANUACTURER. CAULK ASTENER HEADS TOP O PURLIN CUT PANEL 1" SMALLER THAN PENETRATION, BACK CUT TABS, OLD TABS UP AROUND PENETRATION, AND CAULK. NOTE: I PIPE IS MADE O METAL, IT MUST BE PAINTED TO PREVENT RUST RUN-O ROM STAINING PANELS. NOTE: POSITION SQUARE BASED BOOTS IN A DIAMOND ORIENTATION WHERE POSSIBLE TO AID IN DIVERTING WATER. PIPE PENETRATION (PREERRED METHOD) IN PAN O PANEL ONLY - 4" DIA. OR LESS DD-80
32 C B DETAIL DD-84 DEEP-DECK PANEL INSIDE OAM CLOSURE INSTALL ATER LASHING "C" OUTSIDE OAM CLOSURE INSTALL BEORE LASHING "A" IELD CUT PANEL ALONG LINE DETAIL DD-82 DETAIL DD-83 CONTINUOUS BEAD O CAULK AT ALL LASHING LAPS A B IELD CUT PANEL ALONG DOTTED LINE AND INSTALL PANEL. INSTALL LASHING "A" IRST ALONG WITH OAM CLOSURE. INSTALL LASHING "B" SECOND. CAULK ALL LASHING LAPS. INSTALL LASHING"C" LAST. THIS LASHING IS TO BE SLIPPED UNDER THE DEEP-DECK PANEL AND ELT AS SHOWN IN DETAIL DEEP-DECK-84 BEORE THE OAM CLOSURE OR ASTENERS ARE INSTALLED. SEE ALSO DETAILS DEEP-DECK-82 AND DEEP-DECK-83 OR ELTING AND SUBLASHING. ROO PENETRATION DD-81
33 ASTENERS; 20" O.C. MAX. COUNTERLASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS LASHING ROM MECHANICAL EQUIPMENT BY OTHERS PANEL ASTENERS WITH METAL BACKED NEOPRENE WASHER. OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM DEEP-DECK PANEL CONTINUOUS ANGLE LASHING TYPICAL ALL 4 SIDES O PENETRATION # 30 ELT UNDERLAYMENT TOP LAYER O # 30 ELT UNDERLAYMENT TO BE PERPENDICULAR TO ROO SLOPE ASTENERS WITH METAL BACKED NEOPRENE WASHER. 20" O.C. MAX. 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE 1/2" 8" 8" COUNTER LASHING SIDE A ANGLE LASHING ROO PENETRATION SIDE A DD-82
34 LASHING ROM MECHANICAL EQUIPMENT BY OTHERS ASTENERS; 20" O.C. TYP. # 30 ELT UNDERLAYMENT CONTINUOUS ANGLE TYPICAL ALL 4 SIDES O PENETRATION ASTENER WITH METAL 20" O.C. # 30 ELT UNDERLAYMENT COUNTER LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS CONTINUOUS BEAD O CAULK DEEP-DECK PANEL # 30 ELT UNDERLAYMENT TOP LAYER O ELT TO BE PARALLEL WITH ROO SLOPE ASTENER 20" O.C. 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE ANGLE LASHING SIDE B COUNTER LASHING ROO PENETRATION SIDE B DD-83
35 CONTINUOUS COUNTER LASHING INSTALL ATER PANEL INSTALLATION. SLIP LASHING UP UNDER ELT AND PANEL COUNTER LASHING ROM MECHANICAL EQUIPMENT BY OTHERS DEEP-DECK PANEL INSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM INSTALL ATER CONTINUOUS COUNTER LASHING # 30 ELT UNDERLAYMENT PANEL ASTENERS WITH METAL CONTINUOUS ANGLE LASHING TYPICAL ALL 4 SIDES O ROO PENETRATION SLIP COUNTER LASHING UNDER ELT BEORE ASTENING PANEL CONTINUOUS BEAD O CAULK BETWEEN LASHING AND ELT SCRAP DEEP-DECK PANEL UNDER COUNTER LASHING OR SUPPORT 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE ANGLE LASHING ROO PENETRATION SIDE C COUNTER LASHING SIDE C DD-84
36 1'-0" MINIMUM 1'-0" MINIMUM OR ROO PENETRATIONS LARGER THAN 4" IN DIA. CARRY UP TO NEXT PURLIN GRACE ICE AND WATER SHIELD RUN CONTINUOUS TO EAVE SQUARE OR ROUND PENETRATION LAT SHEET SUB-LASHING RUN CONTINUOUS TO EAVE SLOPE CORRUGATED S-DECK SEE SECTION PURLINS EAVE LAT SHEET SUB LASHING GRACE ICE AND WATER SHIELD 16 GA. HAT SECTION SIZE TO IT OVER PURLIN AND TO ACCOMMODATE THE DEPTH O THE CORRUGATED S-DECK. 16 GA. HAT SECTION PURLIN CORRUGATED S-DECK SECTION PENETRATION LARGER THAN 4" - OPEN RAMING DD-85
37 DEEP-DECK PANEL INSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM PANEL ASTENER WITH METAL GIRT SILL LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS, POP RIVET TO GIRT 20" O.C. 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE SILL LASHING GRADE DETAIL OPEN RAMING DD-100
38 # 30 ELT UNDERLAYMENT ASTENERS 20" O.C. MAX. PANEL ASTENER WITH METAL DEEP-DECK PANEL INSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. SILL LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE SILL LASHING GRADE DETAIL DD-101
39 OUTSIDE CORNER CAP; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS ASTENER WITH METAL 20" O.C. CONTINUOUS BEAD O CAULK GIRTS DEEP-DECK PANEL PANEL ASTENER WITH METAL ASTENER WITH METAL 20" O.C. CONTINUOUS BEAD O CAULK 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE OUTSIDE CORNER CAP OUTSIDE CORNER OPEN RAMING DD-102
