MEMORANDUM. National Fire Protection Association

Size: px
Start display at page:

Download "MEMORANDUM. National Fire Protection Association"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: MEMORANDUM To: NEC Code-Making Panel 5 From: Kimberly Shea, Project Administrator Date: April 16, 2015 Subject: NEC First Draft TC FINAL Ballot Results (A2016) According to the final ballot results, all First Revisions received the necessary affirmative votes to pass ballot with the exception of FR As a result, FR 1240 has been redesignated as a Committee Input and is attached for your informaiton. 17 Members Eligible to Vote 0 Members Ballots Not Returned 13 Members voted Affirmative with Comment on one or more Revisions (Beckstrand, Brett Jr., Bowmer, Edwards, J. Harding, S. Harding, Mello, Mohla, O Meara, Palmieri, Phillips, Porter, Simmons) 11 Members voted Negative on one or more Revisions (Beckstrand, Brett Jr., Dobrowsky, J. Harding, S. Harding, Mohla, O Meara, Palmieri, Phillips, Simmons Sasso) 0 Abstentions on one or more Revisions The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each first revision. There are two criteria necessary for each first/second revision to pass ballot: (1) simple majority and (2) affirmative 2 / 3 vote. The mock examples below show how the calculations are determined. (1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes are required to pass ballot. (Sample calculation: 20 members eligible to vote 2 = = 11) (2) Example for Affirmative 2 / 3 : Assuming there are 20 vote eligible committee members and 1 member did not return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample calculation: 20 members eligble to vote 1 not returned 2 abstentions = 17 x 0.66 = = 12 ) As always please feel free to contact me if you have any questions.

2 First Revision No NFPA [ Section No (D) ] (D) Grounded Conductors of Different Systems. Where grounded conductors of different systems are installed in the same raceway, cable, box, auxiliary gutter, or other type of enclosure, each grounded conductor shall be identified by system. Identification that distinguishes each system grounded conductor shall be permitted by one of the following means: (1) One system grounded conductor shall have an outer covering conforming to 200.6(A) or (B). (2) The grounded conductor(s) of other systems shall have a different outer covering conforming to 200.6(A) or 200.6(B) or by an outer covering of white or gray with a readily distinguishable colored stripe other than green running along the insulation. (3) Other and different means of identification as allowed by 200.6(A) or (B) that will shall distinguish each system grounded conductor. The means of identification shall be documented in a manner that is readily available or shall be permanently posted where the conductors of different systems originate. Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jan 15 16:08:04 EST 2015 Committee Statement Committee Statement: Response Message: Deletion of the word as between the identification and allowed was done to comply with section of the NEC Style Manual Public Input No NFPA [Section No (D)] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 16 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Beckstrand, Gary A. Bowmer, Trevor N. Brett, Jr., Martin J. of 115 4/16/2015 9:59 AM

3 Dobrowsky, Paul Harding, Joseph Harding, G. Scott Helfrich, William J. Mello, Charles F. Mohla, Daleep C. O'Meara, Mike Palmieri, Charles J. Philips, Nathan Porter, Christine T. Sasso, Nick Simmons, Phil Steinman, Gregory J. Affirmative with Comment Edwards, Timothy Summaries of discrepancies. FR (A)(1) Two issues: First, the panel statement is not correctly stated. This section is for grounded systems, the panel statement is for the ungrounded section. Second the version of the standard referenced is the 2017 Edition. Question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Also note identical informational note and reference accepted as FR 1204 by the committee did not show up in TerraView. The panel statement in TerraView for FR (B)(1) which would be for ungrounded systems. FR (B)(1) Does not show up in TerraView. It is an identical informational note, applicable to ungrounded systems. Same issue with the date of the standard NFPA 780 FR (C)(1) The word Cable is not underlined it needs to be underlined. Note also misspelled word (ables) in panel statement, it should be cables FR (C)(2) The words or Cable are not underlined they need to be underlined of 115 4/16/2015 9:59 AM

4 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No ]

5 of 115 4/16/2015 9:59 AM Application of Other Articles.

6 of 115 4/16/2015 9:59 AM For other articles applying to particular cases of installation of conductors and equipment, grounding and bonding requirements are identified in Table that are in addition to, or modifications of, those of this article. Table Additional Grounding and Bonding Requirements Conductor/Equipment Article Section Agricultural buildings and Audio signal processing, amplification, and reproduction equipment Branch circuits 210.5, 210.6, Cablebus Cable trays Capacitors , Circuits and equipment operating at less than 50 volts 720 Communications circuits 800 Community antenna television and radio distribution systems Conductors for general wiring 310 Cranes and hoists 610 Electrically driven or controlled irrigation machines Electric signs and outline lighting 600 Electrolytic cells 668 Elevators, dumbwaiters, escalators, moving walks, wheelchair lifts, and stairway chairlifts , , , (C), , , , Fixed electric heating equipment for pipelines and vessels , Fixed outdoor electric deicing and snow-melting equipment Flexible cords and cables , Floating buildings 553.8, , Grounding-type receptacles, adapters, cord connectors, and attachment plugs Hazardous (classified) locations Health care facilities 517 Induction and dielectric heating equipment 665 Industrial machinery Information technology equipment Intrinsically safe systems Luminaires and lighting equipment Luminaires, lampholders, and lamps , , , (B) Marinas and boatyards Mobile homes and mobile home park 550 Motion picture and television studios and similar locations Motors, motor circuits, and controllers 430 Natural and artificially made bodies of water , (B) , , , Network Powered Broadband Communications Circuits , , Optical Fiber Cables

7 of 115 4/16/2015 9:59 AM Conductor/Equipment Article Section Outlet, device, pull, and junction boxes; conduit bodies; and fittings Over 600 volts, nominal, underground wiring methods 314.4, (C) Panelboards Pipe organs 650 Radio and television equipment 810 Receptacles and cord connectors Recreational vehicles and recreational vehicle parks 551 Services 230 Solar photovoltaic systems Swimming pools, fountains, and similar installations 680 Switchboards and panelboards , , , , (D) Switches Theaters, audience areas of motion picture and television studios, and similar locations Transformers and transformer vaults Use and identification of grounded conductors 200 X-ray equipment Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jan 15 16:15:58 EST 2015 Committee Statement Committee Statement: This FR corrects the omissions of and Articles 770 and 830. Response Message: Public Input No NFPA [Section No ] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 16 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Beckstrand, Gary A.

