Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy
|
|
- Octavia Fowler
- 5 years ago
- Views:
Transcription
1 A6/ Test Report CESI Approved Page 1 Client MF Trasformatori s.r.l. - Calcinato (BS) Italy Tested equipment Non-enclosed three-phase dry-type power transformer with three windings, with encapsulated windings, for continuous duty, with cooling by air natural convection (AN): MF /965/965 kva - 15 kv / 0,59/0,59 kv Tests carried out Verification of dynamic ability to withstand short-circuit PUBBLICATO A (PAD ) Standards/Specifications IEC {Ed.1.0} ( ) Test date from September 28, 2006 to September 29, 2006 The results reported in this document relate only to the tested equipment. Partial reproduction of this document is permitted only with the written permission from CESI. No. of pages 14 No. of pages annexed 14 Issue date October 31, 2006 Prepared Verified Approved BU COM - M. Assolari BU COM - F. Pizzi BU COM - V. Scarioni CESI Centro Elettrotecnico Sperimentale Italiano Giacinto Motta spa Via R. Rubattino Milano - Italia Telefono Fax Capitale sociale Euro interamente versato Codice fiscale e numero iscrizione CCIAA Registro Imprese di Milano Sezione Ordinaria N. R.E.A P.I. IT
2 A6/ Test Report CESI Approved Page 2 Tests witnessed by Mr. Bai MF Trasformatori s.r.l. Identification of the object not requested Only for laboratory requirement, in order to reproduce the test conditions, all the laboratory data are contained in the document marked: A6/ The measurement uncertainties of the test results reported in this document comply with the following limits: voltage : ± 5 % ; current : ± 5 % ; time : ± 5 % The measurement uncertainties are estimated at the level of twice the standard deviation (corresponding, in the case of normal distribution, to a confidence level of about 95 %) and have to be considered as maximum estimated values referred to that type of measurement. Activity code 56022M M2001IG
3 M2002IG Contents Page Test date Rated characteristics of the tested object assigned by the Client 4 Verification of dynamic ability to withstand short-circuit 5 to 8 Requested values 5 Test arrangements and test procedures 5 Short-circuit tests with three-phase current 6 September 28, 2006 Test circuit M Measurement of short-circuit inductance 8 September 28, 2006 Verification after short-circuit tests 9 to 12 Dielectric routines tests 9 September 28, 2006 Partial discharge measurements 10 to 12 September 29, 2006 Photographs of test object and test arrangements 13 to 14 Pages annexed: Oscillogram (total pages: 14) Test Report CESI A6/ Approved Page 3
4 A6/ Test Report CESI Approved Page 4 Rated characteristics of the tested object assigned by the Client Dry-type power transformer with three windings Manufacturer MF Trasformatori s.r.l. Calcinato (BS) Manufacturer's serial number /1 Year of manufacturing 2006 Number of phases 3 Rated voltage of the high-voltage winding (primary winding) 15 kv ± 4 x 2,5 % Rated voltage of the low-voltage windings (secondary windings) 590/590 V Rated voltage ratio 15 kv / 0,59-0,59 kv Rated frequency 50 Hz Rated power 1930/965/965 kva Rated current of the high-voltage winding (primary winding) 74,3A Rated current of the low-voltage windings (secondary windings) 944/944 A Short-circuit impedance V cc1-(2-3) 16,56 % Ratio X/R 16,095 Connection symbol Dd0y11 Cooling method AN Total mass 5100 kg Climatic class C2 Environmental class E2 Fire behaviour class F1 Service class VI Characteristics of the windings Highest voltage for equipment applicable to the high-voltage winding 17,5 kv Highest voltage for equipment applicable to the low-voltage windings 1,1 kv Rated insulation levels LI 95 AC 38 / AC 3 Insulation class F Type of construction with circular concentric coils High-voltage winding conductor aluminium Low-voltage windings conductor metal foil (aluminium) Traction transformer conforms to CEI EN Standard Name and signature of Client's witness: M2027IG
