UL Listed power distribution blocks

Size: px
Start display at page:

Download "UL Listed power distribution blocks"

Transcription

1 Technical ata ffective September 2017 Supersedes ugust 2016 atalog number example: P323-3 is a 3-pole P323 Where: The prefix P323 defines the block s lineside characteristics (i.e., one conductor port per pole that accepts 350 kcmil - #6 u/ l conductors) and the loadside characteristics (i.e., six (6) conductor ports per pole that each accepts #4 - #14 u or #4 - #12 l conductors). The suffix 3 in this example defines this as a three-pole block. See the catalog number table for details on the available lineside/loadside characteristics. atalog symbol: P (poles) escription: aton s ussmann series high Short-ircuit urrent Rating (SR) power distribution blocks provide up to 200 k SR and help achieve compliance with National lectrical ode (N ) and OSH requirements by resolving a common SR weak link in industrial control panels. vailable in 1-, 2- and 3-pole panel mount versions with popular lineside and loadside port configurations, these blocks are UL Listed and provide the requisite spacing between uninsulated opposite polarities or ground by meeting the UL through air and 2 over surface spacings required per UL 508 for feeder circuit applications and per N for field installations. To increase application flexibility, these blocks feature dual-wire rated ports that accept copper or aluminum conductors while retaining a UL Listed status. Optional covers are available to enhance electrical safety. How to order: rom the catalog number table, select the catalog number that defines the desired lineside/loadside port and conductor characteristics. dd to the catalog number the suffix that defines the desired pole configuration. Note, you must select from the available number of poles for each catalog number. These appear in the second column of the catalog number tables. Specifications: Ratings Volts: 600 V mps: 175 to 310 SR: 200 k (see table for circuit protection details) lammability rating UL 94 V0 Storage and operating temperature range -4 to 248 (-20 to 120 ) gency information UL 1953 Listed, Guide QPQS, ile S ertified, lass , ile onductors Stranded 75 copper and aluminum Higher temperature rated conductors permitted with appropriate derating s specified in the catalog number table.

2 Technical ata ffective ugust 2016 atalog numbers: Line/load port configuration No. of poles 1, , , , 2, , , , urrent rating () Wire size (Str/ferrule unless noted)* 2/0 - #1 u/l (Str) 1 Wires per port Torque N m (Lb-in) Ports/ pole Wire size (Str/ferrule unless noted)* 2/0 - #1 u/l (Str) 1 #2 - #3 u/l (110) #2 - #3 u/l 1 #4 - #8 u/l 1 #4 - #8 u/l 1 #10 - #12 l (Str) 1 1 #10 - #12 l (Str) 1 #10 - #14 u 1 #10 - #14 u 1 #4 - #8 u/l 2 #4 - #8 u/l (120) #10 - #14 u 2 #10 - #14 u 2 2/0 - #1 u/l (Str) 1 #2 - #3 u/l 1 #8 u (120) 1 #4 - #8 u/l 1-2 #8 l (Str) 1-2 Wires per port Torque N m (Lb-in) 12.4 (110) 13.6 (120) #4 - #6 u/l (Str) (25) #10 - #14 u 1-2 #10 - #14 u (20) 2/0 - #1 u/l (Str) 1 #2 - #3 u/l 1 #4 - #8 u/l 1-2 #10 - #14 u 1-2 2/0 - #1 u/l (Str) 1 Ports/ pole Max SR (k)** atalog number P204-_ P220-_ 13.6 (120) 1 1/4-20 x 3/4 Stud P280-_ #4 - #6 u/l (Str) 1 #2 - #3 u/l 1 #8 l (Str) 1-2 #4 - #8 u/l (120) 1 #8 u (25) #10 - #12 l (Str) 1 #10 - #12 l (Str) 1 #10 - #14 u 1-2 #10 - #14 u (20) 350kcmil - 2/0 u/l (Str) 1 #4 - #6 u/l (Str) 1 #8 l (Str) 1-2 1/0 u/l (Str) 1-2 #8 u (25) 31.1 (275) 1 #10 - #12 l (Str) 1 #1 - #6 u/l kcmil - 2/0 u/l (Str) 1 1/0 u/l (Str) 1-2 #1 - #6 u/l kcmil - 2/0 u/l (Str) 1 1/0 u/l (Str) 1-2 #1 - #6 u/l (275) (275) 1 #10 - #12 u 1 #10 - #14 u 2 #4 - #6 u/l (Str) 1 #8 l (Str) (20) #8 u (25) #10 - #12 l (Str) 1 #10 - #14 u (20) #2 - #3 u/l (Str) 1 #4 - #8 l (Str) 1 #6 - #8 l (Str) 2 #4 u 1 #6 u (50) 5.1 (45) #8 u (40) #10 - #12 u 1-2 #14 u 2 1/0 - #3 u/l (Str) (50) #4 - #6 u/l (45) #8 u/l (40) #10 - #12 u 1 #6 - #14 u 2 #4 - #6 l (Str) (120) P321-_ P323-_ P370-_ P371-_ * 75 wire (higher temperature rated wire acceptable with appropriate derating). Using a ferrule on a stranded conductor requires a correctly sized UL Listed ferrule (customer supplied) applied according to the manufacturer s specifications. errule ratings apply to copper wire only. ** See pages 4 and 5 for the tested upstream overcurrent protective devices necessary for achieving these SRs. Torque rating for dual wire and ferrule application is 30.5 N m (270 Lb-in). Torque rating for ferrule application is 13.6 N m (120 Lb-in). 2 aton.com/bussmannseries