40 OUTSIDE CORNER CAP; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS ASTENER WITH METAL 20" O.C. CONTINUOUS BEAD O CAULK 30 # ELT UNDERLAYMENT DEEP-DECK PANEL PANEL ASTENER WITH METAL ASTENER WITH METAL 20" O.C. CONTINUOUS BEAD O CAULK 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE OUTSIDE CORNER CAP OUTSIDE CORNER DD-103
41 RUN SNAP ON BATTEN UP TO STACK AND CAULK CONTINUOUS BEAD O CAULK CUT PANEL RIBS AND LAP TOP RIBS IN DIRECTION O WATER LOW RUN SNAP ON BATTEN UP TO STACK AND CAULK SECTION A PAGE B-82 ROO PENETRATION CENTERED ON SEAM ** ** SECTION B PAGE B-82 ROO PENETRATION O CENTER O SEAM **CALL BMC BEORE USING THIS DETAIL NOTE: CALL BMC BEORE USING DETAILS ON THIS PAGE. USE ONLY I PENETRATION OCCURS ON SEAM OR WITHIN AREA O PAN THAT WILL NOT ACCOMMODATE BOOT. USE WITH SOLID SUBSTRATE ONLY. BATTEN END CAP CONTINUOUS BEAD O CAULK CONTINUOUS BEAD O CAULK AROUND SEAM CAULK AT SNIPPED OPENINGS A NOTE: I PIPE IS MADE O METAL, IT MUST BE PAINTED TO PREVENT RUST RUN-O ROM STAINING PANELS. INSIDE CORNER OPEN RAMING DD-104
42 ASTENER WITH METAL 20" O.C. CONTINUOUS BEAD O CAULK INSIDE CORNER CAP; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS PANEL ASTENER WITH METAL DEEP-DECK PANEL ASTENER WITH METAL BACKED NEOPRENE WASHER 20" O.C. 30 # ELT UNDERLAYMENT CONTINUOUS BEAD O CAULK PANEL ASTENER WITH METAL 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE INSIDE CORNER CAP INSIDE CORNER DD-105
43 DEEP-DECK PANEL INSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM POP RIVET 20" O.C. MAX GIRT PANEL ASTENER WITH METAL HEAD LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS HEADER 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE HEAD LASHING HEAD DETAIL OPEN RAMING DD-106
44 # 30 ELT UNDERLAYMENT DEEP-DECK PANEL ASTENERS 20" O.C. MAX. PANEL ASTENER WITH METAL INSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. HEAD LASHING 4" END LAPS WITH CONTINUOUS CAULK AT LAPS HEADER 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE HEAD LASHING HEAD DETAIL DD-107
45 JAMB LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS ASTENER WITH METAL 20" O.C. CONTINUOUS BEAD O CAULK CONTINUOUS BEAD O CAULK GIRTS DEEP-DECK PANEL PANEL ASTENER WITH METAL JAMB 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE JAMB LASHING JAMB DETAIL OPEN RAMING DD-108
46 JAMB LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS ASTENER WITH METAL 20" O.C. CONTINUOUS BEAD O CAULK CONTINUOUS BEAD O CAULK 30 # ELT UNDERLAYMENT PANEL ASTENER WITH METAL DEEP-DECK PANEL JAMB 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE JAMB LASHING JAMB DETAIL DD-109
47 SILL CONTINUOUS BEAD O CAULK PANEL ASTENER WITH METAL ASTENER WITH METAL 20" O.C. GIRT SILL LASHING, 4" END LAPS WITH CONTINUOUS CAULK AT LAPS OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM DEEP-DECK PANEL 1. CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. SLOPE = INISH SIDE SILL LASHING SILL DETAIL OPEN RAMING DD-110
48 DEEP-DECK PANEL INSIDE CORNER LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS # 30 ELT UNDERLAYMENT OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. ASTENERS; WITH METAL BACKED NOEPRENE WASHER. 20" O.C. DEEP-DECK PANEL ASTENERS; WITH METAL BACKED NOEPRENE WASHER. 20" O.C. PANEL ASTENERS; WITH METAL BACKED NOEPRENE WASHER SUB-LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS PANEL ASTENERS; WITH METAL BACKED NOEPRENE WASHER 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE CORNER LASHING INSIDE CORNER DD-111
49 OUTSIDE CORNER LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS. PANEL ASTENERS; WITH METAL. ASTENERS; WITH METAL. 20" O.C. DEEP-DECK PANEL # 30 ELT UNDERLAYMENT OUSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. ASTENERS; WITH METAL. 20" O.C. ASTENERS; 20" O.C. MAX. DEEP-DECK PANEL 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING, AND ASTENERS, ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE OUTSIDE CORNER LASHING OUTSIDE CORNER D-112
50 DEEP-DECK PANEL 30 # ELT UNDERLAYMENT ASTENER 20" O.C. MAX. ASTENER WITH METAL 20" O.C. MAX. CONTINUOUS BEAD O CAULK 1" TAPE SEALER CONTINUOUS HEAD HEAD LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE HEAD LASHING HEAD DETAIL DD-113
51 DEEP-DECK PANEL ASTENER WITH METAL 30 # ELT UNDERLAYMENT 20" O.C. MAX. CONTINUOUS BEAD O CAULK OUTSIDE OAM CLOSURE WITH TAPE SEALER TOP AND BOTTOM. JAMB JAMB LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE JAMB LASHING JAMB DETAIL DD-114
