PowerMonitor 5000 Family Advanced Metering Functionality

Size: px
Start display at page:

Download "PowerMonitor 5000 Family Advanced Metering Functionality"

Transcription

1 PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation. This new family of power monitors provides advanced technology, new functionality, and market leading capabilities in response time and accuracy. The PowerMonitor 5000 family provides three levels of functionality: the M5, M6, and M8. The 5000 M5 is the base model and provides an extensive range of basic metering functions. The 5000 M6 and 5000 M8 add additional metering and power quality capabilities. Rockwell publication 1426-WP001, PowerMonitor 5000 The Next Generation, discusses the new, underlying technologies in the PowerMonitor 5000 M5 and compares it to the technology in the PowerMonitor 3000 M5. This publication focuses on the base functionality in the 5000 M5 and how the 5000 M6 expands the metering and power quality capabilities. PowerMonitor 5000 M5 Metering Functions The PowerMonitor 5000 M5 provides the following metering functions: Frequency Phase rotation Voltage, per phase and average, line-to-line and line-to-neutral Voltage, neutral-to-ground Current, per phase and average Current, neutral or ground Power/energy/demand (real, reactive, and apparent), meets class 0.2% accuracy for both ANSI C12.20 and EN Power factor, true and displacement Symmetrical component analysis values for both voltage and current Voltage and current unbalance Crest factor THD for both voltage and current K-factor Direct connect to 690V AC Data Logs (add logs supported) ADD (definition of increased volume for logs)

2 2 PowerMonitor 5000 Family Advanced Metering Functionality The 5000 M5 metering functions are updated every line cycle. The fast, accurate readings are excellent for monitoring power system conditions, monitoring energy usage, and controlling industrial manufacturing systems based on the measured electrical data. In addition to the real-time data, there are also numerous logs available to provide historical information. With the PowerMonitor 5000 M5, you can configure up to 10 setpoints to identify when a measured parameter goes above or below a set threshold. Whenever a setpoint is activated, the event time and the measured parameters pertinent to the event are recorded in a log. The setpoint capability transitions a status bit and can be used to actuate a relay output for control purposes or to identify an abnormal condition. In addition to the user-configurable setpoints, the 5000 M5 provides status bits that identify the occurrence of a voltage sag or swell condition. The PowerMonitor 5000 uses an internal clock to time-stamp the metered values, the occurrence of a setpoint event, and all data log entries. To improve consistency between clocks in multiple power monitors or with the utility, the clock can be sourced by an SNTP time source. For the ultimate in clock synchronization, the PowerMonitor 5000 can use the IEEE 1588 precision time protocol over Ethernet. This provides very precise synchronization among all of the participating meters. There are two time elements to consider when evaluating time protocol; relative time accuracy and absolute time accuracy. Relative accuracy is the time error between different devices on the network. Absolute accuracy is the time error between a device on the network and a precision reference clock such as a GPS clock. The IEEE 1588 precision time protocol lets devices on the network determine the highest quality clock available and to use that clock to source time to all participating devices. A PowerMonitor 5000 can be used as the clock source if absolute accuracy is not required. Excellent relative time accuracy between devices on a properly designed network results by using the IEEE 1588 protocol. When synchronization is required between geographically separate meters or with the utility, absolute accuracy depends on source clock quality. A GPS clock source with IEEE 1588 capability provides very precise time to the power monitors on the network for excellent relative accuracy and absolute accuracy. If neither relative nor absolute time accuracy is required, use the PowerMonitor 5000 local clock. PowerMonitor 5000 M6 Overview The PowerMonitor 5000 M6 retains all functionality of the 5000 M5 plus the following: Additional setpoint capability User configurable voltage sag/swell settings A power quality log that details detected sag/swell events, oscillography, and harmonic analysis IEEE 519 pass/fail capability Ability to synchronize detected events between multiple power monitors If a user has a PowerMonitor 5000 M5 and wants the additional functionality of the 5000 M6, the M5 can be field upgraded to a M6 by purchasing a firmware upgrade.

