ENA Engineering Recommendation G59/3 Type Verification Test Report
|
|
- Valerie Clark
- 5 years ago
- Views:
Transcription
1 ref. PVI-4.2(3.6)(3.0)-TL-OUTD & Derived Models (UK G59/3 Type Verification Test Report) ENA Engineering Recommendation G59/3 Type Verification Test Report Type Approval and manufacturer/supplier declaration of compliance with the requirements of Engineering Recommendation G59/3 Type Test reference number Generating unit technology System Supplier name Address PVI-3.6-TL-OUTD PVI-4.2-TL-OUTD PVI-3.0-TL-OUTD-S PVI-3.6-TL-OUTD-W PVI-4.2-TL-OUTD-W PHOTOVOLTAIC and WIND GRID TIED INVERTER Power-One Italy S.p.A. Via S. Giorgio, Terranuova Bracciolini Arezzo - Italy PVI-3.0-TL-OUTD PVI-3.6-TL-OUTD-S PVI-4.2-TL-OUTD-S PVI-3.0-TL-OUTD-W Tel Fax E:mail service@power-one.com Web site Connection Option Nominal / Maximum rated capacity 4,2 / 4,6 kw single phase (for PVI-4.2 series) 3,6 / 4,0 kw single phase (for PVI-3.6 series) 3,0 / 3,3 kw single phase (for PVI-3.0 series) We, Power-One Italy S.p.A., as manufacturer/supplier of Generating Unit, certifies that all products manufactured/supplied by the company with the above Type Test reference number will be manufactured and tested to ensure that they perform as stated in this document, prior to shipment to site and that no site modifications are required to ensure that the products meet all the requirements of G59/3. Attachment: Extract of Test Report Ref , Generating Unit Type Test Sheet, released by TUeV Rheinland Phoenix, AZ, USA 2014 March 5 (Manufacturer) (Place) (Date) Robert P. White Jr. (Director Product Compliance) Power One Italy, S.p.A Terranuova Bracciolini (AR) Via S.Giorgio, 642 Tel Fax Fax (purch. dept.) Capitale Sociale int. vers. C.C.I.A.A. Arezzo n Reg. Imp. E Cod. Fisc Partita I.V.A Società soggetta alla direzione e controllo della Power-One Inc.
2 Seite 1 von 4 Page 1 of 4 Type of System: System Manufacturer: Manufacturer data: Grid tied inverter Power-One Italy S.p.A. Via S. Giorgio 642, Terranuova Bracciolini (AR) - Italy Reference test report: Issued by TÜV Rheinland Italia S.r.l. on 5 th March 2014 Measuring period: From 20 Th January 2014 to 14 Th February 2014 Type Test reference number: Pacr / Pacmax (Rated AC Power / Maximum AC output Power) Models * PVI-4.2-TL-OUTD PVI-4.2-TL-OUTD-S PVI-4.2-TL-OUTD-W PVI-3.6-TL-OUTD PVI-3.6-TL-OUTD-S PVI-3.6-TL-OUTD-W PVI-3.0-TL-OUTD PVI-3.0-TL-OUTD-S PVI-3.0-TL-OUTD-W Pacr / Pacmax 4200 W / 4600 W 3600 W / 4000 W 3000 W / 3300 W Software version: Device Version ** Booster (DC-DC) Higher than A Inverter (DC-AC) Higher than B.3.4.B MICRO (Supervisor) Higher than C Rated Voltage: 2-phase devices 230 V (Phase/ Neutral) Remarks: Note *: test performed on model PVI-4.2-TL-OUTD. The test result found can be extended on all model of the same product family. All products are completely the same; identical software version and PCB control boards are installed; the difference is related only on output power set. The family product model is made by the following products: PVI-3.6-TL-OUTD; PVI-3.0-TL-OUTD; PVI-4.2-TL-OUTD; PVI-3.6-TL-OUTD-S; PVI-3.0-TL-OUTD-S; PVI-4.2-TL-OUTD-S; PVI-3.6-TL-OUTD-W; PVI-3.0-TL-OUTD-W; PVI-4.2-TL-OUTD-W MODELs: PVI-3.6 and PVI-3.0 series are also evaluated in according to the standard G83/2 Note **: Country Code: UK G59
