Power Quality Overview

Size: px
Start display at page:

Download "Power Quality Overview"

Transcription

1 Power Quality Overview October 2015 Dan Carnovale, PSEC Manager Eaton Corporation. All rights reserved.

2 Power Quality Events Outage 1 Surge 2 Swell 3 Sag 4 Harmonics 5

3 What is Power Quality? The concept of powering and grounding sensitive electronic equipment in a manner that is suitable to the operation of that equipment. 1 What works for YOU and YOUR system??? 1 IEEE

4 How Much Downtime is Acceptable? Power Availability Equivalent Power Disruptions (yr) % ISPs, e-business, Communications, Electronics mfg. N+ Redundancy < 3 seconds % Pharma Processing Server Operating Systems Generators and Some UPS 5.3 minutes 99.9% % Hospitals, Airports, Universities Generator Only Residential Homes Typical Grid Power 0.88 hours 8.8 hours

5 Specification driven or problem resolution driven Specification Driven Problem Resolution Driven SPDs HMT UPS HCU EVR SRT PFC

6 2013 Eaton. All Rights Reserved.

7 Sources Normal (550 kva, 5% Impedance) Alternate (18% Impedance; Simulates a Generator) EPRI Sag Generator (200A) Surge Generator (7 kv) Natural Gas Generator (150 kw) Solar Power (44 kw) * High Current Test Set (30 ka)* Loads Residential, Commercial, Industrial, Data Center 320 Computer Power Supplies (160 kva, Harmonic Load) Resistive Load Bank (250 kw) Motor-Generator Sets Variable Frequency Drives 300 hp Induction Motor Electric Vehicle Supply Equipment 7

8 Purpose Teach Power system issues, especially power quality problems, are difficult to understand Demonstrate This is a full scale demonstration facility it s not a mock up! Using PQ meters and system software, you can see the results Seeing is believing! Demystify There is a considerable amount of mis-information and confusion in the marketplace regarding PQ and energy savings Help End users in selecting the most appropriate (economic and technical) solution R&D/Testing Evaluate and test equipment by Eaton and others 8

9 Technical vs. Economic Solutions Standard Transformer 75 kva Loaded with 100% Harmonics Harmonic Mitigating Transformer Max Temp 176 ºF Max Temp 105 ºF 9

10 Solutions for EFFICIENCY

11 A Culture of SAFETY Understanding Arc Flash Hazards Remote Power Racking II ( RPR2 ) Remote racking with FlashGard MCC

12 Visitors Dr. Ralph Wyndrum IEEE President, USA you make Power Quality seem fun. Mike Holt ( EPRI IEEE PES/IAS Chapters 55% Types of Visitors Eaton Employees Industrial/Commercial/ Residential End Users 20% 25% End Users Students, Consultants, Distributors, Partners Eaton. All Rights Reserved. 12

13 Students and Universities University of Pittsburgh IBEW Carnegie Mellon University Notre Dame Penn State University Ohio State University Point Park University Youngstown State University and others Senior Design Projects Harmonic Demo Surge Demo Load Bank Automation Data Center Build-out See and Learn Physical Experience In-depth Demo Training Power Quality Theory Electrical Distribution and more I learned more here in 2 hours than I did during an entire 16 week class! 13 EE Student (Junior, Undisclosed University)

14 The Power Systems Experience Center Full-scale power system Compare economic vs. technical solutions Demonstrate and test PQ, arc flash and energy solutions for: Residential Commercial Industrial Utility Data Center Green Technologies

15 Power Quality Concepts Harmonic Solutions Effective Grounding Voltage Variation Solutions Surge Solutions 15

16 Common Power Problems Interruption Sag Swell Voltage Variation Solutions Undervoltage Overvoltage Surge Solutions Harmonic Solutions Line Noise Switching Transients Harmonic Distortion 16

17 Surge Protection Harmonic Solutions Effective Grounding Voltage Variation Solutions Surge Solutions The two sources of surges/transient overvoltages that account for the majority of all events are switching and lightning 17

18 Symptoms of Voltage Transients Equipment damage Insulation breakdown on electrical conductors Premature aging of electrical and electronic equipment Process interruption Data loss and data transfer rate reduction 18

19 Equipment Damage Catastrophic damage to equipment can occur as a result of a high energy transient voltage event 19

20 Insulation Breakdown on Conductors Insulation rating on conductors is typically twice line voltage plus 1000V Transient voltages can be well in excess of 20kV insulation breakdown and motor winding failure can occur 20

21 Premature Aging and Failure Damage to trace on electronic printed circuit board Electronic Rust 21

22 Where Do Voltage Transients Come From? 22 20% External Lightning Capacitor switching Short circuits 80% Internal Load switching Short circuits Capacitor switching Imaging equipment VS Drives Arc welders Light dimmers

