MEDIUM-VOLTAGE MEASURING VOLTAGE TRANSFORMERS USER MANUAL
|
|
- Jocelin Payne
- 6 years ago
- Views:
Transcription
1 MEDIUM-VOLTAGE MEASURING VOLTAGE TRANSFORMERS USER MANUAL F.T.M. S. r. l. Fabbrica trasformatori di misura Via Po, Opera MI - Italy Tel : +39 (0) Fax : +39 (0) info@ftmsrl.it Website: MOD.PRG M of 9
2 CONTENTS 1 INTRODUCTION 2 CHOICE OF DEVICES 2.1 SYSTEM SPECIFICATIONS 2.2 ENVIRONMENTAL CONDITIONS 2.3 SAFETY DISTANCES 3 TRANSPORT 4 STORAGE 5 INSTALLATION 5.1 MECHANICAL ASSEMBLY 5.2 CONDENSATION PHENOMENA 5.3 CONNECTIONS TO THE MAIN CIRCUITS 5.4 GROUND CONNECTIONS 5.5 SEALING THE SECONDARY TERMINALS 6 COMMISSIONING 7 MAINTENANCE 8 STAFF TRAINING 9 TECHNICAL SPECIFICATIONS MOD.PRG M of 9
3 1. INTRODUCTION This manual provides all the information needed to safely operate medium voltage measuring transformers (VTs) suitable for installation and use in medium voltage systems (from 7.2 kv to 36 kv), and IEC compliant. 2. CHOICE OF DEVICES Devices must be chosen so as to meet all the electrical parameters of the system in which they will be installed, paying particular attention to the following: 2.1 SYSTEM SPECIFICATIONS Type of connection to two primary poles to one primary pole Power grid s operating voltage TYPE Operating voltage TYPE Operating voltage 7 Up to 7.2 kv 7 Up to 7.2 kv 12 From 7.2 kv to 12 kv 12 From 7.2 kv to 12 kv 17 From 7.2 kv to 17.5 kv 17 From 7.2 kv to 17.5 kv 24 From 7.2 kv to 24 kv 24 From 7.2 kv to 24 kv 36 From 7.2 kv to 36 kv Rated primary voltage TYPE Maximum rated Maximum rated TYPE primary voltage primary voltage V : 3 V V : 3 V V : 3 V V : 3 V : 3 V MOD.PRG M of 9
4 Rated secondary voltage (V) 100: 3-110: 3-100:3 110:3 ( V ) Rated voltage factor and time 1.2 continuous 1.9 / 30 sec or 8 h Frequency Hz Type of use measure or protection All transformer series comply with the product s standards. 2.2 ENVIRONMENTAL CONDITIONS Transformers may be subjected to the following environmental conditions, which need to be carefully taken into account: Temperature All transformer series: from -5 C to +40 C Insulation class E Altitude All transformer series: up to 1000 m a.s.l. Humidity All transformer series: o The mean relative humidity, measured over 24h, must not exceed 95%. o The mean steam pressure, measured over 24h, must not exceed 2.2 kpa. o The mean relative humidity per month must not exceed 90%. o The mean steam pressure per month must not exceed 1.8 kpa. Installation All transformer series: indoor installation Pollution levels All transformer series: installation is possible even in tropical climates MOD.PRG M of 9
5 Corrosive agents To be reported if present Dust and deposits To be reported if present 2.3 SAFETY DISTANCES Safety distances to be complied with in VT installation are as provided by the standards on medium tension insulated power systems. 3. TRASPORT Transformers will be suitably packaged for transport according to the type of product and transport, or to the modality agreed on with the customer. On reception of the device, users are kindly asked to inspect it carefully to ensure the product is undamaged. 4. STORAGE Devices must be stored in clean and dry areas, between -20 C and +70 C (except as otherwise specified). Packaged units may be stacked one on top of another if allowed by and in conformity with the packaging s technical specifications. 5. INSTALLATION All installation operations must be carried out in compliance with all existing accident prevention measures and the following instructions: 5.1 MECHANICAL ASSEMBLY Before tightening, please ensure that the surfaces connecting the conductors and the transformer s primary and secondary terminals are clean and in good conditions. Also ensure that the connections do not cause abnormal mechanical stress to the devices terminals. The maximum and minimum tightening torques of the screw threads to be used for connection to the primary and secondary terminals are as follows: Terminals Screw thread Maximum torque Minimum torque Nm Nm M M6 5 3 Finally, check that no electrical insulation distance was altered during the connecting operation. MOD.PRG M of 9