5 A6/ Test Report CESI Approved Page 5 Verification of dynamic ability to withstand short-circuit Requested values Test current values were calculated neglecting the system impedance. Tap-changer Short-circuit current (*) U position r Z SC X/R k x 2 r.m.s. value peak value - kv % - - A A 5-6/7-8 15,0 16,56 16,095 2,55 259,0 660,4 1-2/7-8 16,5 16,36 16,663 2,55 238,3 607,7 5-6/ ,5 16,83 15,692 2,55 283,2 722,0 (*) Values of phase short-circuit current of the high-voltage winding (delta-connected). Test arrangements and test procedures The transformer was tested connecting a three-phase supply to the high-voltage winding (primary winding). The low-voltage windings were short-circuited before the application of the voltage to the other winding of the transformer (pre-set short-circuit). During each test were recorded the line-to-line supply voltages, the phase currents of the high -voltage winding and the fault current, if any, between the mass (insulated) of the transformer and earth. Nine tests were performed (three tests on each limb): three tests with the tap-changer on the principal tapping (with the maximum peak current on the middle limb), three tests with the tap-changer in the position corresponding to the highest voltage ratio (with the maximum peak current on one of the outer limbs), three tests with the tap-changer in the position corresponding to the lowest voltage ratio (with the maximum peak current on one of the other outer limbs). M2028IG
6 A6/ Test Report CESI Approved Page 6 Short-circuit tests with three-phase current Test circuit: Test frequency: Reference number of the oscillograms: Conditions of the transformer before the tests: Transformer prearranged on the voltage ratio: M Hz MP-A6/ as supplied by the Client 15 kv / 0,59-0,59 kv Date: September 28, 2006 Tap-changer No-load Test current Test Oscillogram position supply peak r.m.s. average Duration voltage value value value No. No./sheets - V A A A s 176,1 1 1/1 5-6/ ,4 174,5 175,6 0,1 176,2 258,9 2 2/ ,5 256,1 258,0 0,5 258,9 258,8 3 3/ ,5 256,5 258,1 0,5 259,0 257,7 4 4/ ,8 254,7 256,8 0,5 257,8 5 5/1 1-2/ ,2 241,5 238,0 240,3 0,5 241,4 6 6/ ,5 241,4 236,2 239,4 0,5 240,7 7 7/ ,8 242,3 237,7 240,5 0,5 241,5 8 8/1 5-6/ ,9 275,8 278,2 0,5 709,5 279,9 9 9/ ,0 273,8 276,3 0,5 702,8 277, / ,9 275,7 278,0 0,5 707,6 279,5 Conditions of the transformer after the tests: see notes - Externally did not show any damage. M2029IG
7 A6/ Test Report CESI Approved Page 7 Test circuit M0022 The symbols used in this diagram are the same as those on the oscillograms. Correspondence between laboratory circuit phase and test object terminal Laboratory circuit phase R S T Test object terminal U V W M0022IG
8 M2032IG Measurement of short-circuit inductance The measurement of short-circuit inductance was performed before the short-circuit tests and after every series of three tests by means of a Schering bridge (Maxwell diagram) which allows a reproducibility of at least ± 0,2%. For all measurements the transformer was set-up in the following conditions: the tap-changer was placed in the position corresponding to the highest voltage ratio, the terminals of the low-voltage windings were short-circuited, the measurement points were applied to the terminals of the high-voltage winding, delta-connected. Date: September 28, 2006 short-circuit inductance variation short-circuit inductance variation tap-changer [mh] [%] [mh] [%] measurement effected position measured at the terminals from the initial measurement calculated for single limb from the initial value U-V U-W V-W U-V U-W V-W U V W U V W 1-2/7-8 before the tests 147,05 146,50 147, , , , /7-8 after the test no ,20 146,54 147,78 0,10 0,03 0,03 220, , ,871 0,15 0,00 0,00 1-2/7-8 after the test no ,06 146,48 147,84 0,01-0,01 0,07 220, , ,761-0,01 0,12-0,05 1-2/7-8 after the test no ,25 146,60 147,92 0,14 0,07 0,12 220, , ,927 0,16 0,13 0,03 Maximum variation of short-circuit inductance stated by Standard: 4%. Test Report CESI A6/ Approved Page 8
