Harmonic Filtering in Variable Speed Drives

Size: px
Start display at page:

Download "Harmonic Filtering in Variable Speed Drives"

Transcription

1 Harmonic Filtering in Variable Speed Drives Luca Dalessandro, Xiaoya Tan, Andrzej Pietkiewicz, Martin Wüthrich, Norbert Häberle Schaffner EMV AG, Nordstrasse 11, 4542 Luterbach, Switzerland Abstract This paper discusses and presents results related to still open controversial issues in passive harmonic filters design, such as the identification of filter resonant frequencies, the effects of interactions of harmonic filters with system impedances and the importance of damping elements. Benefits of passive rectifiers equipped with harmonic filters are compared to those of other rectifier front-ends typically used in VSD applications. An experimental comparative evaluation of harmonic performances of passive and active rectifiers is also provided. 1. Introduction Passive three-phase rectifiers equipped with single tuned (ST) harmonic filters, as shown in Fig. 1, represent the most cost effective, technically simple and robust front end of variable speed drives with low effects on the mains. Harmonic filter design procedures and solutions for complex harmonic filtering application problems have been documented in several publications in the past few decades [1-3]. Every new harmonic mitigation problem still deserves a careful system analysis and special attention needs to be paid on crucial design aspects such as: selection of tuning frequencies and damping factors, interactions between harmonic filter and system impedances, optimal number of harmonic trap branches. Following sections provide further practical insight and considerations on these topics and, additionally, benefits of passive rectifiers equipped with harmonic filters are presented and compared to those of other rectifier front-ends typically used in VSD applications. 2. Single tuned and multi-tuned passive harmonic filters Six pulse current converters are common rectifier interfaces for variable speed drive systems and they are harmonic producing loads [2]. Because grid harmonic current emissions are regulated at both equipment level, e.g. [3, 4] and PCC [5], a typical harmonic mitigation approach is to install single tuned (ST) harmonic filter close to these non-linear loads. An accurate harmonic filter design procedure requires taking into account several aspects, such as estimate of harmonic current injection for different system s loadings, short-circuit level, load demand and harmonic analysis study considering presence in the installation of components which can impact harmonics, as capacitor banks or reactors [2]. A ST filter featuring a sharp tuning close to the 5 th harmonic is typically the first approach to reduce the harmonic distortion, since the 5 th harmonic has higher amplitude for six-pulse converters. If the harmonic content is still above limit, the procedure is to implement further ST filters tuned at higher order harmonics [1, 2, 3]. 148

2 Fig. 1 Effect of a ST harmonic filter tuned at the 5 th harmonic on the mains current i in and on the passive rectifier input current or filter output current i out for a 45 kw, 400V, 50 Hz system. THDi without and with ST harmonic filter is 103.5% and 3.5%, respectively. The attenuation by multiple parallel harmonic traps is achieved at the cost of higher loading of the lower harmonic ST branch, tuned at the 5 th harmonic, and results in higher load current respect to using a ST filter; this effect was also observed in the empirical design procedure presented in [2]. Fig. 2 shows the harmonic spectrum of load or input rectifier current and of the resulting current in the 5 th harmonic trap, corresponding to two different passive harmonic filter (PHF) designs for a 55kW drive: one ST filter tuned at the 5 th harmonic and a filter made out of the combination of four parallel branches each tuned at a different harmonic (5 th, 7 th, 11 th, 13 th ). For both configurations, single trap and multi traps, the passive harmonic filters draw the same level of capacitive current, which is typically 20% of the line current. Furthermore, there is no DC-link choke or rectifier s input choke installed in both cases. The 5th trap inductance in the multi-trap filter results to be three times larger than the one in the single trap model, 4.7mH vs.1.84mh. The 5th branch circuit of the multi-tuned PHF is much more stressed; at the same time it features a larger inductor than a single tuned PHF, which results into a more expensive passive filter solution. The THDi performance is sufficiently good with ST harmonic filter, 5.8% vs 3.3% of multi-tuned PHF. Fig. 2 Harmonic spectrum of load current and the resulting current in the 5 th harmonic trap for the two different PHFs for a 55kW drive: one single filter tuned at the 5 th harmonic and a multi-tuned PHF made out of four parallel branches each tuned to a different harmonic (5 th, 7 th, 11 th, 13 th ). 149

3 3. Interaction with system impedances According to the power rating of the installation and the type of impedances present in the system, PHFs may introduce unwanted distortions and resonances and therefore their design requires a careful system analysis to avoid operational issues. Fig. 3 shows the frequency characteristic of PHFs with different ratings, 1.1kW and 200 kw, installed in input of drives equipped with integrated EMI filters, in particular the X2 capacitor stage. Whilst for the larger rating PHF the interaction with the EMI filter does not cause variations of the frequency characteristic, the curve of the 1.1kW PHF presents a parallel resonance at about 600 Hz, which may result into an amplification of harmonic frequency sources in a range between the 11 th and 13 th order. Such a resonance can hinder the correct functioning of the filter and it is a case of interaction of PHF with EMI filter capacitance which may result into a poorer performance. Fig. 3 Frequency characteristics of PHFs installed in input of drives equipped with EMI filter stage. The interaction of the 1.1kW PHF with the EMI filter capacitance causes an unwanted resonance. The use of adequate damping techniques or even a modification of the filter circuit may preserve correct operation. The frequency and amplitudes values of the first parallel resonance (due to interaction with line impedance L i ) and of the series resonance are given respectively by [2]: f= 1 / 2π (LC + L i C) ½ Q = ((L + L i )/C) ½ / (R+R i ) These two resonances are expected in the ST filter design; the series resonance results from the trap branch LC tuned at about the 5 th harmonic, (L i = R i = 0 in the formula) and has the effect of attenuating the amplitude of the 5 th harmonic source. The parallel resonance, occurring at a lower frequency, is due to the interaction between trap circuit and line-side impedance L i (see Fig. 7a) and it is selected outside the range of harmonic sources; if this condition is not verified, the magnitude of the parallel resonance can be reduced by modifying the filter circuit with additional resistive, damping elements or by varying the value of the line inductor [1]. 150