6 5.2 CONDENSATION PHENOMENA In order for the transformer to withstand the effects of high humidity and condensation, it is advisable to ventilate and heat the installation switchboard, or to apply dehumidifying devices to it. 5.3 CONNECTIONS TO THE MAIN CIRCUITS The primary and secondary connections must be checked to ensure they are compatible with the wiring diagram and the symbols present on the transformers. The graphics printed on the transformers, showing how to connect them correctly, is as follows: Single primary ratio VT with a secondary winding and phase-to-phase connection Single primary ratio VT with a secondary winding and phase-to-ground connection Single primary ratio VT with two secondary windings B/b pole phase-to-phase N/n pole phase-to-ground Single primary ratio VT with two secondary windings, one for measuring, one for residual voltage and phase-to-ground connection Ex.100: 3 Ex. 100: 3 MOD.PRG M of 9
7 Triple primary ratio VT with secondary commutation with a secondary winding B/b pole phase-to-phase N/n pole phase-to-ground Double primary ratio VT with secondary commutation with two secondary windings B/b pole phase-to-phase N/n pole phase-to-ground The correct connections to obtain the different primary burdens are as follows: example: /100 V-V-V/V lowest primary ratio 3000/100 V/V connect to the secondary terminals: a1-b lowest primary ratio 6000/100 V/V connect to the secondary terminals: a2-b highest primary ratio 9000/100 V/V connect to the secondary terminals: a3-b The correct connections to obtain the different primary and secondary burdens are as follows: example: / V-V-V/V-V lowest primary ratio 3000/ V/V first and second windings connect to the secondary terminals: 1a1-1b/ 2a1-2b highest primary ratio 6000/ V/V first and second windings connect to the secondary terminals: 1a2-1b/ 2a2-2b Please pay maximum attention to the conditions of the VTs secondary circuits, which must be connected to the burden or left open at all times. 5.4 GROUND CONNECTIONS The support plates, one terminal per secondary winding and the N primary terminal of phase-ground TVs must be connected to the ground. MOD.PRG M of 9
8 5.5 SEALING THE SECONDARY TERMINALS All transformers are provided with a thermoplastic cap and fixing screws to protect and seal the secondary clamps. 6. COMMISSIONING To guarantee staff and device safety, please make sure, by checking the specifications on the label, that the system s electrical parameters do not exceed the transformer s nominal parameters. The data reported on the identification label are as follows: 1. Series / Type 2 Code This is an 8-figure code, in which the first two figures represent the manufacturing year. 3 Insulation reference voltage / Power frequency withstand voltage / Impulse withstand voltage Expressed in kv. 7.2/20/60-12/28/ /38/95 24/50/125 36/70/170 (IEC standard-compliant values) 4 Rated heating capacity Expressed in VA 5 Rated voltage factor and time 6 Frequency Expressed in Hz 7 Product s reference standards. 8 Rated transformation ratio. Rated primary voltage, V / Rated secondary voltage, V 9 Burden applied to the secondary terminals to which the accuracy class refers. Expressed in VA 10 Accuracy class 11 terminals symbols MOD.PRG M of 9
9 7. MAINTENANCE Before carrying out any operation, make sure that the VTs are not connected to the power grid or powered in any way. Check the tightening of the primary and secondary connections. Ensure that the insulating resin surface shows no signs of deterioration such as carbonisation or cracks. Periodically remove any dust or other deposits that may accumulate on the transformers surfaces. Avoid using solvents. 8. STAFF TRAINING All installation, commissioning and maintenance operations must be carried out by trained staff. Staff need to be trained in order for them to operate competently within the field. 9. TECHNICAL SPECIFICATIONS For further information on the field of application and technical definitions, please refer to the product s standard: IEC The products technical datasheets are available online at: In accordance with the existing law, F.T.M. S.r.l. expressly prohibits any reproduction, retransmission, republication, or other use of all or part of this document without prior authorisation. MOD.PRG M of 9
