Power Quality and Harmonic :Causes and Effects with Paper Mill Factory

Size: px
Start display at page:

Download "Power Quality and Harmonic :Causes and Effects with Paper Mill Factory"

Transcription

1 Power Quality and Harmonic :Causes and Effects with Paper Mill Factory Danaisak Tangsakha PEA Thailand Provincial Electricity Authority, Thailand 1

2 Topics Introduction Power Quality standard Single line diagram Results Power Quality Assessment Relationships in Power Quality Monitoring Systems Simulation Model Conclusion Q&A Provincial Electricity Authority, Thailand 2

3 What is Harmonics Voltage? A sinusoidal voltage with a frequency equal to an integer multiple of the fundamental frequency of the supply voltage (EN50160) Order 3 : 3 50 Hz = 150 Hz Provincial Electricity Authority, Thailand 3

4 Where is the source of the harmonics? Other loads Other loads Harmonic current flow (a) Power flow at the fundamental frequency Three-phase voltage and current measurements Motors and all other linear loads Nonlinear Load PF Correction Capacitor Banks (b) Harmonic power flow Provincial Electricity Authority, Thailand 4

5 Parallel vs Series resonance 132 kv level if f r = f Xc 0 Ic I 11 kv level Transformer 1000 kva, u k = 5 % I Transformer 630 kva, u k = 5 % 415 V level Parallel resonance Series resonance 415 V level I DC drive 600 kw cos = Capacitor bank kw cos = Capacitor bank Provincial Electricity Authority, Thailand 5

6 Parallel vs Series resonance Provincial Electricity Authority, Thailand 6

7 Power Quality standard Point of Common Coupling : PCC (kv) Total Harmonic Distortion Voltage THDv (%) Individual Harmonic Distortion Voltage(%) Odd Even ,12,22 and and above Harmonic : referring to PRC-PQG-01/1998 Provincial Electricity Authority, Thailand 7

8 Power Quality standard Point of Common Coupling : PCC (kv) Pst Plt Below 115 kv More than 115 kv Pst ; Short-Term Severity Values (10 minutes) Plt : Long-Term Severity Values (2 hours) Voltage fluctuation : referring to PRC-PQG-02/1998 Provincial Electricity Authority, Thailand 8

9 Paper Mill Factory Paper Mill(F6) Provincial Electricity Authority, Thailand 9

10 Paper Mill Factory Provincial Electricity Authority, Thailand 10

11 Paper Mill Factory : Survey Paper Mill Machine - DC Motor 200 hp - DC Inverter 6 pulse Provincial Electricity Authority, Thailand 11

12 Single line Diagram Provincial Electricity Authority, Thailand 12

13 Power Quality monitoring Provincial Electricity Authority, Thailand 13

14 Results Table 1 Power Quality Assessment at M1 Provincial Electricity Authority, Thailand 14

15 Results Table 2 Harmonics Current at M1 Provincial Electricity Authority, Thailand 15

16 Relationships in Power Quality Monitoring Systems Supply Voltage Variations Provincial Electricity Authority, Thailand 16

17 Relationships in Power Quality Monitoring Systems Supply Voltage Frequency Provincial Electricity Authority, Thailand 17

18 Relationships in Power Quality Monitoring Systems %THDv 4% < Normal Operation Provincial Electricity Authority, Thailand 18

19 Relationships in Power Quality Monitoring Systems Effect with Paper Mill %THDv 4% < Normal Operation %THDv >5% Provincial Electricity Authority, Thailand 19

20 Simulation Model Provincial Electricity Authority, Thailand 20

21 Simulation Model Full Load With out Cap Provincial Electricity Authority, Thailand 21

22 Simulation Model Full Load On Cap Provincial Electricity Authority, Thailand 22

23 Simulation Model Current Waveform Voltage Waveform Provincial Electricity Authority, Thailand 23

24 Simulation Model Provincial Electricity Authority, Thailand 24

25 Simulation Model Load 50% On Cap Provincial Electricity Authority, Thailand 25

26 Simulation Model Current Waveform Voltage Waveform Provincial Electricity Authority, Thailand 26

27 Simulation Model Provincial Electricity Authority, Thailand 27

28 The popular solutions Structural modification - change size or location of capacitor, transformer connection in 12-Pulse converter Third Harmonic Filter in neutral wire (Blocking Filter) in electrical system not allowed in some countries Detuned filter most popular Tuned filter classical but lots of limitations Active filter most effective but still high investment Provincial Electricity Authority, Thailand 28