8 Bowmer, Trevor N. Brett, Jr., Martin J. Dobrowsky, Paul Harding, Joseph Harding, G. Scott Helfrich, William J. Mello, Charles F. Mohla, Daleep C. O'Meara, Mike Palmieri, Charles J. Philips, Nathan Porter, Christine T. Sasso, Nick Simmons, Phil Steinman, Gregory J. Affirmative with Comment Edwards, Timothy 2017 and 2019 are below FR (A)(6) Task group indication that the word provided was not struck out and replaced with the word if. The word is used in Exception 1, but was also not changed in the word summary document. Not sure what the submitter was looking for here. FR (A)(8) The prohibition against using swimming pool structures and grids was inserted in electrodes permitted (part A), should have been entered as (B)(3) instead. The panel also requested this be sent on to CMP 17 for comment FR The FR the committee acted on was FR1232, The text and underlining in TerraView is correct, as well as the panel statement. There is no mention of the resolved PI in response message. The following PIs may need to be added at the Response Message portion: Public Input No 436 NFPA [Section No ] Public Input No 3837 NFPA [Section No ] Pubic Input No 3708 NFPA [Section No ] FR (in TerraView) should have been noted as FR It is correct for section This does not include the work in FR 1234 that the panel accepted for Table (C)(1). NONE of the work on the Table shows up in TerraView. The panel re-ordered the notes to make it clear when they apply. FR At (A)(1) list item (4)additional wording is missing that should read: if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size. of 115 4/16/2015 9:59 AM

9 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No (A)(1) ] (1) Electrical System Grounding. Electrical systems that are grounded shall be connected to earth in a manner that will limit the voltage imposed by lightning, line surges, or unintentional contact with higher-voltage lines and that will stabilize the voltage to earth during normal operation. Informational Note No. 1: An important consideration for limiting the imposed voltage is the routing of bonding and grounding electrode conductors so that they are not any longer than necessary to complete the connection without disturbing the permanent parts of the installation and so that unnecessary bends and loops are avoided. Informational Note No. 2: See NFPA , Standard for the Installation of Lightning Protection Systems, for information on lightning protection system grounding. Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jan 15 16:18:48 EST 2015 Committee Statement Committee Statement: Response Message: The NEC is not a lightning protection document. Adding the reference to NFPA 780 will provide additional information for ungrounded systems. Public Input No NFPA [Section No (A)(1)] Public Input No NFPA [Section No (C)] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 4 Affirmative All 13 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Dobrowsky, Paul Helfrich, William J. Sasso, Nick Steinman, Gregory J. Affirmative with Comment

10 of 115 4/16/2015 9:59 AM Beckstrand, Gary A. The Panel Statement is incorrect for FR It should read. "The NEC is not a lightning protection document. Adding the reference to NFPA 780 will provide additional information for grounded systems." The addition of the reference to NFPA is inappropriate as the document is not in current cycle. The reference should be verified by the CMP in the Comment cycle. Bowmer, Trevor N. Item (1) - The panel statement for this FR is not correctly stated. This section is for grounded systems, whereas the panel statement is for the ungrounded section. Item (2)- The version of the standard referenced is the 2017 Edition. A question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Item (3) - FR-1204 addressing 250.4(B)(1) is missing from Terraview and this ballot. The FR-1204 accepted by the CMP5 has the same informational note, applicable to ungrounded systems. In addition, the same issue with the date of the referenceed standard NFPA 780 is present. Brett, Jr., Martin J (A)(1) Two issues: First, the panel statement is not correctly stated. This section is for grounded systems, the panel statement is for the ungrounded section. Second the version of the standard referenced is the 2017 Edition. Question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Also note identical informational note and reference accepted as FR 1204 by the committee did not show up in TerraView The panel statement in TerraView for 250.4(B)(1) which would be for ungrounded systems. Edwards, Timothy I could not find any record from Task Group three of any changes to (A)(2) but TerraView shows changes for bonding of metal water piping in building of multiple occupancy. What we had The bonding jumper shall be sized in accordance with Table based on the rating of the overcurrent device supplying the occupancy. has been replaced with The equipment bonding jumper shall be sized in accordance with Table (D), based on the rating of the overcurrent protective device for the circuit supplying the occupancy. At 250/104(A)(3) there is missing existing text that we struck out At (A)(3)(c) additional text has been added if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size At the paragraph following 250/104(A)(3)(c) we had Table referenced, it now shows as Table (C)(1) which is correct, not sure we voted on that however. Section (B) has been changed to reference sizing bonding conductors for other piping in accordance with Table (C)(1) instead and in addition to Table which is kept in this section only for sizing equipment grounding conductors (which makes NO sense) (C) Structural Metal has changes in the main paragraph not shown in our summaries. Harding, G. Scott 250.4(A)(1)The panel statement is not correctly stated. This section is for grounded systems, the panel statement is for the ungrounded section. Second the version of the standard referenced is the 2017 Edition. Question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Also note identical informational note and reference accepted as FR 1204 by the committee did not show up in TerraView. The panel statement in TerraView for FR (B)(1) which would be for ungrounded systems. Harding, Joseph FR (A)(1) Two issues: First, the panel statement is not correctly stated. This section is for grounded systems, the panel statement is for the ungrounded section. Second the version of the standard referenced is the 2017 Edition. Question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Also note identical informational note and reference accepted as FR 1204 by the committee did not show up in TerraView The panel statement in TerraView for 250.4(B)(1) which would be for ungrounded systems. Mello, Charles F. The Informational Note No.1 was noted that the "No. 1" was not underlined indicating the change in text since Informational Note No. 2 was added as a result of the First Revision change. The panel statement should be corrected as follows: "The NEC is not a lightning protection Document. Adding the reference to NFPA 780 will provide additional information for grounded systems." It is also noted that FR 1204 is not on the ballot to have the same informational note added to 250.4(B)(1) with the same panel statement except for the reference to "grounded" systems would be for "ungrounded" systems. Mohla, Daleep C. First, the panel statement is not correctly stated. This section is for grounded systems, the panel statement is for the ungrounded section. Second the version of the standard referenced is the 2017 Edition. Question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Also note identical informational note and reference accepted as FR 1204 by the committee did not show up in TerraView The panel statement in TerraView for 250.4(B)(1) which would be for ungrounded systems. FR (B)(1) Does not show up in TerraView. It is an identical informational note, applicable to ungrounded

11 0 of 115 4/16/2015 9:59 AM systems. Same issue with the date of the standard NFPA 780 O'Meara, Mike Two issues: First, the panel statement is not correctly stated. This section is for grounded systems, the panel statement is for the ungrounded section. Second the version of the standard referenced is the 2017 Edition. Question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Also note identical informational note and reference accepted as FR 1204 by the committee did not show up in TerraView The panel statement in TerraView for 250.4(B)(1) which would be for ungrounded systems. FR (B)(1) Does not show up in TerraView. It is an identical informational note, applicable to ungrounded systems. Same issue with the date of the standard NFPA 780 Palmieri, Charles J (A)(1) Two issues: First, the panel statement is not correctly stated. This section is for grounded systems, the panel statement is for the ungrounded section. Second the version of the standard referenced is the 2017 Edition. Question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Also note identical informational note and reference accepted as FR 1204 by the committee did not show up in Terra View The panel statement in Terra View for 250.4(B)(1) which would be for ungrounded systems. Philips, Nathan FR (A)(1) Two issues: First, the panel statement is not correctly stated. This section is for grounded systems, the panel statement is for the ungrounded section. Second the version of the standard referenced is the 2017 Edition. Question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Also note identical informational note and reference accepted as FR 1204 by the committee did not show up in TerraView. The panel statement in TerraView for FR 1203 should be used for FR (B)(1) which would be for ungrounded systems. Porter, Christine T. FR (A)(1) Two issues: First, the panel statement is not correctly stated. This section is for grounded systems, the panel statement is for the ungrounded section. Second the version of the standard referenced is the 2017 Edition. Question arises as to the validity of using that date. It will be published prior to the publication of the NEC, but is not yet published. Also note identical informational note and reference accepted as FR 1204 by the committee did not show up in TerraView The panel statement in TerraView for 250.4(B)(1) which would be for ungrounded systems. FR (B)(1) Does not show up in TerraView. It is an identical informational note, applicable to ungrounded systems. Same issue with the date of the standard NFPA 780 Simmons, Phil FR-1204 is missing from the NFPA ballot. It adds an Informational Note to 250.4(B)(1). Please insert it as it was accepted by CMP-5 at its meeting.