RING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS USER MANUAL
RING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS F.T.M. S. r. l. Fabbrica trasformatori di misura Via Po, 3 20090 Opera MI - Italy Tel : +39 (0)2 576814 Fax : +39 (0)2 57605296 E-mail: info@ftmsrl.it
More informationMEDIUM VOLTAGE PRODUCT. TJP 6.1, TJP 6.2 Indoor voltage transformers
MEDIUM VOLTAGE PRODUCT TJP 6.1, TJP 6.2 Indoor voltage transformers 2 TJP 6.1, TJP 6.2 INDOOR VOLTAGE TRANSFORMERS Parameters Highest voltage for equipment Power frequency test voltage, 1 min. Lightning
More informationW DATA SHEET Current Transformer 40 x 10, A
W DATA SHEET Current Transformer 40 x 10, 250 600A W SCHRACK-INFO Current transformers for low-voltage network accuracy Single-phase current transformer Passing cable/ bus bar primary Primary current 250
More information36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)
CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994
More informationMEDIUM VOLTAGE PRODUCT. TJP 5.x Indoor voltage transformers
MEDIUM VOLTAGE PRODUCT TJP 5.x Indoor voltage transformers 2 TJP 5.X INDOOR VOLTAGE TRANSFORMERS 01 Voltage transformer TJP 5.1 and TJP 5.2 with suitable fuses Parameters Highest voltage for equipment
More informationVoltage Transformers type UMZ User s Manual, Operation and Maintenance
Voltage Transformers type UMZ User s Manual, Operation and Maintenance ÿþþ Safety at first Safety instructions: Installation, connecting, operation and maintenance should be carried out by the authorised
More informationMEDIUM VOLTAGE PRODUCT. TJP 7.x Indoor voltage transformers
MEDIUM VOLTGE PRODUCT TJP 7.x Indoor voltage transformers 2 TJP 7.X INDOOR VOLTGE TRNSFORMERS Parameters Highest voltage for equipment Power frequency test voltage, 1 min. Lightning impulse test voltage
More informationMEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance
MEDIUM VOLTAGE PRODUCT KOKM Cable current instrument transformers Instruction for Installation, use and maintenance 2 KOKM CABLE CURRENT INSTRUMENT TRANSFORMERS INSTRUCTION FOR INSTALLATION, USE AND MAINTENANCE
More informationAT Current Instrument Transformer Instructions for installation, use and maintenance
Products for High Voltage Application AT Current Instrument Transformer Instructions for installation, use and maintenance 1. Service conditions 2 2. Technical details 2 3. Instruction for installation
More informationMEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly
MEDIUM VOLTAGE PRODUCT PARAMETERS GUIDE How to specify the indoor instrument transformers correctly The range of electric values in the power supply systems is very extensive. This is why it is necessary
More informationOPERATION AND MAINTENANCE MANUAL fervi.com Riveter for threaded inserts Art ORIGINAL INSTRUCTIONS
OPERATION AND MAINTENANCE MANUAL Riveter for threaded inserts Art. 0469 ORIGINAL INSTRUCTIONS FOREWORD Read this manual before operation ORIGINAL INSTRUCTIONS Before starting any operation it is compulsory
More informationMEDIUM VOLTAGE PRODUCT. TPE 6x.xx Indoor supporting current transformers
MEDIUM VOLTAGE PRODUCT TPE 6x.xx Indoor supporting current transformers 2 TPE 6X.XX INDOOR SUPPORTING CURRENT TRANSFORMERS Parameters Values Type TPE 60.xx TPE 63.xx Highest voltage for equipment 25 kv
More informationCOMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS
006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR
More informationTypes CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay
Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay
More informationOUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:
OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description: VTOP 2(1) X Dry Insulated voltage transformer (VT) There are two designs of this voltage transformers: - VTOP 1-X single phase, dry insulated
More informationCast Resin Transformers