52 SILL SILL LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS SLOPE 30 # ELT UNDERLAYMENT ASTENER WITH METAL 20" O.C. MAX. DEEP-DECK PANEL CONTINUOUS BEAD O CAULK 1" TAPE SEALER CONTINUOUS 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. = INISH SIDE SILL LASHING SILL DETAIL DD-115
53 DEEP-DECK PANEL 30 # ELT UNDERLAYMENT ASTENER 20" O.C. MAX. ASTENER WITH METAL 20" O.C. MAX. 1" TAPE SEALER CONTINUOUS SILL LASHING; 4" END LAPS WITH CONTINUOUS CAULK AT LAPS CONTINUOUS CLEAT 1. (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN STRENGTH OR HOLDING POWER O ASTENERS. 2. ALL ELT UNDERLAYMENT, CAULKING AND ASTENERS ARE ITEMS TO BE URNISHED AND INSTALLED BY THE ROOING INSTALLER AT THE DISCRETION O THE ARCHITECT. 1" = INISH SIDE 4" SILL LASHING CLEAT GRADE DETAIL DD-116
S-DECK PANEL INSTALLATION DETAILS BERRIDGE MANUFACTURING COMPANY
S-DECK PANEL INSTALLATION DETAILS MANUACTURING 800-669-0009 www.berridge.com INDEX INDEX INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION INTRODUCTION
More information4. Metal roof jacks at penetrations and attachments
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - SECTION 07 61 00 METAL SHINGLE ROOFING - - - - - - - - - - -
More informationProSnap 100 STANDARD DETAILS
ProSnap 100 OVER WOOD DECK STANDARD DETAILS Austin - Headquarters/Sales Office 830 Sagebrush Drive Austin, TX 78758 (512) 452-1515 (800) 428-7412 Fax (512) 833-7499 www.ctmrs.com email: info@ctmrs.com
More informationREGAL. Installation Manual
REGAL Installation Manual General Information The details shown on the following pages are suggestions or guidelines for installing the Regal system. The installation details shown here are proven methods
More informationEkoroof LiteTile Dimensions
Ekoroof LiteTile Dimensions 7 3 3.5 Height 40 Width 20 Length Weight per Panel: 3 kg / 6.61 lbs 2 2 Area per panel 800 in / 5.55 ft 2 Panels per Square: 20 (including overlap, for a 100 ft covered area)
More informationTremLock T-138 INSTALLATION MANUAL T-138 www.tremcoroofing.com 3735 Green Road Beachwood, Ohio 44122 1.800.852.6013 50 Beth Nealson Drive Toronto, Ontario M4H 1M6 1.800.668.9879 7241 6/8/18 TABLE OF CONTENTS
More informationTABLE OF CONTENTS A-1
TABLE OF CONTENTS PAGE NUMBER: DETAIL DESCRIPTION A-1...TABLE OF CONTENTS A-2...GENERAL NOTES B-1...GENERAL INFORMATION C-1...EAVE DRIP DETAIL C-2...EAVE DRIP with GUTTER DETAIL C-3 & C-4...FIXED RIDGE
More informationTABLE OF CONTENTS A. PBR
TABLE OF CONTENTS A. PBR Panel 1. PBR Panel Architect/Engineer Information....................................... 2 2. PBR Panel UL 90 Requirements............................................... 3 3. PBR
More informationTuff-Rib Install Guide
Install Guide bestbuymetalroof.com Page 2 of 27 Page 3 of 27 1. Page 4 2. a. Installation Guide b. Panel Squaring Pages 5, 6 Pages 7, 8 3. Pages 9, 10 4. a. Fascia (optional) b. Eave / 1.5x3.5 Angle c.
More informationVENTED GABLE DETAIL ROOF PANEL GABLE FLASHING 24" C/C MAX. BUTYL SEALANT TAPE ROOF PURLIN FLASH AB-1, AB-2, AB-3, OR AB-4
GABLE FLASHING FASTENER @ 24" C/C MAX. ROOF PURLIN BUTYL SEALANT TAPE FLASH AB-1, AB-2, AB-3, OR AB-4 FASTENER @ EVERY MAJOR RIB OR 12" C/C MAX. F-J TRIM FABRAL ALUMINUM SOFFIT FASTENER 24" C/C MAX. BUTYL
More informationWESTERN WAVE Panel. Vertical Installation and Technical Information
WESTERN WAVE Panel Vertical Installation and Technical Information Western States Western Wave Wall and Soffit Panels (Vertical) Installation, Flashings & Shop Drawing Detail Guide Section Notes to Designer
More informationWESTERN WAVE Panel. Horizontal Installation and Technical Information
WESTERN WAVE Panel Horizontal Installation and Technical Information Western States Western Wave Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page
More informationInspire Aledora Slate Application Guidelines
July 2014 Inspire Aledora Slate Application Guidelines Only Basic Roofing Tools Required Hand fastened or fastened with a pneumatic nail gun Utility knife or a standard circular saw Tape measure, pry bar,
More informationinstallation guide Villa
installation guide Villa Table of Contents Introduction............................. 2 Safety................................... 2 Tools.................................... 2 Codes & Requirements....................