3 PowerMonitor 5000 Family Advanced Metering Functionality 3 PowerMonitor 5000 M6 New Setpoint Capabilities The 5000 M6 improves how to identify and capture power system issues by increasing the number of configurable setpoints from 10 to 20 so more conditions are identified and more control options are provided. The 20 setpoints in the M6 includes two new types of setpoints, relative setpoints and logical setpoints. Relative setpoints are similar to standard setpoints except for the definition of the reference value. A fixed reference value is specified when a standard setpoint is defined. For example, a setpoint in a 480 VRMS system can be defined to activate when the measured voltage is less than 90% or 432 VRMS. However, the nominal utility-supplied voltage level can vary by the time of day due to power system loading changes. If you wish to identify a reduction to 90% of the actual supplied voltage, then a fixed reference voltage cannot provide the intended result; a relative setpoint must be used. In this example, a rolling average of the utility-supplied voltage is computed over a sliding interval with user configured duration. The rolling average value is now used as the reference value for the setpoint. If the rolling average of the actual supplied voltage falls to 460 VRMS the 90% value now becomes 414 VRMS. The choice between a fixed setpoint and a relative setpoint gives you the ability to identify when the system hits a critical value or to identify when an unexpected change in the system occurs. The PowerMonitor 5000 M6 also sets logical setpoints, which use the results of other user configured standard or relative setpoints as inputs. The configuration uses one level of logic with up to four inputs. The logic supports AND, NAND, OR, NOR, XOR, and XNOR logic functions. The output of the logic function is a setpoint result that can be used in the same manner as other setpoint results. Logical setpoints allow users to create a more complex condition for creating a setpoint action. Power Quality Phenomena per IEEE 1159 The PowerMonitor 5000 M5 provides a considerable amount of metering data so you can monitor the operating condition of their facility s power distribution system and thus manage their energy costs and consumption. To further increase the efficiency and robustness of the power system and the reliability of the control systems connected to it, monitor the system should also be monitored for power quality issues. A good reference for defining and categorizing power quality phenomena is IEEE , IEEE Recommended Practice for Monitoring Electric Power Quality. This document categorizes power quality events and conditions into seven different types with various sub-types where appropriate. The main categories are: Transients Root-mean-square (RMS) variations (short duration or long duration) Imbalance Waveform distortion Voltage fluctuation Power frequency variation A transient is a very short event with a typical duration between 5 micro-seconds and 50 milliseconds. Transients are usually characterized by either rise time or frequency, and they are either impulsive or oscillatory. Transients are typically the result of lightning strikes, system switching events, fault conditions, or intermittent connections.

4 4 PowerMonitor 5000 Family Advanced Metering Functionality Short duration RMS variations are events characterized by voltage magnitude changes between 10 percent and 180 percent of their nominal value. Changes that result in a voltage less than normal are defined as sags and changes that result in a voltage greater than normal are defined as swells. Typical duration is between one-half cycle and one minute. Voltage sags in a power system can be caused by a variety of conditions such as: a fault to ground or another phase either directly or through some impedance, circuit breaker/re-closer operation, a blown fuse, the energization of a large load, the removal of power factor correction capacitors, an overloaded conductor, or a poor connection. Voltage sags that result in a level less than 10 percent of normal are referred to as interruptions. Voltage swell events are typically the result of a fault to ground or another phase either directly or through some impedance, a blown fuse, the de-energization of a large load, the addition of power factor correction capacitors, or a poor connection. Voltage level changes that have similar magnitude changes but last longer than one minute are referred to as sustained interruptions, over-voltages, or under-voltages. In addition to these power quality issues, IEEE 1159 also defines steady state power quality concerns. The presence of an unbalance condition, voltage or current, is one of these concerns. This condition is only defined for three-phase systems and occurs when the voltage magnitudes and phase angles for each of the phases are not equal. The imbalance percentages represent the ratio of the negative sequence component to the positive sequence component as derived through symmetrical component analysis. Voltage and current imbalance are usually the result of uneven distribution of single-phase loads on a three-phase system or a blown fuse. Imbalance conditions adversely affect AC induction motors by producing excess heat in the rotor winding and causing premature failure, by creating unwanted torque oscillations causing possible motor bearing failure, and a reduction in full-load torque capability. Imbalance conditions also create excess current in the neutral conductor of a three-phase wye system. Waveform distortion is comprised of any DC offset that can be present, such as harmonics or inter-harmonics, line notching, and broadband noise. DC offset is a concern because it results in magnetic saturation and unwanted heating of motors and transformers. The causes of DC offset are half-wave rectification and geomagnetic interference. Harmonic AC voltages or currents have a frequency that is an integer multiple of the fundamental frequency. Harmonic currents are caused by non-linear loads on the power system. These are typically variable frequency drives, switched-mode power supplies, or other power electronic switching devices. Harmonic voltages result from harmonic currents flowing through system impedances. The effects of the harmonic current can be transferred to other parts of the power distribution system and the loads connected to it by the resulting harmonic voltage. Inter-harmonics are voltages or currents at frequencies that are not integer multiples of the fundamental frequency. Inter-harmonics are caused by static frequency converters, cyclo-converters, induction furnaces, arc furnaces, and arc welders. Both harmonics and inter-harmonics result in the overheating of conductors, power factor correction capacitors, AC induction motors, chokes, and transformers. Extra care must be exercised when power factor correction capacitors are present. The interaction of the system inductance, capacitance, and one of the frequency components can create a resonant condition with uncontrolled voltage and current oscillations that can damage equipment and shut down the power distribution system. The presence of harmonics and/or inter-harmonics can also disrupt communications and control information. An additional voltage waveform distortion issue is line-notching. Notching occurs due to line commutation of SCRs used in three-phase to DC converters. When the current through the SCR commutates to zero, there is a short instant of time where a line-to-line short occurs. The depth and duration of the notch is a function of the actual commutation time and the system impedance. The Total Harmonic Distortion (THD) calculation is one method used to detect the presence of line notching. However, this is not completely reliable because the harmonics in the system can be created by other