9 A6/ Test Report CESI Approved Page 9 Verification after short-circuit tests Dielectric routines tests (at 100% of the original test values) Separate-source AC withstand voltage test The single-phase test voltage was applied between the terminals of the winding under test and the terminals of the other windings and core and frame, connected together to earth. Date: September 28, 2006 Winding Tap-changer Tapping voltage Test parameters under test position of HV winding voltage frequency duration - - kv kv Hz s high-voltage 5-6/7-8 15,0 38, low-voltage d 3, low-voltage y 3, Test result: no collapse of the test voltage occurred. Induced AC voltage test (ACSD) The three-phase test voltage was applied to the terminals of the low-voltage winding y and the relevant neutral terminal was connected to earth. Date: September 28, 2006 Winding Tap-changer Tapping voltage Test parameters under test position of HV winding voltage frequency duration - - kv kv Hz s low-voltage y 5-6/7-8 15,0 1, Test result: no collapse of the test voltage occurred. M2034IG
10 A6/ Test Report CESI Approved Page 10 Circuit A0153 Induced AC voltage test circuit for partial discharge measurement - Test circuit at 150Hz, three-phase connection CO - frequency converter NUOVA SACCARDO; power 80 kva; input voltage 380V/660V at 50 Hz; output voltage 660 V ± 10 % at 150 Hz G - Faraday cage R - three-phase voltage regulator; power 187 kva; voltage V/ V E - earth connection V 1 - direct reading digital voltmeter FLUKE; CESI No n - neutral connection K - charge pulse generator AMPERE; CESI No D - capacitive voltage divider PASSONI & VILLA; type CD; C= 300 pf; V= 250 kv; scale factor 2551,0; CESI No V 2 - direct reading digital voltmeter AGILENT 34401A; CESI No C a - C b - C c - coupling capacitor PASSONI & VILLA; C= 2000 pf; voltage 150 kv; CESI No (one for each phase) AKV - matching coupling quadrupole HAEFELY TRENCH; type AKV 573; CESI No K - special, multi-wire, connecting cable PD - partial discharge detector HAEFELY TRENCH; type TE 571; CESI No A0153IG
11 A6/ Test Report CESI Approved Page 11 Circuit A0160 Partial discharges measurement Direct circuit - Scheme 1a P - calibrator AMPERE; CESI No C k - coupling capacitor PASSONI & VILLA; C= 2000 pf; voltage 150 kv; CESI No (one for each phase) AKV - matching coupling quadrupole HAEFELY TRENCH; type AKV 573; CESI No K - special, multi-wire, connecting cable PD - partial discharge detector HAEFELY TRENCH; type TE 571; CESI No A0160IG
12 A1262IG Partial discharge measurement (after short-circuit test) Test object: Non-enclosed three-phase dry-type power transformer with three windings, with encapsulated windings, for continuous duty, with cooling by air natural convection (AN): MF 1930/965/965 kva - 15 kv / 0,59/0,59 kv Test circuit: A0153 Measurement circuit: A0160 (direct calibration 5 pc, oscillogram No.11) Arrangement: see photographs from No.3 to No.4 Test frequency: 150 Hz Atmospheric conditions and correction factor b t d /t w h Relative humidity kpa C g / m 3 % 100,23 25,0 / 17,0 10,07 43,9 Date: September 29, 2006 Phase Applied induced voltage Duration of the Partial discharge measurement Required voltage Temperature of lv side HV side voltage the test object voltage increase voltage decrease (phase-to-phase) (phase-to-phase) (phase-to-phase) application Oscillogram V 1 V 2 V HV =V 2 *K 2 * 3 PD level PD level kv rms V rms V rms kv rms s C pc pc No. 1W 1,8Ur direct reading on HV side 6,07 27, ,0 1,3Ur direct reading on HV side 4,39 19, ,5 12 1V 1,8Ur direct reading on HV side 6,07 27, ,0 1,3Ur direct reading on HV side 4,39 19, ,5 13 1U 1,8Ur direct reading on HV side 6,07 27, ,0 1,3Ur direct reading on HV side 4,39 19, ,5 14 Notes Ur is the rated voltage of the high-voltage winding (primary winding) equal to 15,0 kv (phase-to-phase) K 2 is the scale factor of the capacitive voltage divider (D) equal to 2566,4 Test Report CESI A6/ Approved Page 12