More informationInspire Slate Starter Piece Hip and Ridge. 13 1/2" Height: 13 ½" Width: 12" Squares/ Pallet. Bundles/ Square
December 2017 Classic Slate Application Guidelines Only Basic Roofing Tools Required Hand fastened or fastened with a pneumatic nail gun Utility knife or a standard circular saw Tape measure, pry bar,
More informationBrava Old World Slate Installation Guide
Brava Old World Slate Installation Guide Brava Roof Tile Phone: 844-290-4196 www.bravarooftile.com This document includes the recommended and suggested installation procedures for Brava Old World Slate
More informationKS SERIES - VERTICAL INSTALLATION
CS-DS-01-KSV CS DISCLAIMER CS-PJ-01-KSV KS42SL EXPANDED PANEL JOINT CS-PJ-02-KSV KS42SL ENGAGED PANEL JOINT CS-PJ-03-KSV KS45SL EXPANDED PANEL JOINT CS-PJ-04-KSV KS45 FLAT ENGAGED PANEL JOINT CS-PJ-05-KSV
More informationeco-shake INSTALLATION INSTRUCTION
1 eco-shake INSTALLATION INSTRUCTION NOTE: Shuffling the eco-shakes during installation may be necessary to obtain a uniform color throughout the roof. Due to the natural wood content in the ecoshakes,
More informationTIOGA Table of Contents
Table of Contents TABLE OF CONTENTS Product Data Sheet...2 Engineering Data...3 General Information...4 Handling...5 Roof Preparation...5 Fastening Recommendations...6 Field Cutting...7 Touch-up Paint...7
More informationINSTALLATION GUIDE LEARN MORE AT DECRA.COM
Villa Tile INSTALLATION GUIDE LEARN MORE AT DECRA.COM Table of Contents DECRA Villa Tile Roof Overview... 2 Introduction... 3 Safety... 3 Tools.... 3 Estimating Sheet... 3 Codes & Requirements... 3 Roof
More information2 ½ Corrugated Panel Installation Specifications
2 ½ Corrugated Panel Installation Specifications ROOF APPLICATION: Roof slope must be a minimum of a 2/12 pitch to use this product. When using this product butyl lap sealant is recommended for all slopes.
More informationTable of Contents. Notes to Designer/User Map of Typical Roof Conditions Fastener Placement Fastener Selection...
Table of Contents Section Page Notes to Designer/User... 2-3 Map of Typical Roof Conditions... 4 Fastener Placement... 5 Fastener Selection... 6 Ridge/Hip Flashing... 7 Valley Flashing... 8 Eave Flashings...
More informationTable of Contents. Fasteners... 4 Venting Preparation Installation with Battens - DECRA Tile & DECRA Shake 1
Table of Contents DECRA Tile & Shake Roof Overview... 2 Introduction... 3 Safety... 3 Tools.... 3 Estimating Sheets... 4 Codes & Requirements... 4 Roof Slope... 4 Underlayment... 4 Deck Preparation....
More informationBARRELL VAULT BATTENLESS
i BARRELL VAULT BATTENLESS INSTALLATION GUIDE INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation of the Gerard Barrel Vault battenless
More informationFeatures 24 ga steel or 26 ga steel. Colors available on standard or premium and metallic. 16 to 24 o.c. On site factory made.
