Reactors for filtering

Size: px
Start display at page:

Download "Reactors for filtering"

Transcription

1 NEW ZEALAND Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box , Henderson, Auckland, New Zealand Phone: info@LPINZ.co.nz Web: Reactors for filtering

2 Introduction 3 P.7 - Reactors for filtering Product selection table 5 Reactors R / RB Reactors III for harmonic rejection filters (for FR) 7 Reactors RE / RBE Reactors III for harmonic rejection filters (for FRE static) 10 Reactors LR / LRB Reactors for filtering for power converters (network side) 12 P7-2

3 Protection and control Reactors for filtering Many of the low voltage alteration problems can be corrected with filters. In particular, CIRCUTOR has developed an integral power filter manufacturing program to correct the following problems: Resonance problems in the LV networks, caused by the power factor compensation equipment Rejection of harmonics in some parts of the installation Absorption of harmonics to reduce the distortion rate (THD) of the installation Limitation of the short-circuit power in some installation points a resonance frequency that is far away from the harmonic frequencies present in the network. The purpose of the rejection filter is to prevent the resonance between the inductive impedance resulting from the line, power supply transformer and capacitors installed to compensate the power factor and thus prevent an overload of harmonics in the line and the capacitors. The filter is composed of various L-C branches, with a special configuration and response curve, as shown in Fig. 1. The complete filter set can be composed with any number of branches to compensate the reactive energy present in the installation. P.7 Filtering of the current absorbed by static converters (speed variators, etc.) in the alternating or direct current side. CIRCUTOR has the adequate machinery to manufacture any type of LV reactors, in accordance with the customer's specifications. The reactors for this type of filters are specified by the so-called "overvoltage factor", p%, which provides the ration between the reactor and capacitor voltages, establishing the resonance of the L-C set. In addition, it tunes a different frequency that is far from harmonic frequencies. Setup of the rejection filter Reactors for rejection filters p (%) = 100 U L / U C = 100 (f / f r ) 2 A series of capacitor capacitor banks with rejection reactors must be installed to compensate the reactive energy in installations with a high content of harmonics. U L : Voltage drop in the reactor U C : Resulting voltage in the capacitor f: nominal frequency in the network f r : serial frequency tuned by the L-C set Response in standard frequencies In this case, the solution entails the addition of a reactor in series with each capacitor, forming a rejection filter with Direct conversion db / 0.1 Ω to Ω Z Z Z Z (db / 0.1 Ω) Filter (db / 0.1 Ω) Filter 0 0, ,00 2 0, ,25 4 0, ,58 6 0, ,99 8 0, , , , , , , , , , , ,94 Table 1: Conversion of db / 0.1 Ω to Ω P7-3

4 Switching micro-drop filtering in the network and motor Point PCC Inverter Other loads The impedances of filters are generally displayed on logarithmic charts, showing the impedances related to a standard value in order (in our case 0.1 Ω), depending on the frequency (axis of abcissas). The unit is displayed as (db / 0.1 Ω) and defined as: Z (db / 0.1 Ω) = 20 log [Z (filter) / 0.1 Ω] Filter reactors for power converters available. However, CIRCUTOR can design and manufacture the adequate reactors to cater for any need. Fig. 2a and 2b show an example of the typical response of two filter branches for harmonics 5 and 7. Fig. 2c shows the response of a bank of filters composed of branches 5, 7, 11, 13 and an overlapping stage for n > 15. PCC voltage without L red Motor current without L mot PCC voltage with L red Motor current with L mot The speed regulators for direct and alternating current motors (frequency variators), UPS systems and, in general, all converters based on thyristors or power transistors, are prone to the generation of alterations in the network or an excessive rippling in the direct current side (motor, in the case of dc regulators). These alterations affect adjoining equipment and can even affect the operation of the converter. Mains current without L cc Mains current with L cc The basic types of problems are as follows: Fig.2a. Response in branch frequencies n = 5 Elimination of micro-drops and filtering of harmonics Micro-drops in the voltage and excessive di/dt on the network side with the abovementioned equipment Other loads Commutation choke Current peaks in frequency variators, caused by the connection of capacitors to the direct current stage Excessive rippling and switching sparks in the motor of dc equipment Absortion filter Switching improvement inductance in dc All of these problems can be solved with shock reactors or filters, as shown on table 2. Reactors for absorption filters These filters are composed of the branches, groups of L-C branches or harmonics being filtered. The resonance frequencies of the different groups are identical to those of the harmonics being filtered. Fig.2b. Response in branch frequencies n = 7 Mains current without L cc Table 1. Filter reactors Mains current with L cc In construction terms, each branch is similar to that of a rejection filter, but the maximum harmonic current filtered is the important information in this case, so that the inductance and capacitor must be dimensioned for such purposes. There are many different requirements and there are no standard components Fig.2c. Response in filter frequencies with n = 5, 7, 11, 13, >15 P7-4