13 A6/ Test Report CESI Approved Page 13 Photo no. 1 Photo no. 2 M2009IG
14 A6/ Test Report CESI Approved Page 14 Photo no. 3 Photo no. 4 M2009IG
15
16
17
18
19
20
21
22
23
24
25
26
27
28
104 Pattanakan 69, Pravet, Bangkok Thailand A VER
Approved Page 1 Client FINE ART CERAMIC Co., Ltd Address of the Client 104 Pattanakan 69, Pravet, 10250 Bangkok Thailand Tested samples/items Pin-Post Type porcelain insulators type ANSI 56/57-4 Tests
More informationType Test of a 145 kv Termination Type TS 145-II
Test Report No 2009-125/2 Type Test of a 145 kv Termination Type TS 145-II Client: 3 M Deutschland GmbH Carl-Schurz-Str.1 41453 Neuss Reporter: Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer This report includes
More informationTitle Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)
Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationHigh-Voltage Test and
Eberhard Wolfgang Hauschild Lemke High-Voltage Test and Measuring Techniques ^ Springer Contents 1 Introduction 1 1.1 Development of Power Systems and Required High-Voltage Test Systems 1 1.2 The International
More informationTT 0710/03. TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: LB.W.3SA.3.1
TT 0710/03 TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: LB.W.3SA.3.1 Tested by: IPH, Berlin RPT No : 2977.2100555.0379 Date: 09 June to 24 June, 2010 Pages: 30 Appendix: --- TT0710.03 A3
More informationAbout us. Vision. To lead our field in innovation, quality and customer service.
a Index 1 2 4 6 7 8 13 About us Low voltage switchgear & bus duct Medium voltage switchgear & bus duct UKAS ACCREDITATION ASTA RECOGNITION Distribution and Power transformers OUR TEAM About us Vision To
More information05e28 Di-electric Strength (High Voltage) Test and Leakage Current Test Proficiency Testing Program
instructions Di-electric Strength (High Voltage) Test and Leakage Current Test Proficiency Testing Program Please read the instructions carefully and perform the testing as directed. Should you have any
More informationISSN: [IDSTM-18] Impact Factor: 5.164
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A REVIEW OF ROUTINE TESTING ON DISTRIBUTION TRANSFORMER Sukhbir Singh 1, Parul Jangra 2, Anoop Bhagat 3, Vipin Saini 4 1 Assistant
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK PO Box 25876 Safat 13119 Kuwait Contact: Mr Atul Madhukar Vaidya Tel: +965 1822600 Fax: +965 24761963 E-Mail: factory@ahleiasg.com Website:
More informationTechnical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope
Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site
More informationCast resin transformers HARMONY TM
Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety
More informationEFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento
Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date
More informationPURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS
PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More information700 Series AC Dielectric Test Sets
700 Series AC Dielectric Test Sets AC Test Systems HAEFELY HIPOTRONICS standard line of AC Test Systems is designed to perform high voltage AC tests on electrical apparatus in accordance with IEC60, IEEE
More informationشركة الوقت للكهرباء والمقاوالت ذ.م.م.
CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge
The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More information86 chapter 2 Transformers
86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.
More informationThis Certificate consists of 75 pages in total.