3 Seite 2 von 4 Page 2 of 4 Power Quality. Harmonics. Generating Unit rating per phase (rpp) 4,2 kva Harmonic % = Value (Amps) x 23/rating per phase (kva) Harmonic At 45-55% of rated output of rated output Limit in BS EN Value (MV) in Amps % Value (MV) in Amps % 1 phase 3 phase 2 0,023 0,126 0,030 0,164 8,00% 3 0,194 1,062 0,287 1,572 21,60% 4 0,008 0,044 0,010 0,055 4,00% 5 0,052 0,285 0,034 0,186 10,70% 6 0,009 0,049 0,004 0,022 2,67% 7 0,051 0,279 0,067 0,367 7,20% 8 0,005 0,027 0,007 0,038 2,00% 9 0,056 0,307 0,039 0,214 3,80% 10 0,010 0,055 0,004 0,022 1,60% 11 0,059 0,323 0,057 0,312 3,10% 12 0,008 0,044 0,012 0,066 1,33% 13 0,048 0,263 0,059 0,323 2,00% THD 2,51% - 1,71% - 23,00% PWHD 5,42% - 1,66% - 23,00% No Higher limit for odd harmonics 21 and above are applied Power Quality. Voltage fluctuations and Flicker. Values at standard impedance Limits set under BS EN Starting Stopping Running dmax dc d(t) dmax dc d(t) Pst Plt 2 hours 1,004% 0% 0 1,004% 0% 0 0,243 0,242 4% 3,30% 3,3% 500ms 4% 3,30% 3,3% 500ms 1 0,65 Test start date 03\10\2011 Test end date 03\10\2011 Power quality. DC injection. Test power level 10% 55% Recorded value in Amps -0,003 0,001-0,003 as % of rated AC current 0,016% 0,005% 0,016% Limit 0,25 % 0,25 % 0,25 %
4 Seite 3 von 4 Page 3 of 4 Power quality. Power Factor. 216,2V 230V 253V at three voltage levels and at value 0,9996 0,9997 0,9998 full output. Voltage to be maintained within ±1,5% of the stated level during Limit >0.95 >0.95 >0.95 the test. Protection. Frequency tests. Function Setting Trip test No trip tests Frequency Time delay Frequency Time delay Frequency /time Confirm no trip U/F stage 1 47,5Hz 20,05s 47,5 20,043 47,7Hz/ 25s No Trip U/F stage 2 47Hz 0,55s 47 0,558 47,2Hz/ 19,98s No Trip 46,8Hz/ 0,48s No Trip O/F stage 1 51,5Hz 90,05s 51,50 90,043 51,3Hz/95s No Trip O/F stage 2 52Hz 0,55s 52,00 0,554 51,8Hz/ 89,98s No Trip 52,2Hz/ 0,48s No Trip Protection. Voltage tests. Function Setting Trip test No trip tests Voltage Time delay Voltage Time delay Voltage/Time Confirm no trip U/V stage 1 200,1V 2,55s 199,93 2, ,1V/3,5s No Trip U/V stage 2 184V 0,55s 184,06 0, V/2,48s No Trip 180V/0,48s No Trip O/V stage 1 262,2V 1,05s 261,9 1, ,2V/2,0s No Trip O/V stage 2 273,7V 0,55s 273,18 0, ,7V/0,98s No Trip 277,7V/ 0,48s No Trip a) Protection. Loss of Mains test and single phase test. Inverter tested to BS EN The following sub set of tests should be recorded in the following table. Test Power and imbalance Trip time. Limit is 0,5s 33% -5% Q Test 22 66% -5% Q Test 12-5% P Test 5 33% +5% Q Test 31 66% +5% Q Test 21 +5% P Test 10 0,264 0,389 0,432 0,345 0,133 0,383
5 Seite 4 von 4 Page 4 of 4 b) Protection. Frequency change, Stability test. Start Frequency Change End Frequency Confirm no trip Positive Vector Shift 49,5Hz +9 degrees No trip Negative Vector Shift 50,5Hz - 9 degrees No trip Positive Frequency drift 49,5Hz +0,19Hz/sec 51,5Hz No trip Negative Frequency drift 50,5Hz -0,19Hz/sec 47,5Hz No trip c) Protection. Re-connection timer. Time delay setting delay Checks on no reconnection when voltage or frequency is brought to just outside stage 1 limits of table s 35s At 266,2V At 196,1V At 47,4Hz At 51,6Hz Confirmation that the Generating Unit does not reconnect. No reconnection No reconnection No reconnection No reconnection e) Fault level contribution. For Inverter Output Time after fault Volts Amps 20ms 102,03 18,01 100ms 95,23 13,15 250ms 93,95 10,57 500ms 93,61 10,36 Time to trip 0,573 In seconds f) Fault level contribution. NA This extract from the test report is only valid in conjunction with the test report no.:
PVI l-OUTD(-S)-400 PvI10.04CuTD(.s)400 SOLAR GRID TIED INVERTER. Power-One Italy S.p.A.