5 R / RX Reactors Reactors III for harmonic rejection filters Description Features CIRCUTOR has a standard range of rejection reactors p = 7 %, with a resonance frequency of 189 Hz for 50 Hz networks (or on demand 227 Hz for 60 Hz networks). This is the most frequent tuning value to avoid any resonance of the 5th harmonic and above. The set of capacitors-reactors absorbs part of the current of the 5th harmonic and acts as a rejection filter for higher frequencies. In some installations, other values of p % are required, for example 5.6 % (210 Hz), 6 % (204 Hz), 14 % (134 Hz), etc. CIRCUTOR can build reactors on demand, which will be adapted to any power rating, p %, voltage and frequency. Low-powered reactors, R type, are built with plates with low losses and are coiled with a copper conductor. The connection is achieved with the adequate terminals. In the case of higher power ratings, RB reactors are used, with a magnetic plate nucleus and multiple steel cores, which offer excellent characteristics and a low loss ratio. Aluminum band coils are used (or copper band, on demand) and the input and output connections run through a plate. Features Voltage Network frequency Power rating Value of p % Type of conductor Tolerance L ± 5 % Linearity (5 % L) Isolation voltage 400 V On demand: up to 1000 V 50 Hz On demand: 60 Hz In accordance with the table Other values on demand 7 % (189 Hz) Other values on demand R: copper wire RB: aluminum band 1.8 I n 4 kv Maximum room temperature -10 ºC ºC Internal isolation Class F (155 ºC) On demand: class H (180 ºC) Maximum overload Permanent 1.17 I n Temporary (1 min) 2 I n Safety Protection thermostat Opening at 90 ºC Degree of protection IP 00 Indoor Installation Standards UNE-EN-60289, IEC Application Both R and RB type reactors have a vacuum varnish sealing to increase the insulation, providing a greater mechanical resistance and reduce the level of noise. The rejection reactors of the R / RB series have been specially designed for their use in capacitor banks in installations with a high harmonic content. The reactors must be connected in series to each capacitor for the adequate protection of capacitors and to avoid the resonance effects in the installation. P7-5

6 R / RX / RB / RBX Reactors Reactors III for harmonic rejection filters Dimensions R - 7% RB - 7% RX - 7% RBX - 7% Type a b c d e f g R R R R R R R R R R R R Type a b c d e f g RX-6, RX-12, RX RX RBX RBX RBX RBX RBX RBX RBX P7-6

7 R / RX / RB / RBX Reactors Reactors III for harmonic rejection filters Connections Reactancia Condensador References Reactors III series R / RB at 400 Vac, 50 Hz, p = 7 % (189 HZ) For capacitors: kvar I n (A) L (mh) Losses Weight (kg) Type Code CF 46 / 6 5 7,5 7,66 25 W 6 R / R P70110 CF 46 / ,83 50 W 8 R / R-12,5-460 P70115 CF 46 / ,55 57 W 9,5 R / R P70117 CF 46 / ,92 76 W 14 RB / RB P70125 CF 46 / ,53 90 W 14 RB / RB P70130 CF 46 / , W 19 RB / RB P70135 CF 46 / , W 20 RB / RB P70140 CF 46 / , W 27 RB / RB P70145 CF 46 / , W 31 RB / RB P70150 CF 46 / , W 38 RB / RB P70155 CF 46 / 62 x , W 50 RB / RB P70160 CF 46 / 74 x , W 58 RB / RB P70165 Reactors III series R / RB at 400 Vac, 50 Hz, p = 7 % (189 HZ) For capacitors: kvar I n (A) L (mh) Losses Weight (kg) Type Code CFB 46 / 7,5 6,25 9 6, RX-6, P7101F CFB 46 / 15 12,5 18 3, ,2 RX-12,5-400 P71013 CFB 46 / , ,5 RX P71015 CFB 46 / , RX P71016 CFB 46 / , RBX P72125 CFB 46 / , RBX P72130 CFB 46 / , ,5 RBX P72135 CFB 46 / , ,5 RBX P72140 CFB 46 / , ,5 RBX P72145 CFB 46 / , ,7 RBX P72150 CFB 46 / , RBX P72155 P7-7

8 Reactors RE / RBE Reactors III for static capacitor banks Description Features CIRCUTOR has standardized the reactors of the RE / RBE series, with a special design for their use in static capacitor banks. The best operation of the set requires the reactors to be connected within the triangle composed by the capacitor-reactor set. At the same power rating, the RE / RBE reactors have a nominal current value that is 1.73 times smaller and an inductance value that is 3 times greater than that in an R / RB reactor. The company has a standard range of 400 V rejection reactors with p = 7 %, with a resonance frequency of 189 Hz for 50 Hz networks (or on demand 227 Hz for 60 Hz networks). In addition, reactors can be manufactured on demand for static capacitor banks adapted to any value of the power rating, p %, voltage and frequency. Low-powered reactors, RE type, are built with plates with low losses and are coiled with copper wire. The connection is achieved with the adequate terminals. In the case of higher power ratings, RBE reactors are used, with a magnetic plate nucleus and multiple steel cores, which offer excellent characteristics and a low loss ratio. The coils are made with an aluminium band (or copper band, on demand). The input and output connections run through a plate. Both RE and RBE type reactors have a vacuum varnish sealing to increase the insulation and reduce the levels of noise. Features Voltage Network frequency Power rating Value of p % Type of conductor Tolerance L ± 5 % Linearity (5 % L) Isolation voltage Application The rejection reactors of the RE / RBE series have been specially designed for their use in capacitor banks in installations with a high harmonic content. The reactors must be connected in series to each capacitor for the 400 V On demand: up to 1000 V 50 Hz On demand: 60 Hz In accordance with the table Other values on demand 7 % (189 Hz) Other values on demand RE: copper wire RBE: aluminum band 1.8 I n 4 kv Maximum room temperature -10 ºC ºC Internal isolation Class F (155 ºC) On demand: class H (180 ºC) Maximum overload Permanent 1.17 I n Temporary (1 min) 2 I n Safety Protection thermostat Opening at 90 ºC Degree of protection IP 00 Indoor Installation Standards UNE-EN-60289, IEC adequate protection of capacitors, the static operations module and to avoid the resonance effects in the installation. P7-8