Object Heat shrinkable indoor termination 1086-16 Type MZDNK-3-15-C Rated voltage, U 0 /U (U m ) 8,7/15 (17,5) kv Conductor material Cu Conductor cross-section 3 x 185 mm 2 Insulation material XLPE Manufacturer
More informationISOLATING TRANSFORMERS FOR TLC PLANTS
ISOLATING TRANSFORMERS FOR TLC PLANTS Isolating transformers for TLC plants The power supply of telecommunication plants and FM/TV relay stations has always entailed numerous problems and specific needs
More informationDiscipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1
Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector
More informationTest description for dry-type transformers chapter for special tests
Test description for dry-type transformers chapter for special tests 1. SCOPE 4 2. STANDARDS 5 3. LIGHTNING IMPULSE TEST 6 4. SOUND LEVEL MEASUREMENT 7 4.1. STANDARD 7 4.2. AIM 7 4.3. THEORETICAL PRINCIPAL
More informationPower transformers for Network, Rectifiers, Furnace
E N G L I S H OTN, OTR, OTF Transformers Power transformers for Network, Rectifiers, Furnace TTR TTO OTN, OTR, OTF reactors TTH OTN, OTR, OTF Transformers Technology Design Our designers experience combined
More information24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD
A NEW GENERATION VOLTAGE REGULATION DISTRIBUTION TRANSFORMER WITH AN ON LOAD TAP CHANGER FOR POWER QUALITY IMPROVEMENT IN THE ELECTRICAL DISTRIBUTION SYSTEMS Sudheer MOKKAPATY Jens WEISS Frank SCHALOW
More informationHoliday Detector mod. 284/35KV
Holiday Detector mod. 284/35KV Telemagnetica S.r.l. Via Teocrito, 36-20128 Milan - Italy Tel: +39-022552900 - Fax: +39-022553097 e-mail: info@telemagnetica.com - http: January 2013 BR-284-35KV-ENG-00 Pag.
More information700 Series AC Dielectric Test Sets
700 Series AC Dielectric Test Sets AC Test Systems HAEFELY HIPOTRONICS standard line of AC Dielectric Test Systems is designed to perform high voltage AC tests on electrical apparatus in accordance with
More informationMSR Series. Modular Series Resonant Systems kV; 500kVA...60,000kVA
MSR Series Modular Series Resonant Systems - 250...2200kV; kva...60,000kva The MSR Series is designed to provide power for FEATURES tests on cables, HV and EHV transformers, gasinsulated switchgear, bushings,
More informationROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING
ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR 621 212 DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING EE1003 HIGH VOLTAGE ENGINEERING QUESTION BANK UNIT-I OVER VOLTAGES IN ELECTRICAL POWER SYSTEM
More informationsave energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers
save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED
More informationMSR Series. Modular Series Resonant Systems kV; 500kVA...60,000kVA FEATURES BENEFITS APPLICATIONS 1/6
MSR Series Modular Series Resonant Systems - 250...2200kV; 500kVA...60,000kVA The MSR Series is designed to provide power for tests on cables, HV and EHV transformers, gasinsulated switchgear, bushings,
More informationVARIABLE FREQUENCY RESONANT TEST SYSTEM
VARIABLE FREQUENCY RESONANT TEST SYSTEM 400kV,1200kVA Tank Type Reactor for Outdoor Cable Test Field 650kV, 5850kVA, Cylinder Type Reactors for Onsite Testing of GIS and Cable PHENIX Variable Frequency
More informationTransformer Tests BEST BALIKESİR ELEKTROMEKANİK SANAYİ TESİSLERİ A.Ş. Facility 1 : Ağır Sanayi Bölgesi No Balıkesir / Türkiye
BEST BALIKESİR ELEKTROMEKANİK SANAYİ TESİSLERİ A.Ş. Facility 1 : Ağır Sanayi Bölgesi No 149 10040 Balıkesir / Türkiye Tel. : + 90 266 241 82 00 Fax : + 90 266 241 52 36 Facility 2 : Organize Sanayi Bölgesi
More informationThree-Phase Transformer Test Systems
Three-Phase Transformer Test Systems PHENIX TECHNOLOGIES R Testing Applications Models Available Perform tests on utility distribution and power transformers in accordance with IEC 60076 and ANSI / IEEE
More informationRING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS USER MANUAL
RING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS F.T.M. S. r. l. Fabbrica trasformatori di misura Via Po, 3 20090 Opera MI - Italy Tel : +39 (0)2 576814 Fax : +39 (0)2 57605296 E-mail: info@ftmsrl.it
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationEE High Voltage Engineering UNIT IV - MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS PART-A 1. Mention the techniques used in impulse current
EE6701 - High Voltage Engineering UNIT IV - MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS PART-A 1. Mention the techniques used in impulse current measurements. Hall generators, Faraday generators and
