Power Quality Measurements the Importance of Traceable Calibration

Size: px
Start display at page:

Download "Power Quality Measurements the Importance of Traceable Calibration"

Transcription

1 Power Quality Measurements the Importance of Traceable Calibration H.E. van den Brom and D. Hoogenboom VSL Dutch Metrology Institute, Delft, the Netherlands, Summary: Standardization has contributed significantly to comparable analysis methods for power quality parameters. However, in order to have undisputable results, the measurement values themselves should also be comparable. This can only be achieved by traceability to international measurement standards. For this reason, at VSL, the Dutch national metrology institute, a fully traceable reference setup was developed for calibration of power quality analyzers. In this paper, we show the calibration results of the critical components of the reference setup, we demonstrate its applicability by test measurements on the public low-voltage supply system for specific parameters, and show its ability to simulate and generate events that can be detected and analyzed by both the equipment under test and the reference setup. Key words: calibration, power quality, reference system, standardization, traceability, harmonics, flicker 1. INTRODUCTION The voltage in the electricity transport and distribution systems is getting more and more disturbed by strongly varying loads and local energy generation such as photovoltaic cells and wind mills. Therefore it becomes increasingly important to monitor the state of the electricity system and detect events such as voltage dips and swells, transients or bursts of harmonics. Too large voltage distortions should be avoided since this negatively affects the correct operation of instrumentation connected to the electricity grid, and even may lead to failures and blackouts. Therefore, the first goal of grid voltage measurements is to monitor whether or not the grid power quality is within the limits set by the relevant standards. A longer term goal is to explain heavy disturbances and even blackouts by post-processing and analyzing data obtained by precise monitoring of the system state and its power quality as a function of time, marked with proper time stamps, during the disturbance. Ultimately, such an analysis should be performed real time in order to prevent these heavy disturbances and blackouts. For system operators this is extremely important in order to avoid claims from customers related to improper or failing power delivery. Furthermore, by remotely monitoring the power quality in for example substations, in case of faults, service engineers can be instructed or advised real-time to solve the problem and for example replace improperly functioning equipment. Typical power quality parameters for electricity grid applications are frequency and magnitude of supply voltage, harmonics, dips, swells, and transients. Power quality is measured by utilities for monitoring purposes to observe and analyze trends and to maintain stable operation of the transport and distribution grid. However, power quality analyzers produced by different manufacturers came up with different results when measuring the same phenomenon. This has led to the introduction of the standard IEC [1]. This standard further restricts the possibilities the manufacturer still has when using the earlier standards IEC [2] on the measurement of harmonics and IEC [3] on the measurement of flicker severity, and extends its applicability to other power quality parameters. Whereas the describes the measurement techniques themselves, the new upcoming standard IEC [4], [5] distinguishes between power quality monitoring devices for specific applications, such as indoor or outdoor, portable or fixed, and general or harsh EMC environment. Here, a general environment means for example power stations, medium and low voltage substations or industrial applications, whereas harsh environments for example are found in high voltage substations, arc furnaces or welding plants. Limits and conditions for power quality analyzers are put on environment, design and construction, type tests, routine tests, verification and recalibration. At present, most high-end power quality analyzers use the IEC when analyzing the data, which has contributed significantly to comparable test methods and, therefore, to comparable results. However, apart from being carried out according to specified methods, the measurement values themselves should also be comparable in order to have undisputable measurement results. This can only be achieved by traceability to the International System of Units (SI) and to international measurement standards by means of calibrations. Traceability in this case means that the result of a calibration can be related to international measurement standards, through an unbroken chain of measurements, all having stated uncertainties. The importance of traceable calibrations has been recognized by transport and distribution system operators, who raise this issue when measurement results give rise to disputes. The upcoming introduction of the IEC 62586, in which uncertainty tests and calculations are described in detail, makes the availability of traceable calibrations of power quality analyzers even more important. For power quality measurements, understanding of the importance of traceability of calibration equipment is not very wide-spread, although the British national metrology institute (NPL) is working on it already for years [6] and transferring their knowledge to other national metrology institutes by means of EU funded research projects. In these European research projects, the focus of the power quality measurements is on the on-site calibration of the power quality of the electricity grid, e.g. in the distribution network or in high-voltage substations. At present, high-precision power quality recorders and analyzers used for on-site measurements have typical uncertainties of around 0.1% in voltage and current for stationary signals, whereas reference power analyzers can 25