12 of 2 4/15/ :02 AM First Revision No NFPA [ Section No ] Use of Strike Termination Devices. Conductors and driven pipes, rods, or plate electrodes used for grounding strike termination devices shall not be used in lieu of the grounding electrodes required by for grounding wiring systems and equipment. This provision shall not prohibit the required bonding together of grounding electrodes of different systems. Informational Note No. 1: See for spacing from strike termination devices. lightning protection system components. See (D), (J), and (D) for bonding of electrodes. Informational Note No. 2: Bonding together of all separate grounding electrodes will limit potential voltage differences between them and between their associated wiring systems. Submitter Information Verification Submitter Full Name: CMP 5 Organization: NATIONAL FIRE PROTECTION ASSOC Street Address: City: State: Zip: Submittal Date: Fri Jan 23 11:16:21 EST 2015 Committee Statement Committee Statement: The change is made for consistency with NFPA 780. Response Message: Public Input No NFPA [Section No ] Public Input No NFPA [Section No ] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 15 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Beckstrand, Gary A. Bowmer, Trevor N. Brett, Jr., Martin J. Dobrowsky, Paul Harding, Joseph Harding, G. Scott Helfrich, William J. Mello, Charles F. Mohla, Daleep C. O'Meara, Mike

13 Philips, Nathan Porter, Christine T. Sasso, Nick Simmons, Phil Steinman, Gregory J. Affirmative with Comment Edwards, Timothy See attached errata Palmieri, Charles J (B)(1) Does not show up in Terra View. It is an identical informational note, applicable to ungrounded systems. Same issue with the date of the standard NFPA 780 of 2 4/15/ :02 AM

14 1 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No (B) ] (B) Alterations to Stop Objectionable Current. If the use of multiple grounding connections results in objectionable current, one or more of the following alterations shall be permitted to be made, provided that the and the requirements of 250.4(A)(5) or (B)(4) are met:, one or more of the following alterations shall be permitted: (1) Discontinue one or more but not all of such grounding connections. (2) Change the locations of the grounding connections. (3) Interrupt the continuity of the conductor or conductive path causing the objectionable current. (4) Take other suitable remedial and approved action. Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jan 15 16:33:25 EST 2015 Committee Statement Committee Statement: The change is made to comply with the NEC Style Manual and improve clarity. Response Message: Public Input No NFPA [Section No (B)] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 15 Affirmative All 1 Affirmative with Comments 1 Negative with Comments 0 Abstention Affirmative All Beckstrand, Gary A. Bowmer, Trevor N. Brett, Jr., Martin J. Dobrowsky, Paul Harding, Joseph Harding, G. Scott Helfrich, William J. Mello, Charles F.

15 Mohla, Daleep C. O'Meara, Mike Palmieri, Charles J. Philips, Nathan Porter, Christine T. Simmons, Phil Steinman, Gregory J. Affirmative with Comment Edwards, Timothy FR (B) There seems to be a sense that the words should be shall be at least in the same proportion and not shall be in the same proportion. This is directly from Chuck and is clear enough that I did not reformat CMP-5 Task Group 4 Review The following are noted from the review of the final approved template work at the First Revision meeting and the final Terra View document markup. 1) FR 1217 for section (A)(4) good 2) FR 1219 for section (A)(4), (5), (6) a) (4) - Missed the word system between electrode and shall b) (4) - In the exception, did not show strike out of No. 2 to (1) and (2) that is from 2014 Code text. c) (4) - The text is correct as passed by the panel but the legislative text is not correct in what was deleted and what was added to be clear on the exact changes. d) (5) The additional words or as permitted in (C)(1) and (2) are not showing in Terra View. e) (6) The water pipe got added but not as the panel did and the whole aspect of the metal frame of the building got deleted where the panel s action has both inclusive. Terra reads as The metal frame of the building or structure A metal water pipe that complies with (C)(2) (C)(2)250.52(A)(2) or is connected to the grounding electrode system by a conductor that shall not be smaller than 3/0 AWG copper or 250 kcmil aluminum. Negative with Comment Sasso, Nick The panel is using permissive language, "one or more of the following alterations shall be permitted..." If there is objectionable current, then one of the following (1, 2, 3, or 4) NEEDS to happen in order to abate the objectionable current. In reality, the new language gives the inspector no authority to order the correction as it is merely permissive language, see 90.5(B). This should be rewritten with mandatory language, in order to facilitate the Enforcer's corrections. 2 of 115 4/16/2015 9:59 AM

16 3 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No (A) ] (A) General. The following ac systems of 50 volts to 1000 volts shall be permitted to be grounded but shall not be required to be grounded: (1) Electrical systems used exclusively to supply industrial electric furnaces for melting, refining, tempering, and the like (2) Separately derived systems used exclusively for rectifiers that supply only adjustable-speed industrial drives (3) Separately derived systems supplied by transformers that have a primary voltage rating of 1000 volts or less, provided that if all the following conditions are met: a. The system is used exclusively for control circuits. b. The conditions of maintenance and supervision ensure that only qualified persons service the installation. c. Continuity of control power is required. (4) Other systems that are not required to be grounded in accordance with the requirements of (B) Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jan 16 11:16:18 EST 2015 Committee Statement Committee Statement: The change is made to improve the wording in this section but leave the third level subdivisions as a, b and c. Response Message: Public Input No NFPA [Section No (A)] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 16 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All

17 Beckstrand, Gary A. Bowmer, Trevor N. Brett, Jr., Martin J. Dobrowsky, Paul Harding, Joseph Harding, G. Scott Helfrich, William J. Mello, Charles F. Mohla, Daleep C. O'Meara, Mike Palmieri, Charles J. Philips, Nathan Porter, Christine T. Sasso, Nick Simmons, Phil Steinman, Gregory J. Affirmative with Comment Edwards, Timothy This should read as follows with legislative text: The A metal water pipe that complies with (A)(2) (C)(1) or the metal structural frame of a building or structure that complies with (A)(2)250.68(C)(2) or connected to the grounding electrode system by a conductor that shall not be smaller than 3/0 AWG copper or 250 kcmil aluminum. f) (6)(c)(2) - The terms thick and wide were omitted from the millimeter dimensions. The term thick was omitted after 1/4 in. in the parenthesis s part. The word also was omitted between shall and comply 3) FR 1220 for section (B)(3) This was proposed for (A)(8) and the panel action moved with revised text to (B). What is in Terra is: (A)(8) Other Local Metal Underground Systems or Structures. Other local metal underground systems or structures such s piping systems, underground tanks, and underground metal well casings that are not bonded to a metal water pipe. The structures and structural reinforcing steel described at (B)(1) and (B)(2) shall not be considered as a grounding electrode described by this section. The correct text should be in section (B) as new list item (3) as follows: (3) The structures and structural reinforcing steel described in (B)(1 and (B)(2). 4) FR 1221 for section (F) is good 5) FR 1222 for section (A) a) The text or where subject to corrosive conditions is struck out and the panel rejected that proposed change and it should not be struck out. 6) Fr 1223 for section (B) (1) a) The beginning should show the A 4 as stuck out and that is missing. b) The text shall be protected if exposed to physical damage. Should have been struck out and was not, sentence now does not make sense are revised. c) Remainder of text works but legislative text as revised by the panel is different i. (2) 4 of 115 4/16/2015 9:59 AM

