BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP
|
|
- Suzan Lawson
- 5 years ago
- Views:
Transcription
1 The BEST Group THE BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP -Winter Lecture Series HARMONICS Presented by: Syed Khundmir T Department of Electrical Engineering University at Buffalo khundmir@buffalo.edu Prime reference: Electrical Power Systems Quality By Roger C. Dugan, Mark F. McGranaghan, Surya Santoso, H. Wayne Beaty
2 Harmonic Indices Total Harmonic Distortion (THD): It is the potential heating value of the harmonics relative to the fundamental of the quantity. Total Demand Distortion (TDD): It is the potential heating value of the harmonics relative to the peak demand load current.
3 Locating Harmonic Sources
4 Effect of Harmonic Distortion Impact on Capacitors: 1. Problems involving harmonics often show up at capacitors banks first. 2. A capacitor bank experiences high distortion during resonance. 3. The fundamental full load current for a capacitor bank is determined from
5
6 Impact on Transformers Harmonic distortion of current and voltage will contribute significantly to additional heating. Designers often put more cooling ducts in the transformers to accommodate higher frequencies. The harmonic currents increase rms current in a transformer resulting in increased conductor losses. Eddy current losses increase with the square of frequency of the current and thus it is a very important component of transformer losses for harmonic heating.
7 Impact on Motors Harmonic voltage distortion at the motor terminals is translated into harmonic fluxes within the motor. Harmonic fluxes do not contribute significantly to motor torque, but rotate at a frequency different than the rotor synchronous frequency, basically inducing high-frequency currents in the rotor. Decreased efficiency along with heating, vibration, and high-pitched noises are indicators of voltage distortion. Excessive heating problems begin when the voltage distortion reaches 8 to 10 percent and higher. Such distortion should be corrected for long motor life.
8 Impact on Telecommunications Harmonic currents flowing on the utility distribution system or within an end-user facility can create interference in communication circuits sharing a common path. Triplen harmonics are especially troublesome in four-wire systems because they are in phase in all conductors of a three-phase circuit and, therefore, add directly in the neutral circuit, which has the greatest exposure with the communications circuit. The figure in the next slide illustrates coupling from the neutral of an overhead distribution line by induction:
9
10 Impact on Energy and Demand Metering Electrical utility companies usually measure energy consumption in two quantities: The total cumulative energy consumed and the maximum power used for a given period. Thus, there are two charges in any given billing period: Energy charges and Demand charges. Both energy and demand charges are measured using Watthour and demand meters. Harmonic currents from nonlinear loads can impact the accuracy of watthour and demand meters adversely.
11 Contd Conventional magnetic disk watthour meters tend to have a negative error at harmonic frequencies. This error increases with frequency. In general, nonlinear loads tend to inject harmonic power back onto the supply system and linear loads absorb harmonic power due to the distortion in the voltage. While the energy meter should be sufficiently accurate given that the voltage has low distortion, the demand metering could have substantial error.
12 Harmonic Distortion Evaluations End users: For individual end users, IEEE standard limits the level of harmonic current injection at the point of common coupling (PCC). This is the quantity end users have control over. The utility: Since the harmonic voltage distortion on the utility system arises from the interaction between distorted load currents and the utility system impedance, the utility is mainly responsible for limiting the voltage distortion at the Point of Common Coupling (PCC)/ For systems below 69kV, the THD should be less than 5%. Thus, in principle, end users and utilities share responsibility for limiting harmonic current injections and voltage distortion at the PCC.
13 Contd The measurements should be taken continuously over a sufficient period of time so that time variations of harmonic distortions can be accurately represented. The minimum measurement period is usually 1 week since this provides a representative loading cycle for most industrial and commercial loads.
14 Concept of Point of Common Coupling Evaluations of harmonic distortion are usually performed at a point between the end user or customer and the utility system where another customer can be served. This point is known as the point of common coupling. This point can be located at either the primary or secondary side of the service transformer depending on whether or not multiple customers are supplied from the transformer.
15
16 Harmonic Evaluations on the utility system Harmonic evaluations on the utility system involve procedures to determine the acceptability of the voltage distortion for all customers.
17 Contd The two important components for limiting voltage distortion levels on the overall utility system: 1. Harmonic currents injected from individual end users on the supply must be limited. 2. Harmonic current frequencies should not be in resonance with the system resonance frequency. It can result in unacceptable levels of voltage distortion at some system locations.