2 have significantly lower uncertainties. At VSL, the Dutch national metrology institute, a reference setup has been developed for traceable calibration of power quality analyzers according to IEC , where pre-defined or userdefined test signals can be generated. These pre-defined test signals include waveforms and test parameters relevant for limiting standards like the IEC [7] that puts limits on harmonic current emissions, the IEC [8] on voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, the EN [9] on voltage characteristics of electricity supplied by public distribution systems and the earlier described upcoming IEC In the next sections we will describe the reference setup for calibration of power quality analyzers and its possibilities, the calibration measurements to be performed for the setup to be traceable to the SI, first test measurements on the low-voltage grid to validate the analysis software and the measurement system, and initial validation measurements of the system operating when simulating events Calibration Setup 2. MEASUREMENT SYSTEM To provide traceable power quality signals, we developed a setup for both generation and measurement of the desired signals. As a first step, a single-phase system has been designed, with the possibility to upgrade to a three-phase system at a later stage. The heart of the setup is a highprecision two-input analog-to-digital converter (ADC) and two-output digital-to-analog converter (DAC) combination with a resolution of 24 bits and a sampling frequency up to 200 ks/s. The DACs are used to generate a voltage waveform and a current waveform according to the customer s specification, whereas the ADCs are used to measure the same signals. Figure 1 shows a schematic overview of the setup when calibrating a power quality analyzer. The voltage signal as generated by the first DAC is amplified 25 times using a power amplifier and amplified 10 more times using a voltage transformer. The maximum voltage is in the kv regime, but in practice a nominal value of 115 V or 230 V is used. Fig. 1. Schematic setup used to calibrate power quality analyzers. Details can be found in the text. This voltage is delivered to the voltage input of the power quality analyzer under test. In parallel to the device under test, a 100:1 resistive voltage divider scales the voltage down to voltages that can be measured using the first ADC. The current signal as generated by the second DAC (which is in fact a voltage signal at this stage), is also amplified 25 times using a power amplifier. A 3 W shunt resistor then converts the voltage into a current signal before it is increased to the desired level of 20 A maximum using a current transformer. This current signal is delivered to the current input of the power quality analyzer under test. The signal is fed through a 20 mω shunt resistor that is connected in series, over which the voltage is measured using the second ADC. The DACs, amplifiers and transformers are used only to generate a power quality signal that is to be measured simultaneously by the power quality analyzer under test and the reference system, i.e., the two ADCs, the current shunt and the voltage divider. Traceability of the voltage and current signals is obtained by calibrating the two ADCs, the shunt and the voltage divider at different frequencies between DC and, typically, 5 khz. A 1 pulse-per-second signal is used in combination with a 10 MHz reference signal derived from the atomic clock to set the time stamp of the measurements. This time stamp is necessary to reach the accuracy mentioned in the IEC for the determination of the measurement time intervals. At present, a three-phase power quality analyzer has to be calibrated by three independent single-phase calibrations. This means that, for example, the unbalance between the three phases cannot be investigated. In the near future the setup will be upgraded to a three-phase system Software Analysis The use of a high-accuracy and high-resolution data acquisition system makes us very flexible in the choice of power quality signals to be generated, and in how to analyze them. Software is written in LabView to communicate with the hardware, to generate the signals and to analyze the measurement results in full accordance with the , and All sampled data are stored for further analysis at a later stage. The following features have been included so far: Mains frequency and timing accuracy Voltage calibration at 230 V or 115 V at 50 Hz or 60 Hz as is appropriate, performed using a sinusoidal signal Current calibration and linearity testing in all current ranges up to 20 A, performed using a sinusoidal signal Power accuracy test performed at for example 150 W with appropriate voltage and frequency using a distorted, non-sinusoidal, test signal Steady state harmonic calibration for current or voltage as desired, either user defined or reflecting the limits defined in IEC or EN 50160, for harmonics up to the 100th of the fundamental. If desired, verification tests can be performed, assessing the power quality analyzer ability to correctly report a pass or fail for certain combinations of harmonics. Determination of the total harmonic distortion Calibration of the average harmonic amplitudes when the harmonics are fluctuating [10]. If desired, excursions 26 Electrical Power Quality and Utilization, Journal Vol. XVI, No 1, 2013

3 above the limits under certain conditions can be tested, such as peaks of fluctuating harmonics exceeding the limit by up to 200 % for at most 10 % of the time as long as the average harmonic amplitude still obeys the limit (according to the ) Tests with bursts of harmonics [11] Determination of interharmonic voltage or current Calibration of the relative amplitude change for voltage fluctuations (dips and swells) under user defined conditions Flicker severity measurements with square or sinusoidal modulation, for signals with or without harmonic distortion (according to annex C); instantaneous, short-term and long-term flicker severity Flicker severity measurements with complex modulation, i.e., irregular modulation [12] Temporary power frequency overvoltages, i.e., typical duration of a few power line cycles Transient overvoltages, i.e. typical duration of a few milliseconds Mains signaling. The software is continuously expanded, and other new features can be included if desired. 3. MEASUREMENT RESULTS 3.1. Calibration of the power quality reference system As mentioned before, traceability of the voltage and current measurements is obtained by calibrating the critical components, i.e., the two ADCs, the shunt and the voltage divider at different frequencies. The commercial ADCs used in this setup can be calibrated by a direct comparison to a DC and AC calibrator that is traceable to thermal converter based AC-DC transfer standards and the DC Josephson voltage standard. The shunt is calibrated using AC-DC transfer standards in combination with a DC resistor traceable to the quantum Hall resistance standard. The resistive voltage divider is calibrated as follows. First, the ADC is used to measure the DAC output voltage directly for sinusoidal signals with 10 V amplitude. The result, shown in Fig. 2, is a flat frequency response within 1.5 mv or % of the nominal value of 10 V. This means that the ADC and DAC have the same frequency characteristic. However, since we know the frequency characteristic of the ADC from the calibration with the thermal converters, we know the frequency characteristic of the DAC. We can correct for this frequency behavior if we wish, but at 50 Hz or 60 Hz the difference with the DC value was found to be even less than 0.2 mv or %, which is more than sufficient for the power calibration, whereas the largest differences of % occur at the highest frequencies, where they are also more than sufficient for measurements of, for example, harmonics and transients. As a second step, the DAC output is divided by 100 using the resistive divider before measuring with the same ADC. The result is shown in Fig. 3. As we can see, the divider output decreases with frequency, as we expect for the combination of the 10 kω output resistance in combination with the 100 pf per meter cable capacitance and the 100 pf input capacitance of the ADC (which should both be considered as integral part of the resistive divider!). We measure the 0.1 V amplitude output voltage in the 10 V range because we want to compare it to the result of the bare DAC as shown in Fig. 2. Since one might question the capabilities of the ADC when used below 1 % of the range maximum voltage, we also measured the same signal in the 1 V range, and observed the same behavior, as can also be seen in Fig. 3. Note that if necessary we can add a capacitor in parallel to either the output resistance or the input resistance of the divider to flatten the frequency response, just like an oscilloscope probe that has to be tuned to be able to observe fast transients and steps Test measurements on the low-voltage grid As an important test of the measurement part of the setup including analysis software, measurements have been performed on the low-voltage mains supply in our laboratory. To prevent hazardous situations, an isolation transformer was inserted between the supply voltage and the voltage divider. This isolation transformer has a ratio of 230:100, which means that the rms output voltage is 100 V. This voltage is further divided to 1 V by means of the resistive divider. For this test, we recorded and stored only the voltage data during the measurement period, for the software deals with voltage data and current data in the same way. The analysis is performed afterwards, in accordance with the From Fig. 4 we can see that a typical voltage waveform shows small Fig. 2. Direct ADC measurement of a 10 V sinusoidal voltage signal generated by the DAC as a function of frequency. Fig. 3. Frequency dependence of the output of the 1 MΩ : 10 kω resistive divider (in combination with the cable capacitance and the input capacitance of the ADC) for a 10 V sinusoidal input voltage as measured in the 10 V or 1 V range, respectively, of the ADC. 27