Cast Resin Transformers Installation, use and maintenance manual 07/13-01 PC 2 Cast Resin Transformers Table of contents 1 Safety guidelines 4 2 Reference standards 6 3 Rating plate 6 3.1 Conditions for
More informationMT MOTORI ELETTRICI. Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D
MT MOTORI ELETTRICI Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D TABLE OF CONTENTS 1. Introduction 2. Scope of application 3. Installation
More information3. Contact Form A: SPST-NO
0 A Compact and high power latching relay High power switching: 0 A, 6 VAC Compact size: mm mm mm Low temperature-rise High overcurrent capability, conforming to IEC6055- UC RoHS Compliant Model Number
More informationDevice Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.
/9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala
More informationInstallation & Operating Manual. iwap202
Installation & Operating Manual iwap202 This page is intentionally left blank. Document Number 409345 (based on 407655) (See Last Page for Revision Details) For warranty information, refer to Terms and
More informationAccessories. Accessories
Accessories Accessories Voltage transformer Voltage transformer Powerful and precise Input, 3-pole Output is 3-pole + N Use in IT networks without neutral line For reducing the measurement voltage for
More informationUSER S MANUAL POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER ZSP 41 POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER SIGNAL MULTIPLIER ZSP 41/2
(ENG) DECEMBER 2017 USER S MANUAL POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER ZSP 41 POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER SIGNAL MULTIPLIER ZSP 41/2 ISOLATOR - SIGNAL CONVERTER TYPE SP 11 CURRENT
More informationRAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL
RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External
More informationCharlie. Pendant control station. Industrial lifting. Construction lifting. Stage technology. Industrial automation
Charlie Pendant control station Charlie pendant station is a control device for all industrial machinery. It operates as an auxiliary controller of electrical motors through a power interface, such as
More informationREV-201М OPERATING MANUAL MULTIFUNCTIONAL TWO-CHANNEL TIME DELAY RELAY. «NOVATEK-ELECTRO» Ltd Intelligent industrial electronics
Ltd Intelligent industrial electronics MULTIFUNCTIONAL TWO-CHANNEL TIME DELAY RELAY OPERATING MANUAL Review the Operating manual before using the unit. www.novatek-electro.com Store the unit in the operating
More informationGas-Insulated Medium-Voltage Switchgear siemens.com/8dab12
8DB 12 blue GIS Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12 Features Gas-insulated switchgear (GIS) type 8D/B has been an integral part of the medium-voltage portfolio at Siemens for more
More informationMeasuring current transformers of the W, W series
Measuring current transformers of the W, W -8000 series W(-8000)_D00078_01_D_XXEN/09.2015 Measuring current transformers of the W, W -8000 series Product description The highly sensitive W and W -8000
More informationCUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv
CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv June 2016 Issue 1 1. INTRODUCTION Introduction of contestability and the ability of all major customers to become contestable
More informationTransformers, Power Supply Units and Socket Outlets
Transformers, Power Supply Units and Socket Outlets /2 Introduction /3 4AC3 bell transformers /4 4AC3 safety transformers /5 4AC2 power supply units /6 5TE6 REG socket outlets For further technical product
More informationType VDG 13 Undervoltage Relay
Type VDG 13 Undervoltage Relay Type VDG 13 Undervoltage Relay VDG 13 relay withdrawn from case Features l Identical time/voltage characteristics on all taps. l Frequency compensated. l Simple construction,
More informationCDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION
PROTECTION CDV 22, 62 Voltage Controlled Overcurrent Relay CDV22 relay is used for overload and fault protection for ac generators when the sustained short circuit current is less than the full load current.