23 Surge - With Protection L 20,000 Volts 2000 A 20 Amps 10 Ω Load Some residual letthrough voltage. Manageable by load Ohms Law I=E/R I=200V/10Ω I=20 Amps G

24 Installation Lead Length Can Increase Let- Through Voltage by 15-25v Per Inch Additional Let-Through Voltage Using IEEE C1 (6000V, 3000A) Waveform (UL1449 Test Wave) Installation Criteria Order of Importance: 1) Lead Length - 75% reduction 2) Twisting Wires - 23% reduction 3) Larger Wire - minimal reduction

25 Surge Protection Problem Description: Power electronic devices have taken over our world at home, work and school Eaton Solution: Surge Protection ELECTRONICS Televisions, stereo systems, personal computers, video games, entertainment centers, DVD players, printer/fax/copier, satellite receivers, internet modems, telephone, answering machines, clock radios, MP3 players, various battery chargers The average college student has 18 electronic devices APPLIANCES Refrigerators, stoves, microwave ovens, countertop appliances, dishwashers, washer/dryer, electrical tools, treadmill, other exercise equipment INFRASTRUCTURE Air conditioner, heat pump, electric hot water tank, lighting control, garage door openers, lighting, security system, pool pump, hot tub controls $5-20,000 Typical $4-$15,000 Typical $7-25,000 Typical Costs do not include the substantial cost that may be required to hire electrician to repair/replace the infrastructure wiring 25

26 Grounding Example Phone Lines in PVC Conduit Phone Room 480 V 1200 A 208 V 800 A 208 V Metering 300 kva 208/120 V 500 kva 480 V 300 kva 208/120 V 26

27 Grounding Example Don t Use Isolated Ground Rods! NEC Violation IEEE Emerald Book Violation Isolated Ground Rod! Computer or Phone Equipmen t 208 V 800 A 300 kva 208/120 V 27

28 Solutions for Transient Voltages SPD Series Commercial/Industrial surge protection Integrated or side-mount CVX OEM and value line AEGIS Critical 120V and 230V loads Residential Complete Home Surge Protectors Surge Strips 28

29 Multi-Cycle Voltage Variations Sags are responsible for a majority of upsets and nuisance trips of sensitive electrical equipment Harmonic Solutions Effective Grounding Voltage Variation Solutions Surge Solutions 29

30 Symptoms of Voltage Sags Computer Rebooting or Locking-Up Drives Dropping Out Contactors Chatter or Open PLCs Locking-Up and Process Stoppage Corrupted data UV/HID Lamps Shutting Off Incandescent Lamps Flickering 30

31 Types of voltage variations Two components of a voltage variation Magnitude - can range from +/- 5% of nominal voltage to a complete outage Duration can last for cycles (milliseconds) or hours Cost and practicality of solution depends on the magnitude and duration of event 31

32 Which Solution Will Work? SAG SRT/DRT EVR UPS GEN 32

33 Voltage Sag Characteristics Retained Voltage Duration Number of Phases Affected 33

34 Where Do Sags Come From??? How can you prevent Let s have that??? a closer look. 34

35 Area of Vulnerability 40-70% X 20-40% 0-20% 70-90% 35

36 Drive Ride Through (DRT) Problem Description: Progressive Cavity Pumps ( screw pump ) 8 hours of downtime for short duration (<1 sec) events Boscan Oil Field (Maracaibo, Venezuela) Eaton Solution: Drive Ride Through (DRT) with Ultra Capacitor Energy Storage 36

37 Drive Ride Through (DRT) Field Results 95.5% Availability Increased to 99.2% Increased Production by 1440 Barrels per unit At $100/barrel Resulted in Revenue of $144,000 (USD) per unit in 4 months Total Revenue = $864,000 (USD) ROI < 1 month! 37

38 Sag Ride Through (SRT) Problem Description: UV treatment use in drinking water is increasing to reduce the homeland security risk and cost of chlorine treatment Medium Pressure UV Water Treatment Systems require 7-10 minutes to cool down and re-start after a sag event In order to comply with EPA requirements this can require alternate chemical treatment or rerunning the water through the system Eaton Solution: Sag Ride Through (SRT) 38

39 Sag Ride Through (SRT) Washington DC Drinking Water System Water Treatment Plant 12 Calgon Carbon 48 reactors installed treating up to 480 million gallons of water a day Patent pending solution using SRT solution with UV treatment units Reduces 95% of UV treatment light outages Ensures system exceeds EPA ultraviolet treatment standards UPS backup is a choice too Depends on the backup time needed Depends on the power quality at the site 39