4 The amplitude of parallel resonance due to interaction of the filter with EMI filter capacitors can be reduced by implementing a further damping branch [12], for instance in parallel to the line reactor. The attenuation effect of such a solution is visible in the plot of Fig. 3. The additional resistance and losses contribute to decrease the value of the Q factor corresponding to the parallel resonance, hence to flatten the shape of the filter frequency characteristic. The accurate tuning of the harmonic filter is crucial to achieve the target attenuation. However, effects like tolerances, component aging and temperature dependent characteristics need to be considered during design and therefore a ST filter is typically tuned to a frequency lower than the harmonic to suppress. The most crucial tolerances are on components of trap branch as depicted in Fig. 4. Fig 4 Plane of possible resonant frequencies for the 3-phase trap inductor in series with the capacitor bank, as function of the component tolerances. In particular, the lines parallel to the z-axis indicate the case of three limbs of the inductor having different values due to tolerance. An overall system harmonic analysis is crucial to define the best filter solution [1-2] to fulfill the regulations [4-6]. Fig. 5 shows the outcome of an analysis realized with the PQS tool [13] for the case of multi-motor system. Fig 5. Harmonic analysis of a multi motor system performed with PQS of Schaffner. In particular, only one motor is equipped with VSD, and the effect of VSD partial loading on the harmonic distortion is considered, with and without PHF. If the rating of the VSD is larger than the demand of both motors, then the resulting TDD at PCC and THDi for the VSD line have different trend. 151

5 4. Figures of merit of rectifiers for VSD applications A state-of-the-art LV VSD is typically constituted by a diode rectifier front-end cascaded by a voltage source inverter which drives the electric motor. In order to comply with harmonic standards [4-6], the diode bridge is commonly equipped by a ST harmonic filter, able to reduce the THDi, typically below 5%. If the application requires regeneration back into the mains, active-front end (AFE) is used. An active rectifier is able to fulfill the harmonic requirements. The enhanced controllability has an immediate impact on cost, reliability and availability of the system. A compromise to improve the input current THDi is the use of multipulse rectifiers, typically 12 or 18 pulses, together with multi-winding input transformers [11]. This kind of rectifier stage increases considerably the complexity of the front-end and has the drawback of reduced performance in presence of imbalance. A further possibility to reduce the THDi of the drive is to actively compensate harmonics through an active harmonic filter (AHF), which is commonly a shunt device installed at the input terminals of a single or multidrive system [3, 11]. Fig. 6 presents figures of merit, derived from [2,3,11] of rectifiers with low harmonic impact on the mains, typically used in VSD applications. a) b) Fig. 6. Figures of merit of rectifiers typically used in VSD applications for nominal loading, a) passive interfaces and b) active interfaces as active harmonic filter (AHF) and active front end (AFE) compared to passive rectifier equipped with PHF. Line reactor in input of diode bridge is a further simple, cost effective solution. 5. Experimental verification The harmonic performances of two rectifiers, typically used as input rectification stage for 2Q variable speed drive applications, were compared; in particular, the following rectifier topologies were considered: A passive rectifier, 3-phase diode bridge, without DC-link choke, equipped with a ST passive harmonic filter tuned at the 5 th harmonic, designed for a target THDi < 5%. An active front-end (AFE), 3-phase, 2-level PWM rectifier equipped with LCL and EMI input filter stages and switching at a frequency of 1.5 khz. For both rectifiers, the input current and voltage are 95Arms and 400Vrms respectively, the mains frequency is 50 Hz, 75 kw the power rating. In addition, the current spectra were derived and current harmonics until the 40 th order shown in Fig

6 Fig. 7. Rectifiers and their respective input filter stages considered for the comparative evaluation of harmonic performance: a) passive rectifier, 3-phase diode-bridge featuring a single tuned (5 th harmonic) passive harmonic filter and b) AFE equipped with LCL and EMI filters. a) b) Fig. 8. Measured input rectifier current waveforms, a) passive rectifier with PHF and b) AFE equipped with LCL and EMI input filters. The amplitude of the measured current waveforms is the same, 95 Arms, the frequency is 50 Hz. PHF L i mh L o mh L t 0.94 mh C t 3x 440 uf wye LCL L i mh L o 0.33 mh C D 3x 40 uf delta EMI C 10 uf L CM1 0.4 mh 26 uh L CM2 Table 1. Parameters of the filters in input to the rectifiers, as shown in the circuits in Fig.7. Source impedance condition is same for both setups. The total harmonic content (THC) and the reference current I ref were assessed using the formulas as defined in [5] for both measured input rectifier currents shown in Fig.8. The THDi defined after [6] is calculated as well to estimate the harmonic performance; in the IEEE 519 the harmonic content is typically up to the 50 th order. 153