18 5 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No ] Circuits Not to Be Grounded. The following circuits shall not be grounded: (1) Circuits for electric cranes operating over combustible fibers in Class III locations, as provided in (2) Circuits in health care facilities as provided in a nd (3) Circuits for equipment within electrolytic cell working zone as provided in Article 668 (4) Secondary circuits of lighting systems as provided in 411.6(A) (5) Secondary circuits of lighting systems as provided in (A)(2) (6) Class 2 load side circuits for low-voltage suspended ceiling power distribution systems as provided in (B) Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jan 16 11:21:15 EST 2015 Committee Statement Committee Statement: The change is made to align with Response Message: Public Input No NFPA [Section No ] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 15 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Beckstrand, Gary A. Bowmer, Trevor N. Brett, Jr., Martin J. Dobrowsky, Paul Harding, Joseph Harding, G. Scott

19 6 of 115 4/16/2015 9:59 AM Helfrich, William J. Mohla, Daleep C. O'Meara, Mike Palmieri, Charles J. Philips, Nathan Porter, Christine T. Sasso, Nick Simmons, Phil Steinman, Gregory J. Affirmative with Comment Edwards, Timothy d) Missed the underlines for the parentheses marks for (RMC) e) The added requirement for PVC to be the XW type was missed - should read as rigid polyvinyl chloride conduit (PVC), XW-type f) Missed the added requirement for RTRC to be XW type. Should read reinforced thermosetting resin conduit (RTRC-XW) g) Missed the underline for the parentheses marks for (EMT) i. (3) h) The RMC had the parentheses marks deleted but not struck in Terra i) The RTRC conduit was to be the XW type and should show as RTRC-XW j) The parentheses marks for the EMT were to be deleted but were missed. i. (4) k) There is an extra the added in to the text between with and earth. 7. FR 1224 fir section (D) good 8. FR 1225 for section (E)(1) good 9. FR 1226 for section (F) good 10. FR 1227 for section (A) a. Where was to be changed to If b. After the word conductor the words or bonding jumper should have been added as new text. (B) c. Where was to be changed to If d. After the word conductor the words or bonding jumper should have been added as new text. e. The comma after (A)((3) should be shown as deleted (C) f. Where was to be changed to If g. After the word conductor the words or bonding jumper should have been added as new text. h. The comma after (A)((3) should be shown as deleted 11. FR 1228 for section )C) a) The words shall be were incorrectly inserted between piping and located. This is to be statement for where a connection is made, as written the water pipe is now located within five feet of the entry to the building. 12. FR 1229 for section (5) good 13. FR 1230 for section good 14. FR 1240 Mello, Charles F. The text shown is incorrect in the order of words. The text should read: (6) Class 2 load side circuits for suspended ceiling low-voltage power grid distribution systems as provided in (B)" This is the correct text as stated in (B) which the panel used for consistency.

20 7 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No (C) [Excluding any Sub-Sections] ] Where an ac system operating at volts or less is grounded at any point, the grounded conductor(s) shall be routed with the ungrounded conductors to each service disconnecting means and shall be connected to each disconnecting means grounded conductor(s) terminal or bus. A main bonding jumper shall connect the grounded conductor(s) to each service disconnecting means enclosure. The grounded conductor(s) shall be installed in accordance with (C)(1) through (C)(4). Exception: Where two or more service disconnecting means are located in a single assembly listed for use as service equipment, it shall be permitted to connect the grounded conductor(s) to the assembly common grounded conductor(s) terminal or bus. The assembly shall include a main bonding jumper for connecting the grounded conductor(s) to the assembly enclosure. Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jan 16 14:31:39 EST 2015 Committee Statement Committee Statement: This revision is necessary for up to 2000V to avoid a gap in voltage. The change from 1000 to 2000 Volts in this section does not affect the requirements for grounding and bonding and will allow future equipment expansion into this voltage range, such as PV and wind systems. Response Message: Public Input No NFPA [Section No (C) [Excluding any Sub-Sections]] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 12 Affirmative All 2 Affirmative with Comments 3 Negative with Comments 0 Abstention Affirmative All Beckstrand, Gary A. Brett, Jr., Martin J. Harding, Joseph Harding, G. Scott Helfrich, William J. Mello, Charles F.

21 Mohla, Daleep C. Palmieri, Charles J. Philips, Nathan Porter, Christine T. Simmons, Phil Steinman, Gregory J. Affirmative with Comment Bowmer, Trevor N. Increasing these voltage levels does not change the grounding requirements of Article 250. However, making these changes in Article 250 without concomitant and correlating changes in other parts of the code will lead to confusion and inconsistency. Edwards, Timothy See attached errata Negative with Comment Dobrowsky, Paul The voltage level should not be increased to 2000 to be consistent with other code making panels actions to have the threshold be There is no gap in voltage levels in Article 250, it is up to 1000 volts and over 1000 volts. O'Meara, Mike The voltage level should remain at 1000 volts. Making this change may allow additional items to comply with low voltage requirements without substantiation and may create safety issues. Although the change in voltage does not directly impact the grounding requirements in Article 250, it creates inconsistency with other Articles throughout the code, as other CMP s did not accept these Public Inputs Sasso, Nick There is an undercurrent on this panel to replace 1000 volts with "2000 volts." In my opinion, this is arbitrary and being attempted to serve some other purpose. Article 490 has a definition of high voltage (more than 1000 volts) therefore it is sensible and practical for Article 250 to remain consistent with the NEC definition in Article 490. The NEC document needs to be consistent throughout. It is also important to remember that other regulations, such as OSHA, use 1000 volts when the term "high voltage" is referenced. Furthermore, OSHA cooperative programs state that for "OVER 1000 VOLTS" electrical burn wounds possess special clinical characteristics. In addition, for "OVER 1000 VOLTS" there is a risk of wounds which can lead to amputation. The distinction is "over 1000" not "2000 volts." 8 of 115 4/16/2015 9:59 AM

22 9 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No (C)(1) ] (1) Sizing for a Single Raceway or Cable. The grounded conductor shall not be smaller than specified in Table (C)(1). Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jan 16 11:45:54 EST 2015 Committee Statement Committee Statement: The grounded conductor size needs to be consistent for raceways and ables. Response Message: Public Input No NFPA [Section No (C)(1)] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 6 Affirmative All 11 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Dobrowsky, Paul Helfrich, William J. Mello, Charles F. Sasso, Nick Simmons, Phil Steinman, Gregory J. Affirmative with Comment Beckstrand, Gary A. The Panel Statement should be shown as, "The grounded conductor size needs to be consistent for raceways and cables." Bowmer, Trevor N. The word "Cable" is not underlined in Terraview and it needs to be underlined to show it as newly added. Note also there is also a misspelled word (ables) in panel statement, it should be cables Brett, Jr., Martin J (C)(1) The words "or Cable" are not underlined, they need to be underlined. Note also misspelled word