3 Technical ata ffective ugust 2016 eatures and benefits High SRs up to 200 k, assist in achieving high SR for a control panel per N and UL 508 requirements. In compliance with UL 1953 minimum spacing requirements for industrial control panel feeder and branch circuits. Optional covers available to reduce the risk of accidental contact with energized components. ual wire port application Rated for dual wire port application to increase the possible number of lineside and loadside connections..g., P220 can accept two wires into the lineside port (#4 - #14 u, #4 - #8 l) and two wires per port (eight connections per pole total) on the loadside lug (#8 - #14 u, #8 l). ual wire applications are only viable when using two wires of the same size, stranding, and insulating and conductor material in the same port. errule terminal application ussmann series P power distribution blocks are rated for use with UL Listed ferrules (see catalog number table for details). errule applications allow for the use of a broader range of conductor stranding and simulate a more efficient, solid wire connection with the P terminal port. lways use UL Listed ferrules in accordance with the manufacturer s specifications and instructions. Selecting SR power distribution blocks and terminal blocks Short-circuit current rated power distribution blocks ussmann series power distribution blocks have three distinct styles to match different application needs. There are the PS_ and P_ high short-circuit current rated power distribution blocks and the 16_ power terminal blocks. The differences are whether the power distribution blocks are enclosed or not, and whether they are UL 1953 Listed power distribution blocks or UL 1059 Recognized power terminal blocks, which have different minimum spacing requirements. The table on this page will assist you in selecting which block is right for your application. Why these are important Per the N and OSH, equipment cannot be installed in an electrical system at a location where the available fault (short-circuit) current is greater than the equipment s SR. urther, equipment SRs are required in the 2014 N and for UL 508 Listed control panels. Marking the equipment SR on control panels (N ), industrial machinery electrical panels Selection table This table provides an overview of the three ussmann series power distribution and terminal blocks mentioned above. or details on the PS blocks, see data sheet number or the 16_ blocks, see data sheet numbers (UL Recognized power distribution blocks), (splicer blocks) and (stud blocks). atalog symbol UL status nclosed High SR* PS_ P_ 16_ UL 1953 Listed power distribution blocks UL 1953 Listed power distribution blocks UL 1059 Recognized terminal blocks Spacing ** 1 air, 2 surface UL 508 panel branch circuit UL 508 panel feeder circuit HV UL 1995 Yes*** Yes Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes * When protected by proper fuse class with maximum ampere rating specified or smaller. ** or details, see P and T minimum spacing requirements for equipment table below. *** IP20 finger-safe under specific conditions, see data sheet no , page 5. Optional covers are available. Not IP20, but provide a safety benefit. No, except: Yes, if single pole units installed with proper spacings. No Yes No Yes No Yes No Power distribution and terminal block minimum spacing requirements for equipment UL standard Spacing between live parts of opposite polarity Through 600 V Over 600 V 508 feeder circuits branch circuits 3/8 1/2 1/ HV 3/8 1/2 1/2 Note: Refer to specific UL standards for complete spacing details. (N 670.3()), and HV equipment (N 440.4()) is required by the N. Power distribution and terminal blocks not marked with a component SR are typically one of the weakest links in a control panel s equipment SR and may limit the equipment SR to no more than 10 k. The PS_ and P_ products have the increased spacing required for use in feeder circuits of equipment listed to UL 508 (UL 1059 terminal blocks must be evaluated for proper spacings). lso, for building wiring systems, the PS_ and P_ power distribution blocks can be used to meet the 2014 N requirements in section () for power distribution blocks in wireways. See the last page of this data sheet for SR tools and resources to help you further understand and solve your SR needs. Spacing between live parts and grounded parts or 600 V Wireways N () (requires UL 1953) Yes, with optional cover aton.com/bussmannseries 3

4 Technical ata ffective September 2017 Upstream fusing for SR and minimum enclosure data This table contains the tested SR levels for each PS power distribution block using the specified lineside and loadside conductors and ussmann series lass J, RK1, RK5 and T fuses. Using these tested SR levels also requires the power distribution block be installed in an enclosure with the minimum size indicated for each catalog number. atalog number onductors (WG or kcmil) use class and maximum amps* G S (480 V) J LPJ RK1 LPN-RK ( V) LPS-RK (600 V) RK5 RN-R ( V) RS-R (600 V) T JJN (300 V) JJS (600 V) SR Minimum enclosure size (in) P204-1, -3 2/0 - #8 2/0 - # k 16 x 16 x 6.75 #4 - # k P220-1, -3 2/0 - #8 16 x 16 x 6.75 #4 - # k P280-1, -3 2/0 - #8 Stud k 16 x 16 x 6.75 P321-1, -2, -3 2/0 - #8 P323-1, #4 P370-1, #4 P371-1, #4 #4 - # k 24 x 20 x 6.75 #4 - # k #4 - # k 24 x 20 x 6.75 #4 - # k #4 - # k 24 x 20 x 6.75 #4 - # k 1/0 - # k 24 x 20 x /0 - # k mpacities 75 per N Table and UL 508 Table * lass 30 (LP--30, NQ-R-30, KTK-R-30) or less are suitable for all SRs in this table. 4 aton.com/bussmannseries