4 Fig. 4. Typical waveform as measured on the mains supply using an isolation transformer with a ratio of 230:100. From these waveforms several power quality parameters have been analyzed (see Figs. 5-7). Fig. 5. Mains frequency as analyzed over subsequent periods of 10 seconds. deviations from a pure sinusoidal wave. Typical results of the analysis of the frequency, the rms value as compared to the first harmonic, and the third, fifth, seventh and eleventh harmonics, respectively, during a certain test period are shown in Figs The frequency is analyzed over subsequent periods of 10 seconds as described in the Small fluctuations of the order of less than 0.1% are observed for this period, as shown in Fig. 5. The absolute value of the frequency of around Hz is well within the ± 1 % from the nominal value of 50 Hz that has been set out in the EN standard. The values of the rms voltage and the first harmonic, calculated for every subsequent period of 10 power line cycles as described in the , are almost identical. As can be seen in Fig. 6, the value of the first harmonic follows the rms value, but it is always a little bit smaller, which is due to the small part of the power that is contained in the higher harmonics. The amplitude of these higher harmonics, also calculated every 10 power line cycles, are indicated in Fig. 7. As we can see, the values of the harmonics are relatively constant over a period of 15 minutes. Furthermore, we observe that the seventh harmonic is larger than the third. Note that the signals described above are measured on a low-voltage distribution grid for a very short period. Measurements over a longer period, for example in a substation or industrial application, might show much higher deviations from sinusoidal behavior Simulation and generation of events As a second important test, events that typically occur in the electricity grid have been simulated. We can program and generate the events mentioned in Section II.B, and measure the corresponding generated signals for analysis. In fact, this test is similar to a real calibration of a power quality analyzer under test (see Fig. 1), but without any power quality analyzer connected. This way, apart from validating the setup for being capable of calibrating a power quality analyzer under test for specific parameters at values used in practice, or at values given in the different standards, we can also test it to correctly detect certain power quality events. As set out in the , for the detection of events, the values of the parameter under test are updated every half power line cycle, even though the value itself reflects the value of the Fig. 6. Rms value of the voltage compared to the first harmonic, both analyzed over subsequent periods of 10 power line cycles. Fig. 7. Harmonic content of the third, fifth, seventh and eleventh harmonics, analyzed over subsequent periods of 10 power line cycles. parameter during a whole cycle. In practice that means that the value is updated after each zero-crossing. As an example of testing the generation, measurement, detection and analysis of events, a series of swells of 100 % overvoltage above the nominal value of 92 V is generated with durations of one power line cycle (0.02 s), two cycles, four cycles, 0.19 s (equivalent to 9.5 power line cycles), 0.89 s, and 2.99 s, followed by a series of dips leaving only 20 % of the voltage with the same durations as for the swells. This series of swells and series of dips is based on a test described in the upcoming IEC The nominal value of the voltage in this functionality test was 92 V because we did not include a transformer to scale the voltage up. Fig. 8 shows the results of the measurement of this sequence of voltage fluctuations. Note that because the 28 Electrical Power Quality and Utilization, Journal Vol. XVI, No 1, 2013