9 Reactors RE / RBE Reactors III for static capacitor banks Dimensions RE RBE Type a b c d e f g RE RE RE RE RE RE RE RBE RBE RBE References Reactors III series RE / RBE at 400 Vac, 50 Hz, p = 7 % (189 HZ) For capacitors: kvar I n (A) L (mh) Losses (W) Weight (kg) Type Code CF 46 / 6-6B , RE / RE P70210 CF 46 / B , RE / RE-12,5-460 P70215 CF 46 / 19-6B , ,5 RE / RE P70220 CF 46 / 25-6B , ,5 RE / RE P70225 CF 46 / 30-6B , RE / RE P70230 CF 46 / 37-6B , ,5 RE / RE P70235 CF 46 / 50-6B , ,5 RE / RE P70240 CF 46 / 62-6B , RBE / RBE P70245 CF 46 / 74-6B , RBE / RBE P70250 CF 46 / 100-6B , RBE / RBE P70255 Connections Reactancia Condensador P7-9

10 LR / LRB Reactors Reactors for filtering for power converters (network side) Description Features The motor speed regulation equipment, frequency variators, UPS units, etc. generate alterations in the network, which affect other loads in the installation of the operation of the equipment. The LR / LRB reactors connected to the input on the network side of the equipment can attenuate voltage peaks and reduce the harmonic distortion generated by the power electronics. The LR / LRB Reactors for filtering can reduce the current harmonics in any converter from % to values around 20 %. In addition, they reduce the shortcircuit current and increase the safety of the converter's semi-conductors. When installed on the motor side, they can attenuate harmonic frequencies caused during switching operations. Low-powered reactors, LR type, are built with plates with low losses and are coiled with copper wire. The connection is achieved with the adequate terminals. In the case of higher currents, LRB reactors are used, with a magnetic plate nucleus and multiple steel cores, which offer excellent characteristics and a low loss ratio. Copper band coils (or aluminium band, on demand). The connections run through a plate. Both LR and LRB type reactors have a vacuum varnish sealing to increase the insulation, providing a greater mechanical resistance and reduce the level of noise. Features Voltage drop U k % (LR 04: 400 V or Lr 02: 230 V) Voltage Value of L (mh) Nominal current Type of conductor Tolerance L ± 5 % Linearity (5 % L) Isolation voltage Application The reactors of the LR / LRB series are prepared and can be used on the network and motor sides. They attenuate micro-drops and peaks during the initial connection and switching operations, and they reduce the rate of harmonics from the network current. 4 % network at 50 Hz (4.8 % network at 60 Hz) Other values on demand Up to 1000 Vac In accordance with the table Other values on demand In accordance with the table Other values on demand LR: copper wire LRB: copper band (or aluminium, on demand) 1.5 I n 4 kv Maximum room temperature -10 ºC ºC Internal isolation Maximum overload Permanent 1.17 I n Temporary (1 min) 2 I n Safety Protection thermostat On demand Degree of protection IP 00 Indoor Installation Standards UNE-EN-60289, IEC Class F (155 ºC) On demand: class H (180 ºC) P7-10

11 LR / LRB Reactors Reactors for filtering for power converters (network side) Dimensions LR 04 LRB 04 Type a b c Type a b c LR LRB LR LRB LR LRB LR LRB LR LRB LR LRB LR LRB LR LRB LR LRB LR LRB LR LRB LR LR References Type of threephase network at: Motor power (kw) I n (A) L (mh) Losses (W) Weight (kg) Type Code 380 / 415 V 0,75 2,5 14,8 6 1,8 LR P / 415 V 1,5 4 7,90 8 1,8 LR P / 415 V 2,2 5,5 5, LR P / 415 V 3 7,5 4, LR P / 415 V , ,3 LR P / 415 V 5,5 13 2, ,3 LR P / 415 V 7,5 17 1, ,5 LR P / 415 V , ,6 LR P / 415 V , LR P / 415 V 18,5 40 0, ,5 LR P7030A 380 / 415 V , LR P7030B 380 / 415 V , ,5 LR P7030C 380 / 415 V , LR P7030D 380 / 415 V , LRB P7030E 380 / 415 V , LRB P7030F 380 / 415 V , LRB P7030G 380 / 415 V , LRB P7030H 380 / 415 V , LRB P7030J 380 / 415 V , LRB P7030K 380 / 415 V , LRB P7030L 380 / 415 V , LRB P7030M 380 / 415 V , LRB P7030N 380 / 415 V , LRB P7030P 380 / 415 V , LRB P7030Q Voltage drop U k : 4 % for 400 V - 50 Hz / 4.8 % for 400 V - 60 Hz) P7-11

12 LR / LRB Reactors Reactors for filtering for power converters (network side) Dimensions LR 02 LRB 02 Type a b c Type a b c LR LRB LR LRB LR LRB LR LRB LR LRB LR LRB LR LR References Type of threephase network at: Motor power (kw) I n (A) L (mh) Losses (W) Weight (kg) Type Code 220 / 240 V 0,75 4 4,90 8 1,8 LR P / 240 V 1,5 7 2, LR P / 240 V 2,2 10 1, ,3 LR P / 240 V , ,3 LR P / 240 V , ,5 LR P / 240 V 5,5 22 0, ,6 LR P / 240 V 7,5 30 0, LR P / 240 V , ,5 LR P / 240 V , ,5 LRB P / 240 V 18,5 70 0, LRB P7031A 220 / 240 V , LRB P7031B 220 / 240 V , LRB P7031C 220 / 240 V , LRB P7031D 220 / 240 V , LRB P7031E Voltage drop U k : 4 % for 230 V - 50 Hz / 4.8 % for 230 V - 60 Hz) Connections P7-12

