Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions
|
|
- Gladys Ward
- 6 years ago
- Views:
Transcription
1 Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions Harmonics Tutorial 1
2 Power Conversion Equipment can save energy and control motors, heaters, etc, But they may also cause harmonic distortion Input current ASD ASD = Adjustable Speed Drive Harmonic Spectrum For normal balanced system Harmonics Tutorial 2
3 Typical Harmonic Distortion-6pulse rectifiers Typical VFD % THID 1-2 HP > 1 % 25-4 HP 8-1 % 5-15 HP 6-8 % 2 HP up 5-7 % THID = Total Harmonic Current Distortion Magnitude (% of Fundamental) Can cause excessive peak current For 6hz Power System 1 = 6hz 5 = 3hz 7 = 42hz 11 = 66hz 13 = 78hz 17 = 12hz Harmonic Number Harmonics Tutorial 3
4 Harmonic Current Distortion is a function of source impedance Expected input harmonics for given total input impedance for 6-pulse rectifier (6-diode, 3-phase bridge rectifier) Harmonic Number.5% Z 1.% Z 1.5% Z 2.% Z 2.5% Z 3.%Z 5 th th th th th th %THID Amps Increase 43% 23% 17% 13% 11% 9% Harmonics Tutorial 4
5 MTE line Reactors reduce Harmonic Current Distortion Expected input harmonics for given total input impedance for 6-pulse rectifier Use 5% impedance for VFD s Harmonic Number 5.% 6.% 7.% 8.% 9.% 1.% 5 th th th th th th %THID Amps Increase 6% 5% 5% 4% 3% 3% Harmonics Tutorial 5
6 Problems Caused by Harmonics Transformer over-heating Circuit breaker trips Fuse blowing Equipment malfunction Increased KVA demand rms and peak Total Power Factor reduction Wasted energy Harmonics Tutorial 6
7 IEEE-519 Distortion Limits I SC /I L <11 11 h<17 17 h<23 23 h<35 35 h TDD < < < < > I SC = Source Short Circuit Current h = Harmonic order I L = Load Current TDD = Total Demand Distortion Harmonics Tutorial 7
8 PCC per IEEE PCC = At Point of Metering, or PCC = Point Where Non-Linear Load Meets Linear Loads Isc / I L will be greater at this point in the system IEEE-519 limit is higher at this point Harmonics Tutorial 8
9 IEEE TDD = Magnitude of harmonic distortion as a percent of maximum demand current When demand current is known THD = Instantaneous value of harmonic distortion Typically based on motor FLA When demand current is not known Harmonics Tutorial 9
10 IEEE-519 Harmonic Voltage Distortion Limits 3%THVD - Hospitals, Airports 5%THVD - General Systems 1%THVD - Dedicated Systems Harmonics Tutorial 1
11 MTE Line Reactors Reduce Harmonics and Improve the Input Current Waveform ASD RL Reactor Input current Use 5% impedance Line Reactors Harmonics Tutorial 11
12 MTE Line Reactors Reduce Harmonics 15HP, 12% Matrix Filter at Rated Output Current Magnitude [Amperes] Time [seconds] Percent Harmonic No Reactor 5% Impedance Reactor 5% Impedance Reactor & 3% DC Choke Harmonics Tutorial 12
13 Matrix Filters Offer Best Power Quality for Power Conversion Systems Filter Input current Standard 6-pulse VFD 15HP, 12% Matrix Filter at Rated Output Current 35 Magnitude [Ampere Output 33.86% THiD Time [seconds] VFD input current M3-xxxxPD-8 Harmonics Tutorial 13
14 Standard Matrix Filter Circuit Configuration For 12- Pulse Performance Input Power Any 6-pulse VFD < 12% THID Guaranteed at filter input Standard Matrix Filter Harmonics Tutorial 14
15 Harmonic Distortion for 6-pulse Rectifier with Standard Matrix Filters < 8% typical at full load, < 12% THID guaranteed at any load Percent THD Percent Load 7% 6% 5% 4% 3% 2% 1% % Typical Worst Case % THID vs Load Typical Worst Case Harmonic spectrum Harmonics Tutorial 15
16 Typical input voltage distortion with Standard Matrix Filter.8% THVD 2.2% THVD.5%.4%.3%.2%.1%.% 12% Filter Voltage Distortion 1% Load & 1.5% Source W/1.5% source impedance 1.4% 1.2% 1.%.8%.6%.4%.2%.% 12% Filter Voltage Distortion 1% Load & 5.75% Source W/5.75% source impedance Typical Worst Case Typical Worst Case IEEE-519 limits are 3%, 5% or 1% Harmonics Tutorial 16
17 6-pulse Rectifiers with Standard Matrix Filters offer cleaner power than 12- pulse rectifiers 6-pulse VFD with Standard Matrix Filter 12-pulse Rectifier input current waveform at full load and with balanced line voltages Harmonics Tutorial 17