Power and productivity for a better 11 II II tm FID ref PVI-]2.O(1O.O-I-OUTD( -S,)-4OO & Derived Models (UK G59/3 Type VerUication Test Report,) ENA Engineering Recommendation G59/3 Type Verification Test
More informationGrid tied inverter. Reference test report: Issued by TÜV Rheinland Italia S.r.l. on 10 th February 2015
Seite 1 von 7 Page 1 of 7 Type of System: System Manufacturer: Manufacturer data: Grid tied inverter Power-One Italy S.p.A. Via S. Giorgio 642, 52028 Terranuova Bracciolini (AR) - Italy Reference test
More informationGrid tied inverter. Reference test report: Issued by TÜV Rheinland Italia S.r.l. on 19 th Janury 2015
Seite 1 von 5 Page 1 of 5 Type of System: System Manufacturer: Manufacturer data: Grid tied inverter Power-One Italy S.p.A. Via S. Giorgio 642, 52028 Terranuova Bracciolini (AR) - Italy Reference test
More informationSeite 1 von 8 Page 1 of 8 Appendix 4 Type Verification Test Report (G83/2) Grid tied inverter
Seite 1 von 8 Page 1 of 8 Appendix 4 Type of System: System Manufacturer: Manufacturer data: Grid tied inverter Power-One Italy S.p.A. Via S. Giorgio 642, 52028 Terranuova Bracciolini (AR) - Italy Reference
More informationG59/3 TYPE TEST VERIFICATION REPORT. Photovoltaic Microinverter. Tel Fax
Type Tested reference number Unit technology System supplier name Address M250-60-230-S22 Photovoltaic Microinverter Enphase Energy Inc. 1420 North McDowell Blvd. Petaluma, CA USA Tel +1-707-763-4784 Fax
More informationEngineering Recommendation G83/2
Engineering Recommendation G83/2 Type Approval and manufacturer/supplier declaration of compliance with the requirements of Engineering Recommendation G83/2. Type reference number STL 300 Type System Supplier
More informationENA G59/3 TYPE VERIFICATION TEST REPORT
ENA G59/3 TYPE VERIFICATION TEST REPORT Type approval and manufacturer/supplier declaration of compliance with the requirements of Engineering Recommendation G59/3. Unit Type reference number Unit Type
More informationMANUFACTURER AND TEST HOUSE DETAILS
Certificate UK G83/1 The results of tests performed according to reference standard UK G83/1 are summarized in this certificate. Power-One Italy S.p.a. declares that the units set for UK G83/1 operations
More informationSSEG DETAILS (Small-Scale Embedded Generator) SSEG Type Reference: SSEG Model Reference:
Certificate UK G59/2-1 The results of tests performed according to reference standard UK G59/2-1 are summarized in this certificate. Power-One Italy S.p.a. declares that the units set for UK G59/2-1 operations
More informationSSEG DETAILS (Small-Scale Embedded Generator) SSEG Type Reference: SSEG Model Reference:
Certificate BELGIUM C10/11 Pmax=100% The results of tests performed according to reference standard BELGIUM C10/11 Pmax=100% are summarized in this certificate. Power-One Italy S.p.a. declares that the
More informationG59/3 TYPE TEST VERIFICATION REPORT
MATERIALS & SAFETY R&D TR 141110T Page 1 of 10 G59/3 TYPE TEST VERIFICATION REPORT This Type Test sheet shall be used to record the results of the type testing of Generating Unit between 16A per phase
More informationG59/3 TYPE TEST VERIFICATION REPORT
G59/3 TYPE TEST VERIFICATION REPORT Type Tested reference number GW3048-EM, GW3648-EM,GW5048-EM System supplier name Jiangsu GoodWe Power Supply Technology Co.,Ltd. Address NO.189 Kun Lun Shan Road, Suzhou
More informationIt includes the Generating Units supplier declaration of compliance with the requirements of Engineering Recommendation G59/3
MATERIALS & SAFETY R&D TR170801S Page 1 of 8 G59/3 Type Verification Test Report This Type Test sheet shall be used to record the results of the type testing of Generating Unit between 16A per phase and
More informationG59/3 Generating Unit Type Test Sheet
G59/3 Unit Type Test Sheet Type Tested Unit(>16A per phase but 50kW 3 phase or 17kW 1 phase) This Type Test sheet shall be used to record the results of the type testing of Unit between16a per phase and
More informationCertificate. Inverter with integrated automatic disconnection device between a generator and the public low-voltage grid
Certificate Applicant: Product: Victron Energy B.V. De Paal 35 1351 JG Almere-Haven The Netherlands Inverter with integrated automatic disconnection device between a generator and the public low-voltage
More informationTR % L Not stated L % L % L3 2.67% L % L % L3 0.