5 PowerMonitor 5000 Family Advanced Metering Functionality 5 The PowerMonitor 5000 M6 expands on the 5000 M5 capability by addressing the most common power quality events identified by IEEE factors besides notching. Line notching is also easily identified by inspection of the time domain waveform. Voltage fluctuation (also known as flicker ) is either systematic or random changes in voltage magnitude, which are typically in the range of ± 5% of the fundamental magnitude and occur within a frequency range that goes from about two-thirds of the fundamental frequency to just over DC. Then the voltage waveform usually appears as a modulated fundamental frequency similar to an AM radio signal. Analogous to harmonic voltage distortion, voltage fluctuations are caused by the resulting voltage drop from load current passing through the system impedance. Any load that has significant current variation can cause voltage fluctuation to occur. The voltage fluctuation is the actual electromagnetic phenomena. Voltage fluctuation of this magnitude is of little concern to the operation of the power system. However, the fluctuation can cause variation in the light output of lamps energized by the power system. When the variation occurs at an appropriate level and frequency, the variation in light output becomes perceptible and irritating to people. It is this perceptible variation in light output that is called flicker. When the flicker occurs at the right frequency, it can induce seizures in some individuals. Because the variation of the light intensity is the real item of concern, voltage fluctuation is only defined for the typical lighting circuit voltage of 120V or 230V AC. The most common cause of voltage fluctuation is arc furnaces. Analysis of the voltage fluctuation involves computing a human perceptibility index to indicate the level of human sensitivity. The actual computation of the index is a fairly complicated procedure that models the sensitivity of the human eye to how the light output varies with voltage fluctuation. System power frequency is set by the rotational speed of the generators supplying the system. As the load on the system changes, small variation in generator speed can occur, which is power frequency variation. These instantaneous changes occur constantly but any changes that exceed the established limits are usually caused by faults on the utility power transmission system, a significant generation source going off-line, or a large block of loads being disconnected from the system. Significant frequency variation is rare in today s interconnected power grid. Power frequency variations are more common when a power distribution system is supplied by local generation that is not connected to the grid (islanded). New PowerMonitor 5000 M6 Power Quality Functions The PowerMonitor 5000 M5 provides an alarm bit for when a voltage sag or voltage swell occurs. The threshold is fixed at 90 % of configured nominal voltage for sag and 110% for swell. When one of these events occurs, the associated alarm bit is set and maintains for 90 seconds after the system voltage has returned to normal. No other data is available regarding the event. The 5000 M6 model expands on this capability by addressing the most common power quality events identified by IEEE The 5000 M6 provides five configurable threshold values for voltage sags and four values for voltage swells. The following are recorded in the Power Quality Log when a sag or swell is detected: The event time The event duration The configured threshold The minimum sag value or the maximum swell value