5 Technical ata ffective September 2017 Upstream circuit breakers for SR and minimum enclosure data This table contains the tested SR levels for each P power distribution block using the specified lineside and loadside conductors and aton circuit breakers. Using these tested SR levels also requires the power distribution block be installed in an enclosure with the minimum size indicated for each catalog number. P_ SR as rated with aton circuit breakers atalog no. P220 P321 P323 P370 P371 Suitable copper conductors kcmil/wg SR, RMS Overcurrent protection circuit breaker required Sym, k Volts max Type Max amp 2/0 - #8 #4 - # G125, 125, GH125, 125H 125 2/0 - #8 # /0 - #8 # G125, 125, G125, 125, GS125, 125S, GH125, 125H G125, 125, G125, 125, G125, 125, GS125, 125S, GH125, 125H 2/0 - #8 #4 - # G125, 125, GH125, 125H 125 2/0 - #8 # /0 - #8 # G125, 125, G125, 125, GS125, 125S, GH125, 125H G125, 125, G125, 125, G125, 125, GS125, 125S, GH125, 125H #4 #4 - # JGH, JH #4 # JGH, JH #4 # #4 #4 - #6 65 #8 42 #10 25 #8 50 # JGH, JH, JG, J, JGS, JS, JG, J, JGU, JU, JGX, JX #4 #4 - # JGH, JH #4 # JGH, JH #4 # #4 #4 - #6 65 #8 42 # JGH, JH, JG, J, JGS, JS, JG, J, JGU, JU, JGX, JX #4 #4 - # JGH, JH #4 # JGH, JH #4 # #4 #4 - #6 65 #8 50 # JGH, JH, JG, J, JGS, JS, JG, J, JGU, JU, JGX, JX Minimum enclosure size (in.) 16 x 16 x x 20 x x 20 x x 20 x x 20 x 6.75 aton.com/bussmannseries 5

6 Technical ata ffective September 2017 imensions in (mm) Width Length Height atalog No. (Hole) P204-3, P220-3, P (108) 2.88 (73) 2.13 (54) 1.62 (41) 2.25 (57) 0.22 (6) P323-3, P370-3, P (160) 5.50 (140) 3.70 (94) 3.25 (83) 4.75 (121) 0.22 (6) P323-1, P370-1, P (50) 4.00 (102) 3.33 (84) 3.37 (86) 0.21 (5.3) x 0.41 (10) P204-1, P220-1, P (27) 2.88 (73) 1.75 (44) 2.25 (57) 0.20 (5) P (50) 4.00 (102) 3.33 (84) 3.37 (86) 0.21 (5.3) x 0.41 (10) P (91) 4.00 (102) 3.33 (84) 1.62 (41) 3.37 (86) 0.21 (5.3) x 0.41 (10) P (132) 4.00 (102) 3.33 (84) 3.23 (82) 3.37 (86) 0.21 (5) x 0.41 (10) P204 P220 P280 6 aton.com/bussmannseries

7 Technical ata ffective September 2017 P321 P323 P370 P371 aton.com/bussmannseries 7

8 Technical ata ffective September 2017 Optional covers lectrical safety can be enhanced by installing optional covers. rom the table below, order the cover catalog number that matches the block catalog number. Order the quantity indicated in the order quantity column..g., the 3-pole block P204-3 requires ordering three P162-1 covers (one cover for each pole). lock catalog no. Poles over catalog no. Order quantity P P P P P P P P P P P P P P-1 1 P P-1 3 P P-1 1 P P-1 3 P P-1 1 P P-1 3 P P-1* 1 P P-2* 1 P P-3* 1 * or the P321-_ blocks, order one cover for each block (not per pole). SR tools and resources aton offers many resources that help customers understand and assess their SR needs. Please use the following whenever you have questions, concerns or just need help with SR ratings. ngineering services for SR OSR compliance software eliminates the guesswork in equipment SR calculations. This innovative OSR compliance software assists customer compliance with new ode and standards requirements for shortcircuit current ratings as they relate to control panels, equipment and assemblies. Go to OSR.eaton.com and request a seven-day free trial. If your equipment SR needs improvement, contact the ussmann pplication ngineers for a free design review. all toll-free USSMNN ( ) or usetech@eaton.com. Online SR tools and publications ree SR Protection Suite online tool. n easy, fast way to search for components and their SRs. Visit sccr.eaton.com. pplication notes: eveloping an effective SR plan for facilities and purchasers of industrial equipment publication no eveloping an equipment SR standard for manufacturers of industrial equipment publication no our steps to determine equipment SR publication no quipment SR made easy brochure publication no SP (Selecting Protective evices) handbook; over pages covering the application of overcurrent protective devices, SR and more publication no The only controlled copy of this data sheet is the electronic read-only version located on the aton network drive. ll other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. aton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. aton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. aton 1000 aton oulevard leveland, OH aton.com ussmann ivision 114 Old State Road llisville, MO United States aton.com/bussmannseries 2017 aton ll Rights Reserved Printed in US Publication No U-M16049 September 2017 aton, ussmann and OSR are valuable trademarks of aton in the U.S. and other countries. You are not permitted to use the aton trademarks without prior written consent of aton. S is a registered trademark of the anadian Standards Group. N is a registered trademark of the National ire Protection ssociation, Inc. UL is a registered trademark of the Underwriters Laboratories, Inc. or aton s ussmann series product information, call or visit: aton.com/bussmannseries ollow us on social media to get the latest product and support information. 8 aton.com/bussmannseries

Table of Contents. Power Distribution Blocks & Terminal Blocks with High Short-Circuit Current Ratings. Technical Assistance

Table of Contents. Power Distribution Blocks & Terminal Blocks with High Short-Circuit Current Ratings. Technical Assistance Power Distribution Blocks & Terminal Blocks with High Short-Circuit Current Ratings Table of Contents Page Selection Table.... 2 Power Distribution Blocks PDBFS Series....................................3-8

More information

Table of Contents. Power Distribution Blocks & Terminal Blocks with High Short-Circuit Current Ratings. Technical Assistance

Table of Contents. Power Distribution Blocks & Terminal Blocks with High Short-Circuit Current Ratings. Technical Assistance Power Distribution Blocks & Terminal Blocks with High Short-Circuit Current Ratings Table of Contents Page Selection Table.... 2 Power Distribution Blocks PDBFS Series....................................3-8

More information

8.3. Terminal Blocks, Fuse Blocks and Fuse Holders. Contents Description. CHDB Series Power Distribution Blocks. Power Distribution

8.3. Terminal Blocks, Fuse Blocks and Fuse Holders.  Contents Description. CHDB Series Power Distribution Blocks. Power Distribution Terminal Blocks, Fuse Blocks and Fuse Holders.3 CHDB Series Blocks, Enclosed and Open CHDB Series Blocks Product Description Features and Benefits Eaton s CHDB Series of Blocks was designed for high short

