MINISTRY OF ELECTRICITY

Size: px
Start display at page:

Download "MINISTRY OF ELECTRICITY"

Transcription

1 MINISTRY OF ELECTRICITY IRAQ SUPERGRID PROJECTS 400/132 KV GIS SUBSTATIONS VOLUME 3 TECHNICAL SCHEDULES JANUARY 2007

2 LIST OF REVISIONS Current Rev. Date Aug 05 Oct 05 Jan 07 Page affected ALL ALL ALL ALL ALL Prepared by SSA JK/MH JK MH/MH JK/MH Checked by (technical) JW JK/MH JK/MH JW JW Checked by (quality assurance) JW JW JW JW JW Approved by JW JW JW JW JW REVISION HISTORY 3 Aug 05 ALL Updated with MOE comments and general alignment across volumes. 4 Oct 05 ALL Specification split into GIS and AIS versions. Capacitor specification rationalised. Impulse withstand and Power frequency withstand values reviewed in accordance with IEC Details for 11 kv (Tertiary) shunt reactors added. 5 Jan 07 ALL General review

3 CONTENT SHEET VOLUME 1 VOLUME 2 VOLUME 3 TECHNICAL SPECIFICATION PLANT TECHNICAL SPECIFICATION & SCHEDULES CIVIL WORKS TECHNICAL SCHEDULES PLANT

4 CONTENTS Page No. SCHEDULE A - SCHEDULE B - SCHEDULE C - MILESTONES FOR THE PURPOSE OF PAYMENT AND HANDOVER TO THE CLIENT... A.1 TIME PERIODS FOR PROCUREMENT, DESIGN, MANUFACTURE, INSPECTION, TESTING, DELIVERY, INSTALLATION, COMMISSIONING AND HANDOVER... B.1 MANUFACTURERS AND PLACES OF MANUFACTURE, TESTING AND INSPECTION... C.1 SCHEDULE C1-400 KV GAS INSULATED SWITCHGEAR... C.1 SCHEDULE C2-400 KV AIS OUTDOOR SWITCHGEAR... C.2 SCHEDULE C3-132 KV GAS INSULATED SWITCHGEAR... C.2 SCHEDULE C4-132 KV AIS OUTDOOR SWITCHGEAR... C.3 SCHEDULE C5-11 KV METALCLAD SWITCHGEAR... C.4 SCHEDULE C6 - TRANSFORMERS REACTORS AND AUXILIARY PLANT... C.4 SCHEDULE C7 - LV SERVICES EQUIPMENT... C.5 SCHEDULE C8 - CABLES... C.5 SCHEDULE C9 - SUBSTATION CONTROL AND PROTECTION SYSTEMS`... C.6 SCHEDULE D - TECHNICAL PARTICULARS... D.1 SCHEDULE D1-400 KV GAS INSULATED SWITCHGEAR... D1.1 SCHEDULE D2-400 KV OPEN TERMINAL SWITCHGEAR... D2.1 SCHEDULE D3-132 KV GAS INSULATED SWITCHGEAR... D3.1 SCHEDULE D4-132 KV OPEN TERMINAL SWITCHGEAR... D4.1 SCHEDULE D5-11 KV (TERTIARY) METALCLAD SWITCHGEAR... D5.1 SCHEDULE D6 - CRANE FOR GIS BUILDING... D6.1 SCHEDULE D7-400/132 KV POWER TRANSFORMERS... D7.1 SCHEDULE D8-400 KV SHUNT REACTORS... D8.1 SCHEDULE D9 - EARTHING TRANSFORMERS (11 KV TERTIARY)... D9.1 SCHEDULE D10 - AUXILIARY TRANSFORMERS (11 KV TERTIARY)... D10.1

5 CONTENTS - Continued Page No. SCHEDULE D11 - CAPACITORS (11 KV TERTIARY)... D11.1 SCHEDULE D12-11 KV (TERTIARY) SHUNT REACTORS... D12.1 SCHEDULE D13 - LVAC SWITCHGEAR... D13.1 SCHEDULE D14 - DC SYSTEM... D14.1 SCHEDULE D V AC UNINTERRUPTIBLE POWER SUPPLY... D15.1 SCHEDULE D16-132/11 KV POWER CABLES... D16.1 SCHEDULE D17 - LV CABLES... D17.1 SCHEDULE D18 - PROTECTION SYSTEM... D18.1 SCHEDULE D19 - SUBSTATION CONTROL SYSTEM... D19.1 SCEHDULE D20 - CONTROL, OPERATION, INDICATION AND ALARM CIRCUITS. D20.1 SCHEDULE D21 - BUSHINGS... D21.1 SCHEDULE E - TECHNICAL DOCUMENTATION/DRAWINGS AND OPERATING AND MAINTENANCE INSTRUCTIONS... E.1 SCHEDULE E1 - DRAWINGS ISSUED WITH THE TENDER... E.1 SCHEDULE E2 - DRAWINGS REQUIRED WITH TENDER... E.2 SCHEDULE E3 - CONTRACT DRAWING REQUIREMENTS... E.3 SCHEDULE E4 - CONTRACTOR S SUBMITTALS - DRAWING AND DESIGN DATA.. E.5 SCHEDULE E5 - INSTALLATION AND MAINTENANCE INSTRUCTIONS... E.7 SCHEDULE E6 - FINAL RECORDS... E.7 SCHEDULE F - DEVIATIONS FROM THE TECHNICAL SPECIFICATION... F.1 SCHEDULE G - SCHEDULE J1 - SCHEDULE J2 - SCHEDULE J3 - QUANTITIES AND PRICES...G.1 RECOMMENDED SPARES...J1.1 SPECIAL TOOLS, TEST EQUIPMENT...J2.1 TRANSFORMERS AND REACTORS QUANTITIES AND PRICES FOR SPARE PARTS...J3.1 SCHEDULE K - BUILDING SERVICES... K.1

6 SCHEDULE L - HEATING, VENTILATION AND AIR CONDITIONING...L.1

7 SCHEDULE A MILESTONES FOR THE PURPOSE OF PAYMENT AND HANDOVER TO THE CLIENT

8 SCHEDULE A - MILESTONES FOR THE PURPOSE OF PAYMENT AND HANDOVER TO THE CLIENT (Information to be provided with Tender) The Tenderer is to indicate all milestones identified within the programme for the works as defined in this Project Specification. The milestones should align with those included in the priced (fixed sum) activity schedule. Item No Description Section A.1 400kV SUBSTATION VOLUME 3

9 SCHEDULE B TIME PERIODS FOR PROCURMENT, DESIGN, MANUFACTURE, INSPECTION, TESTING, DELIVERY, INSTALLATION, COMMISSIONING AND HANDOVER

10 SCHEDULE B - TIME PERIODS FOR PROCUREMENT, DESIGN, MANUFACTURE, INSPECTION, TESTING, DELIVERY, INSTALLATION, COMMISSIONING AND HANDOVER (Information to be provided with Tender. All time periods are weeks from date of Notice to Proceed) Time within which: Description 1 All arrangement and equipment drawings shall be submitted for approval 2 All schemes and functional drawings shall be submitted for approval 3 All wiring and cable diagrams / schedules shall be submitted 4 Plant shall be available for final inspection / test in manufacturer s works 5 Plant shall be delivered to site 6 Plant shall be installed 7 Overall works are commissioned 8 Overall works are handed over to client B.1