7 Fig. 9. Input rectifier current waveforms spectra. Harmonic frequencies are displayed until 40 th, harmonic amplitudes are in a) passive rectifier with PHF and b) AFE equipped with LCL and EMI filters. The amplitude of the fundamental component (h=1) is 95Arms; the enlarged vertical axes cut the representation of these values. Passive rectifier + PHF AFE + LCL, EMI filters THC 4.34 Arms 6.38 Arms I ref 92.2 Arms 94.4 Arms THC/I ref 4.7 % 6.7% THDi 4.7 % 7% Table 2. Harmonic performance of the tested rectifier systems. For this particular case study, the rectifiers and their respective input filters were commercially available equipment and were not modified for the tests. The measured harmonic performance at nominal loading is summarized in Table 2. The passive rectifier equipped with ST filter yields to a better THDi; nevertheless the PHF corresponding to the values in Table 1 is about 50% more expensive than the LCL combined with EMI filter. However, for same target harmonic performance, e.g THDi = 4.7%, and same switching frequency, the cost of LCL and EMI filter stages would exceed the price of a PHF. Furthermore, a passive rectifier equipped with PHF results about 25% cheaper than a AFE featuring LCL and EMI filter, for a power rating ranging from few kw up to several hundreds of kw [7]. The higher contribution to harmonic distortion of an active rectifier is expected to occur at PWM switching frequency f s in the khz range. If f s is lower than 2 khz, corresponding to the 40 th harmonic order, the switching ripple will contribute to increase the harmonic content as defined by the norms [5, 6]. It is good practice to verify for active rectifiers the amplitude of lower harmonic orders [9], which can increase, for instance, if low frequency signals injection techniques are applied to improve modulation [10]. On the other side, if f s is higher than 2.5 khz, the ripple components will be shifted in a range, khz, for which the compatibility limits are still not regulated. The IEC SC77A WG8 has the task of the standardization for khz, which will result in an updated standard, eg. IEC [8]. For an AFE the LC filter stage has to attenuate the ripple current. Further optimization of the filter components is possible and it consists in finding the trade-off between filter volume and overall system efficiency [9]. 154

8 6. Conclusion Passive harmonic filters in combination with three-phase passive rectifiers constitute the most cost effective, technically simple and robust front end of variable speed drives with low effects on the mains. To solve the harmonic mitigation problem and to properly design the harmonic filter, a careful system analysis is needed and dedicated simulation tools, like the PQS [13], help to take into account and verify all the most important design requirements. The paper has shown that special attention needs to be paid on the selection of tuning frequencies and damping factors. Interactions between harmonic filter and system impedances can cause system resonance, which can be avoided by proper shaping of the filter frequency characteristic. Figures of merit for rectifier front-ends typically used in VSD applications were compared to show the superior advantages of passive rectifiers equipped with PHF. Finally, the experimental comparative evaluation of harmonic performances of passive and active rectifiers confirmed the economic and performance benefits of a passive filter solution. 7. References [1] M. Allenbaugh, T. Dionise, T. Natali, Harmonic Analysis and Filter Bank Design for a New Rectifier for a Cold Roll Mill, IEEE Trans. Ind. Appl. Vol 49, No. 3, May 2013 pp [2] J.C. Das, Passive Filters- Potentialities and Limitations, IEEE Trans. Industry Appl. Vol 40, No. 1, Jan./Febr pp [3] H. Akagi, Modern active filters and traditional passive filters, Bulletin Polish Academy of Sciences, Vol. 54, No. 3, 2006, pp [4] IEC EMC - Part 3-2: Limits for harmonic current emissions (equipment input current 16 A per phase)". [5] IEC EMC - Part 3-12: Limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and 75 A per phase. [6] IEEE , IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems. [7] ABB low voltage drives, ACS800, Product Pricing List, Online Available. [8] IEC :2002, EMC - Part 2-2: Environment - Compatibility levels for low-frequency conducted disturbances and signalling in public low-voltage power supply systems [9] J. Mühlethaler et al. Optimal design of LCL Harmonic Filters for Three-Phase PFC Rectifiers, IEEE Trans. Power Electr., vol. 28, No, 7, July 2013, pp [10] L. Dalessandro et al. Center-Point Voltage Balancing of Hysteresis Current Controlled Three-Level PWM Rectifiers, IEEE Trans. Power Elect., Vol 23, No. 5, Sept. 2008, pp [11] B Bahrani, R Grinberg, Investigation of harmonic filtering for the state-of-the-art variable speed drives, Proc. 13 th European Conf. on Power Electronics and Application EPE 2009, pp [12] Harmonic Filter, Granted patent family US B2. [13] Power Quality Simulator, 155

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER P. SWEETY JOSE JOVITHA JEROME Dept. of Electrical and Electronics Engineering PSG College of Technology, Coimbatore, India.

