POWER QUALITY REPORT

Size: px
Start display at page:

Download "POWER QUALITY REPORT"

Transcription

1 Power Quality Research Lab., I-7, Wyb. Wyspiaoskiego 27, Wrocław, Poland phone , fax , Facility: XXX POWER QUALITY REPORT Start Monitoring: XX Stop Monitoring: XX Received Data: XX Report Generated: XX Survey Type: Equipment Installed and Operating Project Manager: Zbigniew Leonowicz, PhD Eng. Collaborators: XXX SUMMARY OF REPORT: Power quality assessment showed no significant issues. Voltages over upper limit were detected mainly in L2 of the 110 kv distribution network.

2 Acceptable Needs Follow-Up Problem Not Applicable Power Quality Report Category Summary Analysis GENERATOR (10,5 kv) Harmonic current factor Values within the limits Symmetrical components of currents Ratio of the negativesequence component of current to the rated current Voltage and frequency limits during operation Voltage dependence of the generator frequency Values within the limits Values within the limits Values within the limits Values within the limits Events No events recorded Power frequency assessment Long-term flicker severity DISTRIBUTION NETWORK (110 kv) Values within the limits Values within the limits Unbalance Values within the limits Harmonics Values within the limits THD Values within the limits Voltage Values within the limits Events Overvoltages, Voltage over RMS upper limit mainly in L2, see page 25. Page 2

3 CONTENT 1. MEASUREMENTS RELATED TO AC GENERATOR MEASURING EQUIPMENT AC GENERATOR PARAMETERS HARMONIC CURRENT FACTOR (HCF) SYMMETRICAL COMPONENTS OF CURRENTS RATIO OF THE NEGATIVE-SEQUENCE COMPONENT OF CURRENT TO THE RATED CURRENT (I 2 /I N ) VOLTAGE AND FREQUENCY VARIATIONS DURING OPERATION VOLTAGE DEPENDENCE OF THE GENERATOR FREQUENCY SUMMARY OF THE REPORT MEASUREMENTS RELATED TO 110 KV DISTRIBUTION NETWORK MEASURING EQUIPMENT POWER FREQUENCY ASSESSMENT LONG TERM FLICKER SEVERITY VOLTAGE UNBALANCE ASSESSMENT HARMONICS ASSESSMENT SUPPLY VOLTAGE VARIATION EVENTS SUMMARY OF THE REPORT LITERATURE Page 3

4 1. Measurements related to AC generator In this chapter, the power quality (PQ) report contains assessment of set of PQ parameters recorded indirectly at the AC generator (10,5 kv). Recorded values were compared with recommended values. Power quality report includes assessment of : harmonic current factor (HCF) [4] system of currents symmetrical components [4] ratio of the negative-sequence component of current to the rated current [4] voltage and frequency variations during operation [4] voltage dependence of the generator frequency [5] recorded power quality events and transients Measurements were done on the voltage and current transformers terminals in the XXX Localization of the power quality recorder in the generator circuitry presents XX 1.1. Measuring equipment Fluke 1760, Three-Phase Power Quality Recorder Topas, Serial No. Y760588, GPS time synchronization, Class-A compliance AC Generator Parameters Manufacturer: XXX Type: XXX Air cooled turbo generator, apparent power 76 MVA, rated voltage 10,5 kv, current 4205 A, power factor 0,85, speed 3000 rpm. The generator parameters during 1 week assessment time are shown in Table 1-1: Page 4

5 Table 1-1. Generator parameters during the assessment period Parameter min Values Percentile 95% max Active power P [MW] 24,515 62,975 64,291 Reactive power Q [MVAr] 2,604 18,361 22,961 Apparent Power S [MVA] 24,752 64,802 66,782 cosφ 0,934 0,994 0,999 tanφ 0,045 0,110 0,382 Power factor PF 0,964 0,993 0,998 PF is defined as: PF=(P/ S ) (Q h / Q h ) Fig Visualization of the generator s active power in 1 week. (yellow line sum of three phase quantities) Page 5

6 Fig Visualization of the generator s reactive power in 1 week. Fig Visualization of the generator s apparent power in 1 week. Page 6

7 Fig Visualization of the generator s power factor (cosφ) in 1 week. Fig Visualization of the generator s power factor (PF=(P/ S )*(Q h / Q h )) in 1 week. Page 7

8 Fig Localization of the power quality measurements in the generator circuitry Harmonic current factor (HCF) Three-phase a.c. generators shall be suitable for supplying circuits which, when supplied by a system of balanced and sinusoidal voltages result in currents not exceeding a harmonic current factor (HCF) of 5% [4]. The HCF shall be computed by using the following formula: where i n is the ratio of the harmonic current I n to the rated current I N ; n is the order of harmonic; k = 13. Harmonic components are shown in Fig Table 1-2. Assessment of the HCF HCF HCF assessment [%] min 1,01 Percentile 95% 1,69 max 1,83 During 100% of the assessment period the maximum HCF values are within the range of 1,01% 1,83%, all below the limit of 5%. Page 8

9 Fig Visualization of the currents harmonics averaged over 1 week. (in all figures the plots of L1 are blue, L2-red, L3-green) 1.4. Symmetrical components of currents Three-phase a.c. generators shall be suitable for supplying circuits which, when supplied by a system of balanced and sinusoidal voltages result in a system of currents where neither the negative-sequence component nor the zero-sequence component exceed 5% of the positive-sequence component [4]. Currents symmetrical components are shown in Fig. 1.8 and 1.9. Page 9

