Power System Laboratory Manual
|
|
- Nelson Gaines
- 5 years ago
- Views:
Transcription
1 Power System Laboratory Manual B.Tech, 4 th Year, 7 th Semester Electrical Engineering Department Indira Gandhi Institute of Technology Sarang,Dhenkanal , Odisha L.N Electrical Engineering Department-2017
2 Indira Gandhi Institute of Technology, Sarang, Dhenkanal B.Tech, 4 th Year, 7 th Semester, Electrical Engineering Department Power System Laboratory Group A: HARDWARE BASED 1. To plot the Inverse Definite Minimum Time (IDMT) characteristic of an over-current relay with different plug setting multiplier (PSM) and time setting multipliers (TSM). 2. To study the operating principle and characteristics of a biased differential relay with different percentages of biasing setting. 3. Steady State performance of a Transmission Line Objectives: (a) To determine A, B, C, D parameters, Characteristic Impedance and Propagation Constant of an artificial transmission line. (b) To determine the voltage profile of a Transmission Line (i) Without Shunt Compensation (ii) With Shunt Compensation. (c) To determine the reactive power required for zero voltage regulation at different loads (d) To Study the Ferranti Effect of Long Transmission Line. 4. Voltage Control Using STATIC VAR Compensator 5. Study of Performance of the Buchholz Relay used for Protection of Transformer Group B : SIMULATION BASED (MATLAB OR ANY OTHER SOFTWARE) 1. To formulate the Y-Bus matrix for standard Electrical Network. 2. To compute voltage, current, power factor and regulation at the receiving end of a three phase Transmission line (Pi Model) when the voltage and power at the sending end are given and further calculate the efficiency of the Transmission Line at that particular Load. 3. Simulation of symmetrical and unsymmetrical faults in a given Transmission line connected to power network and study of variation of parameters such as Fault type, Fault resistance, Fault Location and Source Impedance on current & voltage magnitude and phase measured at sending end. TEXT BOOKS: 1. Hadi Sadat- Power System Analysis TMH 2. T. K. Nagsarkar and M. S. Sukhija - Power System Analysis Oxford University EE /IGIT/2016/ Faculty : L.N Tripathy
3 Indira Gandhi Institute of Technology Electrical Engineering Department B.E, IV Year(7 th Semester), Electrical Engineering Department Power System Lab Certificate This is to Certify that Mr/Ms University Regd. No of B.Tech 7 th Semester Electrical Engineering Department has completed all experiments prescribed by the Institute as per requirement of B.Tech[Electrical ] Engineering Degree of Biju Patnayak University of Technology, Rourkela for the Academic Year Faculty Signature Head of Department Date:-
4 Indira Gandhi Institute of Technology, Sarang, Dhenkanal B.Tech, 4 th Year, 7 th Semester, Electrical Engineering Department Index Sr.No Name of the Experiments Date Grade Faculty Signature Name of Student:- Roll No :- University Regd. No Group:-
5 Indira Gandhi Institute of Technology, Sarang, Dhenkanal B.Tech, 4 th Year, 7 th Semester, Electrical Engineering Department Experiment No. Date:- Aim:- Development of a Matlab program showing the variation real power through a line w.r.t load angle ( ) and reactive power variation through a line w.r.t variation in terminal voltage of the line. Example:- Two Voltage sources V1=120<-5 0 V and V2 = 100<0 0 V are connected by a short line of Impedance Z= 1+j7. Write a Matlab program such that the phase angle of source- 1 is changed from its initial value by 30 0 in a step of 5 0. Voltage magnitude of two sources and Voltage phase angle of sources-2 is kept constant. Q1. (a) Tabulate the real power at Source-1 (P1) and Real Power at Source-2(P2)and Power Loss in the Line( PL) for different values of Source-1 voltage phase angle ( ). (b) Plot P1, P2 and PL w.r.t Source-1 voltage phase angle ( ). (c) Plot Reactive Power at Source-1(Q1) and Reactive Power at Source-2(Q2) w.r.t (d) Gives your comments on the result in part(c) Q2. Plot Reactive power at Source-1 (Q1) and Reactive Power at Source-2(Q2) and Reactive Power Loss in the Line( QL) for different values of Source-1 voltage magnitude while load angles of both sources and source-2 voltage magnitude are remained constant. Comment on the above results Group No.:- Student Name:- Roll No 1 P a g e P S P / L. N T r i p a t h y
6 Mathematical Analysis and Related Formula I I j j7 * S V I W j363.3var * S V 2I W j294.5var Line Loss S S S 9.8W j68.8var Real L Power Loss( P ) R I 1 (3.135) 9.8W L Re active Power Loss( Q ) X I 7 (3.135) 68.8Var L References:-1. Power System Analysis, Hadi Saadat, TATA McGRAW- HILL, Edition.2004, Page no: P a g e P S P / L. N T r i p a t h y
7 Indira Gandhi Institute of Technology, Sarang, Dhenkanal B.Tech, 4 th Year, 7 th Semester, Electrical Engineering Department Experiment No. Date:- 1. Aim : Steady State performance of a Transmission Line Objectives: (a) To determine A, B, C, D parameters, Characteristic Impedance and Propagation Constant of an artificial transmission line. (b) To determine the voltage profile of a Transmission Line (i) Without Shunt Compensation (ii) With Shunt Compensation. (c) To determine the reactive power required for zero voltage regulation at different loads (d) To Study the Ferranti Effect of Long Transmission Line. Motivation: Transmission line are used to transfer bulk amount of power from one place to other in Electrical system. The availability of well developed high capacity system of transmission line makes it technically and economically feasible to transmit block amount of power over large distance. The performance characteristic of transmission line are important from the point of view of making analytical studies of the system, e.g power flow, voltage regulation,steady state and transient stability etc. Theory : A Transmission line has four parameters (i) Resistance (ii) Inductance (iii) Capacitance and (iv) Conductance. Where (i) and (ii) makes up the series impedance of the line, (iii) &(iv) determine shunt admittance. Shunt conductance are generally neglected in power Transmission line when calculating voltage and current. The classification of Transmission lines according to length depend upon what approximations are justified in treating the parameters of the lines. The Transmission lines are classified as (a) Short Transmission line : These lines are roughly 80 km long. For short transmission line the total capacitive susceptance is so small that it may be neglected(figure-1). (b) Medium Line : Medium lines are roughly between km long. The shunt admittance, generally pure capacitance is included in the equivalent circuit of the line. 3 P a g e / P S P / L. N T r i p a t h y