More information

Power Distribution Blocks with Short-Circuit Current Ratings

Power Distribution Blocks with Short-Circuit Current Ratings Power Distribution Blocks with Short-Circuit Current Ratings General Information: The requirements of the 005 National Electric Code (NEC) and UL508A now require many electrical panels to carry a Short

More information

onlinecomponents.com

onlinecomponents.com Short-Circuit Current Ratings and Feeder Spacing SCCR Information: Power Distribution Blocks with SCCR and Feeder Spacing The requirements of the National Electric Code (NEC) and UL508A now require many

More information

$

$ ircuit reakers or I-LIN Panelboards and Switchboards lass 0, 5, 70, 830 8 PNLORS 8-32 LI3 7.5 in (190 mm) L 7.5 in (190 mm) M, MH 2- and 3-Pole 9 in (229 mm) N, N 2- and 3-Pole 15 in (381 mm) Square ll

More information

3Ø Short-Circuit Calculations

3Ø Short-Circuit Calculations 3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective

More information

Short-Circuit Current Calculations

Short-Circuit Current Calculations Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.

More information

Harmonic Correction Unit NEMA 1 Enclosure

Harmonic Correction Unit NEMA 1 Enclosure ffective: June 2001 Page 1 New Information Harmonic orrection Unit ontents Description Page Harmonic orrection Unit Specifications.......... 2 Sizing and Selection.............................................

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

150 C 30 F B D 8L 152H C 30 F BD 43 8L

150 C 30 F B D 8L 152H C 30 F BD 43 8L ulletin SM - Smart Motor ontrollers atalog Number Explanation Open and Non-ombination F D L a b c d e f g a ulletin Number Solid-State ontroller b ontroller Type SM- c mpere s N F d Enclosure Type Open

More information

Specifications. Class R Blocks 250 V FLNR/FLNR_ID KLNR LLNRK TLN. Torque N-m (120 in-lbs) 2/0-6 AWG

Specifications. Class R Blocks 250 V FLNR/FLNR_ID KLNR LLNRK TLN. Torque N-m (120 in-lbs) 2/0-6 AWG LF Series lass H/K5 AND R Fuse Blocks Specifications Voltage : 250 V, 600 V Ampere s: 0 600 A Leakage urrent:

More information

HPS Universal BUCK-BOOST TRANSFORMERS

HPS Universal BUCK-BOOST TRANSFORMERS BUCK-BOOST TRANSFORMERS Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

Note: The let-through of the protective device must be equal to or less than the short-circuit current rating of the component being protected.

Note: The let-through of the protective device must be equal to or less than the short-circuit current rating of the component being protected. CONDUCTOR SHORT-CIRCUIT PROTECTION Introduction: This paper analyzes the protection of wire from fault currents. It gives the specifier the necessary information regarding the short-circuit current rating

More information

PANELBOARDS FACTORY SEALED CLASS I, DIVISION 2 CLASS I, ZONE 1. Save Installation Dollars - No Poured Seals Required!

PANELBOARDS FACTORY SEALED CLASS I, DIVISION 2 CLASS I, ZONE 1. Save Installation Dollars - No Poured Seals Required! Save Installation ollars - o Poured Seals Required! LSS I, IVISIO LSS I, ZOE TORY SELE PELORS actory Sealed, no External Seals required. ully Wired from Panelboard Enclosure to Terminal Enclosure. External

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection

More information

50AYA6A Product Details

50AYA6A Product Details Y6 Product etails MI/RFI Filters and ccessories lways U RoHS/LV ompliant (Statement of ompliance) Y6 (668-8) T Internal Number: 668-8 ctive Product Highlights: Filter - MI/RFI Filter Type = Power Line

More information

Open Type. SAO12b SAG12b Use Size 0 Use Size 0. SBO2b SBG2b SBW12b SBW22b

Open Type. SAO12b SAG12b Use Size 0 Use Size 0. SBO2b SBG2b SBW12b SBW22b www.schneider-electric.us SO, -Pole Starter ull Starters Rated lass 86 / Refer to atalog 80T70 eneral nformation S magnetic starters are used for full-voltage starting stopping squirrel cage motors. overload

More information

.062 [1.57] Commercial Pin and Socket Connectors

.062 [1.57] Commercial Pin and Socket Connectors .062 [1.57] ommercial Product Facts Polarized avity identification Low contact-mating force Dual locking lances Detent and positive locking ontacts available in brass and phosphor bronze with tin and gold

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Description & Applications Questions & Answers Selection Charts Single Phase Selection Charts Three Phase...

Description & Applications Questions & Answers Selection Charts Single Phase Selection Charts Three Phase... SECTION BUCK-BOOST TRANSFORMERS A simple and economical way to correct offstandard voltages... from 95 to 500 volts; single and three phase, in sizes up to 60 kva. Simplified buck-boost rating charts make

More information

CLASS H/K5 AND R SERIES FUSEBLOCKS

CLASS H/K5 AND R SERIES FUSEBLOCKS LASS H/K5 AND R SERIES FUSEBLOKS lip designs maximize electrical contact and minimize heat rise Standard reinforcing clips on all lass R fuseblocks and lass H fuseblocks rated 00 A and higher RoHS compliant,

More information

Heavy Duty Safety Switches

Heavy Duty Safety Switches eavy uty Safety Switches 240 Volt Class 110 Visible blade heavy duty safety switches are designed for application where maximum performance and continuity of service are required. All heavy duty safety

More information

Lead free RoHS compliant* Low profile package Surface mount Very low forward voltage drop