10 Fig Visualization of currents Zero to Positive sequence ratio. Fig Visualization of currents Negative to Positive sequence ratio. Page 10

11 Table 1-3. Assessment of the negative and zero-sequence components Components ratio assessment min Components ratio [%] Percentile 95% max Zero/Pos 0,43 0,50 0,50 Neg/Pos 0,55 1,11 2,35 During 100% of the assessment period measured values hold in range from 0,43% to 0,50% for zero sequence component and from 0,55% to 2,35% for negative sequence component, all below the limit of 5% Ratio of the negative-sequence component of current to the rated current (I2/IN) Three-phase synchronous machines shall be capable of operating continuously on an unbalanced system in such a way that, with none of the phase currents exceeding the rated current, the ratio of the negative-sequence component of maximum current for continuous operation (I 2 ) to the rated current (I N ) does not exceed the value of 8% for a.c. generators with direct cooled (inner cooled) rotor windings [4]. Table 1-4. Assessment of the I 2 /I N I 2 /I N assessment I 2 /I N [%] I 2 /I N min 0,008 I 2 /I N Percentile 95% 0,152 I 2 /I N max 0,356 Page 11

12 Fig Visualization of currents I 2 /I N ratio. Figure 1.10 and Table 1-4 contains statistical parameters which confirmed that in the investigated case requirements for I 2 /I N are fulfilled. The recorded r.m.s. values hold in range from 0,008% to 0,356% Voltage and frequency variations during operation For a.c. machines rated for use on a power supply of fixed frequency supplied from an a.c. generator (whether local or via a supply network), combinations of voltage variation and frequency variation are classified as being either zone A or zone B, in accordance with Figure 1.11 for generators and synchronous condensers. A machine shall be capable of performing its primary function, continuously within zone A, but need not comply fully with its performance at rated voltage and frequency [4]. Page 12

13 Fig Voltage and frequency limits for generators with plotted limit range of recorded values (red rectangle). Table 1-5. Assessment of voltage and frequency limits Voltage and frequency limits U, f U [p.u.] f [p.u.] min 0,9997 0,9981 Percentile 95% 1,0255 1,0010 max 1,0257 1,0016 Page 13

14 Fig Visualization of voltage variation in 1 week. Fig Visualization of frequency variation in 1 week. Page 14

15 Visualization of the recorded data in Figures 1.12 and and Table 1-5 contain statistical parameters which confirmed that in the investigated case requirements for voltage and frequency limits are fulfilled Voltage dependence of the generator frequency The generating unit should maintain the following relationship between the frequency of the generator and voltage [5] for where f is the change of frequency in p.u. and U g is the change of generator voltage corresponding to the change of frequency, in p.u. Table 1-6. Assessment of voltage dependence on generator frequency U g / f [p.u.] U g / f 10min f 8, U g -5 1, max 0,0196 For measured data, the maximum of numerical approximate gradient showed the point where the change of frequency was the highest ( :00:00), see Table 1-6. Corresponding change of voltage was determined and the ratio U g / f computed at this time point [2]. The requirements are fulfilled Summary of the report Presented in previous section assessment of crucial power quality parameters indicates that: in case of harmonic current factor (HCF), requirements are fulfilled in case of system of currents symmetrical components, requirements are fulfilled in case of the ratio of the negative-sequence component of current to the rated current, requirements are fulfilled in case of voltage and frequency variations during operation, requirements are fulfilled in case of voltage dependence of the generator frequency, requirements are fulfilled Page 15

16 During the assessment period no events were detected (with exception to one generator disconnection from the grid due to causes not relevant to power quality assessment). Page 16

17 2. Measurements related to 110 kv distribution network In this chapter, the power quality (PQ) report contains assessment of set of PQ parameters recorded indirectly at power line of the distribution network (110 kv). Recorded values were compared with recommended values. Power quality report includes assessment of : power frequency long term flicker severity voltage unbalance harmonics recorded power quality events and transients 2.1. Measuring equipment Fluke 1760, Three-Phase Power Quality Recorder Topas, Serial No. UO13379, GPS time synchronization, Class-A compliance. Measurements were done on the voltage and current transformers terminals of transmission line 1 in XXX. Localization of the power quality recorder in the distribution network of the 110 kv line No. 1 presents XX Fig Localization of the power quality measurements in 110 kv distribution network Power frequency assessment The standards [3] and [4] indicate that the nominal frequency of the supply voltage shall be 50 Hz. Under normal operating conditions the mean value of the fundamental frequency measured over 10 s shall be within a range of: for systems with synchronous connection to an interconnected system with the voltage below 220 kv: Page 17

18 50 Hz ± 1 % (i.e. 49,5 Hz... 50,5 Hz) during 99,5 % of a week; 50 Hz + 4 % / - 6 % (i.e. 47 Hz Hz) during 100 % of the week; Fig Visualization of power frequency variation. Table 2-1. Assessment of power frequency variation f Frequency assessment [Hz] f 10s min 49,905 f 10s Percentile 99,5% 50,009 f 10s max 50,109 Visualization of the recorded set of frequency values is shown in Fig Figure 2.2 and Table 1-2 contains the statistical parameters which confirmed that in the investigated case requirements for frequency standards are fulfilled. During 100% of the assessment period frequency values hold in range from 49,905 to 50,109 Hz. Page 18