11 SCHEDULE C MANUFACTURERS AND PLACES OF MANUFACTURE, TESTING AND INSPECTION

12 SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE, TESTING AND INSPECTION (Information to be supplied with Tender) SCHEDULE C1 400 KV GAS INSULATED SWITCHGEAR Item Manufacturer Place of manufacture Place of testing and inspection 400 kv GIS: Current transformers Voltage transformers Surge arresters Circuit breaker operating mechanisms Circuit breaker operating mech. motors Disconnector/earth switch drive motors Support insulators Expansion bellows Bursting discs Gaskets Conductors Enclosures SF 6 Gas handling plant SF 6 Gas Partial discharge capacitive couplers Transducers Local control cubicles Indicating instruments Control switches Status indicators Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval. C.1

13 SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE, TESTING AND INSPECTION CONT SCHEDULE C2 400 KV AIS OUTDOOR SWITCHGEAR Item Manufacturer Place of manufacture Place of testing and inspection 400 kv AIS Current transformers 400 kv AIS Voltage transformers 400 kv AIS Surge arresters 400 kv AIS Disconnector/earth switches Steel Structures Conductor Support insulators Connectors SCHEDULE C3 132 KV GAS INSULATED SWITCHGEAR Item Manufacturer Place of manufacture Place of testing and inspection 132 kv GIS: Current transformers Voltage transformers Surge arresters Circuit breaker operating mechanisms Circuit breaker operating mech. motors Disconnector/earth switch drive motors C.2

14 SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE, TESTING AND INSPECTION CONT SCHEDULE C3 132 KV GAS INSULATED SWITCHGEAR - Cont Item Manufacturer Place of manufacture Place of testing and inspection SF 6 Gas handling plant SF 6 Gas Partial discharge capacitive couplers Local control cubicles GIS Switchroom Crane Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval. SCHEDULE C4 132 KV AIS OUTDOOR SWITCHGEAR Item Manufacturer Place of manufacture Place of testing and inspection 132 kv AIS Current transformers 132 kv AIS Voltage transformers 132 kv AIS Surge arresters 132 kv AIS Disconnector/earth switches Steel Structures Conductor Support insulators Connectors C.3

15 SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE, TESTING AND INSPECTION CONT SCHEDULE C5 11 KV METALCLAD SWITCHGEAR Item Manufacturer Place of manufacture Place of testing and inspection Metalclad enclosures Circuit breakers Circuit breaker operating mechanisms Interrupters Current transformers Voltage transformers Earthing switches Low voltage equipment Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval. SCHEDULE C6 - TRANSFORMERS REACTORS AND AUXILIARY PLANT Item No Description Manufacturer Place of manufacture Place of testing and inspection 1 400/132 kv Transformer 2 Transformer Tap Changer kv Shunt Reactor 4 11/0.4 kv Auxiliary Transformer 5 Earthing Transformer 6 11 kv Tertiary Capacitor Bank 7 Series Reactor for Capacitor Bank 8 11 kv Tertiary Reactor C.4

16 SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE, TESTING AND INSPECTION CONT SCHEDULE C7 - LV SERVICES EQUIPMENT Item Manufacturer Place of manufacture Place of testing and inspection LVAC Equipment DC Equipment Batteries UPS Equipment Standby Diesel Generator Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval. SCHEDULE C8 - CABLES Item Manufacturer Place of manufacture Place of testing and inspection 132 kv power cable 11 kv power cable LV multicore / multipair cable Cable glands Cable trays Cable ladder racks Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval. C.5

17 SCHEDULE C - MANUFACTURERS AND PLACES OF MANUFACTURE, TESTING AND INSPECTION CONT SCHEDULE C9 - SUBSTATION CONTROL AND PROTECTION SYSTEMS` Item Manufacturer Place of manufacture Place of testing and inspection SCS Substation Computer SCS Operator Workstations / HMI Operator Desk and Chair SCS Colour Visual Display Units SCS Substation LAN SCS Printers SCS Bay Control Unit BCU SCS I/O Cards for BCU SCS Software Engineering SCS Database Engineering Protection Relays Any deviation from this Schedule shall be notified as soon as possible for the Engineer's approval. C.6

18 SCHEDULE D TECHNICAL PARTICULARS

19 SCHEDULE D TECHNICAL PARTICULARS SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR 1 GENERAL Unit Data 1.1 Manufacturer & Place of manufacturing 1.2 Type designation GIS 1.3 Type Metal enclosed, gas insulated GIS- indoor 1.4 Standards IEC IEC , 60694, 60270, 60376, Rated voltage kv System Voltage kv Rated frequency Hz Rated lightning impulse withstand voltage - Phase to earth KV p Across the isolating distance kv p Rated power frequency withstand voltage - Phase to earth kv Across the isolating distance kv Phase to earth at SF6 pressure of 1 bar kv 1.1 U phase 1.10 Rated short-time withstand current (1 s) ka Rated peak withstand current ka Type of busbars Breaker and Half 1.13 Type of enclosure Single phase enclosures 1.14 Material of enclosure for: - Circuit breaker Al/St - Busbars Al/St - Other compartments Al/St 1.15 Material of HV conductor Al/Cu 1.16 Material of contacts (indicate bi-metallic where used) 1.17 Type of contact Tulip D1.1

20 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont 1.18 Minimum subdivision of switchgear: Unit Data - Busbars Yes - Busbar disconnect Yes - Circuit breaker Yes - Circuit disconnect Yes - Cable box Yes - Voltage transformer Yes 1.19 Method of compensation of expansion and contraction - For busbars - For enclosure 1.20 Type of pressure relief device Bursting disk 1.21 Rupturing pressure bar 1.22 Type of filter employed for moisture absorption Molecular Sieve 1.23 Design lifetime of moisture absorbent Years Total mass of switchgear (average per bay) kg 1.25 Mass of heaviest single component to be handled during erection kg 1.26 Total mass of SF6 gas (average per bay) kg 1.27 Density of gas in: - Circuit breaker compartment (g/l) - Other than circuit breaker compartments (g/l) 1.28 Nominal working gas pressure at 15 o C in: - Circuit breaker compartment bar - Other than circuit breaker compartment bar 1.29 Nominal working gas pressure at 50 o C in: - Circuit breaker compartment bar - Other than circuit breaker compartment bar 1.30 Design maximum pressure for: - Circuit breaker compartment bar - Other than circuit breaker compartment bar 1.31 Maximum leakage rate for any gas compartment per annum Less than 1% D1.2

21 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont Unit Data 1.32 Maximum leakage rate for the whole switchgear per Less than 1% annum 1.33 Minimum operating period without total years 10 replacement of SF 6 gas 1.34 Minimum thickness of enclosure mm 1.35 Minimum enclosure puncturing time due to internal arc fault at short-time withstand current ms Greater than Minimum factors of safety for switchgear - Busbars or other connections based on elastic 2.5 limit - Complete insulators based on electromechanical 2.5 test - Insulator metal fittings based on elastic limit Steel structures based on elastic limit of 2.5 tension members and on crippling loads of compression members - Foundations for structures against overturning or uprooting under maximum simultaneous working loadings Seismic factor UBC Zone 3 2 CIRCUIT BREAKER 2.1 Manufacturer & Place of manufacturing 2.2 Type designation 2.3 Type Single pressure puffer, SF Standards IEC , IEC , 61233, 60694, 60427, 60376, Rated voltage kv Rated Current at 50 0 C (Contractor to confirm by calculation) - Main busbar A Bay busbar A Line transformer Circuit A 1600 D1.3

22 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont Unit 2.7 Rated frequency Hz Rated lightning impulse withstand voltage - Phase to earth kv p Across the isolating distance kv p Rated power frequency withstand voltage - Phase to earth kv Across the isolating distance kv Rated short-time withstand current (1 s) ka Rated peak withstand current ka p 100 Data 2.12 Rated operating sequence O -0.3 sec- CO -3 min - CO 2.13 Auto reclosing O -0.3 sec- CO -3 min - CO 2.14 Rated making current ka p Rated breaking current (asymmetrical) ka To IEC %dc %dc 2.17 Rated breaking current under out-of-phase conditions ka 2.18 First phase to clear factor a Transient Recovery Voltages TRV s To IEC Rated capacitive breaking current To IEC Rated line charging breaking current A Rated cable charging breaking current A Rated Single/Back to Back Capacitor bank A breaking current D1.4