40 3 (+1) Basic Types of UPS Standby Off Line Normal Operation Power Failure Event Powerware Series 3 The Series 3 (Stand-By) UPS delivers power protection from 3 of the most common power problems that threaten your equipment and data Interruption Sag Swell Line Interactive Buck/Boost Powerware Series 5 The Series 5 (Line-Interactive) UPS delivers power protection from 5 of the most common power problems that threaten your equipment and data Undervoltage Overvoltage Ferroresonant +1 Powerware Series Ferro The Series Ferro UPS delivers galvanic isolated power protection from 8 of the most common power problems that threaten equipment and data Harmonic distortion Line noise Switching transients On Line Double Conversion ( Powerware Series 9 The Series 9 (On-Line) UPS delivers power protection from all 9 of the most common power problems that threaten your equipment and data Frequency variation 41

41 Power conditioning options (non-ups) Eaton Solution Primary Benefit Rating Power-Sure 700 (EVR) Power-Sure 800 Power-Suppress 100 Power-Suppress T7 Sag Ride Through (SRT) Drive Ride Through (DRT) Harmonic Correction Unit (HCU) Voltage regulation 3-ph (10-300kVA) Sag/swell, noise, regulation Electrical noise (EMI/RFI) Electrical noise (EMI/RFI) Sag/swell, regulation Sags/interruptions for VFD s 1-ph (250VA-3.5VA) 3-ph (3.5kVA-25kVA) 1-ph (250VA-7.5kVA) 3-ph (15kVA-225kVA) 3-ph (75 kva-20mva) 3-ph (10HP-1000HP) Harmonics 3-ph (50A, 100A, 300A) Power Conditioning Website 42

42 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Harmonic Solutions Effective Grounding Surge Solutions Voltage Variation Solutions 43

43 Harmonic Symptoms/Concerns Equipment Failure and Misoperation Notching (electronic control malfunctioning, regulator misoperation) Overheating/Failure (transformers, motors, cables/neutral) Nuisance Operation (fuses, breakers) Insulation deterioration Audible noise in electrical equipment Economic Considerations Oversizing (equipment is sized larger to accommodate harmonics) Losses/Inefficiencies/PF Penalties Inconsistent meter reading Harmonic Resonance with Power Factor Correction Capacitors 44

44 Introduction - Harmonics Utility is responsible for providing clean voltage Customer is responsible for not causing excessive current harmonics Utility can only be fairly judged if customer is within its current limits Harmonics cause voltage and current problems in power systems IEEE Std provides a basis for limiting harmonics Multiple methods exist for mitigating harmonics and one size does not fit all 45

45 Harmonics it s not that complicated. VE V = mc IIZ Z 2 d d h G U Misoperation Problems Heating Problems (Load Related) Source Impedance

46 Which came first? Voltage Distortion Current Distortion In this case the Egg! Current distortion causes Voltage distortion Voltage distortion is created by pulling distorted current through an impedance Amount of voltage distortion depends on: System impedance Amount of distorted current pulled through the impedance If either increases, V THD will increase

47 What s YOUR (Harmonic) Problem? Voltage Problem Current Problem Impedance Problem Solutions exist for every problem but you have to understand the problem first!

48 Sources of Harmonics General sources of harmonics Power electronic equipment (drives, rectifiers, computers, etc.) Arcing devices (welders, arc furnaces, florescent lights, etc.) Iron saturating devices (transformers) Rotating machines (generators) Most prevalent and growing harmonic sources Adjustable frequency drives (AFD) Switch-mode power supplies (computers) Fluorescent lightning 49

49 Internal vs. External Sources Some harmonic sources are internal VFDs, switch mode power supplies, etc. Other harmonic sources are external Customers sharing the same line Is the voltage distortion caused by you or your neighbor? Establish a baseline (your neighbor s load) Determine the incremental change (your load) 50

50 Harmonic Limits System Issues Actual measurements at 480 V main breaker - system with large variablefrequency drives Voltage distortion at no load is 4%! 51

51 Expected Harmonics Source Typical Harmonics* 6 Pulse Drive/Rectifier 5, 7, 11, 13, 17, Pulse Drive/Rectifier 11, 13, 23, Pulse Drive 17, 19, 35, 37 Switch-Mode Power Supply 3, 5, 7, 9, 11, 13 Fluorescent Lights 3, 5, 7, 9, 11, 13 Arcing Devices 2, 3, 4, 5, 7... Transformer Energization 2, 3, 4 * Generally, magnitude decreases as harmonic order increases H = NP+/-1 i.e. 6 Pulse Drive - 5, 7, 11, 13, 17, 19, 52

52 Harmonic Sources Continuous Current

53 But Remember Harmonics are not a problem unless they are a problem!

54 Harmonics and Heating Load 100% Harmonics Std Transformer Max Temp 176 F HMT Max Temp 105 F 55

55 Voltage Notching

56 Neutral Heating Oversize Equipment A B C N 10A at 180 Hz 10A at 60 Hz 10A at 180 Hz 10A at 60 Hz 10A at 180 Hz 10A at 60 Hz 0A at 60 Hz 30A at 180 Hz 57