8 If all the shunt admittance is lumped at the middle of the circuit representing the line, the circuit is called Nominal-T(Figure-2). In the Nominal- π circuit the shunt admittance is divided into two equal parts placed at sending and receiving end of the line(figure-3). Long Line: Lines more than about 240km long require calculation in terms of distributed constant if a high degree of accuracy is required. An equivalent circuit representing for such line are shown in figure-4 Let Z= Series impedance per unit length per phase y= Shunt Admittance per unit length per phase l = length of the line Y=yl. R X Z=R+jX V s V R Figure-1 : Equivalent Circuit of Short Transmission Line Figure-2 Nominal T- Circuit 4 P a g e / P S P / L. N T r i p a t h y
9 Figure-3 Nominal π Circuit Figure-4: Equivalent Circuit for long Transmission Line ABCD Constants: The voltage and current at the receiving end (VR and IR ) is related to the voltage and current at sending end (VS and IS) by the equations VS = AVR+BIR (1) IS= CVR+DIR (2) The ABCD constants for lines of various lengths can be determined from their equivalent circuit described as below (1) Short Line A=D=1.0 B=Z= (Series Impedance) C=0.0 (2) Medium Line (a) Nominal T-Model A= 1+YZ/2 5 P a g e / P S P / L. N T r i p a t h y
10 B= Z+YZ 2 /4 C=Y D=1+YZ/2 (b) Nominal π-model A= 1+YZ/2 B=Z C=Y+ZY 2 /4 D=1+YZ/2 The characteristic Impedance(ZC) of a Transmission line is given by Z C Z (3) Y The Propagation Constant (ϒ) of the line is given by YZ (4) Line on No-Load: A long transmission line with no load at receiving end gives a voltage rise at the receiving end. This effect is commonly known as Ferranti effect. The reason for these phenomena is the negative voltage drop caused by line charging current. This effect can be neutralized if an Inductive load is connected at the receiving end. The voltage drop caused at the receiving end of the line because of inductive load as well as voltage rise because of the line charging current at light load or no load, can be neutralized by choosing proper static capacitor /synchronous capacitor or shunt reactor at receiving end. Such compensation can give zero voltage regulation. Pre Experimental Quiz: 1. What are the various parameters of the Transmission line 2. Differentiate between Short, Medium and long line 3. What is the physical significance of attenuation constant of a long Transmission line 4. What is the difference between nominal π and equivalent π network of a transmission line. 5. What do you understand the series and shunt compensation of the line? Where are these used. 6 P a g e / P S P / L. N T r i p a t h y
11 6. Why Transmission Lines are Transposed? 7. What is the effect of Earth on the capacitance of the Transmission Line 8. Does Spacing of the line affect the line parameters? What other physical factors effect the line Parameters Equipments:- Transmission Line simulator Procedure: 1. Determination of ABCD Constants: (a) Connect the apparatus as shown in figure-5. Measure Is with receiving end opencircuited (IR=0), Then ZSO=VS/IS=A/C (b) Short circuit the receiving end (VR=0) and increase the VS gradually such that IS does not exceed the rated value of current. Measure VS, IS. Then ZSS=VS/IS=B/D (c) Open circuit the sending end(is=0), apply voltage from receiving end Then ZRO= VR/IR=D/C (d) Short circuit the sending end(vs=0). Increase the voltage at receiving end gradually such that IR does not exceed the rated values of the current. Measure VR,IR. Then ZRS= VR/IR=B/A. (e) From the above result, calculate A Z SO, Also calculate other constants ( Z Z ) RO RS (f) From the above test results, calculate ZC & γ 2. Shunt Reactor: Connect an inductive load at receiving end such that it completely compensate the voltage rise due to line capacitance i.e the voltage at two ends of the line are equal 3. Voltage Profile: (a) With full load at the receiving end, measure the voltage at 0,1/4 th,1/2,3/4 th and full length of the line. Plot voltage versus line length. (b) Use proper shunt compensation, measure the voltage again. Plot the voltage versus line length. 4. Zero Regulation 7 P a g e / P S P / L. N T r i p a t h y
12 With full load,3/4 th full load,1/2 load,1/4 th load and no load (inductive) at receiving end,determine the values of shunt capacitor C, such that VS=VR. The connection diagram is shown in figure-6 Figure-5, Open Circuit and Short Circuit Test on Transmission Line Figure-6, Zero Voltage Test on Transmission Line 8 P a g e / P S P / L. N T r i p a t h y
13 DATA SHEET: 1. ABCD Constants: VS IS ZSO Remarks VS IS ZSS Remarks VR IR ZRO Remarks VR IR ZSR Remarks 2. Shunt Reactor Compensation: VS VR=VS IR IS W CosΦ Compensating XL Reactance 3. Voltage Profile: V0 At end Sending V1 At.25 Distance V2 At.50 Distance V3 At 0.75 Distance V4 At 1.0 Distance Remark Without Compensation With Compensation 9 P a g e / P S P / L. N T r i p a t h y
14 4. Shunt Compensation for Zero voltage Regulation: V S I R I R V R =V S C W CosΦ Remark 1 Full Load Data Processing and Analysis: For each of the above studies, comment on the observed values(measurements) and calculated values of voltages, currents, power factors, shunt reactor, static capacitors etc. Post Experimental Questions: 1. Comment on the effect of shunt compensation of a Transmission Line 2. What are the various material used for Transmission Line conductor 3. Why are the bundle conductors are used EHV Transmission Line 4. What can be benefit of automatic control for shunt compensation 5. What do you understand by Surge Impedance Loading of a Transmission Line 6. What is understood by a half-wavelength Transmission Line References: 1. Zaborsky, Transmission Line 2. W.D Stevenson, Elements of Power System Analysis 3. O.I Elgerd, Electric Energy System Theory, McGraw Hill Publisher 4. Nagrath & Kothari, Power System Analysis 5. B.M Weedy, Power System 10 P a g e / P S P / L. N T r i p a t h y