23 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont Unit Data 2.20 Rated small inductive/reactor breaking currents of: To IEC small inductive A - reactor A 2.21 Maximum overvoltage factor on any switching duty pu Maximum overvoltage factor when interrupting rated line/cable/capacitor bank charging currents 2.23 Maximum overvoltage factor when switching small inductive/reactor currents 2.24 Maximum total break time (trip initiation to final arc extinction) pu 2.5 pu 2.5 ms Opening time (trip initiation to contact separation) - Without current ms - With 100% rated breaking current ms 2.26 Maximum time interval between opening of first and last phase of three phase circuit breakers 2.27 Maximum time interval between opening of interrupters of one phase 2.28 Closing time from energisation of close coil to latching of circuit breaker in fully closed position ms 3 ms ms 2.29 Making time (energisation of close coil to contact touch) - Without current ms - 100% making current ms 2.30 Maximum time interval between closure of first and last phase of three phase circuit breaker 2.31 Maximum time interval between closure of interrupters of one phase 2.32 Minimum time from extinction of main arc to contact make during auto-reclosing duty 2.33 Mechanical life of circuit breaker and mechanism in No. of operations ms 3 ms ms 10,000 D1.5

24 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont 2.34 Electrical contact life in number of operations at: Unit Data - Rated current A - Fault current - 40 ka 15 to 20 - Cumulative ampere rating 2.35 Number of current interrupting break units in series per phase two 2.36 Type of operating mechanism Spring-charged or hydraulic 2.37 Type of power device (motor charged) - For closing Spring or hydraulic - For opening Spring or hydraulic 2.38 Hand operating facility yes 2.39 Hand charging facility yes 2.40 Manual spring release yes 2.41 Mechanical on/off indicator yes 2.42 Mechanical spring charge / discharge indication yes 2.43 Charging time s 2.44 Number of trip coils Number of close coils Nominal control and operating voltage V 110 DC 2.47 Nominal heater voltage V 220 AC 2.48 Rated power of trip coil W 2.49 Rated power of close coil W 2.50 Rated motor power W 2.51 Total load of heaters for circuit breaker W 2.52 Mass of circuit breaker complete (three pole) kg 2.53 Mass of single phase circuit breaker Emergency Trip Facility during failure of DC supply yes D1.6

25 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont 3 DISCONNECTS Unit Data 3.1 Manufacturer & Place of Manufacturing 3.2 Type designation 3.3 Type of operating mechanism Motor 3.4 Standards IEC , IEC 60694, 61128, , Rated voltage kv Rated current at 50 o C (Contractor to confirm by calculation) Bay selectors A 2000 Circuit disconnector A Rated frequency Hz Rated lightning impulse withstand voltage - Phase to earth kv p Across the isolating distance kv p Rated power frequency withstand voltage - Phase to earth kv Across the isolating distance kv Rated short time withstand current (1 s) ka Rated peak withstand current ka p Maximum capacitive current that can be interrupted by the isolator 3.13 Total time from initiation of opening operation to isolator in fully open position 3.14 Time from contact separation to extinct of capacitive arc 3.15 Total time from initiation of opening operation to time when isolator gap can withstand phase voltage A s s s 3.16 Hand operating facility yes D1.7

26 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont Unit 3.17 Locking arrangement in on/off position yes 3.18 Nominal control and operating voltage V 110 DC Data 3.19 Automatic isolation of control supplies when lock off 3.20 Accessibility to operating mechanism from ground level or catwalk yes yes 3.21 Nominal heater voltage V 220 AC 3.22 Rated power of operation coil W 3.23 Rated motor power W 3.24 Total load of heaters for isolator W 3.25 Total mass of three phase isolator complete kg 3.26 Mass of single phase isolator kg 3.27 Contact type Tulip 4 EARTHING SWITCH 4.1 Manufacturer & place of manufacturing 4.2 Type designation 4.3 Type of operating mechanism Motor 4.4 Standards IEC , IEC 60694, Rated voltage kv Rated frequency Hz Rated lightning impulse withstand voltage phase to earth 4.8 Rated power frequency withstand voltage phase to earth kv p 1425 kv Rated short time withstand current (1 s) ka Rated peak withstand current ka p Hand operating facility yes D1.8

27 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont Unit 4.12 Locking arrangement in on/off position yes 4.13 Nominal control and operating voltage V 110 DC Data 4.14 Automatic isolation of control supplies when lock off 4.15 Accessibility to operating mechanism from ground level or catwalk yes yes 4.16 Nominal heater voltage V 220 AC 4.17 Rated power of operating coil W 4.18 Rated motor power W 4.19 Total load of heaters for earthing switch W 4.20 Total mass of earthing switch complete kg 5 HIGH SPEED EARTHING SWITCH 5.1 Manufacturer & place of manufacturing 5.2 Type designation 5.3 Type of operating mechanism Motor-spring 5.4 Standards IEC , IEC 60694, 61129, Rated voltage kv Rated frequency Hz Rated lightning impulse withstand voltage phase to earth 5.8 Rated power frequency withstand voltage phase to earth kv p 1425 kv Rated short time withstand current (1 s) ka Rated peak withstand current ka p Rated short-circuit making current ka p Rated capacitive symmetrical breaking current A 5.13 Rated inductive symmetrical breaking current A D1.9

28 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont 5.14 Total time from initiation of opening operation to earth switch in fully open position Unit ms Data 5.15 Time from contact separation to extinction of arc when interrupting rated breaking current ms 5.16 Making time ms 5.17 Charging time s 5.18 Hand operating facility yes 5.19 Locking arrangement in on/off position yes 5.20 Nominal control and operating voltage V d.c Automatic isolation of control supplies when lock off 5.22 Accessibility to operating mechanism from ground level or catwalk yes yes 5.23 Nominal heater voltage V 220 AC 5.24 Rated power of operation coil W 5.25 Rated motor power W 5.26 Total load of heaters for earthing switch W 5.27 Total mass of earthing switch complete kg 6 CURRENT TRANSFORMER 6.1 Manufacturer & place of manufacturing 6.2 Type Toroidal, GIS enclosed or external 6.3 Standards IEC 60694, Rated voltage GIS kv 420 Cores V 6.5 Rated lightning impulse withstand voltage phase to earth GIS kv p 1425 Cores kv p D1.10

29 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont Unit Data 6.6 Rated power frequency withstand voltage phase to earth GIS kv 650 Cores kv 3 kv (E K < 2 kv) kv 5 kv (E K 2 kv) 6.7 Rated power frequency voltage between secondaries 6.8 Inter-turn test kv 3 M/P type kv p 4.5 Class PX To IEC Rated frequency Hz Rated continuous thermal current at 50 o C A 6.11 Rated short-time withstand current (1 s) ka Rated dynamic current ka p Are earthed metal screens fitted between primary and secondary windings 6.14 Is current transformer housed in a separate gas compartment 6.15 Details of all current transformers are to be provided by the Contractor post contract award - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) I core II core III core IV core A A A A - Class 7 VOLTAGE TRANSFORMERS 7.1 Manufacturer & Place of manufacturing 7.2 Type designation for - Line transformer 3 phase - Busbar transformer 3 phase D1.11