TR 09 Page 2 of 10 Power Quality. Harmonics. SolarLake 20000TLPM Generating Unit rating per phase (rpp) Harmonic At 4555% of rated r outputt 6.6 kva % of rated outpu Harmonic % = Measured Value(Amps) *23/rating
More informationmmenda 012 erification n Test Rep port e reference number W3600S BP upplier name oodwe Powe Jiangsu Go O.189 Kun Lun w District, Jian ngsu,china
ENA Engineeringg Recom mmenda ation G883 Isssue 2 20 012 erification n Test Rep port roval and maanufacturer/ssupplier declaaration of co ompliance with the requirrements of Engineering ndation G83/2.
More informationHarmonic current emissions as per EN
POWER QUALITY Harmonic current emissions as per EN 61000-3-2 Harmonic Test Value in Amps % of fund Limit in Amps 2 0.014 0.16 1.080 3 0.099 1.14 2.300 4 0.009 0.10 0.430 5 0.040 0.46 1.140 6 0.015 0.17
More informationCertificate of Compliance
Certificate of Compliance Certificate: 2572294 Master Contract: 173688 Project: 2721900 Date Issued: April 24, 2014 Issued to: Power-One, Inc 3201 E Harbour Dr Phoenix, AZ 85034 USA The products listed
More informationPower Quality and Harmonic :Causes and Effects with Paper Mill Factory
Power Quality and Harmonic :Causes and Effects with Paper Mill Factory Danaisak Tangsakha PEA Thailand danaisakpq@gmail.com Provincial Electricity Authority, Thailand 1 Topics Introduction Power Quality
More informationGrid Converters for Photovoltaic
Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements
More informationINTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs
INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection
More informationPage 1 of 28. Ingo Röhr. Frank Hesmer
Page 1 of 28 TEST REPORT Engineering recommendation G83/1 Recommendation for the connection of small-scale embedded generators (up to 16 A per phase) in parallel with public low-voltage distribution networks.
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationPhase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.
Summary Of Interconnection Technical Guidelines for Renewable Energy Systems 0-100 kw under Standard Offer Contract (Extract from JPS Guide to Interconnection of Distributed Generation) This document is
More informationABB central inverters PVI-55.0/ PVI-165.0/ PVI-275.0/ to 330 kw
SOLAR INVERTERS ABB central inverters PVI-55.0/110.0 - PVI-165.0/220.0 - PVI-275.0/330.0 55 to 330 kw ABB s central inverters are extremely scalable, modularinverter systems that are based on 55 kw modular
More informationPower-One, worldwide leader for power supplier and renewable energy products
Power-One, worldwide leader for power supplier and renewable energy products Europa Power-One Italy Spa Via S Giorgio 642 52028, Terranuova Bracciolini, Arezzo, Italy - Phone: (+39) 05591951 - Fax: (+39)
More information16B2011B1 EASY HARMONICS USER MANUAL
6B0B Issued on 03/08/09 R.00 English This manual is integrant and essential to the product. Carefully read the instructions contained herein as they provide important hints for use and maintenance safety.