18 Matrix Filters perform better than 12- pulse in Real Life operating conditions (unbalanced line voltages, % to 1% loading) Total Input Current Distortion 6% 55% 5% 45% 4% 35% 3% 25% 2% 15% 1% 5% % 3% 3% 1% 1% 3% 3% 12 Pulse w/ 1% & 3% Line voltage unbalance Matrix w 1% & 3% 3% 3% 1% 1% 3% 3% 1% 1% 1% 3% 1% 1% 3% 1% % 1% 2% 3% 4% 5% 6% 7% 8% 9% 1% 11% 12% Percent Load Line voltage unbalance 1 % THiD (1%, 12p) 3% THiD (3%, 12p) 1 % THiD (1%, 6p) 3% THiD (3%, 6p) Harmonics Tutorial 18
19 6-pulse Rectifier with Matrix Filter is better than 12-pulse rectifier Matrix Filters Achieve Lower harmonic distortion Cleaner waveforms Higher efficiency Guaranteed distortion levels Matrix filters perform better under real life operating conditions Harmonics Tutorial 19
20 Enhanced Matrix Filter Circuit Configuration For 18- Pulse Performance Input Power < 8% THID Guaranteed at filter input 18-pulse Alternative Matrix Filter 6-pulse VFD This reactor converts a standard matrix filter to 18-pulse performance Harmonics Tutorial 2
21 Enhanced Matrix Filters reduce input current Harmonic Distortion even better than 18-pulse drives Input current Standard 6-pulse VFD Harmonics Tutorial 21
22 Harmonic Distortion with Enhanced Matrix Filter < 5%THID typical at full load, < 8% THID at any load % THID vs Load Harmonic Current Spectrum 1 6% Percent THD % 2% % Percent Load Typical Worst Case Typical Worst Case Harmonics Tutorial 22
23 Typical input voltage distortion with Enhanced Matrix Filter.6% THVD 1.8% THVD 8% Filter Voltage Distortion 1% Load & 1.5% Source 8% Filter Voltage Distortion 1% Load & 5.75% Source.35%.3% With 1.5% source impedance 1.2% 1.% With 5.75% source impedance.25%.2%.15%.1%.5%.%.8%.6%.4%.2%.% Typical Worst Case Typical Worst Case Note: IEEE-519 limits are 3%, 5% or 1% Harmonics Tutorial 23
24 Enhanced Matrix Filters achieve cleaner power than 18-pulse rectifiers Enhanced Matrix Filter Input current waveform THiD = 7.54% pulse Rectifier input current waveform at full load and with balanced line voltages (series bridges, isolation transformer) Harmonics Tutorial 24
25 6-pulse VFD with Enhanced Matrix Filter performs better than 18-pulse drive in real life operating conditions (% to 1% load, unbalanced line voltage) 18 Pulse Drive vs. 6-pulse VFD with Matrix Filter 1 9 Total Harmonic Current Distortion THID, % % Matrix Filter 3%Unbalance 2% Unbalance 1% Unbalance Balanced Line 18-Pulse Drive 3%Line Unbalance 2%Line Unbalance 1% Line Unbalance Balanced Lines Load, % Harmonics Tutorial 25
26 Matrix Filters produce cleaner input current waveforms than multi-pulse 2 THiD = 7.54% drives 8 6 Matrix Filter pulse Pulse Harmonics Tutorial 26
27 Matrix outperforms 12- and 18- pulse drives in real life test Measured Input Current Harmonics for12-pulse VFD 18-pulse VFD, and 6-pulse VFD with Matrix Filter Measured Current Distortion 1% 9% 8% 7% 6% 5% 4% 3% 2% 1% % 3hp dyne under full load 12-pulse - 1.3%THiD 18-pulse % ThiD Matrix Filter %THiD Harmonic Harmonics Tutorial 27
28 Standard Matrix Filters are Better Than Harmonic Traps Standard Matrix Filter 5 th Harmonic Trap Input 7.24% THiD 2% - 3% THID is typical for a 5 th Harmonic trap Harmonics Tutorial 28
29 Matrix Filter Voltage Regulation For both 8 and 12% Matrix Filters (With 48 V rms input) Max output voltage at No Load 52 V rms, 71 V peak ( < 5% boost) Min output voltage at Full load 46 V rms, 6 V peak (< 5% drop) Max filter input voltage (with 6% impedance) 49 V rms, 693 V peak (2% boost) Harmonics Tutorial 29
30 Matrix Filters are Suitable for any 6-pulse Rectifier Diode or SCR front end Including phase control Including SCR pre-charge circuits AC or DC drives VFD w/ DC link choke or AC line reactor Constant or Variable Torque Harmonics Tutorial 3
31 Where to use Matrix Harmonic Filters AC motor drives Variable torque Constant torque DC motor drives Welders UPS / Battery Chargers Distributed generation Harmonics Tutorial 31
32 Matrix Filters help meet IEEE-519 I SC /I L <11 11 h<17 17 h<23 23 h<35 35 h TDD < < < < > pulse ASD with matrix filter can achieve: 5% THID at Full Load 8% THID worst case any Load Harmonics Tutorial 32