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More informationMitigating Murphy s Law While Test. Frédéric Dollinger
Mitigating Murphy s Law While Test Frédéric Dollinger Curriculum Vitae Frédéric Dollinger HAEFELY HIPOTRONICS factory Basel Switzerland Area Sales & Marketing Manager Dipl. Ing. / M.Sc. Mechatronic Language:
More information36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)
CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994
More informationMEDIUM-VOLTAGE MEASURING VOLTAGE TRANSFORMERS USER MANUAL
MEDIUM-VOLTAGE MEASURING VOLTAGE TRANSFORMERS USER MANUAL F.T.M. S. r. l. Fabbrica trasformatori di misura Via Po, 3 20090 Opera MI - Italy Tel : +39 (0)2 576814 Fax : +39 (0)2 57605296 E-mail: info@ftmsrl.it
More informationOnsite Mobile AC High Voltage Test System
TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument
More informationCAST RESIN DRY TRANSFORMER
CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,
More informationDistribution transformers Part 2 Ground mounted transformers not closecoupled
PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Technical Specification 35-1 Distribution transformers Part 2 Ground mounted transformers not closecoupled www.energynetworks.org PUBLISHING
More informationSGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:
SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument
More informationREPORT OF PERFORMANCE TIC
REPORT OF PERFORMANCE TIC 1580-13 OBJECT TYPE Three-core power cable 18/30(36) kv, 3x500 mm2, 2XWY(P)-FR XLPE Rated voltage, U 0/U (U m) 18/30 (36) kv Conductor material Cu Conductor cross-section 3x500
More informationCommissioning Manual Distribution Transformers - Three-phase Oil Filled
1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...
More informationIEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4
IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 This report records the results of type tests made on H4 series 20 ka Line Discharge Class
More informationConventional Paper-II-2011 Part-1A
Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance
More informationPower Frequency Withstand Voltage On-site testing of 400 kv GIS
Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,
More informationNEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :
NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE
More informationMGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide
MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888
More informationType 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s
Designed for Partial Discharge Analyzers (PDA s) monitoring rotating machinery or other medium-voltage equipment from 1 to 35 kvac RMS at power-line frequencies of 10 Hz to 1 khz, Mica Capacitor Type 297
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More information76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE
09-1026 TYPE TEST CERTIFICATE OF COMPLETE TYPE TEST OBJECT single-core power cable TYPE 76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE Rated voltage, U o /U (U m ) 76/132 (145) kv Conductor material
More informationCalibration of High-Voltage Test Equipment
Workshop 2000, Alexandria, Virginia, 13 & 14 September 2000 paper No.: 6 of High-Voltage Test Equipment Uwe Clauss, Stefan Maucksch, HIGHVOLT Prüftechnik Dresden GmbH, Dresden, Germany 1. Abstract The
More informationAustralian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS
AS 60044.1 2007 AS 60044.1 2007 Australian Standard Instrument transformers Part 1: Current transformers (IEC 60044-1 Ed.1.2 (2003) MOD) This Australian Standard was prepared by Committee EL-013, Measurement
More information3MElectrical Markets Division
3MElectrical Markets Division Contents Summary 3 Purpose... 3 Test Specimen 3 Test Deviations... 4 Test Results 5 Impulse Test Oscillograms... 10 Specimen Photographs.. 11 Equipment Documentation: Impulse
More informationDEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What
More informationPower Engineering II. High Voltage Testing
High Voltage Testing HV Test Laboratories Voltage levels of transmission systems increase with the rise of transmitted power. Long-distance transmissions are often arranged by HVDC systems. However, a
More informationTEST REPORT. Table Of Contents
Table Of Contents Page 2 of 15 Voltage Ratio...3 Winding Resistance...4 No Load Losses...5 Load Losses...6 Efficiency...7 Regulation...8 Applied Voltage...9 Induced Voltage... 10 Insulation Resistance...