13 P7-13

14

Automatic capacitor banks with detuned filters

Automatic capacitor banks with detuned filters Power factor correction and harmonic filtering 5 R. /6 Automatic capacitor banks with detuned filters R. 5 /6 Automatic capacitor banks with detuned filters Introduction R5/6-3 R.5 - Automatic capacitor

More information

Automatic capacitor banks with detuned filters

Automatic capacitor banks with detuned filters الکتروه م ند Power factor correction and harmonic filtering Automatic capacitor banks with detuned filters www.electrohamand.com Automatic capacitor banks with detuned filters Introduction R5/6-3 R.5 -

More information

Power factor correction and harmonic filtering. Harmonic filters and EMI

Power factor correction and harmonic filtering. Harmonic filters and EMI Power factor correction and harmonic filtering Harmonic filters and EMI Introduction 3 R.7 - Harmonic filters and EMI Filtering unit selection guide 12 LCL Harmonic filter for power converters 13 LCL-TH

More information

Series P. Applications

Series P. Applications Ratings 25 800 VA Voltage Primary 230 / 400 / 460 V range Secondary 6 / 12 V 12 / 24 V 24 / 48 V 115 / 230 V Voltage selection by means of metal connection bridges, offering the full rated power at any

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

Power factor correction and harmonic filtering. Automatic power factor regulators

Power factor correction and harmonic filtering. Automatic power factor regulators Power factor correction and harmonic filtering Automatic power factor regulators Automatic power factor reguladors R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent

More information

Power factor correction and harmonic filtering. Automatic power factor regulators R.1

Power factor correction and harmonic filtering. Automatic power factor regulators R.1 Power factor correction and harmonic filtering Automatic power factor regulators R.1 R.1 Automatic power factor regulators R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

Protection relays and transformers

Protection relays and transformers NEW ZEALAND WWW.LPINZ.CO.NZ Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box 21-872, Henderson, Auckland, New Zealand Phone:+64 9 833 5749 Email:info@LPINZ.co.nz Web: www.lpinz.co.nz Protection

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Static Frequency Converter TMP-TS250. Series

Static Frequency Converter TMP-TS250. Series Static Frequency Converter TMP-TS250 Series Preface SFC is a load commutated inverter LCI, which drives a gas turbine generator like a synchronous motor, and accelerates up to the gas turbine s self-sustaining

More information

ZITARES LCS Non-SELV, Constant current control gear, 1-channel, non-dimmable

ZITARES LCS Non-SELV, Constant current control gear, 1-channel, non-dimmable ECG versions Order no. Output currents Output power LCS135-70FX-01/220-240 10116496 350 ma max. 70 W LCS150-70FX-01/220-240 10116500 500 ma max. 70 W LCS170-70FX-01/220-240 10116504 700 ma max. 70 W Performance

More information

Static Frequency Converter TMP-TS370. Series

Static Frequency Converter TMP-TS370. Series Static Frequency Converter TMP-TS370 Series Preface SFC is a load commutated inverter (LCI), which drives a gas turbine generator like a synchronous motor, and accelerates up to the gas turbine s self-sustaining

More information

4Q POWER AMPLIFIERS AC AND DC 3000VA 3x3000VA

4Q POWER AMPLIFIERS AC AND DC 3000VA 3x3000VA PERFORMANCES High accuracy High stability Fast transients High inrush current facilities Wide bandwidth 25 khz at -3dB Internal waveform DC and up to 10 khz Very low distortion Quadrant change without

More information

POWER AMPLIFIERS 4 QUADRANTS 3x500 VA to 3x1500 VA - THREE-PHASES

POWER AMPLIFIERS 4 QUADRANTS 3x500 VA to 3x1500 VA - THREE-PHASES PERFORMANCES High accuracy High stability Fast transients High inrush current facilities Wide bandwidth Very low distortion Quadrant change without transition Very low output impedance Low noise RS232

More information

NSL-10 STANDARD LIFE MODULAR CAPACITORS

NSL-10 STANDARD LIFE MODULAR CAPACITORS ADVANCE P.F. CORRECTION SOLUTIONS FROM NEPTUNE-DUCATI Channel Partner Ph: 02621-234524, 99242 04524 Industrial Trading Co. 10B Dharma Super Market, Kim Char Rasta, Contact : Paresh Gandhi (98241 31205)

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. 1 PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. DEFINATIONS Working /Active Power: Normally measured in kilowatts (kw). It does the "work" for the system--providing the motion, torque,

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA SETTING UP REACTIVE POWER COMPENSATION DEVICES SELECTING A REACTIVE POWER COMPENSATION DEVICE To effectively compensate the

More information

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives ABB drives Technical guide No. 6 Guide to harmonics with AC drives 2 Guide to harmonics with AC drives Technical guide No. 6 Technical guide No. 6 Guide to harmonics with AC drives Copyright 2013 ABB.