Lead free RoHS compliant* Low profile package Surface mount Very low forward voltage drop *RoHS OMPLINT eatures Lead free RoHS compliant* Low profile package Surface mount Very low forward voltage drop This series is currently available, but not recommended for new designs. The Model 23- Series

More information

ECL03B1AAA 20A 120V Lighting Contactor

ECL03B1AAA 20A 120V Lighting Contactor 80 South Street 7-7, TX Nacogdoches Phone: --71 Fax: -0-8 L01 0 V Lighting ontactor aton orp Number L01 Manufacturer aton orp escription Lighting ontactor, lectrically eld; Pole; 77/80 V (Filament Lamp),

More information

Overview The Thomas & Betts Method is Better. Just Four Easy Steps to a Perfect Connection! Step 1. Step 2

Overview The Thomas & Betts Method is Better. Just Four Easy Steps to a Perfect Connection! Step 1. Step 2 Overview The Thomas & Betts Method is Better. The Thomas & Betts method of installing compression connectors on power cables is designed to provide a high degree of reliability in electrical wiring. This

More information

lif flex CirCUit ConneCtor 2.54mm [.100"] CeNTerliNe 1.25mm [.049"] CeNTerliNe 1.00mm [.

lif flex CirCUit ConneCtor 2.54mm [.100] CeNTerliNe 1.25mm [.049] CeNTerliNe 1.00mm [. dam Technologies, Inc. INTRODUTION: dam Tech P Dual Series Port D-Sub Flexible onnectors Printed ircuit provide (FP) the and means Flexible to increase Flat able I/O (FF) without connectors utilizing are

More information

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations Bulletin LP NEMA AC Permanent Magnet-Latching Lighting Contactors Product Overview/Product Selection/Wiring Diagram A, -Pole Open Type without Enclosure Bulletin LP Top wiring permanent magnet latching

More information

SMAJ Transient Voltage Suppressor Diode Series

SMAJ Transient Voltage Suppressor Diode Series *RoHS OMPLINT eatures RoHS compliant* Surface Mount SM package Standoff Voltage: 5. to 495 volts Power issipation: 4 watts pplications I 6-4-2 S (Min. Level 4) I 6-4-4 T I 6-4-5 Surge SMJ Transient Voltage

More information

Regal Series Recessed Flatwalls

Regal Series Recessed Flatwalls Regal Series Recessed Flatwalls General Specifications The Amico Regal Series Recessed Flatwall shall be manufactured by Amico Corporation, in accordance with job specific shop drawings and documents.

More information

Article 225: Outside Branch Circuits And Feeders

Article 225: Outside Branch Circuits And Feeders Part C: Code Book Questions Article 225: Outside Branch Circuits And Feeders 1.! Open (individual) aerial overhead conductors shall be insulated or covered when within! feet of a building.! (a) 10! (c)

More information

The International Power Quality Resource

The International Power Quality Resource Type RF Filters Solve Noise Problems MT orporation type RF filters offer an economical solution to many facility interference problems caused by the high frequency emissions of adjustable speed motor drives

More information

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A DATASHEET - PKZM4-50 Delivery program Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection Part no. PKZM4-50 Catalog No. 222355 Eaton Catalog No. XTPR050DC1NL EL-Nummer 0004355161 (Norway)

More information

INSTALLATION INSTRUCTIONS 30" (76.2 CM) DROP-IN CERAMIC ELECTRIC RANGE

INSTALLATION INSTRUCTIONS 30 (76.2 CM) DROP-IN CERAMIC ELECTRIC RANGE INSTLLTION INSTRUTIONS 30" (76.2 M) ROP-IN RMI LTRI RN Table of ontents RN STY...1 INSTLLTION RQUIRMNTS...2 Tools and Parts...2 Location Requirements...2 lectrical Requirements...4 ountertop Preparation...4

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

B. Manufacturers: Square-D, G.E. or Westinghosue.

B. Manufacturers: Square-D, G.E. or Westinghosue. SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Nevco Indoor Accessory Driver IAD Installation Manual

Nevco Indoor Accessory Driver IAD Installation Manual Nevco Indoor ccessory river I Installation Manual Retain this manual in your permanent file. 0//7 5-00R Installation Instructions Installation consists of three steps: Unpacking the equipment, Indoor ccessory

More information

Datawave Magnetic Synthesizer

Datawave Magnetic Synthesizer POWER PROTECTION Datawave Magnetic Synthesizer 100 kva to 200 kva; 50 and 60 Hz Installation, Operation, & Maintenance Manual TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS............................................1

More information

G-Series Servomotors. AC Brushless Servomotors. Understanding the G-Series Servomotor Model Numbers

G-Series Servomotors. AC Brushless Servomotors. Understanding the G-Series Servomotor Model Numbers rushless Servomotors G-Series Servomotors ORME s G-series brushless servomotors provide high torque-to-inertia ratios and excellent continuous torque and peak torque performance in a compact design. These

More information

Bulletin 140U Molded Case Circuit Breakers

Bulletin 140U Molded Case Circuit Breakers Bulletin 40U Multitap End Cap Optional Optional Optional 40U-J-MTLA 40U-J-MTL6A 40U-J-ECM Aluminum Aluminum Molded Housing /4 screw /4 screw lb-in lb-in.6 N m.6 N m Cu/Al Cu/Al 60/7 C 60/7 C () (6) (A)

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012 SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM Unit Objectives Describe the structure of an atom. Identify atoms with a positive charge and atoms with a negative charge. Explain

More information

Warehouse Stock Transformers

Warehouse Stock Transformers Warehouse Stock s Warehouse Stock Buck-Boost Application Description and The Buck-Boost has four separate windings, two-windings in the primary and two-windings in the secondary. The unit is designed for

More information

VP VERSA-PAC Inductors and Transformers (Surface Mount)

VP VERSA-PAC Inductors and Transformers (Surface Mount) Supersedes arch 00 Product features Six winding, surface mount devices that offer more than 00 usable inductor or transformer configurations igh power density and low profile ow radiated noise and tightly