More informationFeatures PVI-55.0 PVI PVI-165.0/220.0 PVI-275.0/330.0 GENERAL SPECIFICATIONS ULTRA CORE PLUS
PVI-55.0 PVI-110.0 PVI-165.0/220.0 PVI-275.0/330.0 CORE PLUS ULTRA GENERAL SPECIFICATIONS These extremely scalable modular inverter systems, based on 55kW modular blocks, increase usable power and improve
More informationIEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces
IEEE PES Boston Chapter Technical Meeting IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces P1547 Chair David
More informationPAS series of 4-Quadrant Amplifiers
PAS series of 4Quadrant Amplifiers THE REAL 4QUADRANT AMPLIFIER The relating standards: IEC/EN 6132 IEC/EN 6133 IEC/EN 61311 IEC/EN 61312 IEC/EN 614611 IEC/EN 6122 IEC/EN 6144 IEC/EN 6145 IEC/EN 6148 IEC/EN
More informationEN50160 Individual Report Summary
EN50160 Individual Report Summary Power Frequency (x.1) Supply Voltage Variations (x.3.x) Rapid Voltage Changes (x.4.1) Flicker (x.4.2) Supply Voltage Dips (x.5) Short Interruption of Supply Voltage (x.6)
More informationOrbital GFI Inverter Series
Orbital GFI Inverter Series Datasheet Key Features One, split or three phases and up to 25 kva Superior efficiency of 95% CAN Bus control and DAQ Power quality and EMC compliance in accordance with European
More informationAC Sources for IEC 1000 Harmonics and Flicker Testing
APPLICATION NOTE #101 IEC 1000-3-2 and IEC 1000-3-3 The IEC 1000-3 standard is concerned with the quality of the utility line power. To ensure good power quality, this standard specifies limits for the
More informationEMC TEST REPORT. According to
EMC TEST REPORT According to EN 55014-1: 2006 EN 55014-2: 1997+A1:2001 EN 61000-3-2: 2006 EN 61000-3-3: 1995+A1:2001+A2:2005 Test Report No. Equipment : BWS-08-EC-0001 : Air cleaner Model No : AIRVAX 33X2
More informationPOWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:
POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION
More informationFeatures PVI-55.0 PVI PVI-165.0/220.0 PVI-275.0/330.0 GENERAL SPECIFICATIONS CENTRALIZED MODELS PLUS
PVI-55.0 PVI-110.0 PVI-165.0/220.0 PVI-275.0/330.0 PLUS GENERAL SPECIFICATIONS CENTRALIZED MODELS These extremely scalable modular inverter systems, based on 55kW modular blocks, increase usable power
More informationEMC TEST REPORT. For. Switching Mode Power Adaptor. Model No.: 9W/14.4V/EU(18V/1.0A), 19W/14.4V/EU(12V/1.5A)
EMC TEST REPORT For Company Limited Liability «Faraday Electronics» Switching Mode Power Adaptor Model No.: 9W/14.4V/EU(18V/1.0A), 19W/14.4V/EU(12V/1.5A) Prepared For : Company Limited Liability «Faraday
More informationLM W High-Efficiency Mono BTL Audio Power Amplifier
10W High-Efficiency Mono BTL Audio Power Amplifier General Description The LM4680 is a high efficiency switching audio power amplifier primarily designed for demanding applications in flat panel monitors
More informationVoltech PM3000ACE UNIVERSAL POWER ANALYZER
Voltech PM3000ACE UNIVERSAL POWER ANALYZER Precision Power Analysis from Voltech Voltech launched the worlds first commercially available digital power analyzer, the PM1000, in 1987 and the worlds first
More informationTEST SUMMARY. Prüfbericht - Nr.: Test Report No.: Seite 2 von 27. Page 2 of 27
15072768 001 Seite 2 von 27 Page 2 of 27 TEST SUMMARY 4.1.1 HARMONICS ON AC MAINS 4.1.2 VOLTAGE CHANGES, VOLTAGE FLUCTUATIONS AND FLICKER ON AC MAINS 4.1.3 MAINS TERMINAL CONTINUOUS DISTURBANCE VOLTAGE
More informationTable of Contents. Introduction... 1
Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...