More information

ZITARES NCS 2 nd Generation Non-SELV, Constant current control gear, 1-channel, non-dimmable

ZITARES NCS 2 nd Generation Non-SELV, Constant current control gear, 1-channel, non-dimmable ECG versions Model Order no. Output currents Output power NCS135-70FX-20/220-240 10112200 120... 350 ma 2... 67 W NCS140-70FX-20/220-240 10120160 120... 400 ma 2... 70 W NCS180-100FX-20/220-240 10112201

More information

Webinar Organizers. Ryan Shea. Don Miller. Joe Ryan. Support Specialist. Applications Specialist. Product Manager. Precision Digital Corporation

Webinar Organizers. Ryan Shea. Don Miller. Joe Ryan. Support Specialist. Applications Specialist. Product Manager. Precision Digital Corporation Webinar Organizers Joe Ryan Product Manager Precision Digital Corporation Ryan Shea Applications Specialist Precision Digital Corporation Don Miller Support Specialist Precision Digital Corporation Agenda,

More information

INDEX. Micro-ohmmeter MH-10 Page 3. MI (5, 10, 15, 20 kv) Page 4 Mega-ohmmeter MD (5 kv) Page 4

INDEX. Micro-ohmmeter MH-10 Page 3. MI (5, 10, 15, 20 kv) Page 4 Mega-ohmmeter MD (5 kv) Page 4 Micro-ohmmeter MH-10 Page 3 MI (5, 10, 15, 20 kv) Page 4 Mega-ohmmeter MD (5 kv) Page 4 Earth resistance meter TL-5 Page 5 Indirect earth contact simulator MPC (5, 20, 50 A) Page 6 Trip time tester CR

More information

LV Compensation & Filtering Products

LV Compensation & Filtering Products GE Grid Solutions LV Compensation & Filtering Products Providing Power Quality and Energy Efficiency Low (LV) reactive power compensation and harmonic filtering solutions help customers to improve the

More information

Question Paper Profile

Question Paper Profile I Scheme Question Paper Profile Program Name : Electrical Engineering Program Group Program Code : EE/EP/EU Semester : Third Course Title : Electrical Circuits Max. Marks : 70 Time: 3 Hrs. Instructions:

More information

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults Enhancement of Power Quality in Distribution System Using D-Statcom for Different s Dr. B. Sure Kumar 1, B. Shravanya 2 1 Assistant Professor, CBIT, HYD 2 M.E (P.S & P.E), CBIT, HYD Abstract: The main

More information

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives 2 TECHNICAL GUIDE NO. 6 GUIDE TO HARMONICS WITH AC DRIVES Guide to harmonics This guide is part of ABB s technical guide series, describing

More information

Power Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers

Power Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers EPCOS Product Brief 2017 Power Quality Solutions of Active Harmonic Filters and Power Optimizers EPCOS has been offering a comprehensive range of key components for power factor correction (PFC) and power

More information

Index. Capacitor Switching - 2 Contactors. Typical Circuit Diagram 2. Auxiliary Contact Blocks 2. Contactors 3. Dimensions 3. Technical Data 4,5,6

Index. Capacitor Switching - 2 Contactors. Typical Circuit Diagram 2. Auxiliary Contact Blocks 2. Contactors 3. Dimensions 3. Technical Data 4,5,6 Index Index Page Capacitor Switching - 2 Contactors Typical Circuit Diagram 2 Auxiliary Contact Blocks 2 Contactors 3 Dimensions 3 Technical Data 4,5,6 Contactor operation 7 Function 8 Construction 9 Oscillogram

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

Harmonic Filtering in Variable Speed Drives

Harmonic Filtering in Variable Speed Drives Harmonic Filtering in Variable Speed Drives Luca Dalessandro, Xiaoya Tan, Andrzej Pietkiewicz, Martin Wüthrich, Norbert Häberle Schaffner EMV AG, Nordstrasse 11, 4542 Luterbach, Switzerland luca.dalessandro@schaffner.com

More information

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution Agenda I. Harmonic Basics II.Harmonic Mitigation Solutions III.Case Study 2 Harmonic

More information

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics Power IT LV Active Filters PQFI PQFM PQFK The ABB comprehensive solution for active filtering of harmonics Harmonics and Power Quality Power Quality relates to the amplitude, frequency and distortion of

More information

Transducing electrical quantities Iskra MIS d.d. Measuring Transducers. Features

Transducing electrical quantities Iskra MIS d.d. Measuring Transducers. Features Measuring Transducers Transducing electrical quantities Iskra MIS d.d. Measuring Transducers Features AC, DC POWER SYSTEM MEASUREMENT MICROPROCESSOR CONTROL HOUSING FOR DIN RAIL MOUNTING IN COMPLIANCE

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer LF 510-S I PN = 500 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated

More information

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable Sample Image ECG versions Model Order no. Output currents 1) Output power NCD140-70FX-30/220-240/LI 10142659 1 x 100... 400 ma 5... 70 W NCD175-100FX-30/220-240/LI 10142661 1 x 350... 750 ma 14... 100

More information

Contents. Measurement and checking equipment for transformation centers Micro-ohmmeter MH-10 Page 3. Indirect earth contact simulator TL-5 Page 5

Contents. Measurement and checking equipment for transformation centers Micro-ohmmeter MH-10 Page 3. Indirect earth contact simulator TL-5 Page 5 Measuring and testing equipments P 6 P.6.01 GB for substations Micro-ohmmeter MH-10 Page 3 Mega-ohmmeter MI (5, 10, 15, 20 kv) Page 4 MD (5 kv) Page 4 Indirect earth contact simulator TL-5 Page 5 Indirect

More information

ENA33LCD. Power line analyzer. User and service manual. Obrezija 5 SI-1411 Izlake

ENA33LCD. Power line analyzer. User and service manual.   Obrezija 5 SI-1411 Izlake ENA33LCD Power line analyzer User and service manual version 2.9 (FW version 6.8 and newer) ETI, d.o.o. Obrezija 5 SI-1411 Izlake www.etigroup.eu/products-services 1. Front control panel and terminal plate

More information

High Current, High Power OPERATIONAL AMPLIFIER

High Current, High Power OPERATIONAL AMPLIFIER High Current, High Power OPERATIONAL AMPLIFIER FEATURES HIGH OUTPUT CURRENT: A WIDE POWER SUPPLY VOLTAGE: ±V to ±5V USER-SET CURRENT LIMIT SLEW RATE: V/µs FET INPUT: I B = pa max CLASS A/B OUTPUT STAGE

More information

Hours / 100 Marks Seat No.