57 3rd Harmonic Summation in Neutral 58

58 3rd Harmonic Summation in Neutral 59

59 Harmonics and Motor Heating X s X T M Linear Load (Motor) Draws Non-60Hz (Harmonic) Current 60 M Distorted Current Causes Distorted Voltage

60 Motor Heating and Vibrations Motor Heating Vibrations System Losses Like driving with one foot on the gas and one on the brake 61

61 Harmonics and Generators Generator Concerns Generator impedance is generally 3-4 times (16-18%) the equivalent source transformer (5-6%) Utility Souce Generator Source 4.4% Vthd 13% Vthd Same Load (all Drives) 62

62 Notching and Generators Generator Source may result in larger commutation notches and transients

63 Harmonics and Generators Utility Source 2.3% THD Generator Source 5.7% THD

64 Harmonics and Generators Example Generator Sync Failure Generator 1 (Loaded) Generator 2 (Unloaded)

65 Harmonics and Generators Example Generator Sync Failure Blue (top) = Generator 1 Bus Voltage Red (bottom) = Sync Check Voltage Generator #1 (Loaded) vs. Generator #2 (Unloaded) Blue (top) = 120 V Filtered Sync Check Input from Generator 1 Red (bottom) = 480 V Generator Bus Voltage Solution: Series-rated surge protector/ring-wave filter

66 Harmonics and Generators Generator Filter UPS Filter On/Off Utility Source Generator Source Harmonic Filter ON Harmonic Filter ON Harmonic Filter OFF

67 PF and Harmonics kva (and Amp) Reduction 125 kva 100 kw 75 kvar 103 kva 100 kw 25 kvar no PFC w/pfc 125 kva 103 kva 50 kvar 25 kvar 125 HP 50 kvar 100 kw 68

68 Somebody has to pay for capacity and losses Wasted Capacity (VAR s) Useful Work (Watts) Capacity (kva) 69

69 What is a VAR? Active power, also called real power, is measured in Watts or kw and performs Useful Work Electrical equipment like motors and transformers require reactive power create a Magnetic Field and allow work to be performed. This reactive power is called volt-amperes-reactive or VAR s Reactive power is measured in vars or kvars Capacitors also draw reactive power but this reactive power is 180 degrees opposite of motors. Total apparent power is called volt-amperes and is measured in VA or kva 70

70 Harmonic Resonance On November 7, 1940, at approximately 11:00 AM, the Tacoma Narrows suspension bridge collapsed due to wind-induced vibrations the bridge had only been open for traffic a few months. 71

71 Harmonic Resonance The Self Correcting Problem Blown Fuses Failed Capacitors Damaged Transformer Harmonics = Wind (Excites Resonance) 72

72 Harmonic Resonance h R kva kvar SC CAP X s 1500 kva 5.0% 480 V 200 HP Drive Source of Harmonics 500 HP 600 kvar Capacitor 73

73 Harmonic Resonance If a capacitor exists on the power system AND Harmonic producing loads are in use You MUST check for harmonic resonance (series and parallel)

74 Harmonic and PF Solutions Line Reactors and DC Chokes K-Rated/Drive Isolation Transformers Harmonic Mitigating Transformers/Phase Shifting Harmonically Hardened Capacitors Tuned and De-Tuned Filters Broadband Filters 18-Pulse Clean Power Drives Active Filters Active Rectifier UPS 75

75 PF Correction and Harmonic Filters Facilities requiring PF correction for utility penalties often use one of the following compensation methods: PF Capacitors (standard or switched) risk of harmonic resonance Harmonically Hardened capacitors like K-rated transformer Harmonic Filter Tuned to reduce overall harmonic distortion (typically 4.7 th tuning ) De-tuned to avoid resonance (typically 4.2 nd tuning ) Active Harmonic Filter (both harmonic compensation and PF correction) Capacitors Hardened Capacitors Cost Harmonic Filters Active Filters 76

76 Active Filter Harmonic Solutions Oversized Generator X s G X T 480 V Filter Low Distortion Electronic Ballast M HMT M Broadband Filter Active Rectifier or 18 Pulse M 12 Pulse + - HMT Active Rectifier, Filter or 12 Pulse UPS PF Corrected

77 Oversized Equipment Transformer Efficiency - 75 kva Example 0.99 Oversized Generator X s G X T 480 V % Load Resistive Load 100% Harmonic Load Oversized Transformer 2X Neutral

78 Drive and Rectifier Solutions Drive without line reactor Drive with line reactor Best cost/kva solution for drive harmonics

79 Current - % of Fundamental Effect of Drive Line Reactors 100% 80% Effect of Line Reactors 0.5% 3.0% 5.0% 60% 40% 20% 0% Harmonic Order