23 0 of 115 4/16/2015 9:59 AM "ables" in panel statement, it should be cables Edwards, Timothy See attached errata Harding, G. Scott (C)(1) The word Cable is not underlined it needs to be underlined. Note also misspelled word (ables) in panel statement, it should be cables Harding, Joseph FR (C)(1) The word Cable is not underlined it needs to be underlined. Note also misspelled word (ables) in panel statement, it should be cables Mohla, Daleep C. The word Cable is not underlined it needs to be underlined. Note also misspelled word (ables) in panel statement, it should be cables O'Meara, Mike The word Cable is not underlined it needs to be underlined. Note also misspelled word (ables) in panel statement, it should be cables Palmieri, Charles J. The legislative underline of the new term Cables is not indicated in the title (C)(1) The word Cable is not underlined it needs to be underlined. Note also misspelled word (ables) in panel statement, it should be cables Philips, Nathan FR (C)(1) The word Cable is not underlined it needs to be underlined. Note also misspelled word (ables) in panel statement, it should be cables Porter, Christine T. FR (C)(1) The word Cable is not underlined it needs to be underlined. Note also misspelled word (ables) in panel statement, it should be cables

24 1 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No (C)(2) ] (2) Parallel Conductors in Two or More Raceways or Cables. If the ungrounded service-entrance conductors are installed in parallel in two or more raceways or cables, the grounded conductor shall also be installed in parallel. The size of the grounded conductor in each raceway or cable shall be based on the total circular mil area of the parallel ungrounded conductors in the raceway or cable, as indicated in (C)(1), but not smaller than 1/0 AWG. Informational Note: See (H) for grounded conductors connected in parallel. Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jan 16 11:48:17 EST 2015 Committee Statement Committee Statement: The grounded conductor size needs to be consistent for raceways and cables. Response Message: Public Input No NFPA [Section No (C)(2)] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 7 Affirmative All 10 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Beckstrand, Gary A. Dobrowsky, Paul Helfrich, William J. Mello, Charles F. Sasso, Nick Simmons, Phil Steinman, Gregory J. Affirmative with Comment Bowmer, Trevor N. The word "or Cable is not underlined in Terraview and it needs to be underlined to show it as newly added. Brett, Jr., Martin J.

25 250.24(C)(2) The words or Cable are not underlined in the title, they need to be underlined Edwards, Timothy See attached errata Harding, G. Scott (C)(2) The words or Cable are not underlined they need to be underlined Harding, Joseph FR (C)(2) The words or Cable are not underlined they need to be underlined Mohla, Daleep C. The words or Cable are not underlined they need to be underlined O'Meara, Mike The words or Cable are not underlined they need to be underlined Palmieri, Charles J. The legislative underline of the new term Cables is not indicated in the title (C)(2) The words or Cable are not underlined they need to be underlined Philips, Nathan The words or Cable are need to be underlined Porter, Christine T. FR (C)(2) The words or Cable are not underlined they need to be underlined 2 of 115 4/16/2015 9:59 AM

26 3 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No (A)(1) ] (1) System Bonding Jumper. An unspliced system bonding jumper shall comply with (A) through (D). This connection shall be made at any single point on the separately derived system from the source to the first system disconnecting means or overcurrent device, or it shall be made at the source of a separately derived system that has no disconnecting means or overcurrent devices, in accordance with (A)(1)(a) or (b). The system bonding jumper shall remain within the enclosure where it originates. If the source is located outside the building or structure supplied, a system bonding jumper shall be installed at the grounding electrode connection in compliance with (C). Exception No. 1: For systems installed in accordance with 450.6, a single system bonding jumper connection to the tie point of the grounded circuit conductors from each power source shall be permitted. Exception No. 2: If a building or structure is supplied by a feeder from an outdoor transformer separately derived system, a system bonding jumper at both the source and the first disconnecting means shall be permitted if doing so does not establish a parallel path for the grounded conductor. If a grounded conductor is used in this manner, it shall not be smaller than the size specified for the system bonding jumper but shall not be required to be larger than the ungrounded conductor(s). For the purposes of this exception, connection through the earth shall not be considered as providing a parallel path. Exception No. 3: The size of the system bonding jumper for a system that supplies a Class 1, Class 2, or Class 3 circuit, and is derived from a transformer rated not more than 1000 volt-amperes, shall not be smaller than the derived ungrounded conductors and shall not be smaller than 14 AWG copper or 12 AWG aluminum. (a) (b) Installed at the Source. The system bonding jumper shall connect the grounded conductor to the supply-side bonding jumper and the normally non current-carrying metal enclosure. Installed at the First Disconnecting Means. The system bonding jumper shall connect the grounded conductor to the supply-side bonding jumper, the disconnecting means enclosure, and the equipment grounding conductor(s). Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jan 16 12:29:04 EST 2015 Committee Statement Committee Statement: Transformers are not the only type of separately derived system Response Message: Public Input No NFPA [Section No (A)(1)] Ballot Results This item has passed ballot 17 Eligible Voters 0 Not Returned 16 Affirmative All

27 4 of 115 4/16/2015 9:59 AM 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Beckstrand, Gary A. Bowmer, Trevor N. Brett, Jr., Martin J. Dobrowsky, Paul Harding, Joseph Harding, G. Scott Helfrich, William J. Mello, Charles F. Mohla, Daleep C. O'Meara, Mike Palmieri, Charles J. Philips, Nathan Porter, Christine T. Sasso, Nick Simmons, Phil Steinman, Gregory J. Affirmative with Comment Edwards, Timothy See attached errata

28 5 of 115 4/16/2015 9:59 AM First Revision No NFPA [ Section No (A)(4) ] (4) Grounding Electrode. The building or structure grounding electrode shall be used as the grounding electrode for the separately derived system. If located outdoors, the grounding electrode shall be in accordance with (C). as near as practicable to, and preferably in the same area as, the grounding electrode conductor connection to the system. The grounding electrode shall be the nearest of one of the following: (0) Metal water pipe grounding electrode as specified in (A)(1) (0) Structural metal grounding electrode as specified in (A)(2) Exception No. 1: Any of the other electrodes identified in (A) shall be used if the electrodes specified by (A)(4) are not available. Exception: to (1) and (2): If a separately derived system originates in listed equipment suitable equipment for use as service equipment, the grounding electrode used for the service or feeder equipment shall be permitted as the grounding electrode for the separately derived system. that is listed and labeled as suitable for use as service equipment, the grounding electrode used for the service or feeder equipment shall be permitted to be used as the grounding electrode for the separately derived system. Informational Note No. 1: See (D) for bonding requirements for interior metal water piping in the area served by separately derived systems. Informational Note No. 2: See and for requirements for bonding all electrodes together if located at the same building or structure. Submitter Information Verification Submitter Full Name: CMP 5 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jan 16 13:31:02 EST 2015 Committee Statement Committee Statement: These revisions better describe a grounding electrode and include the conductors that are suitable to extend the grounding electrode connection. The revisions to this section recognize the water pipe and the structural metal frame as covered in (C) that are being used are not grounding electrodes but rather are conductors extending the grounding electrode connection. The revised text allowed exception No. 1 to be deleted as those options are covered by the referenced sections. Editorial changes were made to (A)(4), former Exception No. 2 to make it technically correct. Response Message: Ballot Results This item has passed ballot