6 6 PowerMonitor 5000 Family Advanced Metering Functionality The additional data helps you to more fully understand the event that affected the power system and if any action is needed to minimize the effect of a similar event in the future. The data also provides sufficient information to classify the event per the IEEE 1159 recommended practice discussed above. The PowerMonitor 5000 can implement the IEEE 1588 Precision Time Protocol over its EtherNet I/P network connection. With an appropriately designed network, the metering results from multiple meters can be precisely aligned in time. This capability lets you determine a very precise sequence of events to see how a power quality event propagates through the power distribution system. The meters can be in a local facility or they can be dispersed across multiple geographic locations. For dispersed meters GPS satellite receivers are used to supply the time clock. The ability to provide precisely aligned measurements is further enhanced by a unique feature of the PowerMonitor 5000 M6. The monitors can be configured to alert other monitors in the system whenever a power quality event is triggered. Upon receipt of the alert the other monitors use the embedded time stamp to capture their local conditions at that point in time. The data is stored in each monitor s power quality log and waveform capture log even if the local magnitude of the event was not sufficient to activate the locally configured trigger. This ensures that when an event occurs, a complete system picture is captured and an enhanced view of system performance is obtained. The parameters recorded during a power quality event are useful for quantifying, categorizing and analyzing the event. However, a visual image of the waveforms before, during, and after the event provides valuable additional information. The waveform shape and its relation to the other waveforms at a particular device and across the power distribution system provides additional diagnostic information to help you analyze an event to determine what caused it and how to prevent it in the future. When a short or long duration RMS voltage variation occurs or when a manual waveform capture command is issued, the PowerMonitor 5000 M6 automatically records the waveforms for the three phase current inputs, the neutral or ground current input, the three phase voltages, and the neutral to ground voltage. The number of cycles captured before and after the event is user configurable. The complete duration of the event is recorded unless the detected event lasts longer than one minute. In that case, it is considered a steady-state condition and the waveform can stop recording. However, the end of the event can still be recorded in the power quality log. A waveform record can consist of multiple events. For example, a sag event where the voltage decreased to 90% of nominal triggers a power quality event and starts a waveform capture. Before the event ends, a second sag event occurs where the voltage decreased to 80% of nominal. The second sag is considered to be part of the same event and the waveform capture can contain both events. Whenever a waveform capture is in process, it can be extended to include subsequent events as long as the subsequent events occur before completion of the post-event capture or the one minute limit has not been reached, whichever occurs first. In addition to short or long duration RMS voltage variations, a waveform record can also be trigger by receiving an alert from another PowerMonitor 5000 in the system. This capability is used to obtain a system wide waveform capture from every monitor in the system, regardless of whether or not a trigger threshold occurred at every location, when an event occurs at one or more locations in the distribution system. To take advantage of this capability, the Precision Time Protocol mentioned earlier must be configured and operating.