33 IEEE Solutions Desired % THID at PCC (IEEE- 519) 3% Line Reactor 5% Line Reactor 3% Line + 3% DC Reactors 5% Line + 3% DC Reactors Matrix (12% Max) Matrix (8% Max) Maximum VFD Load (as % of total load) if all VFD's use same Harmonic Mitigation Method For most economical solution: Determine your THID limit and% VFD content on system, then move right until the chart value meets or exceeds your % VFD content. Harmonics Tutorial 33
34 MTE Gives You... Guaranteed THID levels Either 8% or 12% (5% and 8% THID typical at full load) No adverse system interaction No attraction of harmonics form other loads No harmonic studies required Harmonics Tutorial 34
35 MTE Field Experience Over 5, line / load reactors Over 3 Low Pass Harmonic Filters Harmonics Tutorial 35
36 Harmonics Tutorial 36
Effective Harmonic Mitigation with Active Filters
Advancing Power Quality White Paper Effective Harmonic Mitigation with Active Filters Written by: Ian Wallace Variable Speed Drive with no Harmonic Mitigation Industry standard variable speed drives, with
More informationGE Energy. Matrix Harmonic Filter Series D
GE Energy Matrix Harmonic Filter Series D Matrix Harmonic Filter GE Matrix Harmonic Filters provide broadband reduction of harmonics. Matrix Harmonic Filters not only offer better performance over other
More informationEconomical Solutions to Meet Harmonic Distortion Limits[4]
Economical Solutions to Meet Harmonic Distortion Limits[4] Abstract: The widespread adoption of variable frequency drive technology is allowing electricity to be utilized more efficiently throughout most
More informationHarmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017
Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates
More informationHarmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.
Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics
More informationLow Pass Harmonic Filters
Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power
More informationNJWA - Harmonics and Drives Proper System Design
Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives
More informationMulti-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7
White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,
More informationPQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement
PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to
More informationDrives 101 Lesson 5. Power Input Terminology for a VFD
Drives 101 Lesson 5 Power Input Terminology for a VFD This lesson covers the terminology associated with the incoming power to a Variable Frequency Drive (VFD) and the efforts to protect both the VFD and
More informationAPQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)
APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute
More informationUnderstanding Input Harmonics and Techniques to Mitigate Them
Understanding Input Harmonics and Techniques to Mitigate Them Mahesh M. Swamy Yaskawa Electric America YASKAWA Page. 1 Organization Introduction Why FDs Generate Harmonics? Harmonic Limit Calculations
More informationVariable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation
Variable Frequency Drive Packages with Harmonic Mitigation Low Harmonic Drive Packages Engineered by Rockwell Automation What Do I Need to know About Harmonics? What are Harmonics? Harmonics are deviations
More information2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives
.0 Volume 6 Solid-State Control CA0800007E March 05 www.eaton.com V6-T-47 .0 Adjustable Frequency Drives Overview What Are Harmonics? Take a perfect wave with a fundamental frequency of 60 Hz, which is
More informationHarmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with MTE Matrix AP Harmonic Filter vs. 18-Pulse Drive
DRIVING POWER QUALITY ISO 9001:2008 Certification Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with MTE Matrix AP Harmonic Filter vs. 18-Pulse Drive Abstract November 13, 2012 Todd Shudarek,
More informationHarmonics White Paper
Harmonics White Paper New Breakthrough In PWM Drives Technology Reduces Input Line Harmonics Without the Use of Filtering Devices Harmonic Distortion Damages Equipment and Creates a Host of Other Problems