29 How to choose? in LV Low harmonics Medium harmonics High harmonics Don t worry Parallel resonance Need filtering Install plain capacitors Install detuned filter Install Tune/active filter 29

30 Conclusion Power Quality issues in MDB01 caused by Parallel Resonance by transformer and capacitor bank to become Parallel Resonance from harmonic source. Due to power quality monitoring, it should install Active Filter to reduce harmonic and most effective but still high investment. Provincial Electricity Authority, Thailand 30

31 Q&A Provincial Electricity Authority, Thailand 31

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic

More information

Power Factor & Harmonics

Power Factor & Harmonics Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics

More information

7/15/2002 PP.AFD.08 1 of 28

7/15/2002 PP.AFD.08 1 of 28 Power Quality Considerations When Applying Adjustable Frequency Drives Explanations and Various Countermeasures 7/15/2002 PP.AFD.08 1 of 28 Power Quality Why the Renewed Interest in Power Quality? Copy

More information

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*

More information

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

FAQ for SIMOREG 6RA70 and Control Module

FAQ for SIMOREG 6RA70 and Control Module I DT LD CS 28 / February / 2011 FAQ for SIMOREG 6RA70 and Control Module Question: What requirements apply for line quality and what line interference can occur? Answer: Line requirements: Voltage: rated

More information

NJWA - Harmonics and Drives Proper System Design

NJWA - Harmonics and Drives Proper System Design Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives

More information

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax: POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION

More information

Understanding Input Harmonics and Techniques to Mitigate Them

Understanding Input Harmonics and Techniques to Mitigate Them Understanding Input Harmonics and Techniques to Mitigate Them Mahesh M. Swamy Yaskawa Electric America YASKAWA Page. 1 Organization Introduction Why FDs Generate Harmonics? Harmonic Limit Calculations

More information

Reduce harmonics in HVAC&R inverters through C-Less technology

Reduce harmonics in HVAC&R inverters through C-Less technology Reduce harmonics in HVAC&R inverters through C-Less technology Karim Lamrabtine Global Product Manager VSD 14-15 SEPTEMBER 2011, MUNICH Agenda www.infoplc.net What are Harmonics? Standards Compliance How

More information

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to

More information

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution Agenda I. Harmonic Basics II.Harmonic Mitigation Solutions III.Case Study 2 Harmonic

More information

POWER QUALITY ASSESSMENT AND MITIGATION AT WALYA-STEEL INDUSTRIES AND ETHIO-PLASTIC SHARE COMPANY

POWER QUALITY ASSESSMENT AND MITIGATION AT WALYA-STEEL INDUSTRIES AND ETHIO-PLASTIC SHARE COMPANY POWER QUALITY ASSESSMENT AND MITIGATION AT WALYA-STEEL INDUSTRIES AND ETHIO-PLASTIC SHARE COMPANY Mengesha Mamo and Adefris Merid School of Electrical and Computer Engineering Addis Ababa Institute of

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk. , 2011;4(12) Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces H.A. Khalik, M. A. Aziz, and E. Farouk. Electrical power and Machines Engineering

More information

Voltage-controlled active filter gives standby generator power quality

Voltage-controlled active filter gives standby generator power quality Seite 1 von 5 Voltage-controlled active filter gives standby generator power quality Nowadays, nearly all the consumers connected to the electricity supply network constitute non-linear loads. Their non-sinusoidal

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

SHARDA Make Harmonics Filter

SHARDA Make Harmonics Filter SHARDA Make Harmonics Filter SHARDA offers perfect solution to minimize Harmonics level of industries where non-linear load like, VFD, Electronics load, Convertors, Voltage booster equipment s are present.

More information

LV Compensation & Filtering Products

LV Compensation & Filtering Products GE Grid Solutions LV Compensation & Filtering Products Providing Power Quality and Energy Efficiency Low (LV) reactive power compensation and harmonic filtering solutions help customers to improve the

More information

Harmonic Distortion and Variable Frequency Drives

Harmonic Distortion and Variable Frequency Drives Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation

More information

Southern Company Power Quality Policy

Southern Company Power Quality Policy Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...