29 17 Eligible Voters 0 Not Returned 6 Affirmative All 11 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Beckstrand, Gary A. Dobrowsky, Paul Helfrich, William J. Sasso, Nick Simmons, Phil Steinman, Gregory J. Affirmative with Comment Bowmer, Trevor N. FR-1219 is missing several items accepted during the CMP 5 meeting. In the revised Terraview (A)(4), the text is correct as passed by the panel but the legislative text is not correct in what was deleted and what was added to be clear on the exact changes. Item #(1) The word system needs to added between "electrode" and "shall" Item # (2) In the exception, Terraview did not show the strike out of No. 2 to (1) and (2) that is from 2014 Code text. Brett, Jr., Martin J. FR 1219 for section (A)(4), (5), (6) ****************************** 25030(A)(4) Missed the word system between electrode and shall In the exception, did not show strike out of No. 2 to (1) and (2) that is from 2014 Code text. The text is correct as passed by the panel but the legislative text is not correct in what was deleted and what was added to be clear on the exact changes. ******************************************* (A(5) The additional words or as permitted in (C)(1) and (2) are not showing in Terra View (A)(6) The water pipe got added but not as the panel did and the whole aspect of the metal frame of the building got deleted where the panel s action has both inclusive. Terra reads as The metal frame of the building or structure A metal water pipe that complies with (C)(2) (C)(2)250.52(A)(2) or is connected to the grounding electrode system by a conductor that shall not be smaller than 3/0 AWG copper or 250 kcmil aluminum. This should read as follows with legislative text: The A metal water pipe that complies with (A)(2) (C)(1) or the metal structural frame of a building or structure that complies with (A)(2)250.68(C)(2) or connected to the grounding electrode system by a conductor that shall not be smaller than 3/0 AWG copper or 250 kcmil aluminum. ****************************************** (A)(6) c)(2) - The terms thick and wide were omitted from the millimeter dimensions. The term thick was omitted after 1/4 in. in the parenthesis s part. The word also was omitted between shall and comply Edwards, Timothy See attached errata Harding, G. Scott (4) - Missed the word system between electrode and shall (4) - In the exception, did not show strike out of No. 2 to (1) and (2) that is from 2014 Code text. (4) - The text is correct as passed by the panel but the legislative text is not correct in what was deleted and what was added to be clear on the exact changes. (5) The additional words or as permitted in (C)(1) and (2) are not showing in Terra View. (6) The water pipe got added but not as the panel did and the whole aspect of the metal frame of the building got deleted where the panel s action has both inclusive. Terra reads as A metal water pipe that complies with (C)(2) or is connected to the grounding electrode system by a conductor that shall not be smaller than 3/0 AWG copper or 250 kcmil aluminum. This should read as follows: The metal water pipe that complies with (C)(1) or the metal structural frame of a building or structure that complies with (C)(2) or connected to the grounding electrode system by a conductor not smaller than 3/0 AWG copper or 250 kcmil aluminum. (6)(c)(2) - The terms thick and wide were omitted from the millimeter dimensions. The term thick was omitted after 1/4 in. in the parenthesis s part. The word also was omitted between shall and comply Harding, Joseph FR 1219 for section (A)(4), (5), (6) a) (4) - Missed the word system between electrode and shall b) (4) - In the exception, did not show strike out of No. 2 to (1) and (2) that is from 2014 Code text. c) (4) - The text is 6 of 115 4/16/2015 9:59 AM

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 16 FROM:

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions conduit? 9/8/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Can branch circuits of different services be installed in the same Yes, see 300.3(C)(1) for conductors of different systems

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5 Applied Grounding and Bonding Paul Dobrowsky Member NEC Panel 5 1 Introduction This presentation is a representative sample from the following Chapters of Applied Grounding and Bonding. Chapter 1, Introduction

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

Article 250 Grounding & Bonding

Article 250 Grounding & Bonding Article 250 Grounding & Bonding AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Dr. Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER NOTE: This course is APPROVED for continuing education

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Lightning Protection

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 200-215.3 CHANGES FROM 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 200 Use and Identification of Grounded Conductors 200.2 General Grounded Conductors

More information

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 13 From: Kimberly Shea, Project Administrator

More information

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING 1 1 1 1 1 NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING NORTH CAROLINA BUILDING CODE COUNCIL Notice of Rule-making Proceedings is hereby given by NC Building Code Council in accordance with G.S.

More information

RADIO AND TELEVISION SATELLITE EQUIPMENT

RADIO AND TELEVISION SATELLITE EQUIPMENT ARTICLE 810 RADIO AND TELEVISION SATELLITE EQUIPMENT Introduction to Article 810 Radio and Television Satellite Equipment This article covers transmitter and receiver (antenna) equipment and the wiring

More information

1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights

1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights 1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights These 1 Exam Prep Tabs are based on NFPA 70: National Electrical Code, 2011. Each 1 Exam Prep Tabs sheet has five rows of Tabs. Start

More information

M E M O R A N D U M. NFPA Technical Committee on Electrical Equipment of Industrial Machinery

M E M O R A N D U M. NFPA Technical Committee on Electrical Equipment of Industrial Machinery National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Electrical Equipment

More information

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition Jake Leahy s Electrical Code Connection A look at Grounding and Bonding of Electrical Services Article 250 2014 Florida Building Code 5 th Edition Wiring Integrity. Completed wiring installations shall

More information

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33 Part VIII Electrical CHAPTER 33 GENERAL REQUIREMENTS < SECTION E3301 GENERAL E3301.1 Scope. The installation of electrical systems, equipment and components indoors and outdoors that are within the scope

More information

CHAPTER 2 Wiring and Protection. Article 200 Use and Identification of Grounded Conductors

CHAPTER 2 Wiring and Protection. Article 200 Use and Identification of Grounded Conductors ARTICLE 200 USE AND IDENTIFICATION OF GROUNDED CONDUCTORS 70 35 CHAPTER 2 Wiring and Protection Article 200 Use and Identification of Grounded Conductors 200-1. Scope. This article provides requirements

More information

Continued from Part 1 Rules 1 25.

Continued from Part 1 Rules 1 25. Continued from Part 1 Rules 1 25. 26 225.32 Disconnect Location The disconnecting means for a building or structure must be installed at a readily accessible location, either outside the building or structure

More information

Journeyman's Practice Exam

Journeyman's Practice Exam Journeyman's Practice Exam [Time limit 4.0 hrs.] (The test is open book. I've started at the front of the Code Book and worked toward the back for instructional purposes. The real test will not be in order

More information

Grounding and Bonding of Service Equipment

Grounding and Bonding of Service Equipment Grounding and Bonding of Service Equipment 1. Grounding means: attached to an earth ground. 2. Bonding means: physically connected to insure electrical continuity. NEC 250.4 1. Grounding: Electrical Systems

More information

NEC P14 First Draft Ballot (A2016)

NEC P14 First Draft Ballot (A2016) NEC P14 First Draft Ballot (A2016) FR 3910, Definition: Dusttight., See FR 3910 Affirmative 12 Affirmative with Comment 2 None Donald W. Ankele At the end of informational note 1, add the phrase :"...where

More information

SUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016)

SUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: NEC Code-Making Panel 18 FROM: Kimberly Shea, Administrator, Technical

More information

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4 SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: 16.10 Document Number: KUCSH0039 Rev: 4 16.10.1 INTRODUCTION 16.10.1.1 The intent of this standard is to ensure that continuity

More information

FTTH ENGINEERING AND INSTALLATION INTRODUCTION

FTTH ENGINEERING AND INSTALLATION INTRODUCTION 1 FTTH ENGINEERING AND INSTALLATION INTRODUCTION GROUNDING FTTH SYSTEMS AT THE HOME. By Dean Mischke, P.E., V.P. Grounding and bonding. Why are we worried about such an old school concept in the modern