80 How Does a Filter Work? Generator X s Harmonic Current Divides by Ratio of Harmonic Impedances G X T 6A 480 V 24A 12A 18A Filter Current Flows Here (On Phase Conductors) Total Harmonic Current Divides Here M M M M Filter 12A 12A 12A (5 th Harmonic)

81 Phase Shifting/Cancellation 12 Pulse, 18 Pulse or 24 Pulse Cancellation by Design #1 #2 12 Pulse Example

82 Harmonics and Cancellation Without Cancellation 24 Pulse Cancellation

83 Main HMT 5 th and 7 th Cancellation Say we have a three story building with a variety of loading. How much 5 th and 7 th cancellation can we expect? Normal Delta-Wye Normal Delta-Wye HMT-NON 0 Shift 5 Units 5 Units - 5 Units ZIG-ZAG CONNECTION 4 Units Normal Delta-Wye Normal Delta-Wye Normal Delta-Wye 4 Units 4 Units 3 Units Normal Delta-Wye HMT-NON 0 Shift Normal Delta-Wye Case = 12 Units - 3 Units ZIG-ZAG CONNECTION Case = 6 Units 3 Units Case = 2 Units

84 18 Pulse Rectifier 18 Pulse Design Voltage Eaton Clean Power Current Drive CPX9000

85 Total Demand Distortion CPX 9000 Example HARMONIC 30 HZ 40 HZ 50 HZ 60 HZ THD (% of I 1 ) 26.7 % 14.1 % 9.1 % 5.9 % TDD (% of I L ) 3.6 % 4.1 % 4.5 % 4.8 % All Harmonics RMS (fundamental) A Demand Load

86 Cost of Harmonic Correction Description Cost $/kva Cost p.u. Reactor 3 1 Capacitors (LV) 12 4 Filter (MV) 12 4 Filter (MV) Switched 15 5 K-Rated Transformer 20 7 Capacitors (LV) Switched 25 8 Filter (LV) Filter (LV) Switched Harmonic Mitigating Transformer Blocking Filter (3rd's) Broadband Filter (Drives) Active Filter Per unit costs compared to reactor pricing Note that prices are generalized for comparison only Some equipment must be fully rated for loads - others can be partially rated Capacitors are shown for reference only

87 88

McGill Power Sales & Engineering, INC.

McGill Power Sales & Engineering, INC. 1 McGill Power Sales & Engineering, INC. Power Factor Correction Terry McGill President McGill Power Sales & Engineering Inc. 2007 Eaton Corporation. All rights reserved. Agenda What is power factor? What

More information

Power Factor & Harmonics

Power Factor & Harmonics Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics

More information

Introduction to Harmonics and Power Quality

Introduction to Harmonics and Power Quality NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»

More information

Fundamentals of Power Quality

Fundamentals of Power Quality NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

Power Quality Symptoms What Is Normal? Power Quality Approach. Other Power Quality Solutions

Power Quality Symptoms What Is Normal? Power Quality Approach. Other Power Quality Solutions April 25, 2017 Mike Carter Power Quality Symptoms What Is Normal? Power Quality Approach Find and fix Ride-through Solutions Protection/Compensation Schemes Other Power Quality Solutions What Can Go Wrong?

More information

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE - 519 Solutions Harmonics Tutorial 1 Power Conversion Equipment can save energy and control motors, heaters,

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008 Welcome to the rd Annual Northern Ohio 3 rd Energy Management Conference September 30, 2008 Recover Lost Dollars Demand Side Electrical Energy Savings By Improving Distribution System Efficiency, Capacity

More information

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to

More information

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS. MAIN TOPICS DISCUSSED Electric Rates Electrical system utilization ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K Power quality Harmonics Power factor (Cos phi) improvement Section K - 2 ELECTRIC

More information

Electric Power Quality: Voltage Sags Momentary Interruptions

Electric Power Quality: Voltage Sags Momentary Interruptions Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage

More information

T-68 Protecting Your Equipment through Power Quality Solutions

T-68 Protecting Your Equipment through Power Quality Solutions T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. 2 Agenda What

More information

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017 Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates

More information

7/15/2002 PP.AFD.08 1 of 28

7/15/2002 PP.AFD.08 1 of 28 Power Quality Considerations When Applying Adjustable Frequency Drives Explanations and Various Countermeasures 7/15/2002 PP.AFD.08 1 of 28 Power Quality Why the Renewed Interest in Power Quality? Copy

More information

Harmonics, its Mitigation & Result of Case study of Spinning Mill

Harmonics, its Mitigation & Result of Case study of Spinning Mill International Journal of Innovative Research in Engineering & Management (IJIREM) ISSN: 2350-0557, Volume-2, Issue-4, July 2015, its Mitigation & of Case of Spinning Mill Yogesh Subhash Shimpi M. Tech

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

How adjustable speed drives affect power distribution

How adjustable speed drives affect power distribution How adjustable speed drives affect power distribution Application Note Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality. ASDs as victim loads Although ASDs are usually

More information

Understanding Harmonics

Understanding Harmonics Understanding Harmonics Terry Gaiser Sensus What Are Harmonics? 1 » What is Power Quality?» Power quality is the degree to which both the utilization and delivery of electric power affects the performance

More information

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics Reactive Power and Harmonic Compensation Guide to Harmonics POWER QUALITY The Basics of Harmonics All business types, commercial, industrial, government and energy/utility have a concern with power quality.