More informationCompany Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes
Company Directive STANDARD TECHNIQUE: SD1E/2 Technical Requirements for Customer Export Limiting Schemes Policy Summary This Standard Technique specifies the requirements for customer owned Export Limitation
More informationTechnical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks
2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution
More informationTripping of circuit breakers in PV installations due to zero sequence field impedance
Tripping of circuit breakers in PV installations due to zero sequence field impedance B. Verhelst 1,2, C. Debruyne 1,2, J. Desmet 1,2 1 dept. Electrical Engineering - Lemcko HoWest Kortrijk, Belgium bart.verhelst@howest.be
More informationTechnical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US
Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US ENGLISH SC-US-GridServices-TI-en-10 Version 1.0 Table of Contents SMA Solar Technology
More informationEASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation
EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation This application is to be completed and returned to the Cooperative member service representative in order to begin
More informationMagtech Voltage Booster MVB
Model overview MVB 27.03.08 EG.doc Magtech Voltage Booster Voltage fluctuations caused by unbalanced load in Y-ground grid? Low voltage part of the day due to high load? Quick and profitable solution with
More informationEMC VERIFICATION SUMMARY Report No.: SZHH
EMC VERIFICATION SUMMARY Toy ITE Others Additional Models: 0801 to 0899 INCLUSIVE, 0804, 0804W, 0805, 0806, 0807, 0808, 0809, 0811, 0811W, 0812, 0813, 0814,0815, 0816, 0817,0817 ROOM 619, 6/F. PENINSULA
More informationMagtech Voltage Booster MVB
Model overview MVB 30.04.09 EG.doc Magtech Voltage Booster Voltage fluctuations caused by unbalanced load in Y-ground grid? Low voltage part of the day due to high load? Quick and profitable solution with
More informationOwner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:
Interconnection of a Customer-Owned Renewable Generation System of Greater than 100 KW and Less than or Equal to 1 MW to the LCEC Electric Grid Tier 3 Application and Compliance Form Instructions: Complete
More informationPower Quality under the microscope
We take care of it. Power Quality Power Quality under the microscope Change in the producer and consumer structure The change in the producer and consumer structure of the Central European power grids
More informationVoltage-controlled active filter gives standby generator power quality
Seite 1 von 5 Voltage-controlled active filter gives standby generator power quality Nowadays, nearly all the consumers connected to the electricity supply network constitute non-linear loads. Their non-sinusoidal
More informationTEST REPORT DIN V VDE V :2006 Automatic disconnecting device
age 1 of 23 TEST REORT Automatic disconnecting device Report Reference No...: GZ10080033-1 Date of issue...: August 18, 2010 Total number of pages... 23 pages Testing Laboratory...: Address...: Tested
More informationGrid Code 2015 for Small Scale Distributed Generation (SSDG) Net Metering Scheme Version June 2017 Central Electricity Board
Grid Code 2015 for Small Scale Distributed Generation (SSDG) Net Metering Scheme Version 2.2 - June 2017 Central Electricity Board Foreword The purpose of this document is to assist the public to better
More informationImplementation of Revised IEEE Standard 1547
MAY 31, 2017 HOLYOKE, MASSACHUSETTS Implementation of Revised IEEE Standard 1547 Presentation to ISO-TO Operations Committee David Forrest Key Points As New England adds significant amounts of Distributed
More informationSIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side
www.siemens.com/protection SIPROTEC 5 Application SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT in the delta connection of the compensation Answers for infrastructure and cities. Autotransformer
More informationHARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE
HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE Ibrahim ABDULHADI Federico COFFELE Power Networks Demonstration Centre - UK ibrahim.f.abdulhadi@strath.ac.uk federico.coffele@strath.ac.uk
More informationPM6000. Voltech. Power Analyzer
Voltech PM6000 Power Analyzer A New Standard in Power Analysis Up to 6 wattmeter channels Basic accuracy: 0.02% of reading Bandwidth: 10MHz Easy-to-use in all applications The Voltech PM6000 Power Analyzer
More informationThermocouple Conditioner and Setpoint Controller AD596*/AD597*
a FEATURES Low Cost Operates with Type J (AD596) or Type K (AD597) Thermocouples Built-In Ice Point Compensation Temperature Proportional Operation 10 mv/ C Temperature Setpoint Operation ON/OFF Programmable
More informationWDG 51 - Technical Data Sheet
MV 804 S WDG 51 - Technical Data Sheet FRAME MV 804 S SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international
More informationB9000 FXS kVA B9600 FXS kVA
OF CONTINUOUS SERVICE YEARS WARRANTY B9000 FXS 60-300kVA B9600 FXS 400-800kVA BORRI B9000 FXS B9600 FXS With disturbances to the electrical supply being one of the major causes of IT downtime, the UPS
More informationRoadmap For Power Quality Standards Development
Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel
More informationPOWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER
POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,
More informationHybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation
Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603
More informationENS31 Automatic Isolation Unit Product Description
ENS31 Automatic Isolation Unit Product Description Issue 09/2005 UfE Umweltfreundliche Energieanlagen GmbH Joachim-Jungius-Straße 9 D 18059 Rostock Tel.: +49 3 81 / 405 97 05 Fax: +49 3 81 / 405 97 03
More informationEmicon Engineering Consultants L.L.C.
Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com
More informationSummary of testing: Testing location: Intertek Testing Services Taiwan Ltd.
age 2 of 40 Summary of testing: Tests performed (name of test and test clause): 5.4.3 System reactions flicker 5.4.4 System reactions harmonics and interharmonics 5.4.9 System reactions precautionary measures
More informationMicro DC-DC Converter Family Isolated Remote Sense
APPLICATION NOTE AN:205 Micro DC-DC Converter Family Isolated Remote Sense Application Engineering Vicor Corporation Contents Page Introduction 1 Design Considerations 1 Remote Sense Circuit Functional
More informationTEST SUMMARY. Prüfbericht - Nr.: Test Report No.: Seite 2 von 25. Page 2 of 25
15072259 001 Seite 2 von 25 Page 2 of 25 TEST SUMMARY 4.1.1 HARMONICS ON AC MAINS 4.1.2 VOLTAGE FLUCTUATIONS ON AC MAINS 4.1.3 MAINS TERMINAL CONTINUOUS DISTURBANCE VOLTAGE 4.1.4 DISCONTINUOUS INTERFERENCE
More informationTABLE OF CONTENTS. 1. General Description of EUT General Information of Test Conducted Emission Tests 7-10
TABLE OF CONTENTS 1. General Description of EUT 3 2. General Information of Test 4-6 3.1 Conducted Emission Tests 7-10 3.2 Radiated Emission Tests 11-13 3.3 Radiated Electromagnetic disturbance Test 14-18
More informationIssued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY
WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable
More informationCompany Directive STANDARD TECHNIQUE: SD5F. Relating to connecting multiple small low voltage connections with limited network analysis
Company Directive STANDARD TECHNIQUE: SD5F Relating to connecting multiple small low voltage connections with limited network analysis Policy Summary This document specifies the procedure for connecting
More informationGRID CODE MEDIUM SCALE DISTRIBUTED GENERATION (MSDG) Greater than 50kW and not exceeding 200kW. (Version May 2016) CENTRAL ELECTRICITY BOARD
GRID CODE MEDIUM SCALE DISTRIBUTED GENERATION (MSDG) Greater than 50kW and not exceeding 200kW (Version 1.0 - May 2016) CENTRAL ELECTRICITY BOARD Corporate Office P.O Box 134 Rue du Savoir, Cybercity Ebène
More informationHarmonic Filters for Single Phase Equipment
POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics
More informationTest Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy
A6/028659 Test Report CESI Approved Page 1 Client MF Trasformatori s.r.l. - Calcinato (BS) Italy Tested equipment Non-enclosed three-phase dry-type power transformer with three windings, with encapsulated
More informationENHANCE SWITCHING POWER SUPPLY SPECIFICATION 250 WATT MODEL NO:V525
ENHANCE SWITCHING POWER SUPPLY SPECIFICATION 250 WATT MODEL NO:V525 1.0 SCOPE 2.0 INPUT REQUIREMENTS 2.1 VOLTAGE 2.2 FREQUENCY 2.3 STEAD-STATE CURRENT 2.4 INRUSH CURRENT 3.0 OUTPUT REQUIREMENTS 3.1 AC
More informationGX 340 SERIES (AUTOMATIC VOLTAGE REGULATOR)
GX 340 SERIES (AUTOMATIC VOLTAGE REGULATOR) Email Address: info@powersystems.com.au Web Page: http://www.powersystems.com.au This AVR will replace the following Stamford Part Nos. And many more 350 28700
More informationTEST REPORT AS :2005 and AS :2005 Grid connection of energy systems via inverters Grid protection requirements
TEST REPORT AS 4777.2:2005 and AS 4777.3:2005 Grid connection of energy systems via inverters Grid protection requirements Report reference No...: 09TH0459-AS4777_2 Tested by (printed name and signature)...:
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationPower Analysis Summary
Power Analysis Summary Introduction This is a summary of the power conditions measured with these setup parameters: Measurement File: C:\Users\fhealy\Documents\Fluke\Power Analyze\Core 2 Recording.odn
More informationFuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)
Dynamics and Control of Distributed Power Systems Fuel cell power system connection Ian A. Hiskens University of Wisconsin-Madison ACC Workshop June 12, 2006 This topology is fairly standard, though there