More informationHarmonic Distortion and Variable Frequency Drives
Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation
More information7/15/2002 PP.AFD.08 1 of 28
Power Quality Considerations When Applying Adjustable Frequency Drives Explanations and Various Countermeasures 7/15/2002 PP.AFD.08 1 of 28 Power Quality Why the Renewed Interest in Power Quality? Copy
More informationAdvanced Harmonic Solutions For Harmonic Current Distortion MOTION CONTROLS
Advanced Harmonic Solutions For Harmonic Current Distortion MOTION CONTROLS Highly Efficient, System-Designed Solutions for Harmonic Distortion Introducing Danfoss Advanced Harmonic Solutions (AHS) Danfoss
More informationHARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N
HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic
More informationHarmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with Matrix AP Harmonic Filter vs. AFE Drive
DRIVING POWER QUALITY ISO 9001:2008 Certification Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with Matrix AP Harmonic Filter vs. AFE Drive Abstract December 18 th, 2012 Author: Todd
More informationUnderstanding Harmonics
Understanding Harmonics Terry Gaiser Sensus What Are Harmonics? 1 » What is Power Quality?» Power quality is the degree to which both the utilization and delivery of electric power affects the performance
More informationHarmonic Filters for Single Phase Equipment
POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics
More informationPower Factor & Harmonics
Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics
More information3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.
MAIN TOPICS DISCUSSED Electric Rates Electrical system utilization ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K Power quality Harmonics Power factor (Cos phi) improvement Section K - 2 ELECTRIC
More informationHarmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution
Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution Agenda I. Harmonic Basics II.Harmonic Mitigation Solutions III.Case Study 2 Harmonic
More informationHarmonic Mitigation in AC DC Converters for Induction Motor Drives by Vector Controlled
Harmonic Mitigation in AC DC Converters for Induction Motor Drives by Vector Controlled 1, BANOTH LAXMAN NAIK, 2, CH HARI KRISHNA 1.Student of Electrical and Electronics Engineering at Mother Teresa Institute
More informationHow adjustable speed drives affect power distribution
How adjustable speed drives affect power distribution Application Note Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality. ASDs as victim loads Although ASDs are usually
More informationVARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY Carrier Corporation Syracuse, New York October 2005 TABLE OF CONTENTS INTRODUCTION... 2 Common VFD Terms
More informationPresents. Harmonics Years
Presents Harmonics What is a Harmonic? A harmonic is the term used for current flow on your facilities power system at frequencies other than 60Hertz. Harmonic Problems Include: Harmonic Problems
More informationFundamentals of Power Quality
NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»
More informationTechnical Paper. Harmonic Distortion in Data Centers
Technical Paper Harmonic in Data Centers Written By: Ian Wallace Summary Power quality and power reliability are critical to data center operation. As strides have been made to improve energy efficiency
More informationWelcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008
Welcome to the rd Annual Northern Ohio 3 rd Energy Management Conference September 30, 2008 Recover Lost Dollars Demand Side Electrical Energy Savings By Improving Distribution System Efficiency, Capacity
More informationHarmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez
Harmonic Power A VFDs.com Whitepaper Written by Ernesto Jimenez Table of Contents 1. Need for Clean Electricity 2. What Are Harmonics? 3. Lower Order Harmonics 4. Causes of Harmonics 5. Effects of Harmonics
More informationDo You Have a Harmonic Problem?