19 2.3. Long term flicker severity Fig Visualization of long-term flicker severity Table 2-2. Assessment of long-term flicker severity Flicker assessment L1 L2 L3 [-] [-] [-] Plt 2h Percentile 95% 0,73 0,65 0,63 min 0,15 0,16 0,15 max 0,75 0,66 0,64 Visualization of the recorded set of long-term flicker coefficient values is shown in Fig 2.3. The standards indicate that under normal operating conditions, in any period of one week the long term flicker severity caused by voltage fluctuation should be Plt 0,8 for 95 % of the time [5]. Table 2-2 contains the statistical parameters which confirmed that in the investigated case requirements for flicker severity are fulfilled. 95% of the recorded long-term flicker values hold in range from 0,15 to 0,75. Moreover 100% of the recorded values follows by the standard expectation. Page 19

20 2.4. Voltage unbalance assessment Fig Visualization of the voltage unbalance variation Table 2-3. Assessment of unbalance variation Unbalance assessment Neg/Pos [%] Neg/Pos 10min Percentile 95% 0,26 min 0,15 max 0,29 Visualization of the recorded set of unbalance values is shown in Fig The standard [4] indicates that under normal operating conditions, during each period of one week, 95 % of the 10 min mean r.m.s. values of the negative phase sequence component (fundamental) of the supply voltage shall be within the range 0 % to 1 % of the positive phase sequence component (fundamental). Table 2-3 contains statistical parameters which confirm that in the investigated case requirements for unbalance standards are fulfilled. The recorded unbalance coefficient hold in range from 0,15% to 0,29%.(with 95% values not greater than 0,26%). Page 20

21 2.5. Harmonics assessment Table 2-4. Assessment of harmonic variations Harmonic assessment Percentile95% Max Order Limits L1 L2 L3 L1 L2 L3 Nr. [ % ] [ % ] [ % ] [ % ] [ % ] [ % ] [ % ] 2 1,50 0,06 0,06 0,06 0,09 0,09 0,08 3 2,00 0,26 0,30 0,15 0,28 0,33 0,19 4 1,00 0,03 0,02 0,02 0,04 0,03 0,04 5 2,00 0,74 0,66 0,71 0,90 0,89 0,95 6 0,50 0,02 0,02 0,02 0,04 0,03 0,03 7 2,00 0,41 0,39 0,39 0,53 0,48 0,50 8 0,50 0,03 0,02 0,03 0,05 0,05 0,05 9 1,00 0,04 0,04 0,04 0,07 0,07 0, ,50 0,03 0,03 0,03 0,07 0,06 0, ,50 0,14 0,16 0,15 0,18 0,19 0, ,50 0,02 0,02 0,02 0,02 0,02 0, ,50 0,19 0,19 0,19 0,27 0,28 0, ,50 0,02 0,02 0,02 0,03 0,03 0, ,50 0,02 0,02 0,02 0,03 0,03 0, ,50 0,01 0,01 0,01 0,02 0,02 0, ,00 0,10 0,10 0,12 0,13 0,12 0, ,50 0,01 0,01 0,02 0,02 0,03 0, ,00 0,07 0,06 0,06 0,09 0,10 0, ,50 0,01 0,01 0,01 0,02 0,03 0, ,50 0,01 0,01 0,01 0,03 0,03 0, ,50 0,01 0,01 0,01 0,02 0,02 0, ,70 0,07 0,08 0,08 0,11 0,14 0, ,50 0,01 0,01 0,01 0,02 0,03 0, ,70 0,07 0,06 0,07 0,13 0,11 0,13 26* 0,68 27* 0,66 28* 0,65 29* 0,63 0,02 0,02 0,02 0,02 0,02 0,02 30* 0,62 31* 0,60 0,02 0,02 0,02 0,02 0,02 0,02 Page 21

22 32* 0,59 33* 0,58 34* 0,57 35* 0,56 0,02 0,02 0,02 0,02 0,02 0,02 36* 0,55 37* 0,54 0,02 0,02 0,02 0,02 0,02 0,02 38* 0,53 39* 0,52 40* 0,51 41* 0,50 0,02 0,02 0,03 0,02 0,02 0,03 42* 0,50 43* 0,49 0,02 0,03 0,03 0,02 0,03 0,03 44* 0,48 45* 0,48 0,01 0,01 0,02 0,01 0,01 0,02 46* 0,47 47* 0,47 0,02 0,02 0,02 0,02 0,02 0,02 48* 0,46 49* 0,46 0,02 0,01 0,01 0,02 0,01 0,01 50* 0,45 *For harmonics higher than 25 th the formula for the harmonic limit is 0,2+0,5 (25/h) [%] [5]. Fig, 2.5. Visualization of the voltages harmonic spectrum averaged in 1 week. Page 22

23 Table 2-4 contains limits for particular harmonics defined in [5] and statistical parameters of recorded data. Distribution of the harmonics is also visible in Fig, 2.5. Performed measurements has detected no values over the limit. Fig, 2.6. Visualization of THDV variation Table 2-5. Assessment of THDV variation THDVL1 THDVL2 THDVL3 THDV assessment [%] [%] [%] min 0,37 0,38 0,29 THDV Percentile 95% 0,88 0,81 0,83 10min max 0,99 0,99 1,02 Visualization of the recorded set of total harmonics distortion in voltage is shown in Fig. 2-6, [5] indicates THD of the supply voltage (including all harmonics up to the order 40) shall be less than or equal to 3 %. Table 2-5 contains the statistical parameters of THDV which confirmed that in the investigated case requirements are fulfilled, 95% of the recorded THDV coefficient hold in Page 23