More information

Enclosed circuit breaker (ECB) with Arcflash Reduction Maintenance System

Enclosed circuit breaker (ECB) with Arcflash Reduction Maintenance System Technical Data TD008010EN Supersedes February 2016 Enclosed circuit breaker (ECB) with Arcflash Reduction Maintenance System The information below is taken directly from the National Electrical CodeT (NEC)

More information

Overview Special Lugs for Special Problems Angled, Shaped and Trimmed the Way You Need Them

Overview Special Lugs for Special Problems Angled, Shaped and Trimmed the Way You Need Them Special Lugs for Special Problems Angled, Shaped and Trimmed the Way You Need Them Thomas & Betts can solve your difficult wire bending and terminating problems in confined power distribution panels, switchgear

More information

SMAJ Transient Voltage Suppressor Diode Series

SMAJ Transient Voltage Suppressor Diode Series *RoHS OMPLINT eatures RoHS compliant* Surface Mount SM package Standoff Voltage: 5. to 495 volts Power issipation: 4 watts pplications I 6-4-2 S (Min. Level 4) I 6-4-4 T I 6-4-5 Surge SMJ Transient Voltage

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

AF91 Adjustable Frequency Drives Series B

AF91 Adjustable Frequency Drives Series B Effective: January, 00 Page New Information AF9 Adjustable Model AF9 Description Model AF9 Adjustable Frequency AC Drives are designed to provide adjustable speed control of -phase motors. These microprocessor-based

More information

LF SERIES CLASS R & H/K5 FUSE BLOCKS

LF SERIES CLASS R & H/K5 FUSE BLOCKS 250 V 00 V Specifications Description The Littelfuse Class R and H/K5 blocks offer many benefits such as indication, snap-to-release DIN rail mounting and universal mounting holes. Class H and Class R

More information

FAQ ON EARTHING STANDARDS 16/08/2018

FAQ ON EARTHING STANDARDS 16/08/2018 FAQ ON EARTHING STANDARDS 16/08/2018 This document has been updated to include changes made to substation earthing layouts that have been made necessary due to copper theft. The main changes to be aware

More information

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations Connecting the Power of the Sun DC Disconnects for Solar Photovoltaic Installations DC disconnects for solar photovoltaic installations Solar energy is heating up Interest in renewable energy sources has

More information

Insulated Thermocouple / Extension Wire

Insulated Thermocouple / Extension Wire How to read the catalog number chart leveland Electric Laboratories offers a complete line of insulated thermocouple and extension grade wires in single, duplex and multipair constructions. Ordering with

More information

PKZ 2 Manual Motor Protectors Technical Data

PKZ 2 Manual Motor Protectors Technical Data 08/066 PKZ 2 Manual Motor Protectors General Standards UL 508, CSA C 22.2 No. 14, IEC/EN 60 947, VDE 0660 GL, LR, DNV, PRS, BV, RINA, RS, EZU, MEEI Climatic proofing Damp heat, constant, to IEC 60 068-2-3

More information

3 - Protection components Circuit-breakers

3 - Protection components Circuit-breakers Contents - Protection components Circuit-breakers for the motor protection Selection guide..............................................page /2 Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

CDSOD323-TxxC-DSL - TVS Diode Series

CDSOD323-TxxC-DSL - TVS Diode Series *RoHS OMPLINT & **HLOGN R eatures n Protects one line or one I/O port n idirectional configuration n S protection 30 max. n Low capacitance ~ 3 p typ. n Replaces 0805 MLV devices n RoHS compliant* n Halogen

More information

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The

More information

DONGAN ELECTRIC MANUFACTURING CO.

DONGAN ELECTRIC MANUFACTURING CO. DONGAN ELECTRIC MANUFACTURING CO. Electric Manufacturing Co. 2987 FRANKLIN DETROIT, MI 48207 800.428.2626 313.567.8500 Spec Tech Industrial 203 Vest Ave Valley Park, MO 63088 FAX 313.567.8828 www.dongan.com

More information

NK Technologies Ground Fault Sensor. Instrument Transformer AC Current Transducers NEW SPECIFICATIONS

NK Technologies Ground Fault Sensor. Instrument Transformer AC Current Transducers NEW SPECIFICATIONS Instrument Transformer urrent Transducers Large Window rea 4-20m The PL is a 4 terminal device with separate connections for power and load. The PM is a two terminal device. 24V is applied between the

More information

TSB Suffix Suffix. 503Si 2 Suffix

TSB Suffix Suffix. 503Si 2 Suffix Catalog Numbering Code Europa locks TS 230 02 Suffix Suffix Series Europa locks Options (blank) = Standard (105 ) HT = High Temperature (150 ) US = 600V Pitch 230 = 8mm 500 = 10mm 500SK = 10mm, Elongated

More information

BUCK-BOOST TRANSFORMERS

BUCK-BOOST TRANSFORMERS Where Are Buck-Boost Transformers Used? A typical buck-boost application is 120 volts in, 12 volts out for low voltage lighting or control circuitry. In most applications, this low voltage transformer

More information

CHAPTER F0-08ADH-1 8-CH. ANALOG CURRENT INPUT. In This Chapter...