15 Indira Gandhi Institute of Technology, Electrical Engineering Department B.E, IV Year(7 th Semester), Electrical Engineering Department Power System Lab 11 P a g e / P S P / L. N T r i p a t h y
16 12 P a g e / P S P / L. N T r i p a t h y
17 13 P a g e / P S P / L. N T r i p a t h y
18 14 P a g e / P S P / L. N T r i p a t h y
19 Indira Gandhi Institute of Technology Electrical Engineering Department B.E, IV Year(7 th Semester), Electrical Engineering Department Power System Lab Experiment No Date: Aim:-Write the Matlab program to form the Y Bus of the Electrical network with line data given below and show the results? Line Data: From Bus To Bus Line Resistance(R) Line Reactance(X) Shunt Susceptance(B/2) Q. 1. Write some specific characteristic of Y- Bus matrix Q 2. Why Y-Bus matrix is essential for load flow analysis and not Z -Bus matrix Q. 3. A Electrical Network comprises of 20 buses and 30 Transmission line. (a) What is the size of Y-Bus Matrix (b) In the above Y-Bus Matrix how many elements will be zero and how many elements will be non-zero (c) Explain the sparsity of a matrix. Group No:- Student Name Roll No 15 P a g e / P S P / L. N T r i p a t h y
20 Indira Gandhi Institute of Technology, Sarang, Dhenkanal B.Tech, 4 th Year, 7 th Semester, Electrical Engineering Department Experiment No. Date:- Aim:- Simulate a Transmission line model given below with single phase to ground fault having fault resistance of ohm and ground resistance of ohm with following parameters. The total simulation time is 1.0 second and fault is incepted at 0.7 second and continued till 1.0 second. Source Parameters:- Source-1 Phase to Phase Vrms =400kv, Phase Angle = 10 0, Frequency =50 Hz, Source resistance = Ohm, Source Inductance = mh Source-2 Phase to Phase Vrms =400kv, Phase Angle = 0 0, Frequency =50 HZ, Source resistance = Ohm,Source Inductance = mh Transmission Line Parameters:- R = ohm/km,l = mH/km,C =1274nF, Length of line = 200 km (a) Plot line current, Line voltage & power for different types of fault[ll, LLG, LLLG with different fault inception angle[0 0, 90 0 ] when fault distance is 100km from source-1 (b) For A-phase to ground fault with above fault resistance, Ground resistance and fault distance from source-1, list the different harmonics components relative to fundamental and find the corresponding THD during the fault interval (0.7 to 1.0 second) using FFT analysis. (c) Comment on the above results Group No.:- Students Name:- Roll No 16 P a g e / P S P / L. N T r i p a t h y
21 Indira Gandhi Institute of Technology, Sarang, Dhenkanal B.Tech, 4 th Year, 7 th Semester, Electrical Engineering Department Aim:- In the below RLC circuit, R= 1.4 ohm, L= 2H, and C=0.3 F.The initial inductor Current is zero, initial capacitor voltage is 0.5 V. A step voltage of 1 V is applied at t=0. Plot the i(t) and v(t) graph over the range 0<t<15 sec. Also plot the current versus capacitor voltage and energy stored in capacitor versus time. Write the Matlab program for getting the graph for above problem and attached the figures Experiment No. Date:- Group No.:- Student Name:- Roll No 17 P a g e / P S P / L N T r i p a t h y
22 Indira Gandhi Institute of Technology Electrical Engineering Department B.E, IV Year(7 th Semester), Electrical Engineering Department Power System Lab OBJECTIVE: - Steady State analysis of given Power System using Newton-Raphson method of Load Flow study. System Data: - For 7-bus system Line Data: Sl. No. 1 (From bus) 2 (To bus) 3 (Line impedance) (R + jx) 4 Line charging admittance (b_l)/2 5 tap ratio j 0.000j j 0.030j 1+0j j 0.025j 1+0j j 0.020j 1+0j j 0.020j 1+0j j 0.015j 1+0j j 0.010j 1+0j j 0.025j 1+0j j 0.010j 1.04 Bus Data Sl. No A B C D E j j j j j j P a g e / P S P / L. N T r i p a t h y
23 j j j j j j j j *The column wise description is as follows: 1 -- Bus Number Type of Bus, 0 == slack, 1 == PV, 2 == PQ Initial Choice for Voltage (V) 4 -- Nominal Bus Voltage (V_n) 5 -- Initial Choice for Angle (A) 6 -- Generation Specification (P_g + jq_g) 7 -- Nominal Load Specification (P_dn + jq_dn) 8 -- Reactive Generation Maximum (Q_g^max) 9 -- Reactive Generation Minimum (Q_g^min) A -- Bus Shunt Susceptance (b_sh) B -- Constant Power Load Coefficient (C_p) C -- Constant Current Load Coefficient (C_c) D -- Constant Impedance Load Coefficient (C_i) E -- Generator participation factor (alp) THEORY:- Newton-Raphson is an iterative method for solving non-linear problems. It starts with an initial guess and then makes use of the Taylor series expansion and the approximation for the solution by the first order gradient (derivative). Neglecting the higher order terms we get f(x) = c f(x k + Δx) = f(x k ) + fδx + 2 f Δx 2 + = c 2! This being an iterative scheme; Δx = f 1 [c f(x k )] The process is repeated till a convergence criterion is met. Generally the first order gradient is called the Jacobian. 19 P a g e / P S P / L. N T r i p a t h y
24 The convergence criteria is generally max(abs(delta x)) < a specified tolerance max(abs(mismatch)) < a specified tolerance In Power Flow context, we have P and Q equations to be solved for Bus Voltage and Angle (Polar co-ordinates). P i = V 2 i real(y ii ) + V i V j [cos δ j δ i real Y ji sin δ j δ i imag Y ji ] j i Q i = V 2 i imag(y ii ) + V i V j [sin δ i δ j real Y ji cos δ i δ j imag Y ji ] j i For Voltage dependent load, Similar expression for Q d i. For Voltage dependent Q limits, The Voltage dependent Q limits are to be handled on lines similar Normal Q limits when not violated. Voltage dependent load when violated. Result analysis : For the 7 bus system, perform one iteration for NRLF. The one iteration in NRLF involves computation of Jacobian and the updated bus voltages and angles for that iteration. Compare the results with those with the program executions. Find the following parameters: a) Power flow in all lines b) Power loss in all lines (active, reactive both) 20 P a g e / P S P / L. N T r i p a t h y