More informationDIGITAL PANEL METER N24 AND N25 METER SERIES
DIGITAL PANEL METER N24 AND N25 METER SERIES USER S MANUAL Contents 1. APPLICATION...5 2. METER SET...5 3. OPERATIONAL SAFETY...6 4. INSTALLATION...7 4.1 Fixing Way...7 4.2 External Connection Diagrams...8
More informationPRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance
PRODUCT FOR HIGH VOLTAGE APPLICATION Current transformers for Gasinsulated switchgear type ELK Instructions for installation, use and maintenance 2 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE
More informationRI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters
RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current
More informationBrown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS
SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600
More informationHAWK5000 Operators Manual
HAWK5000 Operators Manual Keison Products P.O. Box 2124, Chelmsford CM1 3UP, England Tel: +44 (0) 1245 600560 Fax: +44 (0) 1245 600030 Email: sales@keison.co.uk www.keison.co.uk KANE INTERNATIONAL LIMITED
More informationPower transformers for Network, Rectifiers, Furnace
E N G L I S H OTN, OTR, OTF Transformers Power transformers for Network, Rectifiers, Furnace TTR TTO OTN, OTR, OTF reactors TTH OTN, OTR, OTF Transformers Technology Design Our designers experience combined
More informationOvertravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0
Touch Switch Unique 18 mm Capacitive Touch Switch with Choice of Three Actuators is Activated with Only a Very Slight Physical Contact Lightweight objects, such as thin wire or foil can be accurately detected.
More information05/09/2012
17.5 mm EMER8 Part number 88829198 Multifunction or mono-function Multi-range (7 ranges) Multi-voltage or single voltage Screw terminals LED status indicator (1 voltage present LED, 1 timer ON LED) Option
More informationHandling Precaution for Terminal and Connector
1 Handling Precaution for Terminal and Connector Handling Precaution for Terminal and Connector This manual is to describe basic precautions for use of terminal and connector in the following. Make use
More informationMANUAL PCE-UT232
www.pce-group-europe.com PCE- Deutschland Gmb H & Co. KG Tel: +49 029 03 976 99-0 Fax: +49 029 03 976 99-29 info@warensortiment.de www.warensortiment.de PCE Group Ibérica S.L. Tel: +34 967 543 548 Fax:
More informationElderfield & Hall, Inc., Kama Bandsaw AD 105S. Instruction Manual: Introduction to the Manual. General Precautions. Equipment. Machine.
Elderfield & Hall, Inc., www.kooltools.com 10901 McBride Lane, Knoxville TN, 37932. Phone: 865.671.7682. Fax: 865.671.7686. Email: bob@kooltools.com Kama Bandsaw AD 105S 110 Volt, Single Phase 2 ¼ HP Portable
More informationMODEL: M2SES SEN TRONIC AG [3] OUTPUT
Super-mini Signal Conditioners Mini-M Series HIGH/LOW SELECTOR Functions & Features Monitors two DC input signals and transmits an output signal proportional to the higher or lower input CE marking UL
More informationFor ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.