24 range from 0,83% to 0,88%, Moreover 100% of the recorded values follow by the standard expectation Supply voltage variation Fig Visualization of supply voltage variation. Table 2-6. Assessment of supply voltage variation U 10min Voltage assesment min Percentile 95% max VL1 VL2 VL3 [V] [V] [V] 67609, , , , , , , , ,00 Visualization of the recorded set of supply voltage values is shown in Fig, 2.7. The [5] indicates that under normal operating conditions: - during each period of one week 95 % of the 10 min mean r.m.s. values of the supply voltage shall be within the range of Un ± 10 %, i.e. in the range 57157, ,38 V. Table 2-6 contains statistical parameters which confirmed that in the investigated case requirements for r.m.s. supply voltage standards are fulfilled, 95% of the recorded r.m.s., Page 24

25 values hold in range from 69407,25 V to 69648,00 V Moreover 100% of the recorded values follows by standard expectation, i.e. are within the range of 50806,82 V 76210,23 V Events During the assessment period the following events were detected: Overvoltages Designation L1 L2 L3 L123-N Number Maximum value [V] Maximum duration 4h 56m 26s 8h 51m 14s 6h 9m 33s 8h 51m 14s Details of recorded events Event Location Detection Date & Time Voltage Swells V L :45:43,71 Voltage Swells V L :45:43,71 Voltage Swells V L :51:22,33 Voltage Swells V L :05:31,08 Voltage Swells V L :18:47,43 Voltage Swells V L :00:50,17 Voltage Swells 3-ph V L123-N :47:40,70 Voltage Swells 3-ph V L123-N :47:40,70 Voltage Swells 3-ph V L123-N :53:02,94 Voltage Swells 3-ph V L123-N :33:09,62 RMS Upper Limit V L :33:09,62 RMS Upper Limit V L :20:18,80 RMS Upper Limit V L :55:21,73 RMS Upper Limit V L :43:38,14 RMS Upper Limit V L :43:38,14 h06 Harmonics V L :15:00,91 h06 Harmonics V L :27:37,11 h06 Harmonics V L :38:24,90 h06 Harmonics V L :05:16,99 Duration 6h 9m 33s 4h 56m 26s 8h 51m 14s 5h 16m 0s 4h 8m 3s 4h 5m 8s 8h 51m 14s 5h 16m 0s 4h 8m 3s 4h 5m 8s 4h 44m 5s 10h 19m 45s 6h 11m 40s 4h 33m 42s 4h 23m 59s Value 6,99e+04 [V] 6,988e+04 [V] 7,014e+04 [V] 7,003e+04 [V] 6,999e+04 [V] 6,991e+04 [V] 7,014e+04 [V] 7,003e+04 [V] 6,999e+04 [V] 6,991e+04 [V] 6,987e+04 [V] 7,012e+04 [V] 7,001e+04 [V] 6,996e+04 [V] 6,989e+04 [V] 200,06ms 0,5343 [%] 200,05ms 0,5235 [%] 199,88ms 0,501 [%] 999,77ms 0,5519 [%] Page 25

26 h06 Harmonics V L :05:16,99 h06 Harmonics V L :05:19,01 h06 Harmonics V L :29:01,27 h06 Harmonics V L :55:14,98 h12 Harmonics V L :44:23,45 199,99ms 0,5788 [%] 1,0002s 0,5491 [%] 200,05ms 0,5054 [%] 200,11ms 0,5294 [%] 199,96ms 0,7392 [%] 2.8. Summary of the report Presented in previous section assessment of crucial power quality parameters indicates that: in case of power frequency, requirements are fulfilled in case of voltage supply, requirements are fulfilled in case of flicker severity, requirements are fulfilled in case of voltage unbalance, requirements are fulfilled in case of THD of the supply voltage, requirements are fulfilled in case of harmonics, requirements are fulfilled Multiple events were detected during the recording time. Closer follow-up require the overvoltages. 3. Literature [1] IEC :2008, Electromagnetic compatibility (EMC): Testing and measurement techniques -Power quality measurement method [2] Bollen M,H,J, Irene Yu-Hua Gu, Signal Processing of Power Quality Disturbances, 2006 The Institute of Electronics and Electrical Engineers, Inc [3] EN 50160: Voltage characteristics of electricity supplied by public distribution networks [4] IEC : Rotating electrical machines: 7 Electrical operating conditions [5] Regulations of the operation and exploitation of the distribution network Page 26

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN Eugenio PEREA*, Eduardo ZABALA*, J. Emilio RODRÍGUEZ*, Asier GIL DE MURO*, Hugo GAGO * * * Fundación LABEIN,

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08 The development of the SA grid code on Power Quality emission Dr. Gerhard Botha 2017/08/08 Overview What is the Grid Code? What is Power Quality? Power Quality Management Principles Differences Challenges

More information

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point 2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION

More information

EN50160 Individual Report Summary

EN50160 Individual Report Summary EN50160 Individual Report Summary Power Frequency (x.1) Supply Voltage Variations (x.3.x) Rapid Voltage Changes (x.4.1) Flicker (x.4.2) Supply Voltage Dips (x.5) Short Interruption of Supply Voltage (x.6)