25 c) Total loop loss Further analysis: Check the effect of the following on convergence: PV bus Q limit violations, Load increase (Bus no. 2 and 3), line R/X ratio(series comp, 30% compensation), Gen rescheduling (loads fixed), PV bus voltage changes (Bus 7-Change voltage to 1.06 p.u.), Addition/removal of voltage control at a bus. Effect of change in slack bus position (Take 7 as slack bus). 21 P a g e / P S P / L. N T r i p a t h y
26 Indira Gandhi Institute of Technology Electrical Engineering Department B.E, IV Year(7 th Semester), Electrical Engineering Department Power System Lab Experiment No:- Date:- Inverse Definite Minimum Time [IDMT] Characteristic of Over Current and Earth fault Relay Motivation The protective Relaying which respond to a rise in current flowing through the protected element over a pre-determined value is called Over Current Protection and the Relay used for this purpose are known as Over Current Relay. Earth fault Relay can be provided with normal Over Current Relay. If the minimum earth faults current in magnitude is more than the pre-set value then the earth fault relay will operate otherwise the earth fault relay does not operate. The design of a comprehensive protection scheme in power system requires the detailed study of time-current characteristics of various relay used in the scheme. Thus it is necessary to obtain the operating time-current characteristic of these relays Objective (i) (ii) To obtain the IDMT characteristic of Induction type Over Current relay To obtain the IDMT characteristic of Induction type Earth fault relay Theory The Induction over current relay works on induction principle. The moving system consists of an aluminum disc fixed on a vertical shaft and rotating on two jewelled bearings, between two poles of an electromagnet and a damping magnet. The winding of the electromagnet is generally provided with seven taps, which are brought on to the front panel, and required tap is selected by a push-in-type plug. The pick up current setting can be varied by the use of such plug multiplier setting. The pick up current value of earth fault relay are normally quite low. The operating time of all over current relays tends to become asymptotic to a definite minimum value with the increase in the value of current. This is an inherent property of the electromagnetic relay due to saturation of the magnetic circuit. By varying the point of saturation, different characteristic can be obtained and those are (a) Definite Time (b) Inverse Definite Minimum Time(IDMT) (c) Very Inverse 22 P a g e / P S P / L. N T r i p a t h y
27 (d) Extremely Inverse The torque of these relays is proportional to φ 1 φ 2 Sinα, where, φ1 and φ2 are the two fluxes and α is angle between them. Where both the fluxes are produced by same quantity ( Singe Quantity relays) as in the case of current or voltage operated, the torque is proportional to I 2, the coil current below saturation or T = KI 2. If core made to saturate at a very early stage with the result that by increasing I, K decreases so that the time of operation remain the same over the working range, the time-current characteristic obtain is known as Definite Time characteristic. If the core is made to saturate at later stage, the characteristic obtain is known as IDMT. The time current characteristic is inverse over some range and then after saturation assumes the definite time form. In order to ensure selectivity, it is essential that the time of operation of relay should be depended on severity of the fault in such a way that more severe the fault, less is the time to operate, this being called Inverse-time characteristic. This will also ensure that the relay shall not operate under normal over load condition of short duration It is essential also that there shall be a definite minimum time of operation, which can be adjusted to suit the requirement of particular installation. At low value of operating current, the shape of the curve is determined by the effect of the restraining force of the control spring, while at high value the effect of saturation predominates. Different time setting can be obtained by moving a knurled clamping screw along a calibrated scale graduated from 0.1 to 1.0 in the step of This arrangement is called Time multiplier setting and will vary the travel of the disc required to close the contact. This will shift the time-current characteristic of the relay parallel to itself. By delaying the saturation point to further, the time current characteristic called Very Inverse and Extremely Inverse can be obtained Pre-Experimental Quiz (1) What do you understand by (a) Primary Relay (b) Secondary Relay (c) Auxiliary Relay? (2) What do you understand by (a) Single quantity Relay (b) Double or Multi- Quantity relay? (3) What are the types of Over current and earth fault relay? (4) Can the over current and earth fault relay be actuated by both A.C and D.C? (5) What is meant by Pick-up current, Drop out current and Drop out ratio? (6) Where do you connect over current and earth fault relay? (7) What is meant by (a) Sensitivity and (b) Selectivity of relay? Materials and Equipments CDG 11 over current relay, Earth fault relay, current transformer, 3 phase contactor, single phase load, Digital timer and Ammeter. 23 P a g e / P S P / L. N T r i p a t h y