CHAPTER F0-08ADH-1 8-CH. ANALOG CURRENT INPUT. In This Chapter... F0-0H- -H. HPTER NLOG URRENT INPUT In This hapter... Module Specifications................................................ onnecting and isconnecting the Field Wiring........................... Wiring

More information

switch Switch Toggle 3-Way 15A 120V Grd WH

switch Switch Toggle 3-Way 15A 120V Grd WH 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 13037W Switch 3-Way 15 120V GR WH aton Wiring evices atalog Number Manufacturer escription Weight per unit Product ategory

More information

Waterpipe Ground Clamps. 1/2 in., 3/4 in., 1 or rebar /4 in., 1-1/2 in. or 2 in. 4 #6, #4, #2 AWG

Waterpipe Ground Clamps. 1/2 in., 3/4 in., 1 or rebar /4 in., 1-1/2 in. or 2 in. 4 #6, #4, #2 AWG Waterpipe Ground Ground Wire Size Water Pipe Size 2-T 1/2 in., 3/4 in., 1 or rebar 4-10 3-T 1-1/4 in., 1-1/2 in. or 2 in. 4 #6, #4, #2 WG 2-1/2 in., 3 in. or 3-1/2 in. 5-T 4 in., 4-1/2 in. or 5 in. 6 6

More information

POWER RELAYS CONTINUOUS DUTY, TYPE II, UNSEALED INTERMITTENT DUTY, TYPE III, UNSEALED

POWER RELAYS CONTINUOUS DUTY, TYPE II, UNSEALED INTERMITTENT DUTY, TYPE III, UNSEALED POWR RLYS INUOUS DUTY, TYP II, UNSLD INTRMITTNT DUTY, TYP III, UNSLD General Specifications Designed to MIL-R- - Type II Unsealed ontinuous Duty - Type III Unsealed Intermittent Duty - overed/gasketed

More information

ROHS DECLARATION OF CONFORMITY

ROHS DECLARATION OF CONFORMITY ROHS ELARATION OF ONFORMITY We ABB Entrelec onnection ivision 184 rue Léon Blum 69100 Villeurbanne France eclare that the product listed below fully comply with the provisions of EU irective(s) 2002/95/E

More information

COPALUM Terminals and Splices (For Solid & Stranded Aluminum or Copper Wire)

COPALUM Terminals and Splices (For Solid & Stranded Aluminum or Copper Wire) Product Facts Bar Crimp Technique Terminals and Splices for aluminum-to-aluminum and aluminum-to-copper stripped wire applications Terminates stripped, stranded and solid (round or rectangular) aluminum

More information

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5 Applied Grounding and Bonding Paul Dobrowsky Member NEC Panel 5 1 Introduction This presentation is a representative sample from the following Chapters of Applied Grounding and Bonding. Chapter 1, Introduction

More information

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA Contactor relay, 2N/O+2N/C, AC Part no. DILA-22(24V60HZ) Catalog No. 276390 Eaton Catalog No. XTRE10B22B6 Delivery program Product range DILA relays Application Contactor relays Description Basic devices

More information

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014

More information

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA DATASHEET - DILA-22(230V50HZ,240V60HZ) Delivery program Contactor relay, 2N/O+2N/C, AC Part no. DILA-22(230V50HZ,240V60HZ) Catalog No. 276399 Eaton Catalog No. XTRE10B22F EL-Nummer 0004130208 (Norway)

More information

PCR Polarization Cell Replacement. The Polarization Cell Replacement (PCR) Technical Literature COMMON APPLICATIONS

PCR Polarization Cell Replacement. The Polarization Cell Replacement (PCR) Technical Literature COMMON APPLICATIONS The Polarization Cell Replacement (PCR) Technical Literature INTRODUCTION The Polarization Cell Replacement (PCR) is a solid-state device commonly used in conjunction with cathodically protected structures.

More information

FLEXIBLE POWER & GROUNDING. Braid Solutions

FLEXIBLE POWER & GROUNDING. Braid Solutions FLEXIBLE POWER & GROUNDING Braid Solutions Flexible Grounding and Power Options One of our signature products, BURNDY Braid Assemblies are an economical and efficient means of protecting electrical equipment

More information

Open Type Without Enclosure

Open Type Without Enclosure Bulletin L NEMA AC Electrically Held Lighting Contactors Product Selection Top Wiring for Non-Motor and Lighting Loads Tungsten Lamp Loads (Max. V Line, V Load) Maximum Continuous Ampere Ratings [A] General

More information

For Immediate Delivery call KMParts.com at (866)

For Immediate Delivery call KMParts.com at (866) Return To MAIN INDEX Magnetic Contactors, Overview / Contactors DIL...M Contactors AC Operated AC Operated, Reversing DC Operated AC/DC Operated, DC Hp ratings / /6 /8 / Starters DIL Universal Contactors

More information

22 22, 24, , 18, AWG. 50 ohm 50 ohm. 75 ohm 75 ohm. 95 ohm 95 ohm

22 22, 24, , 18, AWG. 50 ohm 50 ohm. 75 ohm 75 ohm. 95 ohm 95 ohm ircular onnectors MR 4 Series onnectors General Information high density (.080 [2.0] contact centers), lightweight, subminiature, cylindrical connector series featuring crimp contacts and fingertip, push-pull,

More information

Rectangular Metal Case Paper / Polyester Foil Capacitors

Rectangular Metal Case Paper / Polyester Foil Capacitors Rectangular Metal Case Type CQ72 C Voltage Range: 400 VC to 12,500 VC Capacitance Tolerance: K±10% Operating Temperature: Characteristic E -65 C to +85 C Characteristic F -55 C to +85 C Characteristic

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web: Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation

More information

Bulletin 1497 Global Control Transformers

Bulletin 1497 Global Control Transformers Bulletin 1497 Global Control Transformers Bulletin 1497 Global Control Circuit Transformers Bulletin 1497 Global Control Circuit Transformers are designed to reduce supply voltages to control circuits.

More information

Review 6. unlike poles cause the magnets to attract. like poles cause the magnets to repel.