More information

RECENTLY, the harmonics current in a power grid can

RECENTLY, the harmonics current in a power grid can IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 2, MARCH 2008 715 A Novel Three-Phase PFC Rectifier Using a Harmonic Current Injection Method Jun-Ichi Itoh, Member, IEEE, and Itsuki Ashida Abstract

More information

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation UPEC21 31st Aug - 3rd Sept 21 Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation H. M. Zubi IET and IEEE member hz224@bath.ac.uk R. W. Dunn IEEE member E-mail r.w.dunn@bath.ac.uk

More information

Putting a damper on resonance

Putting a damper on resonance TAMING THE Putting a damper on resonance Advanced control methods guarantee stable operation of grid-connected low-voltage converters SAMI PETTERSSON Resonant-type filters are used as supply filters in

More information

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives 2 TECHNICAL GUIDE NO. 6 GUIDE TO HARMONICS WITH AC DRIVES Guide to harmonics This guide is part of ABB s technical guide series, describing

More information

Understanding Input Harmonics and Techniques to Mitigate Them

Understanding Input Harmonics and Techniques to Mitigate Them Understanding Input Harmonics and Techniques to Mitigate Them Mahesh M. Swamy Yaskawa Electric America YASKAWA Page. 1 Organization Introduction Why FDs Generate Harmonics? Harmonic Limit Calculations

More information

Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost Regulator

Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost Regulator International Journal of Automation and Power Engineering, 2012, 1: 124-128 - 124 - Published Online August 2012 www.ijape.org Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost

More information

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic

More information

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,

More information

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER Akash A. Chandekar 1, R.K.Dhatrak 2 Dr.Z.J..Khan 3 M.Tech Student, Department of

More information

POWER FACTOR CORRECTION AND HARMONIC CURRENT REDUCTION IN DUAL FEEDBACK PWM CONTROLLED AC/DC DRIVES.

POWER FACTOR CORRECTION AND HARMONIC CURRENT REDUCTION IN DUAL FEEDBACK PWM CONTROLLED AC/DC DRIVES. POWER FACTOR CORRECTION AND HARMONIC CURRENT REDUCTION IN DUAL FEEDBACK PWM CONTROLLED AC/DC DRIVES. 1 RAJENDRA PANDAY, 2 C.VEERESH,ANIL KUMAR CHAUDHARY 1, 2 Mandsaur Institute of Techno;ogy,Mandsaur,

More information

SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS

SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS Qin Jiang School of Communications & Informatics Victoria University P.O. Box 14428, Melbourne City MC 8001 Australia Email: jq@sci.vu.edu.au

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System

An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System Milan Anandpara Tejas Panchal Vinod Patel Deaprtment of Electrical Engineering Deaprtment

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

A New 3-phase Buck-Boost Unity Power Factor Rectifier with Two Independently Controlled DC Outputs

A New 3-phase Buck-Boost Unity Power Factor Rectifier with Two Independently Controlled DC Outputs A New 3-phase Buck-Boost Unity Power Factor Rectifier with Two Independently Controlled DC Outputs Y. Nishida* 1, J. Miniboeck* 2, S. D. Round* 2 and J. W. Kolar* 2 * 1 Nihon University Energy Electronics

More information

Harmonic Distortion and Variable Frequency Drives

Harmonic Distortion and Variable Frequency Drives Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation

More information

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter B.S.Nalina 1 Ms.V.J.Vijayalakshmi 2 Department Of EEE Department Of EEE 1 PG student,skcet, Coimbatore, India

More information

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013 Power Quality Enhancement Using Hybrid Active Filter D.Jasmine Susila, R.Rajathy Department of Electrical and electronics Engineering, Pondicherry Engineering College, Pondicherry Abstract This paper presents

More information

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System 1 G.Balasundaram, 2 Dr.S.Arumugam, 3 C.Dinakaran 1 Research Scholar - Department of EEE, St.

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

Handling System Harmonic Propagation in a Diesel-Electric Ship with an Active Filter

Handling System Harmonic Propagation in a Diesel-Electric Ship with an Active Filter Handling System Harmonic Propagation in a Diesel-Electric Ship with an Active Filter Atle Rygg Årdal Department of Engineering Cybernetics, Norwegian University of Science and Technology Email: atle.rygg.ardal@itk.ntnu.no

More information

OUTLINE. Introduction. Introduction. Conducted Electromagnetic Interference in Smart Grids. Introduction. Introduction

OUTLINE. Introduction. Introduction. Conducted Electromagnetic Interference in Smart Grids. Introduction. Introduction Robert Smoleński Institute of Electrical Engineering University of Zielona Gora Conducted Electromagnetic Interference in Smart Grids Introduction Currently there is lack of the strict, established definition

More information

Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives

Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives D.Uma 1, K.Vijayarekha 2 1 School of EEE, SASTRA University Thanjavur, India 1 umavijay@eee.sastra.edu 2 Associate Dean/EEE

More information

SHUNT ACTIVE POWER FILTER

SHUNT ACTIVE POWER FILTER 75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)

More information

BOOST PFC WITH 100 HZ SWITCHING FREQUENCY PROVIDING OUTPUT VOLTAGE STABILIZATION AND COMPLIANCE WITH EMC STANDARDS

BOOST PFC WITH 100 HZ SWITCHING FREQUENCY PROVIDING OUTPUT VOLTAGE STABILIZATION AND COMPLIANCE WITH EMC STANDARDS BOOST PFC WITH 1 HZ SWITCHING FREQUENCY PROVIDING OUTPUT VOLTAGE STABILIZATION AND COMPLIANCE WITH EMC STANDARDS Leopoldo Rossetto*, Giorgio Spiazzi** and Paolo Tenti** *Department of Electrical Engineering,