More information

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008 Welcome to the rd Annual Northern Ohio 3 rd Energy Management Conference September 30, 2008 Recover Lost Dollars Demand Side Electrical Energy Savings By Improving Distribution System Efficiency, Capacity

More information

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD Scientific Journal of Impact (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 04, April -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 ANALYSIS AND

More information

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics

More information

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS. MAIN TOPICS DISCUSSED Electric Rates Electrical system utilization ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K Power quality Harmonics Power factor (Cos phi) improvement Section K - 2 ELECTRIC

More information

ISSN: ISO 9001:2008 Certified International Journal of Engineering and Innovative Technology (IJEIT) Volume 5, Issue 11, May 2016

ISSN: ISO 9001:2008 Certified International Journal of Engineering and Innovative Technology (IJEIT) Volume 5, Issue 11, May 2016 Power Loss Minimization In Distribution System Using Static VAR Compansator Mohamed Hussien Zahran, Hamdy A. M. Shatla, Salama Abo_Zead Dept. of Electrical Engineering, Al-Azhar University, Cairo, Egypt

More information

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017 Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates

More information

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives 2 TECHNICAL GUIDE NO. 6 GUIDE TO HARMONICS WITH AC DRIVES Guide to harmonics This guide is part of ABB s technical guide series, describing

More information

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,

More information

Economical Solutions to Meet Harmonic Distortion Limits[4]

Economical Solutions to Meet Harmonic Distortion Limits[4] Economical Solutions to Meet Harmonic Distortion Limits[4] Abstract: The widespread adoption of variable frequency drive technology is allowing electricity to be utilized more efficiently throughout most

More information

Harmonics. Craig Hartman, P.E. VFDs, Generators & IEEE 519

Harmonics. Craig Hartman, P.E.   VFDs, Generators & IEEE 519 www.emcsolutions.com Harmonics VFDs, Generators & IEEE 519 Craig Hartman, P.E. Specializing in Motors, Drives, Generators, and Electrical Asset Management The Great Horse Manure Crisis of 1894 New York

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

16B2011B1 EASY HARMONICS USER MANUAL

16B2011B1 EASY HARMONICS USER MANUAL 6B0B Issued on 03/08/09 R.00 English This manual is integrant and essential to the product. Carefully read the instructions contained herein as they provide important hints for use and maintenance safety.

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

AccuSine PCS Active Harmonic Filter. Cruise through rough waves in your electrical network

AccuSine PCS Active Harmonic Filter. Cruise through rough waves in your electrical network AccuSine PCS Active Harmonic Filter Cruise through rough waves in your electrical network How Can Active Harmonic Filters Solve Power Quality Issues in Your Facility? Power electronic devices that have

More information

Case Study 38 Reduction in Break Down and Specific Energy Consumption by Reducing Harmonics at Usha Martin Wire Rope Plant.

Case Study 38 Reduction in Break Down and Specific Energy Consumption by Reducing Harmonics at Usha Martin Wire Rope Plant. CS 38 ENRG 14 Reduction in Break Down and Specific Energy Consumption by Reducing Harmonics at a Steel Wire Rope Plant APQI (C) Copyright (2013) All Rights Reserved 1 target of reducing energy consumption

More information

How adjustable speed drives affect power distribution

How adjustable speed drives affect power distribution How adjustable speed drives affect power distribution Application Note Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality. ASDs as victim loads Although ASDs are usually

More information

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY Approximation based on the know-how of SEMAN S.A. The non-linear nature of modern electric loads makes the reception of measures for the confrontation

More information

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder R. W. Erickson Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder 16.4. Power phasors in sinusoidal systems Apparent power is the product of the rms voltage and

More information

Welcome. Power Survey International

Welcome. Power Survey International Welcome Company profile Established since 1948 Manufacturer of low and medium voltage products: Power Factor correction system Harmonic Filter system Steel Cabinet customized to your needs Other products

More information

Analysis of Harmonic Distortion in Non-linear Loads

Analysis of Harmonic Distortion in Non-linear Loads Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna

More information

Examples Paper 3B3/4 DC-AC Inverters, Resonant Converter Circuits. dc to ac converters