Hours / 100 Marks Seat No. 17323 14115 3 Hours / 100 Seat No. Instructions (1) All Questions are Compulsory. (2) Illustrate your answers with neat sketches wherever necessary. (3) Figures to the right indicate full marks. (4) Assume

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

LED Driver Constant voltage

LED Driver Constant voltage Driver LCU 35W 12/24V IP20 EXC EXCITE indoor IP20 series Product description LED Driver Universal input voltage range Constant output voltage Push terminals for simple wiring Nominal life-time up to 50,000

More information

SHUNT ACTIVE POWER FILTER

SHUNT ACTIVE POWER FILTER 75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses Main characteristics Recognized 650 to 300VAC / 63 to 2800A. Exceptionally low I 2 T, Watt losses. Non-magnetic construction, highly reliable low voltage. Indicator system. Conformity to UL, CSA investigated,

More information

Fluke 40/41 Power Harmonics Analysers

Fluke 40/41 Power Harmonics Analysers Data Pack A Issued March 2002 232-4752 Fluke 40/41 Power Harmonics Analysers This data sheet refers to the Fluke 40 and Fluke 41 Power Harmonics Analysers. RS stock no. Description 215-9621 Fluke 41B power

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer LF 210-S/SP3 I PN = 100 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

SUPPLY NETWORK ANALYZER CVM-96 SERIES

SUPPLY NETWORK ANALYZER CVM-96 SERIES SUPPLY NETWORK ANALYZER CVM-96 SERIES (Power Demand) INSTRUCTION MANUAL ( M 981 326 / 00B - GB) (c) CIRCUTOR S.A. ----- Supply network analyzer CVM-96 ------ User's manual --- Page No. 1 CVM-96 SUPPLY

More information

SPECIFICATION Item no.: T60404-N4646-X764

SPECIFICATION Item no.: T60404-N4646-X764 Customer: Standard type Customers Part no: Page 1 of 4 Description Closed loop (compensation) Current Sensor with magnetic field probe Printed circuit board mounting Casing and materials UL-listed Electrical

More information

Advantages. Applications

Advantages. Applications 3 s KH 250 General Data Rated input voltage 2 Vac Rated output voltage 2 Vac Rated power 250 VA Ambient temperature +40 C Degree of protection IP 40 Advantages Compensation for mains voltage fluctuations

More information

Fluke 345. Power Quality Clamp Meter. The ideal meter for commissioning and troubleshooting modern electrical loads

Fluke 345. Power Quality Clamp Meter. The ideal meter for commissioning and troubleshooting modern electrical loads Fluke 345 Power Quality Clamp Meter Technical Data The ideal meter for commissioning and troubleshooting modern electrical loads With a bright color display to analyze the harmonic spectrum, a low-pass

More information

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable ECG versions Model Order no. Output current 1) Output power NCD140-70FX-30/220-240/LI 10142659 100... 400 ma 10... 70 W NCD175-100FX-30/220-240/LI 10142661 350... 750 ma 35... 100 W 1) Adjustable by means

More information

High Performance Current Transducer ITL 900-T = A

High Performance Current Transducer ITL 900-T = A High Performance Current Transducer ITL 900-T For the electronic measurement of currents: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. I PM = 0... 900 A Electrical

More information

DETUNED INDUCTORS FOR PF IMPROVEMENT CAPACITORS

DETUNED INDUCTORS FOR PF IMPROVEMENT CAPACITORS DETUNED INDUCTORS FOR PF IMPROVEMENT CAPACITORS Electrical supply systems harmonics is like a cancer on supply systems and causes extreme bad effects on the supply system component and connected electrical

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer LF 510-S/SP13 I PN = 500 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and

More information

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

شركة الوقت للكهرباء والمقاوالت ذ.م.م. CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution

More information

Chapter 2. The Fundamentals of Electronics: A Review

Chapter 2. The Fundamentals of Electronics: A Review Chapter 2 The Fundamentals of Electronics: A Review Topics Covered 2-1: Gain, Attenuation, and Decibels 2-2: Tuned Circuits 2-3: Filters 2-4: Fourier Theory 2-1: Gain, Attenuation, and Decibels Most circuits

More information

LED Driver Constant voltage

LED Driver Constant voltage Driver LCU 100/96W 12/24V IP20 EXC EXCITE indoor IP20 series Product description LED Driver Universal input voltage range Constant output voltage Push terminals for simple wiring Nominal life-time up to

More information

COMPONENTS MODULES CORES

COMPONENTS MODULES CORES COMPONENTS MODULES CORES 211 SUMIDA Components & Modules GmbH Dr. Hans-Vogt-Platz 1 D-9413 Obernzell Phone: ++49/85 91/937- Fax: ++49/85 91/937-3 E-Mail: contact@sumida-eu.com Internet: www.sumida-eu.com

More information

Vacon Baltic Days Tallinn, Estonia

Vacon Baltic Days Tallinn, Estonia Vacon Baltic Days 22.-23.9.2011 Tallinn, Estonia Vacon Technology Yrjö Karvonen Technical Account Manager Frequency converter Why to use Applications Energy saving Easy to control (ma, V, digital I/O,

More information

EC centrifugal fan. forward curved, dual inlet with housing (flange)

EC centrifugal fan. forward curved, dual inlet with housing (flange) D3G46-AH- ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 D-74673 Mulfingen Phone +49 7938 8- Fax +49 7938 8- info@de.ebmpapst.com www.ebmpapst.com Limited partnership Headquarters Mulfingen County court

More information

Current Transducer CTSR 1-P = 1A

Current Transducer CTSR 1-P = 1A Current Transducer CTSR 1-P I PRN = 1A For the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation between the primary (high power) and the secondary circuit (electronic circuit).