More information

NIPSCO Energy Symposium

NIPSCO Energy Symposium Backup Power Automatic Transfer NIPSCO Energy Symposium symposium Backup Power Applications/Considerations Backup Power Types Automatic Transfer Switch Basics Presenters McGill Power - Jeremy Irmeger Eaton

More information

1C.6.1 Voltage Disturbances

1C.6.1 Voltage Disturbances 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope The purpose of this document is to state typical levels of voltage disturbances, which may be encountered by customers

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

Active Harmonic Filter (AF3)

Active Harmonic Filter (AF3) Active Harmonic Filter (AF3) Active Harmonic Filter Improving the Efficiency and Life of System by use of Digital Active Power Conditioner HARMONICS 50 Hz, fundamental 100 Hz, 2nd Harmonic 150 Hz, 3rd

More information

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014

More information

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives .0 Volume 6 Solid-State Control CA0800007E March 05 www.eaton.com V6-T-47 .0 Adjustable Frequency Drives Overview What Are Harmonics? Take a perfect wave with a fundamental frequency of 60 Hz, which is

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

How Harmonics have led to 6 Power Factor Misconceptions

How Harmonics have led to 6 Power Factor Misconceptions Harmonic and Energy Saving Solutions How Harmonics have led to 6 Power Factor Misconceptions Tony Hoevenaars, P.Eng. Power Factor Misconceptions 1. Low power factor is normally caused by electric motors

More information

Managing Power Quality Issues

Managing Power Quality Issues Managing Power Quality Issues Questline Academy November 4, 2015 Mike Carter Justin Kale 2 Economic Value Productivity Customer Confidence How often do you deal with power quality problems at your facility?

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

Harmonics I Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update

Harmonics I   Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update Power Protection Products, Inc. White Paper by Dan Maxcy l 2018 Update P3 is the industry s trusted and respected critical power, cooling and energy solutions provider. 877-393-1223 I www.p3-inc.com HARMONICS

More information

Power Quality Monitoring and Power Metering Tutorial

Power Quality Monitoring and Power Metering Tutorial Power Quality Monitoring and Power Metering Tutorial Power generation and transmission today are accomplished using three phase alternatingcurrent. To understand electrical power quality monitoring and

More information

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM Abstract Efficient operation of the electrical system of any facility is essential to controlling operational costs while maximizing

More information

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Power Quality and Circuit Imbalances 2015 Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Summary of IEEE 1159 Terms Category Types Typical Duration

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System WHO SHOULD FILE THIS SUBMITTAL: Anyone in the final stages of interconnecting a Generation System with Nodak Electric Cooperative, Inc. This submittal shall be completed and provided to Nodak Electric

More information

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner conditioning products Electronic voltage regulator -Sure 700 & 800 -Suppress T7 & 100 Harmonic correction unit Sag ride-through power conditioner The power to work Basics of power quality The partner you

More information

Understanding Input Harmonics and Techniques to Mitigate Them

Understanding Input Harmonics and Techniques to Mitigate Them Understanding Input Harmonics and Techniques to Mitigate Them Mahesh M. Swamy Yaskawa Electric America YASKAWA Page. 1 Organization Introduction Why FDs Generate Harmonics? Harmonic Limit Calculations

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

PowerMonitor 5000 Family Advanced Metering Functionality

PowerMonitor 5000 Family Advanced Metering Functionality PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation.

More information

Harmonic control devices

Harmonic control devices ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)

More information

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic

More information

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI OVERVIEW In the present business climate, companies are under constant pressure to increase profitability by increasing productivity, maximizing

More information

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution Agenda I. Harmonic Basics II.Harmonic Mitigation Solutions III.Case Study 2 Harmonic

More information

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,

More information

Presents. Harmonics Years

Presents. Harmonics Years Presents Harmonics What is a Harmonic? A harmonic is the term used for current flow on your facilities power system at frequencies other than 60Hertz. Harmonic Problems Include: Harmonic Problems

More information

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY -- D.,.,.,. E S C R I P T I V E B U L L E T I N Bulletin DB-106 Square D Company October, 1990 ---1 I SQU ARED COMPANY -- Electrical Power Distribution System - The Heart of the Business From small commercial

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Emicon Engineering Consultants L.L.C.