5 quality analyzer. In order to use our reference setup for the calibration, we also need to upgrade the setup to a three-phase system. The results of the on-site grid measurements will be used to improve our setup and make it suitable for more specific electricity grid applications. Furthermore, this way we can disseminate the importance of power quality analyzers to be traceable to international measurement standards for all power quality parameters. REFERENCES Fig. 8. Measurement of simulated dips and swells as generated and measured using the configuration of Fig. 1 (without power quality analyzer under test connected). measurement values are updated every half power line cycle and reflect the rms value during a whole cycle, we observe extra values neighboring the dips and swells at values in between the nominal value and the dip or swell value, at which half of the cycle has the nominal amplitude and the other half has the adjusted amplitude. Hence, as a consequence of the procedure of half cycle updates, for these specific fluctuations we observed that indeed the event log shows durations of the detected dips and swells that are two times half a cycle or 0.02 s too long as compared to the generated signals. 4. SUMMARY, CONCLUSIONS AND FUTURE WORK The introduction of the standard IEC has led to comparable test methods and, therefore, more comparable results in the evaluation of power quality analysers. However, apart from being carried out according to specified methods, the measurement values themselves should also be comparable in order to have undisputable measurement results. This can only be achieved by traceability to the International System of Units (SI) and to international measurement standards by means of calibrations. The upcoming standard IEC 62586, in which uncertainty tests and calculations are described in detail, makes the availability of traceable calibrations of power quality analyzers even more important. Therefore, at VSL, the Dutch national metrology institute, we developed a reference setup for calibration of power quality equipment, fully traceable to SI units. In this paper we showed the results of realizing the SI traceability of our new reference setup by calibrating the components comprising the setup. Furthermore, initial tests on the low-voltage distribution grid show that the analysis of the sampled data is in accordance with the IEC for the power quality parameters that were investigated. As an example, correct event detection was demonstrated for a generated series of simulated dips and swells. The analysis shows that the setup is suitable for performing traceable calibrations and for type testing of commercial power quality analyzers. Apart from further fine-tuning and validation measurements of the reference setup, future work will focus on real on-site measurements of power quality in transmission and distribution grids using a calibrated commercial power 1. Electromagnetic compatibility (EMC) Part 4-30: Testing and measurement techniques power quality measurement methods, IEC Std : Electromagnetic compatibility (EMC) Part 4-7: Testing and measurement techniques General guide on harmonics and interharmonics measurements and instrumentation, for power supply systems and equipment connected thereto, IEC Std :2002+A1: Electromagnetic compatibility (EMC) Part 4-15: Testing and measurement techniques Flickermeter Functional and design specifications, IEC Std : Power quality measurement in power supply systems - Part 1: Power Quality Instruments (PQI), IEC Std , to be approved 5. Power quality measurement in power supply systems - Part 2: Functional tests and uncertainty requirements, IEC Std , to be approved. 6. Wright, P.S.: An overview of harmonic and flicker emission standards and the associated measurements. IEE Power Eng. J., vol. 15(2), pp , Electromagnetic compatibility (EMC) Part 3-3: Limits - Limits for harmonic current emissions (equipment input current 16 A per phase), IEC Std : Electromagnetic compatibility (EMC) Part 3-3: Limits - Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated current 16 A per phase and not subject to conditional connection), IEC Std : Voltage characteristics of electricity supplied by public distribution systems, Cenelec Std. EN 50160: Wright, P.S.: A Method for the Calibration of Harmonic Analysers Using Signals Containing Fluctuating Harmonics in Support of IEC IEE Proc.-Sci. Meas. Technol., vol.152(3), pp , May Clarkson P. and Wright P.S.: Wavelet-based method for locating bursts of harmonics applied to the calibration of harmonic analysers. IEE Proc.-Sci. Meas. Technol., vol. 151(5), pp , Sept Clarkson P., Wright P.S.: The Calibration of IEC Standard Flickermeters Using Complex Modulated Signals. IEEE Trans. Instr. Meas., vol. 58(4), pp , April Helko E. van den Brom was born in Utrecht, the Netherlands, in He received the M.Sc. degree in theoretical solid state physics from Utrecht University in 1995, and the Ph.D. degree in experimental solid state physics from Leiden University, the Netherlands, in In that year he joined VSL, the Dutch national metrology institute in Delft, the Netherlands. At present, as a principle scientist and project manager he is responsible for calibration and development of the national DC and low frequency electrical standards. His current research interests are in electrical power and energy, sampling systems, and AC Josephson voltage standards. Dennis Hoogenboom was born in Sassenheim, The Netherlands, in He received his B.Sc. degree in physics from the Haagse Hogeschool, Delft, The Netherlands, in After his studies he joined the NMi Van Swinden Laboratorium, Delft, The Netherlands, in 2012, where he specialized in high voltage and high frequency measurements and became involved in the development of smart grid projects. 29

MEETING ECODESIGN EFFICIENCY REQUIREMENTS: ENSURING ACCURACY IN POWER TRANSFORMER LOSS TESTS VIA TLM SYSTEM CALIBRATIONS

MEETING ECODESIGN EFFICIENCY REQUIREMENTS: ENSURING ACCURACY IN POWER TRANSFORMER LOSS TESTS VIA TLM SYSTEM CALIBRATIONS MEETING ECODESIGN EFFICIENCY REQUIREMENTS: ENSURING ACCURACY IN POWER TRANSFORMER LOSS TESTS VIA TLM SYSTEM CALIBRATIONS Gert RIETVELD Ernest HOUTZAGER Milos ACANSKI Dennis HOOGENBOOM VSL, the Netherlands

More information

PQ Monitoring Standards

PQ Monitoring Standards Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality

More information

The Fluke 6100A. Electrical Power Standard. The most accurate, comprehensive and flexible source of electrical power signals

The Fluke 6100A. Electrical Power Standard. The most accurate, comprehensive and flexible source of electrical power signals The Fluke 6100A Electrical Power Standard The most accurate, comprehensive and flexible source of electrical power signals Measurement validation and calibration for electrical power applications The importance

More information

The Fluke 6100A. Electrical Power Standard. The most accurate, comprehensive and flexible source of electrical power signals

The Fluke 6100A. Electrical Power Standard. The most accurate, comprehensive and flexible source of electrical power signals The Fluke 6100A Electrical Power Standard The most accurate, comprehensive and flexible source of electrical power signals Measurement validation for electrical power applications The importance of accurate

More information

Power quality report. A Manufacturing Plant

Power quality report. A Manufacturing Plant Power quality report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION... 5 2.1 SITE MONITORED...

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

Power Quality Report. A Manufacturing Plant

Power Quality Report. A Manufacturing Plant Power Quality Report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant CHK Power Quality Pty Ltd Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION...