7 PowerMonitor 5000 Family Advanced Metering Functionality 7 The PowerMonitor 5000 is capable of recording a large number of waveforms. The exact number of waveforms varies based on the cumulative duration of the events recorded. Additionally, when Rockwell Automation s FactoryTalk EnergyMetrix software is used to configure and extract data from the monitors, it automatically detects when there are waveform records available and download them from the monitors. This lets individual monitors maximize their waveform capture capabilities and create virtual infinite storage ability. Factory Talk EnergyMetrix software acquires all waveform information from different monitors, properly align the waveforms, and provide a unified display of them. The software can also be used to create various types of reports, such as monthly/annual consumption or power quality reports. The PowerMonitor 5000 M6 also measures the harmonic content of the voltage and current inputs up through the 63rd harmonic. This measurement is computed and updated every line cycle. The measurement data provides both the magnitude and angle for each of the Percent of Fundamental Harmonic Number harmonics, the total harmonic distortion (THD), and the power flow at each harmonic. This lets you analyze the harmonic content to determine what harmonics are present and whether or not they are of sufficient magnitude to cause issues in your power distribution system. If action is warranted, you can install filters or other mitigating technologies to reduce the problematic harmonics and then verify the effectiveness of the solution. The harmonic information is also used to measure compliance to the requirements of IEEE 519, Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems. The intent of IEEE 519 is to provide recommended limits for the level of harmonic current injection due to loads at your facility and to provide recommended limits for the level of harmonic content present in the voltage supplied by the utility. The measurement of these two quantities is to be made at the point of common coupling (PCC) between the utility and you. The PCC is usually defined as the location in the power distribution system where the utility meters are connected. IEEE 519 is not intended to be applied to individual loads or groups of loads in your facility. Rather, IEEE 519 provides limits to the total amount of harmonic content and to the magnitude of individual harmonics. There are different limits for short term and long term intervals. When properly configured, the PowerMonitor 5000 uses the measured harmonics to provide a pass/fail indication for the limits in IEEE 519. The monitor also provides detailed information so you can precisely determine the limits that are being exceeded.

8 PowerMonitor 5000 M8 Overview When available, the PowerMonitor 5000 M8 includes all functionality of the M5 and M6 models, and also implements metering and power quality capabilities as defined in EN , EN , EN , and EN These new capabilities provide a standardized method for measuring and reporting system harmonics as well as measuring both inter-harmonics and sub-harmonics in the power system. The 5000 M8 also measures and reports system voltage fluctuation (flicker). It can also detect and capture sub-cycle transient events. Allen-Bradley, EnergyMatrix, FactoryTalk, LISTEN. THINK. SOLVE., PowerMonitor, Rockwell, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication 1426-WP002A-EN-P October 2013 Supersedes Publication XXX-XXXXXX-XX-X Month 201X Copyright 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in the U.S.A.

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Power Quality and Circuit Imbalances 2015 Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Summary of IEEE 1159 Terms Category Types Typical Duration

More information

1C.6.1 Voltage Disturbances

1C.6.1 Voltage Disturbances 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope The purpose of this document is to state typical levels of voltage disturbances, which may be encountered by customers

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

An Introduction to Power Quality

An Introduction to Power Quality 1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 9 POWER QUALITY Power quality (PQ) problem = any problem that causes

More information

Fundamentals of Power Quality

Fundamentals of Power Quality NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»

More information

PQ Monitoring Standards

PQ Monitoring Standards Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality

More information

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection

More information

A Guide to Power Quality Testing

A Guide to Power Quality Testing A Guide to Power Quality Testing Table of Contents What is power quality?... 3 Power quality phenomenon... 3 Under-voltage... 3 Over-voltage... 3 Voltage dips (sags) and swells... 4 Voltage dips (sags)...

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

QUESTION BANK PART - A

QUESTION BANK PART - A QUESTION BANK SUBJECT: EE6005-Power Quality SEM / YEAR: VII SEMESTER / ACADEMIC YEAR 08-09 UNIT I - INTRODUCTION TO POWER QUALITY Terms and definitions: Overloading - under voltage - over voltage. Concepts

More information

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014

More information

Power Quality Analysers

Power Quality Analysers Power Quality Analysers Review of Power Quality Indicators and Introduction to Power Analysers ZEDFLO Australia 6-Mar-2011 www.zedflo.com.au Power Quality Indicators Review of main indicators of electrical

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality

Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality Deeksha Bansal 1 Sanjeev Kumar Ojha 2 Abstract This paper shows the modelling and simulation procedure for power quality improvement

More information

Power Quality in Metering

Power Quality in Metering Power Quality in Metering Ming T. Cheng Directory of Asian Operations 10737 Lexington Drive Knoxville, TN 37932 Phone: (865) 218.5885 PQsynergy2012 www.powermetrix.com Focus of this Presentation How power

More information

Introduction to Harmonics and Power Quality

Introduction to Harmonics and Power Quality NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»

More information

Southern Company Power Quality Policy

Southern Company Power Quality Policy Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...