Examples Paper 3B3/4 DC-AC Inverters, Resonant Converter Circuits. dc to ac converters Straightforward questions are marked! Tripos standard questions are marked * Examples Paper 3B3/4 DC-AC Inverters, Resonant Converter Circuits dc to ac converters! 1. A three-phase bridge converter using

More information

Harmonic Distortion Evaluations

Harmonic Distortion Evaluations Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion

More information

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric

More information

PART 1 OWNER/APPLICANT INFORMATION

PART 1 OWNER/APPLICANT INFORMATION CALHOUN COUNTY ELECTRIC COOP. ASSN. Application for Operation of Customer-Owned Generation This application should be completed as soon as possible and returned to the Cooperative in order to begin processing

More information

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN Eugenio PEREA*, Eduardo ZABALA*, J. Emilio RODRÍGUEZ*, Asier GIL DE MURO*, Hugo GAGO * * * Fundación LABEIN,

More information

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar. Technical Report on Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by Dr. V. R. Kanetkar (February 2015) Shreem Electric Limited (Plot No. 43-46, L. K. Akiwate

More information

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives ABB drives Technical guide No. 6 Guide to harmonics with AC drives 2 Guide to harmonics with AC drives Technical guide No. 6 Technical guide No. 6 Guide to harmonics with AC drives Copyright 2013 ABB.

More information

Power Quality Monitoring:

Power Quality Monitoring: Power Quality Monitoring: Analyse and Improve your Energy Performance Presented by: David Bradley B.Eng (Hons), MBA, C.Eng, MIET Energy Management & Power Quality Key Drivers PART L The energy efficiency

More information

Power Analysis Summary

Power Analysis Summary Power Analysis Summary Introduction This is a summary of the power conditions measured with these setup parameters: Measurement File: C:\Users\fhealy\Documents\Fluke\Power Analyze\Core 2 Recording.odn

More information

Application of Reactive Compensation equipment in industrial systems under aspects of harmonics and switching transients: A study of real case

Application of Reactive Compensation equipment in industrial systems under aspects of harmonics and switching transients: A study of real case Application of Reactive Compensation equipment in industrial systems under aspects of harmonics and switching transients: A study of real case Patrick Roberto de Almeida BREE patrick.almeida@bree.com.br

More information

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

DETUNED INDUCTORS FOR PF IMPROVEMENT CAPACITORS

DETUNED INDUCTORS FOR PF IMPROVEMENT CAPACITORS DETUNED INDUCTORS FOR PF IMPROVEMENT CAPACITORS Electrical supply systems harmonics is like a cancer on supply systems and causes extreme bad effects on the supply system component and connected electrical

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

APPLICATION NOTE. Applying Type DD60 Capacitors in Harmonic Filter Applications. Total Power Factor PF = cosine ɸ

APPLICATION NOTE. Applying Type DD60 Capacitors in Harmonic Filter Applications. Total Power Factor PF = cosine ɸ APPLICATION NOTE SEPTEMBER 12, 2017 F-AN-001 FRAKO North America W67N222 Evergreen Bvd Suite 209 Cedarburg, WI 53012 Phone: 1-262-618-2403 Fax: 1-262-618-2303 www.frako.de Applying Type DD60 Capacitors

More information

Do You Have a Harmonic Problem?

Do You Have a Harmonic Problem? ??????? Do You Have a Harmonic Problem? Forster Electrical Engineering, Inc. 550 N. Burr Oak Ave, Oregon, WI 53575 (608) 835-9009 (608) 835-9039 fax 1 March 1999 What is THD? Total Harmonic Distortion

More information

POWER FACTOR CORRECTION AND ITS PITFALLS

POWER FACTOR CORRECTION AND ITS PITFALLS Technical Note No. May 1999 POWER FACTOR CORRECTION AND ITS PITFALLS This Technical Note considers power factor correction as applied by large customers and the possible consequences when power factor

More information

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems This application should be completed as soon as possible and returned to the Cooperative in order to

More information

How Harmonics have led to 6 Power Factor Misconceptions

How Harmonics have led to 6 Power Factor Misconceptions Harmonic and Energy Saving Solutions How Harmonics have led to 6 Power Factor Misconceptions Tony Hoevenaars, P.Eng. Power Factor Misconceptions 1. Low power factor is normally caused by electric motors