More information

PWM Control Method for NPC Inverters. with Very Small DC-Link Capacitors

PWM Control Method for NPC Inverters. with Very Small DC-Link Capacitors Paper PWM Control Method for NPC Inverters with Very Small DC-Link Capacitors Member Roberto Rojas (The University of Tokushima) Member Tokuo Ohnishi (The University of Tokushima) Member Takayuki Suzuki

More information

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, VARIATION OF HARMONICS AND RIPPLE WITH PULSE NUMBER Pulse Number

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, VARIATION OF HARMONICS AND RIPPLE WITH PULSE NUMBER Pulse Number 16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 693 Novel 24-Pulse Rectifier Topology based on Single 3-Phase to Four 3-Phase Transformation using Conventional Transformers for Phase Shifting

More information

Novelty Technique for Power factor Improvement by a Single phase Rectifier

Novelty Technique for Power factor Improvement by a Single phase Rectifier 162 Novelty Technique for Power factor Improvement by a Single phase Rectifier Baby.M 1, Poorinima.S 2, Bharani Prakash.T 3, Sudarsan.S 4 Abstract A new technique is implemented to improve the input power

More information

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System 1 Leena N C, 2 B. Rajesh Kamath, 3 Shri Harsha 1,2,3 Department of EEE, Sri Siddhartha Institute of Technology, Tumkur-572105,

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

A Novel Power Factor Correction Rectifier for Enhancing Power Quality

A Novel Power Factor Correction Rectifier for Enhancing Power Quality International Journal of Power Electronics and Drive System (IJPEDS) Vol. 6, No. 4, December 2015, pp. 772~780 ISSN: 2088-8694 772 A Novel Power Factor Correction Rectifier for Enhancing Power Quality

More information

Indirect Current Control of LCL Based Shunt Active Power Filter

Indirect Current Control of LCL Based Shunt Active Power Filter International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 3 (2013), pp. 221-230 International Research Publication House http://www.irphouse.com Indirect Current Control of LCL Based

More information

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems K Siva Shankar, J SambasivaRao Abstract- Power converters for mobile devices and consumer electronics have become extremely lightweight

More information

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller J.Venkatesh 1, K.S.S.Prasad Raju 2 1 Student SRKREC, India, venki_9441469778@yahoo.com

More information

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES White Paper Tim Wylie, Ampcontrol s Chief Technology Officer discusses the impact of Variable Speed Drives (VSDs) on earth fault limited networks.

More information

CHAPTER 4 MEASUREMENT OF NOISE SOURCE IMPEDANCE

CHAPTER 4 MEASUREMENT OF NOISE SOURCE IMPEDANCE 69 CHAPTER 4 MEASUREMENT OF NOISE SOURCE IMPEDANCE 4.1 INTRODUCTION EMI filter performance depends on the noise source impedance of the circuit and the noise load impedance at the test site. The noise

More information

Modeling and Simulation of Paralleled Series-Loaded-Resonant Converter

Modeling and Simulation of Paralleled Series-Loaded-Resonant Converter Second Asia International Conference on Modelling & Simulation Modeling and Simulation of Paralleled Series-Loaded-Resonant Converter Alejandro Polleri (1), Taufik (1), and Makbul Anwari () (1) Electrical

More information

A Novel Control Method to Minimize Distortion in AC Inverters. Dennis Gyma

A Novel Control Method to Minimize Distortion in AC Inverters. Dennis Gyma A Novel Control Method to Minimize Distortion in AC Inverters Dennis Gyma Hewlett-Packard Company 150 Green Pond Road Rockaway, NJ 07866 ABSTRACT In PWM AC inverters, the duty-cycle modulator transfer

More information

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control International Journal of Scientific Engineering and Research (IJSER) Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control Rahul Kumar Patel 1, S. Subha 2 Abstract:

More information

HARMONIC contamination, due to the increment of nonlinear

HARMONIC contamination, due to the increment of nonlinear 612 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 44, NO. 5, OCTOBER 1997 A Series Active Power Filter Based on a Sinusoidal Current-Controlled Voltage-Source Inverter Juan W. Dixon, Senior Member,

More information

Systematical measurement errors

Systematical measurement errors Systematical measurement errors Along the lines of the rule formulated by Schrödinger that a system can influenced even by observing, an EUT can be influenced by a normal measurements. If the measurement

More information

A Current-Source Active Power Filter with a New DC Filter Structure

A Current-Source Active Power Filter with a New DC Filter Structure A Current-Source Active Power Filter with a New DC Filter Structure Mika Salo Department of Electrical Engineering, Institute of Power Electronics Tampere University of Technology P.O.Box 692, FIN-3311

More information

Design of EMI Filters for DC-DC converter

Design of EMI Filters for DC-DC converter Design of EMI Filters for DC-DC converter J. L. Kotny*, T. Duquesne**, N. Idir** Univ. Lille Nord de France, F-59000 Lille, France * USTL, F-59650 Villeneuve d Ascq, France ** USTL, L2EP, F-59650 Villeneuve

More information

Improving Passive Filter Compensation Performance With Active Techniques

Improving Passive Filter Compensation Performance With Active Techniques IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan

More information

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating P.Ankineedu Prasad 1, N.Venkateswarlu 2. V.Ramesh 3, L.V.Narasimharao 4 Assistant Professor 12 & Professor 4& Research Scholar