30 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont Unit Data 7.3 Type Inductive, SF 6 gas insulated, enclosed 7.4 Standards IEC 60186,60694, , Rated voltage kv Rated frequency Hz Rated lightning impulse phase to earth KV p Rated power frequency withstand voltage phase to earth 7.9 Maximum permissible partial discharge level Um 7.10 Maximum permissible partial discharge level 1.2Um / 3 kv 650 pc 10 pc Maximum capacitive current discharge rating A 7.12 Method of suppressing ferroresonance phenomena 7.13 Line bay voltage transformer - Number of secondaries - Rated transformation ratio kv - Rated accuracy class I secondary II secondary - Rated output I secondary II secondary - Mass of single/three phase voltage transformer VA VA kg 7.14 Busbar voltage transformer - Number of secondaries - Rated transformation ratio kv - Rated accuracy class I secondary D1.12

31 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont - Rated output (Burden to be % rated burden) Unit VA Data I secondary - Mass of single/three phase voltage transformer kg 8 SURGE ARRESTERS 8.1 Type 8.2 Standard IEC , , Rated/system voltage kv 420/400 - Maximum overvoltage factor on the system due to any switching duty pu Rated system frequency Hz Condition of system neutral Solid 8.6 Nominal Discharge current ka crest 8.7 Energy capability as per IEC kj/ kv 8.8 Rated voltage - MOA kv 8.9 Long duration discharge class as per IEC Class Maximum Continuous Operating Voltage (COV) kv 8.11 TOV capability for - 1 sec kv - 10 sec kv 8.12 Maximum residual voltage with current wave - Switching Surges - 1kA / 2kA kv - 8/20 μs - 5kA kv - 8/20 μs - 10kA kv 8.14 Discharge current withstand strength - High current (4/10 μs) ka p - Low current 2000A A p D1.13

32 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D1 400 KV GAS INSULATED SWITCHGEAR - Cont 8.15 Pressure relief capability Unit Data - High current (0.2 s) ka - Low current 8.16 Rating of earth connections ka/sec 40/ Surge counter provided Yes 9 CABLE BOX (WHEN APPLICABLE). 9.1 Manufacturer & Place of manufacturing 9.2 Type of designation 9.3 Standards IEC Cable HV test withstand capability kv 9.5 Rated normal current at 40 o C A 9.6 current at 50 o C (Contractor to confirm by calculation) A 9.7 Rated short time withstand current (1s) ka Rated peak withstand current ka Total mass of three phase cable box complete kg 10 MANUFACTURER QUALITY SYSTEM IN ACCORDANCE TO ISO 9000, 9001, 9002, 9003 AND 9004 Yes 10.1 Date of issue Latest 10.2 Validity Valid Certificates Yes 11 TYPE TEST CERTIFICATE TO BE ISSUED BY INDEPENDENT LABORATORY OR INDEPENDENTLY WITNESSED TYPE TEST CERTIFICATE TO BE SUBMITTED Yes D1.14

33 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR 1 GENERAL Unit Data 1.1 Standards IEC IEC , , 60694, 60233, 60044, 60186, 60383, Rated voltage kv System Voltage kv Rated frequency Hz Rated lightning impulse withstand voltage Phase to earth kv p 1425 Across the isolating distance kv p Rated power frequency withstand voltage Phase to earth kv 520 Across the isolating distance kv Rated short-time withstand current (1 s) ka Rated peak withstand current ka Rated Current Cable Feeder at 50 o C (Contractor to confirm by calculation) A 1.10 Material of HV conductor Aluminium 1.11 Material of contacts Bi-metallic 1.12 Minimum factors of safety for switchgear Busbars or other connections based on elastic limit Complete insulators based on electromechanical test Insulator metal fittings based on elastic limit 2.5 Steel structures based on elastic limit of tension members and on crippling loads of compression members Foundations for structures against overturning or uprooting under maximum simultaneous working loadings D2.1

34 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR - Cont Unit 1.13 Creepage distance (based on Um) mm/kv Seismic factor As UBC 2 ISOLATORS 2.1 Type designation 2.2 Type of operating mechanism Motor Data 2.3 Standards IEC , IEC 60694, 61128, Maximum capacitive current that can be interrupted by the isolator A 2.5 Total time from initiation of opening operation to isolator in fully open position 2.6 Time from contact separation to extinct of capacitive arc 2.7 Total time from initiation of opening operation to time when isolator gap can withstand phase voltage s s s 2.8 Hand operating facility Yes 2.9 Locking arrangement in on/off position Yes 2.10 Nominal control and operating voltage V 110 DC 2.11 Automatic isolation of control supplies when lock off 2.12 Accessibility to operating mechanism from ground level Yes Yes 2.13 Nominal heater voltage V 220 AC 2.14 Rated power of operation coil W 2.15 Rated motor power W 2.16 Total load of heaters for isolator W 2.17 Total mass of three phase isolator complete kg 2.18 Mass of single phase isolator kg 2.19 Contact type 2.20 Type of interlocking D2.2

35 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR - Cont 3 EARTHING SWITCH Unit Data 3.1 Type designation 3.2 Type of operating mechanism Hand 3.3 Standards IEC , Hand operating facility Yes 3.5 Locking arrangement in on/off position Yes 3.6 Nominal control and operating voltage V 110 DC 3.7 Automatic isolation of control supplies when lock off 3.8 Accessibility to operating mechanism from ground level Yes Yes 3.9 Nominal heater voltage V 220 AC 3.10 Total load of heaters for earthing switch W 3.11 Total mass of earthing switch complete kg D2.3

36 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR - Cont 4 CURRENT TRANSFORMER Unit Data 4.1 Type Post 4.2 Standards IEC 60694, Rated continuous thermal current at 50 o C Rated extended primary current Note: All Cl PX CTs shall be I SN 1.2 A 4.4 Cable feeder bays current transformer To suit specific requirements Number of cores Rated extended primary current Ratio (TR turns ratio) I core II core III core IV core A A A A Class I core II core III core IV core Knee point voltage (E k ) I core II core III core IV core V V V V Exciting current (I E ) at E k I core II core III core IV core ma ma ma ma Rated output (burden to be % rated burden) I core II core III core IV core VA VA VA VA D2.4

37 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR - Cont Total mass of single phase current transformer complete Unit kg Data 4.5 Bus coupler and bus section bays current transformer To suit specific arrangement Number of cores 120% 5 CAPACITIVE VOLTAGE TRANSFORMERS 5.1 Type Capacitive 5.2 Standards IEC 60186, IEC/PAS : Maximum permissible partial discharge level Um pc Maximum permissible partial discharge level 1.2Um / 3 pc Method of suppressing ferroresonance phenomena 5.5 Line voltage transformer 5.7 Number of secondaries 2 Rated transformation ratio kv 132/ 3 / 0.11/ 3 /0.11/ 3 Rated accuracy class I secondary II secondary 3P/1.0 3P Rated output (burden to be % rated burden) I secondary II secondary Mass of single phase voltage transformer VA VA kg D2.5

38 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR - Cont 6 SURGE ARRESTERS Unit Data 6.1 Type 6.2 Standard IEC , , Rated/system voltage kv 145/ Maximum overvoltage factor on the system due to any switching duty pu Rated system frequency Hz Condition of system neutral Solid 6.7 Nominal Discharge current ka crest 6.8 Energy capability as per IEC kj/ kv 6.9 Rated voltage - MOA kv 6.10 Long duration discharge class as per IEC Maximum Continuous Operating Voltage (COV) Class kv 6.12 TOV capability for 1 sec kv 10 sec kv 6.14 Switching Surges - 1kA / 2kA kv 8/20 μs - 5kA kv 8/20 μs - 10kA kv 6.15 Discharge current withstand strength ka p High current (4/10 μs) A p Low current 2000A 6.16 Pressure relief capability ka High current (0.2 s) Low current ka/sec As per IEC 6.17 Rating of earth connections 40/ Surge counter provided Yes D2.6