28 Procedure:- (1) Over current Relay (a) Study the construction part of the relay and identify the various parts (b) Connect as per the circuit (c) Set the pick-up value of current at 100% full load current by inserting the plug in the groove. (d) Set the time multiplier setting (TMS) initially at 1.0 (e) Adjust the load current to about 1.3 times the full load current by shorting the switch K. Open the switch K to permit this adjusted current to flow through the relay via current transformer and record the time taken for this over load condition. (f) Vary the value of load current in step and record the time taken for operation of the relay in each case with help of timer. (g) Repeat the step (e) and (f) for TMS value of 0.2, 0.4, 0.6 and 0.8. (h) Repeat the above experiment with different pick-up current values using the plug setting Bridge. (2) Earth Fault Relay (a) Study the construction part of the relay and identify the various parts (b) Connect as per the figure replacing the over current relay by earth fault relay (c) The pick-up value of the current is set to Full load current using plug setting Bridge (d) Set the TMS to 1.0 (e) Vary the load current in different steps as in part (1) and record the operating current value and the time of operation in each case. (f) Repeat the step (e) for different TMS value as in over current experiment. (g) Repeat the above experiment with different pick-up current values( Using the plug setting bridge, pick-up current can be varied) Data Sheet: (1) Type of Relay : Pick up Current ( Plug Set) = Sr. No 1 Current In Amp. Plug Setting Multiplier (PSM) Operating Time in Secs for TMS of P a g e / P S P / L. N T r i p a t h y
29 Data Processing and Analysis (a) Plot the operating time versus the multiple of plug setting value for different TMS on the same graph for over current relay (b) Plot on a log-log sheet operating time versus the multiple of plug setting value for different TMS on the same graph for over current relay (c) Observe the Inverse nature of the characteristic as well as the definite minimum time required for the operation of the relay in either case if possible Post Experimental Quiz (1) Do you like to add directional feature for over current protection? (2) Can the over current and earth fault relay made to operate instantaneously and how? (3) Why the relay disc is not normally circular? (4) What are the equation of IDMT, very inverse, extremely inverse over current relay? (5) When do you use negative phase sequence filter Reference: (1) A.R Van C. Warrington Protective Relays, There theory & Practice Volume I and II, Chapman & Hall (2) C.R Mason, Art and Science of Protective Relays. (3) B. Ravindranath and M. Chander, Power System Protection and Switch Gear. (4) Y.G Paithankar, S.R Bhide, Fundamental of Power System Protection, PHI 25 P a g e / P S P / L. N T r i p a t h y
30 IDMT Relay Diagram Figure 1 26 P a g e / P S P / L. N T r i p a t h y
31 Connection Diagram Group No.:- Students Name:- Roll No 27 P a g e / P S P / L. N T r i p a t h y
32 Indira Gandhi Institute of Technology, Sarang, Dhenkanal B.Tech, 4 th Year, 7 th Semester, Electrical Engineering Department Experiment No :- Date:- Principle of Circulating Current differential Relaying Motivation Fault and abnormal conditions are inevitable in power system. In order to provide normal operation of the power system and consumer units, it is necessary to detect and isolate the fault from the healthy circuit in the shortest possible time, thus restoring the normal operating condition. Protective Relaying employed for such task should have qualities of Selectivity, Speed of Operation, Sensitivity and Reliability. Differential protection fulfils these requirements to large extend. The differential scheme is particularly suitable for alternator, Transformer, Transmission line, feeder etc. The main requirement of differential protection scheme is that the Current Transformers used in this scheme should be properly matched. In case such a matched pair is not available, there would be an imbalance secondary current and this should be pre-determined in order to adjust the relay setting. The relay should not operate for this imbalance current. Objectives (a) To determine the imbalances in Current Transformers in the normal operating range (b) To study the circulating current differential scheme. Theory Differential protection is a unit protection scheme which protect a particular equipment for particular fault. For protection of generators, normally unbiased differential relays are used. The differential relay senses the vector difference between incoming and outgoing current of the equipments to be protected. Figure given below explain principle of differential relay. During healthy condition, the incoming current I1 and outgoing current I2 will be equal. So the CT secondary current will be equals and no current will flow through the relay coil.. Similar is the case for external fault at F1. In this case incoming and outing current obviously will be very high, however they will be equal in magnitude and phase. 29 P a g e / P S P / L. N T r i p a t h y
33 The current transformers, if faithfully transform the current, then the secondary current i1 and i2 will be equal and there will be no current in the relay coil. When there is an internal fault at f, the currents i1 and i2 will not be equal and hence differential current (i1-i2) will flow through the relay coil. If this current is higher than the pick-up setting of the relay, it will operate, tripping the Circuit Breaker and thus isolating the faulty apparatus from the source. Figure(1) Requirement of Differential Protection:- (1) The differential protection scheme should be sensitive for in-zone fault and should be stable against external fault (2) The C.T s should be connected with proper polarity as shown in figure, otherwise the sum of the current (i1 + i2 ) will flow through the differential relay and hence the relay will operate even in healthy condition of the equipment to be protected. (3) For ensuring the stability of differential protection scheme against external fault, the CTs should be identical w.r.t to their saturation characteristic. The knee point voltage of CTs should be high. Pre-Experimental Quiz (1) What do you understand by sensitivity of Relay? (2) What are likely consequences if faults are not cleared fast? (3) Why do the current transformer exhibit non identical characteristic? (4) What are the problems can be caused due to the non-identical characteristic of CTs (5) What is magnetic inrush current in transformer and what is its consequences? (6) Why this scheme is not normally used for protection of transmission line? (7) Can a current balance protection scheme be used for protection of busbar? 30 P a g e / P S P / L. N T r i p a t h y