18 Principles of Controlling Harmonics Common causes of harmonic distortion: 1. The source of harmonic currents is too great. 2. The path in which current flow is too long, resulting in either highvoltage distortion or telephone interference. 3. The response of the system magnifies one or more harmonics to a greater degree than can be tolerated.
19 Contd When a problem occurs, the basic options for controlling harmonics are: 1. Reduce the harmonic currents produced by the load. 2. Add filters to the siphon the harmonic currents off the system, block the currents from entering the system, or supply the harmonic currents locally. These options are briefly explained in the next slides:
20 Reducing harmonic currents in loads There is often little that can be done with existing load equipment to significantly reduce the amount of harmonic current it is producing unless it is being mis-operated. While an overexcited transformer can be brought back into normal operation by lowering the applied voltage to the correct range, arcing devices and most electronic power converters are locked into their designed characteristics. Delta-connected transformers can block the flow of triplen harmonics from the line whereas zigzag and grounding transformers can shunt the triplens off the line.
21 Filtering The shunt filter works by short-circuiting harmonics currents as close to the source of distortion as practical. This keeps the current out of the supply system. This is the most common type of filtering applied because of economics and because it also tends to correct the load power factor as well as remove the harmonic current. Another approach is to apply a series filter that blocks the harmonic currents. It offers a high impedance to the harmonic current.
22 Controlling harmonics on utility distribution feeders The feeder banks should not be placed wherever they are needed without concern about harmonics. The usual strategy is to first attempt a solution by moving the offending bank or changing the capacitor size or neutral connection. Some harmonic problems associated with feeder capacitor banks are due to increasing the triplen harmonics in the neutral circuit of the feeder. These problems on distribution feeders often exists only at light loads. The voltage rises, causing the distribution transformers to produce more harmonic currents. Harmonic flow studies should always be performed when large capacitor banks are installed in distribution substations since the magnification by resonance can be severe.
23 In End User facilities When harmonic problems arise in an end user facility, the first step is to determine if the main cause is resonance with the capacitors in the facility. The solution can be just replacing the current capacitor size. In other cases, there will be so many capacitors switched at random with loads that it will be impossible to avoid resonant conditions. Filtering will be necessary. When magnitude of harmonic currents injected by loads is excessive, industrial users should also investigate means of reducing harmonics by using different transformer connections and line chokes.
24 Conclusion Thus harmonics are significantly important part of any system study and should be kept in mind when building a new facility or adding a new capacitor in any system.
Effects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More informationPOWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics
POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics
More informationHarmonic Distortion Evaluations
Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion
More informationFAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS
The BEST Group THE BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP -Winter Lecture Series FAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS Presented by: Syed Khundmir T Department of Electrical Engineering
More informationPrinciples for Controlling Harmonics
Principles for Controlling Harmonics Harmonic distortion is present to some degree on all power systems. Fundamentally, one needs to control harmonics only when they become a problem. There are three common
More informationDo Capacitor Switching Transients Still Cause Problems?
Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution
More informationCHAPTER 4 HARMONICS AND POWER FACTOR
4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried
More informationHarmonic control devices. ECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)
More informationPOWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION
POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014
More informationNew Methods to Mitigate Distribution System Harmonics
Alberta Power Industry Consortium 214 Power & Energy Innovation Forum New Methods to Mitigate Distribution System Harmonics By Wilsun Xu Power Disturbance & Signaling Research Lab November 5, 214 Outline
More informationPowerMonitor 5000 Family Advanced Metering Functionality
PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation.
More information22.0 Harmonics in Industrial Power Systems
1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a
More informationPower Factor & Harmonics
Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics
More informationHarmonics White Paper
Harmonics White Paper New Breakthrough In PWM Drives Technology Reduces Input Line Harmonics Without the Use of Filtering Devices Harmonic Distortion Damages Equipment and Creates a Host of Other Problems
More informationFluke 40/41 Power Harmonics Analysers
Data Pack A Issued March 2002 232-4752 Fluke 40/41 Power Harmonics Analysers This data sheet refers to the Fluke 40 and Fluke 41 Power Harmonics Analysers. RS stock no. Description 215-9621 Fluke 41B power
More informationNJWA - Harmonics and Drives Proper System Design
Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives
More informationPRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.