39 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR - Cont 7 BUSBARS AND CONNECTIONS Unit Data 7.1 Type (flexible or tubular) 7.2 Material 7.3 Short-circuit current rating / duration ka/s 7.4 Normal current rating at 40 o C at 50 o C A A 7.5 Maximum continuous current rating A 7.6 Flexible conductors stranding nominal cross-sectional area outer diameter no. of conductors per bundle spacing between conductors 7.7 Tubular conductors nominal cross-sectional area outer diameter inner diameter 7.8 Maximum stress at surface of flexible conductor 7.9 Radio influence voltage level measured at 1.1 times Us/ 3 at 1 MHz mm 2 mm mm mm 2 mm mm kv/mm µv D2.7

40 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR - Cont 8 POST TYPE INSULATORS Unit Data 8.1 Type designation 8.2 Insulator material 8.3 Number of units in complete post insulator 8.4 Length of each unit mm 8.5 Mass of complete post insulator kg 8.6 Maximum cantilever working load (complete post insulator) 8.7 Minimum cantilever breaking load, upright (complete post insulator) N N 8.8 Power frequency withstand voltage dry: wet kv 8.9 Basic insulation level kvp 8.10 Minimum dry/wet switching surge withstand level 8.11 Radio influence voltage level measured at 1.1 times Us/ 3 at 1 MHz kvp µv D2.8

41 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR - Cont 9 TENSION AND SUSPENSION INSULATORS Unit Data 9.1 Type designation 9.2 Insulator material 9.3 Number of units in string mm 9.4 Greatest diameter of units mm 9.5 Distance between centres of units mm 9.6 Length of string, overall mm 9.7 Mass of string complete with all fittings kg 9.8 Maximum working load N 9.9 Power frequency withstand voltage of complete string kv 9.10 Basic insulation level of complete string kvp 9.11 Minimum wet switching surge withstand level of complete string 9.12 Radio influence voltage measured at 1.1 times Us/ 3 at 1 MHz kvp µv D2.9

42 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D2 400 KV OPEN TERMINAL SWITCHGEAR Cont KV LINE TRAPS Unit Data 10.1 Maker's type and designation 10.2 Main coil insulation class 10.3 Rated continuous current A 10.4 Rated short time current (1 second/3 seconds) ka 10.5 Power frequency 10.6 Insulating level across line traps at: Power frequency Impulse 10.7 Rated voltage level of protective device kv 10.8 Centre frequency khz 10.9 Bank width of blocking range khz Self resonant frequency khz Tapping loss db Blocking impedance Ω Total mass kg D2.10

43 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR 1 GENERAL Unit Data 1.1 Manufacturer & Place of manufacturing 1.2 Type designation GIS 1.3 Type Metal enclosed, gas insulated GISindoor 1.4 Standards IEC IEC , 60694, 60270, 60376, Rated voltage kv System Voltage kv Rated frequency Hz Rated lightning impulse withstand voltage - Phase to earth kv p Across the isolating distance kv p Rated power frequency withstand voltage - Phase to earth kv Across the isolating distance kv Phase to earth at SF6 pressure of 1 bar kv 1.1 U phase 1.10 Rated short-time withstand current (1 s) ka Rated peak withstand current ka Type of busbars Double 1.13 Type of enclosure Single/Three phase enclosed 1.14 Material of enclosure for: - Circuit breaker Al/St - Busbars Al/St - Other compartments Al/St 1.15 Material of HV conductor Al/Cu 1.16 Material of contacts (indicate bi-metallic where used) D3.1

44 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont Unit 1.17 Type of contact Tulip 1.18 Minimum subdivision of switchgear: - Busbars - Busbar isolator - Circuit breaker Yes - Circuit isolator - Cable box - Voltage transformer Yes 1.19 Method of compensation of expansion and contraction - For busbars - For enclosure Data 1.20 Type of pressure relief device Bursting disk 1.21 Rupturing pressure bar 1.22 Type of filter employed for moisture absorption Molecular Sieve 1.23 Design lifetime of moisture absorbent Years Total mass of switchgear (average per bay) kg 1.25 Mass of heaviest single component to be handled during erection kg 1.26 Total mass of SF6 gas (average per bay) kg 1.27 Density of gas in: - Circuit breaker compartment (g/l) - Other than circuit breaker compartments (g/l) 1.28 Nominal working gas pressure at 15 o C in: - Circuit breaker compartment bar - Other than circuit breaker compartment bar 1.29 Nominal working gas pressure at 50 o C in: - Circuit breaker compartment bar - Other than circuit breaker compartment bar 1.30 Design maximum pressure for: - Circuit breaker compartment bar - Other than circuit breaker compartment bar D3.2

45 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont Unit 1.31 Maximum leakage rate for any gas compartment per annum Data Less than 1% 1.32 Maximum leakage rate for the whole switchgear per Less than 1% annum 1.33 Minimum operating period without total replacement of SF 6 gas years Minimum thickness of enclosure mm 1.35 Minimum enclosure puncturing time due to internal arc fault at short-time withstand current ms Greater than Minimum factors of safety for switchgear - Busbars or other connections based on elastic 2.5 limit - Complete insulators based on electromechanical 2.5 test - Insulator metal fittings based on elastic limit Steel structures based on elastic limit of 2.5 tension members and on crippling loads of compression members - Foundations for structures against overturning or uprooting under maximum simultaneous working loadings Seismic factor 2 CIRCUIT BREAKER 2.1 Manufacturer & Place of manufacturing 2.2 Type designation 2.3 Type Single pressure puffer, SF Standards IEC , IEC , 61233, 60694, 60427, 60376, Rated voltage kv a Rated Current Busbars, Bus Section and Bus Coupler - at 50 0 C (Contractor to confirm by calculation) A 3150 D3.3

46 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont 2.6b Rated Current Transformer/Transformer Feeder Unit Data - at 50 0 C (Contractor to confirm by calculation) A c Rated Current Incoming Feeder - at 50 0 C (Contractor to confirm by calculation) A Rated frequency Hz Rated lightning impulse withstand voltage - Phase to earth kv p Across the isolating distance kv p Rated power frequency withstand voltage - Phase to earth kv Across the isolating distance kv Rated short-time withstand current (1 s) ka Rated peak withstand current ka p Rated operating sequence O -0.3 sec- CO -3 min - CO 2.13 Auto reclosing O -0.3 sec- CO -3 min - CO 2.14 Rated making current ka p Rated breaking current (asymmetrical) ka To IEC %dc %dc 2.17 Rated breaking current under out-of-phase conditions ka 2.18 First phase to clear factor a Transient Recovery Voltages TRV s To IEC Rated capacitive breaking current To IEC Rated line charging breaking current A Rated cable charging breaking current A Rated Single/Back to Back Capacitor bank A breaking current D3.4

47 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont Unit Data 2.20 Rated small inductive/reactor breaking currents of: To IEC small inductive A - reactor A 2.21 Maximum overvoltage factor on any switching duty pu Maximum overvoltage factor when interrupting rated line/cable/capacitor bank charging currents 2.23 Maximum overvoltage factor when switching small inductive/reactor currents 2.24 Maximum total break time (trip initiation to final arc extinction) pu 2.5 pu 2.5 ms Opening time (trip initiation to contact separation) - Without current ms - With 100% rated breaking current ms 2.26 Maximum time interval between opening of first and last phase of three phase circuit breakers 2.27 Maximum time interval between opening of interrupters of one phase 2.28 Closing time from energisation of close coil to latching of circuit breaker in fully closed position ms ms 2.29 Making time (energisation of close coil to contact touch) - Without current ms - 100% making current ms 2.30 Maximum time interval between closure of first and last phase of three phase circuit breaker 2.31 Maximum time interval between closure of interrupters of one phase 2.32 Minimum time from extinction of main arc to contact make during auto-reclosing duty 2.33 Mechanical life of circuit breaker and mechanism in No. of operations ms ms ,000 D3.5