Current Transducer IT 700-S ULTRASTAB I PM = 700 A For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Features Closed loop (compensated)
More informationUT232. Operating Manual. Digital Power Clamp Meter
UT232 Operating Manual Digital Power Clamp Meter Model UT232 OPERATING MANUAL TABLE OF CONTENTS TITLE PAGE Overview Unpacking Inspection Safety Information Rules For Safe Operation International Electrical
More informationModular equipment. Presentation, standards. Standard contactors TeSys GC
Presentation, standards Standard contactors TeSys GC Presentation TeSys GC contactors are designed for use in modular panels and enclosures. These contactors feature: b Easy installation v quick clip-on
More informationINSTRUCTIONS FOR THE SAFE APPLICATION OF CABLES
THE SAFE APPLICATIO OF CABLES The cables manufactured by S are only appropriate for the transmission of electric energy for supply and signalling purposes. First of all the valid construction and installation
More informationCAST RESIN DRY TRANSFORMER
CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,
More informationPRELIMINARY DATA SHEET. RI-F400 Series. easywire Single and Three Phase Multifunction Energy Meter
Telephone : 44 (0) 1245 428500 PRELIMIARY DATA SHEET RIF400 Series easywire Single and Three Phase Multifunction Energy Meter DI 96 panel mounted 330mV Input from easywire CTs (or /1A and /5A current transformer
More informationOil-immersed Transformers
Oil-immersed Transformers Manual for Installation, Operation and Maintenance UNITRAFO Electric AB, Askims Industriväg 1A, 436 34 Askim, tel +46-31-68 56 20, fax +46-31-68 58 11 ENGLISH 1 / 13 ENGLISH Technical
More informationشركة الوقت للكهرباء والمقاوالت ذ.م.م.
CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution
More informationPhase-sequence Phase-loss Relay
Phase-sequence Phase-loss Relay K8AB-PH Three-phase Phase-sequence Phase-loss Relay Using Voltage Detection Method Prevents reverse motor rotation due to incorrect wiring. Distinguishes between positive
More informationHIGH VOLTAGE PHASE COMPARATORS
USER'S MANUAL for HIGH VOLTAGE PHASE COMPARATORS PC Series Double Poles Model System Voltage Full Scale MT6k 6.6kV 8kV MT11k 11kV 12kV MT22k 22kV 24kV MT33k 33kV 36kV MT44k 44kV 48kV Exceeds VDE681-5 /
More informationN24, N25 DIGITAL PANEL METER
DIGITAL PANEL METER www.sifamtinsley.co.uk USER S MANUAL Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters DIGITAL PANEL METER Current Transformers
More informationThis section is specifically about safety matters
6 4 ) 1 6 4 1 -, 1 8-4 6-4 1 6 4 7 + 6 1 ) 7 ) 4 ) 6 1-6 6-4. 4. 0 J E? A Thank you for choosing this Mitsubishi transistorized Inverter option. This instruction manual gives handling information and precautions
More informationPRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID
RI-D140 Three Phase Multifunction DIN Rail Energy Meter (MID Certified) Four module DIN rail mounted Energy pulse LED True RMS measurement Cost effective and accurate Modbus communication -/1A or -/5A
More informationThis section is specifically about safety matters
6 4 ) 5 1 5 6 4 1 -, 1 8-4 6-4 1 5 6 4 7 + 6 1 ) 7 ) 5 2 - -,, - 6 - + 6 4. 4. 2 J E? A Thank you for choosing this Mitsubishi transistorized Inverter option. This instruction manual gives handling information
More informationRE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC
Characteristics off-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay range Nominal
More informationConfigured air damper actuators 6FU11xx-xDxxx-xxxx
s OpenAir Configured air damper actuators 6FU11xx-xDxxx-xxxx Electronic motor driven actuators for open-close, three-position and modulating control Nominal torque 5 Nm Operating voltage AC 24 V ~ / DC
More informationRE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC
Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay range Nominal
More informationLXM32AD18M2 motion servo drive - Lexium 32 - single phase supply voltage 115/230V - 0.5/1kW
Product data sheet Characteristics LXM32AD18M2 motion servo drive - Lexium 32 - single phase supply voltage 115/230V - 0.5/1kW Main Range of product Lexium 32 Product or component type Device short name
More informationDATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO
PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %
More informationprinted pages will not be updated
page 1 of 5 for KLINGER SCHÖNEBERG Ball Valves, Type Table of Contents 1 Validity... 2 2 General Remarks... 2 3 Construction and Components of the... 3 4 Assembly of the... 4 4.1 Preparing for Assembly...