34 Procedure:- (Figure 2) (1) See that switch S1 and S2 are open and autotransformer supply zero voltage. Now press the start button. Slowly apply the supply voltage through the autotransformer in step of 25 volt and note the reading of ammeter A1, A2 and A3. This is the normal condition where ammeter A1, A2 will show the same magnitude of current and ammeter A3 will show zero reading. The relay will not operate. (2) Again reduce the supply voltage to zero by autotransformer. Close the switch S2, increase the supply voltage in step of 25V and note the reading of ammeter A1, A2 and A3. This is the condition of external fault where ammeter A1 and A2 will show same ( but higher than the former case) magnitude of current. The relay will not operate. (3) Again reduce the supply voltage. Open the switch S2 and close switch S1, increase the supply voltage in step of 25V and note the reading of Ammeter A1,A2 and A3. Observe the operation of relay and tripping of circuit breaker. This is the condition of internal fault where the current shown by ammeters A1 and A2 will differ by a value shown by ammeter A3. The relay operates after the supply voltage is sufficient to pass more than the pick-up value of the current through the relay coil. Reverse the polarity of any CT. So the CTs are now connected with incorrect polarity. The current (i1 +i2) will flow through the relay coil. Therefore relay will mal operate in normal condition. Figure 2 Data Processing and Analysis. Actual Reading 31 P a g e / P S P / L. N T r i p a t h y
35 Sr. No Type of Operation 1 Normal Supply Voltage in Volt. Incoming Current I in in Amp. Out going Current I out in Amp Diverted Current I div in Amp Relay Current In Amp. Remark 2 Internal fault 3 Internal fault 4 Internal fault 5 Internal fault 6 Internal fault 7 Internal fault 8 CT polarity Reversed Post Experimental Quiz:- (1) Why the differential Relay operate only for Internal fault but remain insensitive to external fault? (2) Why the relay operate when one of the CT polarity is reversed? (3) What do you mean by basic setting and biased setting of differential relay? (4) Explain why biased differential relay is required for Transformer Protection? (5) What are the Applications of differential relay? (6) Write the technical specification of Differential Relay? Reference: (1) A.R Van C. Warrington Protective Relays, There theory & Practice Volume I and II, Chapman & Hall (2) C.R Mason, Art and Science of Protective Relays. (3) B. Ravindranath and M. Chander, Power System Protection and Switch Gear. (4) Y.G Paithankar, S.R Bhide, Fundamental of Power System Protection, PHI Group No.:- Students Name:- Roll No 32 P a g e / P S P / L. N T r i p a t h y
POWER SYSTEM II LAB MANUAL
POWER SYSTEM II LAB MANUAL (CODE : EE 692) JIS COLLEGE OF ENGINEERING (An Autonomous Institution) Electrical Engineering Department Kalyani, Nadia POWER SYSTEM II CODE : EE 692 Contacts :3P Credits : 2
More informationPower System Protection Manual
Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,
More informationDEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR
DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR Power system protection Laboratory (EE 852) 8 th Semester Electrical Expt. No. 852/1 BIFFI S METHOD FOR TESTING CURRENT
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationBusbars and lines are important elements
CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationElectrical Protection System Design and Operation
ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationElectrical Power Systems
Electrical Power Systems CONCEPT, THEORY AND PRACTICE SECOND EDITION SUBIR RAY Professor MVJ College of Engineering Bangalore PHI Learning Pfcte tofm Delhi-110092 2014 Preface xv Preface to the First Edition
More informationDesign and Simulation of Passive Filter
Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt
More informationA NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG
A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when
More informationTransmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection
Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed
More informationEarth Fault Protection
Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
More informationPower systems Protection course
Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and
More informationR10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours
Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions
More informationDetermination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System
ISSN (e): 2250 3005 Vol, 04 Issue, 5 May 2014 International Journal of Computational Engineering Research (IJCER) Determination of Optimal Account and Location of Series Compensation and SVS for an AC
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationSCHEME OF COURSE WORK ( ) Electrical & Electronics Engineering. Electrical machines-i, II and power transmission engineering
SCHEME OF COURSE WORK (2015-2016) COURSE DETAILS: Course Title Course Code Program Branch Semester Prerequisites Course to which it is prerequisite Switchgear and Protection 15EE1116 B.Tech Electrical
More information3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]
Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant
More informationEE 740 Transmission Lines
EE 740 Transmission Lines 1 High Voltage Power Lines (overhead) Common voltages in north America: 138, 230, 345, 500, 765 kv Bundled conductors are used in extra-high voltage lines Stranded instead of
More informationChapter 10: Compensation of Power Transmission Systems
Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome
More informationCOPYRIGHTED MATERIAL. Index
Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationPower System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)
Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving
More informationUnit Protection Differential Relays
Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents
More informationEE 340 Transmission Lines
EE 340 Transmission Lines Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of the power system.