48 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont 2.34 Electrical contact life in number of operations at: Unit Data - Rated current A/1600A - Fault current - 40 ka 15 to 20 - Cumulative ampere rating 2.35 Number of current interrupting break units in series per phase one 2.36 Type of operating mechanism Spring-charged or hydraulic 2.37 Type of power device (motor changed) - For closing Spring or hydraulic - For opening Spring or hydraulic 2.38 Hand operating facility yes 2.39 Hand charging facility yes 2.40 Manual spring release yes 2.41 Mechanical on/off indicator yes 2.42 Mechanical spring charge / discharge indication yes 2.43 Charging time s 2.44 Number of trip coils Number of close coils Nominal control and operating voltage V 110 DC 2.47 Nominal heater voltage V 220 AC 2.48 Rated power of trip coil W 2.49 Rated power of close coil W 2.50 Rated motor power W 2.51 Total load of heaters for circuit breaker W 2.52 Mass of circuit breaker complete (three pole) kg 2.53 Mass of single phase circuit breaker D3.6

49 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont 2.54 Emergency Trip Facility during failure of DC supply Unit yes Data 3 DISCONNECTS 3.1 Manufacturer & Place of Manufacturing 3.2 Type designation 3.3 Type of operating mechanism Motor 3.4 Standards IEC , IEC 60694, 61128, , Rated voltage kv Rated current at 50 o C (Contractor to confirm by calculation) - Busbars, Bus Section and Bus Coupler A Circuits A Rated frequency Hz Rated lightning impulse withstand voltage - Phase to earth kv p Across the isolating distance kv p Rated power frequency withstand voltage - Phase to earth kv Across the isolating distance kv Rated short time withstand current (1 s) ka Rated peak withstand current ka p Maximum capacitive current that can be interrupted by the isolator 3.13 Total time from initiation of opening operation to isolator in fully open position 3.14 Time from contact separation to extinct of capacitive arc A s s D3.7

50 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont 3.15 Total time from initiation of opening operation to time when isolator gap can withstand phase voltage Unit s Data 3.16 Hand operating facility yes 3.17 Locking arrangement in on/off position yes 3.18 Nominal control and operating voltage V 110 DC 3.19 Automatic isolation of control supplies when lock off 3.20 Accessibility to operating mechanism from ground level or catwalk yes yes 3.21 Nominal heater voltage V 220 AC 3.22 Rated power of operation coil W 3.23 Rated motor power W 3.24 Total load of heaters for isolator W 3.25 Total mass of three phase isolator complete kg 3.26 Mass of single phase isolator kg 3.27 Contact type Tulip 4 EARTHING SWITCH 4.1 Manufacturer & place of manufacturing 4.2 Type designation 4.3 Type of operating mechanism Motor 4.4 Standards IEC , IEC 60694, Rated voltage kv Rated frequency Hz Rated lightning impulse withstand voltage phase to earth 4.8 Rated power frequency withstand voltage phase to earth kv p 650 kv 275 D3.8

51 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont Unit 4.9 Rated short time withstand current (1 s) ka Rated peak withstand current ka Hand operating facility yes 4.12 Locking arrangement in on/off position yes 4.13 Nominal control and operating voltage V 110 DC Data 4.14 Automatic isolation of control supplies when lock off 4.15 Accessibility to operating mechanism from ground level or catwalk yes yes 4.16 Nominal heater voltage V 220 AC 4.17 Rated power of operating coil W 4.18 Rated motor power W 4.19 Total load of heaters for earthing switch W 4.20 Total mass of earthing switch complete kg 5 HIGH SPEED EARTHING SWITCH 5.1 Manufacturer & place of manufacturing 5.2 Type designation 5.3 Type of operating mechanism Motor-spring 5.4 Standards IEC , IEC 60694, 61129, Rated voltage kv Rated frequency Hz Rated lightning impulse withstand voltage phase to earth 5.8 Rated power frequency withstand voltage phase to earth kv p 650 kv 275 D3.9

52 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont Unit 5.9 Rated short time withstand current (1 s) ka Rated peak withstand current ka p Rated short-circuit making current ka p Rated capacitive symmetrical breaking current A 5.13 Rated inductive symmetrical breaking current A Data 5.14 Total time from initiation of opening operation to earth switch in fully open position 5.15 Time from contact separation to extinction of arc when interrupting rated breaking current ms ms 5.16 Making time ms 5.17 Charging time s 5.18 Hand operating facility yes 5.19 Locking arrangement in on/off position yes 5.20 Nominal control and operating voltage V d.c Automatic isolation of control supplies when lock off 5.22 Accessibility to operating mechanism from ground level or catwalk yes yes 5.23 Nominal heater voltage V 220 AC 5.24 Rated power of operation coil W 5.25 Rated motor power W 5.26 Total load of heaters for earthing switch W 5.27 Total mass of earthing switch complete kg 6 CURRENT TRANSFORMER 6.1 Manufacturer & place of manufacturing 6.2 Type Toroidal, GIS enclosed 6.3 Standards IEC 60694, D3.10

53 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont 6.4 Rated voltage Unit Data GIS kv 145 Cores V Rated lightning impulse withstand voltage phase to earth GIS kv p 650 Cores kv p 6.6 Rated power frequency withstand voltage phase to earth GIS kv 275 Cores kv 3 kv (E K < 2 kv) kv 5 kv (E K 2 kv) 6.7 Rated power frequency between secondaries 3 kv 6.8 Inter-turn test M/P type 4.5 kv peak Class PX To IEC Rated frequency Hz Rated continuous thermal current at 50 o C Rated extended primary current 6.11 Rated short-time withstand current (1 s) ka Rated dynamic current ka p Are earthed metal screens fitted between primary and secondary windings 6.14 Is current transformer housed in a separate gas compartment 6.15 Transformer bays current transformer: To suit specific - Number of cores arrangement - Rated extended primary current - Ratio (TR = turns ratio) I core II core III core IV core V core A A A A A D3.11

54 SCHEDULE D TECHNICAL PARTICULARS CONT SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR Cont - Class Unit Data I core II core III core IV core V core - Knee point voltage (E k ) I core II core III core IV core V core V V V V V - Exciting current (I E ) at E k I core II core III core IV core V core ma ma ma ma ma - Rated output (Burden to be % rated burden) I core II core III core IV core V core VA VA VA VA VA 6.16 Line bays current transformer To suit specific - Number of cores arrangement - Rated extended primary current - Ratio (TR = turns ratio) - Knee point voltage (E k ) 6.17 Bus Section & Bus Coupler CT No.1 To suit specific - Number of cores arrangement - Rated extended primary current - Ratio (TR = turns ratio) 6.18 Bus Section & Bus Coupler CT No. 2 (at the other side of circuit breaker) To suit specific - Number of cores arrangement D3.12

55 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont - Rated extended primary current - Ratio (TR = turns ratio) Unit Data 7 VOLTAGE TRANSFORMERS 7.1 Manufacturer & Place of manufacturing 7.2 Type designation for - Line transformer 3 phase - Busbar transformer 3 phase 7.3 Type Inductive, SF 6 gas insulated, enclosed 7.4 Standards IEC 60186,60694, , Rated voltage kv Rated frequency Hz Rated lightning impulse phase to earth kv p Rated power frequency withstand voltage phase to earth 7.9 Maximum permissible partial discharge level Um 7.10 Maximum permissible partial discharge level 1.2Um / 3 kv 275 pc 10 pc Maximum capacitive current discharge rating A TBA 7.12 Method of suppressing ferroresonance phenomena 7.13 Line bay voltage transformer - Number of secondaries - Rated transformation ratio kv - Rated accuracy class I secondary II secondary - Rated output I secondary II secondary VA VA D3.13