Strip Width Base Material Thickness Min Tensible Min Yield Coatings 16.00 to 24 in Steel.0128 to.027 in 52 - ksi 50 - ski Painted / Galvalume UL CONSTRUCTION NUMBERS: TGKX539 The Nail Strip 1.5 (NS-150)
More informationUL Construction No. 254
UL Construction No. Wind-Uplift - Class 90 (See Item No. ) / Fire Not Investigated Metal Roof Deck Panels* Snap-Clad No. MSG or No. MSG min. thickness coated steel panels. Panels in. wide max., 0 in. wide
More information900 SERIES WALL PANELS
CI-DS-01-900 CI-PP-01-900 CI-PJ-01-900 CI-PJ-02-900 CI-PJ-03-900 CI-BS-01-900 CI-BS-02-900 CI-BS-03-900 CI-BS-04-900 CI-BS-05-900 CI-OC-01-900 CI-OC-02-900 CI-IC-01-900 CI-FO-01-900 CI-FO-02-900 CI-FO-03-900
More informationFive Star Panel Installation Instructions
Five Star Panel Installation Instructions How to Store Five Star Panels You will need to store FIVE STAR PANELS in dry place to prevent staining, deterioration and possibly void all warranties. Stand the
More informationCertainTeed. Shake / Slate Installation Guide
CertainTeed Shake / Slate Installation Guide Table of Contents System Components... 2 General Conditions, Safety and Roof Preparations... 3... 4 Eave/Drip Edge... 5 Inner Gable... 6 Outer Gable... 7 Open
More informationSteel Roofing & Siding INSTALLATION GUIDE
Steel Roofing & Siding INSTALLATION GUIDE Your Authorized Dealer is: WASHINGTON Auburn (800) 700-7228 WASHINGTON Spokane (866) 321-5954 www.nuraymetals.com CALIFORNIA Redlands (800) 806-8729 CONTENTS BEFORE
More informationTuff Rib Panel Installation Specifications
Tuff Rib Panel Installation Specifications ROOF APPLICATION: Roof slope must be a minimum of a 2/12 pitch to use this product. For slopes lower than a 3/12 pitch, lap sealant is suggested on the side laps
More informationSECTION SHEET METAL FLASHING AND TRIM
SECTION 07620 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Formed roof drainage sheet metal fabrications. 2. Formed low-slope roof sheet metal fabrications. 1.2 SUBMITTALS A. Shop Drawings: Show
More information900 SERIES PANEL SHEET INDEX STAGGERED ENDLAP STAGGERED MALE LEG AT ENDLAP CONTINUOUS FEMALE ENDLAP INSTALLATION SEQUENCE CI-WR
900 SERIES PANEL CI-DS-01-900 CI-PJ-01-900 CI-PJ-02-900 CI-EL-01-900 CI-EL-02-900 CI-EL-03-900 CI-EL-04-900 CI-EL-05-900 CI-EL-06-900 CI-EL-07-900 CI-EL-08-900 CI-RD-01-900 CI-RD-02-900 CI-RD-03-900 CI-EV-01-900
More informationDETAIL MANUAL for Standing Seam / Image II
DETAIL MANUAL for Standing Seam / Image II Best Buy Metals Toll Free 1-800-728-4010 / Phone 423-479-6382 / Fax 423-728-3066 www.bestbuymetals.com Best Buy Metals Standing Seam Roofing Panels Fig. 2 Standing
More informationInstallation Guide. Titan Old World Slate REV Titan Manufacturing Phone: (407) Fax: (866)
Installation Guide Titan Old World Slate REV70908 Titan Manufacturing Phone: (407) 587-5492 Fax: (866) 741-2147 www.titanroofsystems.com This document includes the recommended and suggested installation
More informationDIRECTIONS FOR APPLICATION
Instructions 1 General NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE DIRECTIONS
More informationBarrel Vault Counter Batten and Batten
Barrel Vault Counter Batten and Batten INSTALLATION GUIDE www.gerardusa.com INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation
More information400 SERIES VERTICAL INSTALLATION
CI-DS-01-400V CI-PJ-01-400V CI-PJ-02-400V CI-PJ-03-400V CI-BS-01-400V CI-BS-02-400V CI-BS-03-400V CI-BS-04-400V CI-BS-05-400V CI-OC-01-400V CI-OC-02-400V CI-IC-01-400V CI-IC-02-400V CI-FO-01-400V CI-FO-02-400V
More informationINSTALLATION DETAILS
INSTALLATION DETAILS Front Issued January 23rd, 2005 These install details are provided to demonstrate the recommended installation method for Metro Roof products and accessories. The details and information
More informationInstallation Guide. Step 3. Valley Flashing. Step 7. Transition Flashings and Accessories. Step 6. Hip and Ridge Installation
Step 7. Transition s and Accessories Step 3. Valley Step 6. Hip and Ridge Installation Step 2. Rake Trim Step 5. Installing the Shingles Step 1. Eave Starter Installation Step 4. Endwall s Installation
More informationTable of Contents. Installation Guide for Profile with Hidden Fasteners 3. Installation Steps 4, 5. Prestige Series Moldings 6, 7. Other Accessories 8
1 Table of Contents Page(s) Installation Guide for Profile with Hidden Fasteners 3 Installation Steps 4, 5 Prestige Series Moldings 6, 7 Other Accessories 8 Trims & Accessories 9 Eave Starters 10 Gableboards
More informationInstallation Guide. Cedar Shake. Distributed by: BEST MATERIALS LLC, Phoenx AZ
RPM ROOFING Installation Guide Cedar Shake Distributed by: BEST MATERIALS LLC, Phoenx AZ 602-272-8128 800-474-7570 www.bestmaterials.com Table of Contents OVERVIEW... 1 CAUTION... 1 DISCLAIMER... 1 PRODUCT
More informationSG-30 A P P L I C A T I O N I N S T R U C T I O N S. Directions For Application
1 2 3 General Instructions NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE
More informationTuff-Rib. Installation Manual. Nationwide supplier of quality metal roofing. Toll-Free (800) S. Lee Hwy. Cleveland, TN 37311
Installation Manual Nationwide supplier of quality metal roofing. 65 S. Lee Hwy. Cleveland, TN 7.. www.bestbuymetals.com Toll-Free (800) 78-00 IMPORTANT NOTICE This manual contains suggestions and guidelines
More informationPBR Panel Installation Specifications
4906 St. Stephens Rd. 5780 Hwy 90 W Eight Mile, Al 36613 Theodore, AL 36590 251 456 2254 251 653 1550 251 457 2254(F) 251 653 1514(F) PBR Panel Installation Specifications ROOF APPLICATION: Roof slope
More informationBest Materials LLC distributes backer rod, caulking and sealants for all types of EIFS joints and penetration sealing applications.