More information

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax: POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION

More information

Power Analysis Summary

Power Analysis Summary Power Analysis Summary Introduction This is a summary of the power conditions measured with these setup parameters: Measurement File: C:\Users\fhealy\Documents\Fluke\Power Analyze\Core 2 Recording.odn

More information

On the Evaluation of Power Quality Indices in Distribution Systems with Dispersed Generation

On the Evaluation of Power Quality Indices in Distribution Systems with Dispersed Generation European Association for the Development of Renewable Energies, Environment and Power Quality International Conference on Renewable Energies and Power Quality (ICREPQ 09) Valencia (Spain), 1th to 17th

More information

EN50160 Report: Station 28 Puidoux Accepted Week 12 20/03/ /03/2017

EN50160 Report: Station 28 Puidoux Accepted Week 12 20/03/ /03/2017 EN50160 Report: Station 28 Puidoux Accepted 2017 Week 12 20/03/2017 27/03/2017 Date : 28 march 2017 INTRODUCTION This report covers the time period between Monday, March 20, 2017, 12:00:00 to Monday, March

More information

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO Krasimir Marinov Ivanov, Technical University of Gabrovo, Gabrovo, BULGARIA Georgi Tsonev

More information

Grid Converters for Photovoltaic

Grid Converters for Photovoltaic Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information

Power quality report. A Manufacturing Plant

Power quality report. A Manufacturing Plant Power quality report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION... 5 2.1 SITE MONITORED...

More information

PowerMonitor 5000 Family Advanced Metering Functionality

PowerMonitor 5000 Family Advanced Metering Functionality PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation.

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards Indian Journal of Science and Technology, Vol 9(30), DOI: 10.17485/ijst/2016/v9i30/99034, August 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 A Power Quality Survey on a 22 kv Electrical Distribution

More information

The Fluke 6100A. Electrical Power Standard. The most accurate, comprehensive and flexible source of electrical power signals

The Fluke 6100A. Electrical Power Standard. The most accurate, comprehensive and flexible source of electrical power signals The Fluke 6100A Electrical Power Standard The most accurate, comprehensive and flexible source of electrical power signals Measurement validation for electrical power applications The importance of accurate

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA SETTING UP REACTIVE POWER COMPENSATION DEVICES SELECTING A REACTIVE POWER COMPENSATION DEVICE To effectively compensate the

More information

Data Sheet. RISH Master Record %THD

Data Sheet. RISH Master Record %THD Data Sheet %THD Application : measures important electrical parameters & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, active energy

More information

Power Quality Analysers

Power Quality Analysers Power Quality Analysers Review of Power Quality Indicators and Introduction to Power Analysers ZEDFLO Australia 6-Mar-2011 www.zedflo.com.au Power Quality Indicators Review of main indicators of electrical

More information

N100. example of application Ethernet www/ ftp. Ethernet TCP IP RS X MeaSUreMent of power network parameters.

N100. example of application Ethernet www/ ftp. Ethernet TCP IP RS X MeaSUreMent of power network parameters. cat iii Electrical Safety N100 - power network analyzer Measurement of power network parameters in 3 or 4-wire, balanced or unbalanced systems. two-color led display (red, green). Four quadrant energy

More information

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection

More information

Power Quality Analyzer Topas 2000

Power Quality Analyzer Topas 2000 Power Quality Analyzer Topas 2000 Effecting measurement tasks in medium and low voltage networks faster and with a single tool: Complies with IEC 61000-4-30 class A with synchronization to power frequency

More information

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers

More information

A Power Quality Interface for Low and Medium Voltage Smart Grids

A Power Quality Interface for Low and Medium Voltage Smart Grids Technical Data Power Quality Interface for Low and Medium Voltage Smart Grids Model PQI-D smart 1 Wall-mounted housing 1 DIN-Rail housing 1 Panel mounting housing 1. pplication Solving all measurement

More information

Power Quality Report. A Manufacturing Plant

Power Quality Report. A Manufacturing Plant Power Quality Report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant CHK Power Quality Pty Ltd Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION...

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

An Introduction to Power Quality

An Introduction to Power Quality 1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger

More information

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee

More information

MEASUREMENT METHODS OF THE CHARACTERISTICS AND TARGET VALUES OF THE VOLTAGE QUALITY SUPPLIED BY HYDRO-QUEBEC SYSTEM

MEASUREMENT METHODS OF THE CHARACTERISTICS AND TARGET VALUES OF THE VOLTAGE QUALITY SUPPLIED BY HYDRO-QUEBEC SYSTEM MEASREMENT METHODS OF THE CHARACTERISTICS AND TARGET VALES OF THE VOLTAGE QALITY SPPLIED BY HYDRO-QEBEC SYSTEM Report no.: IREQ-99-0 Revision #1 This document is a translated version of the French document

More information

Power Quality of a Battery Energy Storage System (BESS) with Nonlinear Load Gabriel Haines

Power Quality of a Battery Energy Storage System (BESS) with Nonlinear Load Gabriel Haines Power Quality of a Battery Energy Storage System (BESS) with Nonlinear Load Gabriel Haines 18/04/2018 1 INTRODUCTION Power quality is a broad area that describes how well the electrical power system is

More information

Emission on the low voltage grid: measurements in an urban area

Emission on the low voltage grid: measurements in an urban area International Conference on Renewable Energies and Power Quality (ICREPQ 4) Cordoba (Spain), 8 th to th April, 4 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 7-38 X, No., April 4 Emission on