56 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont - Mass of single/three phase voltage transformer Unit kg Data 7.14 Busbar voltage transformer - Number of secondaries - Rated transformation ratio kv - Rated accuracy class I secondary - Rated output (Burden to be % rated burden) VA I secondary - Mass of single/three phase voltage transformer kg 8 SURGE ARRESTERS 8.1 Type 8.2 Standard IEC , , Rated/system voltage kv 145/132 - Maximum overvoltage factor on the system due to any switching duty pu Rated system frequency Hz Condition of system neutral Solid 8.6 Nominal Discharge current ka crest 8.7 Energy capability as per IEC kj/ kv 8.8 Rated voltage - MOA kv 8.9 Long duration discharge class as per IEC Class 8.10 Maximum Continuous Operating Voltage (COV) kv 8.11 TOV capability for - 1 sec kv - 10 sec kv D3.14

57 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont 8.12 Maximum residual voltage with current wave Unit Data - Switching Surges - 1kA / 2kA kv - 8/20 μs - 5kA kv - 8/20 μs - 10kA kv 8.14 Discharge current withstand strength - High current (4/10 μs) KA p - Low current 2000A A p 8.15 Pressure relief capability - High current (0.2 s) ka - Low current As per IEC 8.16 Rating of earth connections ka/sec 40/ Surge counter provided Yes 9 CABLE BOX 9.1 Manufacturer & Place of manufacturing 9.2 Type of designation 9.3 Standards IEC Rated voltage kv Rated lightning impulse withstand voltage phase to earth 9.6 Rated power frequency withstand voltage phase to earth kv p 650 kv Cable HV test withstand capability kv 9.8 Rated frequency Hz Rated normal current at 40 o C A 9.10 current at 50 o C (Contractor to confirm by calculation) A 9.11 Rated short time withstand current (1s) ka Rated peak withstand current ka Total mass of three phase cable box complete kg D3.15

58 SCHEDULE D3 132 KV GAS INSULATED SWITCHGEAR - Cont 10 MANUFACTURER QUALITY SYSTEM IN ACCORDANCE TO ISO 9000, 9001, 9002, 9003 AND 9004 Unit Yes Data 10.1 Date of issue Latest 10.2 Validity Valid Certificates Yes 11 TYPE TEST CERTIFICATE TO BE ISSUED BY INDEPENDENT LABORATORY OR INDEPENDENTLY WITNESSED TYPE TEST CERTIFICATE TO BE SUBMITTED Yes D3.16

59 SCHEDULE D4 132 KV OPEN TERMINAL SWITCHGEAR 1 GENERAL Unit Data 1.1 Standards IEC IEC , , 60694, 60233, 60044, 60186, 60383, Rated voltage kv System Voltage kv Rated frequency Hz Rated lightning impulse withstand voltage Phase to earth kv p 650 Across the isolating distance kv p Rated power frequency withstand voltage Phase to earth kv 275 Across the isolating distance kv Rated short-time withstand current (1 s) ka Rated peak withstand current ka Rated Current Cable Feeder at 50 o C (Contractor to confirm by calculation) A 1600 (or to suit) 1.10 Material of HV conductor Aluminium 1.11 Material of contacts Bi-metallic 1.12 Minimum factors of safety for switchgear Busbars or other connections based on elastic limit Complete insulators based on electromechanical test Insulator metal fittings based on elastic limit 2.5 Steel structures based on elastic limit of tension members and on crippling loads of compression members Foundations for structures against overturning or uprooting under maximum simultaneous working loadings D4.1

CEYLON ELECTRICITY BOARD SRI LANKA. Procurement of Plant

CEYLON ELECTRICITY BOARD SRI LANKA. Procurement of Plant CEYLON ELECTRICITY BOARD SRI LANKA GREEN POWER DEVELOPMENT AND ENERGY EFFICIENCY IMPROVEMENT INVESTMENT PROGRAMME (TRANCHE 2) PACKAGE 2: LOT A MANNAR NADUKUDA TRANSMISSION DEVELOPMENT (ADB LOAN NO: 47037-SRI)

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

CEYLON ELECTRICITY BOARD SRI LANKA. Procurement of Plant

CEYLON ELECTRICITY BOARD SRI LANKA. Procurement of Plant CEYLON ELECTRICITY BOARD SRI LANKA GREEN POWER DEVELOPMENT AND ENERGY EFFICIENCY IMPROVEMENT INVESTMENT PROGRAMME (TRANCHE 2) (ADB LOAN NO:3483/3484) PACKAGE 3: LOT B Procurement of Plant Design, Supply

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

Substation Preventive Maintenance

Substation Preventive Maintenance Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS

More information

SECTION VI TECHNICAL SCHEDULES

SECTION VI TECHNICAL SCHEDULES SECTION VI TECHNICAL SCHEDULES Kenya Power and Lighting Company VI 4.3 - i Contract A36B TECHNICAL SCHEDULES 1 PREAMBLE...1 TECHNICAL SCHEDULES SUBSTATIONS...2 SCHEDULE VI-1a TECHNICAL GUARANTEES, OUTDOOR

More information

CONTENTS. 1. Introduction Generating Stations 9 40

CONTENTS. 1. Introduction Generating Stations 9 40 CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific

More information

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it. 1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12 8DB 12 blue GIS Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12 Features Gas-insulated switchgear (GIS) type 8D/B has been an integral part of the medium-voltage portfolio at Siemens for more

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

ELE-CMOS-E-2001 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

ELE-CMOS-E-2001 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS 101135-ELE-CMOS-E-2001 Electrical Engineer Holds a B. Sc. in Electrical Power & Machines Engineering and has over 14 years hands-on experience, including 13 years working in operation, maintenance, construction

More information

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV

More information

Insulation Co-ordination For HVDC Station

Insulation Co-ordination For HVDC Station Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

Medium voltage circuit breaker technical guide

Medium voltage circuit breaker technical guide IEC 56-1987 - ANSI C37-06 1987 COMPARISON CONTENTS page 1 - Rated voltage 3 2 - Rated isolating level 3 3 - Rated voltage during normal running 4 4 - Allowable short time current 4 5 - Allowable current

More information

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric

More information

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable: Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

3. COMBINED TRANSFORMERS Oil-paper insulation

3. COMBINED TRANSFORMERS Oil-paper insulation 3. COMBINED TRANSFORMERS Oil-paper insulation 123 kv Combined transformers. 26 Instrument transformers High voltage INTRODUCTION Combined instrument transformers contain a current transformer and an inductive

More information

I -limiter The world s fastest switching device

I -limiter The world s fastest switching device I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

Capacitive voltage transformers

Capacitive voltage transformers Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

Tab 8 Surge Arresters

Tab 8 Surge Arresters s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.