Best Materials LLC distributes backer rod, caulking and sealants for all types of EIFS joints and penetration sealing applications. EXTERIOR INSULATION & FINISH SYSTEM CONSTRUCTION Data Published Courtesy
More informationTable of Contents Light Gauge Metal Roof & Wall Panels
Table of Contents Light Gauge Metal Roof & Wall Panels Installation Guide for Delta Rib, Nor-Clad, Strata Rib & 2-1/2 Corrugated Introduction Important Notice Notes: April 2008 Minimum Recommended Tools
More informationGLOSSARY OF TERMS SECTION 8
GLOSSARY OF TERMS SECTION 8 Anchor Bolt Angle Base Plate Bay Blocking CCB Centerline Chord Cladding Clip Closure Strip An A-307 steel bolt embedded in the concrete footing to anchor the base plate of the
More informationROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION
ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION 1. Scope 4. Underlayment 2. 1.1 This roofing application standard has been developed to provide a responsive
More informationBest Buy Metals Toll Free / Phone / Fax
DETAIL MANUAL for Vertical Seam Best Buy Metals Toll Free 1-800-728-4010 / Phone 423-479-6382 / Fax 423-728-3066 www.bestbuymetals.com Vertical Seam Roofing Panels Fig. 2 Vertical Seam Has 1-3/4" high
More informationROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION
ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION 1. Scope 4. Underlayment 2. 1.1 This roofing application standard has been developed to provide a responsive
More informationStraight Rib Series Metal Roofing Panel Installation Guide
D-Rib G-Rib C-Rib Straight Rib Series Metal Roofing Panel Installation Guide 7000 AIRPORT LINE R.R., BOX 7 HENSALL, ONTARIO N0M X0 EASY BUILDING PRODUCTS TEL. : 5-6-07 TOLL FREE : -888-76-777 FAX: 5-6-08
More informationDIRECTIONS FOR APPLICATION
Instructions 1 General NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE DIRECTIONS
More informationTable of Contents. Roof to Head Wall w/ Side Flashing DECRA Shake XD Roof Overview Roof Penetration - Pipes & Vents...
Table of Contents DECRA Shake XD Roof Overview.... 2 DECRA Shingle XD Roof Overview.... 3 Introduction... 4 Safety... 4 Tools.... 4 Estimating Sheet... 4 Codes & Requirements... 4 Roof Slope... 4 Underlayment...
More informationShapes Siding. Perfection Shingles. Chalk Line
Snap a Chalk Line Shapes Siding Perfection Shingles Chalk Line To establish a straight reference line to guide the positioning of the starter strip and the first course of siding, snap a chalk line. starter
More informationA P P L I C A T I O N I N S T R U C T I O N S
1 2 3 General Instructions NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE
More informationCONTENTS. Transitions Board and Batten Vertical Installation... 10,11
INSTALLATION MANUAL CONTENTS Important Notes... 2-4 Weather Protective Barriers... 2 Storage and Transportation... 2 Tools and Equipment... 2 Fastener Choices... 3 Wall Preparation... 3,4 Flashing... 4
More informationCOMPOSITE SIDING INSTALLATION GUIDE
CENTURY HOME LIVING COMPOSITE SIDING INSTALLATION GUIDE Read all instructions prior to installing any siding product. Failure to install and finish this product in accordance with all local building codes,
More informationMAXIMUM PANEL ATTACHMENT FASTENER SPACING IS 24" O.C. ALL FASTENERS TO PENETRATE WOOD 3/4" MIN. AND METAL FRAMING 1/2" MIN.
PLYWOOD SHEATHING DMI SOFFIT PANEL #10-13 GP PANCAKE HEAD (JC) - J CLOSURE (LC) - L CLOSURE #9-15 X 1 1/2" WOODZAC GP APPROVED MOISTURE BARRIER SOFFIT TO WALL PANEL WPRP-H-01-00 APPROVED MOISTURE BARRIER
More informationMETAL ROOFING INSTALLATION GUIDE
METAL ROOFING INSTALLATION GUIDE STANDING SEAM ROOFING PANELS Horizon 16 and Climaguard 16 Regardless of whether your roofing project is a new installation or a re-roof, and whether your building is residential,
More informationSTACKING MULTI-SLIDE DOOR SYSTEM INSTALLATION INSTRUCTIONS
STACKING MULTI-SLIDE DOOR SYSTEM INSTALLATION INSTRUCTIONS 1290363 Revision 1 12/16 Page 1 Weather Shield Mfg., Inc. NOTICE CAUTION! Failure to install and maintain our product according to these instructions
More informationDIRECTIONS FOR APPLICATION
Instructions 1 General NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE DIRECTIONS
More informationE-Z BUILD STEEL BARN 12' 12' 12' 16' 12' 20'
E-Z BUILD STEEL BARN 12' 12' 12' 16' 12' 20' BUILD You can construct your own E-Z frame barn with the help of this step by step guide. North American softwood dimensional lumber sizes: Nominal Actual in