More information

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER 97 CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER 6.1 INTRODUCTION Multi level inverters are proven to be an ideal technique for improving the voltage and current profile to closely match with the sinusoidal

More information

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions Issue #65 - December 2012 Technical News Industrial Electrical and Automation Products, Systems and Solutions Part 2: Harmonics The link between harmonics and power factor Written by Justin Charlot Product

More information

ISSN Vol.03,Issue.07, August-2015, Pages:

ISSN Vol.03,Issue.07, August-2015, Pages: WWW.IJITECH.ORG ISSN 2321-8665 Vol.03,Issue.07, August-2015, Pages:1276-1281 Comparison of an Active and Hybrid Power Filter Devices THAKKALAPELLI JEEVITHA 1, A. SURESH KUMAR 2 1 PG Scholar, Dept of EEE,

More information

An Integrated Inverter Output Passive Sinewave Filter for Eliminating Both Common and Differential Mode PWM Motor Drive Problems

An Integrated Inverter Output Passive Sinewave Filter for Eliminating Both Common and Differential Mode PWM Motor Drive Problems An Integrated Inverter Output Passive Sinewave Filter for Eliminating Both Common and Differential Mode PWM Motor Drive Problems Todd Shudarek Director of Engineering MTE Corporation Menomonee Falls, WI

More information

Fuzzy Logic Control of APF for Harmonic Voltage Suppression in Distribution System

Fuzzy Logic Control of APF for Harmonic Voltage Suppression in Distribution System Fuzzy Logic Control of APF for Harmonic Voltage Suppression in Distribution System G. Chandrababu, K. V. Bhargav, Ch. Rambabu (Ph.d) 3 M.Tech Student in Power Electronics, Assistant Professor, 3 Professor

More information

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech

More information

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER Rajesh Kr. Ahuja 1, Aasha Chauhan 2, Sachin Sharma 3 Rajesh Kr. Ahuja Faculty, Electrical & Electronics Engineering Dept.

More information

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives ABB drives Technical guide No. 6 Guide to harmonics with AC drives 2 Guide to harmonics with AC drives Technical guide No. 6 Technical guide No. 6 Guide to harmonics with AC drives Copyright 2013 ABB.

More information

Comparison of Concepts for Improving the Line Power Quality of Electrostatic Precipitator Systems

Comparison of Concepts for Improving the Line Power Quality of Electrostatic Precipitator Systems Comparison of Concepts for Improving the Line Power Quality of Electrostatic Precipitator Systems Thiago Soeiro*, Jürgen Biela*, Jörgen Linnér**, Per Ranstad**, and Johann W. Kolar* * Power Electronic

More information

TAMING THE POWER ABB Review series

TAMING THE POWER ABB Review series TAMING THE POWER ABB Review series 54 ABB review 3 15 Beating oscillations Advanced active damping methods in medium-voltage power converters control electrical oscillations PETER AL HOKAYEM, SILVIA MASTELLONE,

More information

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL 14 CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL 2.1 INTRODUCTION Power electronics devices have many advantages over the traditional power devices in many aspects such as converting

More information

Modeling of Conduction EMI Noise and Technology for Noise Reduction

Modeling of Conduction EMI Noise and Technology for Noise Reduction Modeling of Conduction EMI Noise and Technology for Noise Reduction Shuangching Chen Taku Takaku Seiki Igarashi 1. Introduction With the recent advances in high-speed power se miconductor devices, the

More information

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE KARTIK TAMVADA Department of E.E.E, V.S.Lakshmi Engineering College for Women, Kakinada, Andhra Pradesh,

More information

NJWA - Harmonics and Drives Proper System Design

NJWA - Harmonics and Drives Proper System Design Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives

More information

Topologies for Optimizing Efficiency, EMC and Time to Market

Topologies for Optimizing Efficiency, EMC and Time to Market LED Power Supply Topologies Topologies for Optimizing Efficiency, EMC and Time to Market El. Ing. Tobias Hofer studied electrical engineering at the ZBW St. Gallen. He has been working for Negal Engineering

More information

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017 Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates

More information

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to

More information

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Dr. Jagdish Kumar, PEC University of Technology, Chandigarh Abstract the proper selection of values of energy storing

More information

New Unidirectional Hybrid Delta-Switch Rectifier

New Unidirectional Hybrid Delta-Switch Rectifier 2011 IEEE Proceedings of the 37th Annual Conference of the IEEE Industrial Electronics Society (IECON 2011), Melbourne, Australia, November 7-10, 2011. New Unidirectional Hybrid Delta-Switch Rectifier

More information

Fuzzy Controlled Capacitor Voltage Balancing Control for a Three Level Boost Converter

Fuzzy Controlled Capacitor Voltage Balancing Control for a Three Level Boost Converter Fuzzy Controlled Capacitor Voltage Balancing Control for a Three evel Boost Converter Neethu Rajan 1, Dhivya Haridas 2, Thanuja Mary Abraham 3 1 M.Tech student, Electrical and Electronics Engineering,

More information

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez Harmonic Power A VFDs.com Whitepaper Written by Ernesto Jimenez Table of Contents 1. Need for Clean Electricity 2. What Are Harmonics? 3. Lower Order Harmonics 4. Causes of Harmonics 5. Effects of Harmonics