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation between the primary and the secondary circuit. Current Transducer CASR series I PN = 6, 5, 25, 5 A Ref: CASR 6-NP, CASR 5-NP, CASR 25-NP, CASR 5-NP For the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation between the primary

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer LF 2010-S I PN = 2000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated

More information

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Phanikumar.Ch, M.Tech Dept of Electrical and Electronics Engineering Bapatla Engineering College, Bapatla,

More information

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation Portable Description Features Measures all of the main electrical parameters of an electricity network Measurement in true root mean square Built-in energy meter With 4 voltage channels and 4 current channels

More information

M.8. Portable power analyzers and accessories CONTENTS. Page. Introduction 3 AR.5 AR5L. Power analyzers 4. Applications 4 Harmonics.

M.8. Portable power analyzers and accessories CONTENTS. Page. Introduction 3 AR.5 AR5L. Power analyzers 4. Applications 4 Harmonics. Portable system analyzer and accesories M8 M.8.01 GB CONTENTS Introduction 3 AR.5 AR5L Power analyzers 4 Applications 4 Harmonics 5 Disturbances 5 Flicker 6 Fast-Check - motor starting 6 Check-Meter -

More information

M.3. Electrical measurement and control. Electrical energy meters for partial consumption

M.3. Electrical measurement and control. Electrical energy meters for partial consumption M.3 Electrical measurement and control Electrical energy meters for partial consumption M.3 Electrical energy meters for partial consumption M.3 - Electrical energy meters for partial consumption Introduction

More information

POWER QUALITY ASSESSMENT AND MITIGATION AT WALYA-STEEL INDUSTRIES AND ETHIO-PLASTIC SHARE COMPANY

POWER QUALITY ASSESSMENT AND MITIGATION AT WALYA-STEEL INDUSTRIES AND ETHIO-PLASTIC SHARE COMPANY POWER QUALITY ASSESSMENT AND MITIGATION AT WALYA-STEEL INDUSTRIES AND ETHIO-PLASTIC SHARE COMPANY Mengesha Mamo and Adefris Merid School of Electrical and Computer Engineering Addis Ababa Institute of

More information

Voltage and Current Waveforms Enhancement using Harmonic Filters

Voltage and Current Waveforms Enhancement using Harmonic Filters Voltage and Current Waveforms Enhancement using Harmonic Filters Rajeb Ibsaim rabsaim@yahoo.com, Azzawia University, Libya Amer Daeri ibnjubair1@yahoo.co.uk Azzawia University, Libya Abstract The demand

More information

PS-3000-AVAS PS-5000-AVAS DC SOURCE FOR AUTOMOTIVE TESTS

PS-3000-AVAS PS-5000-AVAS DC SOURCE FOR AUTOMOTIVE TESTS PERFORMANCES High accuracy High stability Fast times of transition High inrush current Wide bandwidth Switching from Q1 to Q4 without transition Very low output impedance Ripple & noise superposition Dips

More information

SPECIFICATION. Online UPS 3000VA

SPECIFICATION. Online UPS 3000VA Page 1 / 7 DESCRIPTION Pure sine-wave output UPS on-line double conversion type. INPUT AC Mains voltage 230V ac 1 phase Mains voltage range 184...264V ac Mains frequency range 47...63Hz Power factor at

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

Energy Management Energy Analyzer Type EM210 MID

Energy Management Energy Analyzer Type EM210 MID Energy Management Energy Analyzer Type Multi-use housing: for both DIN-rail and panel mounting applications MID annex MI-003 (Measuring Instruments Directive) compliant Class B (kwh) according to EN50470-3

More information

DS400ID. Specification highlights Symbol Unit Min Typ Max. Features. Applications: Linearity error maximum 1.5 ppm. MPS for particles accelerators

DS400ID. Specification highlights Symbol Unit Min Typ Max. Features. Applications: Linearity error maximum 1.5 ppm. MPS for particles accelerators Ultra-stable, high precision (ppm class) fluxgate technology DS Series current transducer for non-intrusive, isolated DC and AC current measurement up to 600A Features Linearity error maximum 1.5 ppm Fluxgate,

More information

400,440Vac Vdc V, A, W, VA, var, Hz, V, Avg. A cos phi, sin phi and phi measurement kwh, kvarh (via Pulse Output)

400,440Vac Vdc V, A, W, VA, var, Hz, V, Avg. A cos phi, sin phi and phi measurement kwh, kvarh (via Pulse Output) MODEL EM4000ACF Multifunction Transducer for alternating voltage and current Power supply voltages: Suitable for DIN-rail mounting 85 240Vac 400,440Vac 24 65Vdc 100..330Vdc V, A, W, VA, var, Hz, V, Avg.

More information

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state.