More information

2014 NEC Changes Part 1

2014 NEC Changes Part 1 www.garyklinka.com Page 1 of 8 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Electrical Wiring: Commercial, Seventh Canadian Edition

Electrical Wiring: Commercial, Seventh Canadian Edition Electrical Wiring Commercial Canadian 7th Edition Mullin SOLUTIONS MANUAL Full download at: https://testbankreal.com/download/electrical-wiring-commercialcanadian-7th-edition-mullin-solutions-manual/ Unit

More information

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Introduction The topic of system grounding is extremely important, as it affects the susceptibility of the system to voltage

More information

M E M O R A N D U M. NFPA 101A First Draft Correlating Committee FINAL Ballot Results (A2018)

M E M O R A N D U M. NFPA 101A First Draft Correlating Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Correlating on Safety to Life Kelly Carey,

More information

Article 225: Outside Branch Circuits And Feeders

Article 225: Outside Branch Circuits And Feeders Part C: Code Book Questions Article 225: Outside Branch Circuits And Feeders 1.! Open (individual) aerial overhead conductors shall be insulated or covered when within! feet of a building.! (a) 10! (c)

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Gas Hazards Lawrence

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 17 FROM: Kimberly Shea DATE:

More information

Article 700: Emergency Systems. 2.! Audible and visual signal devices shall be provided, where practicable to indicate.

Article 700: Emergency Systems. 2.! Audible and visual signal devices shall be provided, where practicable to indicate. Part N: Code Book Questions Article 700: Emergency Systems 1.! For emergency systems, the authority having jurisdiction shall conduct or witness a test on the! complete system upon installation and periodically

More information

AGENDA. NEC Code-Making Panel 5. Report on Comment Meeting. November 28-December 1, Redondo Beach, CA

AGENDA. NEC Code-Making Panel 5. Report on Comment Meeting. November 28-December 1, Redondo Beach, CA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 5 Report on Comment Meeting November 28-December

More information

2017 NEC TABLE OF CONTENTS

2017 NEC TABLE OF CONTENTS Article 90 Introduction 90.1 Purpose (A) Practical Safeguarding (B) Adequacy (C) Relation to Other International Standards 90.2 Scope (A Covered (B) Not Covered (C) Special Permission 90.3 Code Arrangement

More information

DESIGN CHECKLIST INTRODUCTION

DESIGN CHECKLIST INTRODUCTION INTRODUCTION 1 The checklist is intended to serve as a convenient guide in design development as well as the final checking of plans and specifications for construction projects. Its main usefulness for

More information

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM 2004 Specifications CSJ 3622-01-001, ETC. SPECIAL SPECIFICATION 8398 LIGHTNING PROTECTION SYSTEM 1. Description. This Special Specification governs the design and installation of Lightning Protection System

More information

NATIONAL ELECTRICAL CODE CODE-MAKING PANEL 5 NFPA 70 Second Draft Meeting Agenda October 25-27, 2018 San Diego, CA

NATIONAL ELECTRICAL CODE CODE-MAKING PANEL 5 NFPA 70 Second Draft Meeting Agenda October 25-27, 2018 San Diego, CA NATIONAL ELECTRICAL CODE CODE-MAKING PANEL 5 NFPA 70 Second Draft Meeting Agenda San Diego, CA 1. Call to Order Nathan Phillips, Chair 2. Introductions 3. Approval of Previous Meeting Minutes (Attachment

More information

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS Residential Pool Permit Requirements FEES: A nonrefundable permit application fee of $25.25 and a nonrefundable plan review fee of $40.40 will be

More information

A. Product Data: For each electrical identification product indicated.

A. Product Data: For each electrical identification product indicated. SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Suggested Statement/Substantiation for The PoE Task Group PIs

Suggested Statement/Substantiation for The PoE Task Group PIs All Text was agreed without objection by polling on the 6/2/17 call, blue text may be used in PI s but probably not if a single PI is filed. Yellow highlighted names (only shown on 840.160 PI) are individuals

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY Section 16195 A. This Section includes electrical identification for the following: 1. Nameplates and labels 2. Wire and cable markers 3. Conduit markers 4. Cable tray markers

More information

I dedicate this book to the Lord Jesus Christ, my mentor and teacher. Proverbs 16:3 NOTICE TO THE READER ABOUT THE AUTHOR

I dedicate this book to the Lord Jesus Christ, my mentor and teacher. Proverbs 16:3 NOTICE TO THE READER ABOUT THE AUTHOR April 28, 2018 NOTICE TO THE READER The publisher does not warrant or guarantee any of the products described herein or perform any independent analysis in connection with any of the product information

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also, delete any other item or

More information

ECET Fall 2017 Name: _ Lab Assignment #01

ECET Fall 2017 Name: _ Lab Assignment #01 ECET 4520 - Fall 2017 Name: _ Lab Assignment #01 General Instructions: This assignment is to be completed individually. All answers/work required for each problem should be neatly written in the space

More information

Department of Labor and Industry Electrical Licensing

Department of Labor and Industry Electrical Licensing Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants

More information

SECTION CABLE TRAYS

SECTION CABLE TRAYS SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Initiating Devices

More information

First Revision No. 112-NFPA [ Global Input ] Submitter Information Verification. Committee Statement and Meeting Notes 1/14/2015 1:57 PM

First Revision No. 112-NFPA [ Global Input ] Submitter Information Verification. Committee Statement and Meeting Notes 1/14/2015 1:57 PM of 26 1/14/2015 1:57 PM First Revision No. 112-NFPA 780-2014 [ Global Input ] Change L 0 (L sub zero) to L o (L sub O) throughout Annex L including tables, figures and formulas. Submitter Information Verification

More information

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION SECTION 16715 COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION PART 1 - GENERAL 1.01 SECTION DESCRIPTION AND BASIC REQUIREMENTS A. The Electrical Power Distribution System provides power distribution from

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER GROUNDED ELECTRICAL POWER DISTRIBUTION Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER .0 Conductors for Electrical Power Distribution For single-phase transmission of AC power or

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

Applying the NEC to Amateur Radio. By Tim Kuhlman, PE

Applying the NEC to Amateur Radio. By Tim Kuhlman, PE Applying the NEC to Amateur Radio By Tim Kuhlman, PE KD7RUS Purpose of this Course Detail Review of the National Electrical Code as it Applies to Amateur Radio Overview of the NEC Structure Define Article

More information

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56 1. Two Electrical Technicians are discussing markings that are required for AC wiring. Tech A says that AC conductors must be rated for 600 volts and must have their jackets and individual conductors marked

More information

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL PROVINCE.OF BRITISH COLUMBIA ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL Order in Council No. 0640 Approved and Oidered a -1.1995 cieuisvunigott3mor Executive Council Chambers, Victoria On the recommendation

More information

First Revision No. 141-NFPA [ Global Input ]

First Revision No. 141-NFPA [ Global Input ] of 161 2/8/2018, 2:49 PM First Revision No. 141-NFPA 780-2017 [ Global Input ] In Annex L text, tables and formulas replace all symbols with lower case italics r and upper case subscripts with lower case

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable

More information

Paul Dobrowsky Innovative Technology Services

Paul Dobrowsky Innovative Technology Services Significant Changes to NFPA 70E -2009 Edition Paul Dobrowsky Innovative Technology Services 2008 IEEE PCIC 1 Repeat Presentation This has been previously presented 2008 IEEE Electrical Safety Workshop