More information

The unified power quality conditioner: the integration of series and shunt-active filters

The unified power quality conditioner: the integration of series and shunt-active filters Engineering Electrical Engineering fields Okayama University Year 1997 The unified power quality conditioner: the integration of series and shunt-active filters Hideaki Fujita Okayama University Hirofumi

More information

Case Study Survey of Harmonic Pollution Generated by Railway Systems and Filtering Solutions

Case Study Survey of Harmonic Pollution Generated by Railway Systems and Filtering Solutions Case Study Survey of Harmonic Pollution Generated by Railway Systems and Filtering Solutions MIHAELA POPESCU, ALEXANDRU BITOLEANU, MIRCEA DOBRICEANU Faculty of Electromechanical, Environmental and Industrial

More information

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder R. W. Erickson Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder 16.4. Power phasors in sinusoidal systems Apparent power is the product of the rms voltage and

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution Agenda I. Harmonic Basics II.Harmonic Mitigation Solutions III.Case Study 2 Harmonic

More information

Reduce harmonics in HVAC&R inverters through C-Less technology

Reduce harmonics in HVAC&R inverters through C-Less technology Reduce harmonics in HVAC&R inverters through C-Less technology Karim Lamrabtine Global Product Manager VSD 14-15 SEPTEMBER 2011, MUNICH Agenda www.infoplc.net What are Harmonics? Standards Compliance How

More information

Power Factor Pre-regulator Using Constant Tolerance Band Control Scheme

Power Factor Pre-regulator Using Constant Tolerance Band Control Scheme Power Factor Pre-regulator Using Constant Tolerance Band Control Scheme Akanksha Mishra, Anamika Upadhyay Akanksha Mishra is a lecturer ABIT, Cuttack, India (Email: misakanksha@gmail.com) Anamika Upadhyay

More information

Comparison Between CCM Single-Stage And Two-Stage Boost PFC Converters *

Comparison Between CCM Single-Stage And Two-Stage Boost PFC Converters * Comparison Between CCM Single-Stage And Two-Stage Boost PFC Converters * Jindong Zhang 1, Milan M. Jovanoviü, and Fred C. Lee 1 1 Center for Power Electronics Systems The Bradley Department of Electrical

More information

CHAPTER 3. SINGLE-STAGE PFC TOPOLOGY GENERALIZATION AND VARIATIONS

CHAPTER 3. SINGLE-STAGE PFC TOPOLOGY GENERALIZATION AND VARIATIONS CHAPTER 3. SINGLE-STAGE PFC TOPOLOG GENERALIATION AND VARIATIONS 3.1. INTRODUCTION The original DCM S 2 PFC topology offers a simple integration of the DCM boost rectifier and the PWM DC/DC converter.

More information

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier Transactions on Electrical Engineering, Vol. 1 (2012), No. 1 30 Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier Jan Michalík1), Jan Molnár2) and Zdeněk Peroutka2)

More information

7/15/2002 PP.AFD.08 1 of 28

7/15/2002 PP.AFD.08 1 of 28 Power Quality Considerations When Applying Adjustable Frequency Drives Explanations and Various Countermeasures 7/15/2002 PP.AFD.08 1 of 28 Power Quality Why the Renewed Interest in Power Quality? Copy

More information

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive B. Mohan Reddy 1, G.Balasundaram 2 PG Student [PE&ED], Dept. of EEE, SVCET, Chittoor

More information

Sepic Topology Based High Step-Up Step down Soft Switching Bidirectional DC-DC Converter for Energy Storage Applications

Sepic Topology Based High Step-Up Step down Soft Switching Bidirectional DC-DC Converter for Energy Storage Applications IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 3 Ver. IV (May June 2017), PP 68-76 www.iosrjournals.org Sepic Topology Based High

More information

TO LIMIT degradation in power quality caused by nonlinear

TO LIMIT degradation in power quality caused by nonlinear 1152 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 6, NOVEMBER 1998 Optimal Current Programming in Three-Phase High-Power-Factor Rectifier Based on Two Boost Converters Predrag Pejović, Member,

More information

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Control Of Shunt Active Filter Based On Instantaneous Power Theory B.Pragathi Department of Electrical and Electronics Shri Vishnu Engineering College for Women Bhimavaram, India Control Of Shunt Active Filter Based On Instantaneous Power Theory G.Bharathi Department

More information

A Modular Single-Phase Power-Factor-Correction Scheme With a Harmonic Filtering Function

A Modular Single-Phase Power-Factor-Correction Scheme With a Harmonic Filtering Function 328 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 2, APRIL 2003 A Modular Single-Phase Power-Factor-Correction Scheme With a Harmonic Filtering Function Sangsun Kim, Member, IEEE, and Prasad

More information

EMI Filters Demystified. By William R. Bill Limburg February 21, 2018 Phoenix Chapter, IEEE EMC Society

EMI Filters Demystified. By William R. Bill Limburg February 21, 2018 Phoenix Chapter, IEEE EMC Society EMI Filters Demystified By William R. Bill Limburg February 21, 2018 Phoenix Chapter, IEEE EMC Society An EMI Filter Defined An EMI filter is a network designed to prevent unwanted electrical conducted

More information

A Single Phase Single Stage AC/DC Converter with High Input Power Factor and Tight Output Voltage Regulation

A Single Phase Single Stage AC/DC Converter with High Input Power Factor and Tight Output Voltage Regulation 638 Progress In Electromagnetics Research Symposium 2006, Cambridge, USA, March 26-29 A Single Phase Single Stage AC/DC Converter with High Input Power Factor and Tight Output Voltage Regulation A. K.