More informationFCL VOLTAGE & FREQUENCY CONVERTERS. FCL H SERIES - SINGLE PHASE - 2 to 30 kva H SERIES MODELS. AC SINGLE PHASE 2 TO 30 kva STATIC VARIABLE AC
STATIC VARIABLE AC VOLTAGE & FREQUENCY CONVERTERS AC SINGLE PHASE 2 TO 30 kva IGBT SOLID STATE PWM DESIGN MODELS INPUT: 22-23 - 24 - OUTPUT: - 40 70Hz FCL 22 / 23 / 24-2 WIRE SINGLE PHASE THE UNIVERSAL
More informationHarmonic Distortion Evaluations
Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion
More informationGSC57 Rel of 257/10/05
Integrated meter for test verify and Power Quality analysis Pag 1 of 7 1. ELECTRICAL SPECIFICATIONS VERIFY TESTS Accuracy is indicated as ± (% readings + no. of digits) at 23 C ± 5 C, con relative humidity
More informationSOLAR300N Rel /01/10
Photovoltaic installation certifier + professional network analyzer Pag 1 of 5 1. SOLAR300N MAIN FEATURES SOLAR300N performs all tests on PV plants by using of SOLAR-02 remote unit which, after a preliminary
More informationUV3 _ Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High)
1MRS752333-MUM Issued 10/1997 Version: H/23.06.2005 Data subject to change without notice Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High) Contents 1. Introduction...
More informationSolectria Renewables Modbus Level 5 For models PVI KW
Solectria Renewables Modbus Level 5 For models PVI 50 100KW Revision B 2014, Solectria Renewables, LLC DOCR 070381 B Table of Contents 1 Solectria Renewables Modbus Level 5... 3 1.1 Determine Modbus Level...
More informationAD596/AD597 SPECIFICATIONS +60 C and V S = 10 V, Type J (AD596), Type K (AD597) Thermocouple,
AD597 SPECIFICATIONS (@ +60 C and V S = 10 V, Type J (AD596), Type K (AD597) Thermocouple, unless otherwise noted) Model AD596AH AD597AH AD597AR Min Typ Max Min Typ Max Min Typ Max Units ABSOLUTE MAXIMUM
More informationAn Introduction to Power Quality
1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger
More informationDOBLE F6150e TECHNICAL SPECIFICATIONS
DOBLE F6150e TECHNICAL SPECIFICATIONS The F6150e line of System Simulators is designed for simulation tests on relay and protection schemes. There are four distinct models for your specific testing needs.
More informationUp to 15 kw Power in Charge, 14.4 kva in Standalone and 13.2 kva in Utility Mode. 90 % Typical Efficiency. Charge Mode Output VDC
The Bel Power Solutions 350INVCHGT150-120-240-8G is a 15 kw inverter/charger that converts AC to DC voltages in charge mode and converts DC voltages to pure sine wave AC in standalone or utility mode.
More informationEMC Test report for LED Panel Light Models , , , , ,
4326247.50 EMC Test report for LED Panel Light Models 000529, 000530, 000531, 000532, 000535, 000536 Guangzhou, date of issue: 2016-02-24 Author:Jazz Liang By order of Marvo Verlichting B.V. at Hoogeveen,
More informationE N G I N E E R I N G M A N U A L
1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn
More informationTL082 Wide Bandwidth Dual JFET Input Operational Amplifier
TL082 Wide Bandwidth Dual JFET Input Operational Amplifier General Description These devices are low cost, high speed, dual JFET input operational amplifiers with an internally trimmed input offset voltage
More information~=E.i!=h. Pre-certification Transformers
7 Transformers Section 26 of the electrical code governs the use and installations of transformers. A transformer is a static device used to transfer energy from one alternating current circuit to another.
More informationSwitching Power Supply SPECIFICATION
IS-1U40PD8 IS-1U40PD8 Switching Power Supply ( 1U - 400W ) SPECIFICATION Revision: 1.1 istarusa Group 727,. Phillips Drive City of Industry. CA 91748. USA http:// www.istarusa.com TEL: 626-3038885 FAX:
More informationT-68 Protecting Your Equipment through Power Quality Solutions
T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. 2 Agenda What
More informationDP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation
DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More information