More information

6135A/PMUCAL Phasor Measurement Unit Calibration System

6135A/PMUCAL Phasor Measurement Unit Calibration System Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) 6135A/PMUCAL Phasor Measurement Unit Calibration System Fast, automated, traceable calibrations that comply with IEEE

More information

p. 1 p. 6 p. 22 p. 46 p. 58

p. 1 p. 6 p. 22 p. 46 p. 58 Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for

More information

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

POWER QUALITY MONITORING - PLANT INVESTIGATIONS Technical Note No. 5 January 2002 POWER QUALITY MONITORING - PLANT INVESTIGATIONS This Technical Note discusses power quality monitoring, what features are required in a power quality monitor and how it

More information

Immunity Testing for the CE Mark

Immunity Testing for the CE Mark Immunity Testing for the CE Mark Summary The European Union (EU) currently has 25 member countries with 2 additional countries to be added in 2007. The total population at that time will be nearly a half

More information

Power Quality - 1. Introduction to Power Quality. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič

Power Quality - 1. Introduction to Power Quality. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič Course Power Quality - 1 Ljubljana, Slovenia 2013/14 Prof. dr. Igor Papič igor.papic@fe.uni-lj.si Introduction to Power Quality Content Session 1 Session 2 Session 3 Session 4 1st day 2nd day 3rd day 4th

More information

Fluke Three-Phase Power Quality Recorder Topas. Class-A compliance for the most demanding power quality tests

Fluke Three-Phase Power Quality Recorder Topas. Class-A compliance for the most demanding power quality tests Test Equipment Depot - 800.517.8431-99 Washington Street Melrose, MA 02176 - TestEquipmentDepot.com Fluke 1760 Three-Phase Power Quality Recorder Topas Technical Data Class-A compliance for the most demanding

More information

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease Fluke 1740 Series Three-Phase Power Quality Loggers Memobox Technical Data Assess power quality and conduct long-term studies with ease Compact and rugged, the Fluke 1740 Series three-phase power quality

More information

EMC Seminar Series All about EMC Testing and Measurement Seminar 1

EMC Seminar Series All about EMC Testing and Measurement Seminar 1 EMC Seminar Series All about EMC Testing and Measurement Seminar 1 Introduction to EMC Conducted Immunity Jeffrey Tsang Organized by : Department of Electronic Engineering 1 Basic Immunity Standards: IEC

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering

More information

Low Frequency Measuring System

Low Frequency Measuring System Emission Measurements Low Frequency Measuring System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 4 Generator Specifications.................

More information

Fundamentals of Power Quality

Fundamentals of Power Quality NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»

More information

Southern Company Power Quality Policy

Southern Company Power Quality Policy Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...

More information

Power Quality in Metering

Power Quality in Metering Power Quality in Metering Ming T. Cheng Directory of Asian Operations 10737 Lexington Drive Knoxville, TN 37932 Phone: (865) 218.5885 PQsynergy2012 www.powermetrix.com Focus of this Presentation How power

More information

UNIT-4 POWER QUALITY MONITORING

UNIT-4 POWER QUALITY MONITORING UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and

More information

Fluke 5820A Oscilloscope Calibrator Specifications

Fluke 5820A Oscilloscope Calibrator Specifications Fluke 5820A Oscilloscope Calibrator Specifications Voltage Function Volt Function DC Signal Square Wave Signal 1 Load into 50Ω into 1 MΩ into 50Ω into 1 MΩ Amplitude Range 0V to ±6.6V 0V to ±130V ±1 mv

More information

Power Quality Analysers

Power Quality Analysers Power Quality Analysers Review of Power Quality Indicators and Introduction to Power Analysers ZEDFLO Australia 6-Mar-2011 www.zedflo.com.au Power Quality Indicators Review of main indicators of electrical

More information

II. RESEARCH METHODOLOGY

II. RESEARCH METHODOLOGY Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College

More information

DEVELOPMENT AND PERFORMANCE ANALYSIS

DEVELOPMENT AND PERFORMANCE ANALYSIS AN IEC 61000-4-30 CLASS A - POWER QUALITY MONITOR DEVELOPMENT AND PERFORMANCE ANALYSIS Andrés E. Legarreta 1, Javier H. Figueroa 2, Julio A. Bortolín 3 1 ECAMEC Tecnología, Buenos Aires, Argentina, desarrollo@ecamec.com.ar

More information

Power Quality Issues from an EMC Point of View

Power Quality Issues from an EMC Point of View Power Quality Issues from an EMC Point of View Brian Jones BSc (Hons) C Eng MIEE MIEEE Overview What is EMC? How does it apply to power quality? The effects of equipment on power quality The effects of

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

For the National Voluntary Laboratory Accreditation Program

For the National Voluntary Laboratory Accreditation Program SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 Intertek Japan K.K. Calibration Laboratory 3-2 Sunayama Kamisu Ibaraki 314-0255 JAPAN Ms. Masako Oyamada Phone: 81-465 89 2316 Fax: 81-465 89 2160 E-mail: masako.oyamada@intertek.com

More information

RCTrms Technical Notes

RCTrms Technical Notes RCTrms Technical Notes All measuring instruments are subject to limitations. The purpose of these technical notes is to explain some of those limitations and to help the engineer maximise the many advantages

More information

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk. , 2011;4(12) Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces H.A. Khalik, M. A. Aziz, and E. Farouk. Electrical power and Machines Engineering

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information

Protection from Voltage Sags and Swells by Using FACTS Controller

Protection from Voltage Sags and Swells by Using FACTS Controller Protection from Voltage Sags and Swells by Using FACTS Controller M.R.Mohanraj 1, V.P.Suresh 2, G.Syed Zabiyullah 3 Assistant Professor, Department of Electrical and Electronics Engineering, Excel College

More information

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO Krasimir Marinov Ivanov, Technical University of Gabrovo, Gabrovo, BULGARIA Georgi Tsonev

More information

Transient Current Measurement for Advance Materials & Devices

Transient Current Measurement for Advance Materials & Devices & Devices 8 May 2017 Brian YEO Application Engineer Keysight Technologies Agenda 2 High speed data acquisition basics Challenges & solutions for transient current measurement. Considerations when making