More information

Effective Harmonic Mitigation with Active Filters

Effective Harmonic Mitigation with Active Filters Advancing Power Quality White Paper Effective Harmonic Mitigation with Active Filters Written by: Ian Wallace Variable Speed Drive with no Harmonic Mitigation Industry standard variable speed drives, with

More information

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE - 519 Solutions Harmonics Tutorial 1 Power Conversion Equipment can save energy and control motors, heaters,

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions Issue #65 - December 2012 Technical News Industrial Electrical and Automation Products, Systems and Solutions Part 2: Harmonics The link between harmonics and power factor Written by Justin Charlot Product

More information

Fluke 40/41 Power Harmonics Analysers

Fluke 40/41 Power Harmonics Analysers Data Pack A Issued March 2002 232-4752 Fluke 40/41 Power Harmonics Analysers This data sheet refers to the Fluke 40 and Fluke 41 Power Harmonics Analysers. RS stock no. Description 215-9621 Fluke 41B power

More information

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation This application is to be completed and returned to the Cooperative member service representative in order to begin

More information

Reactors for filtering

Reactors for filtering NEW ZEALAND WWW.LPINZ.CO.NZ Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box 21-872, Henderson, Auckland, New Zealand Phone:+64 9 833 5749 Email:info@LPINZ.co.nz Web: www.lpinz.co.nz Reactors

More information

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. 1 PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. DEFINATIONS Working /Active Power: Normally measured in kilowatts (kw). It does the "work" for the system--providing the motion, torque,

More information

ZENER ELECTRIC PTY LTD

ZENER ELECTRIC PTY LTD ACN 00 595 428 APPLICATION NOTE: IM 0002 Revision -, June 996 Effective: 24/06/96 Topic: Mains Harmonic Disturbance and Variable Speed AC-Drives Introduction Most common industrial variable speed drives

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

Harmonic Filters for Single Phase Equipment

Harmonic Filters for Single Phase Equipment POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics

More information

DATA SHEET POWER CAPACITOR

DATA SHEET POWER CAPACITOR Issued August 2009 10470 DATA SHEET POWER CAPACITOR General Data * POWER FACTOR CORRECTION The power factor of a load is defined as the ratio of active power to apparent power, i.e. kw : kva and is referred

More information

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative:  Address: Fax Number: Interconnection of a Customer-Owned Renewable Generation System of Greater than 100 KW and Less than or Equal to 1 MW to the LCEC Electric Grid Tier 3 Application and Compliance Form Instructions: Complete

More information

Emicon Engineering Consultants L.L.C.

Emicon Engineering Consultants L.L.C. Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com

More information

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM Liebert AF2 Next Generation Active Harmonic Filter Power Protection for Business-Critical Continuity TM LIEBERT AF2 You Need To Be Aware Of Harmonics During the last few years industries has witnessed

More information

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation UPEC21 31st Aug - 3rd Sept 21 Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation H. M. Zubi IET and IEEE member hz224@bath.ac.uk R. W. Dunn IEEE member E-mail r.w.dunn@bath.ac.uk

More information

LINEATOR. Advanced Universal Harmonic Filter

LINEATOR. Advanced Universal Harmonic Filter R International Inc. LINEATOR Patented Revolutionary New Reactor esign Advanced Universal Harmonic Filter Wide Spectrum Harmonic Filter for treatment of all harmonics generated by 3-phase diode or thyristor

More information

ABB n.v. Power Quality Products, October 2014

ABB n.v. Power Quality Products, October 2014 ABB n.v. Power Quality Products, October 2014 Power Quality Harmonic Basics Problems and solutions March 19, 2015 Slide 1 828m high 160 floors in total Total 113 PQF in this tower, 12000A PQFS 45M IP30

More information

Grid tied inverter. Reference test report: Issued by TÜV Rheinland Italia S.r.l. on 19 th Janury 2015

Grid tied inverter. Reference test report: Issued by TÜV Rheinland Italia S.r.l. on 19 th Janury 2015 Seite 1 von 5 Page 1 of 5 Type of System: System Manufacturer: Manufacturer data: Grid tied inverter Power-One Italy S.p.A. Via S. Giorgio 642, 52028 Terranuova Bracciolini (AR) - Italy Reference test

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

McGill Power Sales & Engineering, INC.