More informationTest Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy
A6/028659 Test Report CESI Approved Page 1 Client MF Trasformatori s.r.l. - Calcinato (BS) Italy Tested equipment Non-enclosed three-phase dry-type power transformer with three windings, with encapsulated
More informationSafety switches with slotted hole lever
Safety switches with slotted hole lever Selection diagram C1 C C C4 C5 Straight slotted hole lever Slotted hole lever at the left Slotted hole lever at the right (without bend) Slotted hole lever at the
More informationSAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS
SAUDI STANDARD NO. SASO IEC 60669-2-2: 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS Part 2-2: Particular requirements Electromagnetic remote-control switches (RCS) SAUDI ARABIAN
More information99 Washington Street Melrose, MA Fax TestEquipmentDepot.com # # AAC Clamp Meter. Instruction Manual
99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com #61-732 #61-736 400 AAC Clamp Meter Instruction Manual AC HOLD APO DC KMΩ mva WARNING Read First: Safety Information Understand
More informationIsoTrans 41. The load capability of the 20 ma source is limited and therefore requires efficient use of the load voltage.
ProLine Interface Technology Loop-Powered Isolators for Standard Signals For isolation of 0(4)... 20 ma standard current signals on up to 3 channels. The Task If no power supply is available, the galvanic
More informationLXM32MD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw
Product data sheet Characteristics LXM32MD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V - 1.8 kw Main Range of product Lexium 32 Product or component type Device short name
More informationLC35/2-DA-iC. 35 W Dimmable two channel intelligent Colour LED driver. 35 W V 0 / Hz. Functional Description. Mains Characteristics
35 W Dimmable two channel intelligent Colour LED driver 2-channel tunable white for human centric lighting 35 W 220 240 V 0 / 50 60 Hz Wide dynamic range of colour temperatures on all dimming levels SELV
More informationP2 H2 NAMEPLATE 6 HOLES M8-10 M SCREW S1 1S2 1S3 X1 X2 X3 PARALLEL HIGH RATIO
TYPE : K52 INSULATION LEVEL : up to 24/50/125kV PRIMARY CURRENT : up to 0A up to 0A single 1 to 2 secondary cores 226 M10 205 30 2 225 30 210 20 80 65,5 6 HOLES M8-10 4 Additional MTG base 2 270 4 HOLES
More informationRI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters
RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA
More informationEnergy Division. Bowthorpe LV/MV Surge Arresters
Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early
More informationRobot e.do. Safety requirements and technical specifications. Rel axes and 6 axes versions
Robot e.do Rel. 00-4 axes and 6 axes versions Safety requirements and technical specifications Requirements and instructions for safe installation, use, and decommissioning of the Robot. Robot Technical
More informationJewell DPM Power / Power Factor Size 96/96 BEST IN CLASS
Application: The Jewell DPM Power 96x96 series measures system active Power (Import/Export), Reactive Power (Import/Export), Apparent Power & Power Factor of Three Phase and Single Phase Network. It has
More informationRotary actuators for ball valves
s ACVATIX Rotary actuators for ball valves GLB..9E Electromotoric rotary actuators for open-close, three-position or modulating control. Used in heating, ventilation and air conditioning plants. For 2-port
More informationCONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS
CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer ITL 4000-S I PN = 4000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. I > 0 P Features Closed
More informationPrecipitation Monitor ,
THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 021197/11/09 Precipitation Monitor 5.4103.10.000, 5.4103.10.700 ADOLF THIES GmbH & Co. KG Hauptstraße
More informationISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances
ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances
More informationAir damper actuators. OpenAir GDB..1E. Electronic motor driven actuators for open-close, three-position and modulating control
s OpenAir Air damper actuators GDB..1E Electronic motor driven actuators for open-close, three-position and modulating control Nominal torque 5 Nm Operating voltage AC 24 V ~ / DC 24 48 V or AC 100 240
More informationRS Pro ENGLISH. Datasheet
Datasheet ENGLISH Article No: 136-5390 Digital AC Ammeter, 48x96, 3Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5391 Digital AC Ammeter, 96x96, 3Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5393
More informationFor ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.