More informationDynamic Model Of 400 Kv Line With Distance Relay. Director Research, The MRPC Company, Hyderabad, India 2
Dynamic Model Of 400 Kv Line With Distance Relay Ramleela Khare 1, Dr Filipe Rodrigues E Melo 2 1 Director Research, The MRPC Company, Hyderabad, India 2 Assoc. Professor Commerce, St. Xavier s College
More informationIn Class Examples (ICE)
In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6
More informationIGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004
IGEE 40 Power System Analysis FINAL EXAMINATION Fall 004 Special instructions: - Duration: 150 minutes. - Material allowed: a crib sheet (double sided 8.5 x 11), calculator. - Attempt 4 out of 7 questions.
More informationFatima Michael college of Engineering and Technology
Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric
More informationMODEL POWER SYSTEM TESTING GUIDE October 25, 2006
October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date
More informationSHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP
SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,
More informationPROTECTION APPLICATION HANDBOOK
BOOK No 6 Revision 0 Global Organization Innovative Solutions Product & Substation System Business Business PROTECTION APPLICATION HANDBOOK BA THS / BU Transmission Systems and Substations LEC Support
More informationSequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network
Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria
More informationPOWER SYSTEM PROTECTION LECTURE NOTE
POWER SYSTEM PROTECTION LECTURE NOTE BY Dr R.K.Jena 1 Disclaimer This document does not claim any originality and cannot be used as a substitute for prescribed textbooks. The information presented here
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More informationConventional Paper-II-2011 Part-1A
Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance
More informationDEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What
More informationPIPSPC. Prepared by Eng: Ahmed Safie Eldin. And. Introduction. Protection Control. Practical. System. Power
PIPSPC Practical Introduction Power System Protection Control Practical Introduction To Power System Protection And Control Prepared by Eng: Ahmed Safie Eldin 2005 Contents POWER SYSTEMS PRINCIPALS. 1
More informationEE 340 Transmission Lines. Spring 2012
EE 340 Transmission Lines Spring 2012 Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of
More informationwww. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay
Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:
More informationConventional Paper-II-2013
1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine
More informationUniversity of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab
University of Jordan School of Engineering Electrical Engineering Department EE 219 Electrical Circuits Lab EXPERIMENT 7 RESONANCE Prepared by: Dr. Mohammed Hawa EXPERIMENT 7 RESONANCE OBJECTIVE This experiment
More informationR10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)
R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between
More informationRajasthan Technical University, Kota
COURSE FILE POWER SYSTEM ENGINEERING Name Branch Session Semester : Dr. Dinesh Birla : Electrical Engineering : 2012-13, Odd Semester : B. Tech VII Semester Index: Course File Sr. No. 1 Students Detail
More informationPAPER-II (Subjective)
PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More information1 Introduction General Background The New Computer Environment Transmission System Developments Theoretical Models and Computer Programs
Modeling Techniques in Power Systems 1 General Background The New Computer Environment Transmission System Developments Theoretical Models and Computer Programs 2 Transmission Systems Linear Transformation
More informationCHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM
CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM 3.1 INTRODUCTION Static synchronous compensator is a shunt connected reactive power compensation device that is capable of generating or
More informationTransmission Line Transient Overvoltages (Travelling Waves on Power Systems)
Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) The establishment of a potential difference between the conductors of an overhead transmission line is accompanied by the production
More informationTypes CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay
Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationTRANSFORMER OPERATION
Chapter 3 TRANSFORMER OPERATION 1 A transformer is a static device (no moving parts) used to transfer energy from one AC circuit to another. This transfer of energy may involve an increase or decrease
More informationEQUIVALENT CIRCUIT OF A SINGLE-PHASE TRANSFORMER
Electrical Machines Lab Experiment-No. One Date: 15-11-2016 EQUIVALENT CIRCUIT OF A SINGLE-PHASE TRANSFORMER Aim: The determination of electrical equivalent circuit parameters of a single phase power transformer
More informationINSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE
INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of
More informationRelay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle
Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic
More informationPower System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur
Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur Lecture - 10 Transmission Line Steady State Operation Voltage Control (Contd.) Welcome
More informationTesting of Circuit Breaker and over Current Relay Implementation by Using MATLAB / SIMULINK
Testing of Circuit Breaker and over Current Relay Implementation by Using MATLAB / SIMULINK Dinesh Kumar Singh dsdineshsingh012@gmail.com Abstract Circuit breaker and relays are being utilized for secure,
More informationAlternating Current Study Guide. Preface. This module is DIFFICULT.
Preface This module is DIFFICULT. This material will take more effort to understand and more effort to pass than tests from previous modules. This is on par with a college-level electrical engineering
More informationROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING
ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR 621 212 DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING EE1003 HIGH VOLTAGE ENGINEERING QUESTION BANK UNIT-I OVER VOLTAGES IN ELECTRICAL POWER SYSTEM
More informationGATE 2000 Electrical Engineering
GATE 2000 Electrical Engineering SECTION A (TOTAL MARKS=75) 1. This question consists of 25 (TWENTTY FIVE) sub-questions. Each sub-question carries ONE mark. The answers to these sub-questions MUST be
More informationDelayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines
Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,
More informationExperiment 3. Performance of an induction motor drive under V/f and rotor flux oriented controllers.