McGill Power Sales & Engineering, INC. 1 McGill Power Sales & Engineering, INC. Power Factor Correction Terry McGill President McGill Power Sales & Engineering Inc. 2007 Eaton Corporation. All rights reserved. Agenda What is power factor? What

More information

Harmonic Filtering in Variable Speed Drives

Harmonic Filtering in Variable Speed Drives Harmonic Filtering in Variable Speed Drives Luca Dalessandro, Xiaoya Tan, Andrzej Pietkiewicz, Martin Wüthrich, Norbert Häberle Schaffner EMV AG, Nordstrasse 11, 4542 Luterbach, Switzerland luca.dalessandro@schaffner.com

More information

ENA Engineering Recommendation G59/3 Type Verification Test Report

ENA Engineering Recommendation G59/3 Type Verification Test Report ref. PVI-4.2(3.6)(3.0)-TL-OUTD & Derived Models (UK G59/3 Type Verification Test Report) ENA Engineering Recommendation G59/3 Type Verification Test Report Type Approval and manufacturer/supplier declaration

More information

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1 LV PFC Basics Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1 What are the different types of loads? Ohmic loads Lighting bulbs Iron Resistive heating Capacative loads Capacitors Underground

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

MASTER S THESIS. Effects of Imbalances and Non-linear Loads in Electricity Distribution System

MASTER S THESIS. Effects of Imbalances and Non-linear Loads in Electricity Distribution System FACULTY OF TECHNOLOGY LUT ENERGY ELECTRICAL ENGINEERING MASTER S THESIS Effects of Imbalances and Non-linear Loads in Electricity Distribution System Examiners Supervisor Prof. Jarmo Partanen M.Sc. Oleg

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV 6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV SOLIDSTATE CONTROLS, INC. Solidstate Controls Incorporated 875 Dearborn Drive Columbus, Ohio 43085 Tel : (614) 846-7500 Fax: (614) 885-3990 6L]LQJ $ 836 6\VWHP )RU 1RQ/LQHDU

More information

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System WHO SHOULD FILE THIS SUBMITTAL: Anyone in the final stages of interconnecting a Generation System with Nodak Electric Cooperative, Inc. This submittal shall be completed and provided to Nodak Electric

More information

Harmonic Analysis and Power Factor Correction For Food Processing Industry

Harmonic Analysis and Power Factor Correction For Food Processing Industry International Journal of Computational Engineering Research Vol, 03 Issue, 6 Harmonic Analysis and Power Factor Correction For Food Processing Industry Rupali Shinde 1, Amit Pathak 2, Bhakti Chaughule

More information

Thailand Integrates Large-Scale Wind Farms

Thailand Integrates Large-Scale Wind Farms PQSynergy 2016 Thailand Integrates Large-Scale Wind Farms Chakphed Madtharad, Ph.D. Provincial Electricity Authority (PEA) http://tdworld.com/renewables/thailand-integrates-large-scale-wind-farms PEA May

More information

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics Reactive Power and Harmonic Compensation Guide to Harmonics POWER QUALITY The Basics of Harmonics All business types, commercial, industrial, government and energy/utility have a concern with power quality.

More information

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company Engineering data submittal Page 1 WHO SHOULD FILE THIS SUBMITTAL : Anyone in the final stages of in terconnecting a Generation System with Otter Tail Power. This submittal shall be completed and provided

More information

Harmonic Requirements

Harmonic Requirements Chapter 1 Harmonic Requirements 1.1 INTRODUCTION Placing limits upon the effects that nonlinear loads may produce on users of electric power requires definition of system and equipment parameters. The

More information

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation R. S. Al Abri, M. H. Albadi, M. H. Al Abri, U. K. Al Rasbi, M. H. Al Hasni, S. M. Al Shidi Abstract This paper presents an analysis

More information

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards Indian Journal of Science and Technology, Vol 9(30), DOI: 10.17485/ijst/2016/v9i30/99034, August 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 A Power Quality Survey on a 22 kv Electrical Distribution

More information

CHAPTER 4 HARMONICS AND POWER FACTOR

CHAPTER 4 HARMONICS AND POWER FACTOR 4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried

More information

Harmonics White Paper

Harmonics White Paper Harmonics White Paper New Breakthrough In PWM Drives Technology Reduces Input Line Harmonics Without the Use of Filtering Devices Harmonic Distortion Damages Equipment and Creates a Host of Other Problems

More information