More informationONDUVILLA. The Attractive Alternative to Shingles I N S T A L L A T I O N I N S T R U C T I O N S
ONDUVILLA The Attractive Alternative to Shingles I N S T A L L A T I O N I N S T R U C T I O N S 1 INSTALLATION INSTRUCTIONS Even though ONDUVILLA is easy to install, it is important to read through these
More informationDW HORIZONTAL INSTALLATION
AR-PJ-01-DW2H 2" HORIZONTAL PANEL JOINT AR-PJ-02-DW2H 2" VERTICAL PANEL JOINT AR-PJ-03-DW2H 3" HORIZONTAL PANEL JOINT AR-PJ-04-DW2H 3" VERTICAL PANEL JOINT AR-PJ-05-DW2H CUSTOM REVEAL AR-PJ-06-DW2H DW-2000S
More informationDECRA Shingle Installation Guidelines
Installation Guide DECRA Shingle Installation Guidelines General Instructions Failure to use these guidelines may void the product warranty. Local building codes may require additional application techniques
More informationBARDOLINE INSTALLATION INSTRUCTIONS
BARDOLINE INSTALLATION INSTRUCTIONS www.onduline.com CONTENTS General conditions Material requirements Terms Estimating shingle requirements Roof preparation Shingle application 9 GENERAL CONDITIONS ONDULINE
More informationThompson Architectural TM-RIB PANEL ACCESSORY DETAIL GUIDE
TM-RIB PANEL ACCESSORY DETAIL GUIDE FL11101.1 FL11101.2 TA125 (UL580 Class 90) Certified Thompson Architectural Metal Roofing is proud to be a partner of the Energy Star Roof Products Program SINGLE SOURCE
More informationInstallation Manual SOLID CORE SIDING
Installation Manual SOLID CORE SIDING SOLID CORE SIDING Installation Information contained in this manual can be viewed in video form at: www.youtube.com/epbc CONTENTS Important Notes...2-4 Weather Protective
More informationHERITAGE LAMINATED ASPHALT SHINGLES Frederick, MD
Application Instructions for FORMERLY 30 THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR
More informationPREMIUM LAMINATED ASPHALT SHINGLES Frederick, MD
Application Instructions for FORMERLY 50 THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR
More informationPREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS
Application Instructions for FORMERLY 50 THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR
More informationKS42 MF SERIES - HORIZONTAL INSTALLATION
CI-DS-01-KSMF H CI-PJ-01-KSMF H CI-PJ-02-KSMF H CI-PJ-03-KSMF H CI-PJ-04-KSMF H CI-PJ-05-KSMF H CI-PJ-06-KSMF H CI-PJ-07-KSMF H CI-PJ-08-KSMF H CI-PJ-09-KSMF H CI-PJ-10-KSMF H CI-PJ-11-KSMF H CI-PJ-12-KSMF
More informationVENTED GABLE DETAIL ROOF PANEL GABLE FLASHING 24" C/C MAX. BUTYL SEALANT TAPE ROOF PURLIN FLASH AB-1, AB-2, AB-3, OR AB-4
ROOF PANEL GABLE FLASHING FASTENER @ 24" C/C MAX. ROOF PURLIN BUTYL SEALANT TAPE FLASH AB-1, AB-2, AB-3, OR AB-4 FASTENER @ EVERY MAJOR RIB OR 12" C/C MAX. F-J TRIM FABRAL ALUMINUM SOFFIT FASTENER 24"
More informationAssembly Book. 10' x 16' the Cambridge II. revised July 15, 2014
Assembly Book revised July 15, 2014 the Cambridge II 10' x 16' Manufactured by Reynolds Building Systems, Inc. 205 Arlington Drive Greenville, PA 16125 724-646-3775 This manual is copyrighted. Under the
More informationinstallation guide 7 8 Corrugated corrugated metal panel
installation guide / 7 8 Corrugated corrugated metal panel Table of Contents General Notes Handling and Storage 1-3 Tools and Equipment, Field Cutting Panels 4 Safety 5 Preparing to Install your New Roofing
More informationSHEET METAL FLASHING AND TRIM Christ on the Mountain
SECTION 076200 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Compatibly with the bumping of flashings and trim as identified in the Membrane Roofing Section 075000.
More informationStoring, Handling, and Cutting Steel Panels
Storing, Handling, and Cutting Steel s Storing Specifically check your quantities, colors, and lengths All materials should be used as soon as possible Steel bundles should be stored indoors with enough
More informationDETAIL MANUAL. Metal Roofing Wholesalers. Classic Rib Roofing Panels
Metal Roofing Wholesalers Classic Rib Roofing Panels DETAIL MANUAL 1178 Topside Rd Louisville, TN 37777 The Classic Rib Roofing Panel Figure 1 House With Classic Rib Metal Roofing Installed Classic Rib
More information3-Tab Shingle Instructions DURA-SEAL 20 DURA-SEAL 25
3-Tab Shingle Instructions DURA-SEAL 20 DURA-SEAL 25 1 Directions For Applying Malarkey 3-Tab Shingles GENERAL INSTRUCTIONS Install Malarkey 3-tab shingles according to building code and local amendments.