Emicon Engineering Consultants L.L.C. Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com

More information

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners IEEE Canada Webinar Presentation May 21, 2008 Bob Hanna, FIEEE, P.Eng. RPM Engineering Ltd. www.rpm-eng.com David

More information

NJWA - Harmonics and Drives Proper System Design

NJWA - Harmonics and Drives Proper System Design Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

PART 1 OWNER/APPLICANT INFORMATION

PART 1 OWNER/APPLICANT INFORMATION CALHOUN COUNTY ELECTRIC COOP. ASSN. Application for Operation of Customer-Owned Generation This application should be completed as soon as possible and returned to the Cooperative in order to begin processing

More information

Power Protection and Conditioning

Power Protection and Conditioning 2/50 Voltage Wave Attenuation CBEMA Constant Voltage Power Supply Voltage surge with a virtual front time of 1.2 ms and a time to half-value of 50 ms delivered across an open circuit. 8/20 Current Wave

More information

1C.4.1 Harmonic Distortion

1C.4.1 Harmonic Distortion 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well

More information

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation Variable Frequency Drive Packages with Harmonic Mitigation Low Harmonic Drive Packages Engineered by Rockwell Automation What Do I Need to know About Harmonics? What are Harmonics? Harmonics are deviations

More information

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company Engineering data submittal Page 1 WHO SHOULD FILE THIS SUBMITTAL : Anyone in the final stages of in terconnecting a Generation System with Otter Tail Power. This submittal shall be completed and provided

More information

SECTION 1 INTRODUCTION

SECTION 1 INTRODUCTION Power PE Engineering Pro Guides Full Exam 80 exam difficulty level problems and detailed solutions Tests concepts not tested by other sample exams. Follows the exam outline and covers the main topics.

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

Power Quality Analysers

Power Quality Analysers Power Quality Analysers Review of Power Quality Indicators and Introduction to Power Analysers ZEDFLO Australia 6-Mar-2011 www.zedflo.com.au Power Quality Indicators Review of main indicators of electrical

More information

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative:  Address: Fax Number: Interconnection of a Customer-Owned Renewable Generation System of Greater than 100 KW and Less than or Equal to 1 MW to the LCEC Electric Grid Tier 3 Application and Compliance Form Instructions: Complete

More information

Power Quality in Metering

Power Quality in Metering Power Quality in Metering Ming T. Cheng Directory of Asian Operations 10737 Lexington Drive Knoxville, TN 37932 Phone: (865) 218.5885 PQsynergy2012 www.powermetrix.com Focus of this Presentation How power

More information

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY by Cesar Chavez, Engineering Manager, Arteche / Inelap, and John Houdek, President, Allied Industrial Marketing, Inc. Abstract: Industrial facility harmonic distortion problems can surface in many different

More information

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation This application is to be completed and returned to the Cooperative member service representative in order to begin

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

APPLICATION GUIDE. Harmonics in HVAC applications

APPLICATION GUIDE. Harmonics in HVAC applications APPLICATION GUIDE Harmonics in HVAC applications Table of contents 4 Harmonics in general and why we should care 4 Introduction 4 Basics of harmonics 5 Causes of harmonic distortion 5 Problems caused

More information

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013 Investigating the Effect of Using Capacitorsin the Pumping Station on the Harmonic Contents (Case Study: Kafr El-Shikh Governorate, Egypt) Khaled M. Fetyan Abstract Power Factor (PF) is one of the most

More information

Effective Harmonic Mitigation with Active Filters

Effective Harmonic Mitigation with Active Filters Advancing Power Quality White Paper Effective Harmonic Mitigation with Active Filters Written by: Ian Wallace Variable Speed Drive with no Harmonic Mitigation Industry standard variable speed drives, with

More information

An Introduction to Power Quality

An Introduction to Power Quality 1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger

More information

Harmonic Filters for Single Phase Equipment

Harmonic Filters for Single Phase Equipment POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics

More information

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems This application should be completed as soon as possible and returned to the Cooperative in order to

More information

Cost Considerations When Selecting Variable Frequency Drive Solution

Cost Considerations When Selecting Variable Frequency Drive Solution Cost Considerations When Selecting Variable Frequency Drive Solution Introduction Advancements made in the development of drive technology mean users have more options than ever when selecting a drive

More information

Technical Paper. Harmonic Distortion in Data Centers

Technical Paper. Harmonic Distortion in Data Centers Technical Paper Harmonic in Data Centers Written By: Ian Wallace Summary Power quality and power reliability are critical to data center operation. As strides have been made to improve energy efficiency

More information

APPENDIX B: Generation Interconnection Application Form

APPENDIX B: Generation Interconnection Application Form 2 APPENDIX B: Generation Interconnection Application Form WHO SHOULD FILE THIS APPLICATION: Anyone expressing interest to install generation which will interconnect with Xcel Energy (Local electric utility)