More information

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS 66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic

More information

Design and Development of Protective Circuit against Voltage Disturbances

Design and Development of Protective Circuit against Voltage Disturbances Design and Development of Protective Circuit against Voltage Disturbances Shashidhar Kasthala 1, Krishnapriya 2, Rajitha Saka 3 1,2 Facultyof ECE, Indian Naval Academy, Ezhimala, Kerala 3 Assistant Professor

More information

UNIT-4 POWER QUALITY MONITORING

UNIT-4 POWER QUALITY MONITORING UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and

More information

Harmonic Distortion Evaluations

Harmonic Distortion Evaluations Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI OVERVIEW In the present business climate, companies are under constant pressure to increase profitability by increasing productivity, maximizing

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453 www.ijecs.in International Journal Of Engineering And Computer Science ISSN:2319-7242 Volume 3 Issue 6 June, 2014 Page No. 6453-6457 Role of Fault Current Limiter in Power System Network Poornima G P.1,

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP The BEST Group THE BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP -Winter Lecture Series HARMONICS Presented by: Syed Khundmir T Department of Electrical Engineering University at Buffalo khundmir@buffalo.edu

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 BACKGROUND The increased use of non-linear loads and the occurrence of fault on the power system have resulted in deterioration in the quality of power supplied to the customers.

More information

1C.4.1 Harmonic Distortion

1C.4.1 Harmonic Distortion 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well

More information

EFFICIENT POWER QUALITY: AN APPROACH TO ENERGY CONSERVATION

EFFICIENT POWER QUALITY: AN APPROACH TO ENERGY CONSERVATION EFFICIENT POWER QUALITY: AN APPROACH TO ENERGY CONSERVATION Nirmal Singh 1, Manish Kumar Jain 2 Neeru Goyal 3, Prashant Kumar Tayal 4 1,4 Faculty,Department of Electrical Engg., Dr.K.N. Modi University,

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

p. 1 p. 6 p. 22 p. 46 p. 58

p. 1 p. 6 p. 22 p. 46 p. 58 Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for

More information

Unit V. Power Quality Monitoring

Unit V. Power Quality Monitoring .. Unit V Power Quality Monitoring Monitoring Considerations monitoring and diagnostic techniques for various power quality problems modeling of power quality problems by mathematical simulation tools

More information

POWER QUALITY REPORT

POWER QUALITY REPORT Power Quality Research Lab., I-7, Wyb. Wyspiaoskiego 27, 50-370 Wrocław, Poland phone +48713202626, fax +48713202006, email: zbigniew.leonowicz@pwr.wroc.pl Facility: XXX POWER QUALITY REPORT Start Monitoring:

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) 7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series

More information

Power Quality Monitoring and Power Metering Tutorial

Power Quality Monitoring and Power Metering Tutorial Power Quality Monitoring and Power Metering Tutorial Power generation and transmission today are accomplished using three phase alternatingcurrent. To understand electrical power quality monitoring and

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU

STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU Department of Electrical Engineering National Institute of Technology, Rourkela May 2015 STUDY OF UNIFIED POWER

More information

Literature Review for Shunt Active Power Filters

Literature Review for Shunt Active Power Filters Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller

More information

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS 24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 97 RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS Pengfei WEI Yonghai XU Yapen WU Chenyi

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

The seven types of power problems

The seven types of power problems Computing & Software The seven types of power problems by Joseph Seymour and Terry Horsley, APC, USA Many of the mysteries of equipment failure, downtime, software and data corruption are the result of

More information

Improve Power Factor and Reduce the Harmonics Distortion of the System

Improve Power Factor and Reduce the Harmonics Distortion of the System Research Journal of Engineering Sciences ISSN 2278 9472 Improve Power Factor and Reduce the Harmonics Distortion of the System Abstract Jain Sandesh, Thakur Shivendra Singh and Phulambrikar S.P. Electrical

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Understanding Harmonics

Understanding Harmonics Understanding Harmonics Terry Gaiser Sensus What Are Harmonics? 1 » What is Power Quality?» Power quality is the degree to which both the utilization and delivery of electric power affects the performance

More information

Power System Stability. Course Notes PART-1

Power System Stability. Course Notes PART-1 PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed

More information

T-68 Protecting Your Equipment through Power Quality Solutions

T-68 Protecting Your Equipment through Power Quality Solutions T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. 2 Agenda What