More information

ASSESSING COMPLICATED POWER QUALITY ISSUES OFF-LINE WITH IEC COMPLIANT TOOLBOX

ASSESSING COMPLICATED POWER QUALITY ISSUES OFF-LINE WITH IEC COMPLIANT TOOLBOX ASSESSING COMPLICATED POWER QUALITY ISSUES OFF-LINE WITH IEC 61000-4-30 COMPLIANT TOOLBOX Bernard Dethy (bernard.dethy@laborelec.com ) Emmanuel De Jaeger (emmanuel.dejaeger@laborelec.com) Michel Dascotte

More information

Motors and drives. Module B- Introduction to input measurements

Motors and drives. Module B- Introduction to input measurements Motors and drives Module B- Introduction to input measurements Introduction to input measurements There are a number of locations where input measurements may be made Which is the most important location

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Power Quality and Circuit Imbalances 2015 Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Summary of IEEE 1159 Terms Category Types Typical Duration

More information

Network Analyzer for Low-, Medium- and High-Voltage Networks

Network Analyzer for Low-, Medium- and High-Voltage Networks Technical data Network nalyzer for Low-, Medium- and High-Voltage Networks Model PQ-Box 100 1 Fault detection 1 Evaluation of voltage quality according to EN50160 and IEC61000-2-2 (2-4) 1 Fault recorder

More information

Power Quality Analyzer Topas 2000

Power Quality Analyzer Topas 2000 Power Quality Analyzer Topas 2000 Effecting measurement tasks in medium and low voltage networks faster and with a single tool: Complies with IEC 61000-4-30 class A with synchronization to power frequency

More information

A POWER QUALITY INSTRUMENT FOR HARMONICS INTERHARMONICS AND AMPLITUDE DISTURBANCES MEASUREMENTS

A POWER QUALITY INSTRUMENT FOR HARMONICS INTERHARMONICS AND AMPLITUDE DISTURBANCES MEASUREMENTS Proceedings, XVII IMEKO World Congress, June 7, 003, Dubrovnik, Croatia Proceedings, XVII IMEKO World Congress, June 7, 003, Dubrovnik, Croatia XVII IMEKO World Congress Metrology in the 3rd Millennium

More information

EMC Pulse Measurements

EMC Pulse Measurements EMC Pulse Measurements and Custom Thresholding Presented to the Long Island/NY IEEE Electromagnetic Compatibility and Instrumentation & Measurement Societies - May 13, 2008 Surge ESD EFT Contents EMC measurement

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

Network Analyzer for Low-, Medium- and High-Voltage Networks

Network Analyzer for Low-, Medium- and High-Voltage Networks Technical data Network nalyzer for Low-, Medium- and High-Voltage Networks Model PQ-Box 150 1 Fault detection 1 Evaluation of voltage quality according to EN50160 and IEC61000-2-2 (2-4) 1 FFT nalysis up

More information

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 36-41 Analysis, Modeling and Simulation of Dynamic Voltage

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

Publishable JRP Summary for Project T4 J03 JOSY. Next generation of quantum voltage systems for wide range applications

Publishable JRP Summary for Project T4 J03 JOSY. Next generation of quantum voltage systems for wide range applications Publishable JRP Summary for Project T4 J3 JOSY Next generation of quantum voltage systems for wide range applications The main objective of this project is to introduce quantum-based measurement systems

More information

Choosing the right Pico Technology active differential probe

Choosing the right Pico Technology active differential probe Pico Technology offers many active s covering a wide range of voltages, category (CAT) ratings and bandwidths. As the name suggests, these probes have two major features: Active: Active probes achieve

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim

More information

CHROMA ATE INC. Programmable AC Source 61500/61600 Series. Product Manager: Galen Chou

CHROMA ATE INC. Programmable AC Source 61500/61600 Series. Product Manager: Galen Chou CHROMA ATE INC. Programmable AC Source 61500/61600 Series Product Manager: Galen Chou Chroma AC Source Family Outline 1. What is programmable AC source? 2. What is user s need? 3. What do they test with

More information

Power Quality Notes 3-2 (MT)

Power Quality Notes 3-2 (MT) Power Quality Notes 3-2 (MT) Marc Thompson, Ph.D. Senior Managing Engineer Exponent 21 Strathmore Road Natick, MA 01760 Alex Kusko, Sc.D, P.E. Vice President Exponent 21 Strathmore Road Natick, MA 01760

More information

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease Fluke 1740 Series Three-Phase Power Quality Loggers Memobox Technical Data Assess power quality and conduct long-term studies with ease Compact and rugged, the Fluke 1740 Series three-phase power quality

More information

Active: Active probes achieve low input capacitance and high sensitivity by buffering and amplifying the signal close to the point of measurement.

Active: Active probes achieve low input capacitance and high sensitivity by buffering and amplifying the signal close to the point of measurement. Application Note Pico Technology offers many s covering a wide range of voltages, category (CAT) ratings and bandwidths. As the name suggests, these probes have two major features: Active: Active probes

More information

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks GB Technical data Issue 06/2009 PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks Fault detection Evaluation of voltage quality according to EN50160 and IEC61000-2-2 Fault recorder

More information

A New Method for the Calibration of the mv Ranges of an AC Measurement Standard

A New Method for the Calibration of the mv Ranges of an AC Measurement Standard A New Method for the Calibration of the mv Ranges of an AC Measurement Standard Speaker/Author Neil Faulkner Fluke Corporation PO Box 9090, Everett, WA 98206 Phone: (425) 446-5538 FAX: (425) 446-5649 E-mail:

More information

A Comparison Between MIL-STD and Commercial EMC Requirements Part 2. By Vincent W. Greb President, EMC Integrity, Inc.