Current Transducer IT 700-SB ULTRASTAB I PM = 700 A For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Features ± 10 V voltage output
More informationCONTENTS XV300K GB r doc XV300K 2/13
XV300K CONTENTS 1 PRELIMINARY CHECK GUARANTEE RECYCLING... 3 2 XV300K SPECIFICATIONS OF USE... 3 3 CODES - MODELS... 4 4 TECHNICAL SPECIFICATIONS... 4 5 STANDARD REFERENCES... 5 6 MECHANICAL INSTALLATION...
More informationOPERATING INSTRUCTIONS 5-AXIS CLAMPING SYSTEM + ACCESSORIES
OPERATING INSTRUCTIONS 5-AXIS CLAMPING SYSTEM + ACCESSORIES 1 Contents 1. Introduction 2. Safety instructions and precautions 3 Operating the clamp 3.1 Clamp set up 3.2 Sequence for clamp set up 3.3 Adjusting
More informationLXM32AD72N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw
Product data sheet Characteristics LXM32AD72N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V - 0.4 kw Main Range of product Lexium 32 Product or component type Device short name
More information374 FC/375 FC/376 FC Clamp Meter
374 FC/375 FC/376 FC Clamp Meter PN 4705494 September 2015 2015 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their respective
More informationSEPARATOR P20G TYPE USER S MANUAL
SEPARATOR P20G TYPE USER S MANUAL 1 2 Contents 1. APPLICATION... 5 2. SEPARATOR SET... 5 3. OPERATIONAL SAFETY... 6 4. FITTING... 7 4.1. Fixing Way... 7 4.2. External Connection Diagrams... 8 5. SERVICE...
More informationLXM32MU60N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw
Product data sheet Characteristics LXM32MU60N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V - 0.4 kw Main Range of product Lexium 32 Product or component type Device short name
More informationINTERNATIONAL STANDARD
INTENATIONAL STANDAD IEC 60044-2 Edition 1.2 2003-02 Edition 1:1997 consolidated with amendments 1:2000 and 2:2002 Instrument transformers Part 2: Inductive voltage transformers This English-language version
More informationTS RES - OUTSTANDING ISSUES
TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next
More informationRS Pro ENGLISH. Datasheet
Datasheet Article No: 136-5385 Digital AC Ammeter, 48x96, 1Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5387 Digital AC Ammeter, 96x96, 1Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5388 Digital
More information323/324/325 Clamp Meter
323/324/325 Clamp Meter Users Manual May 2012 Rev.1, 06/15 2012-2015 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their
More informationINTELLIMETER REGISTER
INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products
More informationPowersafe Termination Guide
Powersafe Termination Guide Contents Index 1. Introduction 2. Overview 3. Termination Methods 3.1 Set screw termination 3.2. Recommended Assembly Procedure for Panel Mounted Connectors 3.3. Crimp Termination
More informationRE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC
Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Complementary Contacts material Control type [Us] rated supply voltage Voltage range Main Range of product Product or component
More informationOperating Instructions for Pressure Sensor with Ceramic Sensor Element. Model: SEN-9601
Operating Instructions for Pressure Sensor with Ceramic Sensor Element Model: SEN-9601 We don t accept warranty and liability claims neither upon this publication nor in case of improper treatment of the
More informationDRIVIA cabinets LIMOGES Cedex France 1. DESCRIPTION, USE 3. DIMENSIONS 2. RANGE, CAT. NO. EQUIVALENCE TABLE
87045 LIMOGES Cedex France Tel: (+33) 05 55 06 87 87 Fax: (+33) 05 55 06 88 88 DRIVIA cabinets CONTENTS NTS PAGES 1. Description, use....1 2. Range, equivalence table...1 3. Dimensions...1 4. General characteristics...2
More informationSECTION CABLE TRAYS
SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More information10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units
BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells
More information