More information

Drives 101 Lesson 5. Power Input Terminology for a VFD

Drives 101 Lesson 5. Power Input Terminology for a VFD Drives 101 Lesson 5 Power Input Terminology for a VFD This lesson covers the terminology associated with the incoming power to a Variable Frequency Drive (VFD) and the efforts to protect both the VFD and

More information

New power tools provide quality and efficiency By

New power tools provide quality and efficiency By Typical Delta-wye transformer New power tools provide quality and efficiency By Steve Terry For quite some time, it has been well understood that phase-control SCR dimming systems used in the entertainment

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics

More information

Fluke 40/41 Power Harmonics Analysers

Fluke 40/41 Power Harmonics Analysers Data Pack A Issued March 2002 232-4752 Fluke 40/41 Power Harmonics Analysers This data sheet refers to the Fluke 40 and Fluke 41 Power Harmonics Analysers. RS stock no. Description 215-9621 Fluke 41B power

More information

PRODUCT FEATURES TYPICAL APPLICATIONS

PRODUCT FEATURES TYPICAL APPLICATIONS The AVR voltage regulator and PLC power conditioner product lines consists of over 250 standard units arranged in 29 different voltage families to provide 95% coverage of day-to-day application needs.

More information

Harmonic Filters and Reactors

Harmonic Filters and Reactors Harmonic Filters and Reactors Harmonics are invisible but costly If one looks up the meaning of harmonics in any one of several technical dictionaries, it is normally defined as being A sinusoidal component

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

Harmonic Mitigating Transformer - Technical Guide

Harmonic Mitigating Transformer - Technical Guide Harmonic Mitigating - Technical Guide HARMONY Series s HARMONY-1 www.mirusinternational.com Benefits: Prevent voltage flat-topping while reducing energy costs. Reduce voltage distortion caused by harmonic

More information

Power Quality and Power Factor Correction

Power Quality and Power Factor Correction Power Quality and Power Factor Correction Introduction Since most loads in modern electrical distribution systems are inductive, there is an ongoing interest in improving power factor. The low power factor

More information

UNDERSTANDING POWER QUALITY

UNDERSTANDING POWER QUALITY Technical Note No. 1 June 1998 UNDERSTANDING POWER QUALITY This Technical Note describes the range of problems, what causes them, what they affect and what could be done to manage them. Integral Energy,

More information

ECET Modern Power

ECET Modern Power ECET 273000 Modern Power Course Instructors Course Philosophy This course is an introduction to a wide range of electrical energy systems technologies. Topics include fundamentals of energy conversion,

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

Dynamic Harmonic Mitigation and Power Factor Correction

Dynamic Harmonic Mitigation and Power Factor Correction Dynamic Harmonic itigation and Power Factor Correction Cesar Chavez, Eng Engineering Dept., Arteche. Naucalpan, Edo. de éxico, éxico John A. Houdek, ember, IEEE President, Allied Industrial arketing ilwaukee,

More information

POWER QUALITY PRODUCTS FOR NON-LINEAR LOADS

POWER QUALITY PRODUCTS FOR NON-LINEAR LOADS Voltage Regulators, Line Voltage Conditioners and Super Isolation Transformers Electrical Problems Related to Power Quality... 138 Electrical Problems on Non-Linear Systems... 139 Protection of Electrical

More information

Understanding Harmonic Suppression Systems

Understanding Harmonic Suppression Systems Slot Tech Feature Article Understanding Harmonic Suppression Systems Get a Handle on Wasted Energy and Excess Heat A typical casino will have thousands of switched-mode power supplies on-line, twenty-four

More information

Analysis of Harmonic Distortion in Non-linear Loads

Analysis of Harmonic Distortion in Non-linear Loads Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna

More information

EE 2028 POWER QUALITY

EE 2028 POWER QUALITY A Course Material on EE 2028 POWER QUALITY By Mr. R.RAJAGOPAL ASSISTANT PROFESSOR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING SASURIE COLLEGE OF ENGINEERING VIJAYAMANGALAM 638 056 QUALITY CERTIFICATE

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

IDEAL Test and Measurement THE BASICS OF POWER QUALITY

IDEAL Test and Measurement THE BASICS OF POWER QUALITY IDEAL Test and Measurement THE BASICS OF POWER QUALITY Table of Contents What is Power Quality? 2 Power Quality: An Introduction The Basics of Power Quality is a convenient guide to understanding the essential

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

VFDs and Harmonics in HVAC Applications

VFDs and Harmonics in HVAC Applications VFDs and Harmonics in HVAC Applications Larry Gardner Product Marketing Manager Yaskawa America, Inc. Jeff Grant Senior Sales Engineer LONG Building Technologies October 20, 2016 2016 Yaskawa America,

More information