More informationTMC Transformers TMC
TMC Product & Technology Presentation Cast Resin Transformer (CRT) History Cast resin transformers first appeared in Germany during the 1960s. This new style of dry type transformer was developed with
More informationGENERATOR TESTING APPLICATION GUIDE. reliable. precision.
GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing
More informationSGM series. AC Resonant Test System. Applications & Advantages
SGM series AC Resonant Test System insulated switchgear (GIS), but also large rotating machines, instrument and power transformers (for applied voltage tests). Resonant test systems enable not only HVAC
More informationSTS Fully automatic. Large graphic display. Primary injection testing capabilities: up to 3000 A, with the optional module BUX 3000
STS 4000 Multifunction substation maintenance & commissioning test system for current, voltage and power transformers. Capacitance / Tan Delta diagnostic system with the optional module TD 5000. w w w.
More informationA Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment
International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV
More informationGroup F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A
Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating
More informationTMS 580. Transformer Loss Measuring System FEATURES BENEFITS APPLICATIONS
TMS 580 Transformer Loss Measuring System The measurement of the losses in power transformers is an indispensable quality-verification process. Due to the fact that normally the transformer user puts a
More informationElectrical Description
History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60044-2 Edition 1.2 2003-02 Edition 1:1997 consolidated with amendments 1:2000 and 2:2002 Instrument transformers Part 2: Inductive voltage transformers IEC 2003 Copyright -
More informationTEST REPORT NO. 046/081701/99
1775 Old Highway 8 NW Suite 107 St. Paul, MN USA 55112 Tel. +1 (651) 639-0775 Fax. +1 (651) 639-0873 TEST REPORT NO. 046/081701/99 Date: August 26, 1999 Total Number of Pages: 13 Equipment: PM4351 Comet
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities
More informationIntroduction. Centrado leading-edge transformer. Introduction
Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,
More informationSPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers
SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.
More informationTransformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications
The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of
More informationCOMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3
CONTENTS COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONSTRUCTION... 4 ~ 5 A. CORE AND FRAME... 4 B. COIL... 5 C. TEMPERATURE INDICATOR... 5 CHARACTERISTICS... 6 MANUFACTURING FACILITIES...
More informationMobile Power Transformer Test Systm
TMPTTS Series Mobile Power Transformer Test Systm MPTTS Series Mobile Power Transformer Test System is design to test and diagnose in both single phase and three phase power transformer up to 500MVA. The
More informationTest description for dry-type transformers chapter for routine tests
Test description for dry-type transformers chapter for routine tests 1. SCOPE 4 2. STANDARDS 5 3. SEPARATE-SOURCE AC WITHSTAND VOLTAGE TEST 6 3.1. STANDARD 6 3.2. AIM 6 3.3. TEST 6 3.3.1. Tapping position
More informationHigh Votage Module AC/DC/Impulse Test System
TSGADI Series High Votage Module AC/DC/Impulse Test System A digital control and measuring system is used to be control the difference output AC/DC/Impulse and related protection device such as over voltage
More informationHOW TO SAFE GUARD THE TRANSFORMER..???
CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various
More informationDATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO
PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %
More informationPresco AG. Peak Voltmeter. Type PVM-100. Instruction Manual. Table of contents
Zürcherstrasse 70 -CH 8104 Weiningen Tel. + 41 44 750 63 63 Fax + 41 44 750 63 66 P.O. Box 155 Switzerland Email : info@prescoag.com Internet : www.prescoag.com Peak Voltmeter Type PVM-100 Instruction
More informationDielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor
Dielectric response and partial discharge measurements on stator insulation at varied low frequency Nathaniel Taylor Rotating Electrical Machines : The Stator and its Windings turbo-generator motor hydro-generator
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationArc Suppression Coils
Arc Suppression Coils (22kV Arc Suppression Coils ) Introduction Resonance grounding by Petersen coils (Arc Suppression Coils) has been used in Scandinavia and other European countries for some eighty
More informationMEDIUM & HIGH VOLTAGE
MEDIUM & HIGH VOLTAGE TESTING EQUIPMENT VOLTAGE WITHSTAND SGM Series Resonant Systems The SGM series are used for generating high AC voltages at a fixed frequency (mainly 50 or 60 Hz) by means of an excited
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-29792-3 IEC 60076-3:2013 SOUTH AFRICAN NATIONAL STANDARD Power transformers Part 3: Insulation levels, dielectric tests and external clearances in air This national standard is the identical
More informationNXCT 345 kv Test Performance Record For LAPEM
2005 NxtPhase T&D Corporation 2635 Lillooet St. Vancouver, Canada, V5M 4P7 www.nxtphase.com Tel: 604 215 9822 Fax: 604 215 9833 NXCT 345 kv Test Performance Record For LAPEM Information in this document
More informationMINISTRY OF ELECTRICITY
MINISTRY OF ELECTRICITY IRAQ SUPERGRID PROJECTS 400/132 KV GIS SUBSTATIONS VOLUME 3 TECHNICAL SCHEDULES JANUARY 2007 LIST OF REVISIONS 1 2 3 4 5 Current Rev. Date 19.11.04 18.03.05 Aug 05 Oct 05 Jan 07
More informationMETHODS AND CIRCUITS FOR POWER ARC TEST IN AC CURRENT OF THE SIMPLE AND DOUBLE INSULATOR SETS WITH COMPOSITE MATERIAL FOR AERIAL ELECTRIC LINES
METHODS ND CIRCUITS FOR POWER RC TEST IN C CURRENT OF THE SIMPLE ND DOUBLE INSULTOR SETS WITH COMPOSITE MTERIL FOR ERIL ELECTRIC LINES George CURCNU, Constantin INCU, Corneliu CHICIU ICMET-Craiova, Calea
More informationWestern Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.
Western Mining Electric Association San Antonio TX NOVEMBER 15, 2012 PRESENTED BY David L. Harris, PE Customer Technical Executive SPX Transformer Solutions, Inc. Office: 262-521-0166 Cell: 262-617-3039
More informationCDAX 605 High Precision Capacitance & Dissipation Factor Test Set
CDAX 605 High Precision Capacitance & Dissipation Factor Test Set 1 Tan delta and capacitance measurements Hi V A Lo Ground C HL Measure with AC test signal, use Ohms law to calculate: Dissipation factor
More informationAdvanced Test Equipment Rentals ATEC (2832) Lightning Surge Simulator LSS-F02.
Lightning Surge Simulator Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) LSS-F02 www.noiseken.com Conforming to IEC61000-4-5 ed2 Standard LSS-F02 series A simulator
More informationRegional Technical Seminar SHORT CIRCUIT FORCES
Regional Technical Seminar SHORT CIRCUIT FORCES Short Circuit Forces Wallace Exum Electrical Design Engineer wallace.exum@spx.com Agenda 1. What is Short Circuit 2. Types of Faults 3. How to Calculate
More informationIGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards
APPROVED IGS Iranian Gas Standards Contactors. Fax:(9821)-8131-5679 --. /012 34-52673892 :;395- 8? /@A7 B;CD /E FGH 34-52673892I2
More information