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state. 1991 1.12 The operating state that distinguishes a silicon controlled rectifier (SCR) from a diode is (a) forward conduction state (b) forward blocking state (c) reverse conduction state (d) reverse blocking

More information

Introduction to Rectifiers and their Performance Parameters

Introduction to Rectifiers and their Performance Parameters Electrical Engineering Division Page 1 of 10 Rectification is the process of conversion of alternating input voltage to direct output voltage. Rectifier is a circuit that convert AC voltage to a DC voltage

More information

ZITARES CCD FX-20 25W SELV (isolated), adjustable functions and current, 1-channel, dimmable

ZITARES CCD FX-20 25W SELV (isolated), adjustable functions and current, 1-channel, dimmable Sample image ECG versions Model Order no. Output current 1) Output power CCD175-25FX-20/220-240/LI 10132980 100... 750 ma 2... 25 W 1) Adjustable by means of zitares360 software or resistor. Performance

More information

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 40 CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 3.1 INTRODUCTION The low power factor effects on transmission line, switchgear, transformers etc. It is observed that if the power

More information

High Performance Current Transducer IT 200-S ULTRASTAB = A. ε L

High Performance Current Transducer IT 200-S ULTRASTAB = A. ε L High Performance Current Transducer IT 200-S ULTRASTAB For the electronic measurement of currents: DC, AC, pulsed..., with galvanic isolation between the primary circuit and the secondary circuit. I PM

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer CKSR series N = 6, 5, 25, 5 A Ref: CKSR 6-NP, CKSR 5-NP, CKSR 25-NP, CKSR 5-NP For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary

More information

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet PowerLogic power-monitoring units PM700 series power meter Technical data sheet 2009 Functions and characteristics The PowerLogic PM700 series power meter offers all the measurement capabilities required

More information

SPECIFICATION Item no.: T60404-N4646-X400

SPECIFICATION Item no.: T60404-N4646-X400 Customer: Standard type Customers Part no.: Page 1 of 5 Description Closed loop (compensation) Current Sensor with magnetic field probe Printed circuit board mounting Casing and materials UL-listed Electrical

More information

Measurement and control. Digital instruments and measuring transducers

Measurement and control. Digital instruments and measuring transducers Measurement and control Digital instruments and measuring transducers M.2 - Digital instruments and measuring transducers Introduction...M2-3 Product selection table...m2-5 DC Series Digital indicator

More information

How adjustable speed drives affect power distribution

How adjustable speed drives affect power distribution How adjustable speed drives affect power distribution Application Note Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality. ASDs as victim loads Although ASDs are usually

More information

Analog Digital Multimeter with Insulation Resistance Measurement

Analog Digital Multimeter with Insulation Resistance Measurement RISH MIT 30 Product Features: RISH MIT 30 is Analog Digital Multimeter with insulation resistance measurement, which measures VAC, VDC, VAC+DC,Frequency, ma DC, ma AC+DC,Resistance, continuity, Diode,

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

TDA W MONO CLASS-D AMPLIFIER 18W OUTPUT POWER:

TDA W MONO CLASS-D AMPLIFIER 18W OUTPUT POWER: 18 MONO CLASS-D AMPLIFIER 18 OUTPUT POER: RL = 8Ω/4Ω; THD = 10% HIGH EFFICIENCY IDE SUPPLY VOLTAGE RANGE (UP TO ±25V) SPLIT SUPPLY OVERVOLTAGE PROTECTION ST-BY AND MUTE FEATURES SHORT CIRCUIT PROTECTION

More information

CUSTOMER S ACCEPTANCE SPECIFICATIONS

CUSTOMER S ACCEPTANCE SPECIFICATIONS LG FOR MESSRS : Uniservice Co. Ltd CUSTOMER S ACCEPTANCE SPECIFICATIONS MAGNETRON : 2M809 15GKH (Inverter 900W) CONTENTS DATE : Feb.20,2012 COVER 1 RECORD OF REVISION TEST SPECIFICATIONS CHARACTERISTIC

More information

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to

More information

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic

More information

Advantages There are many diverse advantages of a portable analyzer for the user. The most important is information.

Advantages There are many diverse advantages of a portable analyzer for the user. The most important is information. Portable s CIRCUTOR offers a wide range of portable analyzers designed to measure, display and/or record the most important parameters of an electrical network. With the analysis of the electrical parameters,

More information

79/26 Series III Multimeter

79/26 Series III Multimeter 79/26 Series III Multimeter Instruction Sheet W Read First: Safety Information Never use the meter if the meter or test leads look damaged. Be sure the test leads and switch are in the correct position

More information

Power Quality and Harmonic :Causes and Effects with Paper Mill Factory

Power Quality and Harmonic :Causes and Effects with Paper Mill Factory Power Quality and Harmonic :Causes and Effects with Paper Mill Factory Danaisak Tangsakha PEA Thailand danaisakpq@gmail.com Provincial Electricity Authority, Thailand 1 Topics Introduction Power Quality

More information

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar. Technical Report on Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by Dr. V. R. Kanetkar (February 2015) Shreem Electric Limited (Plot No. 43-46, L. K. Akiwate

More information

RAP Ripple Control Coupling for parallel injection of RC signals in Medium and High Voltage Networks

RAP Ripple Control Coupling for parallel injection of RC signals in Medium and High Voltage Networks RAP Ripple Control Coupling for parallel injection of RC signals in Medium and High Voltage Networks We reserve all rights to this document, and the subject-matter it deals with. Duplication, dissemination

More information

ZITARES NCD 2 nd Generation Non-SELV, constant current control gear, 1-channel, dimmable

ZITARES NCD 2 nd Generation Non-SELV, constant current control gear, 1-channel, dimmable Sample Image: Original product may differ! ECG versions Model Order no. Output currents 1) Output power NCD140-70FX-20/220-240/LI 10116488 120... 400 ma 5... 70 W NCD180-100FX-20/220-240/LI 10116492 350...

More information