More informationSlate Shingle Specifications
Slate Shingle Specifications California Slate is a proud member of the Slate Roofing Contractors Association of North America, Inc. (SRCA) which publishes Section 07310 Slate Shingles setting forth architectural
More informationb) Symphony comes pre-packaged in color and width blends. There is no need to mix Symphony at the job site. Currently Symphony is available in the
PART 1 GENERAL 1) DESCRIPTION a) CertainTeed Symphony TM composite slate is an innovative roofing product that simulates the appearance, texture, and contours of traditional natural slate. It is a carefully
More informationINSTALLATION GUIDE SAVANNAH SMOOTH & SIERRA PREMIUM SHAKE
INSTALLATION GUIDE SAVANNAH SMOOTH & 1 NICHIHA INSTALLATION GUIDE FOR SAVANNAH SMOOTH & GENERAL INSTRUCTIONS FOR SAVANNAH SMOOTH & CONSTRUCTION REQUIREMENTS Savannah Smooth and Sierra Premium Shake boards
More informationRED DIAMOND SHINGLES Roof Installation Introduction:
RED DIAMOND SHINGLES Roof Installation Introduction: The guidelines set forth in this manual are intended for use with the application of Red Diamond shingles. Wallaba specie (Eperua Falcata) shingles
More informationTable of Contents. Important Notices 3. Residential Roofing Application 4. Trims & Accessories 5. Trim Glossary 6, 7, 8. Estimating Material 9
Table of Contents Page(s) Important Notices 3 Residential Roofing Application 4 Trims & Accessories 5 Trim Glossary 6, 7, 8 Estimating Material 9 Eave Trim Installation 10 Connecting Eavestarters 10 Gable
More informationThe chimney must extend at least 2 above any part of the roof within 10 of it. A fireplace must have an intake combustion air duct installed to plan.
ROOF ASSEMBLY FURNACE VENT In the utility room or where the furnace is located, there is an access panel to inspect the furnace chimney pipe for gas fired units. Remove the cover and check to see that
More informationSLATE & SHINGLE INSTALLATION
EAVE EDGE Apply a small strip of roofing paper to the bottom of eave. Eave flashing is attached to substrate with roofing nails every 9". Install underlayment over entire roof. (See Fig. 1) PAGE 1 Bend
More informationSmartVent Eave Edge Installation Instructions
SmartVent Eave Edge Installation Instructions STEP 1: Cut a slit 1 wide (or a series of 1 ¾ holes at 3 on center) into the roof decking 6 to 7 up from the drip edge. SmartVent is rated 9NFA. Ensure drip
More informationTimberline and Sovereign Expanded Fastener Placement Area
Timberline and Sovereign Expanded Fastener Placement Area Information Sheet Updated: 2004 Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Less Fastening Hassles! Announcing
More informationCapstone Application Instructions
Capstone Application Instructions Information Sheet Updated: 2007 Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer L IFETIME D ESIGNER S HINGLES APPLICATION INSTRUCTIONS
More informationStone coated steel roof tile INSTALLATION GUIDE
Stone coated steel roof tile INSTALLATION GUIDE Ⅰ. Introduction These installation details are provided to demonstrate recommended installation methods for KD One roof products and accessories. Consult
More informationSECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY
SECTION 07312 PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This Section Includes the following: 1. Endureed Dominica PVC thatch shingles. 2. Self- adhering sheet underlayment. B. Related
More informationReference Guide and Installation Instructions
Reference Guide and Installation Instructions Pocket Install Guide Congratulations and Thank You for your purchase! DryJoistEZ is an easy to install structural aluminum joist, that also provides a watertight
More informationTerrabella Shake & Shingle Znap Ver. 2.0
Terrabella Shake Znap Actual length = 52.6 Actual Width = 16.33 Coverage length = 49.7 Coverage width = 14 Terrabella Shingle Znap Actual Length = 52.375 Actual Width = 15.25 Coverage Length = 49.375 Coverage
More informationAIA Specification. Section Slate Shingles PART 1 GENERAL
AIA Specification Section 07315 Slate Shingles PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationROOFING APPLICATION STANDARD (RAS) No. 130 INSTALLATION CRITERIA FOR WOOD SHINGLES AND SHAKES APPLICATION
ROOFING APPLICATION STANDARD (RAS) No. 130 INSTALLATION CRITERIA FOR WOOD SHINGLES AND SHAKES APPLICATION 1. 2. 3. Scope 1.1 This application standard provides the minimum installation criteria for wood
More informationDETAIL MANUAL. For R-Panel / PBR Panel. Metal Roofing Wholesalers
Metal Roofing Wholesalers DETAIL MANUAL For R-Panel / PBR Panel 1178 Topside Rd Louisville, TN 37777 Picture of Gulf Coast Figure 1 Metal Roofing Plant PBR/R-Panel The 26-gauge R-Panel is a strong, durable,
More informationROOFING APPLICATION STANDARD (RAS) No. 130
ROOFING APPLICATION STANDARD (RAS) No. 130 1. Scope 1.1 This application Standard provides the minimum installation criteria for wood shingles and shakes. 2. Definitions 2.1 For definitions of terms used
More informationHatteras Shingles. CertainTeed Shingle Applicator s Manual. YOUR OBJECTIVE: To learn the correct procedures for installing Hatteras shingles
CertainTeed Applicator s Manual Hatteras s 14 YOUR OBJECTIVE: To learn the correct procedures for installing Hatteras shingles HATTERAS SHINGLES Hatteras shingles are a premium oversize (18" x 36") roofing
More informationEffective February, 2015
Effective February, 2015 Table of Contents Ensuring System Performance 1 Components 2 Frequently Asked Questions 3 List of Tools 3 Before you Begin Preparation 3 Quality Tips 4 Cold Weather Tips 4 Cleaning
More information