More information

E N G I N E E R I N G M A N U A L

E N G I N E E R I N G M A N U A L 1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn

More information

Power Quality Measurements Essential Theory

Power Quality Measurements Essential Theory Power Quality Measurements Essential Theory Course No: E04-035 Credit: 4 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877)

More information

HARMONICS CAUSES AND EFFECTS

HARMONICS CAUSES AND EFFECTS HARMONICS CAUSES AND EFFECTS What is Harmonics? Harmonics is defined as the content of the signal whose frequency is an integral multiple of the system frequency of the fundamentals. Harmonics current

More information

ULTRA RAPID POWER QUALITY ANALYZER

ULTRA RAPID POWER QUALITY ANALYZER ULTRA RAPID POWER QUALITY ANALYZER Ultra rapid (cycle by cycle) advanced electrical network analysis Complete network harmonics analysis, up to 63 rd harmonic High visibility, 5 graphic LCD screen with

More information

VALLIAMMAI ENGINEERING COLLEGE

VALLIAMMAI ENGINEERING COLLEGE VALLIAMMAI ENGINEERING COLLEGE SRM Nagar, Kattankulathur 60 0. DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK VII SEMESTER EE6005 Power Quality Regulation 0 Academic Year 07 8 Prepared

More information

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES MATH H. J. BOLLEN IRENE YU-HUA GU IEEE PRESS SERIES I 0N POWER ENGINEERING IEEE PRESS SERIES ON POWER ENGINEERING MOHAMED E. EL-HAWARY, SERIES EDITOR IEEE

More information

Mitigation of Voltage Sag/Swell Using UPQC

Mitigation of Voltage Sag/Swell Using UPQC Mitigation of Voltage Sag/Swell Using UPQC 1 Rajat Patel, 2 Prof.Maulik A. Chaudhari 1 PG Scholar, 2 Assistant Professor Electrical Department, Government engineering college, Bhuj Gujarat Technological

More information

UNDERSTANDING POWER QUALITY

UNDERSTANDING POWER QUALITY Technical Note No. 1 June 1998 UNDERSTANDING POWER QUALITY This Technical Note describes the range of problems, what causes them, what they affect and what could be done to manage them. Integral Energy,

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

POWER QUALITY MONITORING - PLANT INVESTIGATIONS Technical Note No. 5 January 2002 POWER QUALITY MONITORING - PLANT INVESTIGATIONS This Technical Note discusses power quality monitoring, what features are required in a power quality monitor and how it

More information

Power Quality Disturbaces Clasification And Automatic Detection Using Wavelet And ANN Techniques

Power Quality Disturbaces Clasification And Automatic Detection Using Wavelet And ANN Techniques International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 13, Issue 6 (June 2017), PP.61-67 Power Quality Disturbaces Clasification And Automatic

More information

Emicon Engineering Consultants L.L.C.

Emicon Engineering Consultants L.L.C. Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com

More information

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017 Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

Power Analysis Summary

Power Analysis Summary Power Analysis Summary Introduction This is a summary of the power conditions measured with these setup parameters: Measurement File: C:\Users\fhealy\Documents\Fluke\Power Analyze\Core 2 Recording.odn

More information

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Research Journal of Engineering Sciences ISSN 2278 9472 Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Abstract Srishti Verma * and Anupama Huddar Electrical Engineering

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric

More information

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN Eugenio PEREA*, Eduardo ZABALA*, J. Emilio RODRÍGUEZ*, Asier GIL DE MURO*, Hugo GAGO * * * Fundación LABEIN,

More information

Harmonic Filters for Single Phase Equipment

Harmonic Filters for Single Phase Equipment POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics

More information

EN50160 Individual Report Summary

EN50160 Individual Report Summary EN50160 Individual Report Summary Power Frequency (x.1) Supply Voltage Variations (x.3.x) Rapid Voltage Changes (x.4.1) Flicker (x.4.2) Supply Voltage Dips (x.5) Short Interruption of Supply Voltage (x.6)

More information

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring The first Real-Time Protection and Automation platform that can be adapted to a wide variety of applications. While

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 19 1 Today Flicker Power quality and reliability benchmarking