University of New South Wales School of Electrical Engineering & Telecommunications ELEC4613 - ELECTRIC DRIVE SYSTEMS Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented
More information# - - Internal * On Line Examination
COURSE NAME : ELECTRICAL ENGINEERING GROUP COURSE CODE : EE/EP SEMESTER : FIFTH SUBJECT TITLE : SWITCHGEAR and PROTECTION SUBJECT CODE : Teaching and Examination Scheme: Teaching Scheme TH TU PR PAPER
More information2. Current interruption transients
1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,
More informationTopic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017
Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationBus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero
Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic
More informationCOURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II
COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II [260908] B.E. Third Year Class Electrical 204 Term: 6/2 (DEC-6 to APR-7) Faculty: PROF. J. I. JARIWALA PROF. A. S. SHAH PROF. T. M. PANCHAL PROF. N. B.
More informationELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment)
ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment) 1. In an A.C. circuit A ; the current leads the voltage by 30 0 and in circuit B, the current lags behind the voltage by 30 0. What is the
More informationEarth Fault Relay EFSPL-1A/5A
Earth Fault Relay EFSPL-1A/5A IEEE DEVICES CODE-50N Features Static Device Compact, Reliable with Aesthetic Value Rugged, Robust and Tropicalised design Consistent repeat accuracy Wide Current Operating
More informationStability Enhancement for Transmission Lines using Static Synchronous Series Compensator
Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationAC CURRENTS, VOLTAGES, FILTERS, and RESONANCE
July 22, 2008 AC Currents, Voltages, Filters, Resonance 1 Name Date Partners AC CURRENTS, VOLTAGES, FILTERS, and RESONANCE V(volts) t(s) OBJECTIVES To understand the meanings of amplitude, frequency, phase,
More informationSize Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM
Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Dr. Jagdish Kumar, PEC University of Technology, Chandigarh Abstract the proper selection of values of energy storing
More informationRAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements
RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationCourse No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content
Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION Sr. No. Course Content 1.0 Fault Current Calculations 1.1 Introduction to per unit and percentage impedance 1.2
More informationSymmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines
Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India
More informationPower Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer
Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer C.GOPI*, M.KISHOR** *(Department. of Electrical and Electronics Engineering, SVPCET, Puttur)
More informationCourse ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation
Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission
More informationEEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER
EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER Objective To analyse the differential protection scheme as applied to a three-phase power transformer
More informationVALLIAMMAI ENGINEERING COLLEGE
P a g e 2 Question Bank Programme Subject Semester / Branch : BE : EE6201-CIRCUIT THEORY : II/EEE,ECE &EIE UNIT-I PART-A 1. Define Ohm s Law (B.L.T- 1) 2. List and define Kirchoff s Laws for electric circuits.
More informationTransformer Waveforms
OBJECTIVE EXPERIMENT Transformer Waveforms Steady-State Testing and Performance of Single-Phase Transformers Waveforms The voltage regulation and efficiency of a distribution system are affected by the
More informationTransmission Line Models Part 1
Transmission Line Models Part 1 Unlike the electric machines studied so far, transmission lines are characterized by their distributed parameters: distributed resistance, inductance, and capacitance. The
More informationEASUN REYROLLE LIMITED
OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT
More informationFigure Derive the transient response of RLC series circuit with sinusoidal input. [15]
COURTESY IARE Code No: R09220205 R09 SET-1 B.Tech II Year - II Semester Examinations, December-2011 / January-2012 NETWORK THEORY (ELECTRICAL AND ELECTRONICS ENGINEERING) Time: 3 hours Max. Marks: 80 Answer
More informationTransformer Fault Categories
Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)
More informationUnit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21
Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive
More informationPreface...x Chapter 1 Electrical Fundamentals
Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5
More informationCHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit
CHAPTER 2 Basic Concepts, Three-Phase Review, and Per Unit 1 AC power versus DC power DC system: - Power delivered to the load does not fluctuate. - If the transmission line is long power is lost in the
More informationElectrical Machines (EE-343) For TE (ELECTRICAL)
PRACTICALWORKBOOK Electrical Machines (EE-343) For TE (ELECTRICAL) Name: Roll Number: Year: Batch: Section: Semester: Department: N.E.D University of Engineering &Technology, Karachi Electrical Machines
More informationPROTECTION of electricity distribution networks
PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of
More informationImplementing Re-Active Power Compensation Technique in Long Transmission System (750 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool
Implementing Re-Active Power Compensation Technique in Long Transmission System (75 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool Dabberu.Venkateswara Rao, 1 Bodi.Srikanth 2 1, 2(Department
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationMAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI UNIT III TUNED AMPLIFIERS PART A (2 Marks)
MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI-621213. UNIT III TUNED AMPLIFIERS PART A (2 Marks) 1. What is meant by tuned amplifiers? Tuned amplifiers are amplifiers that are designed to reject a certain
More informationRelay Coordination in the Protection of Radially- Connected Power System Network
Relay Coordination in the Protection of Radially- Connected Power System Network Zankhana Shah Electrical Department, Kalol institute of research centre, Ahemedabad-Mehshana Highway, kalol, India 1 zankhu.shah@gmail.com
More informationOvercurrent Protective Relays
Power System Protection Overcurrent Protective Relays Dr.Professor Mohammed Tawfeeq Lazim Alzuhairi 99 Power system protection Dr.Mohammed Tawfeeq Overcurrent Protective Relays Overcurrent relays Overcurrent
More informationCHAPTER 3 OVER CURRENT AND EARTH FAULT RELAY COORDINATION
18 CHAPTER 3 OVER CURRENT AND EARTH FAULT RELAY COORDINATION 3.1. OVERVIEW OF RELAY COORDINATION Relay coordination has to be carried out based on many other power system studies and Equipment Sizing calculation,
More informationThe measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms
Why Measure Winding Resistance? The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Partial or dead short-circuited
More information