Review 6. unlike poles cause the magnets to attract. like poles cause the magnets to repel. Review 6 1. The two characteristics of all magnets are: they attract and hold Iron, and, if free to move, they will assume roughly a south - north position. 2. Lines of flux always leave the north pole

More information

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit. ECET4520 Exam II Sample Exam Problems Instructions: This exam is closed book, except for the reference booklet provided by your instructor and one (8.5 x11 ) sheet of handwritten notes that may not contain

More information

High-current terminal block - UKH

High-current terminal block - UKH Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid

More information

J7M-AM/-BM. Motor--protective circuit--breaker system. J7M -BM System IEC 947, EN IEC 947, EN 60947

J7M-AM/-BM. Motor--protective circuit--breaker system. J7M -BM System IEC 947, EN IEC 947, EN 60947 Motor--protective circuit--breaker system J7M -AM System Rated operational current 25 A. Switching capacity up to 10 A, 100 ka/415 V. Switching capacity 16 A, 20 A, 25 A, 16 ka/415 V. Fixed short--circuit

More information

C440 NEMA Electronic Overload

C440 NEMA Electronic Overload Instructional Leaflet IL010001E Effective July 2010 Supersedes June 2010 440 NEM Electronic Overload - Self Powered UNIT STTUS angerous Electrical urrent! Only skilled qualified persons may carry out the

More information

3.6. Control Relays and Timers D A M D 2. Contents. Product Overview. Catalog Number Selection. Solid-State Relays

3.6. Control Relays and Timers D A M D 2. Contents. Product Overview. Catalog Number Selection. Solid-State Relays .6 Control Relays and Timers Product Overview Catalog Number Selection D9, D96 and D99 Series Description D9 = Hockey puck D96 = Compact D99 = DIN rail Contents D 9 2 5 A M D 2 Output Voltage 1 = 2 60

More information

NOVA-TS Triple-Single Recloser and Form 5/TS Control Frequently Asked Questions

NOVA-TS Triple-Single Recloser and Form 5/TS Control Frequently Asked Questions NOVA-TS Triple-Single Recloser and Form 5/TS Control Frequently Asked Questions How To Use This Publication This document (Bulletin 99068) contains detailed product and application information and provides

More information

Data Sheet. Earth Leakage Relay RISH ELR/ELR+/ELR VI/ELR VI(NE) A V RISH ELR VI. Record. Digital Protection Relay RESET TEST ENTER

Data Sheet. Earth Leakage Relay RISH ELR/ELR+/ELR VI/ELR VI(NE) A V RISH ELR VI. Record. Digital Protection Relay RESET TEST ENTER ata Sheet arth eakage Relay RISH R/R+/R VI/R VI() RISH R VI 8.8. 8. 8. V R-1 R-2 igital Protection Relay K RST TST TR nalyze ata Sheet arth eakage Relay RISH R RISH arth eakage Relay is used to etect and

More information

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection: Utility Systems Technologies, Inc. Sag Fighter TM Deep Voltage Sag Protection: D e e p Vo l t a g e S a g P r o t e c t i o n For three phase application: Q u a l i t y P o w e r. B e t t e r B u s i n

More information

CDSOT23-T24CAN CANbus Protector

CDSOT23-T24CAN CANbus Protector *RoHS OMPLINT 2801L eatures n Single device for two I/O lines n Low capacitance for high-speed Nbus n I 61000-4-2 30 kv S n I 61000-4-5 (Level 1, WG 1.2/50) 500 V Surge n RoHS compliant* pplications n

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

System Components and Accessories

System Components and Accessories OutBack Panel Mount Breakers Panel mounted hydraulic-magnetic type breakers that can be used for DC sources, inverters or load circuits. Model Current Voltage Branch Terminals Width Rating Rating Circuit

More information

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition Jake Leahy s Electrical Code Connection A look at Grounding and Bonding of Electrical Services Article 250 2014 Florida Building Code 5 th Edition Wiring Integrity. Completed wiring installations shall

More information

Reduced Voltage Starters

Reduced Voltage Starters Reduced Voltage Starters ontrolled starting for low in-rush and smooth operation Sprecher + Schuh reduced voltage starters are designed for starting squirrel cage induction motors where the starting current

More information

IMCjr Hardware Manual for models IMJ-307_-X-D IMJ-31L_-4-D. Pub 330R6. A publication of

IMCjr Hardware Manual for models IMJ-307_-X-D IMJ-31L_-4-D. Pub 330R6. A publication of IMCjr Hardware Manual for models jr IMJ-105_-1-D IMJ-313_-X-D IMJ-314_-X-D IMJ-304_-X-D IMJ-317_-X-D IMJ-307_-X-D IMJ-317_-4-D IMJ-31G_-2-D IMJ-31T_-2-D IMJ-31L_-4-D Pub 330R6 A publication of 1050 Highland

More information

Reduced Voltage Starters

Reduced Voltage Starters Reduced Voltage Starters ontrolled starting for low in-rush and smooth operation Sprecher + Schuh reduced voltage starters are designed for starting squirrel cage induction motors where the starting current

More information

Single, dual, and multi-tap primary voltages Single phase EN finger-safe protection RoHS compliant 1497 A M1 3 N

Single, dual, and multi-tap primary voltages Single phase EN finger-safe protection RoHS compliant 1497 A M1 3 N Bulletin Product Overview/Catalog Number Explanation Cat. No. -B-HXJX--N Control Circuit Transformer, - pole with Optional Cat. No. -R Fuse Cover Cat. No. -C-BASX--N Control Circuit Transformer, Non-Fused

More information

Solid-State Soft Starters

Solid-State Soft Starters Selection and ordering data Rated operational voltage U e V Soft starters for three-phase asynchronous motors 3RW30 25-1B14 3RW30 35-1B14 t ambient temperature 40 C Size Order No. Price Weight Pack. Rated

More information

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz POWER QUALITY INSTRUCTION MANUAL Type SWF Sine Wave Filters 690 Volts, 50Hz Page 2 of 24 Contents 1. Introduction & SAFETY 2. Theory of operation 3. Typical results of the Sine Wave Filters 4. Transportation,

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information