A Comparison Between MIL-STD and Commercial EMC Requirements Part 2. By Vincent W. Greb President, EMC Integrity, Inc. A Comparison Between MIL-STD and Commercial EMC Requirements Part 2 By Vincent W. Greb President, EMC Integrity, Inc. OVERVIEW Compare and contrast military (i.e., MIL-STD) and commercial EMC immunity

More information

High precision measurement system for current and voltage IHC-A/B-RM01/03

High precision measurement system for current and voltage IHC-A/B-RM01/03 Measurement Offset-free and low-noise 16 bit data acquisition system ISA-ASIC Internal sample rate 3,500 Hz Communication Standard RS232- or RS485 interface Advantages Direct measurement on the bus bar

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Title: 550A Getting Started Supplement Issue: Part Number: 415509 Issue Date: 9/18 Print Date: November 01 Page Count: 19 Revision/Date: This supplement contains information necessary to ensure

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg Coupling modes Véronique Beauvois, Ir. 2015-2016 General problem in EMC = a trilogy Parameters Amplitude Spectrum Source (disturbing) propagation Coupling modes Victim (disturbed) lightning electrostatic

More information

PQube 3 Specifications

PQube 3 Specifications PQube 3 Specifications Reference conditions for factory tests: 19~25 C, 10%~70% RH MAINS VOLTAGE MEASURING CHANNELS Measurement Channels Power Configuration/ Range of Nominal Input Voltage 3 Line to Neutral,

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

IEC Electrical fast transient / Burst immunity test

IEC Electrical fast transient / Burst immunity test CONDUCTED RF EQUIPMENT POWER AMPLIFIERS IEC 61000-4-4 Electrical fast transient / Burst immunity test IEC 61000-4-4 Electrical fast transient / Burst immunity test Markus Fuhrer Phenomenom open a contact

More information

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES MATH H. J. BOLLEN IRENE YU-HUA GU IEEE PRESS SERIES I 0N POWER ENGINEERING IEEE PRESS SERIES ON POWER ENGINEERING MOHAMED E. EL-HAWARY, SERIES EDITOR IEEE

More information

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08 The development of the SA grid code on Power Quality emission Dr. Gerhard Botha 2017/08/08 Overview What is the Grid Code? What is Power Quality? Power Quality Management Principles Differences Challenges

More information

Calibration of High-Voltage Test Equipment

Calibration of High-Voltage Test Equipment Workshop 2000, Alexandria, Virginia, 13 & 14 September 2000 paper No.: 6 of High-Voltage Test Equipment Uwe Clauss, Stefan Maucksch, HIGHVOLT Prüftechnik Dresden GmbH, Dresden, Germany 1. Abstract The

More information

Introduction to Harmonics and Power Quality

Introduction to Harmonics and Power Quality NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

HARMONIC contamination, due to the increment of nonlinear

HARMONIC contamination, due to the increment of nonlinear 612 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 44, NO. 5, OCTOBER 1997 A Series Active Power Filter Based on a Sinusoidal Current-Controlled Voltage-Source Inverter Juan W. Dixon, Senior Member,

More information

Performance of high voltage transducers for measurement of power quality disturbances modeling and simulation

Performance of high voltage transducers for measurement of power quality disturbances modeling and simulation Performance of high voltage transducers for measurement of power quality disturbances modeling and simulation HÉDIO TATIZAWA 1, ERASMO SILVEIRA NETO 2, GERALDO F. BURANI 1, ANTÔNIO A. C. ARRUDA 1, KLEIBER

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

Standby Power. Primer

Standby Power. Primer Standby Power Primer Primer Table of Contents What is Standby Power?...3 Why is Standby Power Important?...3 How to Measure Standby Power...4 Requirements for a Measurement...4 Standby Measurement Challenges...4

More information

Scale Manufacturers Association (SMA) Recommendation on. Electrical Disturbance

Scale Manufacturers Association (SMA) Recommendation on. Electrical Disturbance Scale Manufacturers Association (SMA) Recommendation on Electrical Disturbance (SMA RED-0499) Provisional First Edition Approved by SMA Pending Final Comment April 24, 1999 Copyright: SMA, April, 1999

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

CHARACTERIZATION ISSUE OF POWER QUALITY INSTRUMENTS

CHARACTERIZATION ISSUE OF POWER QUALITY INSTRUMENTS XIX IMEKO World Congress Fundamental and Applied Metrology September 6 11, 2009, Lisbon, Portugal CHARACTERIZATION ISSUE OF POWER QUALITY INSTRUMENTS Daniele Gallo, Carmine Landi, Mario Luiso Dipartimento

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 19 1 Today Flicker Power quality and reliability benchmarking

More information

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point 2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Title: 5502E Getting Started Supplement Issue: 3 Part Number: 4155211 Issue Date: 9/18 Print Date: November 2012 Page Count: 12 Revision/Date: This supplement contains information necessary to ensure

More information

Calibration Laboratory Assessment Service CLAS Certificate Number Page 1 of 10

Calibration Laboratory Assessment Service CLAS Certificate Number Page 1 of 10 Calibration Laboratory Assessment Service CLAS Certificate Number 95-02 Page 1 of 10 400 Britannia Road East, Unit #1 Mississauga, Ontario L4Z 1X9 Contact: Mr. Vince Casali Tel (905) 890-7600, (800) 36FLUKE

More information

Power Quality Analyzer / High Frequency Recorder

Power Quality Analyzer / High Frequency Recorder Technical data Power Quality nalyzer / High Frequency Recorder Model PQ-Box 300 1 Fault detection 1 Evaluation of voltage quality according to EN50160 und IEC61000-2-2/-2-4 1 Permanent FFT nalysis from