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock

More information

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected

More information

E6500 Power Quality Analyzer

E6500 Power Quality Analyzer E6500 Power Quality Analyzer E6500 power quality analyzer can record and analyze all power quality parameters such as harmonics, voltage, current, frequency, fluctuation, flicker, power and three-phase

More information

new! nd30 - METER OF POWER NETWORk PARAMETERS EXAMPlE OF APPliCATiON MEASUREMENT AND ViSUAliZATiON OF POWER NETWORk PARAMETERS

new! nd30 - METER OF POWER NETWORk PARAMETERS EXAMPlE OF APPliCATiON MEASUREMENT AND ViSUAliZATiON OF POWER NETWORk PARAMETERS new! cat iii Electrical Safety nd30 - METER OF POWER NETWORk PARAMETERS Measurement of power network parameters in 3- or 4-wire balanced and unbalanced systems. Color graphic display: lcd TFT 3,5, 320

More information

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features: Application : RISH Master 3430 measures important electrical parameters in 3 phase and single phase Network & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

POWER QUALITY, LHC EARTHING AND CABLE INSTALLATION

POWER QUALITY, LHC EARTHING AND CABLE INSTALLATION LHC machine EMC Workshop 25 th Nov. 24 POWER QUALITY, LHC EARTHING AND CABLE INSTALLATION 1. Definition of Power Quality and Network Disturbances 2. Statistics 23 3. Harmonics 4. LHC Engineering Specification

More information

VIM Series. 90 & 60 W, Efficient, CV Class 2 LED Drivers ORDERING INFORMATION

VIM Series. 90 & 60 W, Efficient, CV Class 2 LED Drivers ORDERING INFORMATION 060W-12 100W-24 Nominal Input Voltage 90 &, Efficient, CV Class 2 Max. Output Power Nominal Output Voltage Max. Output Current 120 & 277 Vac 12, 24 Vdc 5, 3.75 A Efficiency up to 90% typical Max. Case

More information

Power Converters and Power Quality

Power Converters and Power Quality Power Converters and Power Quality Karsten KAHLE, CERN karsten.kahle@cern.ch, Baden (CH) 2 References EN 50160 (2010) IEC 61000 IEC 61000-2-2 IEC 61000-2-4 IEC 61000-2-12 IEC 61000-3-4 IEC 61000-3-6 IEC

More information

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES MATH H. J. BOLLEN IRENE YU-HUA GU IEEE PRESS SERIES I 0N POWER ENGINEERING IEEE PRESS SERIES ON POWER ENGINEERING MOHAMED E. EL-HAWARY, SERIES EDITOR IEEE

More information

Energy Management Energy Meter GM3D

Energy Management Energy Meter GM3D Energy Management Energy Meter Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Accuracy ±0.5 RDG (current/voltage) Energy meter Instantaneous variables readout: 3 DGT Energies

More information

E6000 E6000. Handheld Power Quality Analyzer. Features. Functions

E6000 E6000. Handheld Power Quality Analyzer. Features. Functions E6000 Handheld Power Quality Analyzer The E6000 Handheld Power Quality and Energy Analyzer offer the best in power quality analysis and introduce, for the first time ever, the ability to monetarily quantify

More information

16B2011B1 EASY HARMONICS USER MANUAL

16B2011B1 EASY HARMONICS USER MANUAL 6B0B Issued on 03/08/09 R.00 English This manual is integrant and essential to the product. Carefully read the instructions contained herein as they provide important hints for use and maintenance safety.

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks 2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution

More information

nd30 EXAMPlE OF APPliCATiON MEASUREMENT AND ViSUAliZATiON OF POWER NETWORk PARAMETERS Ethernet www/ ftp Modbus TCP Modbus RS-485

nd30 EXAMPlE OF APPliCATiON MEASUREMENT AND ViSUAliZATiON OF POWER NETWORk PARAMETERS Ethernet www/ ftp Modbus TCP Modbus RS-485 cat iii Electrical Safety nd30 - METER OF POWER NETWORk PARAMETERS Measurement and recording of 54 power network parameters, including current and voltage harmonics up to 51st, in 1-phase 2-wire or 3-phase

More information

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM]

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM] Feature Suit for LV/ HV voltage system Compact design with all real-time measurement Consist of basic unit and optional modules 10 years back-up of integrated energy data Large LCD, high brightness High

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Fluke Three-Phase Power Quality Recorder Topas. Class-A compliance for the most demanding power quality tests

Fluke Three-Phase Power Quality Recorder Topas. Class-A compliance for the most demanding power quality tests Test Equipment Depot - 800.517.8431-99 Washington Street Melrose, MA 02176 - TestEquipmentDepot.com Fluke 1760 Three-Phase Power Quality Recorder Topas Technical Data Class-A compliance for the most demanding

More information

APPLICATION NOTE STANDARD EN VOLTAGE CHARACTERISTICS OF ELECTRICITY SUPPLIED BY PUBLIC ELECTRICITY NETWORKS

APPLICATION NOTE STANDARD EN VOLTAGE CHARACTERISTICS OF ELECTRICITY SUPPLIED BY PUBLIC ELECTRICITY NETWORKS APPLICATION NOTE STANDARD EN 50160 VOLTAGE CHARACTERISTICS OF ELECTRICITY SUPPLIED BY PUBLIC ELECTRICITY NETWORKS Antoni Klajn, Marta Bątkiewicz-Pantuła March 2013 ECI Available from www.leonardo-energy.org/node/145851

More information

1 In This Document Elspec

1 In This Document Elspec 1. Change to read: 10/12 Continuous Non-Overlapping Cycles. a. changed in doc - if I redo the pdf it will delete all my comments. see 2nd doc attached. mpm 1 In This Document Elspec IN THIS DOCUMENT I.