More information

EPG. by Chris C. Kleronomos

EPG. by Chris C. Kleronomos April 1994 EFFECTIVE EQUIPMENT GROUNDING ECOS Electronics Corporation by Chris C. Kleronomos The quality of the electrical wiring and grounding in a facility containing sensitive electronic equipment is

More information

Grounding and Bonding

Grounding and Bonding Grounding and Bonding 2017 Communications Academy Joe Blaschka Jr., PE Grounding/Bonding What is it? Why do we do it? What does the National Electrical Code say? What about fixed locations? What about

More information

6. Internal lightning protection

6. Internal lightning protection 6. Internal lightning protection 6.1 Equipotential bonding for metal installations Equipotential bonding according to IEC 60364-4- 41 and IEC 60364-5-54 Equipotential bonding is required for all newly

More information

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web: Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation

More information

Page Electric Utility Service Specifications

Page Electric Utility Service Specifications T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum - UG-1 Sheet 1 of 3 87 T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum

More information

SECTION BUILDING WIRE AND CABLE

SECTION BUILDING WIRE AND CABLE SECTION 260519 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wire and cable. 2. Wiring connectors and connections. B. RELATED SECTIONS 1. Section 26 05 53 Electrical Identification. 2. Section

More information

Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada

Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada and Philip Giddings Engineering Harmonics Toronto, Canada The original document and figures

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Venting Systems for Cooking

More information

Electrical IP Red Seal Practice Exam

Electrical IP Red Seal Practice Exam Electrical IP Red Seal Practice Exam PRACTICE EXAM-3 1. What size 2 pole breaker must you use on a 3HP, 115V single phase motor? A. 40A B. 50A C. 80A. D. 100A. 2. An electrical equipment approved for use

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Means of Egress

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings SOLAR MICROINVERTER/M STANDARD PLAN - COMPREHENSIVE Microinverter and M Systems for One- and Two- Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters or Modules

More information

Wiring Methods, Components, and Equipment for General Use -- OSHA Standard

Wiring Methods, Components, and Equipment for General Use -- OSHA Standard ABE285 Wiring Methods, Components, and Equipment for General Use -- OSHA Standard 1910.305 1 Carol J. Lehtola, Charles M. Brown, and William J. Becker 2 The Impact of Safety on Florida Agriculture Florida

More information

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP) Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.

More information

Code Check Electrical is a field guide to common code issues in residential

Code Check Electrical is a field guide to common code issues in residential INTRODUCTION u CODES u ABBREVIATIONS Code 3Check Electrical 5th Edition By Redwood Kardon & DOUGLAS HANSEN Illustrations & Layout: Paddy Morrissey 2008 by The Taunton Press, Inc. ISBN 978-1-60085-012-7

More information

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents.

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. SECTION 26 05 19 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. 1.2 CONTRACTOR SUBMITTALS A. The

More information

ELPT 1429 RESIDENTIAL WIRING

ELPT 1429 RESIDENTIAL WIRING SYLLABUS ELPT 1429 RESIDENTIAL WIRING INDUSTRIAL AND COMMERCIAL ELECTRICITY BRAZOSPORT COLLEGE LAKE JACKSON TEXAS PREPARED BY: Larry Grable DATE: September 13, 2005 INSTRUCTOR RECOMMENDED BY: RECOMMENDED

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

Spec Section: , Complete Elec, Comm, and Fire Alarm , Complete Elec, Comm, and Fire Alarm Data Sheets RAN/GCAN

Spec Section: , Complete Elec, Comm, and Fire Alarm , Complete Elec, Comm, and Fire Alarm Data Sheets RAN/GCAN SUBMITTAL REVIEW Submittal: No. 019.00 Spec Section: 26 0000, 28 0000 Complete Elec, Comm, and Fire Alarm Reviewed By: Laura Landon, Comma-Q Architecture Date: June 29, 2012 Project: BPS Belgrade Elementary

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 13 DISTRIBUTION SWITCHBOARDS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Electrical/Telecommunications Design

ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Electrical/Telecommunications Design PART 1: GENERAL 1.01 Electrical/Telecommunications Design A. This section of the design and construction standard outlines general requirements for electrical and telecommunications designs to be performed

More information

3Ø Short-Circuit Calculations

3Ø Short-Circuit Calculations 3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective

More information

RESIDENTIAL SOLAR ROOF TOP EXPEDITED PERMITTING GUIDELINE. 10 KW OR LESS

RESIDENTIAL SOLAR ROOF TOP EXPEDITED PERMITTING GUIDELINE. 10 KW OR LESS RESIDENTIAL SOLAR ROOF TOP EXPEDITED PERMITTING GUIDELINE. 10 KW OR LESS INFORMATION GUIDELINE 24A May 2015 CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA 92025 (760) 839-4647 Plan

More information

M E M O R A N D U M. NFPA 1989 Second Draft Technical Committee FINAL Ballot Results (A2018 Cycle)

M E M O R A N D U M. NFPA 1989 Second Draft Technical Committee FINAL Ballot Results (A2018 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Respiratory Protection

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

2. Electrical rooms shall be centrally located and stacked so that feeder conduits and bus duct are run as straight and short as possible.

2. Electrical rooms shall be centrally located and stacked so that feeder conduits and bus duct are run as straight and short as possible. PART 1: GENERAL 1.01 Electrical/Telecommunications Design A. This section of the design and construction standard outlines general requirements for electrical and telecommunications designs to be performed

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit. ECET4520 Exam II Sample Exam Problems Instructions: This exam is closed book, except for the reference booklet provided by your instructor and one (8.5 x11 ) sheet of handwritten notes that may not contain

More information

Boat Dock Exposure Voltage Mitigation

Boat Dock Exposure Voltage Mitigation Jodie Lane National Conference Boat Dock Exposure Voltage Mitigation Frank C. Lambert December 9, 2013 Problem Statement Swimming or working in the water around docks with customer owned electrical circuits

More information

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes FINAL - ER 70 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.

More information

Customer Requirements RF Antenna Installations

Customer Requirements RF Antenna Installations Application Terms Attachment requirements and clearances on the Pole for Radio Frequency (RF) antenna equipment installations. This standard is intended to allow electrical workers to perform their normal

More information

Standards Update Notice (SUN) Issued: June 6, 2017

Standards Update Notice (SUN) Issued: June 6, 2017 Standard Information Standard Number: UL 758 Standard Name: Standard for Safety for Appliance Wiring Material Standard Edition and Issue Date: 3 rd Edition Dated May 2, 2014 Date of Revisions: 2 nd Ed.

More information

SECTION TRANSFORMERS

SECTION TRANSFORMERS SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section

More information

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 12/12/ :15 AM

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 12/12/ :15 AM Second Revision No. 1-NFPA 1221-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

SECTION EMERGENCY RESPONDER RADIO COVERAGE SYSTEMS

SECTION EMERGENCY RESPONDER RADIO COVERAGE SYSTEMS 510.1 Emergency responder radio coverage in new buildings. Approved radio coverage for emergency responders shall be provided within all buildings meeting any one of the following conditions: 1. There

More information

MEMORANDUM. Technical Committee on Wildland and Rural Fire Protection. NFPA 1144 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Wildland and Rural Fire Protection. NFPA 1144 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Wildland and Rural Fire Protection

More information