More information

EN :2007+A1:2011 Electromagnetic compatibility Emission standard for residential, commercial and light-industrial environments

EN :2007+A1:2011 Electromagnetic compatibility Emission standard for residential, commercial and light-industrial environments EMC Page 3 / 33 Test report No.: EN 61000-6-3:2007+A1:2011 Electromagnetic compatibility Emission standard for residential, commercial and light-industrial environments Date of measurement: 2013-10-16

More information

shunt (parallel series

shunt (parallel series Active filters Active filters are typically used with diode/thyristor rectifiers, electric arc furnaces, etc. Their use in electric power utilities, industry, office buildings, water supply utilities,

More information

Power Quality under the microscope

Power Quality under the microscope We take care of it. Power Quality Power Quality under the microscope Change in the producer and consumer structure The change in the producer and consumer structure of the Central European power grids

More information

DRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

Power Quality Survey in a Distribution System, Standard Procedures and Limitations. H. Mokhtari S. Hasani and M. Masoudi

Power Quality Survey in a Distribution System, Standard Procedures and Limitations. H. Mokhtari S. Hasani and M. Masoudi THD Voltage Ubc Power Quality Survey in a Distribution System, Standard Procedures and Limitations H. Mokhtari S. Hasani and M. Masoudi Associate Professor Department of Electrical Engineering Sharif University

More information

Evaluation and Updating of Harmonic Voltage Limits

Evaluation and Updating of Harmonic Voltage Limits Evaluation and Updating of Harmonic Voltage Limits J.F.G. Cobben D.A.M. Geldtmeijer A.F.J Almering J.B.M. van Waes Dept. of Electrical Engineering Dept. of Asset Management Dept. of Standardization Energy

More information

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE 8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE TRANSMILLE LTD. Version 1.1 : Apr 2015 TABLE OF CONTENTS PREPARING FOR CALIBRATION... 4 INTRODUCTION... 4 CALIBRATION INTERVAL SELECTION...

More information

Reliable Power Meters Multipoint Power Recorder

Reliable Power Meters Multipoint Power Recorder Reliable Power Meters Multipoint Power Recorder High-speed capability for permanent installation Technical Data What is Full Disclosure Technology? Full Disclosure Technology is built into all Fluke and

More information

Module 1: Introduction to Experimental Techniques Lecture 2: Sources of error. The Lecture Contains: Sources of Error in Measurement

Module 1: Introduction to Experimental Techniques Lecture 2: Sources of error. The Lecture Contains: Sources of Error in Measurement The Lecture Contains: Sources of Error in Measurement Signal-To-Noise Ratio Analog-to-Digital Conversion of Measurement Data A/D Conversion Digitalization Errors due to A/D Conversion file:///g /optical_measurement/lecture2/2_1.htm[5/7/2012

More information

CHAPTER 7 HARDWARE IMPLEMENTATION

CHAPTER 7 HARDWARE IMPLEMENTATION 168 CHAPTER 7 HARDWARE IMPLEMENTATION 7.1 OVERVIEW In the previous chapters discussed about the design and simulation of Discrete controller for ZVS Buck, Interleaved Boost, Buck-Boost, Double Frequency

More information

Discontinuous Disturbance (Click) EN :2006+A1:2009+A2:2011 Clause N/A** Radiated Emission, 30MHz to 1000MHz

Discontinuous Disturbance (Click) EN :2006+A1:2009+A2:2011 Clause N/A** Radiated Emission, 30MHz to 1000MHz Reference No.: WTN13F0706038E Page 2 of 40 1 Test Summary Test Item Mains Terminal Disturbance Voltage, 148.5kHz to 30MHz Disturbance Power, 30MHz to 300MHz EMISSION Test Standard Class / Severity Result

More information

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech

More information

Three Phase Power Calibrator and Tester of Power Engineering Devices

Three Phase Power Calibrator and Tester of Power Engineering Devices C300B Data Sheet Three Phase Power Calibrator and Tester of Power Engineering Devices C300B Power Calibrator and Tester 3-phase voltage source up to 560V 3-phase current source up to 120A and 1-phase up

More information

Design and Development of Protective Circuit against Voltage Disturbances

Design and Development of Protective Circuit against Voltage Disturbances Design and Development of Protective Circuit against Voltage Disturbances Shashidhar Kasthala 1, Krishnapriya 2, Rajitha Saka 3 1,2 Facultyof ECE, Indian Naval Academy, Ezhimala, Kerala 3 Assistant Professor

More information

Power Quality and Digital Protection Relays

Power Quality and Digital Protection Relays Power Quality and Digital Protection Relays I. Zamora 1, A.J. Mazón 2, V. Valverde, E. Torres, A. Dyśko (*) Department of Electrical Engineering - University of the Basque Country Alda. Urquijo s/n, 48013

More information

EXAM Amplifiers and Instrumentation (EE1C31)

EXAM Amplifiers and Instrumentation (EE1C31) DELFT UNIVERSITY OF TECHNOLOGY Faculty of Electrical Engineering, Mathematics and Computer Science EXAM Amplifiers and Instrumentation (EE1C31) April 18, 2017, 9.00-12.00 hr This exam consists of four

More information

How accurate is a measurement? Why should you care? Dr. Andrew Roscoe

How accurate is a measurement? Why should you care? Dr. Andrew Roscoe How accurate is a measurement? Why should you care? Dr. Andrew Roscoe Does V=IR? You are asked to confirm the hypothesis that V=IR. The following equipment is used: I, RMS Current (Amps) V, RMS Voltage

More information