1 PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. DEFINATIONS Working /Active Power: Normally measured in kilowatts (kw). It does the "work" for the system--providing the motion, torque,
More informationA PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits
CS 36 HOSP 14 36 Abstract A leading hospital in southern India faced chronic problems in terms of humming noise in capacitor bank, its failure, high temperature in transformer, and disturbances on the
More informationAnalysis of Harmonic Distortion in Non-linear Loads
Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna
More informationVoltage and Current Waveforms Enhancement using Harmonic Filters
Voltage and Current Waveforms Enhancement using Harmonic Filters Rajeb Ibsaim rabsaim@yahoo.com, Azzawia University, Libya Amer Daeri ibnjubair1@yahoo.co.uk Azzawia University, Libya Abstract The demand
More information1C.4.1 Harmonic Distortion
2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well
More informationHarmonic Filters for Single Phase Equipment
POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics
More informationLiterature Review for Shunt Active Power Filters
Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller
More informationHarmonic control devices
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)
More informationINTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION
International Journal of Electrical, Electronics and Data Communication, ISSN: 23284 Volume, Issue-4, April14 INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION 1 V.S.VENKATESAN, 2 P.CHANDHRA
More informationPOWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:
POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION
More informationWorld Journal of Engineering Research and Technology WJERT
wjert, 2017, Vol. 3, Issue 4, 120-128 Original Article ISSN 2454-695X Vimalakeerthy. WJERT www.wjert.org SJIF Impact Factor: 4.326 HARMONICS ELIMINATION IN ISOLATED POWER SYSTEM USING COMPENSATORS Dr.
More informationPeteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1
Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS December 14, 2011 Slide 1 Agenda Harmonics: What they are? Where do they come from? Why bother? Regulations How to detect? How to avoid? Summary
More informationHarmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions
Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE - 519 Solutions Harmonics Tutorial 1 Power Conversion Equipment can save energy and control motors, heaters,
More informationARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services
ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion
More informationModule 1. Introduction. Version 2 EE IIT, Kharagpur
Module 1 Introduction Lesson 1 Introducing the Course on Basic Electrical Contents 1 Introducing the course (Lesson-1) 4 Introduction... 4 Module-1 Introduction... 4 Module-2 D.C. circuits.. 4 Module-3
More informationLoad Isolation Transformers
4 Non-Linear Load Isolation Transformers Section Special winding techniques minimize eddy current losses. A double sized neutral handles excessive neutral currents. UL Listed for K Factor Loads 4, 13 &
More informationHarmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution
Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution Agenda I. Harmonic Basics II.Harmonic Mitigation Solutions III.Case Study 2 Harmonic
More informationGENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW
GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945
More informationEconomical Solutions to Meet Harmonic Distortion Limits[4]
Economical Solutions to Meet Harmonic Distortion Limits[4] Abstract: The widespread adoption of variable frequency drive technology is allowing electricity to be utilized more efficiently throughout most
More informationUnit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21
Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive
More informationPreface...x Chapter 1 Electrical Fundamentals
Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5
More informationPower Quality Analysis in Power System with Non Linear Load
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 10, Number 1 (2017), pp. 33-45 International Research Publication House http://www.irphouse.com Power Quality Analysis in Power System
More informationImprove Power Factor and Reduce the Harmonics Distortion of the System
Research Journal of Engineering Sciences ISSN 2278 9472 Improve Power Factor and Reduce the Harmonics Distortion of the System Abstract Jain Sandesh, Thakur Shivendra Singh and Phulambrikar S.P. Electrical
More informationEmicon Engineering Consultants L.L.C.
Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com
More informationPOWER QUALITY AND SAFETY
POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION
More informationGENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW
GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW Electric Utility Contact Information DTE Energy Interconnection Coordinator One Energy Plaza, SB
More informationHARMONICS CAUSES AND EFFECTS
HARMONICS CAUSES AND EFFECTS What is Harmonics? Harmonics is defined as the content of the signal whose frequency is an integral multiple of the system frequency of the fundamentals. Harmonics current
More informationINTRODUCTION TO POWER QUALITY
CHAPTER 1 INTRODUCTION TO POWER QUALITY 1.1 INTRODUCTION This chapter reviews the power quality definition, standards, causes and effects of harmonic distortion in a power system. 1.2 DEFINITION OF ELECTRIC
More informationOPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY
OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY D. M. Soomro and M. M. Almelian Department of Electrical Power Engineering, Faculty of Electrical and Electronic
More informationISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer
ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering
More informationHarmonic Filters and Reactors
Harmonic Filters and Reactors Harmonics are invisible but costly If one looks up the meaning of harmonics in any one of several technical dictionaries, it is normally defined as being A sinusoidal component
More informationHarmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.
Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics
More informationThyristorised Automatic Power Factor
Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor
More informationSouthern Company Power Quality Policy
Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...
More informationECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 22 1 Today Homework 5 questions Homework 6 discussion More on
More informationUse only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at
Reviewed: Sergey Kryuchkov Distribution Engineering Scott Merriman Distribution Standards Valentina Dabic Distribution Planning Warren Quan Distribution Operations, FVO Raj Solanki Distribution Engineering
More information3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.
MAIN TOPICS DISCUSSED Electric Rates Electrical system utilization ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K Power quality Harmonics Power factor (Cos phi) improvement Section K - 2 ELECTRIC
More informationHarmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits
WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationSection 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services
Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality
More informationPOWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC
CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee
More informationPOWER FACTOR CORRECTION AND ITS PITFALLS
Technical Note No. May 1999 POWER FACTOR CORRECTION AND ITS PITFALLS This Technical Note considers power factor correction as applied by large customers and the possible consequences when power factor
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationGeneral Description & Features Selection Charts Definition of Terms... 42
SECTION NON-LINEAR LOAD ISOLATION TRANSFORMERS Special winding techniques minimize eddy current losses. A double sized neutral handles excessive neutral currents. UL Listed for K Factor Loads 4, 1 & 20.
More informationLow Pass Harmonic Filters
Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power
More informationAlternators Reactance for Nonlinear Loads
Alternators Reactance for Nonlinear Loads Allen Windhorn. P.E. 26 July, 2013 Introduction Widespread invocation of IEEE Std 519 on systems powered by generators, together with increased use of equipment
More informationHarmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions
Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers
More informationTHE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY
by Cesar Chavez, Engineering Manager, Arteche / Inelap, and John Houdek, President, Allied Industrial Marketing, Inc. Abstract: Industrial facility harmonic distortion problems can surface in many different
More informationGuide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics
Reactive Power and Harmonic Compensation Guide to Harmonics POWER QUALITY The Basics of Harmonics All business types, commercial, industrial, government and energy/utility have a concern with power quality.
More informationNew power tools provide quality and efficiency By
Typical Delta-wye transformer New power tools provide quality and efficiency By Steve Terry For quite some time, it has been well understood that phase-control SCR dimming systems used in the entertainment
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationPlacement Paper For Electrical
Placement Paper For Electrical Q.1 The two windings of a transformer is (A) conductively linked. (B) inductively linked. (C) not linked at all. (D) electrically linked. Ans : B Q.2 A salient pole synchronous
More informationHarmonics Reduction using 4-Leg Shunt Active Power Filters
Harmonics Reduction using 4-Leg Shunt Active Power Filters K Srinivas Assistant Professor & Department of EEE & JNTUH CEJ Telangana, India. Abstract Harmonics in power system are caused by highly non-linear
More informationGenerator Advanced Concepts
Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves
More information2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives
.0 Volume 6 Solid-State Control CA0800007E March 05 www.eaton.com V6-T-47 .0 Adjustable Frequency Drives Overview What Are Harmonics? Take a perfect wave with a fundamental frequency of 60 Hz, which is
More informationPresents. Harmonics Years
Presents Harmonics What is a Harmonic? A harmonic is the term used for current flow on your facilities power system at frequencies other than 60Hertz. Harmonic Problems Include: Harmonic Problems
More informationZENER ELECTRIC PTY LTD
ACN 00 595 428 APPLICATION NOTE: IM 0002 Revision -, June 996 Effective: 24/06/96 Topic: Mains Harmonic Disturbance and Variable Speed AC-Drives Introduction Most common industrial variable speed drives
More informationControl of Shunt Active Power Filter for Improvement of Power Quality
Available Online at www.ijcsmc.com International Journal of Computer Science and Mobile Computing A Monthly Journal of Computer Science and Information Technology ISSN 232 88X IMPACT FACTOR: 6.17 IJCSMC,
More informationHarmonic Requirements
Chapter 1 Harmonic Requirements 1.1 INTRODUCTION Placing limits upon the effects that nonlinear loads may produce on users of electric power requires definition of system and equipment parameters. The
More informationElectrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants
Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants Sherif M. Ismael Electrical Engineering Division, Engineering for the Petroleum and Process
More informationPicture perfect. Electromagnetic simulations of transformers