??????? Do You Have a Harmonic Problem? Forster Electrical Engineering, Inc. 550 N. Burr Oak Ave, Oregon, WI 53575 (608) 835-9009 (608) 835-9039 fax 1 March 1999 What is THD? Total Harmonic Distortion
More information1C.4.1 Harmonic Distortion
2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well
More informationHarmonic Mitigation Harmonic Data Comparisons
Harmonic Data Comparisons 1336 PLUS, 1336 PLUS II, 1336 IMPACT and 1336 FORCE AC Drives with 6-Pulse, 12-Pulse, and 18-Pulse Front-Ends Topologies 6-Pulse drive 12-Pulse drive 18-Pulse drive Harmonic Spectrum
More information22.0 Harmonics in Industrial Power Systems
1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a
More informationHow Harmonics have led to 6 Power Factor Misconceptions
Harmonic and Energy Saving Solutions How Harmonics have led to 6 Power Factor Misconceptions Tony Hoevenaars, P.Eng. Power Factor Misconceptions 1. Low power factor is normally caused by electric motors
More informationAPPLICATION GUIDE. Harmonics in HVAC applications
APPLICATION GUIDE Harmonics in HVAC applications Table of contents 4 Harmonics in general and why we should care 4 Introduction 4 Basics of harmonics 5 Causes of harmonic distortion 5 Problems caused
More informationElectromagnetic Harmonic Filters Technical Guide
Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other triplen
More informationVFDs and Harmonics in HVAC Applications
VFDs and Harmonics in HVAC Applications Larry Gardner Product Marketing Manager Yaskawa America, Inc. Jeff Grant Senior Sales Engineer LONG Building Technologies October 20, 2016 2016 Yaskawa America,
More informationGuide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics
Reactive Power and Harmonic Compensation Guide to Harmonics POWER QUALITY The Basics of Harmonics All business types, commercial, industrial, government and energy/utility have a concern with power quality.
More informationElectric Power Quality: Voltage Sags Momentary Interruptions
Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage
More informationOpen-Delta Systems Affect Variable Frequency Drives
Open-Delta Systems Affect Variable Frequency Drives To avoid premature drive failure, proper precautions must be taken when installing VFDs on open-delta supplies. Written by: Dan Peters, Yaskawa America,
More informationHarmonic Distortion Evaluations
Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion
More informationSection 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services
Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality
More informationReducing Total Harmonic Distortion with Variable Frequency Drives
Reducing Total Harmonic Distortion with Variable Frequency Drives Low Harmonic Technology in Optidrive Eco Overview Overview Both AC line chokes and DC link chokes have historically been used with Variable
More informationThyristorised Automatic Power Factor
Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor
More informationIntroduction to Harmonics and Power Quality
NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»
More informationElevator Drives, Power Quality and Energy Savings
CERTIFIED ELEVATOR TECHNICIAN Focus on Continuing Education Elevator Drives, Power Quality and Energy Savings by Jonathan Bullick and Brad Wilkinson Value: 1 contact hour (0.1 CEU) This article is part
More informationPOWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics
POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics
More informationA. Harmonics. non-linear loads. are. required)
Harmonic Comparison between Fluorescent and WOLED (White Organic LED) Lamps Hari Maghfiroh, Fadhila Tresna Nugraha, and Harry Prabowo Abstract Fluorescent and WOLED are widely used because it consumes
More informationThe increase in the application
Harmonic mitigation for AC variable frequency pump drives Pump applications increasingly use AC variable speed drives. However, their operation introduces harmonic distortion of voltage supplies, which
More informationAnalysis of Harmonic Distortion in Non-linear Loads
Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna
More informationVARIABLE FREQUENCY DRIVE
VARIABLE FREQUENCY DRIVE Operation and application of variable frequency drive technology Carrier HVAC Europe - Marketing Department June 2014 TABLE OF CONTENTS INTRODUCTION...2 Common VFD Terms...2 VFD
More informationHarmonics, its Mitigation & Result of Case study of Spinning Mill
International Journal of Innovative Research in Engineering & Management (IJIREM) ISSN: 2350-0557, Volume-2, Issue-4, July 2015, its Mitigation & of Case of Spinning Mill Yogesh Subhash Shimpi M. Tech
More informationMIRUS International Inc.