More information

EE 1402 HIGH VOLTAGE ENGINEERING

EE 1402 HIGH VOLTAGE ENGINEERING EE 1402 HIGH VOLTAGE ENGINEERING Unit 5 TESTS OF INSULATORS Type Test To Check The Design Features Routine Test To Check The Quality Of The Individual Test Piece. High Voltage Tests Include (i) Power frequency

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Current Transducer CTSR 0.6-TP/SP2 I PRN = 600 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Features

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Power Frequency Withstand Voltage On-site testing of 400 kv GIS Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications: SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

La protection sélective des réseaux électriques

La protection sélective des réseaux électriques La protection sélective des réseaux électriques ULG 21. 11. 2012 The T&D grids Generation Transmission Distribution Industry The electricity network ensure an efficient supply of energy High Voltage Transformers

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Single Line Diagram of Substations

Single Line Diagram of Substations Single Line Diagram of Substations Substations Electric power is produced at the power generating stations, which are generally located far away from the load centers. High voltage transmission lines are

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62271-100 Edition 1.1 2003-05 Edition 1:2001 consolidated with amendment 1:2002 High-voltage switchgear and controlgear Part 100: High-voltage alternating-current circuit-breakers

More information

AC Resonant Test Systems Tank Type Up to 150 kv

AC Resonant Test Systems Tank Type Up to 150 kv R AC Resonant Test Systems Tank Type Up to 150 kv PHENIX TECHNOLOGIES Testing Applications AC Resonant Test Systems are used where the load is largely capacitive with very low real power losses such as

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Testing of 400 kv GIS

Testing of 400 kv GIS Testing of 400 kv GIS Robert le Roux, Dermot Dorgan, Brian Perry ESB International - Ireland Paper 028 1 Introduction The 400 kv transmission is designed for critical periods of low loading. Due to critical

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 21 25 Sep $3,750 Dubai, UAE In any of the 5 star

More information

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

VariSTAR Type AZL heavy-duty distribution-class MOV arrester Surge s Catalog Data CA235006EN Supersedes TD235007EN September 2014 COOPER POWER SERIES VariSTAR Type AZL heavy-duty distribution-class MOV arrester General Eaton incorporates the latest in metal oxide

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

MEDIUM & HIGH VOLTAGE

MEDIUM & HIGH VOLTAGE MEDIUM & HIGH VOLTAGE TESTING EQUIPMENT VOLTAGE WITHSTAND SGM Series Resonant Systems The SGM series are used for generating high AC voltages at a fixed frequency (mainly 50 or 60 Hz) by means of an excited

More information

Onsite Mobile AC High Voltage Test System

Onsite Mobile AC High Voltage Test System TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument

More information

AC High-Voltage Circuit Breakers

AC High-Voltage Circuit Breakers AC High-Voltage Circuit Breakers Everything you wanted to know about ac highvoltage circuit breakers but were afraid to ask IEEE Switchgear Committee Portland (Maine, USA), October 2017 Denis Dufournet

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

GENERAL TECHNICAL SPECIFICATION (Turnkey Work)

GENERAL TECHNICAL SPECIFICATION (Turnkey Work) GENERAL TECHNICAL SPECIFICATION (Turnkey Work) March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,

More information

GENERAL TECHNICAL SPECIFICATION

GENERAL TECHNICAL SPECIFICATION GENERAL TECHNICAL SPECIFICATION September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.

More information

General Requirements. Technical Specification LVAC Systems

General Requirements. Technical Specification LVAC Systems Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks LVAC Systems NO: 423-1

More information

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved. Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Energy Division. Bowthorpe LV/MV Surge Arresters

Energy Division. Bowthorpe LV/MV Surge Arresters Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

Unit 2. Single Line Diagram of Substations

Unit 2. Single Line Diagram of Substations Unit 2 Single Line Diagram of Substations Substations Electric power is produced at the power generating stations, which are generally located far away from the load centers. High voltage transmission

More information

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR CIRCUIT BREAKER SF 6 ING. VÁCLAV JEŽEK PROF. ING. ZDENĚK VOSTRACKÝ, DRSC., DR.H.C. Abstract: This article describes the analysis of faults interrupted by generator

More information

KENYA ELECTRICITY GENERATING COMPANY LTD

KENYA ELECTRICITY GENERATING COMPANY LTD KENYA ELECTRICITY GENERATING COMPANY LTD TENDER No. KGN-HYD-014-2016 TENDER FOR REHABILITATION OF PROTECTION EQUIPMENT FOR MASINGA HYDRO POWER STATION 20/06/2016 ADDENDUM NO. 1 In accordance with the tender

More information

Arc Suppression Coils

Arc Suppression Coils Arc Suppression Coils (22kV Arc Suppression Coils ) Introduction Resonance grounding by Petersen coils (Arc Suppression Coils) has been used in Scandinavia and other European countries for some eighty

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER

TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER HM0.154.1901 SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. General 1. General 3 2. Technical specifications 4 3. Type explanation 5 4. Terms and definitions

More information

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD. Our Ref.: 14/2018- Date : Messrs: Dear sir, Tender 14/2018 11& 33 KV Lightning Arrestors. You are kindly requested to quote for the supply and delivery to our stores in Shufat Jerusalem, (DDP) of the following

More information

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD. Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules

More information

Electrical Description

Electrical Description History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced

More information

RELEVANT ELECTRICAL STANDARDS

RELEVANT ELECTRICAL STANDARDS RELEVANT ELECTRICAL STANDARDS Issue 1 September 2005 National Grid 2005 No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means electronic,

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design

More information

Miniature circuit-breakers S 280 UC series. System pro M. Technical data

Miniature circuit-breakers S 280 UC series. System pro M. Technical data Technical data 11 Robbie Rd. / Avon, MA 02322 T:(508)513-1000 F:(508)513-1100 70 Ernest St. / Providence, RI 02905 T:(401)781-7100 www.controllerservice.com System pro M Prior to connection of aluminum

More information

Transformers connected via a cable Overvoltage protection

Transformers connected via a cable Overvoltage protection A P P L I C AT I O N N OT E 2. 1 Transformers connected via a cable Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage

More information

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-308 Session 2004 CIGRÉ HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES G.E. Agafonov, I.V. Babkin, B.E. Berlin Y. F. Kaminsky, S. V. Tretiakov,

More information

Ritz Instrument Transformers GmbH. Welcome

Ritz Instrument Transformers GmbH. Welcome Ritz Instrument Transformers GmbH Welcome About Ritz together with over 200 years of experience in instrument transformer production since 1945 since 1945 since 1945 since 1904 RITZ Group - Organization

More information

Switchgear Type SIMOSEC up to 24 kv, Air-insulated, Extendable

Switchgear Type SIMOSEC up to 24 kv, Air-insulated, Extendable Switchgear Type SIMOSEC up to 4 kv, Air-insulated, Extendable Medium-Voltage Switchgear Catalog HA 41.1 0 Answers for energy. R-HA41-055 eps R-HA41-08 eps Contents Application Typical uses Pages Application,

More information

This is a preview - click here to buy the full publication

This is a preview - click here to buy the full publication CONSOLIDATED VERSION IEC TR 62271-306 Edition 1.1 2018-08 colour inside High-voltage switchgear and controlgear Part 306: Guide to IEC 62271-100, IEC 62271-1 and other IEC standards related to alternating

More information

HIGH VOLTAGE CIRCUIT BREAKERS

HIGH VOLTAGE CIRCUIT BREAKERS HIGH VOLTAGE CIRCUIT BREAKERS Design and Applications Second Edition, Revised and Expanded RUBEN D. GARZON Square D Co. Smyrna, Tennessee MARCEL Ш D E К К E R MARCEL DEKKER, INC. NEW YORK BASEL CONTENTS

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer ITL 4000-S I PN = 4000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. I > 0 P Features Closed

More information

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED LIGHTNING ARRESTOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, SectorII, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;

More information

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc. Surge Arresters Secondary Arresters and Protective Gaps Electrical Apparatus 235-10 GENERAL INFORMATION The necessity of providing surge arrester protection on low-voltage circuits is fundamentally the

More information

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Medium-Voltage Switchgear Catalog HA 40.2 2009 Answers for energy. -HA40-111.eps -HA40-110.eps -HA40-109.eps -HA40-112.eps

More information

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description: OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description: VTOP 2(1) X Dry Insulated voltage transformer (VT) There are two designs of this voltage transformers: - VTOP 1-X single phase, dry insulated

More information

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information