More information

1 In This Document Elspec

1 In This Document Elspec 1 In This Document Elspec IN THIS DOCUMENT I. Input Characteristics... 3 II. BLACKBOX Web Interface Display... 4 III. Measurement Range, Resolution & Accuracy... 10 IV. Measurement Method... 12 V. General

More information

Southern Company Power Quality Policy

Southern Company Power Quality Policy Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...

More information

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming Energy Management Type WM14 DI version Protection degree (front): IP40 2 digital outputs 16 freely configurable alarms with OR/AD logic linkable with up to 2 digital outputs RS422/485 serial output (MODBUS-RTU),

More information

Centrale de mesure Power Meter PM500 Merlin Gerin

Centrale de mesure Power Meter PM500 Merlin Gerin Notice d'installation et d'utilisation Installation and user manual Centrale de mesure Power Meter PM500 Merlin Gerin 059473_D Introduction and description Package contents c one PM500 power meter with

More information

GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS

GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE ELECTRICITY TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH AFRICA Version 2.9 (July 2016) This document is approved

More information

Contents. Introduction and description Package contents Device identification PM Options... 80

Contents. Introduction and description Package contents Device identification PM Options... 80 Contents 1 Introduction and description Package contents... 77 Device identification... 77 2 Characteristics PM500... 78 Options... 80 3 Installation Front-panel cut-out... 82 Mounting... 82 4 Connections

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Supplement Manual Title: 434-II/435-II/437-II Users Supplement Issue: 5 CD Part Number: 4822 872 3093x Issue Date: 11/16 Print Date: January 2012 Page Count: 5 Revision/Date: 1, 6/12 This supplement

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Research and Trends in Power Quality

Research and Trends in Power Quality Institute of Control and Industrial Electronics Warsaw University of Technology Research and Trends in Power Quality Roman Barlik Institute of Control and Industrial Electronics Warsaw University of Technology

More information

A POWER QUALITY INSTRUMENT FOR HARMONICS INTERHARMONICS AND AMPLITUDE DISTURBANCES MEASUREMENTS

A POWER QUALITY INSTRUMENT FOR HARMONICS INTERHARMONICS AND AMPLITUDE DISTURBANCES MEASUREMENTS Proceedings, XVII IMEKO World Congress, June 7, 003, Dubrovnik, Croatia Proceedings, XVII IMEKO World Congress, June 7, 003, Dubrovnik, Croatia XVII IMEKO World Congress Metrology in the 3rd Millennium

More information

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001 ELECTRICITY ASSOCIATION SERVICES LIMITED 2001 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical,

More information

MID. Energy Management Energy Meter Type EM23 DIN. Product Description. Type Selection. How to order EM23 DIN AV9 3 X O1 PF A EM23 DIN

MID. Energy Management Energy Meter Type EM23 DIN. Product Description. Type Selection. How to order EM23 DIN AV9 3 X O1 PF A EM23 DIN Energy Management Energy Meter Type EM23 DIN Certified according to MID Directive (option PF only): see how to order below Other version available (not certified, option X): see how to order on the next

More information

OPERATING MANUAL POWER QUALITY ANALYZER PQM-707

OPERATING MANUAL POWER QUALITY ANALYZER PQM-707 OPERATING MANUAL POWER QUALITY ANALYZER PQM-707 SONEL S.A. ul. Wokulskiego 11 58-100 Świdnica, Poland Version 1.10 14.03.2017 2 CONTENTS 1 General Information... 7 1.1 Safety... 7 1.2 General characteristics...

More information

PQVO3H Voltage Waveform Distortion Measurement

PQVO3H Voltage Waveform Distortion Measurement 1MRS752336-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice Voltage Waveform Distortion Measurement Contents 1 Introduction... 3 1.1 Features... 3 1.2 Harmonic distortion...

More information

Energy Management Energy Analyzer Type EM210

Energy Management Energy Analyzer Type EM210 Energy Management Energy Analyzer Type EM210 Multi-use housing: for both DIN-rail and panel mounting applications Current inputs AV option: CT 5A Current inputs MV option: current sensor 333 mv (CTV series)

More information

MID. Energy Management Energy Meter Type EM33 DIN. Product Description. How to order EM33 DIN AV3 3 X XS PF. Type Selection EM33 DIN

MID. Energy Management Energy Meter Type EM33 DIN. Product Description. How to order EM33 DIN AV3 3 X XS PF. Type Selection EM33 DIN Energy Management Energy Meter Type EM33 DIN Easy connections management Certified according to MID Directive (option PF only): see how to order below Other version available (not certified, option X):

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 9 POWER QUALITY Power quality (PQ) problem = any problem that causes

More information

C.A Complete electrical network analysis at the tips of your fingers! Power Quality Monitor. Keeping up with the standards

C.A Complete electrical network analysis at the tips of your fingers! Power Quality Monitor. Keeping up with the standards Keeping up with the standards C.A 8352 Power Quality Monitor Complete electrical network analysis at the tips of your fingers! All measurements for complete analysis: powers, harmonics, flicker, symmetry,