LINEATOR Universal Harmonic Filter for VFD s Questions and Answers This document has been written to provide answers to the more frequently asked questions we have received regarding the application of
More informationMitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India
Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India Abstract: The objective of this research is to develop a novel voltage control scheme that
More informationLineator-HP High Performance model used where the highest power quality demands must be met
LINEATOR TM Advanced Universal Harmonic Filter The LINEATOR Advanced Universal Harmonic Filter (AUHF) is a revolutionary advancement in the area of passive harmonic mitigation. No other device on the market
More informationPower Quality Basics. Presented by. Scott Peele PE
Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng
Investigation Nathan Schachter, Peng Objectives Learn what happened Explain why it happened Discuss solutions Suggest remedies so it does not happen again Prevention is the key to success 2 ACS 1000 VFD
More informationAn Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System
An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System Milan Anandpara Tejas Panchal Vinod Patel Deaprtment of Electrical Engineering Deaprtment
More informationVARIABLE FREQUENCY DRIVE
VARIABLE FREQUENCY DRIVE Yatindra Lohomi 1, Nishank Nama 2, Umesh Kumar 3, Nosheen aara 4, Uday Raj 5 (Assistant Professor in Department of Electrical Engineering GIET Kota2) (Department of Electrical
More informationComparison of Different Common Passive Filter Topologies for Harmonic Mitigation
UPEC21 31st Aug - 3rd Sept 21 Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation H. M. Zubi IET and IEEE member hz224@bath.ac.uk R. W. Dunn IEEE member E-mail r.w.dunn@bath.ac.uk
More information1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.
Section 16680 VARIABLE SPEED DRIVE SYSTEMS OR AFD Part I - GENERAL I.01 Description A. This specification is to cover a complete adjustable frequency motor drive consisting of a pulse width modulated (PWM)
More informationAC Drives and Soft Starter Application Guide
Feature AC Drives and Soft Starter Application Guide by Walter J Lukitsch PE, Gary Woltersdorf Jeff Theisen, and John Streicher Allen-Bradley Company Abstract: There are usually several choices for starting
More informationHarmonics. Craig Hartman, P.E. VFDs, Generators & IEEE 519
www.emcsolutions.com Harmonics VFDs, Generators & IEEE 519 Craig Hartman, P.E. Specializing in Motors, Drives, Generators, and Electrical Asset Management The Great Horse Manure Crisis of 1894 New York
More informationInternational Journal of Electrical Engineering and Technology (IJEET), ISSN (Print), INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING &
INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume 5, Issue 2, February (2014), pp. 60-67 IAEME: www.iaeme.com/ijeet.asp Journal Impact
More informationPrepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA
ATCO Electric Hangingstone Substation HARMONIC STUDY Prepared By Pierre Archambault, PEng Power Survey International Inc. 8025 Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA Rev.: 6 March 2007 TABLE OF
More informationAC VOLTAGE CONTROLLER (RMS VOLTAGE CONTROLLERS)
AC VOLTAGE CONTROLLER (RMS VOLTAGE CONTROLLERS) INTRODUCTION AC voltage controllers (AC line voltage controllers): are employed to vary the RMS value of the alternating voltage applied to a load circuit
More informationReduce harmonics in HVAC&R inverters through C-Less technology
Reduce harmonics in HVAC&R inverters through C-Less technology Karim Lamrabtine Global Product Manager VSD 14-15 SEPTEMBER 2011, MUNICH Agenda www.infoplc.net What are Harmonics? Standards Compliance How
More informationPump ED 101. Two Steps To Increased Pump Life (Part Two) Voltage Unbalance
Pump ED 101 Two Steps To Increased Pump Life (Part Two) Voltage Unbalance Joe Evans, Ph.D http://www.pumped101.com Last month we investigated the importance of identifying the actual operating point of
More informationFigure 1 Typical Inverter Block Diagram
AC Drives and Soft Starter Application Guide Walter J Lukitsch PE, Gary Woltersdorf Jeff Theisen, John Streicher Allen-Bradley Company Milwaukee, WI Abstract: There are usually several choices for starting
More informationHarmonic Solutions. Clean Power Drive Solution to Harmonic Distortion
Harmonic Solutions Clean Power Drive Solution to Harmonic Distortion UTILITY GRID UTILITY SWITCH YARD IN THE FACILITY IEEE-519 POINT OF COMMON COUPLING POWER PLANT GENERATION TRANSMISSION MEDIUM VOLTAGE
More information1C.6.1 Voltage Disturbances
2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope The purpose of this document is to state typical levels of voltage disturbances, which may be encountered by customers
More informationFluke 40/41 Power Harmonics Analysers