More information

University of Kurdistan. Adaptive virtual impedance scheme for selective compensation of voltage unbalance and harmonics in microgrids

University of Kurdistan. Adaptive virtual impedance scheme for selective compensation of voltage unbalance and harmonics in microgrids University of Kurdistan Dept. of Electrical and Computer Engineering Smart/Micro Grid Research Center smgrc.uok.ac.ir Adaptive virtual impedance scheme for selective compensation of voltage unbalance and

More information

Electronics II. 3. measurement : Tuned circuits

Electronics II. 3. measurement : Tuned circuits Electronics II. 3. measurement : Tuned circuits This laboratory session involves circuits which contain a double-t (or TT), a passive RC circuit: Figure 1. Double T passive RC circuit module The upper

More information

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications.

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications. Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications. 1 Vikas Kumar Chandra, 2 Mahendra Kumar Pradhan 1,2 ECE Department, School of

More information

Design of a Hybrid Active Filter for Harmonics Suppression in Industrial Facilities

Design of a Hybrid Active Filter for Harmonics Suppression in Industrial Facilities Design of a Hybrid Active Filter for Harmonics Suppression in Industrial Facilities Tzung-Lin Lee Yen-Ching Wang Jian-Cheng Li Department of Electrical Engineering National Sun Yat-sen University 7, Lienhai

More information

TD-100. HAEFELY HIPOTRONICS Technical Document

TD-100. HAEFELY HIPOTRONICS Technical Document HAEFELY HIPOTRONICS Technical Document Breaking the limit of power capacitor resonance frequency with help of PD pulse spectrum to check and setup PD measurement P. Treyer, P. Mraz, U. Hammer, S. Gonzalez

More information

LOW ORDER HARMONICS IMPROVEMENT OF A SINGLE GRID CONNECTED INVERTER SYSTEM UNDER PR CONTROL TECHNIQUE

LOW ORDER HARMONICS IMPROVEMENT OF A SINGLE GRID CONNECTED INVERTER SYSTEM UNDER PR CONTROL TECHNIQUE LOW ORDER HARMONICS IMPROVEMENT OF A SINGLE GRID CONNECTED INVERTER SYSTEM UNDER PR CONTROL TECHNIQUE S. Salimin 1, A. A Bakar 1 and M. Armstrong 2 1 Department of Electrical Power, Faculty of Electrical

More information

Designing Passive Filter Using Butterworth Filter Technique

Designing Passive Filter Using Butterworth Filter Technique International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 8, Number 1 (2015), pp. 57-65 International Research Publication House http://www.irphouse.com Designing Passive Filter

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION 1.1 Introduction Power semiconductor devices constitute the heart of the modern power electronics, and are being extensively used in power electronic converters in the form of a

More information

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Harmonics Reduction using 4-Leg Shunt Active Power Filters Harmonics Reduction using 4-Leg Shunt Active Power Filters K Srinivas Assistant Professor & Department of EEE & JNTUH CEJ Telangana, India. Abstract Harmonics in power system are caused by highly non-linear

More information

Study of Harmonics and THD of Nine Phase PWM Inverter Drive with CLC Filter for motor drive applications

Study of Harmonics and THD of Nine Phase PWM Inverter Drive with CLC Filter for motor drive applications International Journal of Electronics Engineering Research. ISSN 0975-6450 Volume 9, Number 3 (2017) pp. 369-376 Research India Publications http://www.ripublication.com Study of Harmonics and THD of Nine

More information

Shunt Active Power Filter for Compensation of System Harmonics

Shunt Active Power Filter for Compensation of System Harmonics Volume 5, Issue 1 (February, 018) E-ISSN : 48-7 P-ISSN : 454-1 Shunt Active Power Filter for of System Harmonics Badal Devanand Umare 1, A. S. Sindekar 1 PG Scholar, HOD, Department of Electrical Engineering,

More information

Analysis of Harmonic Distortion in Non-linear Loads

Analysis of Harmonic Distortion in Non-linear Loads Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna

More information

THREE PHASE RECTIFIER TOPOLOGY WITH PRACTICALLY SINUSOIDAL INPUT CURRENTS

THREE PHASE RECTIFIER TOPOLOGY WITH PRACTICALLY SINUSOIDAL INPUT CURRENTS THREE PHASE RECTIFIER TOPOLOGY WITH PRACTICALLY SINUSOIDAL INPUT CURRENTS By D.Alexa, I.V.Pletea, N.Lucanu, E.Coca, L.Ţigaeru Technical University of Iasi, Faculty of Electronics and Telecommunications

More information

CHAPTER 4 4-PHASE INTERLEAVED BOOST CONVERTER FOR RIPPLE REDUCTION IN THE HPS

CHAPTER 4 4-PHASE INTERLEAVED BOOST CONVERTER FOR RIPPLE REDUCTION IN THE HPS 71 CHAPTER 4 4-PHASE INTERLEAVED BOOST CONVERTER FOR RIPPLE REDUCTION IN THE HPS 4.1 INTROUCTION The power level of a power electronic converter is limited due to several factors. An increase in current

More information