More information

E N G I N E E R I N G M A N U A L

E N G I N E E R I N G M A N U A L 1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn

More information

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters Technical Data Sheet Alpha 20 Alpha 20 is a compact multifunction instrument which Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel

More information

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease Fluke 1740 Series Three-Phase Power Quality Loggers Memobox Technical Data Assess power quality and conduct long-term studies with ease Compact and rugged, the Fluke 1740 Series three-phase power quality

More information

nd30pnet - METER Of POwER NETwORk PARAMETERS with profinet EXAMPlE Of APPlICATION MEASUREMENT ANd VISUAlIZATION Of POwER NETwORk PARAMETERS

nd30pnet - METER Of POwER NETwORk PARAMETERS with profinet EXAMPlE Of APPlICATION MEASUREMENT ANd VISUAlIZATION Of POwER NETwORk PARAMETERS nd30pnet tri Measurement of 54 power network parameters, including current and voltage harmonics up to 51st, in 1-phase 2-wire or 3-phase 3 or 4-wire balanced and unbalanced systems. graphical color display:

More information

Power System Stability. Course Notes PART-1

Power System Stability. Course Notes PART-1 PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed

More information

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces IEEE PES Boston Chapter Technical Meeting IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces P1547 Chair David

More information

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana JANUARY 2015 i Table of Content PART A: 1 1 Introduction 1 1.1 Scope 1 1.2 Status 1 1.3 Terms

More information

Monitoring power quality beyond EN and IEC

Monitoring power quality beyond EN and IEC Monitoring power quality beyond EN 50160 and IEC 61000-4-30 by A Broshi and E Kadec, Elspec, Israel The standards currently in place provide minimum requirements, since they want to create a level playing

More information

Harmonic Distortion Evaluations

Harmonic Distortion Evaluations Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion

More information

Version 2.6 October Comments to this document can be forwarded to:

Version 2.6 October Comments to this document can be forwarded to: GRID CONNECTION CODE REQUIREMENTS FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH AFRICA Version 2.6 October 2012 Comments to this document

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase

More information

Jewell DPM Power / Power Factor Size 96/96 BEST IN CLASS

Jewell DPM Power / Power Factor Size 96/96 BEST IN CLASS Application: The Jewell DPM Power 96x96 series measures system active Power (Import/Export), Reactive Power (Import/Export), Apparent Power & Power Factor of Three Phase and Single Phase Network. It has

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

VGM Series. 100 & 60 W, Efficient, CV Class 2 LED Drivers for Signage Applications ORDERING INFORMATION

VGM Series. 100 & 60 W, Efficient, CV Class 2 LED Drivers for Signage Applications ORDERING INFORMATION Nominal Input Voltage Max. Output Power Nominal Output Voltage Max. Output Current 120/277 Vac 12, 24, Vdc 5, 3.92 A Efficiency up to 90% typical Max. Case Temperature 100 C (measured at the hot spot)

More information

Power Quality Evaluation of Electrical Distribution Networks

Power Quality Evaluation of Electrical Distribution Networks Power Quality Evaluation of Electrical Distribution Networks Mohamed Idris S. Abozaed, Suliman Mohamed Elrajoubi Abstract Researches and concerns in power quality gained significant momentum in the field

More information

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at Reviewed: Sergey Kryuchkov Distribution Engineering Scott Merriman Distribution Standards Valentina Dabic Distribution Planning Warren Quan Distribution Operations, FVO Raj Solanki Distribution Engineering

More information

Power Quality Measurements the Importance of Traceable Calibration

Power Quality Measurements the Importance of Traceable Calibration Power Quality Measurements the Importance of Traceable Calibration H.E. van den Brom and D. Hoogenboom VSL Dutch Metrology Institute, Delft, the Netherlands, hvdbrom@vsl.nl Summary: Standardization has

More information

A robust voltage unbalance allocation methodology based on the IEC/TR guidelines

A robust voltage unbalance allocation methodology based on the IEC/TR guidelines University of Wollongong Research Online Faculty of Engineering - Papers (Archive) Faculty of Engineering and Information Sciences 2009 A robust voltage unbalance allocation methodology based on the IEC/TR

More information

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

Technical Data Sheet AMIK 300 / 301

Technical Data Sheet AMIK 300 / 301 USA SINCE 1936 RELIABILITY BEYOND MEASURE Technical Data Sheet AMIK 300 / 301 LISTED File No. E471457 AMIK AMIK 300 is a compact multifunction instrument with touch screen LCD utility which measures important

More information

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks GB Technical data Issue 06/2009 PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks Fault detection Evaluation of voltage quality according to EN50160 and IEC61000-2-2 Fault recorder

More information

Power quality measurements in a singlehouse

Power quality measurements in a singlehouse 24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 2: Power quality and electromagnetic compatibility Power quality measurements in a singlehouse microgrid

More information

PQ Monitoring Standards

PQ Monitoring Standards Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality

More information

Energy Management Energy Meter Type EM21 72R Retro-Fit

Energy Management Energy Meter Type EM21 72R Retro-Fit Energy Management Energy Meter Type EM21 72R Retro-Fit Including 3 miniature split-core current sensors 10mm (90A), 16mm (150A) and 24mm (250A) diameter holes Class A (kwh) according to EN50470-3 Class

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information