Data Pack A Issued March 2002 232-4752 Fluke 40/41 Power Harmonics Analysers This data sheet refers to the Fluke 40 and Fluke 41 Power Harmonics Analysers. RS stock no. Description 215-9621 Fluke 41B power
More informationABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives
ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives 2 TECHNICAL GUIDE NO. 6 GUIDE TO HARMONICS WITH AC DRIVES Guide to harmonics This guide is part of ABB s technical guide series, describing
More informationCASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant
CASE STUDY Implementation of Ford Motor Company SA Silverton Plant 1 SCENARIO Ford Motor Company is a global automotive and mobility company based in Dearborn, Michigan. Ford Motor Company of Southern
More informationEffects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More informationHarmonic Requirements
Chapter 1 Harmonic Requirements 1.1 INTRODUCTION Placing limits upon the effects that nonlinear loads may produce on users of electric power requires definition of system and equipment parameters. The
More informationCHAPTER 4 HARMONICS AND POWER FACTOR
4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried
More informationAnalysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 36-41 Analysis, Modeling and Simulation of Dynamic Voltage
More informationLINEATOR. Advanced Universal Harmonic Filter
R International Inc. LINEATOR Patented Revolutionary New Reactor esign Advanced Universal Harmonic Filter Wide Spectrum Harmonic Filter for treatment of all harmonics generated by 3-phase diode or thyristor
More informationInternational Journal of Research Available at
Multipulse Ac Dc Converters With Reduced Magntetics Feeding Vector Controlled Induction Motor Drives For Improving The Power Quality At The Point of Common Coupling M. Akhila 1 Dr.Samalla Krishna 2 Mr.S.Srikanth
More informationTuningintobetter power quality
Technology Review Third harmonic filters Tuningintobetter power quality Jouko Jaakkola Your PC screen flickers, stops flickering, starts again... Irritating to be sure, and perhaps the first visible sign
More informationPower Quality Notes 2-1 (MT)
Power Quality Notes 2-1 (MT) Marc Thompson, Ph.D. Senior Managing Engineer Exponent 21 Strathmore Road Natick, MA 01760 Alex Kusko, Sc.D, P.E. Vice President Exponent 21 Strathmore Road Natick, MA 01760
More informationSECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)
ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX
More informationPOWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:
POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION
More informationHarmonics Elimination Using Shunt Active Filter
Harmonics Elimination Using Shunt Active Filter Satyendra Gupta Assistant Professor, Department of Electrical Engineering, Shri Ramswaroop Memorial College of Engineering and Management, Lucknow, India.
More informationLecture Note. DC-AC PWM Inverters. Prepared by Dr. Oday A Ahmed Website: https://odayahmeduot.wordpress.com
Lecture Note 10 DC-AC PWM Inverters Prepared by Dr. Oday A Ahmed Website: https://odayahmeduot.wordpress.com Email: 30205@uotechnology.edu.iq Scan QR DC-AC PWM Inverters Inverters are AC converters used
More informationHarmonics Reduction using 4-Leg Shunt Active Power Filters
Harmonics Reduction using 4-Leg Shunt Active Power Filters K Srinivas Assistant Professor & Department of EEE & JNTUH CEJ Telangana, India. Abstract Harmonics in power system are caused by highly non-linear
More informationZENER ELECTRIC PTY LTD
ACN 00 595 428 APPLICATION NOTE: IM 0002 Revision -, June 996 Effective: 24/06/96 Topic: Mains Harmonic Disturbance and Variable Speed AC-Drives Introduction Most common industrial variable speed drives
More informationRoadmap For Power Quality Standards Development
Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel
More informationAGN 026 Harmonic Voltage Distortion
Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 026 Harmonic Voltage Distortion Comment; The critical level of acceptable harmonic voltage distortion % is set
More informationInstallation Manual. Passive Harmonic Filters. ECOsine Economy Line & ECOsine Economy Line LV
Passive Harmonic Filters ECOsine Economy Line & ECOsine Economy Line LV Schaffner Group Nordstrasse 11 4542 Luterbach Switzerland T +41 32 681 66 26 F+ 41 32 681 66 30 www.schaffner.com 210/50 FN3416 (50Hz)
More informationMatrix Technology for next generation Variable Speed Electric Motor Control
Matrix Technology for next generation Variable Speed Electric Motor Control First.Why do we need variable speed control of electric motors? Soft starting of electric motor Multiple starts and stops without
More informationAn Introduction to Power Quality
1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger
More informationFrequently Asked Questions (FAQs) MV1000 Drive
QUESTION 1. What is a conventional PWM Inverter? 2. What is a medium voltage inverter? 3. Are all MV inverters Voltage Source (VSI) design? 4. What is a Current Source Inverter (CSI)? 5. What output power
More information