38 ABB review 3 13 Picture perfect Electromagnetic simulations of transformers Daniel Szary, Janusz Duc, Bertrand Poulin, Dietrich Bonmann, Göran Eriksson, Thorsten Steinmetz, Abdolhamid Shoory Power transformers
More informationPQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement
PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to
More informationHARMONICS ANALYSIS USING SEQUENTIAL-TIME SIMULATION FOR ADDRESSING SMART GRID CHALLENGES
HARMONICS ANALYSIS USING SEQUENTIAL-TIME SIMULATION FOR ADDRESSING SMART GRID CHALLENGES Davis MONTENEGRO Roger DUGAN Gustavo RAMOS Universidad de los Andes Colombia EPRI U.S.A. Universidad de los Andes
More informationPerformance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System
Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System Engr.Kavitha Vasantha 1 Lecturer, BSIE, College of Engineering, Salmabad, Kingdom of Bahrain 1 Abstract: As end
More informationGMD Impacts on Generators
Walling Energy Systems Consulting, LLC GMD Impacts on Generators Reigh Walling 1 CME interacts with earth magnetic field Large solar flare - Coronal Mass Ejection (CME) Protons and electrons in solar wind
More informationUnderstanding Harmonics
Understanding Harmonics Terry Gaiser Sensus What Are Harmonics? 1 » What is Power Quality?» Power quality is the degree to which both the utilization and delivery of electric power affects the performance
More informationSYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
More informationDISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS
DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS Le Tang, Jeff Lamoree, Mark McGranaghan Members, IEEE Electrotek Concepts, Inc. Knoxville, Tennessee Abstract - Several papers have
More informationIMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)
IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR) Hadi Suyono 1, Lauhil Mahfudz Hayusman 2 and Moch. Dhofir 1 1 Department of Electrical Engineering, Brawijaya University, Malang,
More informationPower System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur
Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur Lecture - 10 Transmission Line Steady State Operation Voltage Control (Contd.) Welcome
More informationMAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS. J. Stones*, S. Perera*, V. Gosbell* and N. Browne**
ABSTRACT MAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS J. Stones*, S. Perera*, V. Gosbell* and N. Browne** *School of Electrical, Computer and Telecommunications Engineering University of Wollongong
More informationInternational Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD
Scientific Journal of Impact (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 04, April -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 ANALYSIS AND
More informationPrepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA
ATCO Electric Hangingstone Substation HARMONIC STUDY Prepared By Pierre Archambault, PEng Power Survey International Inc. 8025 Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA Rev.: 6 March 2007 TABLE OF
More informationFundamentals of Power Quality
NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»
More informationUtility System Lightning Protection
Utility System Lightning Protection Many power quality problems stem from lightning. Not only can the high-voltage impulses damage load equipment, but the temporary fault that follows a lightning strike
More informationPower Quality and Power Factor Correction
Power Quality and Power Factor Correction Introduction Since most loads in modern electrical distribution systems are inductive, there is an ongoing interest in improving power factor. The low power factor
More informationElectrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018
Electrical Theory Power Principles and Phase Angle PJM State & Member Training Dept. PJM 2018 Objectives At the end of this presentation the learner will be able to: Identify the characteristics of Sine
More informationPower Quality Monitoring and Power Metering Tutorial
Power Quality Monitoring and Power Metering Tutorial Power generation and transmission today are accomplished using three phase alternatingcurrent. To understand electrical power quality monitoring and
More informationHarmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017
Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates
More informationApplication of Tuned Passive Filter for Industrial Six-Pulse Rectifier with R-L Load Viralkumar A. Rana 1 Keyur Rana 2 Atul Talati 3
IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 02, 2014 ISSN (online): 2321-0613 Application of Tuned Passive Filter for Industrial Six-Pulse Rectifier with R-L Load
More informationAPQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)
APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute
More informationMulti-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7
White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,
More informationHARMONIC MITIGATIONCASE STUDY
HARMONIC MITIGATIONCASE STUDY CNCE AND NCE INSTALLATION AT BROADCASTING STUDIO Concerned about video noise detected on some of its studio equipment, E! Entertainment Television (ETV), commissioned a study
More informationImpact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation
Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation R. S. Al Abri, M. H. Albadi, M. H. Al Abri, U. K. Al Rasbi, M. H. Al Hasni, S. M. Al Shidi Abstract This paper presents an analysis
More information