More information

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM Abstract Efficient operation of the electrical system of any facility is essential to controlling operational costs while maximizing

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Agilent 6800 Series AC Power Source/Analyzer

Agilent 6800 Series AC Power Source/Analyzer Agilent 6800 Series AC Power Source/Analyzer Product Note Using the Agilent Technologies 6800 Series AC Power Source/Analyzers for Generation and Measurement Applications: Simulating AC Line Sub-Cycle

More information

CHAPTER 4 HARMONICS AND POWER FACTOR

CHAPTER 4 HARMONICS AND POWER FACTOR 4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried

More information

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation Variable Frequency Drive Packages with Harmonic Mitigation Low Harmonic Drive Packages Engineered by Rockwell Automation What Do I Need to know About Harmonics? What are Harmonics? Harmonics are deviations

More information

PQube 3 Specifications

PQube 3 Specifications PQube 3 Specifications Reference conditions for factory tests: 19~25 C, 10%~70% RH MAINS VOLTAGE MEASURING CHANNELS Measurement Channels Power Configuration/ Range of Nominal Input Voltage 3 Line to Neutral,

More information

Energy Explorer PROFESSIONAL POWER & HARMONICS ANALYSER

Energy Explorer PROFESSIONAL POWER & HARMONICS ANALYSER 1 Energy Explorer PORTABLE POWER ANALYSERS DESCRIPTION PROFESSIONAL POWER & HARMONICS ANALYSER ENERGY EXPLORER is an advanced Power Analyser, designed for use by electricians, plant engineers and energy

More information

Reliability and Power Quality Indices for Premium Power Contracts

Reliability and Power Quality Indices for Premium Power Contracts Mark McGranaghan Daniel Brooks Electrotek Concepts, Inc. Phone 423-470-9222, Fax 423-470-9223, email markm@electrotek.com 408 North Cedar Bluff Road, Suite 500 Knoxville, Tennessee 37923 Abstract Deregulation

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality

The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality J. O. Estima A. J. Marques Cardoso University of Coimbra, FCTUC/IT Department of Electrical

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

BED INTERCONNECTION TECHNICAL REQUIREMENTS

BED INTERCONNECTION TECHNICAL REQUIREMENTS BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2

More information

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg Coupling modes Véronique Beauvois, Ir. 2015-2016 General problem in EMC = a trilogy Parameters Amplitude Spectrum Source (disturbing) propagation Coupling modes Victim (disturbed) lightning electrostatic

More information

Power Quality and Digital Protection Relays

Power Quality and Digital Protection Relays Power Quality and Digital Protection Relays I. Zamora 1, A.J. Mazón 2, V. Valverde, E. Torres, A. Dyśko (*) Department of Electrical Engineering - University of the Basque Country Alda. Urquijo s/n, 48013

More information

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks 2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution

More information

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p. Preface p. xv Acknowledgements p. xix Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p. 6 Power Quality Monitoring p. 7 Power

More information

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO Krasimir Marinov Ivanov, Technical University of Gabrovo, Gabrovo, BULGARIA Georgi Tsonev

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

Sizing Generators for Leading Power Factor

Sizing Generators for Leading Power Factor Sizing Generators for Leading Power Factor Allen Windhorn Kato Engineering 24 February, 2014 Generator Operation with a Leading Power Factor Generators operating with a leading power factor may experience

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

ABB n.v. Power Quality Products, October 2014

ABB n.v. Power Quality Products, October 2014 ABB n.v. Power Quality Products, October 2014 Power Quality Harmonic Basics Problems and solutions March 19, 2015 Slide 1 828m high 160 floors in total Total 113 PQF in this tower, 12000A PQFS 45M IP30

More information

Power Quality Overview

Power Quality Overview Power Quality Overview James Brackett P.E. Colorado Springs Utility, GE, Retired What I will present today Introduction and thank you PQ overview Cause of PQ problems How Smart Grid, DER, VVAR and AMI

More information

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 86 CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 5.1 INTRODUCTION Distribution systems face severe power quality problems like current unbalance, current harmonics, and voltage unbalance,

More information

Generation and Load Interconnection Standard

Generation and Load Interconnection Standard Generation and Load Interconnection Standard Rev. 0A DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5

More information